Introduction

Adding Visualization to Your Control System

As a machine builder or end user, you design control solutions with an eye toward improving safety, higher levels of performance and efficiency, and better integration with the rest of the manufacturing operation. To achieve these goals, you need a scalable, modular control system that offers safety, throughput and information management capabilities to match each application’s requirements.

The Rockwell Automation® Integrated Architecture™ system is unique in that it offers scalable, integrated safety, motion control, and visualization capabilities that are ideal for machine builders and end users who want a single control and development environment, regardless of the application size or complexity.

The visualization products comprise a suite of scalable HMI software and operator interface hardware that provide plant floor machine operators, supervisors, engineers, and business managers a window to critical data, and production and process information. And all this can be done from the plant floor or remotely from a web browser.

Whether it’s a machine-level or site-level HMI, a Windows CE platform, a smaller component HMI, or an industrial computer, Rockwell Automation has a portfolio of visualization solutions to match your system requirements.

PanelView™ Plus terminals, FactoryTalk® View Machine Edition, and FactoryTalk View Site Edition provide premier integration in a number of ways.

• Reduce programming time with Logix native addressing and the ability to browse directly to Logix tags without creating a separate database.

• Simplifies interaction of all networks with support for all Core Integrated Architecture CIP networks including EtherNet/IP, ControlNet, and numerous other drivers.

• Simplifies development time with pre-engineered, pre-tested faceplates for specific motion, drives, and process applications.

Page 3: Selection Guide - kvc.com.my · PDF file• ControlLogix® or CompactLogix ... • With or without battery backup Select a PanelView Plus ... • Recipe upload/download • Trending

4 Rockwell Automation Publication VIEW-SG001G-EN-P - August 2011

Visualization Platforms

Visualization Platforms

PanelView Plus Family PanelView Component Family

page 26page 7

Select an Operator Interface

Do you need:• Machine-level HMI with

FactoryTalk View ME?• Dedicated platform?• Component level HMI?

Yes

No

Machine-level HMI

Do you need a machine-level HMI?• Small to large applications• FactoryTalk View ME software • ControlLogix® or CompactLogix™

controllers

Do you need a component-level HMI?:• Small applications• Web-based software• MicroLogix™, SLC™, Micro800™

controllers or device

Select a PanelView ComponentConsider:• Display size• Monochrome or color display• Operator input• Communication• With or without battery backup

Select a PanelView PlusConsider:• Windows CE desktop access• Remote access and file viewers• Display size• Operator input• Power requirements• Communication• Environmental requirements

Select• Accessories• Cables

Select• FactoryTalk View ME software• Optional communication module• Accessories• Cables

For technical specifications, certifications, and environmental specifications on the PanelView Plus terminals, refer to the PanelView Plus Specifications Technical Data, publication 2711P-TD005

For technical specifications, certifications, and environmental specifications on the PanelView Component terminals, refer to the PanelView Component Specifications Technical Data, publication 2711C-TD001

Page 4: Selection Guide - kvc.com.my · PDF file• ControlLogix® or CompactLogix ... • With or without battery backup Select a PanelView Plus ... • Recipe upload/download • Trending

Rockwell Automation Publication VIEW-SG001G-EN-P - August 2011 5

Visualization Platforms

Industrial MonitorsIntegrated Display Computers Non-display Computers

Select• Accessories

Performance page 45

Standard page 45

Non-displaypage 40

Compact Non-displaypage 43

Integrated Displaypage 32

Display with Keypadpage 37

Select an Industrial Computer

Do you need:• Site-level HMI with

FactoryTalk View SE?• Open platform?• Processing power of an

industrial computer?

Yes

Hazardous Location Computers

Select• FactoryTalk View software if needed• Accessories

Hazardous Locationpage 39

Select• FactoryTalk View software if needed• Accessories

Site-level HMI

HMI Servers

FactoryTalkData Server

Data Servers

Do you need:• Integrated display?• Integrated display with keypad?• Rockwell Software® and

third-party software?

• Extended temperature range?• Class 1 Div 2 and ATEX certification?• Rockwell Software and

third-party software?

Do you need:• Computer without a display?• Compact form factor option?• Rockwell Software and

third-party software?

Do you need:• Monitor only?• Class 1 Div 2 certification?• Standard industrial environment?

Select a Display ComputerConsider:• Display size and input method• Resistive touch screen• Solid-state or hard-disk drive• Standard or performance options• Operating system• Power requirements• Bezel type

Select Hazardous Location Computer

Consider:• Computer with display• Computer without display

Select a Non-display ComputerConsider:• Environmental requirements• Compact form factor• Solid-state or hard-disk drive• Power requirements• Operating system• Mounting method• Standard or performance options

Select a MonitorConsider:• Environment• Display size • Touch screen option• Bezel type• Mounting method

Select• FactoryTalk View Software if needed• Accessories

For technical specifications, certifications, and environmental specifications on the industrial computers and monitors, refer to the Industrial Computers and Monitors Specifications Technical Data, publication IC-TD001.

Do you need:

Page 5: Selection Guide - kvc.com.my · PDF file• ControlLogix® or CompactLogix ... • With or without battery backup Select a PanelView Plus ... • Recipe upload/download • Trending

Rockwell Automation Publication VIEW-SG001G-EN-P - August 2011 6

HMI Terminal Comparison

HMI Terminal Comparison This table provides a quick glance at comparisons between the different HMI terminal platforms.

Table 1 - HMI Terminal Comparison

Characteristic 2711P PanelView Plus 6700, 1000, 1250, 1500

2711P PanelView Plus 400, 600

2711P PanelView Plus Compact 400, 600, 1000

2711C PanelView ComponentC200, C300, C600, C1000

Display 700: 6.5 in. color TFT1000: 10.4 inch color TFT1250: 12.1 in. color TFT1500: 15 in. color TFT

400: 3.5 in. color TFT400: 3.8 in. grayscale600: 5.5 in. color TFT600: 5.5 in. grayscale TFT

400: 3.5 in. color TFT400: 3.8 in. grayscale600: 5.5 in. color TFT100: 10.4 in. color TFT

C200: 2 in. monoC300: 3 in. monoC600: 5.7 in. color TFT or monoC1000: 10.4 in. color TFT

Input type All models: keypadAll models: touch screenAll models: key/touch

400: key/touch (3.5 in.)400: keypad (3.8 in.)600: touch screen

400: key/touch (3.5 in.)400: keypad (3.8 in.)600/1000: touch screen

C200: 4-keys C200: 10-keys+numeric C300: 10-keys/+numeric C600/C1000: touch screen

Built-in communication ports

RS-232EtherNet2 USB host and 1 USB device

RS-232EtherNet1 USB

RS-232EtherNet1 USB: 400/6002 USB: 1000

RS-232RS-422/RS-4851 USB host and 1 USB deviceEtherNet: C600/C1000C only

Add-on communication module

DH+DH-485ControlNet

DH+DH-485ControlNet

None None

Serial communication RS-232: DF1 or DH-485 RS-232: DF1 or DH-485 RS-232: DF1 or DH-485 RS-232: DF1, DH-485, multivendor options, RS-485

Programming software FactoryTalk View ME 6.0 or laterViewPoint web server 1.2 or later

FactoryTalk View ME 5.1 or earlier FactoryTalk View ME 5.1 or later DesignStation 2.0 or laterWeb-enabled softwareresident in terminalPC-based emulator available

Operating system Windows CE 6.0 operating systemsupports this features:• FTP Server• VNC client/server• PDF reader• Active X controls• Third-party device support

Additional functionality is available by ordering terminals with optional extended features(1)

• Internet Explorer web browser• Remote desktop connection• Media player• File viewers for Microsoft Office

Word, PowerPoint, and Excel• WordPad text editor

None None None

Open or closed system Open or closed desktop Closed Closed Closed

Memory 512 MB nonvolatile flash/512 MB RAM 64 MB nonvolatile flash/64 MB RAM 64 MB nonvolatile flash/64 MB RAM 64 MB nonvolatile flash/64 MB RAM

External storage Secure Digital (SD) cardUSB flash drives

CompactFlash CompactFlash USB flash: C200/C300USB flash/SD card: C600/C1000

Power AC or DC AC or DC DC DC

Preferred controller ControlLogix CompactLogix CompactLogix MicroLogix, SLC, PowerFlex 4 drive, Micro800

Capabilities • High memory capacity• desktop access enabled or disabled• backup and restore function• Multi-network/multivendor

connectivity• Alarm messages (email alarms)• Recipes• Trending • Data logging

• Multi-network/multivendor connectivity

• Alarm messages• Recipes• Trending • Data logging

• Single controller• 25 displays• 200 alarm messages• Recipes• Trending• Data logging

• Single device• <20 displays• <100 alarm messages• Recipe upload/download• Trending • Data logging

Key differentiators • Windows CE desktop access• Larger application size• Pre-engineered faceplates for

motion, process, and drives• Native Logix addressing• Direct referencing of Logix tags• Modular hardware simplifies

system integration and updates• FactoryTalk View Machine Edition

comes installed and activated

• Pre-engineered faceplates for motion, process, and drives

• Native Logix addressing• Direct referencing of Logix tags• Modular hardware simplifies

system integration and updates• FactoryTalk View Machine Edition

comes installed and activated

• Single controller for midrange applications

• Pre-engineered faceplates for motion, process, and drives

• Native Logix addressing• Direct referencing of Logix tags• FactoryTalk View Machine Edition

comes installed and activated

• Component-level device for small applications

• No programming software required

(1) Extended features are available by ordering catalog numbers ending in 9, for example, 2711P-Kxxxx9, 2711P-Bxxxx9, 2711P-Txxxx9.

Page 6: Selection Guide - kvc.com.my · PDF file• ControlLogix® or CompactLogix ... • With or without battery backup Select a PanelView Plus ... • Recipe upload/download • Trending

Rockwell Automation Publication VIEW-SG001G-EN-P - August 2011 7

PanelView Plus Terminals

PanelView Plus Terminals PanelView Plus devices give operators a clear view into monitoring and controlling applications. With FactoryTalk View Machine Edition already installed and activated, development time is reduced. The PanelView Plus family of products provides a broad range of rugged terminals that offer the following:

• Premier integration with the Integrated Architecture platform• Real-time monitoring of a terminal’s displays from a web browser• Common development software• Scalable 4 to 15-inch displays with a touch screen, keypad, or both

Figure 1 - Selecting a PanelView Plus Platform

• Internet Explorer• Remote desktop connection• Microsoft Office file viewers• WordPad text editor• Media player (MPEG)

PanelView Plus 6 Terminals with extended features

See page 10

PanelView Plus 400 and 600 Terminals

See page 16

PanelView Plus Compact Terminals

See page 19

• > 6-inch display• Access to CE desktop• Web browser/file viewers• Remote access• PDF reader• Multiple apps

Do you need any of these?

Yes

No

Yes

• Multiple controllers?

• > 25 displays

• > 200 alarms

• < 6-inch display?

Yes

No

For complete technical specifications, certifications, and environmental specifications on the PanelView Plus terminals, refer to the PanelView Plus Specifications Technical Data, publication 2711P-TD005

Do you need any of these?

No

Do you need any of these?

Cat. No. 2711P-xxxx9 or 2711P-RP9x

Cat. No. 2711P-xxxx8 or 2711P-RP8x

PanelView Plus 6 Terminals without extended features

See page 10

Page 7: Selection Guide - kvc.com.my · PDF file• ControlLogix® or CompactLogix ... • With or without battery backup Select a PanelView Plus ... • Recipe upload/download • Trending

8 Rockwell Automation Publication VIEW-SG001G-EN-P - August 2011

PanelView Plus Terminals

Typical Configurations Figure 2 shows a configuration where a PanelView Plus terminal is used with a Logix controller in standalone or machine-level mode using serial connectivity.

Figure 2 - Standalone Machine

In Figure 3, a PanelView Plus Compact terminal and the 1769-L3x CompactLogix system provide an integrated solution for midsize applications. Typically, these applications are machine-level control applications that require smaller I/O quantities and more communication capabilities than serial connectivity.

Figure 3 - Midsize Application

To Business Systems

Page 8: Selection Guide - kvc.com.my · PDF file• ControlLogix® or CompactLogix ... • With or without battery backup Select a PanelView Plus ... • Recipe upload/download • Trending

Rockwell Automation Publication VIEW-SG001G-EN-P - August 2011 9

PanelView Plus Terminals

In Figure 4, a PanelView Plus 6 terminal communicates with all devices by using EtherNet/IP communication. A Logix controller along with a Kinetix® 300 servo drive offer a scalable power platform cost-sensitive applications, such as simple packaging machinery, indexing tables, automatic assembly equipment, tool changing machinery, and feed and withdrawal equipment.

Figure 4 - Indexing Motion

To Business Systems

Page 9: Selection Guide - kvc.com.my · PDF file• ControlLogix® or CompactLogix ... • With or without battery backup Select a PanelView Plus ... • Recipe upload/download • Trending

26 Rockwell Automation Publication VIEW-SG001G-EN-P - August 2011

PanelView Component Terminals

PanelView Component Terminals

This component level operator interface provides a control and visualization solution for low-level applications by using serial or Ethernet communication. Preferred controllers are the Micrologix, SLC, and Micro800™ controllers plus you can connect directly to component devices such as the PowerFlex 4® drives.

This platform offers a full line of 2- to 10-inch displays with touch or function key input. Plus, the integrated mounting clips on the terminal simplifies panel installation and maintenance. Other key features include the following:

• Design software resident in the terminal means no additional software to install on your computer.

• Secured programming access protects applications from unauthorized modifications.

• Unicode language switching in languages such as Russian, Greek, Chinese, Japanese, and Korean.

• Alarm messages with embedded variables and history. • Recipe capability lets you upload and download groups of data or

parameter settings.

For complete technical specifications, certifications, and environmental specifications on the PanelView Component terminals, refer to the PanelView Component Specifications Technical Data, publication 2711C-TD001.

Software

The built-in programming software is accessed from a web browser over a USB or Ethernet connection. This means you can design your application and adjust terminal settings while viewing the results directly on the connected terminal. For those times when a PanelView Component terminal is not available, you can still create an application by using the free emulator or DesignStation, version 2.0 or later.

Typical Configuration

A PanelView Component terminal is typically connected to a MicroLogix controller or another component, such as a PowerFlex 4 drive, over an Ethernet or serial connection.

Ethernet or Serial Connection

Page 10: Selection Guide - kvc.com.my · PDF file• ControlLogix® or CompactLogix ... • With or without battery backup Select a PanelView Plus ... • Recipe upload/download • Trending

Rockwell Automation Publication VIEW-SG001G-EN-P - August 2011 27

PanelView Component Terminals

Product Selections

Product Accessories

Tables 45…48 list accessories for the PanelView Component terminals.

BulletinNumber Input Type Display Size Display Type

| | |

2711C- F = Function keys 2 = 2 in. C = Color

K= Keypad and function keys 3 = 3 in. M = Grayscale

T = Touch screen 6 = 6 in. T = TFT Color

10 = 10 in.

Table 44 - PanelView Component Terminals

Cat. NoDisplay

Input TypeCommunication

Power Size Type Serial(1) Ethernet

C200 Model

2711C-F2M2-in. Monochrome STN display

4 function keys • – 24V DC

2711C-K2M 10 function keys and numeric keypad • – 24V DC

C300 Model

2711C-T3M3-in. Monochrome FSTN display

Touch screen • – 24V DC

2711C-K3M 10 function keys and numeric keypad • – 24V DC

C600 Model

2711C-T6M 6 in. Monochrome FSTN display Touch screen • • 24V DC

2711C-T6T Color TFT display Touch screen • • 24V DC

C1000 Model

2711C-T10C 10 in. Color TFT display Touch screen • • 24V DC

(1) Serial refers to RS-232 (DF1), RS-232 (DH-485), RS-485 communication.

Table 45 - Antiglare Overlays

Cat. No.(1)

(1) Three overlays are shipped with each catalog number.

PanelView Component Model

Input Type

Function Key Numeric Keypad Touch

2711C-RG2F C200 •

C300 •

2711C-RG2K C200 •

C300 •

2711C-RG6T C600 •

2711C-RG10T C1000 •

Page 11: Selection Guide - kvc.com.my · PDF file• ControlLogix® or CompactLogix ... • With or without battery backup Select a PanelView Plus ... • Recipe upload/download • Trending

28 Rockwell Automation Publication VIEW-SG001G-EN-P - August 2011

PanelView Component Terminals

Communication Cables

This table summarizes cables used by the PanelView Component terminals.

Table 46 - Memory Cards

Cat. No. Description

2711C-RCSD USB to Secure Digital (SD) adapter for SD card

Table 47 - Power Terminal Blocks

Cat. No. Description Quantity

2711C-RJ422 RS-422/RS-485 connector with resistor 10

2711-TBDC DC power terminal block 10

Table 48 - Power Supply

Cat. No. Description Quantity

2711P-RSACDIN DIN-rail mount AC-to-DC power supply, 85…265V AC, 47…63 Hz 1

Table 49 - Cables and Adapters

Cat. No. Description Connectors Length

2711C-CBL-UU02 USB host to USB device programming cable. 2 m (6.5 ft)

2711C-CBL-AB03 RS-485 (5-pin) to RJ45 operating/programming cable for connecting PanelView Component terminals to SLC 5/01, 5/02, 5/03 controllers.

RS-485 (5-pin) to RJ45

1747-CP3 Operating/programming cable for connecting PanelView Component terminals to SLC and MicroLogix controllers.

9-pin D-shell to 9-pin D-shell null modem cable

3 m (10 ft)

1761-CBL-PM02 RS-232 operating/programming cable for connecting PanelView Component terminals to MicroLogix controllers.

9-pin D-shell to 8-pin mini DIN 2 m (6.5 ft)

2711-CBL-PM05 RS-232 operating/programming cable for connecting PanelView Component terminals to MicroLogix controllers. 9-pin D-shell to 8-pin mini DIN 5 m (16.4 ft)

2711-CBL-PM10 RS-232 operating/programming cable for connecting PanelView Component terminals to MicroLogix controllers. 9-pin D-shell to 8-pin mini DIN 10 m (32.7 ft)

2711P-CBL-EX04 Ethernet CAT5 crossover cable for use with PanelView Component C600 and C1000 terminals. RJ45 to RJ45 4.3 m (14 ft)

1761-NET-AIC AIC+ advanced interface converter, RS-232/RS-485. — —

Page 12: Selection Guide - kvc.com.my · PDF file• ControlLogix® or CompactLogix ... • With or without battery backup Select a PanelView Plus ... • Recipe upload/download • Trending

Rockwell Automation Publication VIEW-SG001G-EN-P - August 2011 29

PanelView Component Terminals

Tables 50…53 lists required cables for runtime communication between the PanelView Component terminals and controllers.

Table 50 - Runtime Communication Cables: PanelView Component Terminals to SLC Controllers

Protocol PanelView Component Comm Port

SLC-500, 5/01, 5/02CH1 RJ45 (DH-485)

SLC-5/03, 5/04, 5/05CH0 (9-pin RS-232)

(DF1 or DH-485)

SLC 5/03CH1 (RJ45)

(DH-485)SLC 5/04

CH1 (DH+)SLC 5/05

CH1 (ENET)

DF1 RS-232 (DF1) port (9-pin) — 1747-CP3 (3 m/10 ft) — — —

DH-485RS-232 (DH-485) port (9-pin)

Use AIC+ Module(1761-NET-AIC) to

connect to port 1 or 21747-CP3 (3 m/10 ft)

Use AIC+ Module(1761-NET-AIC) to

connect to port 1 or 2

— —

RS-485 (DH-485) port (5-pin) 2711C-CBL-AB03(1) — 2711C-CBL-AB03(1) — —

EtherNet/IP EtherNet/IP port —Use 1761-NET-ENI module

with Ethernet cable— —

1585J-M type cable or 2711P- CBL-EX04

(4 m/14 ft) (2)

(1) The AIC+ module is recommended for isolation purposes when the terminal and controller are not on the same power supply.(2) For a direct connection between the terminal and controller, use the 2711P-CBL-EX04 crossover cable.

Table 51 - Runtime Cables: PanelView Component Terminals to MicroLogix Controllers

Protocol PanelView Component Comm Port

MicroLogix 1400, 1500LRPCH1/CH2 (9-pin RS-232)

(DF1 or DH-485)

MicroLogix 1000, 1100, 1200, 1400, 1500LSPCH0 (8-pin Mini DIN)

(DF1 or DH-485)MicroLogix 1100, 1400

Ethernet

DF1 RS-232 (DF1) port (9-pin) 1747-CP3 (3 m/10 ft)1761-CBL-PM02 (2 m/6.5 ft)2711-CBL-PM05 (5 m/16 ft)

2711-CBL-PM10 (10 m/12 ft) (1)—

DH-485 RS-232 (DH-485) port (9-pin) 1747-CP3 (3 m/10 ft)1761-CBL-PM02 (2 m/6.5 ft)2711-CBL-PM05 (5 m/16 ft)

2711-CBL-PM10 (10 m/12 ft) (1)—

EtherNet/IP EtherNet/IP PortUse 1761-NET-ENI module

with Ethernet cable1585J-M type cable or

2711P- CBL-EX04 (4 m/14 ft) (2)

(1) The AIC+ module is recommended for isolation purposes when the terminal and controller are not on same power supply.(2) For a direct connection between the terminal and controller, use the 2711P-CBL-EX04 crossover cable.

Table 52 - Runtime Cables: PanelView Component Terminals to CompactLogix Controllers

Protocol PanelView Component Comm Port

CompactLogixCH0 (9-pin RS-232)

(DF1 or DH-485)

DF1 RS-232 (DF1) port (9-pin)2711-NC13 (5 m/16 ft)

2711-NC14 (10 m/32 ft)

DH-485 RS-232 (DH-485) port (9-pin)2711-NC13 (5 m/16 ft)

2711-NC14 (10 m/32 ft)

EtherNet/IP EtherNet/IP port 1585J-M type cable or 2711P- CBL-EX04 (4 m/14 ft) (1)

(1) For a direct connection between the terminal and controller, use the 2711P-CBL-EX04 crossover cable.

Table 53 - Runtime Cables: PanelView Component Terminals to Interface Modules

ProtocolPanelView Plus

Comm Port1761-NET-AICPort 1 (9-pin)

1761-NET-AICPort 2 (8-pin Mini DIN()

1761-NET-AICPort 3 (DH-485)

DF1 RS-232 port (9-pin) 1747-CP3 (3 m/10 ft)1761-CBL-PM02 (2 m/6.5 ft)2711-CBL-PM05 (5 m/16 ft)

2711-CBL-PM10 (10 m/12 ft) —

DH-485 RS-232 port (9-pin) 1747-CP3 (3 m/10 ft)1761-CBL-PM02 (2 m/6.5 ft)2711-CBL-PM05 (5 m/16 ft)

2711-CBL-PM10 (10 m/12 ft) —