Samuele Infanti - Test Laboratory Director
Seismic Base Isolation Applications within the Scope of New Codes
Workshop
3 May 2018 – Thursday
Wyndham Hotel – Ankara
SEISMIC ISOLATION2013-2014
Van Medical Campus, TurkeyVan Medical Campus, TurkeyHIGHLIGHTSHIGHLIGHTS
Seismic Base Isolation Applications within the Scope of New Codes
Workshop
3 May 2018 – Thursday
Wyndham Hotel – Ankara
Devices 512 nos. Pendulum Isolators
NEd 3500÷6000 kN
R 6000 mm
dEd ± 500 mm
TT 12 nos. units tested in U.S.A.
at UCSD
FPC 95 nos. units tested in Italy
at SISLAB
SEISMIC ISOLATION2015
Kahramanmaras Elbistan Hospital, TurkeyKahramanmaras Elbistan Hospital, TurkeyHIGHLIGHTSHIGHLIGHTS
Seismic Base Isolation Applications within the Scope of New Codes
Workshop
3 May 2018 – Thursday
Wyndham Hotel – Ankara
Devices 455 nos. Pendulum Isolators
NEd 1000÷7500 kN
R 3100 mm
dED ± 300 mm
TT 16 nos. units tested in Italy
at EUCENTRE and SISLAB
FPCT 13 nos. units tested in Italy
at EUCENTRE and SISLAB
SEISMIC ISOLATION2015-2016
Samsun Ammonia Tank, TurkeySamsun Ammonia Tank, TurkeyHIGHLIGHTSHIGHLIGHTS
Seismic Base Isolation Applications within the Scope of New Codes
Workshop
3 May 2018 – Thursday
Wyndham Hotel – Ankara
Devices 121 nos. Pendulum Isolators
NEd 1840÷3100 kN
R 4500 mm
dEd ± 450 mm
TT 6 nos. units tested in Italy
at FIP laboratory and
witnessed by Padua University
FPC 2 nos. units tested in Italy
at FIP laboratory
SEISMIC ISOLATION2015-2016
Manisa Merkez Efendi Hospital, TurkeyManisa Merkez Efendi Hospital, TurkeyHIGHLIGHTSHIGHLIGHTS
Seismic Base Isolation Applications within the Scope of New Codes
Workshop
3 May 2018 – Thursday
Wyndham Hotel – Ankara
Devices 505 Pendulum Isolators
NEd 2000÷18000 kN
R 4500 mm
dEd ± 360 mm; ± 380 mm.
TT 12 nos. units tested in Italy
at FIP laboratory and
witnessed by Padua University
FPC 17 nos. units tested in Italy
at FIP laboratory
SEISMIC ISOLATION2017
Tokat Erbaa Hospital, TurkeyTokat Erbaa Hospital, TurkeyHIGHLIGHTSHIGHLIGHTS
Seismic Base Isolation Applications within the Scope of New Codes
Workshop
3 May 2018 – Thursday
Wyndham Hotel – Ankara
Devices 309 nos. Pendulum Isolators
NEd 1500÷22500 kN
R 5000 mm
dEd ± 440 mm
TT 10 nos. units tested in Italy
at FIP laboratory and
witnessed by Padua University
FPC 9 nos. units tested in Italy
at FIP laboratory
SEISMIC ISOLATION2017-2018
Mugla Bodrum Hospital, TurkeyMugla Bodrum Hospital, TurkeyHIGHLIGHTSHIGHLIGHTS
Seismic Base Isolation Applications within the Scope of New Codes
Workshop
3 May 2018 – Thursday
Wyndham Hotel – Ankara
Devices 245 nos. Pendulum Isolators
NEd 5000÷14250 kN
R 4500 mm
dEd ± 330 mm
TT 4 nos. units tested in Italy
at FIP laboratory and
witnessed by Padua University
FPC 10 nos. units tested in Italy
at FIP laboratory
Description of the Samsun ammonia tank
• new double wall refrigerated storage tank - 22000 m3
capacity, De=35.1 m, H=31 m - filled with liquefied ammonia• high seismicity: Tekkeköy, Samsun region, Turkey
PGA: 0.278 g at DBE, 0.490 g at MCE• the aim is to keep the existing substructure
Seismic Base Isolation Applications within the Scope of New Codes
Workshop
3 May 2018 – Thursday
Wyndham Hotel – Ankara
• the aim is to keep the existing substructure(r.c. slab on 121 square columns) without reducing the capacity of the tank
• problems: a) insufficient strengthof the existing columns;b) sliding of the tank
• solution: seismic retrofit w.seismicisolation with pendulum isolators
Seismic input
• site specific seismic hazard analysis
1
1.2
1.4
Sa (g
)
MCE Site Specific RS DBE Site Specific RS
Seismic Base Isolation Applications within the Scope of New Codes
Workshop
3 May 2018 – Thursday
Wyndham Hotel – Ankara
0
0.2
0.4
0.6
0.8
1
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5
Period (s)
SeismicSeismic isolationisolation systemsystem
• max. base shear at DBE(475 years return period earthquake): 11% W
• max. base shear at MCE
Design Design requirementsrequirements
Seismic Base Isolation Applications within the Scope of New Codes
Workshop
3 May 2018 – Thursday
Wyndham Hotel – Ankara
• max. base shear at MCE(2475 years return period earthquake): 18% W
• response modification factor 1.0for all the earthquake levels
• max. displacement capacity 450 mm (at MCE)
Seismic isolation systemSeismic isolation systemCharacteristics of the selected isolatorsCharacteristics of the selected isolators
• 3 types of pendulum isolators
• R=4.5 m
• two types of friction material(M and L)
• average friction coefficient6.2 %
Seismic isolation systemSeismic isolation systemCharacteristics of the selected isolatorsCharacteristics of the selected isolators
Isolator Type Isolator mark
Max vertical
load at ULS
seismic
Max vertical
load at ULS
static
Nominal
coefficient of
dynamic
friction at NEd
Nos.
NEd [kN] Fzd [kN]
1 FIP-D M 1150/900 (4500) 3100 4000 5.5% 32
Seismic Base Isolation Applications within the Scope
of New Codes Workshop
3 May 2018 – Thursday
Wyndham Hotel – Ankara
2 FIP-D M 960/900 (4500) 2110 3000 5.5% 64
3 FIP-D L 530/900 (4500) 1840 2750 2.5% 25
Maximum displacement capacity (dEd): ±450 mm
Equivalent radius of curvature (Req): 4500 mm
Maximum rotation combined with maximum displacement (α): ±0.005 rad
SimplifiedSimplified modellingmodelling
• Preliminary analyseson a simplified 3 masses modelto design the seismic isolationsystem
• Non-linear time history analyseswith 3 couples of ground motion recordswith 3 couples of ground motion records
NonNon--linear time history analyseslinear time history analysesInput: Input: selectedselected Ground Motion Ground Motion RecordsRecords
� ERZINCAN1992
� KOCAELI1999
� DUZCE1999
NonNon--linear time history analyseslinear time history analysesInput:check of spectrum compatibilityInput:check of spectrum compatibility
2.5
3
Sa (g
)
MCE Site Specific RS MCE Erzincan SRSS RS MCE Kocaeli SRSS RSMCE Duzce SRSS RS DBE Site Specific RS DBE Erzincan SRSS RSDBE Kocaeli SRSS RS DBE Duzce SRSS RS
0
0.5
1
1.5
2
2.5
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6
Period (s)
NonNon--linear time history analyseslinear time history analysesResults: base shearResults: base shear
Kocaeli 1999 gives the most severe response, well within the required limits:
Erzincan
MCE DBE
The required limitswere:11% at DBE
0% 2% 4% 6% 8% 10% 12% 14%
Duzce
Kocaeli
Base Shear / Total Weight (%)
11% at DBE18% at MCE
NonNon--linear time history analyseslinear time history analysesResults: displacementResults: displacement
The requiredlimit was:450 mm at MCE
Erzincan
MCE DBE
0 50 100 150 200 250 300 350 400 450
Duzce
Kocaeli
Displacement (mm)
NonNon--linear time history analyseslinear time history analysesResults (Kocaeli 1999 scaled at MCE)Results (Kocaeli 1999 scaled at MCE)
1
3
5
Acc
eler
atio
n (m
/s2 )
Ground Motion Impulsive Mass Convective Mass
-5
-3
-1
1
0.0 2.5 5.0 7.5 10.0 12.5 15.0 17.5 20.0 22.5 25.0
Acc
eler
atio
n (m
/s
Time (s)
The peak accerelation of the impulsive mass is 1.57 m/s2, i.e. 1/3 of the PGA
Tests on isolatorsTests on isolators
• according to European Standard EN 15129+ additional test
at FIP Industriale’s Dynamic Test at FIP Industriale’s Dynamic Test FacilityFacility
FIP Dynamic Test FacilityFIP Dynamic Test FacilityIsolators Test System Isolators Test System -- Main FeaturesMain Features
Dynamic Vertical Load: 200kN÷20000kN
Maximum Static Vertical Load: 30000kN
Dynamic Horizontal Load: 3000kN
Seismic Base Isolation Applications within the Scope of New Codes
Workshop
3 May 2018 – Thursday
Wyndham Hotel – Ankara
Dynamic Horizontal Displacement: ±500mm
Horizontal Velocity Actuator: ±1570mm/s
Dynamic Vertical Displacement: 0÷65mm
Static Vertical Displacement: 0÷700mm
Isolators Test System
Max Vertical Load: 30000kN
Total V. Stroke: 700mm
Horizontal Load: 3000kN
Stroke: ±500mm
Seismic Base Isolation Applications within the Scope of New Codes
Workshop
3 May 2018 – Thursday
Wyndham Hotel – AnkaraFIP Dynamic Test FIP Dynamic Test
FacilityFacility
Automatic Sample Loading
System
Tests on isolatorsTests on isolators
• FIP-D M 1150/900(4500)vertical load 2210 kN
atat FIP FIP Industriale’sIndustriale’s LaboratoryLaboratory --TypeType TestsTests
• FIP-D L 530/900(4500)vertical load 1503 kN
3 fully reversed cycles, sinusoidal input,displacement ± 450 mm, peak velocity 664 mm/s
TestsTests on on isolatorsisolatorsatat FIP FIP Industriale’sIndustriale’s LaboratoryLaboratory ––TypeType TestsTests• FIP-D M 960/900(4500)
displacement ± 359 mm, peak velocity 530 mm/s
TestsTests on on isolatorsisolatorsatat FIP FIP Industriale’sIndustriale’s Laboratory Laboratory -- Type Type TestsTests
Friction Vs. Vertical Friction Vs. Vertical LoadLoadD3 D3 -- E1 E1 -- E2 TestsE2 TestsD3 D3 -- E1 E1 -- E2 TestsE2 TestsEN15129:2009EN15129:2009
TestsTests on on isolatorsisolatorsatat FIP FIP Industriale’sIndustriale’s LaboratoryLaboratory ––TypeType TestsTests
FIP-D L 530/900(4500) – 450mm_664mm/s E1-FIP-DL530.mp4
FIP-D L 1150/900(4500)-450mm_664mm/sD3-FIP-DM1150.mp4
TestsTests on on isolatorsisolatorsatat FIP FIP Industriale’sIndustriale’s Laboratory Laboratory --Time Time HistoryHistory TestsTests
TestsTests on on isolatorsisolatorsatat FIP FIP Industriale’sIndustriale’s Laboratory Laboratory --Time Time HistoryHistory TestsTests
TestsTests on on isolatorsisolatorsatat FIP FIP Industriale’sIndustriale’s Laboratory Laboratory --Time Time HistoryHistory TestsTests
Tests on isolatorsTests on isolatorsatat FIP FIP Industriale’sIndustriale’s LaboratoryLaboratory ––Time Time HistoryHistory TestsTests
MAH00925.MP4MAH00925.MP4MAH00926.MP4MAH00926.MP4
InstallationInstallationSeismic Base Isolation Applications within the Scope of New Codes
Workshop
3 May 2018 – Thursday
Wyndham Hotel – Ankara
a pendulum isolator (FIP-D series) as installed
Dampers Test SystemDampers Test SystemFIP Dynamic Test FacilityFIP Dynamic Test Facility
Seismic Base Isolation Applications within the Scope of New Codes
Workshop
3 May 2018 – Thursday
Wyndham Hotel – Ankara
V. Damper OT(P)500/4000
Design Load: 5000kN
Test Stroke: ±200mm
Frequency: 0.4Hz
Test Velocity: 500mm/s
Izmit Bay Bridge, Turkey Izmit Bay Bridge, Turkey OTP.mp4OTP.mp4
• Seismic isolation is an effective solution for the protection of new and existing structures (Buildings, bridges, industrial plants, etc.)
• seismic isolation with pendulum isolators (double concave curved surface sliders) guarantees the possibility of
ConclusionsConclusionsSeismic Base Isolation Applications within the Scope of New Codes
Workshop
3 May 2018 – Thursday
Wyndham Hotel – Ankara
curved surface sliders) guarantees the possibility of reusing the existing tank substructures without reducingthe tank capacity
• the nonlinear time history analyses results show that the acceleration on the impulsive mass is less than 1/3 of PGA
• the results of the dynamic tests carried out on the isolatorsconfirm that their behaviour corresponds to the theoreticalone
Thanks for Your kind attention .