seismic base isolation applications within the scope of new codes workshop 3 … · 2018. 5....

33
Samuele Infanti - Test Laboratory Director Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 May 2018 – Thursday Wyndham Hotel – Ankara

Upload: others

Post on 14-Nov-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

Samuele Infanti - Test Laboratory Director

Seismic Base Isolation Applications within the Scope of New Codes

Workshop

3 May 2018 – Thursday

Wyndham Hotel – Ankara

Page 2: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

SEISMIC ISOLATION2013-2014

Van Medical Campus, TurkeyVan Medical Campus, TurkeyHIGHLIGHTSHIGHLIGHTS

Seismic Base Isolation Applications within the Scope of New Codes

Workshop

3 May 2018 – Thursday

Wyndham Hotel – Ankara

Devices 512 nos. Pendulum Isolators

NEd 3500÷6000 kN

R 6000 mm

dEd ± 500 mm

TT 12 nos. units tested in U.S.A.

at UCSD

FPC 95 nos. units tested in Italy

at SISLAB

Page 3: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

SEISMIC ISOLATION2015

Kahramanmaras Elbistan Hospital, TurkeyKahramanmaras Elbistan Hospital, TurkeyHIGHLIGHTSHIGHLIGHTS

Seismic Base Isolation Applications within the Scope of New Codes

Workshop

3 May 2018 – Thursday

Wyndham Hotel – Ankara

Devices 455 nos. Pendulum Isolators

NEd 1000÷7500 kN

R 3100 mm

dED ± 300 mm

TT 16 nos. units tested in Italy

at EUCENTRE and SISLAB

FPCT 13 nos. units tested in Italy

at EUCENTRE and SISLAB

Page 4: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

SEISMIC ISOLATION2015-2016

Samsun Ammonia Tank, TurkeySamsun Ammonia Tank, TurkeyHIGHLIGHTSHIGHLIGHTS

Seismic Base Isolation Applications within the Scope of New Codes

Workshop

3 May 2018 – Thursday

Wyndham Hotel – Ankara

Devices 121 nos. Pendulum Isolators

NEd 1840÷3100 kN

R 4500 mm

dEd ± 450 mm

TT 6 nos. units tested in Italy

at FIP laboratory and

witnessed by Padua University

FPC 2 nos. units tested in Italy

at FIP laboratory

Page 5: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

SEISMIC ISOLATION2015-2016

Manisa Merkez Efendi Hospital, TurkeyManisa Merkez Efendi Hospital, TurkeyHIGHLIGHTSHIGHLIGHTS

Seismic Base Isolation Applications within the Scope of New Codes

Workshop

3 May 2018 – Thursday

Wyndham Hotel – Ankara

Devices 505 Pendulum Isolators

NEd 2000÷18000 kN

R 4500 mm

dEd ± 360 mm; ± 380 mm.

TT 12 nos. units tested in Italy

at FIP laboratory and

witnessed by Padua University

FPC 17 nos. units tested in Italy

at FIP laboratory

Page 6: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

SEISMIC ISOLATION2017

Tokat Erbaa Hospital, TurkeyTokat Erbaa Hospital, TurkeyHIGHLIGHTSHIGHLIGHTS

Seismic Base Isolation Applications within the Scope of New Codes

Workshop

3 May 2018 – Thursday

Wyndham Hotel – Ankara

Devices 309 nos. Pendulum Isolators

NEd 1500÷22500 kN

R 5000 mm

dEd ± 440 mm

TT 10 nos. units tested in Italy

at FIP laboratory and

witnessed by Padua University

FPC 9 nos. units tested in Italy

at FIP laboratory

Page 7: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

SEISMIC ISOLATION2017-2018

Mugla Bodrum Hospital, TurkeyMugla Bodrum Hospital, TurkeyHIGHLIGHTSHIGHLIGHTS

Seismic Base Isolation Applications within the Scope of New Codes

Workshop

3 May 2018 – Thursday

Wyndham Hotel – Ankara

Devices 245 nos. Pendulum Isolators

NEd 5000÷14250 kN

R 4500 mm

dEd ± 330 mm

TT 4 nos. units tested in Italy

at FIP laboratory and

witnessed by Padua University

FPC 10 nos. units tested in Italy

at FIP laboratory

Page 8: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

Description of the Samsun ammonia tank

• new double wall refrigerated storage tank - 22000 m3

capacity, De=35.1 m, H=31 m - filled with liquefied ammonia• high seismicity: Tekkeköy, Samsun region, Turkey

PGA: 0.278 g at DBE, 0.490 g at MCE• the aim is to keep the existing substructure

Seismic Base Isolation Applications within the Scope of New Codes

Workshop

3 May 2018 – Thursday

Wyndham Hotel – Ankara

• the aim is to keep the existing substructure(r.c. slab on 121 square columns) without reducing the capacity of the tank

• problems: a) insufficient strengthof the existing columns;b) sliding of the tank

• solution: seismic retrofit w.seismicisolation with pendulum isolators

Page 9: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

Seismic input

• site specific seismic hazard analysis

1

1.2

1.4

Sa (g

)

MCE Site Specific RS DBE Site Specific RS

Seismic Base Isolation Applications within the Scope of New Codes

Workshop

3 May 2018 – Thursday

Wyndham Hotel – Ankara

0

0.2

0.4

0.6

0.8

1

0 0.5 1 1.5 2 2.5 3 3.5 4 4.5

Period (s)

Page 10: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

SeismicSeismic isolationisolation systemsystem

• max. base shear at DBE(475 years return period earthquake): 11% W

• max. base shear at MCE

Design Design requirementsrequirements

Seismic Base Isolation Applications within the Scope of New Codes

Workshop

3 May 2018 – Thursday

Wyndham Hotel – Ankara

• max. base shear at MCE(2475 years return period earthquake): 18% W

• response modification factor 1.0for all the earthquake levels

• max. displacement capacity 450 mm (at MCE)

Page 11: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

Seismic isolation systemSeismic isolation systemCharacteristics of the selected isolatorsCharacteristics of the selected isolators

• 3 types of pendulum isolators

• R=4.5 m

• two types of friction material(M and L)

• average friction coefficient6.2 %

Page 12: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

Seismic isolation systemSeismic isolation systemCharacteristics of the selected isolatorsCharacteristics of the selected isolators

Isolator Type Isolator mark

Max vertical

load at ULS

seismic

Max vertical

load at ULS

static

Nominal

coefficient of

dynamic

friction at NEd

Nos.

NEd [kN] Fzd [kN]

1 FIP-D M 1150/900 (4500) 3100 4000 5.5% 32

Seismic Base Isolation Applications within the Scope

of New Codes Workshop

3 May 2018 – Thursday

Wyndham Hotel – Ankara

2 FIP-D M 960/900 (4500) 2110 3000 5.5% 64

3 FIP-D L 530/900 (4500) 1840 2750 2.5% 25

Maximum displacement capacity (dEd): ±450 mm

Equivalent radius of curvature (Req): 4500 mm

Maximum rotation combined with maximum displacement (α): ±0.005 rad

Page 13: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

SimplifiedSimplified modellingmodelling

• Preliminary analyseson a simplified 3 masses modelto design the seismic isolationsystem

• Non-linear time history analyseswith 3 couples of ground motion recordswith 3 couples of ground motion records

Page 14: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

NonNon--linear time history analyseslinear time history analysesInput: Input: selectedselected Ground Motion Ground Motion RecordsRecords

� ERZINCAN1992

� KOCAELI1999

� DUZCE1999

Page 15: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

NonNon--linear time history analyseslinear time history analysesInput:check of spectrum compatibilityInput:check of spectrum compatibility

2.5

3

Sa (g

)

MCE Site Specific RS MCE Erzincan SRSS RS MCE Kocaeli SRSS RSMCE Duzce SRSS RS DBE Site Specific RS DBE Erzincan SRSS RSDBE Kocaeli SRSS RS DBE Duzce SRSS RS

0

0.5

1

1.5

2

2.5

0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6

Period (s)

Page 16: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

NonNon--linear time history analyseslinear time history analysesResults: base shearResults: base shear

Kocaeli 1999 gives the most severe response, well within the required limits:

Erzincan

MCE DBE

The required limitswere:11% at DBE

0% 2% 4% 6% 8% 10% 12% 14%

Duzce

Kocaeli

Base Shear / Total Weight (%)

11% at DBE18% at MCE

Page 17: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

NonNon--linear time history analyseslinear time history analysesResults: displacementResults: displacement

The requiredlimit was:450 mm at MCE

Erzincan

MCE DBE

0 50 100 150 200 250 300 350 400 450

Duzce

Kocaeli

Displacement (mm)

Page 18: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

NonNon--linear time history analyseslinear time history analysesResults (Kocaeli 1999 scaled at MCE)Results (Kocaeli 1999 scaled at MCE)

1

3

5

Acc

eler

atio

n (m

/s2 )

Ground Motion Impulsive Mass Convective Mass

-5

-3

-1

1

0.0 2.5 5.0 7.5 10.0 12.5 15.0 17.5 20.0 22.5 25.0

Acc

eler

atio

n (m

/s

Time (s)

The peak accerelation of the impulsive mass is 1.57 m/s2, i.e. 1/3 of the PGA

Page 19: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

Tests on isolatorsTests on isolators

• according to European Standard EN 15129+ additional test

at FIP Industriale’s Dynamic Test at FIP Industriale’s Dynamic Test FacilityFacility

Page 20: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

FIP Dynamic Test FacilityFIP Dynamic Test FacilityIsolators Test System Isolators Test System -- Main FeaturesMain Features

Dynamic Vertical Load: 200kN÷20000kN

Maximum Static Vertical Load: 30000kN

Dynamic Horizontal Load: 3000kN

Seismic Base Isolation Applications within the Scope of New Codes

Workshop

3 May 2018 – Thursday

Wyndham Hotel – Ankara

Dynamic Horizontal Displacement: ±500mm

Horizontal Velocity Actuator: ±1570mm/s

Dynamic Vertical Displacement: 0÷65mm

Static Vertical Displacement: 0÷700mm

Page 21: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

Isolators Test System

Max Vertical Load: 30000kN

Total V. Stroke: 700mm

Horizontal Load: 3000kN

Stroke: ±500mm

Seismic Base Isolation Applications within the Scope of New Codes

Workshop

3 May 2018 – Thursday

Wyndham Hotel – AnkaraFIP Dynamic Test FIP Dynamic Test

FacilityFacility

Automatic Sample Loading

System

Page 22: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

Tests on isolatorsTests on isolators

• FIP-D M 1150/900(4500)vertical load 2210 kN

atat FIP FIP Industriale’sIndustriale’s LaboratoryLaboratory --TypeType TestsTests

• FIP-D L 530/900(4500)vertical load 1503 kN

3 fully reversed cycles, sinusoidal input,displacement ± 450 mm, peak velocity 664 mm/s

Page 23: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

TestsTests on on isolatorsisolatorsatat FIP FIP Industriale’sIndustriale’s LaboratoryLaboratory ––TypeType TestsTests• FIP-D M 960/900(4500)

displacement ± 359 mm, peak velocity 530 mm/s

Page 24: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

TestsTests on on isolatorsisolatorsatat FIP FIP Industriale’sIndustriale’s Laboratory Laboratory -- Type Type TestsTests

Friction Vs. Vertical Friction Vs. Vertical LoadLoadD3 D3 -- E1 E1 -- E2 TestsE2 TestsD3 D3 -- E1 E1 -- E2 TestsE2 TestsEN15129:2009EN15129:2009

Page 25: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

TestsTests on on isolatorsisolatorsatat FIP FIP Industriale’sIndustriale’s LaboratoryLaboratory ––TypeType TestsTests

FIP-D L 530/900(4500) – 450mm_664mm/s E1-FIP-DL530.mp4

FIP-D L 1150/900(4500)-450mm_664mm/sD3-FIP-DM1150.mp4

Page 26: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

TestsTests on on isolatorsisolatorsatat FIP FIP Industriale’sIndustriale’s Laboratory Laboratory --Time Time HistoryHistory TestsTests

Page 27: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

TestsTests on on isolatorsisolatorsatat FIP FIP Industriale’sIndustriale’s Laboratory Laboratory --Time Time HistoryHistory TestsTests

Page 28: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

TestsTests on on isolatorsisolatorsatat FIP FIP Industriale’sIndustriale’s Laboratory Laboratory --Time Time HistoryHistory TestsTests

Page 29: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

Tests on isolatorsTests on isolatorsatat FIP FIP Industriale’sIndustriale’s LaboratoryLaboratory ––Time Time HistoryHistory TestsTests

MAH00925.MP4MAH00925.MP4MAH00926.MP4MAH00926.MP4

Page 30: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

InstallationInstallationSeismic Base Isolation Applications within the Scope of New Codes

Workshop

3 May 2018 – Thursday

Wyndham Hotel – Ankara

a pendulum isolator (FIP-D series) as installed

Page 31: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

Dampers Test SystemDampers Test SystemFIP Dynamic Test FacilityFIP Dynamic Test Facility

Seismic Base Isolation Applications within the Scope of New Codes

Workshop

3 May 2018 – Thursday

Wyndham Hotel – Ankara

V. Damper OT(P)500/4000

Design Load: 5000kN

Test Stroke: ±200mm

Frequency: 0.4Hz

Test Velocity: 500mm/s

Izmit Bay Bridge, Turkey Izmit Bay Bridge, Turkey OTP.mp4OTP.mp4

Page 32: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

• Seismic isolation is an effective solution for the protection of new and existing structures (Buildings, bridges, industrial plants, etc.)

• seismic isolation with pendulum isolators (double concave curved surface sliders) guarantees the possibility of

ConclusionsConclusionsSeismic Base Isolation Applications within the Scope of New Codes

Workshop

3 May 2018 – Thursday

Wyndham Hotel – Ankara

curved surface sliders) guarantees the possibility of reusing the existing tank substructures without reducingthe tank capacity

• the nonlinear time history analyses results show that the acceleration on the impulsive mass is less than 1/3 of PGA

• the results of the dynamic tests carried out on the isolatorsconfirm that their behaviour corresponds to the theoreticalone

Page 33: Seismic Base Isolation Applications within the Scope of New Codes Workshop 3 … · 2018. 5. 28. · SEISMIC ISOLATION 2015 Kahramanmaras Elbistan Hospital, Turkey HIGHLIGHTS Seismic

Thanks for Your kind attention .