Installation Instructions Certified to comply with ASME A112.19.2 © 2014 AS America, Inc. SELECTRONIC ® CONCEALED TOILET FLUSH VALVE 1.28 & 1.6 GPF Concealed Flushometer for 1-1/2" Top or Back Spud Bowls CLOG RESISTANT ONE SENSOR FITS ALL 6065.22X 6067.22X 6068.22X MODEL NUMBERS 6065.26X 6067.26X 6068.26X • Self-cleaning piston valve prevents clogging and reduces maintenance. • Only 1 sensor for entire Selectronic™ line of faucets, urinals, and ush valves. Range can be adjusted manually or with optional remote control. • Sensor Features Low Battery Indicator. M965640 (11/14) CAUTION: Use only American Standard supplied cable sets. Using non-AS supplied cables, or cutting, splicing or modifying any components will void the warranty. Concealed Back Spud Exposed Back Spud Top Spud NOTE TO INSTALLER: Please give this manual to the customer after installation. To learn more about American Standar d Selectronic ® Pr oducts visit our website at: www.americanstandard-us.com or e-mail us at: [email protected] For Parts, Service, Warranty or other Assistance, please call (844) CRT-TEAM / (844) 278-8326 (In Canada: 1-800-387-0369) (In Toronto Area only: 1-905-306-1093)

Upload: others

Post on 03-May-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Ins

tall

ati

on

In

str

uc

tio

ns

Certified to comply with ASME A112.19.2

© 2014 AS America, Inc.

SELECTRONIC®CONCEALEDTOILET FLUSH VALVE1.28 & 1.6 GPF

Concealed Flushometerfor 1-1/2" Top or Back Spud Bowls

CLOG RESISTANT

ONE SENSOR FITS ALL

6065.22X6067.22X 6068.22X

MODEL NUMBERS

6065.26X6067.26X6068.26X

• Self-cleaning piston valve prevents clogging and reduces maintenance.

• Only 1 sensor for entire Selectronic™ line of faucets, urinals, and ush valves.• Range can be adjusted manually or with optional remote control.• Sensor Features Low Battery Indicator.

M965640 (11/14)

CAUTION: Use only American Standard supplied cable sets. Using non-AS supplied cables, or cutting, splicing or modifying any components will void the warranty.

Concealed Back SpudExposed Back Spud Top Spud

NOTE TO INSTALLER: Please give this manual to the customer after installation.NOTE TO INSTALLER: Please give this manual to the customer after installation.

To learn more about American Standard Selectronic® Products visit our website at: www.americanstandard-us.comor e-mail us at: [email protected]

For Parts, Service, Warranty or other Assistance,please call (844) CRT-TEAM / (844) 278-8326 (In Canada: 1-800-387-0369)

(In Toronto Area only: 1-905-306-1093)

All American Standard Products Are Water Tested At Our Factory. Some Residual Water May Remain In The Valve During Shipping.

Thank you for selecting American-Standard...the benchmark of fine quality for over 100 years. To ensure that your installation proceeds smoothly--please read these instructions carefully before you begin.

UNPACKINGRemove the Flush Valve items from the carton. The illustration below shows all items after they have been removed from the carton. Some items may be packaged partially assembled to other items.

1M965640 (11/14)

3

4

1

6

8c8b8a

5

DO NOT REMOVE PROTECTIVEFILM FROM SENSOREYE UNTIL INSTALLATIONIS COMPLETE.

T O P

2

7

606X.2X1 606X.2X2

VACUUM BREAKER FLUSH CONNECTIONS

606X.2X3

1. Installation Instructions

2. Flush Valve Body Assembly

3. Cover Plate with Sensor4. Electrical Box5. Sweat Adapter

Vacuum Breaker Flush Connection(Top Spud)DC Standard Battery and Battery HolderAC Power Supply (Model# 6067)27" Cable Extension, Qty. (2)Y-Adapter10' Extension

8c.

9a.

9b.

10.

11.

12.

Stop ValveManual Override Hoses

Vacuum Breaker Flush Connection(Exposed Back Spud)

Vacuum Breaker Flush Connection(Concealed Back Spud)

6.

8a.

8b.

7 .

Ins

tall

ati

on

In

str

uc

tio

ns

Ins

tall

ati

on

In

str

uc

tio

ns

Certified to comply with ASME A112.19.2

© 2014 AS America, Inc.

SELECTRONIC™CONCEALEDTOILET FLUSH VALVE1.28 & 1.6 GPF

Concealed Flushometerfor 1-1/2" Top or Back Spud Bowls

CLOG RESISTANT

ONE SENSOR FITS ALL

6065.22X6067.22X 6068.22X

MODEL NUMBERS

6065.26X6067.26X6068.26X

• Self-cleaning piston valve prevents clogging and reduces maintenance.

• Only 1 sensor for entire Selectronic™ line of faucets, urinals, and !ush valves.• Range can be adjusted manually or with optional remote control.• Sensor Features Low Battery Indicator.

M965640 (11/14)

CAUTION: Use only American Standard supplied cable sets. Using non-AS supplied cables, or cutting, splicing or modifying any components will void the warranty.

Concealed Back SpudExposed Back Spud Top Spud

10 10 10

12

1111

9b

9a

DC StandardBattery

6065. Series

Power Source

AC Plug-in6067. Series

AC Multi6068. Series

NOTE TO INSTALLER: Please give this manual to the customer after installation.NOTE TO INSTALLER: Please give this manual to the customer after installation.To learn more about American Standard Selectronic® Products visit our website at: www.americanstandard-us.comor e-mail us at: [email protected]

For Parts, Service, Warranty or other Assistance,please call (844) CRT-TEAM / (844) 278-8326 (In Canada: 1-800-387-0369)

(In Toronto Area only: 1-905-306-1093)

RECOMMENDED TOOLS; Fig. 2 Fig. 21.2.3.4.5.6.7.8.9.

10.

Teflon Tape Flat Blade ScrewdriverAdjustable Wrench Tape Measure HacksawTubing CutterFileFor Sweat Connection; Solder and Torch2.5mm Hex Wrench1.5mm Hex Wrench

1 2 3

4

56

7 9 10

8

• Flush all water lines prior to operation (See Step 3). Dirt and debris can cause flush valve to run continuously.

• With the exception of Stop Valve Inlet, DO NOT use pipe sealant or plumbing grease on any valve component or coupling!

• Protect the chrome or special finish on chrome plated items.DO NOT USE toothed tools on finished surfaces to install or service these valves. Also see “Care and Cleaning” section of this manual.

• This product contains mechanical and/or electrical components that are subject to normal wear. These components should be checked on a regular basis and replaced as needed to maintain the valve’s performance.

2

10'

M965640 (11/14)

PRIOR TO INSTALLATIONNote: Prior to installing the Selectronic™Flush Valve the following items must be installed.

1. Toilet

2. Drain line

3. Water supply line

IMPORTANT:• All plumbing and electrical wiring must be installed in accordance with applicable codes, regulations and standards.• The use of water hammer arrestors is strongly recommended for commercial applications. All piping behind the walls should be properly secured and fastened.• Water supply lines must be sized to provide an adequate volume of water for each fixture.

240mm MAX.(9-1/2) MAX.

Fig. 1

Roughing-inDimensions

GENERAL DESCRIPTION:

Concealed Flushometerfor 1-1/2" Spud Fixtures

SELECTRONIC™PROXIMITY TOILET FLUSH VALVE

Exclusive, self cleaning piston-type flush valve with proximity operation and manual override. Operates on DC (battery) or AC power (Plug-in). Recommended operating pressure 25psi (flowing) to 80 psi (static). Can install left or right-handed. Detection Zone can also be adjusted manually, or with optional remote control.

-C-L- -C-L-

51mm(2)

70mm(2-3/4) DIA.

25mm (1) MAX.

160mm(6-1/4)

OVERRIDEBUTTON

160mm(6-1/4)

127mm X 127mm(5X5 CUTOUTFOR BOX)

128mm MAX.(5) MAX.400mm MAX.

(15-3/4) MAX.

FOR LOCATION OF INLET SUPPLY ON BACK INLETFIXTURES AND CORRECT HEIGHT FROM FINISHED FLOOR,

REFER TO FIXTURE INSTRUCTION SHEET.

FINISHEDWALL

CONCEALED BACKSPUD TOILET

EXPOSED BACKSPUD TOILET

TOP SPUDTOILET

TOP OFFIXTURE

FINISHEDFLOOR

FINISHEDFLOOR

FINISHEDFLOOR

TOP OFFIXTURE

SENSOR

SUPPLY(1) NPT

108mm-134mm(4-1/4 TO 5-1/4)

*Note: The Critical Line (-C-L-) on VacuumBreaker must typically be 6" (152mm) min.above fixture. Consult Codes for details.

51mm(2)

51mm(2)

WALL THICKNESS

15˚

TOP OFFIXTURE

CAUTION: Use only American Standard supplied cable sets. Using non-AS supplied cables, or cutting, splicing or modifying any components will void the warranty.

450mm MAX.(17-3/4) MAX.

DETECTION ZONE400mm-800mm(Factory Setting: 400mm)

152mm MIN.(6) MIN.

*-C-L-

152mm MIN.(6) MIN.

*-C-L-

360mm MAX.(14-3/16) MAX.

Fig. 4

Fig. 5

3

INSTALL ELECTRICAL BOX; Fig. 31. Cut a 127x127mm (5"x 5") opening in finished wall for ELECTRICAL BOX (1) at the dimension shown.

2. Rotate the 4 MOUNTING TABS (2) flat against the electrical box. Holding the MOUNTING TABS (2) in position, install the ELECTRICAL BOX (1) into the opening. Make sure the MOUNTING TABS (2) are behind the wall.

3. Tighten the the 4 MOUNTING SCREWS (3) until the ELECTRICAL BOX (1) is almost secure in the wall. Before tighting fully, rest a level at the top edge of the ELECTRICAL BOX (1) and make sure the box is level.

4. Cut a 2" diameter hole for outlet pipe at dimension shown.*

1

Fig.3 (TOP SPUD FIXTURE ILLUSTRATED)

1

3

2

2

1

1

1. Open STOP VALVE (1).

3. Turn on water supply line to flush line of any debris orsediment.

4. Close STOP VALVE (1) and turn off water supply line.

FLUSH OUT SUPPLY LINES; Fig. 53

*FOR HOLE LOCATION OFOUTLET PIPE ON BACK INLETFIXTURES, REFER TO FIXTUREBEING INSTALLED FOR CORRECTHEIGHT FROM FINISHED FLOOR

127mm(5)

127mm(5)

INSTALL SWEAT ADAPTER; Fig. 4CAUTION Turn water supplies off before beginning

Note: Stop Valve inlet is 1" NPT. For optional sweat connection, install Sweat Adapter (1) (Supplied) for 1" copper pipe supply line.

1. Clean the end of the supply pipe. Push the threaded SWEAT ADAPTER (1) until it is seated against the internal stop. Sweat the ADAPTER (1) to the pipe.

2. Install the STOP VALVE (2) to the water supply line with the outlet positioned as required (Behind the Wall).

3. Support piping as required.

2

T O P

FILEEDGES

CLEAN & SOLDER TO ADAPTER (1)

115mm-134mm(4-1/2 TO 5-1/4)

STOP VALVE(1" NPT)

STOPVALVE

OUTLET

CLOCKWISE CLOSESSTOP VALVE

COUNTER-CLOCKWISEOPENS STOP VALVE

T O P

T O P

2

128mm MAX.(5) MAX.

M965640 (11/14)

FLUSH VALVE INSTALLATION

360mm MAX.(14-3/16) MAX.

M965640 (11/14)4

Fig. 6

Fig. 6a

Fig. 6b

Fig. 6c

34 INSTALL VACUUM BREAKER ANDFLUSH CONNECTIONS; Fig. 64

1. Place the SPUD FLANGE (1) over the spud on the Fixture. Fig. 6.

2. Place FRICTION WASHER (3) and SEAL WASHER (4) inside SPUD COUPLING NUT (2) and thread onto Spud. Do not ntighten fully. Fig. 6.

3. Remove the ELBOW COUPLING NUTS (6, 6a) from the CHROME ELBOW (5). Make sure you have a TAPERED RUBBER WASHER (7), PLASTIC SUPPORT (8) and SQUARE SEAL WASHER (9). Fig. 6a.

4. Install the SQUARE SEAL WASHER (9) onto the PLASTIC SUPPORT (8) if not already installed. Insert the PLASTIC SUPPORT (8) into the VERTICAL OUTLET PIPE (10). Slide the ELBOW COUPLING NUT (6) onto the VERTICAL OUTLET PIPE (10). Connect the ELBOW COUPLING NUT (6) to the CHROME ELBOW (5) and tighten fully.

5. Insert the VERTICAL OUTLET PIPE (10) with assembled CHROME ELBOW (5) into the SPUD COUPLING NUT (2) and push it down. Do not tighten fully. Fig. 6a.

Note: Cutting the VERTICAL OUTLET PIPE (10) may be necessary for the CHROME ELBOW (5) center line to line up with opening in the wall.

6. Measure and cut the HORIZONTAL OUTLET PIPE (11) to length required. Fig. 6b.

Important: Make sure that there is a minimum of 1-1/4" for engagement with elbow when making your measurement.

7. Remove the ELBOW COUPLING NUT (14) from BRASS ELBOW (12) and slide it onto the HORIZONTAL OUTLET PIPE (11). Install the SQUARE SEAL WASHER (13) onto the PLASTIC SUPPORT (15) if not already installed. Insert the PLASTIC SUPPORT (15) into the HORIZONTAL OUTLET PIPE (11). Connect the ELBOW COUPLING NUT (14) to the BRASS ELBOW (12) and tighten fully. Fig. 6b.

8. From behind the wall, insert the assembled BRASS ELBOW and HORIZONTAL OUTLET PIPE (12, 11) through the hole in the wall. Install WALL ESCUTCHEON (16) onto the HORIZONTAL OUTLET PIPE (11). Slide the ELBOW COUPLING NUT (6a) and TAPERED RUBBER WASHER (7) onto the HORIZONTAL OUTLET PIPE (11). Push the HORIZONTAL OUTLET PIPE (11) into the CHROME ELBOW (5). Tighten ELBOW COUPLING NUT (6a) but not fully. Fig. 6b.

9. For back spud installations: Follow steps #1 and #2 to install the spud coupling kit. Push the HORIZONTAL OUTLET PIPE (11) into the spud connection on the back of the fixture. Do not tighten fully. If spud coupling kit is not required, install HORIZONTAL OUTLET PIPE (11) into back spud on fixture and hand tighten. Fig. 6b.

10. All installations: If required, cut scored VACUUM BREAKER PIPE (17), leave a minimum of 1-1/4" (32mm) of pipe to ensure engagement with compression coupling. Assemble the ELBOW COUPLING NUT (14a) and TAPERED RUBBER WASHER (19) onto the VACUUM BREAKER PIPE (17). Install VACUUM BREAKER PIPE (17) into BRASS ELBOW (12) and hand tighten COUPLING NUT (14a). Fig. 6c.

Note: If cutting VACUUM BREAKER PIPE (17) to size, note that Critical Line (C/L) on Vacuum Breaker must typically be 6" (152mm) above fixture. Consult Code for details.

1

23 4

1-1/2" TOP SPUD

9

6a

8

7

5

610

FLANGE END UP

2

TAPERED SIDE

14

1612

11

15

57

6a

13

FLANGE END

11

14a

19

19

17

TOP SPUDINSTALLATION

BACK SPUDINSTALLATION

BACK SPUDINSTALLATION TOP SPUD

INSTALLATION

TAPEREDSIDE

12

TAPERED SIDE UP

TAPEREDSIDE UP

7

9

6

25

10

Fig. 8

Fig. 7

5

7

1. Insert the side ADJUSTABLE TAILPIECE (1) on the FLUSH VALVE (2) into the STOP VALVE (3). Lubricate the TAILPIECE O-RING (4) with water if necessary. Thread the COUPLING NUT (5) onto the STOP VALVE (3) and tighten lightly. Fig. 7.

Important: Do not use lubricants (other than water) or any type of thread sealing paste or tape.

INSTALL FLUSH VALVE; Fig. 75

1. Align the FLUSH VALVE BODY (2) directly above the VACUUM BREAKER TUBE (7) and VACUUM BREAKER COUPLING NUT (6). Make sure that GASKET (10) is installed.

Note: There is a +13mm, -6mm (+1/2"-1/4") tolerance for the 121mm (4-3/4) dimension.

2. Pull the VACUUM BREAKER TUBE (7) up to meet the threaded FLUSH VALVE (2) and hand tighten the COUPLING NUT (6). Align all components of the flush valve assembly.

3. Lightly tighten the TAILPIECE COUPLING NUT (5) connection first, then the VACUUM BREAKER COUPLING NUT (6) and finally the SPUD COUPLING NUT (9). Once alligned correctly, use a wrench to tighten all couplings to make water tight connections.

4. Secure piping behind wall as required.

CONNECT FLUSH VALVE TOVACUUM BREAKER TUBE; Fig. 86

3

25 4

1

121mm,+13mm, -6mm(4-3/4)(+1/2, -1/4)

M965640 (11/14)

M965640 (11/14)66

T O P

21

3

4

7

68

10

ELECTRICALOUTLET

59

TERMINAL SIDE

Fig. 9

Fig. 10

Fig. 10a

1

6

3

4

25

8 AC VERSION; Fig. 9, 10a

1. Attach the SAFETY CHAIN (1) from the COVER PLATE (2) to the MOUNTING POST (3) as shown. Fig. 9.

2. Connect one end of the 27" EXTENSION CABLE (1) to one SENSOR CABLE (2). Connect the other end of the 27" EXTENSION CABLE (1) to the SOLENOID CABLE (3). Fig.10.

3. Insert BATTERY (6) into BATTERY HOLDER (4), making sure terminal side is inserted first. Fig.10

4. Connect BATTERY HOLDER (4) to available SENSOR CABLE (5). Place BATTERY HOLDER (4) into electrical box. Fig.10.

1. Attach the SAFETY CHAIN (1) from the COVER PLATE (2) to the MOUNTING POST (3) as shown. Fig. 9.

2. Connect one end of the first 27" EXTENSION CABLE (4) to one SENSOR CABLE (5). Connect the other end of the 27" EXTENSION CABLE (4) to the SOLENOID CABLE (6).Fig.10a.

3. Connect AC POWER SUPPLY (8) to the single terminal of the Y-ADAPTER (10). Fig.10a.

4. Connect one end of the second 27" EXTENSION CABLE (7) to one of the two available terminals of Y-ADAPTER (10), and the other end of the 27" EXTENSION CABLE (7) to available SENSOR CABLE (9). Fig.10a.

5. Plug AC POWER SUPPLY (8) into outlet. Fig. 10a.

6. Place Y-ADAPTER (10) into electrical box.

7 DC VERSION; Fig. 9, 10

ELECTRICAL INSTALLATION

M965640 (11/14)7

2

Fig. 11

Unit #1 Unit #2 Unit #3

Unit #4

POWER SUPPLY

MAXIMUM OF 15 UNITS PER POWER SUPPLY. 10' MAXIMUM CABLE LENGTH BETWEEN UNITS.

9 MULTI-AC VERSION (DAISY-CHAIN); Fig. 11

CAUTION: Use only American Standard supplied cable sets. Using non-AS supplied cables, or cutting, splicing or modifying any components will void the warranty.

3

4

1

4

3a

Important: Disconnect AC Power Supply from wall outlet before making daisy-chain connections.

Note: For Unit #1 installation instructions, refer to AC version section (page 6).

For subsequent Units...

1. Take the first 27" EXTENSION CABLE (1) and connect one end to the solenoid cable, the otherend to a sensor cable.

2. Take the second 27" EXTENSION CABLE (2) and connect one end to the available sensorcable, the other end to one of the two terminals at the one end of the Y-ADAPTER (3).

3. Take the 10' EXTENSION (4) and connect one end to the single terminal of Y-ADAPTER (3), andthe other end to available terminal of the previous unit’s Y-ADAPTER (3a).

4. Repeat process for each subsequent unit.

5. Place Y-ADAPTERS (3) into respective electrical box.

6. Plug in AC power supply into wall outlet once all daisy-chain unit connections have been made.

(See AC version installationinstructions, page 6)

Already installed

TO FLUSHVALVE SOLENOID

TO FLUSHVALVE SOLENOID

TO FLUSHVALVE SOLENOID

INSTALL COVER PLATE; Fig. 12

M965640 (11/14)8

1. Push the BLACK HOSE (1) into the BOTTOM HOSE CONNECTOR (2) on flush valve body and push the other end into the back of the MANUAL OVERRIDE VALVE (3).

2. Push the BLUE HOSE (4) into the TOP HOSE CONNECTOR (15) on flush valve body and push the other end into the BOTTOM CONNECTOR (6) of the manual override valve.

CONNECT OVERRIDE HOSES,AC & DC POWER; Fig. 1311

10

2

5

4 BLUEHOSE

1 BLACKHOSE

Fig. 13

6

3

T O P

Fig. 12

1. Install the two TABS (1) on the back side of COVER PLATE (2) into the two SLOTS (3) located on the top edge of the ELECTRICAL BOX (4).

2. Push on the bottom edge of the COVER PLATE (2) until it snaps into place. If COVER PLATE (2) will not snap into place, then loosen the MOUNTING SCREWS (6) on the ELECTRICAL BOX (4) slightly.

3. To remove COVER PLATE (2), insert WIRE KEY (5) (supplied) into the two holes located at the bottom of the COVER PLATE (2). Push the WIRE KEY (5) up until it releases the bottom clips. Pull the bottom edge away and lift the COVER PLATE (2) off.

PUSH TOSNAP PANELINTO PLACE

5

6

2

1

23

4

M965640 (11/14)

INSTALL NEWBATTERY

CR-P2

CR-P2

Fig. 14

9

Fig. 15

CLOCKWISE CLOSESSTOP VALVE

COUNTER-CLOCKWISEOPENS STOP VALVE1

2

INSTALL NEW BATTERY;Fig. 14

14

32

IMPORTANT: To avoid overflowing, the STOP VALVE (2) must never be opened to the point where the flow from the valve exceeds the flow capacity of the fixture. Valve is designed to provide stated flush volume with a 25 GPM flow rate.

1. After installation is complete, peel off the PROTECTIVE FILM (1) from the sensor. Standing to one side, block the sensor with your hand for 10 seconds. Remove your hand and listen for audible “click” from within the valve.

2. Turn on STOP VALVE (2) 1/4 turn to 1/2 turn(CCW) and test for leaks.

Note: Unit may flush for approximately 5 to 10 seconds when water is first turned on. If flow persists, turn water off and repeat step #1 above.

3. Actuate the FLUSH VALVE: A)

B)

4. Adjust STOP VALVE (2) after each flush until the stated flush volume is achieved, no splashing occurs and the fixture is properly cleansed.

ADJUST STOP VALVE; Fig. 15

1. Remove the COVER PLATE (1). For removing front panel instructions, see Step 10.

2. Remove old BATTERY (2) from BATTERY HOLDER (4). Install the new BATTERY (3), making sure the shape of the BATTERY (2) follows the shape of the BATTERY HOLDER (4).

3. Install COVER PLATE (1).

A

B

MAINTENANCE

Cover sensor with hand for 10 seconds. NOTE: Stand outside of sensor detection area.

Remove hand from dection area; unit willflush in approximately 3 seconds.

M965640 (11/14)10

Fig. 16

213

1 1

4

Fig. 17

1" - 2" (30mm - 50mm)

BLINKING LED

5 BLINKING LED

SET DETECTION RANGE(If Required); Fig. 16 & 17.Note: The detection distance is preset and ideal for most installations. Should an adjustment be required, follow the steps below.

1. Remove COVER PLATE (1). See Step 10 for front panel removal instructions.

2. Disconnect SENSOR CABLE (2) from BATTERY HOLDER (3) or from POWER SUPPLY 27" EXTENSION CABLE (4). Fig. 16.

3. Keeping hands away from the front of the sensor, reconnect the SENSOR CABLE (2). Do not secure the COVER PLATE (1) at this time. Fig. 16.

Note: You have 5 seconds to begin entering the program code after power connection is made.

4. While the SENSOR CONTROL LED (5) is blinking slowly, place your hand 1 to 2". (30-50mm.) in front of the sensor. Fig. 17.

5. When the LED (5) stops blinking and stays "ON", move your hand to the desired position from sensor and hold in place until the LED (5) begins to blink again. Fig. 17.

Note: Detection Zone is 400mm - 800mm.(Factory Setting: 400mm) 6. Once the SENSOR CONTROL LED (5) begins to blink again, remove your hand from the detection zone. When the flashing stops, the detection distance is set.

7. Replace and secure COVER PLATE (1).

8. Actuate the FLUSH VALVE: A) Cover sensor with hand for 10 seconds.

Note: Stand outside of sensor detection area.

B) Remove hand from detection area; unit will flush in approximately 3 seconds.

C

DO: CLEAN WITH CLEAR WATER. DRY WITH A SOFT COTTON FLANNEL CLOTH.DO NOT: DO NOT CLEAN THE PRODUCT WITH SOAPS, ACID, POLISH, ABRASIVES,HARSH CLEANERS, OR A CLOTH WITH A COARSE SURFACE.

CARE INSTRUCTIONS:

T O P

DETECTION ZONE400mm - 800mm

(Factory Setting: 400mm)

11 M965640 (11/14)

TROUBLESHOOTING FLOW CHARTS

NNOO

YYEESS

NNOO

YYEESS

NNOO

11 22

11 22

YYEESS

NNOO

YYEESS

NNOO

UNIT DOES NOT FUNCTION

NNOO

NNOO

11

22

11

22

YYEESS

NNOO

NNOO

YYEESS

UNIT WILL ONLY FLUSH MANUALLY

YYEESS

NNOO

NNOO

11

22

11

22

NNOO

YYEESS

UNIT IS CONTINUOUSLY FLUSHING

OPEN VALVE

CRITICALLY LOW BATTERY . INSTALLNEW BATTERY

DEAD BATTERY. INSTALL NEWBATTERY. REPEAT.DAMAGED SENSOR WIRE. REPLACESENSOR. (ONLY IF ABSOLUTELY NEEDED)

DAMAGED SOLENOID. REPLACESOLENOID

DAMAGED MANUAL OVERRIDEBUTTON. REPLACE MANUALOVERRIDE BUTTON

DEAD BATTERY. INSTALL NEWBATTERY. REPEAT.

DAMAGED SENSOR WIRES. REPLACESENSOR. (ONLY IF ABSOLUTELY NEEDED)

DAMAGED SENSOR WIRES. REPLACESENSOR. (ONLY IF ABSOLUTELY NEEDED)

CRITICALLY LOW BATETRY. INSTALLNEW BATTERY

IS ANGLE STOP OPEN?

REPEATED DOUBLEFLASH ON SENSOR?

RECONNECT BATTERY TO SENSOR.FLASH ON SENSOR FOR 5SECONDS?

PUSH MANUAL OVERRIDEBUTTON; WILL THE UNIT FLUSH?

REPLACE PISTON ASSEMBLY.

CLOSE ANGLE STOP AND OPENAGAIN TO PRIME THE VALVE.DOES FLUSHING STOP?

PUSH MANUAL OVERRIDEBUTTON. DOES IT RETURN TO ITSORIGINAL POSITION FREELY?

RECONNECT BATTERY TO SENSOR.FLASH ON SENSOR FOR 5SECONDS?

REPLACE PISTON & SOLENOIDASSEMBLY.

REPEATED DOUBLEFLASH ON SENSOR?

RECONNECT BATTERY TO SENSOR.FLASH ON SENSOR FOR 5SECONDS?

REPLACE SOLENOID.

DEAD BATTERY. INSTALL NEWBATTERY. REPEAT.

HOT LINE FOR HELPFor toll-free information and answers to your questions, call:

(844) CRT-TEAM / (844) 278-8326Weekdays 8:00 a.m. to 6:00 p.m. EST

IN CANADA 1-800-387-0369 (TORONTO 1-905-306-1093)Weekdays 8:00 a.m. to 7:00 p.m. EST

IN MEXICO 01-800-839-1200

Product names l isted herein are trademarks of AS America, Inc. ©2014

To learn more about American Standard Selectronic® Products visit our website at:www.americanstandard-us.com or e-mail us at: [email protected]

12 M965640 (11/14)

M950319-0071600ASENSOR ASSEMBLY (1.6 gpf)

M950319-0071280ASENSOR ASSEMBLY (1.28 gpf)

A906680-0070ABONNET NUT

M964941-0021280ACOVER WITH SENSOR (1.28 gpf)

M964941-0021600ACOVER WITH SENSOR (1.6 gpf)

M962745-0070AELECTRICAL BOXASSEMBLY

M962749-0070ACHAIN ASSEMBLY

A922270-0070A“U” KEY FOR COVER

M962754-0070A1" STOP VALVE KIT

M964945-0020AADJUSTABLE TAILPIECE

M962926-0070A1" SWEAT ADAPTER

A912809-0070AO-RING

M962750-0070AMANUAL VALVE

HOSE KIT

T O P M964944-0020AMANUAL OVERRIDE BUTTON

M964402-0070AVACUUM BREAKER KIT

M964551-0070APISTON ASSEMBLY

M964302-0070ASOLENOID ASSEMBLY

M964852-0070ASOLENOID & PISTONSUBASSEMBLY

SELECTRONIC®

PROXIMITY TOILETCONCEALED FLUSH VALVE

1.28 & 1.6 GPF

6065.22X6067.22X 6068.22X

MODEL NUMBERS

6065.26X6067.26X6068.26X

M950510-0070A27" EXTENSION

CABLE

M950510-0070A27" EXTENSION CABLE

M950510-0070A27" EXTENSION CABLE

6065. Series

6067. Series

6068. Series

M950338-0070APOWER SUPPLY

M950511-0070A10' EXTENSION

A923654-0070ABATTERY 6V CR-P2

M950514-0070ABATTERY HOLDER

AC Plug-in

AC Multi

DC STANDARD BATTERY

M950512-0070AY-ADAPTER

M950512-0070AY-ADAPTER

M950216-0020AVACUUM BREAKER FLUSH

CONNECTION KIT(Top Spud)

M950218-0020AVACUUM BREAKER FLUSH

CONNECTION KIT(Exposed Back Spud)

(FOR MODEL 606X.2X1) (FOR MODEL 606X.2X2) (FOR MODEL 606X.2X3)

M950217-0020AVACUUM BREAKER FLUSH

CONNECTION KIT(Concealed Back Spud)

M962748-0070ASENSOR MOUNTING KIT(SMALL PLATE)

HOT LINE FOR HELPFor toll-free information and answers to your questions, call:

(844) CRT-TEAM / (844) 278-8326Weekdays 8:00 a.m. to 6:00 p.m. EST

IN CANADA 1-800-387-0369 (TORONTO 1-905-306-1093)Weekdays 8:00 a.m. to 7:00 p.m. EST

IN MEXICO 01-800-839-1200

Product names l isted herein are trademarks of AS America, Inc. ©2014

To learn more about American Standard Selectronic® Products visit our website at:www.americanstandard-us.com or e-mail us at: [email protected]