seminar on substation training
TRANSCRIPT
ABOUT THE FIRM
Punjab State Power Corporation Ltd.
(POWERCOM)
Starting with the modest installed capacity of 62 MW, the PSEB (from which
POWERCOM unbundled)grew up by leaps and bounds. Envisaged with an
aim to produce power required for multitude of uses in state of
Punjab, POWERCOM generated 37222 million units during 2008-09 , which is more than 2006-07 by 2238 Million Units resulting of 6.40% increase in two years. It has its thermal power
plants situated in Ropar, Bathinda and Lehra Mohabbat and
hydel projects in form of Ranjit Sagar Dam, Shanan Power
House, Anandpur Sahib Hydel project, Mukerian Hydel Project
Stage 1 and U.B.D.C. (Upper Bari Doab Canal) Hydro Electric
Power House. The Corporation has an ambitious plan to add sufficient generating capacity in the State in order to bridge the gap between demand and supply. A beginning was made in this regard by improving the performance of the existing units.
ABOUT THE
TRAINING I had my training in 66
..TRAINING REPORT SUBMITTED BY-: PARDEEP DIXIT [Type the abstract of the document here. The abstract is typically a short summary of the contents of the document. Type the abstract of the document here. The abstract is typically a short summary of the contents of the document.] [Type the author name] [Pick the date]
KV Substation located in sector 71, Mohali. Commissioned in 2-
2-2011, this substation has incoming from 220 KV Substation
located in Mohali phase 1. It basically has a step down
distribution 66/11 KV transformer and is responsible for supply
to 11 kv substation located in 3B1 Mohali, Mattur village, 3B2
and Phase7.Training basically included of being part of work
culture in substation, information about all the parts present in
substation, their uses and intricacies involved.From these
substations the power reaches our home through distribution
transformers.
SUBSTATION
A substation is a part of an electrical generation,
transmission, and
distribution system.
Substations
transform voltage
from high to low, or
the reverse, or
perform any of
several other
important functions.
Electric power may flow through several substations
between generating plant and consumer, and its voltage
may change in several steps.
A substation that has a step-up transformer increases the
voltage while decreasing the current, while a step-down
transformer decreases the voltage while increasing the
current for domestic and commercial distribution.
NEED OF SUBSTATIONS
1. For efficient and reliable power distribution
2. To improve power factor whenever needed
3. It is practically unfeasible to control and keep
an eye on the power supply of large region, so
we need substations controlling smaller regions.
4. It houses vrios protection devices such as
lightening arresters,circuit breakers,isolators. 5. With number of substations ,fault isolation,detection
and correction becomes convenient
VARIOUS PARTS PRESENT IN 66 KV
SUBSTATION
DISTRIBUTION TRANSFORMER 66/11 KV, 20 MVA
by IMP
CURRENT TRANSFORMER
VOLTAGE TRANSFORMER
SULPHUR HEXAFLOURIDE CIRCUIT BREAKERS
ISOLATOR
RELAYS(STATIC AND ELECTROMAGENTIC)
LIGHTENING ARRESTERS
BATTERY ROOM
TRANSFORMER
It is a static electric device which transforms electric
energy from one circuit to another through magnetic
medium without any change in frequency. Because a
transformer works on the principle of electromagnetic induction,
it must be used with
an input source
voltage that varies in
amplitude.
Transformer can be
Step Up or Step
Down depending
on requirement at
the receiving end.
On the basis of
location these are of
two types-:
1. Power Transformer-
These are designed to have maximum efficiency at
full load. These are basically used at the generating
end such as various power generating plants. These
are Step Up transformers. Voltage is stepped up to
minimize losses occurring in the long transmission
line given by
H = I^2*R*T
2. Distribution Transformer-
These are designed to have maximum efficiency at
half of a load. These are widely used in the
substations to step down the high voltage coming
from power transformers present in power plants.
On the basis of construction these are of following
type
1. Core Type-
These have L or U type laminations.
Material used- silicon steel
Joints of different laminations are alternative.
Alternative joints are to provide path to flux so that
flux continues to pass through laminations.
Laminations are insulated to reduce eddy current
losses.
Thickness of L type laminations- 0.35 mm
2. Shell Type-
In this, laminations shapes are of E and I types.
Thickness of laminations 0.35 mm
Laminations are placed inverted to each other to
provide continuous flux flow
Used in remote and hilly areas
Parts of a Transformer-:
CORE Transformers have silicon steel cores for flow of magnetic field.
This keeps the field more concentrated around the wires, so that
the transformer is more compact. The core of a power
transformer must be designed so that it does not reach magnetic
saturation. Carefully designed gaps are sometimes placed in the
magnetic path to help prevent saturation.
Practical transformer cores are always
made of many stamped pieces of thin
steel. The high resistance between layers
reduces eddy currents in the cores that
waste power by heating the core. These
are common in power and audio circuits.
A typical laminated core is made from E-
shaped and I-shaped pieces, leading to the
name "EI transformer".
WINDINGS
The winding material depends on the application. Small power
and signal transformers are wound with insulated solid copper
wire, often enameled. Larger power transformers may be wound
with wire, copper or aluminum rectangular conductors, or strip
conductors for very heavy currents. Windings on both primary
and secondary of a power transformer may have taps to allow
adjustment of the voltage ratio; taps may be connected to
automatic on-load tap changer switchgear for voltage regulation
of distribution circuits.
INSULATION
The conductor material must have
insulation to ensure the current
travels around the core, and not
through a turn-to-turn short-
circuit. In power transformers, the
voltage difference between parts
of the primary and secondary windings can be quite large.
Layers of insulation are inserted between layers of windings to
prevent arcing, and the transformer is immersed in transformer
oil that provides further insulation and acts as a cooling medium.
COOLING
High-power or high-voltage transformers are bathed in
transformer oil - a highly-refined mineral oil that is stable at
high temperatures. Large transformers to be used indoors must
use a non-flammable liquid. Today, nontoxic, stable silicone-
based oils or fluorinated hydrocarbons may be used, where the
expense of a fire-resistant liquid offsets additional building cost
for a transformer vault.
The oil cools the transformer, and
provides part of the electrical
insulation between internal live
parts. It has to be stable at high
temperatures so that a small short
or arc will not cause a breakdown
or fire. To improve cooling of
large power transformers, the oil-filled tank may have radiators
through which the oil circulates by natural convection. Very
large or high-power transformers (with capacities of millions of
watts) may have cooling fans, oil pumps. Oil transformers ar
equipped with Buchholz relays.
BUCHHOLZ RRELAY
Buchholz relay is a safety device mounted on oil-filled power
transformers and reactors, equipped with an external overhead
oil reservoir called a conservator. On a slow accumulation of
gas, due perhaps to slight overload, gas produced by
decomposition of insulating oil accumulates in the top of the
relay and forces the oil level down. A float switch in the relay is
used to initiate an alarm signal.If an arc forms, gas accumulation
is rapid, and oil flows rapidly into the conservator. This flow of
oil operates a switch attached to a vane located in the path of the
moving oil. This switch normally will operate a circuit breaker
to isolate the apparatus before the fault causes additional
damage. Buchholz relays have
a test port to allow the accumulated gas to be withdrawn for
testing. Flammable gas found in the relay indicates some
internal fault such as overheating or arcing, whereas air found in
the relay may only indicate low oil level or a leak .
OTHER PARTS
Transformer also has a temperature measuring devices in it. It
measures temperature of both primary and secondary winding
and of transformer oil. This proves of great use especially in
summer season.
It also has a motor for circulation of transformer oil. It
automates the oil level in transformer.
With time,it turns pink due to
moisture and hass to be replaced manually.
INSTRUMENT
TRANSFO
RMERS
Instrument transformers (ITs) are designed to
transform voltage or current from the high values in the transmission and distribution systems to the low values that can be utilized by low voltage metering devices. Depending on the requirements for those applications, the IT design and construction can be quite different. Generally, the metering ITs require high accuracy in the range of normal operating voltage and current. During a disturbance, such as system fault or overvoltage
transients, the output of the IT is used by a protective relay to initiate an appropriate action (open or close a breaker, reconfigure
the system, etc.) to sort the disturbance and protect the rest of the power system. Instrument transformers are the most common and economic way to detect a disturbance. CURRENT TRANSFORMER
Current transformer (CT) is
used for measurement of electric
currents. When current in a
circuit is too high to directly
apply to measuring instruments, a current transformer produces
a reduced current accurately proportional to the current in the
circuit, which can be conveniently connected to measuring and
recording instruments. A current transformer also isolates the
measuring instruments from what may be very high voltage in
the monitored circuit. Current transformer has a primary
winding, a magnetic core, and a secondary winding. A primary
objective of current transformer design is to ensure that the
primary and secondary circuits are efficiently coupled, so that
the secondary current bears an accurate relationship to the
primary current.
The most common design of CT consists of a length of wire
wrapped many times around a silicon steel ring passed over the
circuit being measured. The CT's primary circuit therefore
consists of a single 'turn' of conductor, with a secondary of many
hundreds of turns. The primary winding may be a permanent
part of the current transformer, with a heavy copper bar to carry
current through the magnetic core. Shapes and sizes can vary
depending on the end user or switchgear manufacturer.
From construction point of view, there are two types of
current transformers which are commonly used in laboratories
and panels. These are:-
1. Clamp-On or Clip-On
2. Bar Type
1. Clamp-On or Clip-On:- It is a Current Transformer in which the core can be opened
with the help of clamp and the conductor can be inserted in the
core. A single conductor acts as a primary and secondary is
wound on the core. An ammeter connected across the secondary
winding of the transformer which measure the current flowing to
the conductor directly. It is a portable instrument and generally
used in laboratories for testing purposes.
2. Bar-Type:- A Bar-Type current transformer has a circular ring type core
over which secondary is wound. An ammeter is connected
across the secondary. When a bar conductor or bus bar is
inserted through it, the ammeter measure current flowing
through bar conductor directly.
These are generally used with
instruments placed on panels or used
with the protective relays.
POTENTIAL TRANSFORMER
The potential transformer are
basically step-down transformers.
The connections of voltmeter when used in conjuction with the
potential transformer for measurement of high A.C. voltages.
The voltage to be measured is applied across the primary
winding which has a large no. of turns is coupled magnetically
to the primary winding. Turn ratio is so adjusted that the
secondary voltage is 110V when full rated primary voltage is
applied to primary.
Potential transformers are used to operate voltmeter, the
potential coils of wattmeter and relays from high voltage lines.
The design of potential transformer is quite similar to that of
power transformer. But the loading capacity of a potential
transformer is very small in comparison to that of power
transformer. The loading of a potential transformer some time
is only a few volt amperes. These transformers are made shell
type because this condition develops a high degree of accuracy.
For medium voltages i.e. upto 6.6 KV the potential transformer
are usually of dry type, between 6.6 KV to 1.1 KV they may be
either dry or oil immersed but for voltage more than 11 KV they
always oil immersed type. An out of door type oil immersed
voltage transformer having ratio 66000/110.
The working of a potential transformer is essentially the
same as that of a P.T. is very small and consequently the
exciting currents almost of the same order as that of secondary
current. Whereas in power transformers exciting current is very
small fraction of secondary load current.
USE OF C.T. AND P.T. FOR POWER
MEASUREMENT
For measurement of power or energy in a high voltage
power system, both C.T. and P.T. are used. P.T. is used to step
down the system voltage and C.T. is used to step down the
system current up to the required level. P.T. is connected in
parallel and C.T. is connected in series. The potential coil of
wattmeter is connected across the secondary of P.T. and
current coil is connected across the secondary of C.T.
Wattmeter or Energy meter so connected measure the power
or energy of the circuit directly.
ISOLATORS
A disconnector or isolator
switch is used to make sure
that an electrical circuit can
be completely de-energised
for service or maintenance. Such switches are often found in
electrical distribution and industrial applications where
machinery must have its source of driving power removed for
adjustment or repair. High-voltage isolation switches are used in
electrical substations to allow isolation of apparatus such as
circuit breakers and transformers, and transmission lines, for
maintenance. Often the isolation switch is not intended for
normal control of the circuit and is only used for isolation.
In some designs the isolator switch has the additional ability to
earth the isolated circuit thereby providing additional safety.
Such an arrangement would apply to circuits which inter-
connect power distribution systems where both end of the circuit
need to be isolated.
CIRCUIT BREAKERS
A circuit breaker is an automatically operated electrical switch
designed to protect an electrical circuit from damage caused by
overload or short circuit. Its basic function is to detect a fault
condition and, by interrupting continuity, to immediately
discontinue electrical flow. Unlike a fuse, which operates once
and then has to be replaced, a circuit breaker can be reset (either
manually or automatically) to resume normal operation. Circuit
breakers are made in varying sizes, from small devices that
protect an individual household appliance up to large switchgear
designed to protect high voltage circuits feeding an entire city.
The circuit breaker must detect a fault condition; in low-voltage
circuit breakers this is usually done within the breaker enclosure.
Circuit breakers for large currents or high voltages are usually
arranged with pilot devices to sense a fault current and to
operate the trip opening mechanism. The trip solenoid that
releases the latch is usually energized by a separate battery,
although some high-voltage circuit breakers are self-contained
with current transformers, protection relays, and an internal
control power source.
Once a fault is detected, contacts within the circuit breaker must
open to interrupt the circuit; some mechanically-stored energy
(using something such as springs or compressed air) contained
within the breaker is used to separate the contacts, although
some of the energy required may be obtained from the fault
current itself. Small circuit breakers may be manually operated;
larger units have solenoids to trip the mechanism, and electric
motors to restore energy to the springs.
The circuit breaker contacts must carry the load current without
excessive heating, and must also withstand the heat of the arc
produced when interrupting (opening) the circuit. Contacts are
made of copper or copper alloys, silver alloys, and other highly
conductive materials. Service life of the contacts is limited by
the erosion of contact material due to arcing while interrupting
the current. Miniature and molded case circuit breakers are
usually discarded when the contacts have worn, but power
circuit breakers and high-voltage circuit breakers have
replaceable contacts.
When a current is interrupted, an arc is generated. This arc must
be contained, cooled, and extinguished in a controlled way, so
that the gap between the contacts can again withstand the
voltage in the circuit. Different circuit breakers use vacuum, air,
insulating gas, or oil as the medium in which the arc forms.
SF6 CIRCUIT BREAKERS
. These breakers are available for indoor or outdoor applications,
the latter being in the form of breaker poles housed in ceramic
insulators mounted on a structure.
Current interruption in a high-voltage circuit-breaker is obtained
by separating two contacts in a medium, such as SF6, having
excellent dielectric and arc quenching properties. After contact
separation, current is carried through an arc and is interrupted
when this arc is cooled by a gas blast of sufficient intensity.
Gas blast applied on the arc must be able to cool it rapidly so
that gas temperature between the contacts is reduced from
20,000 K to less than 2000 K in a few hundred microseconds, so
that it is able to withstand the transient recovery voltage that is
applied across the contacts after current interruption. Sulphur
hexafluoride is generally used in present high-voltage circuit-
breakers (of rated voltage higher than 52 kV).
Into the 1980s, the pressure necessary to blast the arc was
generated mostly by gas heating using arc energy. It is now
possible to use low energy spring-loaded mechanisms to drive
high-voltage circuit-breakers up to 800 kV.
DISADVANTAGES OF SF6 CIRCUIT BREAKERS
1. SF6 is the most potent greenhouse gas that the Intergovernmental Panel on Climate Change has evaluated. It has a global warming potential that is 23,900 times worse than CO2.
2. When an arc is formed in SF6 gas small quantities of lower order gases are formed. Some of these byproducts are toxic and can cause irritation to eyes and respiratory system.
3. SF6 is heavier than air so care must be taken when entering low confined spaces due to the risk of oxygen displacement
LIGHTENING ARRESTER
The lightning arresters provide protection against atmospheric
lightening. A lightning arrester is a protective device, which
conducts the high voltage surges on the power system to the
ground.
It consists of a spark gap in series with a non-linear resistor. One
end of the diverter is connected to the terminal of the equipment
to be protected and the other end is effectively grounded. The
length of the gap is so set that normal voltage is not enough to
cause an arc but a dangerously high voltage will break down the
air insulation and form an arc. The property of the non-linear
resistance is that its resistance increases as the voltage (or
current) increases and vice-versa.
The action of the lightning arrester or surge diverter is as under:
(i) Under normal operation, the lightning arrester is off the line
i.e. it conducts no current to earth or the gap is non-conducting
(ii) On the occurrence of over voltage, the air insulation across
the gap breaks down and an arc is formed providing a low
resistance path for the surge to the ground. In this way, the
excess charge on the line due to the surge is harmlessly
conducted through the arrester to the ground instead of being
sent back over the line.After the surge is over, the resistor offers
high resistance to make the gap non-conducting.
JUMPER and TOWER
In a straight run line, one terminal pole is provided after
very 1km so as to
facilitate sagging.
Sagging of a line means
The short length of
conductor used to
connect line conductor
on one side of terminal
pole to the line
conductor on the other side of terminal poleis known as
jumper.
A jumper is made of same material and has same current
carrying capacity as that of line conductor. With a suitable
clamp for HV lines, jumpers are arranged in such a way
that under maximum deflection condition, there is
maximum clearance of 0.3m between line jumpers and
other metallic parts.
COUPLING CAPACITOR AND WAVE
TRAP
These instruments are not used for electrical supply.
Coupling capacitor is used for communication. It takes place
conversion between two Sub Stations. Wave Trap is also for
communication. It receives the sound below 20 hertz frequency
and left the sound above 20 hertz frequency. This reaches the
sound one Sub-Station to another Sub-Station and
communication takes place.
CAPACITOR BANKS
Shunt capacitor banks are used to improve the quality of the
electrical supply and the efficient operation of the power system.
Studies show that a flat voltage profile on the system can
significantly reduce line losses. Shunt capacitor banks are
relatively inexpensive and can be easily installed anywhere on
the network. Shunt capacitor banks (SCB) are mainly installed
to provide capacitive reactive compensation/power factor
correction. The use of SCBs has increased because they are
relatively inexpensive,easy and quick to install and can be
deployed virtually anywhere in the network. Its installationhas
other beneficial effects on the system such as: improvement of
the voltage at the load, better voltage regulation (if they were
adequately designed), reduction of losses and reduction or
postponement of investments in transmission.The main
disadvantage of SCB is that its reactive power output is
proportional to the square of the voltage and consequently when
the voltage is low and the system need them most, they are the
least efficient.
RELAYS
A Relay is an electrically operated switch. Many relays use an
electromagnet to operate a switching mechanism mechanically,
but other operating principles are also used. Relays are used to
protect electrical circuits from overload or faults; in modern
electric power systems these functions are performed by digital
instruments still called "protective relays".
ELECTROMAGENTIC RELAYS
The core of the electromagnetic relay is an electromagnet,
formed by winding a coil around an iron core. When the coil is
energized by passing current through it, the core in turn becomes
magnetized, attracting a pivoting iron armature. As the armature
pivots, it operates one or more sets of contacts, thus affecting the
circuit. When the magnetic charge is lost, the armature and
contacts are released. Demagnetization can cause a leap of
voltage across the coil, damaging other components of the
device when turned off. Therefore, the electromagnetic relay
usually makes use of a diode to restrict the flow of the charge,
with the cathode connected at the most positive end of the
coil.The electromagnetic relay is capable of controlling an
output of higher power than the input.
STATIC RELAY
The conventional relay type of electromagnet relays can be
replaced by static relays which essentially consist of electronic
circuitry. Static relays are superior to electro-magnetic relays.
1. The moving parts and the contacts are largely eliminated. The only moving element in a static relay is the final tripping contact.
2. More precise and high speed operation.
Static relay consists of DC supply required for energizing the
circuitry of the static relay. This is obtained from DC batteries.
It then compares the actual quantity with the pre-set quantity.
For example in an over-current relay it will compare the actual
current supplied by CT with the pre-determined set current over
which tripping is required. By using the gate circuits conditions
of operation of relays are set and relay can only be operated
when requisite conditions are satisfied. The actual tripping of
relay can be achieved by firing the SCR i.e. silicon controlled
rectifier.
DIFFERENTIAL RELAY
Another common form of protection for high voltage apparatus such as transformers and power lines is current
differential. This type of protection works on the basic theory of Kirchhoff's current law which states that the sum of the currents entering a node will equal zero. It is important to note the direction of the currents as well as the magnitude, as they are vectors. It requires a set of current transformers (smaller transformers that transform currents down to a level which can be measured) at each end of the power line, or each side of the transformer. The current protection relay then compares the currents and calculates the difference between the two.
As an example, a power line from one substation to another will have a current differential relay at both substations which communicate with each other. In a healthy condition, the relay at substation A may read 500 amps (power exporting) and substation B will read 500 amps (power importing). If a path to earth or ground develops there will be a surge of current. As supply grids are generally well interconnected the fault in the previous example will be fed from both ends of the power line. The relay at substation A will see a massive increase in current and will continue to export. Substation B will also see a massive increase in current, however it will now start to export as well. In turn the protection relay will see the currents travelling in opposite directions (180 degrees phase shift) and instead of cancelling each other out to give a summation of zero it will see a large value of current. The relays will trip the associated circuit breakers. This type of protection is called unit protection, as it only
protects what is between the current transformers. It is important to note that generally the higher the currents in the lines the larger the differential current required for the relay to see it as a fault.