selection of station insulators

Upload: dc12dc

Post on 02-Jun-2018

219 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/10/2019 Selection of Station Insulators

    1/7

  • 8/10/2019 Selection of Station Insulators

    2/7

    FARZANEHet al.: SELECTION OF STATION INSULATORS WITH RESPECT TO ICE AND SNOWPART I 265

    Fig. 1. Density function of melted-ice conductivity [15].

    be wettable. This also may present a criticalflashover conditionin cases of heavily polluted snow or pre-contaminated insulator

    surfaces.

    2) Amount and Distribution of Ice: The amount of ice has

    a significant influence onflashover performance [4], [28], [30],[31]. Normally, a thickness of 530 mm, measured on a standardrod [28], is recommended for ice testing. The thickness should

    be decided by utilities depending on their service experience in

    exposure [55] and desired reliability [28].

    The distribution of ice along the insulators is another impor-

    tant parameter. For typical precipitation intensities and duration,

    ice and icicles cover the windward side of the insulator and the

    opposite side is free of ice. The level of ice bridging between the

    sheds determines the size and number of air gaps where initial

    discharges and partial arcs are triggered. This level of bridging is

    mainly influenced by the electricfield distribution along the in-

    sulator, which in turn is governed by the level of applied voltage,the presence of grading rings and grading devices on apparatus

    insulators (e.g., capacitors), bus bars, support structures and in-

    sulator orientation.

    3) Electrical Conductivity of Water: Ions in cloud droplets,

    rain, and wet snow may stem from sea salt, nitrates, sulphates

    and various industrial pollutants [15].

    As concerns insulator icing tests, three types of conductivity

    can be identified: (i) applied water conductivity (also calledfreezing water conductivity), (ii) dripping water conductivity,

    and (iii) melted ice conductivity. The conductivity of applied

    wateris always measured and usually reported.However, it is the

    conductivity of the waterfilm on the ice surface, best correlatedwith dripping water conductivity that mainly determines theflashover voltage. This is similar to the insulator surface conduc-tivity in the caseofflashover mechanisms of polluted insulators.

    The Norwegian Power Grid Company (STATNETT) pro-

    vided information about the conductivity of 122 ice samples

    taken from service, between 1987 to 1995 [16]. The probability

    density function of the conductivity of these melted-ice samples

    is shown in Fig. 1.

    These samples, mostly of rime ice, were taken from racks and

    towers close to the ground, which thus corresponds to applied

    water conductivity. The samples are assumed to be more con-

    taminated than snow on the ground, because of the higher con-

    tent of rime. The results were statistically evaluated and it wasfound that a log-normal distribution, with mean value of 3.2 (av-

    Fig. 2. Relationship between ESDD and distance from seacoast.

    TABLE IPOLLUTIONLEVELS ANDRECOMMENDEDSPECIFIC LEAKAGE DISTANCE

    ACCORDING TOIEC 60815 AND ESTIMATEDESDD IN-SERVICE LEVELS

    erage conductivity 25.4 S/cm) and standard deviation of 0.8

    (6.4 S/cm) gave the bestfit. The log-normal distribution for

    conductivity can be approximated by (1), as follows:

    (1)

    B. Clean Ice Deposit on Contaminated Surfaces

    Fig. 2 shows monthly rates of increase of contamination

    levels as a function of distance from seacoast in Japan [61];

    superimposed are three increase rates in ESDD observed for

    urban, suburban, and rural areas in Ontario.

    IEC 60 815 [56], currently under revision, has defined fourpre-existing pollution levels and specific leakage distance re-

    quirements for insulators, as shown in Table I. As well, theIEEE TF has added a recommended range of pollution levels,

    expressed as ESDD values, to Table I.

    The pre-existing ESDD will dominate the electrical conduc-

    tivity of the ice for any (generally thin) layer of ice, freezing

    fog or drizzle. Only the surfaces in direct contact with ice ac-

    cretion, typically top surfaces and vertical portions of insulators,

    will contribute to the conductivity of ice. The contribution of the

    ESDD to the ice conductivity can be calculated using [57]

    ESDD Area

    Volume (2)

    Area is in cm , ESDD in g/cm , volume in ml, conductivityin S/cm.

  • 8/10/2019 Selection of Station Insulators

    3/7

    266 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 1, JANUARY 2005

    C. Combined Pollution: Ice and Snow on Contaminated

    Surface

    One of the most difficult winter conditions for insulators isassociated with build-up of contamination over a period of a

    month, as shown in Fig. 2, combined with a moderate amount

    of ice or wet-snow accretion. Accretion onto a pre-contami-

    nated surface will draw in the surface ions, enhancing or dom-inating the natural conductivity of the ice. Through the process

    of freeze-thaw partitioning, these ions will migrate to the ice

    surface, lower the surface impedance and reduce theflashovervoltage further as described in Part II of the paper.

    An estimate of the increase in ice conductivity is given by

    (2), using the ESDD on the top surface of the sheds, the surface

    area and volume of the ice cap. For complex situations, where

    different surfaces have different ESDD levels, it is suggested

    that the ice conductivity and weight be measured directly or

    inferred from the dripping water properties.

    D. Methods for Evaluating the Electrical Performance ofInsulators and Ranking Under Icing Conditions

    Laboratory test methods should simulate a wide range of ice

    accretion types and regimes. Two common accretion methods

    are (i) by freezing precipitation, where generally icicles are

    formed by run-off of supercooled water; and (ii) through con-

    solidation of snow or rime in melting conditions. In both cases,

    a waterfilm may appear during melting caused by a rise in airtemperature above 0 C or by solar input.

    It is generally agreed that the simultaneous presence of a

    highly conductive water film and initial air gaps are neededforflashover to occur [32]. Thus, for the evaluation tests, theexperimental procedure should reproduce these conditions

    as closely as possible. The procedure for icing test methods

    including preparation, exposure, quantification, and evaluationfeatures have been reported in detail in the previous position

    paper [28]. The two following methods for evaluating and

    comparing the electrical performance of ice-covered insulators

    have already been recommended in that work [28].

    i) Compare the icing performance of the insulators for a

    given test severity.

    ii) Compare the icing performance of different insulators at

    the maximum possible ice severity (e.g., maximum pos-

    sible level of bridging), giving the worst case icing test

    performance for each insulator.

    The approaches for the evaluation and ranking of insulator

    performance following this outline have already been proposed

    and discussed in [28].

    III. CLIMATE ANDENVIRONMENTAL CONTEXT

    A. Climate

    The risks offlashover on station insulators are correlated withthe occurrence, in general, of freezing rain, drizzle or wet snow.

    Hence, meteorological statistics may provide relevant informa-

    tion for the estimation of risk levels. However, it is also impor-

    tant to note that the pollution level of such precipitation mayvary significantly, as a result of both long-range [15] and short-

    Fig. 3. Annual number of hours with freezing rain.

    Fig. 4. Annual number of hours of freezing drizzle.

    Fig. 5. Number of hours per year with fog or freezing fog with

    C

    [33].

    range transport of contamination. It is also important to be aware

    of enhanced salt content in wet snow, stemming from rough sea

    and heavy production of sea spray in the upwind area, prior

    to the deposition. Two seemingly equal wet snow or freezing

    rain events may therefore have different impacts on electrical

    equipment.

    Figs. 35 show periodic observations of the annual number ofhours with freezing rain [33], freezing drizzle [58], and freezing

    fog, respectively. This data can be used further for the estimationof a number of icing events.

  • 8/10/2019 Selection of Station Insulators

    4/7

    FARZANEHet al.: SELECTION OF STATION INSULATORS WITH RESPECT TO ICE AND SNOWPART I 267

    B. Environment

    Insulator pollution standards, such as IEC 60 815 [56],

    currently under revision, provide some guidance in Table I re-

    garding the leakage distance needed for reliable long-term use

    as a function of insulator pollution level. The present IEEE TF

    recommends the use of four pollution levels in Table I as ranges

    of equivalent salt deposit density (ESDD). A revised standardIEC 60 815 will also take into account another important

    pollution parameter, i.e., nonsoluble deposit density (NSDD).

    Equivalent advice is given below for icing and cold-fog con-

    ditions. However, there is little guidance for establishing the

    anticipated ESDD level, except for test values near the sea [13].

    Winter exposure is somewhat similar to desert exposure in

    the sense that the top surfaces are not exposed to rain for ex-

    tended periods of weeks or months, depending on the local am-

    bient temperature. Short-term exposure of several weeks tends

    to have a linear relationship between ESDD and duration, while

    the ESDD levels off for long-term exposure of 6 to 18 months.

    Under winter conditions, top-surface ESDD values increase tolevels higher than bottom surfaces.The rate of increase of ESDD

    with time must be established from the local pollution environ-

    ment, and used in conjunction with climate records for the me-

    dian or extreme duration of dry periods.

    A model for pollution exposure at substations can be de-

    rived from the massflux of nearby point, line, or area pollutionsources. An example of a point source would be a chimney lo-

    cated several kilometers upwind of the station. Road salting on

    expressways ata level of metrictons ofNaClper lanekm is

    a common line source, and generating stations located near the

    sea are exposed to a half-plane source whenever the wind blows

    in from the ocean. The source strength of the half-plane formed

    by the sea is strongly influenced by wind speeds and wave ac-tion [13].

    Thewind rosette,a polar plot of wind speed and directionover the exposure period, is used in common surface deposi-

    tion models. The probability of being directly downwind from

    a point source is fairly low, so the exposures from line and area

    sources usually dominate the calculation. When such models are

    applied on a sea surface area, it is important to consider the dif-

    ferences in surface winds and the wind direction at 5001000 mlevels, where the main transportation of the pollution, as well

    as the release of precipitation, takes place. Due to the veering

    of wind with height, the local surface wind direction may be as

    much as 90 (anticlockwise on the northern hemisphere) off thetransport direction of sea salt aloft, depending on the roughness

    of the terrain.

    IV. EFFECTS OF ATMOSPHERICICE ANDPOLLUTION WITH

    RESPECT TOINSULATORPARAMETERS

    A. Exposed Surface to Icing

    The surface exposed to icing is normally a product of insu-

    lator dry arcing distance and diameter, with some adjustment for

    different shed profiles. Whenever the leakage distance is fullybridged with ice or snow, the insulation strength is established

    mainly by the electrical properties of the ice or snow, and the ex-posed surface area. Under the most severe meteorological con-

    ditions that lead to slow melting, (3) and (4) have approximated

    the insulation strength [60]:

    kV m dry arc for ice (3)

    kV m dry arc for snow. (4)

    ISP is the product of the ice layer weight (g/cm of dry arcing

    distance) and the ice layer conductivity ( S/cm). Reference [8]

    also notes a nonlinear relationship for EHV insulators.

    B. Diameter

    North American experience during heavy ice storms suggests

    that station insulators of greater diameter are more prone to

    iceflashover than neighboring post insulators of smaller diam-eter [34]. The relationship between ice accretion diameter and

    flashover strength for afixed shed profile was recently studied[35] and can be expressed as:

    V kV m dry arc W (5)

    where W is the ice width (525 cm).A rough relation, as recently established during the experi-

    ment at the CIGELE laboratory (UQAC), can be made between

    the ice thickness on the reference cylinder and the weight of ac-

    creted ice per meter of 300-mm uniform shed profile station postinsulators, as follows:

    Weight Thickness (6)

    During this experiment the applied-water conductivity was

    80 S/cm and the maximum ice thickness was 20 mm on a

    rotating monitoring cylinder.

    C. Shed Spacing

    Typically, station post insulators differ from line insulators of

    the same voltage class in their shed spacing. Cap-and-pin line

    insulators with 146-mm construction height have a spacing of

    about 100 mm from the bottom of one skirt to the top surface

    of the next insulator. Sheds on typical ceramic post station insu-

    lators are about 50 mm apart. It is obvious that, with the same

    ice exposure and similar diameter, ice bridging will occur much

    more rapidly on station insulators. Once the insulators are fully

    bridged, the accumulation rates on station and line insulators are

    almost the same, and their electrical performance tends to con-

    verge. This means stations will have more problems than lines,

    especially in areas where there are several moderate ice storms

    per year.

    D. Shed Profile

    Additional leakage distance is provided on insulators by, for

    example, forming bottom parts of the sheds with deep under-

    ribs. The leakage distance thus obtained is 2 or 3 times longer

    than the dry arcing distance. This parameter improves pollution

    performance for a wide range of pollution conditions when no

    icing occurs.

    Many different shed profiles can be obtained for the samedry-arcing distance. Under conditions of heavy icing, deeper

    sheds tend to pack more ice and snow, before bridging, leadingto a greater ice weight (g/cm of dry arcing distance) for the same

  • 8/10/2019 Selection of Station Insulators

    5/7

    268 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 1, JANUARY 2005

    Fig. 6. Comparison of Clean-Fog and Cold-Fog flashover strength as afunction of ESDD.

    icing exposure, but this effect is less important than insulator di-

    ameter. Alternating diameters of sheds and multi-cone profilescan improve ice and snowflashover performance in some con-ditions by delaying the onset of ice bridging, compared to de-

    signs with uniform shed profile [1], [18], [21], [24], [36], [42].Booster sheds of various designs have also been evaluated for

    this function.

    Tests on a wide range of shed profiles are reported for 24-kVclass insulators [10]. These results suggest that the influence ofshed profile onflashover voltage is relatively limited comparedto the parameters of the ice deposit.

    E. Leakage Distance

    Leakage distance and the so-calledprotected leakage dis-tance play an important role in pollutionflashover strength forvery light levels of freezing rain, drizzle, and fog accumulation,

    but are less important when ice or snow bridging of insulator

    shed spacing occurs. In the worst case, the effective leakage dis-

    tance is reduced to the dry arcing distance.

    Generally, there is a reasonable agreement between the results

    of cold-fog tests versus clean-fog tests, according to IEC 60507,

    with cold-fog giving strengths that are 1020% lower than cleanfog results [40]. Empirically the electricalflashover strength ofleakage distance in cold-fog conditions, as a function of ESDD,

    is given by (7).

    V kV/m leakage ESDD (7)

    ESDD in g/cm .

    Fig. 6 shows the strength predicted by (7), superimposed on

    a summary of conventional clean-fog strength, replotted from

    data in [40] using a rough conversion factor of 2.5x for the re-

    lation between leakage and arcing distance.

    F. Orientation

    Testing experience for iced station insulators has generally

    been for vertical orientations, since these are most common.

    Results for V-strings of suspension insulators [37] suggest an

    improvement in strength for oblique angles, compared to ver-tical. Operational and testing experience with wetflashover of

    Fig. 7. Icing test on a T-shaped circuit-breaker at (a) open position and(b) closed position.

    wall bushings [41] suggest that horizontal orientation may per-

    form in unexpected ways compared to vertical post insulators.

    Ice or snow accretion on the top of the horizontal insulator will

    bridge the dry arcing distance at a lower precipitation amount.

    However, overall ice thickness will not build up as fast because

    icicles will develop vertically downward, not across the shed

    spacings, see example in Fig. 7.

    The placement of two station insulators in close proximity

    will tend to degrade the performance, compared to the single

    insulator. This is true for both heavy snow and ice accretion and

    was previously noted for line insulators [38].

    A special question for orientation concerns the ice perfor-

    mance of T-shaped circuit-breakers, or disconnecting circuit-

    breakers. To simulate the service case, it was decided to perform

    ice accretion on both chambers (horizontal part) and support in-

    sulator (vertical part). The Ice Progressive Stress Method (IPS)

    was used for testing [20], [21]. The test results of the breaker

    shown in Fig. 7 demonstrated a drastic difference in ice distri-

    bution at the breaker in open and closed operating positions (see

    examples). This also resulted in differentflashover voltages inopen and closed positions.

    G. Surface Material and Finish

    The ice accretion onset and rate tend to be relatively unaf-

    fected by insulator surface materials, whether ceramic or non-

    ceramic. However, the electrical performance of nonceramic

    or silicone-coated ceramic insulators is somewhat better, es-

    pecially under conditions of partial ice bridging [2], [39]. An-

    other surface that improves performance under icing conditions

    is a semi-conductive glaze with a surface resistivity of about

    1030 M [63]. This surface suppresses the onset of arcing[39], [42][46], [59] and is more effective under heavy ice con-ditions than silicone.

  • 8/10/2019 Selection of Station Insulators

    6/7

    FARZANEHet al.: SELECTION OF STATION INSULATORS WITH RESPECT TO ICE AND SNOWPART I 269

    The surfacefinish of the insulator affects performance inan indirect way. Test results show that ice slides off more

    easily from smooth, new ceramic surfaces than from aged

    porcelain, silicone-coated porcelain or nonceramic sheds of the

    same shape. This shortens the time that melting ice is on the

    insulators and proportionally reduces risk offlashover.

    V. CONCLUSION

    This first part of the paper has provided the physical andchemical background needed to describe the electricalflashoveron iced insulators. Several ice and snow parameters, including

    type and density, amount and distribution, water conductivity,

    as well as certain insulator parameters, such as diameter, shed

    spacing and profile, insulator orientation, and exposed surfaceto ice, influenceflashover mechanisms and performance.

    The most important aspect of icing performance is specif-

    ically related to the partial or complete bridging of insulator

    leakage distance by icicles extending from shed to shed. Under

    fully bridged conditions, the insulator leakage distance is re-duced nearly to the dry arcing distance. This drastic reduction

    in leakage distance (by a factor of about three) can lead to se-

    vere but sporadic ice-inducedflashovers at a number of affectedutilities.

    Flashover can also occur along the leakage distance of the sta-

    tion insulator under conditions of light or moderate icing com-

    bined with pre-deposited pollution. For many cold regions, the

    maximum levels of insulator contamination (ESDD) are reached

    in the winter. The exposure can be aggravated from the effects

    of high winds and road salting. An additional margin of 1020%over the existing design recommendations for specific leakagedistance for adequate clean-fog performance is needed for suffi-cient cold-fog performance on vertical ceramic post insulators.

    PartII ofthe paper [62] applies the environmental parameters,

    as described in Part I, to the selection process and mitigation

    options.

    ACKNOWLEDGMENT

    The Chairman would like to thank Dr. W. A. Chisholm espe-

    cially for his enthusiasm, dedication, and contributions, to Tom

    Grisham for helping with IEEE administration and to Dr. Igor

    Gutman for links to the IEC 60 815 revision process.

    REFERENCES

    [1] E. A. Cherney,Flashover performance of artificially contaminated andiced long-rod transmission line insulators, IEEE Trans. Power App.Syst., vol. PAS-99, no. 1, pp. 4652, Jan./Feb. 1980.

    [2] W. A. Chisholmet al.,The cold-fog test,IEEE Trans. Power Del., vol.11, no. 4, pp. 18741880, Oct. 1996.

    [3] M. Farzaneh and O. T. Melo,Flashover performance of insulators inthe presence of short icicles,Int. J. Offshore Polar Eng., vol. 4, no. 2,pp. 112118, 1994.

    [4] M. Farzaneh and J. Kiernicki, Flashover problems caused by icebuild-up on insulators, IEEE Electr. Insul. Mag., vol. 11, no. 2, pp.517, Mar./Apr. 1995.

    [5] J. F. Drapeau and M. Farzaneh,Ice accumulation characteristics onHydro-Quebec HV insulators, in Proc. 6th Int. Workshop on Atmo-spheric Icing of Structures, Budapest, Hungary, 1993, pp. 225230.

    [6] L. Guet al.,ACflashover characteristics of EHV line insulators forhigh altitude contamination regions,in Proc. ICPAPM, 1988.

    [7] L. Shu, C. Sun, J. Zhang, and L. Gu,ACflashover performance oniced and polluted insulators for high altitude regions,in Proc. 7th Int.Symp. High Voltage Engineering, vol. 4, Dresden, Germany, 1991, pp.303306. Paper 43.13.

    [8] V. Sklenicka and J. Vokalek,Insulators in icing conditions: Selectionand measures for reliability increasing, in Proc. 7th Int. Workshop

    Atmospheric Icing of Structures, Chicoutimi, QC, Canada, 1996, pp.7276.

    [9] J. S. Forest,The performance of high voltage insulators in pollutedatmospheres, in Proc. Conf. Paper IEEE Winter Meeting, New York,1969.

    [10] K. Kannus, K. Verkonnen, andV.Lavkervi, Effects of icecoating on theAC performance of medium-voltage insulators,in Proc. Nordic Symp.

    Elect. Insulation, NORD-IS 86, Esbo, Finland, 1986, pp. 111.[11] H. Matsuda, H. Komuro, and K. Takasu,Withstand voltage character-

    istics of insulator strings covered with snow or ice,IEEE Trans. PowerDel., vol. 6, no. 3, pp. 12431250, Jul. 1991.

    [12] T. Fujimura, K. Naito, Y. Hasegawa, and K. Kawaguchi,Performanceof insulators covered with snow or ice,IEEE Trans. Power App. Syst.,vol. PAS-98, no. 5, pp. 16211631, Sep./Oct. 1979.

    [13] R. Matsuoka, S. Ito, K. Sakanishi, and K. Naito,Flashover on contam-inated insulators with different diameters,IEEE Trans. Dielectr. Electr.

    Insul., vol. 26, no. 6, pp. 11401146, Dec. 1991.[14] M. Yasui, K. Naito, and Y. Hasegawa,AC withstand voltage character-

    istics of insulator string covered with snow, IEEE Trans. Power Del.,

    vol. 3, no. 2, pp. 828838, Apr. 1988.[15] S. M. Fikke, J. E. Hanssen, and L. Rolfseng,Long range transported

    pollution and conductivity on atmospheric ice on insulators, IEEETrans. Power Del., vol. 8, no. 3, pp. 13111321, Jul. 1993.

    [16] S. M. Fikke, T. M. Ohnstad, T. Telstad, H. Frster, and L. Rolfseng,Effect of Long Range Airborne Pollution on Outdoor Insulation, 1994.NORD-IS 94, Paper 1.6.

    [17] A. Meier and W. M. Niggli,The influence of snow and ice deposits onsupertension transmission line insulator strings with special reference tohigh altitude operations,in Proc. IEEE Conf. Publ. 44, London, U.K.,1968, pp. 386395.

    [18] D. Wu, K. A. Halsan, and S. M. Fikke,Artificial ice tests for long in-sulator strings,inProce. 7th Int. Workshop Atmospheric Icing of Struc-tures, Chicoutimi, QC, Canada, 1996, pp. 6771.

    [19] D. Wu and R. Hartings,Correlation between the AC withstand voltageand insulator lengths under icing tests,in Proc. 9th Int. Workshop At-mospheric Icing of Structures, Chester, U.K., 2000, p. 6.

    [20] I. Gutman, S. Fikke, and K. Halsan,Development of the ice progres-sive test method applicable for the full-scale testing of the 420 kV classoverhead line insulators,in IWAIS, Brno, Czech Republic, Jun. 2002.61.

    [21] I. Gutman, K. Halsan, and D. Hbinette,Application of ice progressivestress method for selection of different insulation options,inProc. 13th

    Int. Symp. High-Voltage Engineering (ISH), Delft, Holland, Aug. 2003.[22] M. Kawai,ACflashover test at project UHV on ice-coated insulators,

    IEEE Trans. Power App. Syst., vol. PAS-89, no. 8, pp. 18001804,Nov./Dec. 1970.

    [23] M. D. Charneski, G. L. Gaibrois, and B. F. Whitney,Flashover tests onartificiallyiced insulators,IEEE Trans. Power App. Syst., vol. PAS-101,no. 8, pp. 24292433, Aug. 1982.

    [24] H. M. Schneider,Artificial ice tests on transmission line insulatorsAprogress report,in Proc. IEEE/Power Eng. Soc. Summer Meeting, SanFrancisco, CA, 1975, pp. 347353. Paper A75-491-1.

    [25] Z. Vuckovic and Z. Zdravkivic,Effect of polluted snow and ice accre-tion on high voltage transmission line insulators, inProc. 5th Int. Work-shop Atmospheric Icing Structures, Tokyo, Japan, 1990. Paper B4-3.

    [26] Repercussions of ice and snow on theflashover performance of outdoorinsulators, CIGRE Working Group 33 Colloq. Group 4, Jul. 1997.

    [27] Reply to the Questionnaire on the Mechanical & Electrical Failures ofInsulators Caused by Ice and Snow, 2000. CIGRE WG B2-03, documentB2-02 (WG03) IWD-190.

    [28] M. Farzanehet al.,Insulator icing test methods and procedures,IEEETrans. Power Del., vol. 18, no. 4, pp. 15031515, Oct. 2003.

    [29] J. F. Drapeau, M. Farzaneh, M. Roy, R. Chaarani, and J. Zhang,Anexperimental study offlashover performance of various post insulatorsunder icing conditions,in Proc. Conf. Electrical Insulation DielectricPhenomena (CEIDP), vol. 1, Victoria, BC, Canada, 2000, pp. 359364.

    [30] M. Farzaneh and J. F. Drapeau,ACflashover performance of insulatorscovered with artificial ice,IEEE Trans. Power Del., vol. 10, no. 2, pp.10381051, Apr. 1995.

  • 8/10/2019 Selection of Station Insulators

    7/7

    270 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 1, JANUARY 2005

    [31] M. Farzaneh and J. Kiernicki,Flashover performance of IEEE standardinsulators under ice conditions,IEEE Trans. Power Del., vol. 12, no. 4,pp. 16021613, Oct. 1997.

    [32] M. Farzaneh,Ice accretion on high-voltage conductors and insulatorsand related phenomena, Philos. Trans. Roy. Soc., vol. 358, no. 1776,pp. 29713005, Nov. 2000.

    [33] J. V. Cortinas Jr., C. C. Robbins, B. C. Bernstein, and J. W. Strapp,Aclimatology of freezing rain, freezing drizzle andice pellets acrossNorth

    America, in Proc. 9th Conf. Aviation, Range, Aerospace Meterology,Orlando, FL, 2000, AMS, pp. 292297.[34] J. F. Drapeau, R. Beauchemin, J. Laflamme, R. Martin, and M. J.

    Roy,Tenue sous verglas de lisolation externeRapport #1: Risquesde contournements en conditions de verglasd et impacts des pertesdquipements associs, in Tenue sous verglas (Confidential):Hydro-Qubec Working Group, Nov. 1996.

    [35] R. Chaarani, tude de linfluence des caractristiques des isolateurs surleurs performanceslectriques dans des conditions de givrage, Ph.D.dissertation, Univ. Quebec Chicoutimi, Apr. 2003.

    [36] C. C. Erven,500 kV insulatorflashovers at normal operating voltage,inProc. Presentation to the Can. Elect. Assoc. (CEA) Spring Meeting ,Montreal, QC, Canada, 1988.

    [37] K. Kannus, K. Verkonnen, and E. Lakervi,Effect of ice coating on thedielectric strength of high voltage insulators, in Proc. 4th Int. Workshop

    Atmospheric Icing of Structures, Paris, France, 1988, pp. 296300.[38] M. M. Khalifa and R. M. Morris, Performance of line insulators

    under rime ice,IEEE Trans. Power App. Syst., vol. PAS-86, no. 6, pp.692698, Jun. 1968.

    [39] J. S. Barrett and M. A. Green,A statistical method for evaluating elec-trical failures, IEEE Trans. Power Del., vol. 9, no. 3, pp. 15241530,Jul. 1994.

    [40] R. S. Gorur, E. A. Cherney, and J. T. Burnham,Outdoor insulators,Ravi S. Gorur Inc., 1999.

    [41] P. J. Lambeth, Y. Beausjour, and S. I. Kamel,Behavior of HVDC wallbushings under nonuniform rain,Rep., Report for the Canadian Elec-trical Association CEA 203 T 787, Jul. 1996.

    [42] M. Farzaneh, J. F. Drapeau, S. Brettschneider, and M. Roy,tude com-parative de performancelectrique des isolateurs externes dans des con-ditions de glace atmosphrique en vue du choix adquat disolateurs depostes 735 kV, in Colloquium on Icing, ACFAS Conf. Sherbrooke, QC,2001, http://icevolt.uqac.uquebec.ca/cigele.

    [43] V. Jaiswal, M. Farzaneh, and D. A. Lowther,Impulse flashover per-formance of semi-conducting glazed insulators equipped with boostersheds under icing conditions,inProc. Canadian Conf. Electrical Com-

    puter Eng., Montreal, QC, Canada, May 2003.[44] V. Jaiswal and M. Farzaneh,Effects of semi-conducting glaze coating

    on the electrical performance of a H.V. station post insulator coveredwith ice, in Proc. 13thInt. Symp. High-Voltage Engineering, Delft,Hol-land, Aug. 2003.

    [45] J.-F. Drapeau, M. Farzaneh, and M. Roy,An exploratory study of var-ious solutions for improving ice flashover performance of station postinsulators,in Proc. Int. Workshop Atmospheric Icing Structures, Brno,Czech Republic, Jun. 2002.

    [46] W. A. Chisholm,Effects of Flue-Gas Contamination of Ceramic In-sulator Performance in Freezing Conditions,, EPRI Rep. TR-110 296,1998.

    [47] M. Farzaneh, C. Volat, and A. Gakwaya, Electric field calculationaround ice-covered insulator using boundary element method,in Proc.

    IEEE Int. Symp. Electrical Insulation, Anaheim, CA, Apr. 2000, pp.349355.

    [48] V. Sklenickaet al.,Influence of conductive ice on electric strength ofHV insulators,in Proc. Int. Symp. Pollution Performance of Insulatorsand Surge Diverters, vol. 1, Madras, Tamilnadu, India, 1983. paper 1.02.

    [49] M. Farzaneh, J. Zhang, and X. Chen,Modeling of the AC arc discharge

    on ice surfaces,IEEE Trans. Power Del., vol. 12, no. 1, pp. 325338,Jan. 1997.[50] M. Farzaneh, I. Fofana, C. Tavakoli, and X. Chen,Dynamic modeling

    of DC arcdischargeon icesurfaces,IEEE Trans. Dielectr. Electr. Insul.,vol. 10, no. 3, pp. 463474, Jun. 2003.

    [51] J. Zhang and M. Farzaneh, Computation of AC critical flashovervoltage of insulators covered with ice,inProc. Int. Conf. Power SystemTechnology, vol. 1, Beijing, China, Aug. 1998, pp. 524528.

    [52] M. Farzaneh, Y. Li, J. Zhang, L. Shu, X. Jiang, W. Sima, and C. Sun,Electrical performance of ice-covered insulators at high altitudes,

    IEEE Trans. Dielect. EIectr. Insul., vol. 11, no. 5, pp. 870880, Oct.2004.

    [53] Influence of Ice and Snow on the Flashover Performance of OutdoorInsulatorsPart I: Effects of Ice, 1999. CIGRE TF 33 04 09, Electra no.187.

    [54] Influence of Ice and Snow on the Flashover Performance of OutdoorInsulatorsPart II: Effects of Snow, 2000. CIGRE TF 33 04 09, Electra

    no. 188.[55] IEEE/ANSI Std. C2.

    [56] Guide for Selection of Insulators in Polluted Areas. IEC 60 815.[57] W. A. Chisholm, P. G. Buchan, and T. Jarv,Accurate measurement of

    low insulator contamination levels,IEEE Trans. Power Del., vol. 9, no.3, pp. 15521557, Jul. 1994.

    [58] C. C. Robbins and J. V. Cortinas Jr.,Local and synoptic environmentsassociated with freezing rain in the contiguous united states, AMSWeather Forecasting, pp. 4765, Feb. 2003.

    [59] M. Farzaneh, J.-F. Dapeau, J. Zang, M. J. Roy, and J. Farzaneh,

    Flashover performance of transmission class insulators under icingconditions, in Proc. Insulator News Market Rep. Conf., Marbela,Spain, Aug. 2003, pp. 315326.

    [60] W. A. Chisholm, J. Kuffel, and M. Farzaneh,The icing stress product:A measure for testing and design of outdoorinsulators in freezing condi-tions,inProc. 2nd Int. Workshop on High Voltage Engineering, Tottori,Japan, 2000. session 8.

    [61] Technical Guide, NGK Nagoya, Tech. Guide, Cat. No. 91-R, 1991.Second Edition, p. 107.

    [62] IEEE Task Force On Icing Performance of Station Insulators et al.,

    Selection of station insulators with respect to ice and snowPart II:Methods of selection and options for mitigation, IEEE Trans. Power

    Del., vol. 20, no. 1, pp. 271277, Jan. 2005.[63] Y. Suzuki, S. Seike, and O. Imai,A practical study of semiconducting

    glaze for insulators,Elect. Eng. Jpn., vol. 131, no. 1, pp. 1018, 2000.