seleccion de valvulas as de presion de angulo
TRANSCRIPT
-
8/6/2019 Seleccion de Valvulas as de Presion de Angulo
1/9
Fire Valve sizing
For all ZW4000 series valves, hose or sprinklerEnter the data in the three green boxes. Click tabs below for other models.
Outlet pressures appear below for each of the bonnet choices.
Entering the desired outlet pressure is optional,
but helps find the closest setting Desired
Static Residual Flow Residual
Inlet (psi) Inlet (psi) (gpm) Outlet
210 200 150
UL rated inlet Models ZW4000, ZW4000G, ZW4004, ZW4004G
pressure for each Angle Body Static Residual Difference
letter setting: Bonnet Type Outlet Outlet to desired400 psi N 78 62 62
400 O 85 66 66
360 P 96 78 78
310 Q 110 89 89
290 R 122 101 101
250 S 138 114 114
225 T 155 131 131
200 U 165 150 150
Grooved Models ZW4000ILG, ZW4004ILG
Globe Body Static Residual Difference
Bonnet Type Outlet Outlet to desired
N 78 67 67
O 85 69 69
P 96 82 82
Q 110 92 92
R 122 101 101
S 138 114 114
T 155 133 133
U 165 149 149
-
8/6/2019 Seleccion de Valvulas as de Presion de Angulo
2/9
Fire Valve sizing
For all 1-1/2" ZW4100 series valves, hose or sprinklerEnter the data in the three green boxes.
Outlet pressures appear below for each of the bonnet choices.
Entering the desired outlet pressure is optional,
but helps find the closest setting Desired
Static Residual Flow Residual
Inlet (psi) Inlet (psi) (gpm) Outlet
UL rated inlet Models ZW4100, ZW4100G, ZW4104, ZW4104G
pressure for each Angle Body Static Residual Differenceletter setting: Bonnet Type Outlet Outlet to desired
400 psi J 0 0 0
400 K 0 0 0
400 L 0 0 0
360 M 0 0 0
325 N 0 0 0
290 O 0 0 0
240 P 0 0 0
200 Q 0 0 0
All outlet pressures are +/- 10%.
Static and residual outlet must be below 175 psi for UL approval
UL rated pressure keeps the valve below 175 psi for all flowing conditions.
If pressure reads zero, that bonnet is not available for that pressure or flow.
8/6/2008
-
8/6/2019 Seleccion de Valvulas as de Presion de Angulo
3/9
Fire Valve sizing
For all Z3000 series valves, hose or sprinklerEnter the data in the three green boxes. Click tabs below for other models.Outlet pressures appear below for each setting choice.
Entering the desired outlet pressure is optional but helps find the closest setting
Desired
Static Residual Flow Residual
Inlet (psi) Inlet (psi) (gpm) Outlet
Models Z3000, 3004,3005
Angle
BodiesStatic Residual Difference
Setting Outlet Outlet to desired
A 0 0 0
B 0 0 0
C 0 0 0
D 0 0 0
E 0 0 0
F 0 0 0
G 0 0 0
H 0 0 0
I 0 0 0
J 0 0 0
K 0 0 0L 0 0 0
Models Z3000ILG, 3004ILG
Globe Grooved
Bodies Static Residual DifferenceSetting Outlet Outlet to desired
A 0 0 0
B 0 0 0
C 0 0 0
D 0 0 0
E 0 0 0
F 0 0 0
G 0 0 0H 0 0 0
I 0 0 0
J 0 0 0
K 0 0 0
L 0 0 0
All outlet pressures are +/- 10%.
Static outlet must be below 175 psi for UL listing.
-
8/6/2019 Seleccion de Valvulas as de Presion de Angulo
4/9
If outlet pressure reads zero, that setting is not available for that pressure or flo
5/7/2010
-
8/6/2019 Seleccion de Valvulas as de Presion de Angulo
5/9
Fire Valve sizing
For all Z2100 series valvesEnter the data in the three green boxes.Outlet pressures appear below for each setting choice.
Entering the desired outlet pressure is optional but helps find the closest setting.
Desired
Static Residual Flow Residual
Inlet (psi) Inlet (psi) (gpm) Outlet
Models Z2100, Z2105
Angle Body Static Residual DifferenceSetting Outlet Outlet to desired
A 0 0 0
B 0 0 0
C 0 0 0
D 0 0 0
E 0 0 0
F 0 0 0
G 0 0 0
All outlet pressures are +/- 10%.
Static outlet must be below 175 psi.
If outlet pressure reads zero, that setting is not available for that pressure or flow.
5/2/2011
-
8/6/2019 Seleccion de Valvulas as de Presion de Angulo
6/9
ZW4000 Fire Valve Part Number Assistant
Check off the box in each group that matches the choice you want.
If a choice is blank, this is standard and you add nothing to the part number. If there are letters after the checkbox,
then you add those letters to the part number in that order from left to right.
A bonnet setting has to be part of the part number since the ZW4000 series valves are factory set and not field adjustable.
Example
Sprinkler Floor Control Valve (Factory Set)
Angle Body Threaded Ends Rough Bonnet Setting TypeX Monitor Switch No Handwheel Chrome -N -O -P
ZW4004 Globe Body Grooved Ends Adapter Bracket Capped Bonnet Plated
X IL G X MSA CAP CH -Q -R -S
X -T -U
2-1/2" Hose Valve (Factory Set)Angle Body Threaded Inlet 2-" National Hose Thread Rough Bonnet Setting Type
Chrome -N -O -P
ZW4000 Globe Body Grooved Inlet 3" Hose Thread w/Cap and Chain Plated
IL G SF CC CH -Q -R -SSpecial Thread
ST -T -U
2-1/2" Sprinkler Floor Control Valve (Factory Set)Angle Body Threaded Ends Supervisory Switch Rough Bonnet Setting Type
SS No Handwheel Chrome -N -O -P
ZW4004 Globe Body Grooved Ends Monitor Switch Capped Bonnet Plated
IL G Adapter Bracket CAP CH -Q -R -S
MSA
Specify if the body should be tapped and plugged for gauges. -T -U
Qty Part number Notes
The flow curves must be used by the system designer to select the correct bonnet setting.
In this example the part number would be ZW4004ILMSA-T
-
8/6/2019 Seleccion de Valvulas as de Presion de Angulo
7/9
Z3000 Fire Valve Part Number Assistant
Check off the box in each group that matches the choice you want.
If a choice is blank, this is standard and you add nothing to the part number. If there are letters after the checkbox,
then you add those letters to the part number in that order from left to right.
Example
2-1/2" Sprinkler Floor Control Valve (Adjustable)
Angle Body Threaded Ends Supervisory Switch RoughX SS No Handwheel Chrome
Z3004 Globe Body Grooved Ends Monitor Switch Capped Bonnet Plated
X IL X G Adapter Bracket CAP CH
MSA
2-1/2" Hose Valve (Adjustable)Angle Body Threaded Inlet 2-" National Hose Thread Rough
Chrome
Z3000 Globe Body Grooved Inlet 3" Hose Thread w/Cap and Chain Plated
IL G SF C/C CHSpecial Thread
ST
Hose Rack Valve Rough
Angle Body Chrome
NPT Threaded Outlet Plated
Z3005 Globe Body CH
IL
2-1/2" Sprinkler Floor Control Valve (Adjustable)
Angle Body Threaded Ends Supervisory Switch RoughSS No Handwheel Chrome
Z3004 Globe Body Grooved Ends Monitor Switch Capped Bonnet Plated
IL G Adapter Bracket CAP CH
MSA
Specify if the body should be tapped and plugged for gauges.
Qty Part number Notes
The flow curves must be used by the system designer to verify the valve will function properly.
In this example the part number would be Z3000ILGSS
-
8/6/2019 Seleccion de Valvulas as de Presion de Angulo
8/9
ZW4100 Fire Valve Part Number Assistant
Check off the box in each group that matches the choice you want.
If a choice is blank, this is standard and you add nothing to the part number. If there are letters after the checkbox,
then you add those letters to the part number in that order from left to right.
A bonnet setting has to be part of the part number since the ZW4100 series valves are factory set and not field adjustable.
Example
1-1/2" Sprinkler Floor Control Valve or Hose Rack Valve (Factory Set)
Angle Body Threaded Ends Supervisory Switch Rough Bonnet Setting TypeX X SS No Handwheel Chrome -J -K -L
ZW4104 Grooved Ends Monitor Switch Capped Bonnet Plated
G Adapter Bracket CAP CH X -M -N -O
X MSA
-P -Q
1-1/2" Hose Valve (Factory Set)Angle Body Threaded Inlet 1-" National Hose thread Rough Bonnet Setting Type
Chrome -J -K -L
ZW4100 Grooved Inlet Special Thread w/Cap and Chain Plated
G ST CC CH -M -N -O
-P -Q
1-1/2" Sprinkler Floor Control Valve or Hose Rack Valve (Factory Set)Angle Body Threaded Ends Supervisory Switch Rough Bonnet Setting Type
SS No Handwheel Chrome -J -K -L
ZW4104 Grooved Ends Monitor Switch Capped Bonnet Plated
G Adapter Bracket CAP CH -M -N -O
MSA
-P -Q
Qty Part number Notes
The flow curves must be used by the system designer to select the correct bonnet setting.
In this example the part number would be ZW4104MSA-M
-
8/6/2019 Seleccion de Valvulas as de Presion de Angulo
9/9
Z2100 Fire Valve Part Number Assistant
Check off the box in each group that matches the choice you want.
If a choice is blank, this is standard and you add nothing to the part number. If there are letters after the checkbox,
then you add those letters to the part number in that order from left to right.
Example
1-1/2" Hose Valve (Adjustable)
1-" National Hose ThreadAll X
Z2100 Angle Body Special Thread w/Cap and Chain Rough
NPT Threaded ST X C/C Chrome
Inlet Plated
NPT Threaded Outlet X CH
Z2105 Hose Rack Valve
1-1/2" Hose Valve (Adjustable)
1-" National Hose ThreadAll
Z2100 Angle Body Special Thread w/Cap and Chain Rough
NPT Threaded ST C/C Chrome
Inlet Plated
NPT Threaded Outlet CH
Z2105 Hose Rack Valve
Qty Part number Notes
The flow curves must be used by the system designer to verify the valve will function properly.
In this example the part number would be Z2100C/CCH