score 2003 power quality basics

Upload: cetincelik

Post on 30-May-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/14/2019 SCORE 2003 Power Quality Basics

    1/30

    SCORE 2003Short Course On Reliability &

    Energy

    Power Quality Basics

  • 8/14/2019 SCORE 2003 Power Quality Basics

    2/30

    Copyright 2003 Progress Energy Short Course On Reliability & Energy 2

    PQ Basics

    Terms and Definitions Causes of Events

    Possible Mitigation Questions

  • 8/14/2019 SCORE 2003 Power Quality Basics

    3/30

    Copyright 2003 Progress Energy Short Course On Reliability & Energy 3

    What is Power Quality

    Any power problem manifested involtages, current, or frequencydeviations that results in failure or

    misoperation of customer equipment.

  • 8/14/2019 SCORE 2003 Power Quality Basics

    4/30

    Copyright 2003 Progress Energy Short Course On Reliability & Energy 4

    -150

    -100

    -50

    0

    50

    100

    150

    0

    Power Quality Measurement

    Duration (Time) Cycles (.016 seconds per cycle)

    Seconds, Minutes, Hours

    Magnitude (Voltage level) Transient level I.e. = 1000 volts

    RMS - Voltage level i.e. = 120 volts

    Waveforms Distortions

  • 8/14/2019 SCORE 2003 Power Quality Basics

    5/30

    Copyright 2003 Progress Energy Short Course On Reliability & Energy 5

    -200

    -150

    -100

    -50

    0

    50

    100

    150

    200

    0

    Magnitude and Duration

    60 cycles/sec = 60 Hz

    Duration

    Time

    Magnitude

    VoltageLevel

    169 volts

    120 Volts RMS

    One Cycle

    .01666 seconds

  • 8/14/2019 SCORE 2003 Power Quality Basics

    6/30Copyright 2003 Progress Energy Short Course On Reliability & Energy 6

    Terms and Definitions

    Transient or Surge

    Sag

    Swell

    Interruption

    Outage

    Harmonics

    Magnitude and Duration

    Magnitude and Duration

    Magnitude and Duration

    Magnitude and Duration

    Duration

    Steady State Condition

  • 8/14/2019 SCORE 2003 Power Quality Basics

    7/30Copyright 2003 Progress Energy Short Course On Reliability & Energy 7

    Transient or Surge (Impulse)

    Transient or Surge (Oscillatory)

    Sag

    Swell

    Momentary Interruption

    Interruption

    Outage Harmonics

    Unbalance

    .00000005 -- .002 sec

    .000005 -- .050 sec

    .008 -- 1 min

    .008 -- 1 min

    .008 -- 3 sec

    3 sec to 1 min

    Greater than 1 min Steady State Condition

    Steady State Condition

    Duration

  • 8/14/2019 SCORE 2003 Power Quality Basics

    8/30

    Copyright 2003 Progress Energy Short Course On Reliability & Energy 8

    What is Power Quality & Reliability?

    0

    100

    200

    300

    400

    500

    0.000001 0.00001 0.0001 0.001 0.01 0.1 1 10 100

    Time in Seconds

    Per

    centofNom

    inalVoltag

    e

    Voltage Tolerance EnvelopeApplicable to Single-Phase120- Volt Equipment SWELL Region

    Outage

    Long

    TermE

    vent

    ShortTermE

    vent

    T

    ransient

    Surge

    Interruptions (

  • 8/14/2019 SCORE 2003 Power Quality Basics

    9/30

    Copyright 2003 Progress Energy Short Course On Reliability & Energy 9

    A Transient can be classified into two categories,

    impulsive and oscillatoryDuration < 50 ns to 50 ms .00000005 seconds to .002 seconds

    .000005 seconds to .050 seconds

    What is a Transient or Surge?

  • 8/14/2019 SCORE 2003 Power Quality Basics

    10/30

    Copyright 2003 Progress Energy Short Course On Reliability & Energy 10

    This is the category that TVSS (Transient

    Voltage Surge Suppressor) SPD equipmentis designed to mitigate.

    Impulsive

  • 8/14/2019 SCORE 2003 Power Quality Basics

    11/30

    Copyright 2003 Progress Energy Short Course On Reliability & Energy 11

    Sources of Transients

    Lightning

    Static

    Arc Welding

    Switching

    Contactor

    Relays SCRs

  • 8/14/2019 SCORE 2003 Power Quality Basics

    12/30

    Copyright 2003 Progress Energy Short Course On Reliability & Energy 12

    Oscillatory (Low Frequency)

  • 8/14/2019 SCORE 2003 Power Quality Basics

    13/30

    Copyright 2003 Progress Energy Short Course On Reliability & Energy 13

    Capacitor Bank Switch

    Substation Bank Line Bank

  • 8/14/2019 SCORE 2003 Power Quality Basics

    14/30

    Copyright 2003 Progress Energy Short Course On Reliability & Energy 14

    Voltage Sags

  • 8/14/2019 SCORE 2003 Power Quality Basics

    15/30

    Copyright 2003 Progress Energy Short Course On Reliability & Energy 15

    Momentary Interruptions

    Breaker Tripped

  • 8/14/2019 SCORE 2003 Power Quality Basics

    16/30

    Copyright 2003 Progress Energy Short Course On Reliability & Energy 16

    Outage

  • 8/14/2019 SCORE 2003 Power Quality Basics

    17/30

    Copyright 2003 Progress Energy Short Course On Reliability & Energy 17

    Causes of Sag, Interruptions Outages

  • 8/14/2019 SCORE 2003 Power Quality Basics

    18/30

    Copyright 2003 Progress Energy Short Course On Reliability & Energy 18

    115 kV Substation

    23k

    VFeeder

    Transformer

    480 V

    Customer

    Transformer

    480 V

    Transformer

    480 V

    Transformer

    480 V

    Customer Customer

    Customer

    Fuse Fuse

    Fuse Fuse

    Fuse

    Fuse

    Feeder

    Breaker

    Simplified Utility SystemTransmission @ 115 kV

    Transformer

    Distribution @ 23 kV

    Regulator

    23k

    VFeeder

    23kVFeeder

    Transformer

    480 V

    Customer

    Transformer

    480 V

    Transformer

    480 V

    Transformer

    480 V

    CustomerCustomer

    Customer

    FuseFuse

    FuseFuse

    Fuse

    Fuse

    Feeder

    Breaker

    23k

    VFeeder

  • 8/14/2019 SCORE 2003 Power Quality Basics

    19/30

    Copyright 2003 Progress Energy Short Course On Reliability & Energy 19

    Example

  • 8/14/2019 SCORE 2003 Power Quality Basics

    20/30

    Copyright 2003 Progress Energy Short Course On Reliability & Energy 20

    115 kV Substation

    23k

    VFeeder

    Transformer

    480 V

    Customer

    Transformer

    480 V

    Transformer

    480 V

    Transformer

    480 V

    Customer Customer

    Customer

    Fuse Fuse

    Fuse Fuse

    Fuse

    Fuse

    Feeder

    Breaker

    Simplified Utility System

    Transmission @ 115 kV

    Transformer

    Distribution @ 23 kV

    Regulator

    23k

    VFeeder

    23k

    VFeeder

    Transformer

    480 V

    Customer

    Transformer

    480 V

    Transformer

    480 V

    Transformer

    480 V

    CustomerCustomer

    Customer

    FuseFuse

    FuseFuse

    Fuse

    Fuse

    Feeder

    Breaker

    23k

    VFeeder

    Outage

    Momentary Interruption

    Sag

  • 8/14/2019 SCORE 2003 Power Quality Basics

    21/30

    Copyright 2003 Progress Energy Short Course On Reliability & Energy 21

    Steady State Condition

    Waveform Distortion

    Harmonics Interharmonics

    Voltage Balance Overvoltage

    Undervoltage

  • 8/14/2019 SCORE 2003 Power Quality Basics

    22/30

    Copyright 2003 Progress Energy Short Course On Reliability & Energy 22

    Wave Distortion

  • 8/14/2019 SCORE 2003 Power Quality Basics

    23/30

    Copyright 2003 Progress Energy Short Course On Reliability & Energy 23

    Harmonics

  • 8/14/2019 SCORE 2003 Power Quality Basics

    24/30

    Copyright 2003 Progress Energy Short Course On Reliability & Energy 24

    Voltage or Current Unbalance

    Maximum Deviation from Average Voltage

    Average Voltage

    243 Volts RMS

    241 Volts RMS

    233 Volts RMS

    X 100 (for Percent)

    239 Average Volts

    6

    2392.5% Voltage UnbalanceX 100 =

    EXAMPLE

    Measured Voltages

  • 8/14/2019 SCORE 2003 Power Quality Basics

    25/30

    Copyright 2003 Progress Energy Short Course On Reliability & Energy 25

    Customized Solutions

    0

    100

    200

    300

    400

    500

    0.000001 0.00001 0.0001 0.001 0.01 0.1 1 10 100

    Time in Seconds

    PercentofNominalVoltage

    Voltage Tolerance EnvelopeApplicable to Single-Phase120- Volt Equipment

    SWELL Region

    Outage

    LongTermE

    vent

    ShortTermE

    vent

    Tr

    ansient

    Surge

    Interruptions

    SAG RegionUndervoltage

    Overvoltage

  • 8/14/2019 SCORE 2003 Power Quality Basics

    26/30

    Copyright 2003 Progress Energy Short Course On Reliability & Energy 26

    Customized Solutions

    0

    100

    200

    300

    400

    500

    0.000001 0.00001 0.0001 0.001 0.01 0.1 1 10 100

    Time in Seconds

    PercentofNominalVoltage

    Voltage Tolerance EnvelopeApplicable to Single-Phase120- Volt Equipment

    SWELL Region

    Outage

    LongTermE

    vent

    ShortTermE

    vent

    Tr

    ansient

    Surge

    Interruptions

    SAG Region

    TVSS or SPD

    Line Reactors

    Isolation Transformers

    Undervoltage

    Overvoltage

  • 8/14/2019 SCORE 2003 Power Quality Basics

    27/30

    Copyright 2003 Progress Energy Short Course On Reliability & Energy 27

    Customized Solutions

    0

    100

    200

    300

    400

    500

    0.000001 0.00001 0.0001 0.001 0.01 0.1 1 10 100

    Time in Seconds

    PercentofNominalVoltage

    Voltage Tolerance EnvelopeApplicable to Single-Phase120- Volt Equipment

    SWELL Region

    Outage

    LongTermE

    vent

    ShortTermE

    vent

    Tr

    ansient

    Surge

    Interruptions

    SAG Region

    TVSS or SPD

    Line Reactors

    Isolation Transformers

    Power Conditioner

    orCVTUndervoltage

    Overvoltage

  • 8/14/2019 SCORE 2003 Power Quality Basics

    28/30

    Copyright 2003 Progress Energy Short Course On Reliability & Energy 28

    Customized Solutions

    0

    100

    200

    300

    400

    500

    0.000001 0.00001 0.0001 0.001 0.01 0.1 1 10 100

    Time in Seconds

    PercentofNominalVoltage

    Voltage Tolerance EnvelopeApplicable to Single-Phase120- Volt Equipment

    SWELL Region

    Outage

    LongTermE

    vent

    ShortTermE

    vent

    Tr

    ansient

    Surge

    Interruptions

    SAG Region

    TVSS or SPD

    Line Reactors

    Isolation Transformers

    Power Conditioner

    orCVTUndervoltage

    Overvoltage

    UPS

    UPS

    &

    Genset

  • 8/14/2019 SCORE 2003 Power Quality Basics

    29/30

    Copyright 2003 Progress Energy Short Course On Reliability & Energy 29

    IEEE 1159-1995Recommended Practice For Monitoring Electric Power Quality

    Table 2 Categories and typical characteristics of power system

    electromagnetic phenomena

    Categories Typical Spectral Typical Durat ion Typical Voltage

    Content Magnitude

    1.0 Transient

    1.1 Impulsive

    1.1.1 Nanosecond 5 ns rise < 50 ns

    1.1.2 Microsecond 1 us rise 50 ns - 1 m s

    1.1.3 Millisecond 0.1 m s rise >1 m s

    1.2 Oscillatory

    1.2.1 Low frequency < 5 k Hz 0.3 - 50 m s 0 - 4 pu

    1.2.2 Medium frequency 5 - 500 k Hz 20 us 0 - 8 pu1.2.3 High frequency 0.5 - 5 M Hz 5 us 0 - 4 pu

    2.0 Short duration variations

    2.1 Instantaneous

    2.1.1 Sag 0.5 - 30 cycles 0.1 - 0.9 pu

    2.1.2 Swell 0.5 - 30 cycles 1.1 - 1.8 pu

    2.2 Momentary

    2.2.1 Interruption 0.5 cycles - 3 s < 0.1 pu

    2.2.2 Sag 30 cycles - 3 s 0.1 - 0.9 pu2.2.2 Swell 30 cycles - 3 s 1.1 - 1.4 pu

    2.3 Temporary

    2.3.1 Interruption 3 s - 1 min < 0.1 pu

    2.3.2 Sag 3 s - 1 min 0.1 - 0.9 pu

    2.3.3 Swell 3 s - 1 min 1.1 - 1.2 pu

    3.0 Long duration variation

    3.1 Interruption, sustained > 1 min 0.0 pu

    3.2 Undervoltage > 1 min 0.8 - 0.9 pu

    3.3 Overvoltage > 1 min 1.1 - 1.2 pu

    4.0 Voltage imbalance steady state 0.5 - 2%

    5.0 Waveform distortion

    5.1 DC offset steady state 0 - 0.1%

    5.2 Harmonics 0 - 100th H steady state 0 - 20%

    5.3 Interharmonics 0 - 6 k Hz steady state 0 - 2%

    5.4 Notching steady state

    5.5 Noise broad-band steady state 0 - 1%

    6.0 Voltage fluctuations < 25 Hz intermittent 0.1 - 7%

    7.0 Power frequency variations < 10 s

  • 8/14/2019 SCORE 2003 Power Quality Basics

    30/30

    Copyright 2003 Progress Energy Short Course On Reliability & Energy 30

    PQ Events