score 2003 power quality basics
TRANSCRIPT
-
8/14/2019 SCORE 2003 Power Quality Basics
1/30
SCORE 2003Short Course On Reliability &
Energy
Power Quality Basics
-
8/14/2019 SCORE 2003 Power Quality Basics
2/30
Copyright 2003 Progress Energy Short Course On Reliability & Energy 2
PQ Basics
Terms and Definitions Causes of Events
Possible Mitigation Questions
-
8/14/2019 SCORE 2003 Power Quality Basics
3/30
Copyright 2003 Progress Energy Short Course On Reliability & Energy 3
What is Power Quality
Any power problem manifested involtages, current, or frequencydeviations that results in failure or
misoperation of customer equipment.
-
8/14/2019 SCORE 2003 Power Quality Basics
4/30
Copyright 2003 Progress Energy Short Course On Reliability & Energy 4
-150
-100
-50
0
50
100
150
0
Power Quality Measurement
Duration (Time) Cycles (.016 seconds per cycle)
Seconds, Minutes, Hours
Magnitude (Voltage level) Transient level I.e. = 1000 volts
RMS - Voltage level i.e. = 120 volts
Waveforms Distortions
-
8/14/2019 SCORE 2003 Power Quality Basics
5/30
Copyright 2003 Progress Energy Short Course On Reliability & Energy 5
-200
-150
-100
-50
0
50
100
150
200
0
Magnitude and Duration
60 cycles/sec = 60 Hz
Duration
Time
Magnitude
VoltageLevel
169 volts
120 Volts RMS
One Cycle
.01666 seconds
-
8/14/2019 SCORE 2003 Power Quality Basics
6/30Copyright 2003 Progress Energy Short Course On Reliability & Energy 6
Terms and Definitions
Transient or Surge
Sag
Swell
Interruption
Outage
Harmonics
Magnitude and Duration
Magnitude and Duration
Magnitude and Duration
Magnitude and Duration
Duration
Steady State Condition
-
8/14/2019 SCORE 2003 Power Quality Basics
7/30Copyright 2003 Progress Energy Short Course On Reliability & Energy 7
Transient or Surge (Impulse)
Transient or Surge (Oscillatory)
Sag
Swell
Momentary Interruption
Interruption
Outage Harmonics
Unbalance
.00000005 -- .002 sec
.000005 -- .050 sec
.008 -- 1 min
.008 -- 1 min
.008 -- 3 sec
3 sec to 1 min
Greater than 1 min Steady State Condition
Steady State Condition
Duration
-
8/14/2019 SCORE 2003 Power Quality Basics
8/30
Copyright 2003 Progress Energy Short Course On Reliability & Energy 8
What is Power Quality & Reliability?
0
100
200
300
400
500
0.000001 0.00001 0.0001 0.001 0.01 0.1 1 10 100
Time in Seconds
Per
centofNom
inalVoltag
e
Voltage Tolerance EnvelopeApplicable to Single-Phase120- Volt Equipment SWELL Region
Outage
Long
TermE
vent
ShortTermE
vent
T
ransient
Surge
Interruptions (
-
8/14/2019 SCORE 2003 Power Quality Basics
9/30
Copyright 2003 Progress Energy Short Course On Reliability & Energy 9
A Transient can be classified into two categories,
impulsive and oscillatoryDuration < 50 ns to 50 ms .00000005 seconds to .002 seconds
.000005 seconds to .050 seconds
What is a Transient or Surge?
-
8/14/2019 SCORE 2003 Power Quality Basics
10/30
Copyright 2003 Progress Energy Short Course On Reliability & Energy 10
This is the category that TVSS (Transient
Voltage Surge Suppressor) SPD equipmentis designed to mitigate.
Impulsive
-
8/14/2019 SCORE 2003 Power Quality Basics
11/30
Copyright 2003 Progress Energy Short Course On Reliability & Energy 11
Sources of Transients
Lightning
Static
Arc Welding
Switching
Contactor
Relays SCRs
-
8/14/2019 SCORE 2003 Power Quality Basics
12/30
Copyright 2003 Progress Energy Short Course On Reliability & Energy 12
Oscillatory (Low Frequency)
-
8/14/2019 SCORE 2003 Power Quality Basics
13/30
Copyright 2003 Progress Energy Short Course On Reliability & Energy 13
Capacitor Bank Switch
Substation Bank Line Bank
-
8/14/2019 SCORE 2003 Power Quality Basics
14/30
Copyright 2003 Progress Energy Short Course On Reliability & Energy 14
Voltage Sags
-
8/14/2019 SCORE 2003 Power Quality Basics
15/30
Copyright 2003 Progress Energy Short Course On Reliability & Energy 15
Momentary Interruptions
Breaker Tripped
-
8/14/2019 SCORE 2003 Power Quality Basics
16/30
Copyright 2003 Progress Energy Short Course On Reliability & Energy 16
Outage
-
8/14/2019 SCORE 2003 Power Quality Basics
17/30
Copyright 2003 Progress Energy Short Course On Reliability & Energy 17
Causes of Sag, Interruptions Outages
-
8/14/2019 SCORE 2003 Power Quality Basics
18/30
Copyright 2003 Progress Energy Short Course On Reliability & Energy 18
115 kV Substation
23k
VFeeder
Transformer
480 V
Customer
Transformer
480 V
Transformer
480 V
Transformer
480 V
Customer Customer
Customer
Fuse Fuse
Fuse Fuse
Fuse
Fuse
Feeder
Breaker
Simplified Utility SystemTransmission @ 115 kV
Transformer
Distribution @ 23 kV
Regulator
23k
VFeeder
23kVFeeder
Transformer
480 V
Customer
Transformer
480 V
Transformer
480 V
Transformer
480 V
CustomerCustomer
Customer
FuseFuse
FuseFuse
Fuse
Fuse
Feeder
Breaker
23k
VFeeder
-
8/14/2019 SCORE 2003 Power Quality Basics
19/30
Copyright 2003 Progress Energy Short Course On Reliability & Energy 19
Example
-
8/14/2019 SCORE 2003 Power Quality Basics
20/30
Copyright 2003 Progress Energy Short Course On Reliability & Energy 20
115 kV Substation
23k
VFeeder
Transformer
480 V
Customer
Transformer
480 V
Transformer
480 V
Transformer
480 V
Customer Customer
Customer
Fuse Fuse
Fuse Fuse
Fuse
Fuse
Feeder
Breaker
Simplified Utility System
Transmission @ 115 kV
Transformer
Distribution @ 23 kV
Regulator
23k
VFeeder
23k
VFeeder
Transformer
480 V
Customer
Transformer
480 V
Transformer
480 V
Transformer
480 V
CustomerCustomer
Customer
FuseFuse
FuseFuse
Fuse
Fuse
Feeder
Breaker
23k
VFeeder
Outage
Momentary Interruption
Sag
-
8/14/2019 SCORE 2003 Power Quality Basics
21/30
Copyright 2003 Progress Energy Short Course On Reliability & Energy 21
Steady State Condition
Waveform Distortion
Harmonics Interharmonics
Voltage Balance Overvoltage
Undervoltage
-
8/14/2019 SCORE 2003 Power Quality Basics
22/30
Copyright 2003 Progress Energy Short Course On Reliability & Energy 22
Wave Distortion
-
8/14/2019 SCORE 2003 Power Quality Basics
23/30
Copyright 2003 Progress Energy Short Course On Reliability & Energy 23
Harmonics
-
8/14/2019 SCORE 2003 Power Quality Basics
24/30
Copyright 2003 Progress Energy Short Course On Reliability & Energy 24
Voltage or Current Unbalance
Maximum Deviation from Average Voltage
Average Voltage
243 Volts RMS
241 Volts RMS
233 Volts RMS
X 100 (for Percent)
239 Average Volts
6
2392.5% Voltage UnbalanceX 100 =
EXAMPLE
Measured Voltages
-
8/14/2019 SCORE 2003 Power Quality Basics
25/30
Copyright 2003 Progress Energy Short Course On Reliability & Energy 25
Customized Solutions
0
100
200
300
400
500
0.000001 0.00001 0.0001 0.001 0.01 0.1 1 10 100
Time in Seconds
PercentofNominalVoltage
Voltage Tolerance EnvelopeApplicable to Single-Phase120- Volt Equipment
SWELL Region
Outage
LongTermE
vent
ShortTermE
vent
Tr
ansient
Surge
Interruptions
SAG RegionUndervoltage
Overvoltage
-
8/14/2019 SCORE 2003 Power Quality Basics
26/30
Copyright 2003 Progress Energy Short Course On Reliability & Energy 26
Customized Solutions
0
100
200
300
400
500
0.000001 0.00001 0.0001 0.001 0.01 0.1 1 10 100
Time in Seconds
PercentofNominalVoltage
Voltage Tolerance EnvelopeApplicable to Single-Phase120- Volt Equipment
SWELL Region
Outage
LongTermE
vent
ShortTermE
vent
Tr
ansient
Surge
Interruptions
SAG Region
TVSS or SPD
Line Reactors
Isolation Transformers
Undervoltage
Overvoltage
-
8/14/2019 SCORE 2003 Power Quality Basics
27/30
Copyright 2003 Progress Energy Short Course On Reliability & Energy 27
Customized Solutions
0
100
200
300
400
500
0.000001 0.00001 0.0001 0.001 0.01 0.1 1 10 100
Time in Seconds
PercentofNominalVoltage
Voltage Tolerance EnvelopeApplicable to Single-Phase120- Volt Equipment
SWELL Region
Outage
LongTermE
vent
ShortTermE
vent
Tr
ansient
Surge
Interruptions
SAG Region
TVSS or SPD
Line Reactors
Isolation Transformers
Power Conditioner
orCVTUndervoltage
Overvoltage
-
8/14/2019 SCORE 2003 Power Quality Basics
28/30
Copyright 2003 Progress Energy Short Course On Reliability & Energy 28
Customized Solutions
0
100
200
300
400
500
0.000001 0.00001 0.0001 0.001 0.01 0.1 1 10 100
Time in Seconds
PercentofNominalVoltage
Voltage Tolerance EnvelopeApplicable to Single-Phase120- Volt Equipment
SWELL Region
Outage
LongTermE
vent
ShortTermE
vent
Tr
ansient
Surge
Interruptions
SAG Region
TVSS or SPD
Line Reactors
Isolation Transformers
Power Conditioner
orCVTUndervoltage
Overvoltage
UPS
UPS
&
Genset
-
8/14/2019 SCORE 2003 Power Quality Basics
29/30
Copyright 2003 Progress Energy Short Course On Reliability & Energy 29
IEEE 1159-1995Recommended Practice For Monitoring Electric Power Quality
Table 2 Categories and typical characteristics of power system
electromagnetic phenomena
Categories Typical Spectral Typical Durat ion Typical Voltage
Content Magnitude
1.0 Transient
1.1 Impulsive
1.1.1 Nanosecond 5 ns rise < 50 ns
1.1.2 Microsecond 1 us rise 50 ns - 1 m s
1.1.3 Millisecond 0.1 m s rise >1 m s
1.2 Oscillatory
1.2.1 Low frequency < 5 k Hz 0.3 - 50 m s 0 - 4 pu
1.2.2 Medium frequency 5 - 500 k Hz 20 us 0 - 8 pu1.2.3 High frequency 0.5 - 5 M Hz 5 us 0 - 4 pu
2.0 Short duration variations
2.1 Instantaneous
2.1.1 Sag 0.5 - 30 cycles 0.1 - 0.9 pu
2.1.2 Swell 0.5 - 30 cycles 1.1 - 1.8 pu
2.2 Momentary
2.2.1 Interruption 0.5 cycles - 3 s < 0.1 pu
2.2.2 Sag 30 cycles - 3 s 0.1 - 0.9 pu2.2.2 Swell 30 cycles - 3 s 1.1 - 1.4 pu
2.3 Temporary
2.3.1 Interruption 3 s - 1 min < 0.1 pu
2.3.2 Sag 3 s - 1 min 0.1 - 0.9 pu
2.3.3 Swell 3 s - 1 min 1.1 - 1.2 pu
3.0 Long duration variation
3.1 Interruption, sustained > 1 min 0.0 pu
3.2 Undervoltage > 1 min 0.8 - 0.9 pu
3.3 Overvoltage > 1 min 1.1 - 1.2 pu
4.0 Voltage imbalance steady state 0.5 - 2%
5.0 Waveform distortion
5.1 DC offset steady state 0 - 0.1%
5.2 Harmonics 0 - 100th H steady state 0 - 20%
5.3 Interharmonics 0 - 6 k Hz steady state 0 - 2%
5.4 Notching steady state
5.5 Noise broad-band steady state 0 - 1%
6.0 Voltage fluctuations < 25 Hz intermittent 0.1 - 7%
7.0 Power frequency variations < 10 s
-
8/14/2019 SCORE 2003 Power Quality Basics
30/30
Copyright 2003 Progress Energy Short Course On Reliability & Energy 30
PQ Events
Questions?