12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 1/37
Second Revision No. 601NFPA 702015 [ Section No. 300.4 [Excluding
any SubSections] ]
Where subject to physical damage, conductors, raceways, and cables shall beprotected.
Informational Note: Minor damage to a raceway, cable armor, or cable insulationdoes not necessarily violate the integrity of either the contained conductors or theconductors’ insulation.
Submitter Information Verification
Submitter Full Name:CMP 3Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Mon Nov 02 11:49:07 EST 2015
Committee Statement
CommitteeStatement:
The informational note provides guidance to an electrical inspector that minor(superficial) damage to the jacket of a cable is not an issue. The first sentence ofthe proposed informational note is unnecessary since it states the obvious thatphysical damage doesn’t just occur from normal building operation.
ResponseMessage:
Public Comment No. 1028NFPA 702015 [Section No. 300.4 [Excluding any SubSections]]
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 2/37
Second Revision No. 623NFPA 702015 [ Section No. 300.5(A) ]
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 3/37
(A) Minimum Cover Requirements.
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 4/37
Directburied cable, or conduit, or other raceways shall be installed to meet theminimum cover requirements of Table 300.5.
Table 300.5 Minimum Cover Requirements, 0 to 1000 Volts, Nominal, Burial inMillimeters (Inches)
Type of Wiring Method or Circuit
Location ofWiring Method
or Circuit
Column 1DirectBurial
Cables orConductors
Column 2Rigid MetalConduit orIntermediate
MetalConduit
Column 3NonmetallicRacewaysListed forDirectBurialWithoutConcrete
Encasementor OtherApprovedRaceways
Column 4ResidentialBranchCircuitsRated 120Volts orLess withGFCI
Protectionand
MaximumOvercurrentProtection
of 20Amperes
Column 5Circuits
forControl ofIrrigation
andLandscapeLightingLimited toNot MoreThan 30Volts andInstalledwith TypeUF or inOther
IdentifiedCable orRaceway
mm in. mm in. mm in. mm in. mm in.
All locations notspecified below 600 24 150 6 450 18 300 12 150a,
b 6a, b
In trench below 50mm (2 in.) thickconcrete orequivalent
450 18 150 6 300 12 150 6 150 6
Under a building 0 0 0 0 0 0 0 0 0 0(in racewayor Type MCor Type MI
cableidentified fordirect burial)
(in racewayor Type MCor Type MI
cableidentified fordirect burial)
(in racewayor Type MCor Type MI
cableidentified fordirect burial)
Under minimum of102 mm (4 in.)thick concreteexterior slab withno vehicular trafficand the slabextending not lessthan 152 mm (6in.) beyond theundergroundinstallation
450 18 100 4 100 4
150 6 150 6
(direct burial)(directburial)
100 4 100 4
(in raceway) (in raceway)
Under streets,highways, roads,alleys, driveways,and parking lots
600 24 600 24 600 24 600 24 600 24
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 5/37
One and twofamily dwellingdriveways andoutdoor parkingareas, and usedonly for dwellingrelated purposes
450 18 450 18 450 18 300 12 450 18
In or under airportrunways,including adjacentareas wheretrespassingprohibited
450 18 450 18 450 18 450 18 450 18
aA lesser depth shall be permitted where specified in the installation instructions of alisted lowvoltage lighting system.
b A depth of 150 mm (6 in.) shall be permitted for pool, spa, and fountain lighting,installed in a nonmetallic raceway, limited to not more than 30 volts where part of alisted lowvoltage lighting system.
Notes:
1. Cover is defined as the shortest distance in millimeters mm (inches in. ) measuredbetween a point on the top surface of any directburied conductor, cable, conduit, orother raceway and the top surface of finished grade, concrete, or similar cover.
2. Raceways approved for burial only where concrete encased shall require concreteenvelope not less than 50 mm (2 in.) thick.
3. Lesser depths shall be permitted where cables and conductors rise for terminations orsplices or where access is otherwise required.
4. Where one of the wiring method types listed in Columns 1 through 3 is used for one ofthe circuit types in Columns 4 and 5, the shallowest depth of burial shall be permitted.
5. Where solid rock prevents compliance with the cover depths specified in this table,the wiring shall be installed in a metal raceway, or a nonmetallic raceway permitted fordirect burial. The raceways shall be covered by a minimum of 50 mm (2 in.) of concreteextending down to rock.
Supplemental Information
File Name Description300.5_SR623_LM.docx
Submitter Information Verification
Submitter Full Name:CMP 3Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Nov 03 10:35:31 PST 2015
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 6/37
Committee Statement
CommitteeStatement:
Swimming pool, spa, and fountain low voltage lighting in a nonmetallic raceway orsimilar installation should not be required to be installed any deeper than any otherColumn 5 less than 30 volt low voltage landscape lighting. Since the actual textcovering pools, spas and fountains is not located in Column 5, there are inspectorswho require the nonmetallic raceway containing these low voltage lightingconductors to be installed at an 18inch depth.
ResponseMessage:
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 7/37
Second Revision No. 602NFPA 702015 [ Section No. 300.7(B) ]
(B) Expansion, ExpansionDeflection, and Deflection Fittings.Raceways shall be provided with expansion, expansiondeflection, or deflection fittingswhere necessary to compensate for thermal expansion, deflection, and contraction.
Informational Note: Table 352.44 and Table 355.44 provide the expansioninformation for polyvinyl chloride (PVC) and for reinforced thermosetting resinconduit (RTRC), respectively. A nominal number for steel conduit can bedetermined by multiplying the expansion length in Table 352.44 by 0.20. Thecoefficient of expansion for steel electrical metallic tubing, intermediate metalconduit, and rigid metal conduit is 1.170 × 105 (0.0000117 mm per mm of conduitfor each °C in temperature change) [0.650 × 105 (0.0000065 in. per inch ofconduit for each °F in temperature change)].
A nominal number for aluminum conduit and aluminum electrical metallic tubingcan be determined by multiplying the expansion length in Table 352.44 by 0.40.The coefficient of expansion for aluminum electrical metallic tubing and aluminumrigid metal conduit is 2.34 × 105 (0.0000234 mm per mm of conduit for each °Cin temperature change) [1.30 × 105 (0.000013 in. per inch of conduit for each °Fin temperature change)].
Submitter Information Verification
Submitter Full Name:CMP 3Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Mon Nov 02 13:01:37 EST 2015
Committee Statement
CommitteeStatement:
The revised text makes it clear to inspectors, designers, and contactors thatexpansiondeflection and deflection fittings are acceptable to be used with racewaysto address thermal expansion, deflection, and contraction. Revising the text alsorequires a revision of the title to this subsection.
ResponseMessage:
Public Comment No. 99NFPA 702015 [Section No. 300.7(B)]
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 8/37
Second Revision No. 603NFPA 702015 [ Section No. 300.11(B)(1) ]
(1) FireRated Assemblies.Wiring located within the cavity of a firerated floor–ceiling or roof–ceiling assembly shallnot be secured to, or supported by, the ceiling assembly, including the ceiling supportwires. An independent means of secure support shall be provided and shall be permittedto be attached to the assembly. Where independent support wires are used, they shallbe distinguishable by color, tagging, or other effective means from those that are part ofthe firerated design.
Exception: The ceiling support system shall be permitted to support wiring andequipment that have been tested as part of the firerated assembly.
Informational Note: One method of determining fire rating is testing in accordancewith ANSI/ASTM E1192014 2015 , Method for Fire Tests of BuildingConstruction and Materials.
Submitter Information Verification
Submitter Full Name:CMP 3Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Mon Nov 02 13:48:28 EST 2015
Committee Statement
Committee Statement: The ANSI/ASTM E119 has been changed from 2014 to 2015.Response Message:
Public Comment No. 122NFPA 702015 [Section No. 300.11(B)(1)]
Public Comment No. 801NFPA 702015 [Section No. 300.11(B)(1)]
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 9/37
Second Revision No. 604NFPA 702015 [ Section No. 300.19(A) ]
(A) Spacing Intervals — Maximum.
Conductors in vertical raceways shall be supported if the vertical rise exceeds thevalues in Table 300.19(A). At least one support method shall be provided for eachconductor or cable assembly at the top of the vertical raceway or as close to the top aspractical. Intermediate supports shall be provided as necessary to limit supportedconductor lengths to not greater than those values specified in Table 300.19(A).
Exception: Steel wire armor cable shall be supported at the top of the riser with acable support that clamps the steel wire armor. A safety device shall be permitted atthe lower end of the riser to hold the cable in the event there is slippage of the cable inthe wirearmored cable support. Additional wedgetype supports shall be permitted torelieve the strain on the equipment terminals caused by expansion of the cable underload.
Table 300.19(A) Spacings for Conductor Supports
Conductors
Conductor Size Support of Conductors in VerticalRaceways
Aluminumor
CopperClad
Aluminum
Copper
m ft m ft18 AWG through 8 AWG Not greater than 30 100 30 1006 AWG through 1/0 AWG Not greater than 60 200 30 1002/0 AWG through 4/0AWG Not greater than 55 180 25 80
Over 4/0 AWG through350 kcmil Not greater than 41 135 18 60
Over 350 kcmil through500 kcmil Not greater than 36 120 15 50
Over 500 kcmil through750 kcmil Not greater than 28 95 12 40
Over 750 kcmil Not greater than 26 85 11 35
Submitter Information Verification
Submitter Full Name:CMP 3Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Mon Nov 02 13:51:21 EST 2015
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 10/37
Committee Statement
CommitteeStatement:
Deleting cable assembly ensures that each individual conductor is supportedat the top of a vertical raceway.
ResponseMessage:
Public Comment No. 1151NFPA 702015 [Section No. 300.19(A)]
Second Revision No. 605NFPA 702015 [ Section No. 300.22(C)(3) ]
(3) Equipment.Electrical equipment with a metal enclosure, or electrical equipment with a nonmetallicenclosure listed for use within an airhandling space and having low smoke and heatrelease properties, and associated wiring material suitable for the ambient temperatureshall be permitted to be installed in such other space unless prohibited elsewhere in thisCode.
Informational Note: One method to determine low smoke and heat releaseproperties is that the equipment exhibits a maximum peak optical density of 0.50or less, an average optical density of 0.15 or less, and a peak heat release rate of100kW or less when tested in accordance with ANSI/UL 20432008 2013 , FireTest for Heat and Visible Smoke Release for Discrete Products and TheirAccessories Installed in AirHandling Spaces.
Exception: Integral fan systems shall be permitted where specifically identified for usewithin an airhandling space.
Submitter Information Verification
Submitter Full Name:CMP 3Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Mon Nov 02 14:16:41 EST 2015
Committee Statement
CommitteeStatement:
This updates the informational note to the latest version of UL 2043. ANSI hasbeen retained in the title of the UL Standard.
ResponseMessage:
Public Comment No. 163NFPA 702015 [Section No. 300.22(C)(3)]
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 11/37
Second Revision No. 624NFPA 702015 [ Section No. 300.37 ]
300.37 Aboveground Wiring Methods.
Aboveground conductors shall be installed in rigid metal conduit, in intermediate metalconduit, in electrical metallic tubing, in RTRC and PVC conduit, in cable trays, inauxiliary gutters, as busways, as cablebus, in other identified raceways, or as exposedruns of metalclad cable suitable for the use and purpose. In locations accessible toqualified persons only, exposed runs of Type MV cables, bare conductors, and barebusbars shall also be permitted. Busbars shall be permitted to be either copper oraluminum.
Exception: Airfield lighting cable used in series circuits that are powered by regulatorsand installed in restricted airport lighting vaults shall be permitted as exposed cableinstallations.
Informational Note: FAA L824 cables installed as exposed runs within arestricted vault area are common applications.
Submitter Information Verification
Submitter Full Name:CMP 3Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Nov 03 11:12:31 PST 2015
Committee Statement
CommitteeStatement:
This revision recognizes that these cables are often installed exposed within arestricted airport lighting vault to facilitate easy access for modifications andreconnections during emergency situations.
ResponseMessage:
Public Comment No. 108NFPA 702015 [Section No. 300.37]
Public Comment No. 113NFPA 702015 [Section No. 300.37]
Public Comment No. 115NFPA 702015 [Section No. 300.37]
Public Comment No. 1472NFPA 702015 [Section No. 300.37]
Public Comment No. 1496NFPA 702015 [Section No. 300.37]
Public Comment No. 246NFPA 702015 [Section No. 300.37]
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 12/37
Second Revision No. 606NFPA 702015 [ Section No. 590.4(G) ]
(G) Splices.A box, conduit body, or other enclosure, with a cover installed, shall be required for allsplices except where:
(1) The circuit conductors being spliced are all from nonmetallic multiconductor cord orcable assemblies, provided that the equipment grounding continuity is maintainedwith or without the box.
(2) The circuit conductors being spliced are all from metal sheathed cable assembliesterminated in listed fittings that mechanically secure the cable sheath to maintaineffective electrical continuity.
Submitter Information Verification
Submitter Full Name:CMP 3Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Mon Nov 02 16:08:00 EST 2015
Committee Statement
CommitteeStatement:
The addition of “nonmetallic” ensures that (1) applies to splices of multiconductorcords or cable assemblies with a nonmetallic jacket.
ResponseMessage:
Public Comment No. 826NFPA 702015 [Section No. 590.4(G)]
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 13/37
Second Revision No. 607NFPA 702015 [ Section No. 590.4(J) ]
(J) Support.Cable assemblies and flexible cords and cables shall be supported in place at intervalsthat ensure that they will be protected from physical damage. Support shall be in theform of staples, cable ties, straps, or similar type fittings installed so as not to causedamage. Cable assemblies and flexible cords and cables installed as branch circuits orfeeders shall not be installed on the floor or on the ground. Extension cords shall not berequired to comply with 590.4(J). Multiconductor cord or cable of a type identified inTable 400.4 for hard usage or extrahard usage shall not be required to comply with590.4(J) . Vegetation shall not be used for support of overhead spans of branch circuitsor feeders.
Exception: For holiday lighting in accordance with 590.3(B), where the conductors orcables are arranged with strain relief devices, tension takeup devices, or otherapproved means to avoid damage from the movement of the live vegetation, treesshall be permitted to be used for support of overhead spans of branchcircuitconductors or cables.
Submitter Information Verification
Submitter Full Name:CMP 3Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Mon Nov 02 16:11:00 EST 2015
Committee Statement
CommitteeStatement:
Multiconductor cords or cables that are identified in Table 400.4 for hard usage orextra hard usage shall not be required to comply with 590.4(J) as far as support isconcerned. The extra text helps clarify what types of cords are acceptable for thistemporary application.
ResponseMessage:
Public Comment No. 1143NFPA 702015 [Section No. 590.4(J)]
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 14/37
Second Revision No. 608NFPA 702015 [ Section No. 590.6(B) ]
(B) Use of Other Outlets.For temporary wiring installations, receptacles, other than those covered by 590.6(A)(1)through (A)(3) used to supply temporary power to equipment used by personnel duringconstruction, remodeling, maintenance, repair, or demolition of buildings, structures, orequipment, or similar activities, shall have protection in accordance with (B)(1), (B)(2),or the assured equipment grounding conductor program in accordance with (B)(2) (3) .
(1) GFCI Protection.Groundfault circuitinterrupter protection for personnel.
(2) SPGFCI Protection.Special purpose groundfault circuitinterrupter protection for personnel.
(3) Assured Equipment Grounding Conductor Program.A written assured equipment grounding conductor program continuously enforced at thesite by one or more designated persons to ensure that equipment grounding conductorsfor all cord sets, receptacles that are not a part of the permanent wiring of the building orstructure, and equipment connected by cord and plug are installed and maintained inaccordance with the applicable requirements of 250.114, 250.138, 406.4(C), and590.4(D).
(a) The following tests shall be performed on all cord sets, receptacles that are notpart of the permanent wiring of the building or structure, and cordandplugconnectedequipment required to be connected to an equipment grounding conductor:
(1) All equipment grounding conductors shall be tested for continuity and shall beelectrically continuous.
(2) Each receptacle and attachment plug shall be tested for correct attachment of theequipment grounding conductor. The equipment grounding conductor shall beconnected to its proper terminal.
(3) All required tests shall be performed as follows:
a. Before first use on site
b. When there is evidence of damage
c. Before equipment is returned to service following any repairs
d. At intervals not exceeding 3 months
(b) The tests required in item (2) (3) (a) shall be recorded and made available to theauthority having jurisdiction.
Supplemental Information
File Name Description590.6_B_SR608_JS.docx Word document shows changes made in SR 608
Submitter Information Verification
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 15/37
Submitter Full Name:CMP 3Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Mon Nov 02 16:19:21 EST 2015
Committee Statement
CommitteeStatement:
The changes to 590.6(B) involving special purpose groundfault circuitinterrupterprotection (SPGFCI) for personnel are accepted since Panel 2 has accepted a newdefinition of SPGFCI, however, Equipment GroundFault Protective Devices(EGFPD) is listed by UL for equipment protection, not personnel protection. Sincethe requirements in 590.6 are for protection of personnel, the changes suggested forEGFPD are not accepted.
ResponseMessage:
Public Comment No. 615NFPA 702015 [Section No. 590.6(B)]
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 16/37
Second Revision No. 609NFPA 702015 [ Section No. 725.3(C) ]
(C) Ducts, Plenums, and Other AirHandling Spaces.Class 1, Class 2, and Class 3 circuits installed in ducts, plenums, or other space usedfor environmental air shall comply with 300.22.
Exception No. 1: As permitted in Class 2 and Class 3 cables selected in accordancewith Table 725.154 and installed in accordance with 725.135(B) and 300.22(B) ,Exception shall be permitted to be installed in ducts specifically fabricated forenvironmental air. .
Exception No. 2: Class 2 and Class 3 cables selected in accordance with Table725.154 and installed in accordance with 725.135(C) shall be permitted to beinstalled in other spaces used for environmental air (plenums).
Submitter Information Verification
Submitter Full Name:CMP 3Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Mon Nov 02 16:24:52 EST 2015
Committee Statement
CommitteeStatement:
The First Revision FR 614 modified 300.22(B) by adding a new Exception indicatingClass 2 and Class 3 cables are permitted in ducts specifically fabricated forenvironmental air with two conditions (a) The wiring methods or cabling systemsshall be permitted only if necessary to connect to equipment or devices associatedwith the direct action upon, or sensing of the contained air and (b) The total length ofsuch wiring methods or cabling systems shall not exceed 1.2 m (4 ft). These twoconditions correspond to Section 4.3.4.2 in NFPA 90A—2015. The 2017 FirstRevision FR 614 in 300.22(B) reads as follows:
Exception: Wiring methods and cabling systems, listed for use in other spaces usedfor environmental air (plenums), shall be permitted to be installed in ductsspecifically fabricated for environmental airhandling purposes under the followingconditions:
(a) The wiring methods or cabling systems shall be permitted only if necessary toconnect to equipment or devices associated with the direct action upon, or sensingof the contained air and
(b) The total length of such wiring methods or cabling systems shall not exceed 1.2m (4 ft).
Class 2 or Class 3 plenum rated cable is acceptable in ducts specifically fabricated
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 17/37
for environmental air but only where connecting to equipment used to sense or hasdirection action on the contained air and limited to a maximum of 4foot length basedon NFPA 90A.
ResponseMessage:
Public Comment No. 460NFPA 702015 [Section No. 725.3(C)]
Second Revision No. 610NFPA 702015 [ New Section after 725.121(B) ]
(C) The power sources for limited power circuits in 725.121(A)(3) and limited powercircuits for listed audio/video information technology (equipment) and listed industrialequipment in 725.121(A)(4) shall have a label indicating the maximum voltage andcurrent output for each connection point. The effective date shall be January 1, 2018.
Submitter Information Verification
Submitter Full Name:CMP 3Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Mon Nov 02 17:03:37 EST 2015
Committee Statement
CommitteeStatement:
This new section addresses labeling of limited power circuit output connectionpoints on listed IT equipment and listed industrial control panels and equipment.Bundling of large numbers of Class 2 conductors from IT servers and other similarIT and industrial equipment can create safety issues with very small current levelsso having the output ports identified with the current and voltage rating is critical sothe installer can connect the proper cable types. Labeling the output connections willpermit the installer to have ready access to the current and voltage levels at thepoint of connection at the equipment, rather than internally within the equipment. Theeffective date was inserted to allow the manufacturers to comply with thisrequirement.
ResponseMessage:
Public Comment No. 1351NFPA 702015 [New Section after 725.121]
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 18/37
Second Revision No. 612NFPA 702015 [ Section No. 725.133 ]
725.133 Installation of Conductors and Equipment in Cables, Compartments, CableTrays, Enclosures, Manholes, Outlet Boxes, Device Boxes, Raceways, and CableRouting Assemblies for Class 2 and Class 3 Circuits.
Conductors and equipment for Class 2 and Class 3 circuits shall be installed inaccordance with 725.135 through 725.143 725.144 .
Submitter Information Verification
Submitter Full Name:CMP 3Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Mon Nov 02 19:38:52 EST 2015
Committee Statement
Committee Statement: The addition of 725.144 requires modification of 725.133.Response Message:
Public Comment No. 689NFPA 702015 [Section No. 725.133]
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 19/37
Second Revision No. 613NFPA 702015 [ Section No. 725.135(A) ]
(A) Listing.Class 2, Class 3, and PLTC cables installed in buildings shall be listed and labeled .
Submitter Information Verification
Submitter Full Name:CMP 3Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Nov 03 08:10:11 PST 2015
Committee Statement
CommitteeStatement:
FR 638 already accepted this text. The panel reaffirms its stance on this topic: Byadding the word "labeled," it will identify that listed products also need to be labeled.Both terms "listed" and "labeled" are defined in Article 100, but are not usedconsistently throughout the NEC.
ResponseMessage:
Public Comment No. 1423NFPA 702015 [Section No. 725.135(A)]
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 20/37
Second Revision No. 620NFPA 702015 [ Section No. 725.135(K) ]
(K) Other Building Locations.The following wires and cables shall be permitted to be installed in building locationsother than the locations covered in 725.135(B) through (I):
(1) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, and PLTC cables
(2) A maximum of 3 m (10 ft) of exposed Type CL2X wires and cables innonconcealed spaces
(3) A maximum of 3 m (10 ft) of exposed Type CL3X wires and cables innonconcealed spaces
(4) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, and PLTC cables installed in thefollowing:
a. Plenum communications raceways
b. Plenum cable routing assemblies
c. Riser communications raceways
d. Riser cable routing assemblies
e. Generalpurpose communications raceways
f. Generalpurpose cable routing assemblies
(5) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, CL2X, CL3X, and PLTC cablesinstalled in raceways recognized in Chapter 3
(6) Type CMUC undercarpet communications wires and cables installed under carpet,floor covering, modular tiles, or planks. Carpet, floor covering, modular tiles, orplanks shall be freefloating and shall use interlocking means to attach to eachother or shall be adhered to the floor and shall be attached with releasetypeadhesives, but shall not be attached to the floor using grout, nails, orscrews modular flooring, and planks
Submitter Information Verification
Submitter Full Name:CMP 3Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Nov 03 09:59:16 PST 2015
Committee Statement
CommitteeStatement:
Type CMUC under carpet communication wire and cables are permitted to beinstalled under carpet with an installation expansion for modular flooring and planks.
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 21/37
The installation instructions for free floating and interlocking does not necessarilyapply to all kinds of modular flooring and planks and could be overly restrictive.
ResponseMessage:
Public Comment No. 223NFPA 702015 [Section No. 725.135(K)]
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 22/37
Second Revision No. 621NFPA 702015 [ Section No. 725.135(L) ]
(L) Multifamily Dwellings.The following wires and cables shall be permitted to be installed in multifamily dwellingsin locations other than the locations covered in 725.135(B) through (I):
(1) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, and PLTC wires and cables
(2) Type CL2X wires and cables less than 6 mm (1∕4 in.) in diameter in nonconcealedspaces
(3) Type CL3X wires and cables less than 6 mm (1∕4 in.) in diameter in nonconcealedspaces
(4) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, and PLTC wires and cables installedin the following:
a. Plenum communications raceways
b. Plenum cable routing assemblies
c. Riser communications raceways
d. Riser cable routing assemblies
e. Generalpurpose communications raceways
f. Generalpurpose cable routing assemblies
(5) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, CL2X, CL3X, and PLTC wires andcables installed in raceways recognized in Chapter 3
(6) Type CMUC undercarpet communications wires and cables installed under carpet,floor covering, modular tiles, or planks. Carpet, floor covering, modular tiles, orplanks shall be freefloating and shall use interlocking means to attach to eachother or shall be adhered to the floor and shall be attached with releasetypeadhesives, but shall not be attached to the floor using grout, nails, orscrews modular flooring, and planks
Submitter Information Verification
Submitter Full Name:CMP 3Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Nov 03 10:02:54 PST 2015
Committee Statement
CommitteeStatement:
Type CMUC under carpet communication wire and cables are permitted to beinstalled under carpet with an installation expansion for modular flooring and planks.
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 23/37
The installation instructions for free floating and interlocking does not necessarilyapply to all kinds of modular flooring and planks and could be overly restrictive.
ResponseMessage:
Public Comment No. 224NFPA 702015 [Section No. 725.135(L)]
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 24/37
Second Revision No. 622NFPA 702015 [ Section No. 725.135(M) ]
(M) One and TwoFamily Dwellings.The following wires and cables shall be permitted to be installed in one and twofamilydwellings in locations other than the locations covered in 725.135(B) through (I):
(1) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, and PLTC wires and cables
(2) Type CL2X wires and cables less than 6 mm (1∕4 in.) in diameter
(3) Type CL3X wires and cables less than 6 mm (1∕4 in.) in diameter
(4) Communications wires and Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, andPLTC cables installed in the following:
a. Plenum communications raceways
b. Plenum cable routing assemblies
c. Riser communications raceways
d. Riser cable routing assemblies
e. Generalpurpose communications raceways
f. Generalpurpose cable routing assemblies
(5) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, CL2X, CL3X, and PLTC wires andcables installed in raceways recognized in Chapter 3
(6) Type CMUC undercarpet communications wires and cables installed under carpet,floor covering, modular tiles, or planks. Carpet, floor covering, modular tiles, orplanks shall be freefloating and shall use interlocking means to attach to eachother or shall be adhered to the floor and shall be attached with releasetypeadhesives, but shall not be attached to the floor using grout, nails, orscrews modular flooring, and planks
Submitter Information Verification
Submitter Full Name:CMP 3Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Nov 03 10:03:55 PST 2015
Committee Statement
CommitteeStatement:
Type CMUC under carpet communication wire and cables are permitted to beinstalled under carpet with an installation expansion for modular flooring and planks.The installation instructions for free floating and interlocking does not necessarilyapply to all kinds of modular flooring and planks and could be overly restrictive.
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 37/37
Second Revision No. 614NFPA 702015 [ Part IV. ]
725.170 Listing and Marking of Equipment for Power and Data Transmission.The listed power source for circuits intended to provide power and data over Class 2cables to remote equipment shall be as specified in 725.121(A)(1) , (A)(2), (A)(3), or(A)(4). In accordance with 725.121(B) , the power sources shall not have the outputconnections paralleled or otherwise interconnected, unless listed for suchinterconnection. Powered devices connected to a circuit supplying data and power shallbe listed. Marking of equipment output connections shall be in accordance with725.121(C) .
Submitter Information Verification
Submitter Full Name:CMP 3Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Nov 03 08:14:41 PST 2015
Committee Statement
CommitteeStatement:
This new section provides appropriate references to other Sections within Article725 that apply to Power and Data Transmission equipment. Marking of the outputconnections was referred back to 725.121(C) where the marking requirementoriginates.
ResponseMessage:
Public Comment No. 691NFPA 702015 [Part IV.]
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 25/37
ResponseMessage:
Public Comment No. 225NFPA 702015 [Section No. 725.135(M)]
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 26/37
Second Revision No. 611NFPA 702015 [ New Section after 725.143 ]
725.144 Transmission of Power and Data.The requirements of 725.144(A) and (B) shall apply to Class 2 and Class 3 circuitsthat transmit power and data to a powered device. The requirements of Parts I and IIIof Article 725 and 300.11 shall apply to Class 2 and Class 3 circuits that transmitpower and data. The conductors that carry power for the data circuits shall be copper.The current in the power circuit shall not exceed the current limitation of theconnectors.
Informational No. 1: One example of the use of cables that transmit power anddata is the connection of closedcircuit TV cameras (CCTV).
Informational Note No. 2: The 8P8C connector is in widespread use withpowered communications systems. These connectors are typically rated at 1.3amperes maximum.
Table 725.144 Ampacities of Each Conductor in Amperes in 4Pair Class 2 or Class 3Data Cables Based on Copper Conductors at an Ambient Temperature of 30°C (86°F) with all All Conductors in All Cables Carrying Current, 60°C (140°F), 75°C (167°F),and 90°C (194°F) Rated Cables
AWG
Number of 4Pair Cables in a Bundle1 2–7 8–19 20–37
TemperatureRating
TemperatureRating
TemperatureRating
TemperatureRating
Temperature
60°C 75°C 90°C 60°C 75°C 90°C 60°C 75°C 90°C 60°C 75°C 90°C 60°C26 1 1 1 1 1 1 0.7 0.8 1 0.5 0.6 0.7 0.424 2 2 2 1 1.4 1.6 0.8 1 1.1 0.6 0.7 0.9 0.523 2.5 2.5 2.5 1.2 1.5 1.7 0.8 1.1 1.2 0.6 0.8 0.9 0.522 3 3 3 1.4 1.8 2.1 1 1.2 1.4 0.7 0.9 1.1 0.6
Note 1: For bundle sizes over 192 cables, or for conductor sizes smaller than 26 AWG,ampacities shall be permitted to be determined by qualified personnel underengineering supervision.
Note 2: Where only half of the conductors in each cable are carrying current, thevalues in the table shall be permitted to be increased by a factor of 1.4.
Informational Note: The conductor sizes in data cables in widespread use are typically22–26 AWG.
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 27/37
(A) Use of Class 2 or Class 3 Cables to Transmit Power and Data.Where Types CL3P, CL2P, CL3R, CL2R, CL3, or CL2 transmit power and data, thefollowing shall apply, as applicable:
(1) The ampacity ratings in Table 725.144 shall apply at an ambient temperature of30°C (86°F).
(2) For ambient temperatures above 30°C (86°F), the correction factors of 310.15(B)(2) shall apply.
Informational Note: One example of the use of Class 2 cables is anetwork of closed circuit TV cameras using 24 AWG, 60°C rated, TypeCL2R, Category 5e local area network (LAN) cables.
(B) Use of Class 2LP or Class 3LP Cables to Transmit Power and Data.Types CL3PLP, CL2PLP, CL3RLP, CL2RLP, CL3LP, or CL2LP shall be permittedto supply power to equipment at a current level up to the marked ampere limit locatedimmediately following the suffix LP and shall be permitted to transmit data to theequipment. The Class 2LP and Class 3LP cables shall comply with the following, asapplicable:
Informational Note 1: The “(xxA)” following the suffix LP indicates theampacity of each conductor in a cable.
Informational Note 2: An example of a limited power (LP) cable is a cablemarked Type CL2LP(0.5A), 23 AWG. A Type CL2LP(0.5), 23 AWG could beused in any location where a Type CL2 could be used; however, the LP cablewould be suitable for carrying up to 0.5 A per conductor, regardless of thenumber of cables in a bundle. If used in a 7cable bundle, the same cable couldcarry up to 1.2 amperes per conductor.
(1) Cables with the suffix “LP” shall be permitted to be installed in bundles,raceways, cable trays, communications raceways, and cable routingassemblies.
(2) Cables with the suffix “LP” and a marked ampere level shall follow thesubstitution hierarchy of Table 725.154 and Figure 725.154(A) for the cabletype without the suffix “LP” and without the marked ampere level.
(3) System design shall be permitted by qualified persons under engineeringsupervision.
Supplemental Information
File Name Description725.144_SR611_JS.docx For staff use.
Submitter Information Verification
Submitter Full Name:CMP 3Organization: [ Not Specified ]Street Address:City:State:
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 28/37
Zip:Submittal Date: Mon Nov 02 19:37:38 EST 2015
Committee Statement
CommitteeStatement:
The new section 725.144 and the accompanying table has been added based uponthe Fact Finding Report on Power over Local Area Network type cables withadditionally an introduction to new cable type LP that provides the current limitationdue to cable bundling and some other installation considerations for power overEthernet.
ResponseMessage:
Public Comment No. 692NFPA 702015 [Section No. 725.143]
Public Comment No. 1689NFPA 702015 [Section No. 725.143]
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 34/37
Second Revision No. 617NFPA 702015 [ Section No. 760.135(A) ]
(A) Listing.PLFA cables installed in buildings shall be listed and labeled .
Submitter Information Verification
Submitter Full Name:CMP 3Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Nov 03 08:55:04 PST 2015
Committee Statement
CommitteeStatement:
FR 634 already accepted this text. The panel reaffirms its stance on this topic: Byadding the word "labeled," it will identify that listed products also need to be labeled.Both terms "listed" and "labeled" are defined in Article 100, but are not usedconsistently throughout the NEC.
ResponseMessage:
Public Comment No. 1429NFPA 702015 [Section No. 760.135(A)]
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 29/37
Second Revision No. 615NFPA 702015 [ Section No. 725.179 ]
725.179 Listing and Marking of Class 2, Class 3, and Type PLTC Cables.Class 2, Class 3, and Type PLTC cables, installed as wiring methods within buildings,shall be listed as resistant to the spread of fire and other criteria in accordance with725.179(A) through (H I ) and shall be marked in accordance with725.179(J)725.179(J)725.179(J)725.179(J)725.179(I) .
(A) Types CL2P and CL3P.Types CL2P and CL3P plenum cable shall be listed as suitable for use in ducts,plenums, and other space for environmental air and shall be listed as having adequatefireresistant and lowsmoke producing characteristics.
Informational Note: One method of defining a cable that is lowsmoke producingand fire resistant is that the cable exhibits a maximum peak optical density of0.50 or less, an average optical density of 0.15 or less, and a maximum flamespread distance of 1.52 m (5 ft) or less when tested in accordance with NFPA2622015 , Standard Method of Test for Flame Travel and Smoke of Wires andCables for Use in AirHandling Spaces.
(B) Types CL2R and CL3R.Types CL2R and CL3R riser cables shall be marked as Type CL2R or CL3R,respectively, and be listed as suitable for use in a vertical run in a shaft or from floor tofloor and shall be listed as having fireresistant characteristics capable of preventing thecarrying of fire from floor to floor.
Informational Note: One method of defining fireresistant characteristics capableof preventing the carrying of fire from floor to floor is that the cables pass therequirements of ANSI/UL 16662012, Test for Flame Propagation Height ofElectrical and OpticalFiber Cable Installed Vertically in Shafts.
(C) Types CL2 and CL3.Types CL2 and CL3 cables shall be marked as Type CL2 or CL3, respectively, and belisted as suitable for generalpurpose use, with the exception of risers, ducts, plenums,and other space used for environmental air, and shall be listed as resistant to the spreadof fire.
Informational Note: One method of defining resistant to the spread of fire is thatthe cables do not spread fire to the top of the tray in the UL flame exposure,vertical tray flame test in ANSI/UL 16852010, Standard for Safety for VerticalTray FirePropagation and SmokeRelease Test for Electrical and OpticalFiberCables. The smoke measurements in the test method are not applicable.
Another method of defining resistant to the spread of fire is for the damage (charlength) not to exceed 1.5 m (4 ft 11 in.) when performing the CSA vertical flametest for— cables in cable trays, as described in CSA C22.2 No. 0.3M2001, TestMethods for Electrical Wires and Cables.
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 30/37
(D) Types CL2X and CL3X.Types CL2X and CL3X limiteduse cables shall be marked as Type CL2X or CL3X, andbe listed as suitable for use in dwellings and raceways and shall be listed as resistant toflame spread.
Informational Note: One method of determining that cable is resistant to flamespread is by testing the cable to the VW1 (vertical wire) flame test in ANSI/UL15812011, Reference Standard for Electrical Wires, Cables and Flexible Cords.
(E) Type PLTC.Type PLTC nonmetallicsheathed, powerlimited tray cable shall be listed as beingsuitable for cable trays and shall consist of a factory assembly of two or more insulatedconductors under a nonmetallic jacket. The insulated conductors shall be 22 AWGthrough 12 AWG. The conductor material shall be copper (solid or stranded). Insulationon conductors shall be rated for 300 volts. The cable core shall be two or more parallelconductors, one or more group assemblies of twisted or parallel conductors, or acombination thereof. A metallic shield or a metallized foil shield with drain wire(s) shallbe permitted to be applied over the cable core, over groups of conductors, or both. Thecable shall be listed as resistant to the spread of fire. The outer jacket shall be asunlight and moistureresistant nonmetallic material. Type PLTC cable used in a wetlocation shall be listed for use in wet locations or have a moistureimpervious metalsheath.
Exception No. 1: Where a smooth metallic sheath, continuous corrugated metallicsheath, or interlocking tape armor is applied over the nonmetallic jacket, an overallnonmetallic jacket shall not be required. On metallicsheathed cable without an overallnonmetallic jacket, the information required in 310.120 shall be located on thenonmetallic jacket under the sheath.
Exception No. 2: Conductors in PLTC cables used for Class 2 thermocouple circuitsshall be permitted to be any of the materials used for thermocouple extension wire.
Informational Note: One method of defining resistant to the spread of fire is thatthe cables do not spread fire to the top of the tray in the UL flame exposure,vertical tray flame test in ANSI/UL 16852010, Standard for Safety for VerticalTray FirePropagation and SmokeRelease Test for Electrical and OpticalFiberCables. The smoke measurements in the test method are not applicable.
Another method of defining resistant to the spread of fire is for the damage (charlength) not to exceed 1.5 m (4 ft 11 in.) when performing the CSA vertical trayflame test for cables in cable trays, as described in CSA C22.2 No. 0.3M2001,Test Methods for Electrical Wires and Cables.
(F) Circuit Integrity (CI) Cable or Electrical Circuit Protective System.Cables that are used for survivability of critical circuits under fire conditions shall meeteither 725.179(F)(1) or (F)(2) as follows:
(1) Circuit Integrity (CI) Cables.Circuit Integrity (CI) cables, specified in 725.179(A), (B), (C), and (E), and used forsurvivability of critical circuits, shall have the additional classification using the suffix“CI.” Circuit integrity (CI) cables shall only be permitted to be installed in a racewaywhere specifically listed and marked as part of an electrical circuit protective system ascovered in 725.179(F)(2).
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 31/37
(2) Electrical Circuit Protective System.Cables specified in 725.179(A), (B), (C), (E), and (F)(1) that are part of an electricalcircuit protective system shall be identified with the protective system number andhourly rating printed on the outer jacket of the cable and installed in accordance with thelisting of the protective system.
Informational Note No. 1: One method of defining circuit integrity (CI) cable or anelectrical circuit protective system is by establishing a minimum 2hour fireresistive rating when tested in accordance with UL 21962012, Standard for Testsof Fire Resistive Cables.
Informational Note No. 2: UL guide information for electrical circuit protectivesystems (FHIT) contains information on proper installation requirements tomaintain the fire rating.
(G) Class 2 and Class 3 Cable Voltage Ratings.Class 2 cables shall have a voltage rating of not less than 150 volts. Class 3 cablesshall have a voltage rating of not less than 300 volts. Class 2 and Class 3 cables shallhave a temperature rating of not less than 60°C (140°F).
(H) Class 3 Single Conductors.Class 3 single conductors used as other wiring within buildings shall not be smaller than18 AWG and shall be Type CL3. Conductor types described in 725.49(B) that are alsolisted as Type CL3 shall be permitted.
Informational Note: One method of defining resistant to the spread of fire is thatthe cables do not spread fire to the top of the tray in the UL flame exposure,vertical tray flame test in ANSI/UL 16852010, Standard for Safety for VerticalTray FirePropagation and SmokeRelease Test for Electrical and OpticalFiberCables. The smoke measurements in the test method are not applicable.
Another method of defining resistant to the spread of fire is for the damage (charlength) not to exceed 1.5 m (4 ft 11 in.) when performing the CSA vertical trayflame test for cables in cable trays, as described in CSA C22.2 No. 0.3M2001,Test Methods for Electrical Wires and Cables.
(I) Limited Power (LP) Cables.Limited power (LP) cables shall be listed as suitable for carrying power and datacircuits up to a specified current limit for each conductor without exceeding thetemperature rating of the cable where the cable is installed in cable bundles in free airor installed within a raceway, cable tray, or cable routing assembly. The cables shall bemarked with the suffix “LP” with the ampere limit located immediately following thesuffix LP, where the current limit is in amperes per conductor.
Informational Note: The ampere limit located immediately following the suffixLP is the ampacity of each conductor in a cable. For example, 1 ampere Class2 limitedpower cables would be marked CL2LP (1.0A), CL2RLP (1.0A), orCL2LP (1.0A).
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 32/37
(J) Marking.Cables shall be marked in accordance with 310.120(A)(2), (A)(3), (A)(4), (A)(5), andTable 725.179(K) Table 725.179(J) . Voltage ratings shall not be marked on the cables.Temperature rating shall be marked on the jacket of Class 2 and Class 3 cables thathave a temperature rating exceeding 60°C (140°F).
Informational Note: Voltage markings on cables may be misinterpreted to suggestthat the cables may be suitable for Class 1 electric light and power applications.
Exception: Voltage markings shall be permitted where the cable has multiple listingsand a voltage marking is required for one or more of the listings.
Temperature rating shall be marked on the jacket of Class 2 and Class 3 cables thathave a temperature rating exceeding 60°C (140°F).
Table 725.179(J) Cable Marking
Cable Marking TypeCL3P Class 3 plenum cableCL2P Class 2 plenum cableCL3R Class 3 riser cableCL2R Class 2 riser cablePLTC Powerlimited tray cableCL3 Class 3 cableCL2 Class 2 cableCL3X Class 3 cable, limited useCL2X Class 2 cable, limited use
Informational Note: Class 2 and Class 3 cable types are listed in descendingorder of fire resistance rating, and Class 3 cables are listed above Class 2 cablesbecause Class 3 cables can substitute for Class 2 cables.
Submitter Information Verification
Submitter Full Name:CMP 3Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Nov 03 08:20:28 PST 2015
Committee Statement
Committee Statement: Information on limited power cables is being added to the Code.Response Message:
Public Comment No. 688NFPA 702015 [Section No. 725.179]
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 33/37
Second Revision No. 616NFPA 702015 [ Section No. 760.3(B) ]
(B) Ducts, Plenums, and Other AirHandling Spaces.Section 300.22 , where Powerlimited and nonpowerlimited fire alarm cables installedin ducts or , plenums, or other spaces used for environmental air shall comply with300.22 .
Exception No. 1: As permitted in 760.53(B)(1) and (B)(2) and Table 760.154 .Powerlimited fire alarm cables selected in accordance with Table 760.154 andinstalled in accordance with 760.135(B) and 300.22(B) , Exception shall be permittedto be installed in ducts specifically fabricated for environmental air.
Exception No. 2: Powerlimited fire alarm cables selected in accordance with Table760.154 and installed in accordance with 760.135(C) shall be permitted to beinstalled in other spaces used for environmental air (plenums).
Submitter Information Verification
Submitter Full Name:CMP 3Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Nov 03 08:40:41 PST 2015
Committee Statement
CommitteeStatement:
The existing exception was not in compliance with the NEC Style manual. Thesecond exception was inserted to deal with powerlimited fire alarm cables installedin other spaces used for environmental air (plenums). The reference to 300.22(B),Exception was inserted to ensure correlation with the requirements in NFPA 90A.
ResponseMessage:
Public Comment No. 454NFPA 702015 [Section No. 760.3(B)]
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 35/37
Second Revision No. 618NFPA 702015 [ Section No. 760.176
[Excluding any SubSections] ]
Nonpowerlimited fire alarm cables installed as wiring within buildings shall be listed inaccordance with 760.176(A) and (B) and as being resistant to the spread of fire inaccordance with 760.176(C) through (F), and shall be marked in accordance with760.176(G). Cable used in a wet location shall be listed for use in wet locations or havea moistureimpervious metal sheath. Nonpowerlimited fire alarm cables shall have atemperature rating of not less than 60°C (140°F).
Submitter Information Verification
Submitter Full Name:CMP 3Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Nov 03 08:57:59 PST 2015
Committee Statement
CommitteeStatement:
The temperature rating of these cables is required to provide pertinent informationso the installer is aware of the temperature limitation of the conductors.
ResponseMessage:
Public Comment No. 461NFPA 702015 [Section No. 760.176 [Excluding any SubSections]]
12/22/2015 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 36/37
Second Revision No. 619NFPA 702015 [ Section No. 760.179(C) ]
(C) Ratings.The cable shall have a voltage rating of not less than 300 volts. The cable shall have atemperature rating of not less than 60°C (140°F).
Submitter Information Verification
Submitter Full Name:CMP 3Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Nov 03 08:59:57 PST 2015
Committee Statement
CommitteeStatement:
The temperature rating of these cables is required to provide pertinent informationso the installer is aware of the temperature limitation of the conductors.
ResponseMessage:
Public Comment No. 450NFPA 702015 [Section No. 760.179(C)]