    Building components found in a private school at NY

    Heating SystemType: Water 1 pipe? or2 pipe?Storage Tanks: 2Fuel: Oil #2Other: Asbestos insulated tank and pipes

    BoilersQuantity: 2Type: Federal Boiler FMA 850 (serial # T1160 & T1161)Input Capacity: 1890 MBH SBI Steam/WaterOutput Capacity: 75 HP SBI Gross 2520 MBHMax Pressure: 40 lbs Water

    BurnersQuantity: 2

    Type: Carlin 801CRDFiring Range: 11.4 19.8 GPHElectric Rating: 120 V, 60 Hz, 3.0 A

    DHWQuantity: 2Type: A.O. Smith PGC 75 M00N010000 (serial # MM00-0066282-230)Capacity: 74.5 galManufacture Rating: 76.8 gal/hr

    PumpsQuantity: 2 for drinking waterType: Marathon 2C184TDR344CD

    Capacity: 1.5 HP (208-220/440 V, 5.1 A)Other: 1730 rpm, 40oC rise, 1.2 s.f. (4.8/2.4 A) or1420 rpm, 50oC rise, 1.0 s.f. (6/3 A)

    Quantity: 2 Bell & Gossett Universal Pumps for boilers (model U-4T, ID# 104306)1. Type: Westinghouse Life Line T, model 05-3H4SBDP-MKBMotor Style: 680B640G41Specs: 3 HP, 1735 rpm, 9.9/4.95 A, 3 phase, 60 cycle

    2. Type: Marble IC-11764Motor Style: 109-9Specs: 3 HP, 1750 rpm, 40oC rise, 9.1 A, 3 phase, 60 cycle

    Boiler Room Lights8 incandescent, 100 Watt bulbs inside room1 incandescent, 60 Watt bulb outside door

    Boiler Test InformationDescription: Far Boiler, near windows was tested midday on 10.31.2008Boiler Temp: 229oC (444oF) Ambient Temp: 23.8oC (74.8oF)Efficiency: 75.9%CO2: 5.4% O2: 13.6%CO: 21 ppm AFUE CO: 60Excess Air: 172.7% Pressure: -0.07 WC

  • 8/2/2019 School Building Components

    2/2

    ThermostatsOnly 2 thermostats in building 1 on Bath St side of building and 1 on 19 th St side of buildingNo other switches to control boilers and/or heating system

    Air ConditionersQuantity: 7

    Location: throughout 2nd

    floor, 1 per classroomType: 24,000 Btu/h, 8.5 EER

    Quantity: 12Location: throughout 1st floorType: General Electric AC261146 13,800 Btu/h, 10.8 EER

    Quantity: 1Location: 1st floor officeType: AF5120EX 12,200 Btu/h, 10.8 EER

    Quantity: 10Location: throughout 1st and 2nd floorsType: Unknown,

    Fans on RoofQuantity: 4Type: SwartOut Fiber Air 228FCB (208 V, 2.14 A)

    Quantity: 2Type: SwartOut Fiber Air 26FC (115 V, 1.64 A)

    Lunch Room DetailsLocation: beneath 1st floor, near boiler roomLights: 120 fluorescent lights, 3 Exit lights in lunch room and kitchen

    4 CFL, 2 Exit lights outside room, in hallway near bathroomsMicrowaves: 1 Panasonic 1300 Watt and 1 Samsung 1500 WattRefrigerators: 1 General Electric GTS18HBSARWW, 18 ft3 (100 V, 60 Hz, 6.5 A)

    1 True GDM-45HL, 33ft3, 0.5 HP (115 V, 8.9 A)

    Warmer: 1 Lockwood CA73-PF16-CD-R, 1500 Watt (110 V, 60 Hz, 12.5 A)Dishwashers: NOT IN USE 2 Hobart UM-40 (115 V, 34 A)Stoves: NOT IN USE Garland 2 oven, 6 burner, large hood

    Office AppliancesLocation: 2nd floor, classroom #22Notes: 2 TVs, 1 small radio, 1 microwave, 1 half-refrigerator,

    2 computers (5 cubicles possibly 3 more computers for office)

    Location: 1st floor, corner of Bath & 19th StNotes: 3 Dell computers, 2 large copiers, 3 fax/printers

    Location: 1st floor, 19th StNotes: 4 Dell Optiplex 745 computers, 1 large copiers, 1 paper shredder

    *One computer was tested CPU: 77 Watts, Monitor: 39 Watts (7 Watts standby)

    Other2 water coolers in 1st floor hallwayat least 2 TVs and 2 radios in other classrooms throughout school