section7_1-dtt_pt2_iex
TRANSCRIPT
-
7/30/2019 Section7_1-DTT_PT2_Iex
1/12
1
Transformer Excitation
Current Test Procedures
Doble Engineering DiagnosticsToolbox
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry 2
Abnormal core grounds Winding faults: shorts, open
circuits
LTC problems
Manufacturing defects
The Doble Excitation Current Test has beeneffective in finding:
-
7/30/2019 Section7_1-DTT_PT2_Iex
2/12
2
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry 3
1) When an AC Voltage Source, such as a Doble Test Set, is placed on a
transformer, a small current will flow.
2) This small current is the Magnetizing Current: the current required to
magnetize the Transformer core with the Magnetic Fluxmag. ThisMagnetizing Current is the Excitation Current we measure and record.3) This Magnetic Flux will induce a voltage across the secondary
windings: V2
Iexcitation =Imag
V1
mag
+
-V2
+
-
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry 4
1) When a Load is placed on the secondary windings a current will flow
I2=V2/R2 [ Ohms Law ]
2) The Current I2
will in-turn create an Opposing Magnetic Flux2.
3) The Generator, which regulates voltage at a set level, will provide more
current to maintain the core magnetized equal to the opposing flux
Iexcitation =Imag+I2
I22
V2
+
-
V1
Iexcitation =Imag+I2
+
-
mag+2
R2
-
7/30/2019 Section7_1-DTT_PT2_Iex
3/12
3
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry 5
E1
mag+fault
Ifault
X0
X1UST
fault
+
-
Imag+IfHV
LV
H0
H1
1) If a fault develops in the secondary windings, this fault will act as aload across the faulted windings drawing a current Ifault
2) As a result, the Excitation Current will go up due to the opposing flux
created by the fault [fault]
Result: A Fault will cause Excitation Current to Increase
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry 6
Iexcitation=Imag+Ifault
1) If the secondary winding has a grounded neutral and one of the windingsdevelops a fault to ground, grounded windings will draw a fault current
2) As a result, the Excitation Current will go up due to the opposing flux createdby the fault [fault]
Result: A grounded winding on a transformer with a grounded
neutral will cause the Excitation Current to go up.
H0
H1
fault
X1
Ifault
mag+fault
XoNeutral Ground
Ground Fault
HV
LV
UST
+
-
-
7/30/2019 Section7_1-DTT_PT2_Iex
4/12
4
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry 7
When an autotransformer is connected across two taps it acts as aload and the primary current goes up.
Result: When a LTC transitioning device such as a Preventive
Autotransformer is in the bridging position the
excitation current goes up.
Iexcitation=Imag+IAT
H0
H1
AT
X1mag+AT
Xo
HV
LV
UST
+
-
IA
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry 8
Excitation Current test results present patterns:
Three Phase Transformers: Between phases
(Two Similar Highs and One Low)* Within each Phase
(When Tap Changers are present)**
Single Phase Transformers
Reverse measurement for confirmation
* There are exceptions** Pattern will depend on Tap Changer type and Manufacture
-
7/30/2019 Section7_1-DTT_PT2_Iex
5/12
5
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry 9
=
(b) Reluctance Circuit(a) Ferrous Core
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry 10
For simplicity assume that each section has a reluctance of 1
1
1
1 1
1 1 A B C
In this example we have a three Phase three legged core
-
7/30/2019 Section7_1-DTT_PT2_Iex
6/12
6
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry 11
HV
-
P1
P2
A B C
When you energize Phase A the equivalent reluctance circuit becomes:
HV
-
P1
P2
3.75
The same holds true when you energize Phase C
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry 12
B
For Phase B the equivalent reluctance circuit becomes:
HV
-
P1
P2
2.5
P1
P2
-
7/30/2019 Section7_1-DTT_PT2_Iex
7/12
7
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry 13
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry 14
Benchmark or Base Measurement:
LTC only: all positions NLTC only: all positions LTC and NLTC combination:
all LTC positions with NLTC in
center position; then all positions
in NLTC with LTC in neutral
On a Routine Basis:
NLTC only: as found or positionregularly tapped
LTC only: one full range plus neutraland one position in opposite range
NLTC and LTC combination:NLTC in regularly tapped position or as
found testing the LTC one full range
plus neutral and one position in opposite
range
When Tap Changers are present, test as follows:
-
7/30/2019 Section7_1-DTT_PT2_Iex
8/12
8
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry 15
Perform tests at the highest Voltage possible
Test each Phase at the same Voltage
Perform subsequent tests at the same Voltage forcomparison
If a Preventive Autotransformer is included in thetransformer, it might not be possible to excite thatposition of the LTC. In this event, testing might bepossible with the Preventive Autotransformer bypassedor at a lower voltage
If the test set trips, choose a lower Voltage and repeat
all three phases Never allow test voltage to exceed rated L-L for Delta
and L-G for Wye
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry 16
Be aware of test equipment limitations Have consistent procedures Document special conditions, be specific If the Test set trips, choose a lower Voltage and repeat
all three phases
Example
M4K is rated for 300 mA at 10 kV
10 kV 300 mA
9 kV 333 mA
8 kV 375 mA7 kV 429 mA
6 kV 500 mA
5 kV 600 mA
-
7/30/2019 Section7_1-DTT_PT2_Iex
9/12
9
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry 17
=
(b) Reluctance Circuit(a) Ferrous Core
Remember this:
Because test must comply with:
Test at the highest Voltage possible Test each Phase at the same Voltage
Phase demanding the highest current should be tested first
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry 18
-
7/30/2019 Section7_1-DTT_PT2_Iex
10/12
10
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry 19
H1
H2H3
HV
USTI1-2 I1-3
Test Measure
1 H1-H2
2 H2-H3
3 H3-H1
When Low Voltage side is Wye configuration, remember to
ground the Neutral
LV
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry 20
H1
H0
H2 H3
HV
LV
UST I1-0Test Measure
1 H1-H0
2 H2-H0
3 H3-H0
When Low Voltage side is Wye configuration, remember to
ground the Neutral
-
7/30/2019 Section7_1-DTT_PT2_Iex
11/12
11
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry 21
Remember that the Excitation Current test is the only test where
the short circuit jumpers are taken off the bushings
H1
H0
HV
LV
USTI1-0
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry 22
Check the pattern: two similar high readings and onelow reading is normal (though there are exceptions)
When Tap Changers are present, consider the patternwithin the phase
For three-phase units, compare both high readings withthe following criterion: Readings 50 mA, differences should not exceed 5%
For single phase units both readings should becompared using the same above criterion
Compare Normal test to alternate tests; results shouldbe similar for a winding in good condition
-
7/30/2019 Section7_1-DTT_PT2_Iex
12/12
12
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry 23
Compare Normal test to alternate tests; results shouldbe similar for a winding in good condition
Compare readings to previous results. Ensure that thesame voltage was used for both tests for consistentnumerical comparison
If the core is magnetized an irregular pattern (high,medium, low readings) will be present and you will beunable to compare results effectively. A true problemcould be masked, therefore core should be
demagnetized and test should be repeated If unusual results are obtained, consider performing an
alternate test to further investigate