    CE 197 Seismic Loading Example

    A 3-storey reinforced concrete hospital is to be built 10 km from anearthquake fault in Metro Manila. The interstory height is 3 m. The

    dead load on each floor is 400 kN. Determine the load distribution

    on the structure.

  • 7/25/2019 Seismic Loading Example

    2/3

    2 of 3

    For Zone 4: >0.8

    =

    0.8(1.2)(0.4)(1.5)

    8.5

    V > 0.0678W