school of engineering and design brunel institute of power...
TRANSCRIPT
![Page 1: School of Engineering and Design Brunel Institute of Power ...reschool.chania.teicrete.gr/Lecture_notes/1_2_Taylor2 Integration of... · School of Engineering and Design Brunel Institute](https://reader033.vdocument.in/reader033/viewer/2022050718/5e16d6185a91c21cbe0a6791/html5/thumbnails/1.jpg)
School of Engineering and Design
www.brunel.ac.uk/about/acad/sed
Brunel Institute of Power Systems
RESchool 2009
Integration of RES into Distribution Networks
Overcoming Voltage Control Issues
![Page 2: School of Engineering and Design Brunel Institute of Power ...reschool.chania.teicrete.gr/Lecture_notes/1_2_Taylor2 Integration of... · School of Engineering and Design Brunel Institute](https://reader033.vdocument.in/reader033/viewer/2022050718/5e16d6185a91c21cbe0a6791/html5/thumbnails/2.jpg)
2
School of Engineering and Design
www.brunel.ac.uk/about/acad/sed
Brunel Institute of Power Systems
Agenda
�Distribution networks design and operation
�Distributed generation (RES) in distribution networks
�Voltage control issues
�Coordinated Voltage Control schemes for Active Network Management
�EDF Energy Networks’ case study systems
�Q & A
![Page 3: School of Engineering and Design Brunel Institute of Power ...reschool.chania.teicrete.gr/Lecture_notes/1_2_Taylor2 Integration of... · School of Engineering and Design Brunel Institute](https://reader033.vdocument.in/reader033/viewer/2022050718/5e16d6185a91c21cbe0a6791/html5/thumbnails/3.jpg)
3
School of Engineering and Design
www.brunel.ac.uk/about/acad/sed
Brunel Institute of Power Systems
Distribution Networks Design and Operation
� Determined by load demand� Fit and Forget principle
� Based on worst case scenario� Predictable load profile
� Static control
![Page 4: School of Engineering and Design Brunel Institute of Power ...reschool.chania.teicrete.gr/Lecture_notes/1_2_Taylor2 Integration of... · School of Engineering and Design Brunel Institute](https://reader033.vdocument.in/reader033/viewer/2022050718/5e16d6185a91c21cbe0a6791/html5/thumbnails/4.jpg)
4
School of Engineering and Design
www.brunel.ac.uk/about/acad/sed
Brunel Institute of Power Systems
Distribution Networks Design and Operation
http://www.edfenergy.com/powerup/index.html
![Page 5: School of Engineering and Design Brunel Institute of Power ...reschool.chania.teicrete.gr/Lecture_notes/1_2_Taylor2 Integration of... · School of Engineering and Design Brunel Institute](https://reader033.vdocument.in/reader033/viewer/2022050718/5e16d6185a91c21cbe0a6791/html5/thumbnails/5.jpg)
5
School of Engineering and Design
www.brunel.ac.uk/about/acad/sed
Brunel Institute of Power Systems
Distribution Network with Distributed generation
Connection of DG to distribution networks affects:
� Load flow �From uni-drectional to bi-directional
� Fault level � Increase in fault current�Protection settings
� Losses� Load power factor� Voltage control
�Voltage Rise�Automatic Voltage Control (AVC) Schemes
![Page 6: School of Engineering and Design Brunel Institute of Power ...reschool.chania.teicrete.gr/Lecture_notes/1_2_Taylor2 Integration of... · School of Engineering and Design Brunel Institute](https://reader033.vdocument.in/reader033/viewer/2022050718/5e16d6185a91c21cbe0a6791/html5/thumbnails/6.jpg)
6
School of Engineering and Design
www.brunel.ac.uk/about/acad/sed
Brunel Institute of Power Systems
Voltage control in Distribution Network with Distributed Generation
![Page 7: School of Engineering and Design Brunel Institute of Power ...reschool.chania.teicrete.gr/Lecture_notes/1_2_Taylor2 Integration of... · School of Engineering and Design Brunel Institute](https://reader033.vdocument.in/reader033/viewer/2022050718/5e16d6185a91c21cbe0a6791/html5/thumbnails/7.jpg)
7
School of Engineering and Design
www.brunel.ac.uk/about/acad/sed
Brunel Institute of Power Systems
Methods to overcome voltage control rise issue - Theory
( )LG PPR −⋅
( ) ( )V
jQPjXRIjXRV
−⋅+=+=∆
112 V
XQRPVV
++≈
( ) ( )1
12 V
QQXPPRVV LGLG −±⋅+−⋅+≈
� Decreasing R and/or X
� Reducing source voltage V1
� Changing one or both of the terms: ( )LG QQX −±⋅
![Page 8: School of Engineering and Design Brunel Institute of Power ...reschool.chania.teicrete.gr/Lecture_notes/1_2_Taylor2 Integration of... · School of Engineering and Design Brunel Institute](https://reader033.vdocument.in/reader033/viewer/2022050718/5e16d6185a91c21cbe0a6791/html5/thumbnails/8.jpg)
8
School of Engineering and Design
www.brunel.ac.uk/about/acad/sed
Brunel Institute of Power Systems
Voltage control rise issuefrom Theory to Practice
![Page 9: School of Engineering and Design Brunel Institute of Power ...reschool.chania.teicrete.gr/Lecture_notes/1_2_Taylor2 Integration of... · School of Engineering and Design Brunel Institute](https://reader033.vdocument.in/reader033/viewer/2022050718/5e16d6185a91c21cbe0a6791/html5/thumbnails/9.jpg)
9
School of Engineering and Design
www.brunel.ac.uk/about/acad/sed
Brunel Institute of Power Systems
� Decreasing R and/or X
�
� Changing
�
� Changing
�
� Reducing source voltage V1
�
�
Voltage control rise issuefrom Theory to Practice
( ) ( )1
12 V
QQXPPRVV LGLG −±⋅+−⋅+≈
( )LG PPR −⋅
( )LG QQX −±⋅
Coordinated Active Voltage Control
![Page 10: School of Engineering and Design Brunel Institute of Power ...reschool.chania.teicrete.gr/Lecture_notes/1_2_Taylor2 Integration of... · School of Engineering and Design Brunel Institute](https://reader033.vdocument.in/reader033/viewer/2022050718/5e16d6185a91c21cbe0a6791/html5/thumbnails/10.jpg)
10
School of Engineering and Design
www.brunel.ac.uk/about/acad/sed
Brunel Institute of Power Systems
Coordinated Voltage Control schemes for Active Network Management
� Centralized distribution management system
(DMS) control
� Local Voltage Controller
� Advanced Automatic Voltage Control relay
![Page 11: School of Engineering and Design Brunel Institute of Power ...reschool.chania.teicrete.gr/Lecture_notes/1_2_Taylor2 Integration of... · School of Engineering and Design Brunel Institute](https://reader033.vdocument.in/reader033/viewer/2022050718/5e16d6185a91c21cbe0a6791/html5/thumbnails/11.jpg)
11
School of Engineering and Design
www.brunel.ac.uk/about/acad/sed
Brunel Institute of Power Systems
Centralized distribution management system (DMS) control
![Page 12: School of Engineering and Design Brunel Institute of Power ...reschool.chania.teicrete.gr/Lecture_notes/1_2_Taylor2 Integration of... · School of Engineering and Design Brunel Institute](https://reader033.vdocument.in/reader033/viewer/2022050718/5e16d6185a91c21cbe0a6791/html5/thumbnails/12.jpg)
12
School of Engineering and Design
www.brunel.ac.uk/about/acad/sed
Brunel Institute of Power Systems
Local Voltage Controller
Key features:
� numbers of RTUs and communication infrastructure
� Distribution State Estimator
Advantages:
� efficient network utilization
� support significant amount of DG
� specific limits for individual nodes
Disadvantages:
� uncertainty in state estimation due to lack of RTUs
� static network model
� significant investment costs
![Page 13: School of Engineering and Design Brunel Institute of Power ...reschool.chania.teicrete.gr/Lecture_notes/1_2_Taylor2 Integration of... · School of Engineering and Design Brunel Institute](https://reader033.vdocument.in/reader033/viewer/2022050718/5e16d6185a91c21cbe0a6791/html5/thumbnails/13.jpg)
13
School of Engineering and Design
www.brunel.ac.uk/about/acad/sed
Brunel Institute of Power Systems
Advanced AVC relay
Key features:� local measurements
� no need for RTUs – can be employ
Advantages:� increased network ability to accommodate DG
� simplicity of the scheme
� cost effective and easy to installDisadvantages:
� inaccuracies of the estimation technique
� security margin is required � identical voltage limits for whole network
![Page 14: School of Engineering and Design Brunel Institute of Power ...reschool.chania.teicrete.gr/Lecture_notes/1_2_Taylor2 Integration of... · School of Engineering and Design Brunel Institute](https://reader033.vdocument.in/reader033/viewer/2022050718/5e16d6185a91c21cbe0a6791/html5/thumbnails/14.jpg)
14
School of Engineering and Design
www.brunel.ac.uk/about/acad/sed
Brunel Institute of Power Systems
Case Study Networks
Medium sized town network:� 3 Transformers 30 MVA each� 13 feeders� 5 MW of DG
Rural network:� 2 Transformers 15 MVA each� 3 feeders� 3 MW of DG
![Page 15: School of Engineering and Design Brunel Institute of Power ...reschool.chania.teicrete.gr/Lecture_notes/1_2_Taylor2 Integration of... · School of Engineering and Design Brunel Institute](https://reader033.vdocument.in/reader033/viewer/2022050718/5e16d6185a91c21cbe0a6791/html5/thumbnails/15.jpg)
15
School of Engineering and Design
www.brunel.ac.uk/about/acad/sed
Brunel Institute of Power Systems
Simulation software
� OCEPS based SuperTAPP n+ simulation software
� Developed at Brunel Institute of Power Systems and EDF Energy Networks
� GenAVC Assessment Tool � Developed by Econnect and EDF Energy
Networks
![Page 16: School of Engineering and Design Brunel Institute of Power ...reschool.chania.teicrete.gr/Lecture_notes/1_2_Taylor2 Integration of... · School of Engineering and Design Brunel Institute](https://reader033.vdocument.in/reader033/viewer/2022050718/5e16d6185a91c21cbe0a6791/html5/thumbnails/16.jpg)
16
School of Engineering and Design
www.brunel.ac.uk/about/acad/sed
Brunel Institute of Power Systems
Results – Advanced AVC relay SuperTAPP n+
Performance of the SuperTAPP n+ scheme
Voltage target adjustment in SuperTAPP n+ scheme
![Page 17: School of Engineering and Design Brunel Institute of Power ...reschool.chania.teicrete.gr/Lecture_notes/1_2_Taylor2 Integration of... · School of Engineering and Design Brunel Institute](https://reader033.vdocument.in/reader033/viewer/2022050718/5e16d6185a91c21cbe0a6791/html5/thumbnails/17.jpg)
17
School of Engineering and Design
www.brunel.ac.uk/about/acad/sed
Brunel Institute of Power Systems
Results – Local Voltage Controller GenAVCTM
Voltage Headroom and available generation capacity with GenAVC
Voltage Headroom and available generation capacity for GenAVC with additional RTU
![Page 18: School of Engineering and Design Brunel Institute of Power ...reschool.chania.teicrete.gr/Lecture_notes/1_2_Taylor2 Integration of... · School of Engineering and Design Brunel Institute](https://reader033.vdocument.in/reader033/viewer/2022050718/5e16d6185a91c21cbe0a6791/html5/thumbnails/18.jpg)
18
School of Engineering and Design
www.brunel.ac.uk/about/acad/sed
Brunel Institute of Power Systems
SuperTAPP n+ Trial
GPRS
SuperTAPP n+
GPRS
iHost
PM710 NX30
CANBUS
NX11
![Page 19: School of Engineering and Design Brunel Institute of Power ...reschool.chania.teicrete.gr/Lecture_notes/1_2_Taylor2 Integration of... · School of Engineering and Design Brunel Institute](https://reader033.vdocument.in/reader033/viewer/2022050718/5e16d6185a91c21cbe0a6791/html5/thumbnails/19.jpg)
19
School of Engineering and Design
www.brunel.ac.uk/about/acad/sed
Brunel Institute of Power Systems
Summary
� Principles of Distribution Networks design and operation
� Effect of DG in Distribution Networks
� Theoretical considerations of voltage control
� Practical solutions for voltage control in DNs with DG
� Active voltage control schemes for distribution network with distributed generation
� Technical limitations and commercial barriers
� Assessment software for two active network management techniques is presented
� Two case studies based on EDF Energy Networks
![Page 20: School of Engineering and Design Brunel Institute of Power ...reschool.chania.teicrete.gr/Lecture_notes/1_2_Taylor2 Integration of... · School of Engineering and Design Brunel Institute](https://reader033.vdocument.in/reader033/viewer/2022050718/5e16d6185a91c21cbe0a6791/html5/thumbnails/20.jpg)
20
School of Engineering and Design
www.brunel.ac.uk/about/acad/sed
Brunel Institute of Power Systems
Questions & Answers
THANK YOU