  • SENSING THECHANGE

    TRANSMITTERS

  • Pyropress is a leading designer and manufacturer of switches, transmitters, valves and sensors offering engineering solutions for hazardous area, marine and industrial applications. For over 60 years we have built a solid and impressive reputation for quality, with reliable and durable products.

    Our products are designed to work in demanding and hazardous environments which require fast and cost effective solutions in instrumentation and control. Pyropress control sensors provide safe and reliable electrical switching of alarm or control circuits in response to changes in temperature, pressure, differential pressure, vacuum, fluid, flow and level conditions.

    ABOUT PYROPRESS

    Pyropress is based in Plymouth in the south of England and operate from a modern and purpose built 17,000 square foot facility. All of our manufacturing and design is undertaken here by our skilled engineers, and our close-knit team allows for a fluid and efficient component production line. We have excellent links by air, sea and road allowing us to offer exceptional delivery times.

    Our comprehensive product range incorporates proven design techniques and technology for flameproof (Exd), Intrinsically Safe (Exia), marine or industrial areas.

    3 cc

    PRESSURETRANSMITTER

    These ‘smart’ pressure transmitters provide high accuracy pressure measurement incorporating 2 wire microprocessor based technology and are suitable for measuring gauge pressure, vacuum and absolute pressure of gases, vapours and liquids.

    Local configuration can be carried out in the field via the pushbuttons inside the housing or from a remote point via the 2 wire 4 – 20mA line and communication via the HART® protocol.

    The measured pressure is indicated on the integral LCD display in selectable units and a 4 – 20mA output signal generated, directly or inversely proportional to the connected pressure.

    The LCD display can be rotated within the housing to ensure the measured readout can be easily viewed regardless of the angle of installation.

    The active sensing element is a piezoresistant silicon sensor separated from the process medium by a metal diaphragm and a manometric fluid to provide highly accurate measurements.

    PYRP-2000ALW ATEX/ IECEx Exd or ExiaCERTIFIED OR INDUSTRIAL PRESSURE TRANSMITTER

    FEATURES

    PRESSURE TRANSMITTER

    Aluminium alloy or 316 st. steel housinga Local adjustment panel keysa

    Output: 4–20mA + HART® communicationa Integral LCD display a

    ATEX/IECEx Flameproof or Intrinsically Safea

    Accuracy ≤ +/- 0.075% (0.05% option)a

    Rangeability (up to) 114:1a

    Thermal drift is automatically compensated via a thermister integrated into the pressure sensor and this coupled with the high accuracy sensor ensures a precison measuring system which will satisfy the most demanding applications.

    The transmitters are suitable for hazardous or non-hazardous areas, the former being certified either ATEX/IECEx Flameproof (Exd) or Intrinsically Safe (Exia).

    INDEXATEX/IECEx Exd or Exia Transmitters PAGEPYRP-2000 (Pressure) 3PYRD-2000 (Diff. Pressure) 9PYRT-2000 (Temperature) 15

    Industrial and Intrinsically Safe TransmittersPYRP-28 (Pressure) 19PYRD-28 (Diff. Pressure) 25

  • 3 cc

    PRESSURETRANSMITTER

    These ‘smart’ pressure transmitters provide high accuracy pressure measurement incorporating 2 wire microprocessor based technology and are suitable for measuring gauge pressure, vacuum and absolute pressure of gases, vapours and liquids.

    Local configuration can be carried out in the field via the pushbuttons inside the housing or from a remote point via the 2 wire 4 – 20mA line and communication via the HART® protocol.

    The measured pressure is indicated on the integral LCD display in selectable units and a 4 – 20mA output signal generated, directly or inversely proportional to the connected pressure.

    The LCD display can be rotated within the housing to ensure the measured readout can be easily viewed regardless of the angle of installation.

    The active sensing element is a piezoresistant silicon sensor separated from the process medium by a metal diaphragm and a manometric fluid to provide highly accurate measurements.

    PYRP-2000ALW ATEX/ IECEx Exd or ExiaCERTIFIED OR INDUSTRIAL PRESSURE TRANSMITTER

    FEATURES

    PRESSURE TRANSMITTER

    Aluminium alloy or 316 st. steel housinga Local adjustment panel keysa

    Output: 4–20mA + HART® communicationa Integral LCD display a

    ATEX/IECEx Flameproof or Intrinsically Safea

    Accuracy ≤ +/- 0.075% (0.05% option)a

    Rangeability (up to) 114:1a

    Thermal drift is automatically compensated via a thermister integrated into the pressure sensor and this coupled with the high accuracy sensor ensures a precison measuring system which will satisfy the most demanding applications.

    The transmitters are suitable for hazardous or non-hazardous areas, the former being certified either ATEX/IECEx Flameproof (Exd) or Intrinsically Safe (Exia).

    PAGE 3PYRP-2000

  • ATEX INTRINSICALLY SAFE IECEX INTRINSICALLY SAFE Ex II 1/2G Ex ia IIC T5/T6 Ex ia IIC T5/T6 Ga/GbIM1 Ex ia I Ma Ex ia IIB T5/T6 Ga/Gb (PTFE cable option)II 1D Ex ia IIIC T105°C Da Ex ia I Ma (316 st. steel housing) Ex ia IIIC T105°C DaATEX FLAMEPROOF II 1/2G Exia/d IIC T5/T6 Ga/Gb IECEX FLAMEPROOFII 1/2D Exia/t IIIC T85°C/T100°C Da/Db Ex ia/d IIC T5/T6 Ga/GbI M2 Exd ia I Mb Ex ia/IIIC T85°C/T100°C Da/Db Exd ia I Mb

    Special conditions for safe use:• Only the components (spares) referenced in the O & M manual can be replaced.• The maximum (declared by the manufacturer) gap of the spigot joint designated in document as L4 is smaller

    than specified in EN 60079-1. Details are given in the O & M Manual

    CERTIFICATION

    The housing is available in epoxy painted aluminium alloy ideally suited for industrial environments or 316 stainless steel suitable for offshore or corrosive environments.

    The ingress protection level is IP66 on Exia and non Ex versions (IP67 optional), and IP67 on Exd, to BS EN 60529:1992.

    Wetted parts are 316L st steel NACE MR-01-75 compliant as standard, with certification on request. Hastelloy C276 option is available on particular process sizes and forms (see part no. breakdown table).

    When neither of these materials meet the process requirements either for reasons of chemical incompatibility or temperature being outside permitted limits we can offer a range of diaphragm seals or chemical seals either for direct mounting on the transmitter or remote via stainless steel capillary (for details of these seals please contact our sales office).

  • (Max. 690Bar)

    (Min. 0.1/Max. 690Bar) (Min. 2.5/Max.* 690Bar)*1000Bar on request.TYPE GFS

    PAGE 5PYRP-2000

  • RANGE CODE

    30

    27

    25

    23

    20

    17

    13

    11

    8

    48

    57

    47

    45

    43*

    52

    53

    54

    55

    NOMINAL MEASURING RANGE

    (FSO)

    0 – 1000 Bar g

    0 – 300 Bar g

    0 – 160 Bar g

    0 – 70 Bar g

    0 – 25 Bar g

    0 – 7 Bar g

    0 – 2 Bar g

    0 – 1 Bar g

    0 – 0.25 Bar g

    -1 to +7 Bar g

    -1 to +1.5 Bar g

    -0.5 to +0.5 Bar g

    -100 to + 100 mBar g

    -15 to +70 mBar g

    0 – 1.3 Bar abs

    0 – 7 Bar abs

    0 – 25 Bar abs

    0 – 70 Bar abs

    10 Bar g

    3 Bar g

    1.6 Bar g

    0.7 Bar g

    0.25 Bar g

    70 mBar g

    100 mBar g

    50 mBar g

    25 mBar g

    70 mBar g

    120 mBar g

    50 mBar g

    20 mBar g

    5 mBar g

    100 mBar abs

    100 mBar abs

    0.25 Bar abs

    0.7 Bar abs

    MINIMUM CALIBRATED RANGE

    RANGEABILITY

    100:1

    100:1

    100:1

    100:1

    100:1

    100:1

    20:1

    20:1

    10:1

    114:1

    20:1

    20:1

    10:1

    17:1

    13:1

    70:1

    100:1

    100:1

    OVERPRESSURELIMIT

    1200 Bar g

    450 Bar g

    450 Bar g

    140 Bar g

    50 Bar g

    14 Bar g

    4 Bar g

    2 Bar g

    1 Bar g

    14 Bar g

    4 Bar g

    2 Bar g

    1 Bar g

    0.5 Bar g

    2 Bar g

    14 Bar g

    50 Bar g

    140 Bar g

    MEASURING RANGE TABLE

    NOTES:1) Burst Pressure - 4 x Nominal Measuring Range2) All ranges can withstand a permanent full vacuum, though on ranges up to 70 Bar this requirement should be advised at the ordering stage by incorporating “V” in part no. options section.3) *Range43-Flameproofcertificationforthisrangeisfor2Gand2Ginstallationsonlynot1/2Gand1/2D, andcannotbefittedwithchemical/diaphragmseals.4) OtherNominalMeasuringRangesareavailable,pleasecontactPyropressSalesOfficewithyour particular requirements.

  • FUNCTIONALOutput 4 – 20mA, 2 wire with Hart® Rev 5.1 digital communication protocol.Power supply Industrial (non Ex) 10 – 55 Vdc Intrinsically safe Exia 10.5 – 28 Vdc Flameproof Exd 13.5 – 45 Vdc Display Main 5 digit LCD display of pressure in user selectable units with 2 x smaller displays, one for process in mA or % and one for transmitter information e.g. setting options and transmitter error codes. Rangeablity/Turndown Up to 114:1Damping Adjustable from 0 – 60 secondsZero and Span Adjustable via local internal buttons or HART® digital communication.Failure alarm In the event of sensor or circuit failure, self diagnostics drives the output to 3.6mA (downscale) or 22mA (upscale) according to choice.

    PERFORMANCETurn on time Fully functional within 2 seconds of power being applied.Accuracy ≤ +/- 0.075% of the calibrated range when between 30 – 100% of the transmitter nominal range (with increased accuracy option of ≤ +/- 0.05% if required).Long term stability Stated accuracy is guaranteed for a minimum of 3 years.Thermal effect ≤ +/- 0.05% (FSO)/10°C (except ranges 43 and 45 which is ≤ +/- 0.1%) Max. +/- 0.25% (FSO) across the whole thermal compensation range (except ranges 43 and 45 which is ≤ +/- 0.4%).Thermal compensation -25 to +80°C (with special option of -40 to + 80°C).Power supply effect 0.002% (FSO)/VResponse time 16 – 480ms (programmable)SIL 2 option In accordance to IEC 61508/61511 ENVIRONMENTAL and EXTERNAL PARAMETERSIngress protection Intrinsically safe Exia and non Ex models – IP66 (with IP67 option). Flameproof Exd – IP67 (standard)Ambient temperature Industrial (non Ex) -40 to 85°C Intrinsically safe Exia -40 to 80°C Flameproof Exd -40 to 75°C Process temperature limits -40 to 120°C (non freezing).Humidity (RH) Maximum 98% non condensingEMC immunity EN 61326-1 and EN 61000-6-2:2005Shock protection level EN 60068-2-27, 50g/11ms Vibration protection level EN 60068-2-6, test Fc; up to 1.6mm for 2 - 25Hz, up to 4g for 25 - 100Hz

    CONSTRUCTIONHousing Aluminium alloy (blue epoxy painted) or 316 stainless steel.Wetted parts 316L or Hastelloy C276 (Gold plated diaphragm option available for hydrogen applications >70Bar).Fill liquid Silicon (standard) and inert fill (oxygen service).Electrical entry M20 x 1.5 ISO (std) or ½” NPT option via adapter (brass for the aluminium housing and 316 st. steel for the st. steel housing)Available accessories 316 st. steel manifold valves Universal mounting bracket for wall or 2” pipe (plated or 316 st. steel) Chemical/diaphragm seals in various materials to suit the application.

    TECHNICAL SPECIFICATION

    PAGE 7PYRP-2000

  • Our products are designed to work in demanding and hazardous environments which require fast and cost effective solutions in instrumentation

    and control. Pyropress control sensors provide safe and

    reliable electrical switching of alarm or control circuits in response to changes in temperature, pressure, differential

    pressure,vacuum, fluid, flow and level conditions.

    ABOUTPYROPRESS QUALITY

    To support the design of state of the art products the company has invested heavily in the latest CNC technology.

    We are able to produce our own components to a high degree of aaccuracy assuring a reliable and

    consistent quality product.

    T: +44 (0)1752 333933 | [email protected] www.pyropress.com

    P Y R P - 2 0 0 0 A L W / S S / I S / 2 0 / 0 - 1 6 B a r g / G B / M / A L S

    COMMON BASE NO.

    HOUSING MATERIAL A = CAST ALUMINIUM ALLOY (EPOXY PAINTED BLUE TO RAL 5015)SS = 316 STAINLESS STEEL

    CERTIFICATIONA = NONE - SAFE AREAIS = INTRINSICALLY SAFE - DUAL ATEX/IECEX EXIAD = FLAMEPROOF - DUAL ATEX/IECEX EXD

    PART NUMBER BREAKDOWN

    ELECTRICAL CONNECTIONM = M20 X 1.5 ISOUL = ½” NPT

    RANGE CODESELECT FROM MEASURING RANGE TABLE

    REQUIRED CALIBRATED RANGEPLEASE SPECIFY RANGE AND UNITS REQUIRED

    PROCESS CONNECTIONGB = G½” MALE (WITH 3MM BORE)GC = G½” MALE (WITH 12MM BORE)GA = G¼” MALE (MIN 10MBAR/ MAX 350BAR)N2 = ½” NPT MALE (WITH ¼” BSPP INTERNAL THREAD)F2 = ½” NPT FEMALE (VIA ADAPTER)(MAX. 690BAR)GD = G1” MALE WITH FLUSH DIAPHRAGM (MIN. 0.1/MAX. 70BAR)GF = G½” MALE WITH FLUSH DIAPHRAGM (MIN 2.5/ MAX 300 BAR)GFS =AS GF EXCEPT SPECIAL OPTION MAX. 1000BARX = CHEMICAL SEAL (SPECIFY REQUIREMENTS

    ACCESSORIES AND OPTIONSNA = NACE MR-01-75 CERTIFIED WETTED PARTSHA = HASTELLOY WETTED PARTS (GC,GD & *N2 CONNS ONLY) *MAX. PRESSURE 40 BARGP = GOLD PLATED DIAPHRAGM (NOT AVAILABLE RANGES 30 & 27)V = FULL VACUUM SUITABLE RANGES 8, 11,13, 17, 20 AND 23 (ALL OTHERS ARE VACUUM SUITABLE AS STANDARD)SP = 2” PIPE MOUNTING GRP SUNSHADEPC = ALUMINIUM PROTECTION COVER AGAINST VERTICAL IMPACT STRIKEST1 = EXTENDED COMPENSATION RANGE -40 TO +80°CT2 = EXTENDED COMPENSATION RANGE -60 TO 50°COXY = OXYGEN SERVICE (GB CONN ONLY) AL = UNIVERSAL WALL/2” PIPE MTG., BRACKET, ZINC PLATED STEELALS = UNIVERSAL WALL/2” PIPE MTG., BRACKET, 316 ST. STEELIP67 = IP67 (FOR EXIA AND SAFE AREA – EXD MODEL IS IP67 AS STD) SIL = SAFETY INTEGRITY LEVEL (SIL) 2MT = 316 ST. STEEL TAG

    PPSSC1083 | issue 2

    3 cc

    DIFFERENTIAL PRESSURETRANSMITTER

    These ‘smart’ differential pressure transmitters provide high accuracy pressure measurement incorporating 2 wire microprocessor based technology and are suitable for measuring differential pressure of gases, vapours and liquids.

    Local configuration can be carried out in the field via the pushbuttons inside the housing or from a remote point via the 2 wire 4 – 20mA line and communication via the HART® protocol.

    The measured pressure is indicated on the integral LCD display in selectable units and a 4 – 20mA output signal generated, directly or inversely proportional to the connected pressure line.

    The LCD display can be rotated within the housing to ensure the measured readout can be easily viewed regardless of the angle of installation.

    The active sensing element is a piezoresistant silicon sensor separated from the process medium by a metal diaphragm and a manometric fluid to provide highly accurate measurements.

    PYRD-2000ALW ATEX/ IECEx Exd or ExiaCERTIFIED OR INDUSTRIAL DIFFERENTIAL PRESSURE TRANSMITTER

    FEATURES

    DIFFERENTIAL PRESSURE TRANSMITTER

    Aluminium alloy or 316 st. steel housinga Local adjustment panel keysa

    Output: 4–20mA + HART® communicationa Integral LCD display a

    ATEX/IECEx Flameproof or Intrinsically Safea

    Accuracy ≤ +/- 0.075% (0.05% option)a

    Rangeability (up to) 25:1a

    Thermal drift is automatically compensated via a thermister integrated into the pressure sensor and this coupled with the high accuracy sensor ensures a precison measuring system which will satisfy the most demanding applications.

    The transmitters are suitable for hazard-ous or non-hazardous areas, the latter being certified either ATEX/IECEx Flameproof (Exd) or Intrinsically Safe (Exia).

  • Our products are designed to work in demanding and hazardous environments which require fast and cost effective solutions in instrumentation

    and control. Pyropress control sensors provide safe and

    reliable electrical switching of alarm or control circuits in response to changes in temperature, pressure, differential

    pressure,vacuum, fluid, flow and level conditions.

    ABOUTPYROPRESS QUALITY

    To support the design of state of the art products the company has invested heavily in the latest CNC technology.

    We are able to produce our own components to a high degree of aaccuracy assuring a reliable and

    consistent quality product.

    T: +44 (0)1752 333933 | [email protected] www.pyropress.com

    P Y R P - 2 0 0 0 A L W / S S / I S / 2 0 / 0 - 1 6 B a r g / G B / M / A L S

    COMMON BASE NO.

    HOUSING MATERIAL A = CAST ALUMINIUM ALLOY (EPOXY PAINTED BLUE TO RAL 5015)SS = 316 STAINLESS STEEL

    CERTIFICATIONA = NONE - SAFE AREAIS = INTRINSICALLY SAFE - DUAL ATEX/IECEX EXIAD = FLAMEPROOF - DUAL ATEX/IECEX EXD

    PART NUMBER BREAKDOWN

    ELECTRICAL CONNECTIONM = M20 X 1.5 ISOUL = ½” NPT

    RANGE CODESELECT FROM MEASURING RANGE TABLE

    REQUIRED CALIBRATED RANGEPLEASE SPECIFY RANGE AND UNITS REQUIRED

    PROCESS CONNECTIONGB = G½” MALE (WITH 3MM BORE)GC = G½” MALE (WITH 12MM BORE)GA = G¼” MALE (MIN 10MBAR/ MAX 350BAR)N2 = ½” NPT MALE (WITH ¼” BSPP INTERNAL THREAD)F2 = ½” NPT FEMALE (VIA ADAPTER)(MAX. 690BAR)GD = G1” MALE WITH FLUSH DIAPHRAGM (MIN. 0.1/MAX. 70BAR)GF = G½” MALE WITH FLUSH DIAPHRAGM (MIN 2.5/ MAX 300 BAR)GFS =AS GF EXCEPT SPECIAL OPTION MAX. 1000BARX = CHEMICAL SEAL (SPECIFY REQUIREMENTS

    ACCESSORIES AND OPTIONSNA = NACE MR-01-75 CERTIFIED WETTED PARTSHA = HASTELLOY WETTED PARTS (GC,GD & *N2 CONNS ONLY) *MAX. PRESSURE 40 BARGP = GOLD PLATED DIAPHRAGM (NOT AVAILABLE RANGES 30 & 27)V = FULL VACUUM SUITABLE RANGES 8, 11,13, 17, 20 AND 23 (ALL OTHERS ARE VACUUM SUITABLE AS STANDARD)SP = 2” PIPE MOUNTING GRP SUNSHADEPC = ALUMINIUM PROTECTION COVER AGAINST VERTICAL IMPACT STRIKEST1 = EXTENDED COMPENSATION RANGE -40 TO +80°CT2 = EXTENDED COMPENSATION RANGE -60 TO 50°COXY = OXYGEN SERVICE (GB CONN ONLY) AL = UNIVERSAL WALL/2” PIPE MTG., BRACKET, ZINC PLATED STEELALS = UNIVERSAL WALL/2” PIPE MTG., BRACKET, 316 ST. STEELIP67 = IP67 (FOR EXIA AND SAFE AREA – EXD MODEL IS IP67 AS STD) SIL = SAFETY INTEGRITY LEVEL (SIL) 2MT = 316 ST. STEEL TAG

    PPSSC1083 | issue 2

    3 cc

    DIFFERENTIAL PRESSURETRANSMITTER

    These ‘smart’ differential pressure transmitters provide high accuracy pressure measurement incorporating 2 wire microprocessor based technology and are suitable for measuring differential pressure of gases, vapours and liquids.

    Local configuration can be carried out in the field via the pushbuttons inside the housing or from a remote point via the 2 wire 4 – 20mA line and communication via the HART® protocol.

    The measured pressure is indicated on the integral LCD display in selectable units and a 4 – 20mA output signal generated, directly or inversely proportional to the connected pressure line.

    The LCD display can be rotated within the housing to ensure the measured readout can be easily viewed regardless of the angle of installation.

    The active sensing element is a piezoresistant silicon sensor separated from the process medium by a metal diaphragm and a manometric fluid to provide highly accurate measurements.

    PYRD-2000ALW ATEX/ IECEx Exd or ExiaCERTIFIED OR INDUSTRIAL DIFFERENTIAL PRESSURE TRANSMITTER

    FEATURES

    DIFFERENTIAL PRESSURE TRANSMITTER

    Aluminium alloy or 316 st. steel housinga Local adjustment panel keysa

    Output: 4–20mA + HART® communicationa Integral LCD display a

    ATEX/IECEx Flameproof or Intrinsically Safea

    Accuracy ≤ +/- 0.075% (0.05% option)a

    Rangeability (up to) 25:1a

    Thermal drift is automatically compensated via a thermister integrated into the pressure sensor and this coupled with the high accuracy sensor ensures a precison measuring system which will satisfy the most demanding applications.

    The transmitters are suitable for hazard-ous or non-hazardous areas, the latter being certified either ATEX/IECEx Flameproof (Exd) or Intrinsically Safe (Exia).

    PAGE 9PYRD-2000

  • ATEX INTRINSICALLY SAFE IECEX INTRINSICALLY SAFE Ex II 1/2G Ex ia IIC T5/T6 Ex ia IIC T5/T6 Ga/GbIM1 Ex ia I Ma Ex ia IIB T5/T6 Ga/Gb (PTFE cable option)II 1D Ex ia IIIC T105°C Da Ex ia I Ma (316 st. steel housing) Ex ia IIIC T105°C DaATEX FLAMEPROOF II 1/2G Exia/d IIC T5/T6 Ga/Gb IECEX FLAMEPROOFII 1/2D Exia/t IIIC T85°C/T100°C Da/Db Ex ia/d IIC T5/T6 Ga/GbI M2 Exd ia I Mb Ex ia/IIIC T85°C/T100°C Da/Db Exd ia I MbSpecial conditions for safe use:• Only the components (spares) referenced in the O & M manual can be replaced.• The maximum (declared by the manufacturer) gap of the spigot joint designated in document as L4 is smaller

    than specified in EN 60079-1. Details are given in the O & M Manual

    CERTIFICATION

    The housing is available in epoxy painted aluminium alloy ideally suited for industrial environments or 316 stainless steel suitable for offshore or corrosive environments.

    The ingress protection level is IP66 on Exia and non Ex versions (IP67 optional), and IP67 on Exd, to BS EN 60529:1992.

    Wetted parts are in 316L stainless steel as standard (to NACE MR-01-75) with the option of a Hastelloy C276 diaphragm.

    When neither of these materials meet the process requirements either for reasons of chemical incompatibility or temperature being outside permitted limits we can offer a range of diaphragm seals or chemical seals either for direct mounting on the transmitter or remote via stainless steel capillary (for details of these seals please contact our sales office).

    RANGE CODE

    23

    19

    14

    11

    20

    47

    45

    42

    44

    NOMINAL MEASURING RANGE

    (FSO)

    0 – 70 Bar

    0 – 16 Bar

    0 – 2.5 Bar

    0 – 1 Bar

    0 – 0.25 Bar

    -0.5 to +0.5 Bar

    -100 to +100 mBar

    -5 to 70 mBar

    -25 to +25 mBar

    7 Bar

    1.6 Bar

    0.2 Bar

    50mBar

    10 mBar

    100 mBar

    10 mBar

    4 mBar

    2 mBar

    MINIMUM CALIBRATED RANGE

    RANGEABILITY

    10:1

    10:1

    12.5:1

    20:1

    25:1

    10:1

    20:1

    18:1

    25:1

    OVERPRESSURELIMIT

    C – Kidney flange manifold type

    pressure housing - 250 Bar (std), option for 320 and 420 Bar.

    N4 – In line type pressure housing 40 Bar (except range 23

    which is 70 Bar)

    C – type 200 Bar; N4 – type 40 Bar

    MEASURING RANGE TABLE

    Note: Other Nominal Measuring Ranges are available, please contact Pyropress Sales Office with your particular requirements.

  • UNF (standard)

    PAGE 11 PYRD-2000

  • FUNCTIONALOutput 4 – 20mA, 2 wire with Hart® Rev 5.1 digital communication protocol.Power supply Industrial (non Ex) 10 – 55 Vdc Intrinsically safe Exia 10.5 – 28 Vdc Flameproof Exd 13.5 – 45 Vdc Display Main 5 digit LCD display of pressure in user selectable units with 2 x smaller displays, one for process in mA or % and one for transmitter information e.g. setting options and transmitter error codes. Rangeablity/Turndown Up to 25:1Damping Adjustable from 0 – 60 secondsZero and Span Adjustable via local internal buttons or HART® digital communication.Failure alarm In the event of sensor or circuit failure, self diagnostics drives the output to 3.6mA (downscale) or 22mA (upscale) according to choice.

    PERFORMANCETurn on time Fully functional within 2 seconds of power being applied.Accuracy ≤ +/- 0.075% of the calibrated range when between 30 – 100% of the transmitter nominal range (with increased accuracy option of ≤ +/- 0.05% if required).Long term stability Stated accuracy is guaranteed for a minimum of 3 years.Thermal effect ≤ +/- 0.05% (FSO)/10°C Max. +/- 0.25% (FSO) across the whole thermal compensation range Thermal compensation -25 to +80°CPower supply effect 0.002% (FSO)/VResponse time 16 – 480ms (programmable)SIL 2 option In accordance to IEC 61508/61511 ENVIRONMENTAL and EXTERNAL PARAMETERSIngress protection Intrinsically safe Exia and non Ex models – IP66 (with IP67 option). Flameproof Exd – IP67 (standard)Ambient temperature Industrial (non Ex) -25 to 85°C (-40 to 85°C – special option) Intrinsically safe Exia -25 to 80°C Flameproof Exd -25 to 75°C Process temperature limits -40 to 120°C (non freezing).Humidity (RH) Maximum 98% non condensingEMC immunity EN 61326-1 and EN 61000-6-2:2005Shock protection level EN 60068-2-27, 50g/11ms Vibration protection level EN 60068-2-6, test Fc; up to 1.6mm for 2 - 25Hz, up to 4g for 25 - 100Hz

    CONSTRUCTIONHousing Aluminium alloy (blue epoxy painted) or 316 stainless steel.Wetted parts 316L (Hastelloy C276 diaphragm option) (Gold plated diaphragm option available for hydrogen applications).Fill liquid Silicon (standard) and inert fill (oxygen service).Electrical entry M20 x 1.5 ISO (std) or ½” NPT option via adapter (brass for the aluminium housing and 316 st. steel for the st. steel housing)Available accessories 316 st. steel 3 or 5 valve manifolds (loose or integral) Mounting brackets for wall or 2” pipe (plated or 316 st. steel) Chemical/diaphragm seals in various materials to suit the application.

    TECHNICAL SPECIFICATION

  • Our products are designed to work in demanding and hazardous environments which require fast and cost effective solutions in instrumentation

    and control. Pyropress control sensors provide safe and

    reliable electrical switching of alarm or control circuits in response to changes in temperature, pressure, differential

    pressure,vacuum, fluid, flow and level conditions.

    ABOUTPYROPRESS QUALITY

    To support the design of state of the art products the company has invested heavily in the latest CNC technology.

    We are able to produce our own components to a high degree of aaccuracy assuring a reliable and

    consistent quality product.

    T: +44 (0)1752 333933 | [email protected] www.pyropress.com

    P Y R D - 2 0 0 0 A L W / S S / I S / 1 4 / 0 - 1 B a r / C 7 / 1 6 / M / N A / A L S

    COMMON BASE NO.

    HOUSING MATERIAL A = CAST ALUMINIUM ALLOY (EPOXY PAINTED BLUE TO RAL 5015)SS = 316 STAINLESS STEEL

    CERTIFICATIONA = NONE - SAFE AREAIS = INTRINSICALLY SAFE - ATEX/IECEX EXIAD = FLAMEPROOF - ATEX/ IECEX EXD

    PART NUMBER BREAKDOWN

    ELECTRICAL CONNECTIONM = M20 X 1.5 ISOUL = ½” NPT

    RANGE CODESELECT FROM MEASURING RANGE TABLE

    REQUIRED CALIBRATED RANGEPLEASE SPECIFY RANGE AND UNITS REQUIRED

    PROCESS CONNECTIONC7/16” = 316L KIDNEY FLANGE MANIFOLD WITH 7/16” UNF BOLT HOLES (STD)C = 316L KIDNEY FLANGE MANIFOLD WITH M10 BOLT HOLESN4 = IN LINE PRESSURE HOUSING WITH 2 X ¼” NPT FEMALE CONNSGA = IN LINE PRESSURE HOUSING WITH 2 X G¼” MALE CONNSGB = IN LINE PRESSURE HOUSING WITH 2 X G½” MALE CONNSX = CHEMICAL SEAL (SPECIFY REQUIREMENTS)

    ACCESSORIES AND OPTIONSC32 = 320 BAR OVERPRESSURE OPTIONC42 = 420 BAR OVERPRESSURE OPTIONNA = NACE MR-01-75 CERTIFIED WETTED PARTSHA = HASTELLOY DIAPHRAGMGP = GOLD PLATED DIAPHRAGM T1 = EXTENDED COMPENSATION RANGE -40 TO +80°COXY = OXYGEN SERVICE AL = UNIVERSAL WALL/2” PIPE MTG., BRACKET, ZINC PLATED STEELALS = UNIVERSAL WALL/2” PIPE MTG., BRACKET, 316 ST. STEELBCZ = WALL/2” PIPE MTG. BRACKET, ZINC PLATED STEEL FOR C TYPE PROCESS CONNECTIONBCS = WALL/2” PIPE MTG. BRACKET, 316 ST. ST FOR C TYPE PROCESS CONNECTIONBF = 25MM PIPE BRACKET, 316 ST. ST. FOR N4/GA/GB IN LINE VERSIONIP67 = IP67 (FOR EXIA AND SAFE AREA – EXD MODEL IS IP67 AS STD) SIL = SAFETY INTEGRITY LEVEL (SIL) 2MT = 316 ST. STEEL TAGVM-3 = INTEGRAL 316 ST. ST 3 VALVE MANIFOLD, ½” NPT CONNSVM-5 = INTEGRAL 316 ST. ST 5 VALVE MANIFOLD, ½” NPT CONNSSP = 2” PIPE MOUNTING GRP SUNSHADEPC = ALUMINIUM PROTECTION COVER AGAINST VERTICAL IMPACT STRIKES

    PPSSC1084 | issue 2PAGE 13

    PYRD-2000

  • 3 cc

    TEMPERATURETRANSMITTER

    These ‘smart’ temperature transmitters provide high accuracy temperature measurement incorporating microprocessor based technology and are suitable for measuring temperatures from -200 to +550°C depending on the element incorporated.

    Local configuration can be carried out in the field via the pushbuttons inside the housing or from a remote point via the 2 wire 4 – 20mA line and communication via the HART® protocol.

    The measured temperature is indicated on the integral LCD display in selectable units and a 4 – 20mA output signal generated, directly or inversely proportional to the measured temperature.

    The LCD display can be rotated within the housing to ensure the measured readout can be easily viewed regardless of the angle of installation.

    The transmitters are suitable for hazardous or non-hazardous areas, the former being certified either ATEX Flameproof (Exd) or Intrinsically Safe (Exia).

    The housing is available in epoxy painted aluminium alloy ideally suited for industrial environments or 316 stainless steel suitable for offshore or corrosive environments.

    PYRT-2000ALW ATEXExd OR Exia CERTIFIED OR INDUSTRIAL TEMPERATURE TRANSMITTER

    TEMPERATURETRANSMITTER

    The ingress protection level is IP66 on Exia and non Ex versions (IP67 optional), and IP67 on Exd, to BS EN 60529:1992

    The sensing probe is manufactured from 6mm OD stainless steel tube with fixed or adjustable insertion fittings in ½” BSPP or ½” NPT (other options are available on request).

    Thermowells can be manufactured from barstock, one piece forgings or fabricated from stainless steel tube.

    Depending on the application, the process medium and/or the environmental conditions the thermowells can be produced in a wide range of materials including 316L stainless steel, Inconel®600, Hastelloy® C276 and Hastelloy®C22 (other materials are available on request). FEATURES

    Aluminium alloy or 316 st. steel housinga PT100 or Type K elementa

    ATEX Flameproof or Intrinsically Safe a Integral LCD displaya

    Output: 4–20mA + HART® communicationa Spring loaded sensora

    PAGE 15PYRT-2000

  • TECHNICAL DATACONSTRUCTIONHousing Aluminium alloy (blue epoxy painted) or 316 stainless steel.

    Sensor probe 6mm OD 321 stainless steel (316SS option) with ½” BSPP or NPT fitting.

    Thermowells Available in 316, 316L (NACE), Inconel® 600, Hastelloy® C276 and Hastelloy® C22 (other materials available on request).

    Electrical entry M20 x 1.5 ISO (std) or ½” NPT option via adapter (brass for the aluminium housing and 316 st. steel for the st. steel housing)

    FUNCTIONALOutput 4 – 20mA, 2 wire with Hart® Rev 5.1 digital communication protocol. Minimum resistance required for communication (Hart®) – 240 Ω

    Power supply Industrial (non Ex) and Flameproof 12 – 55 Vdc Intrinsically safe Exia 13.5 – 28 Vdc

    Display Main 5 digit LCD display of pressure in user selectable units with 2 x smaller displays, one for process in mA or % and one for transmitter information e.g. setting options and transmitter error codes.

    Damping Adjustable from 0 – 60 seconds

    Zero and Span Adjustable via local internal buttons or HART® digital communication.

    Failure alarm In the event of sensor or circuit failure, self diagnostics drives the output to 3.8mA (downscale) or 23mA (upscale) according to choice.

    PERFORMANCETurn on time Fully functional within 2 seconds of power being applied.Nominal Ranges PT100 sensor: -200 to +550°C / Type K sensor: -40 to +550°C *For GB type sensor probe -50 to +150°C Min. Set Range Span 10°C

    ENVIRONMENTAL and EXTERNAL PARAMETERS

    Ingress protection Exia and non Ex models – IP66 (with IP67 option). Exd – IP67 (standard)Ambient temperature Industrial (non Ex) -40 to 85°C Intrinsically safe Exia -40 to 80°C Flameproof Exd -40 to 75°C (T5) , -40 to 45°C (T6) Minimum immersion length L = 100mmHumidity (RH) Maximum 98% non condensingEMC immunity EN 61326-1.2 for industrial applications.Shock protection level EN 60068-2-27, 50g/11ms Vibration protection level EN 60068-2-6, test Fc; up to 1.6mm for 2 - 25Hz, up to 4g for 25 - 100Hz

    CERTIFICATION ATEX Flameproof ATEX Intrinsically Safe II 1/2G Exia/d IIC T* Ga/Gb ExII 1/2G Ex ia IIC T5/T6 II 1/2D Exia/t IIIC T* Da/Db I M1 Exia I Ma (with 316SS housing) I M2 Exd ia I Mb II 1D Exia IIIC T105°C Da

    Analogue output – addit error +/-0.04% x z Where:“ta” = Absolute value of the measured temperature in °C“t” = Value of the measured temperature in °C“z” = Transmitter set range

    Error (digital value)

    +/- 0.05 + (0.05% x z) + (0.001 x ta)°C for PT100 sensor.+/- 0.05 + (0.05% x z)°C for Type K sensor and t ≤ 375°C+/- 0.05 + (0.05% x z) + ((0.002 x (t – 375))°C for Type K sensor and t > 375°C.

  • THERMOWELL TYPE

    OG2.9

    OG2.11

    T1

    SW1 SW2

    SW1T SW2T

    SW1G SW2G

    0[mm]

    9

    11

    11

    18 24

    18 24

    18 24

    100, 160, 250, 400

    100, 160, 250, 400

    100, 160, 250, 400

    100 140 200

    100 140 200

    100 140 200

    L[mm] I[mm]

    -

    -

    -

    35 65 65

    35 65 65

    35 65 65

    STANDARD PROCESS

    CONNECTIONS(OTHERS AVAILABLE)

    G1/2”, G3/4”, 1/2”NPT

    G1/2”, G3/4”, 1/2”NPT

    Flange according to DIN and ANSI

    -

    Flange according to DIN and ANSI

    G1/2” G3/4”,

    STANDARD THERMOWELL DATA

    STANDARD DIMENSIONS OF THERMOWELL THERMOWELLMATERIALS

    316L SS

    316L SS

    316L SS

    316L SS

    316L SS

    316L SS

    140 200

    140 200

    140 200

    65 65

    65 65

    65 65

    (std)

    (std)

    Size threads in below table

    Across Flats

    PAGE 17PYRT-2000

  • Our products are designed to work in demanding and hazardous environments which require fast and cost effective solutions in instrumentation

    and control. Pyropress control sensors provide safe and

    reliable electrical switching of alarm or control circuits in response to changes in temperature, pressure, differential

    pressure,vacuum, fluid, flow and level conditions.

    ABOUTPYROPRESS QUALITY

    To support the design of state of the art products the company has invested heavily in the latest CNC technology.

    We are able to produce our own components to a high degree of aaccuracy assuring a reliable and

    consistent quality product.

    T: +44 (0)1752 333933 | [email protected] www.pyropress.com PPSSC1085 | issue 2

    Full Model Coding No. PYRT-2000ALW/A/D/GN/OG2.9/G½/L=100mm/PT100/0-350°C/23mA/M/MT

    Common Base No.

    Housing Material Cast aluminium alloy (expoxy painted) A316 stainless steel SSCertificationNone - safe area AIntrinsically Safe - ATEX Exia ISFlameproof - ATEX Exd D Probe type GB or GN (GN extension for temps 150°C)Thermowell type – from table (i.e. OG2.9, OG2.11, T1, SW1 etc) Thermowell thread or flange detail (i.e. G½, ½” NPT, flange spec. etc)

    Immersion or thermowell “U” dims (in mm)

    Element type (PT100 or K)

    Calibrated range

    Failure Alarm signal - 3.8mA / 23mA

    Electrical ConnectionM20 x 1.5 ISO M½” NPT UL

    Accessories and OptionsIP67 (for Exia and safe area – Exd model is IP67) IP67 316 st. steel tag MT2” pipe mounting GRP sunshade SPAluminium protection cover againstvertical strikes PC

  • 3 cc

    PRESSURETRANSMITTER

    The PYRP-28 pressure transmitter is suitable for the measurement of pressure, vacuum and absolute pressure of gases, vapours and liquids for industrial and hazardous area (Exia) applications for -1 to 1000 Bar.

    • Ranges from 0-25 mBar up to 0-1000 Bar

    • 4 - 20 mA two-wire or 0 - 10 V output

    • ATEX Intrinsically Safe (Gas and Dust) certification

    • Low-voltage version with ATEX certificate available

    • Gold plated diaphragm option > 60 Bar

    Calibration

    Potentiometers can be used to adjust the zero position and the range by up to ±10% without altering the settings.

    Installation

    The active sensing element is a piezoresistant silicon sensor separated from the medium by a diaphragm. The electronics are housed in a casing with a degree of protection IP-65 or IP-67 depending on the type of electrical connection provided.

    II 1/2G Ga/Gb Ex ia IIC T4/T5/T6

    I M1 Ex ia I

    II 1DEx ia D20 T105C

    PYRP-28 INDUSTRIAL &INTRINSICALLY SAFE PRESSURE TRANSMITTER

    PRESSURE TRANSMITTER

    Installation

    The transmitter can be installed directly on the installation.When the pressure of steam or other hot media is measured, a siphon or impulse line should be used.

    When special process connections are required for measurement of levels and pressures (e.g. food and chemical industries) the transmitter can be provided with a diaphragm seal. Installing accessories and a full scope of diaphragm seals are detailed in separate literature.

    Transmitters for hazardous area applications

    ATEX Intrinsically Safe versions are available for measurements in areas where explosive gases and dusts are present.

    PAGE 19PYRP-28

  • PYRP-28 transmitter with PD type electrical connection• Degree of protection

    IP-65• Angle electrical

    connector• DIN 43650• When the connector

    is removed both zero point adjustment and range setting potentiometers are accessible

    PYRP-28 transmitter with PZ type electrical connection• Degree of protection

    IP-66• Stainless steel

    electrical housing with M20x1.5 packing gland

    • When the box is opened both zero point adjustment and range setting potentiometers are accessible

    PYRP-28 transmitter with PK type electrical connection• Degree of protection

    IP-67• Cable electrical

    connection, contact with the atmosphere through the capillary inside the cable. Standard cable length is 3M, (other cable lengths are available)

    PYRP-28 transmitter with PM12 type electrical connection• Degree of protection

    IP-67• Electrical connection

    with thread M12x1, contact with the atmosphere through the capillary inside the cable. Standard cable length is 3M (other cable lengths are available)

    Overpressure Limit(repeated, without hysteresis)

    Burst pressure

    Accuracy

    Long term stability

    Thermal error

    100 mBar

    1 Bar

    2 Bar

    0.3%

    0.2% / year

    Typically 0.3% / 10°CMax 0.4% / 10°C

    Measuring range 400mBar

    2.5 Bar

    5 Bar

    0.2% (0.16% - special version)

    0.1% / year

    0-1 bar to 1000 Bar

    4 x rangeMax 1200 Bar

    8 x rangeMax 2000 Bar

    Typically 0.2% / 10°CMax 0.3% / 10°C

    Technical Data 0-25 mBar to 0-1000 Bar (pressure, vacuum) 400 mBar - 80 Bar (absolute pressure)

    Any measuring ranges within the above spans can be supplied.

  • GF TypeG1/2˝ with flush diaphragmWetted parts material:316 Stainless steelApplicationSuitable for measuring the pressure of viscous and contaminated mediaMin range: 2.5 BarMax range: 300 BarSpecial option: Max. 1000BAR GFS Type

    GB TypeG1/2˝, Ø3 hole316 Stainless steelApplicationSuitable for measuring thepressure of uncontaminated gases, vapours and liquidsMax range: 1000 Bar

    RG TypeG1/2˝ with radiator316 Stainless steelApplicationSuitable for measuring thepressure of uncontaminated gases, vapours and liquids at temperatures up to 170°C with no impulse line.Min range: 160 mBarMax range: 40 Bar

    GC TypeG1/2˝, Ø12 hole316 Stainless steel orHastelloy C-276 optionApplicationSuitable for measuringthe pressure of viscousand contaminated mediaMax range: 400 Bar

    GA TypeG1/4”Wetted parts materials:316 Stainless steelApplicationSuitable for measuringthe pressure of viscousand contaminated mediaMax range: 400 Bar

    GD TypeG1˝ with flush diaphragmWetted parts material:316 Stainless steel orHastelloy C-276 optionApplicationSuitable for measuringthe pressure of viscousand contaminated mediaMin range: 100 mBarMax range: 70 Bar

    N2 Type1/2˝NPT, internal thread G1/4”Wetted parts materials:316 Stainless steelApplicationSuitable for measuring thepressure of uncontaminated gases, vapours and liquidsMax range: 1000 Bar

    3

    PAGE 21PYRP-28

  • Measuring rangein relation to4-20mA or voltageoutput

    Model Description

    PYRP-28 Pressure transmitter

    -3...............0 - 25 mBar-4...............0 - 40 mBar-5...............0 - 60 mBar-6...............0 - 100 mBar-7...............0 - 160 mBar-8...............0 - 250 mBar-9...............0 - 400 mBar-10.............0 - 600 mBar-11.............0 - 1 Bar-X ..................... Customer specified - select nearest range and suffix “X”

    -12.............0 - 1.6 Bar-14.............0 - 2.5 Bar-15.............0 - 4 Bar-16.............0 - 6 Bar-18.............0 - 10 Bar-19.............0 - 16 Bar-20.............0 - 25 Bar-21.............0 - 40 Bar-22.............0 - 60 Bar

    -24.............0 - 100 Bar-25.............0 - 160 Bar-26.............0 - 250 Bar-28.............0 - 400 Bar-29.............0 - 600 Bar-30.............0 - 1000 Bar-51.............0 to -1 Bar

    Casing and electricalconnections

    -PD.........-PDS......-PZ.........-PS.........-PM.........-PK.........

    304 Stainless steel housing IP65 with DIN43650 connector316 Stainless steel housing IP65 with DIN43650 connector304 Stainless steel housing IP66 with M20 electrical connection316 Stainless steel housing IP66 with M20 electrical connectionHousing IP67 with M12x1 threaded connector304 Stainless steel housing IP67 with cable connection (3M standard)If other cable length is required please specify as PK5 for 5M etc

    Process connections-GB.........-GC.........-GF.........-GFS.......-RG.........-GD.........-GA.........-N2.........-F2...........-X............

    G1/2” Male with 3mm boreG1/2” Male with 12mm boreG1/2” Male with flush diaphragm - Min. 2.5/Max. 300BarAs GF except rated for 1000Bar Max.G1/2” Male with cooling radiator up to 170°C - Min. 160mBar/Max. 40BarG1” Male with flush diaphragm - Min. 0.1/ 60 Bar- HA: Hastelloy wetted parts with GC, GD and NZ process connections(N2 option Max. 40Bar)- SIL: Suitable for use within SIL1 systems- PC: Wall mounting bracket

  • Our products are designed to work in demanding and hazardous environments which require fast and cost effective solutions in instrumentation

    and control. Pyropress control sensors provide safe and

    reliable electrical switching of alarm or control circuits in response to changes in temperature, pressure, differential

    pressure,vacuum, fluid, flow and level conditions.

    ABOUTPYROPRESS QUALITY

    To support the design of state of the art products the company has invested heavily in the latest CNC technology.

    We are able to produce our own components to a high degree of aaccuracy assuring a reliable and

    consistent quality product.

    T: +44 (0)1752 333933 | [email protected] www.pyropress.com PPSSC1086 | issue 2

    Output signal

    4...20 mA, two wire transmission

    0...10 VDC

    Power supply

    8 - 36VDC (Ex 9 - 28V)

    13 - 30VDC (output 0 - 10V)

    Load resistance R [Ω] ≤(for current output)

    Error due to supply voltage changes0.005%/V)

    Wetted parts316 Stainless steel - (Hastelloy C-276 and gold plated options)

    Casing304 Stainless steel (316 Stainless steel option)

    Usup [V] - 8V

    0.02A

    Hysteresis, repeatability 0.05%Response time

  • 3 cc

    DIFFERENTIAL PRESSURETRANSMITTER

    The PYRD-28 transmitter is suitable for the measurement of differential pressure of gases, vapours and liquids.

    Construction

    The active element is a piezoresistance silicon sensor separated from the medium by a 316L Stainless Steel diaphragm. The special design of the active sensing element ensures it can withstand the pressure surges and overloads of up to 320 Bar. The electronics are housed with a degree of protection to IP65 or IP67 depending on the type of electrical connection supplied.

    Calibration

    Potentiometers can be used to adjust the zero position and the range by up to 10% without altering the settings.

    Installation

    The transmitter with P type process connection can be installed directly onto impulse lines or wall or pipe mounted (25mm Ø) using BF mounting bracket.

    The C type process connection can be fitted directly to a 3 or 5 valve manifold. Transmitters without a valve manifold can be fitted in any position on a 2” pipe or on a wall using the BCZ or BCS mounting bracket.

    PYRD-28 INDUSTRIAL &INTRINSICALLY SAFE DIFFERENTIAL PRESSURE TRANSMITTER

    FEATURES

    DIFFERENTIALPRESSURE TRANSMITTER

    Accuracy 0.25%a ATEX Intrinsically safe (Gas and Dust)a

    Overloads up to 420 Bar total pressurea Any range from 0-25 mbar up to 0-25 Bara

    Materials:

    Wetted parts: Type P process conn. 316 Stainless Steel Type C process conn. 316 Stainless Steel

    Diaphragm: 316L Stainless Steel (Hastelloy C276 or gold plated options)

    Casing: 304 Stainless Steel (316 Stainless Steel Option)

    Technical Data

    Hysteresis, repeatability: 0.05%

    Thermal compensation range: 0 - 70°C

    Operating temperature range: -25 to +80°C

    Medium temperature range: -25 to +120°C (direct measurement)

    Over 120°C - measurement with the use of impulse line or diaphragm seals

    PAGE 25PYRD-28

  • Measuring rangein relation to4-20mA or voltageoutput

    Model Description

    PYRD-28 Differential pressure transmitter

    -3...............0 - 25 mBar-4...............0 - 40 mBar-5...............0 - 60 mBar-6...............0 - 100 mBar-7...............0 - 160 mBar-8...............0 - 250 mBar

    -9...............0 - 400 mBar-10.............0 - 600 mBar-11.............0 - 1 Bar-12.............0 - 1.6 Bar-14.............0 - 2.5 Bar-15.............0 - 4 Bar

    -16.............0 - 6 Bar-18.............0 - 10 Bar-20.............0 - 25 Bar-X...............Non Standard

    Casing and electricalconnections

    -PD......-PDS....-PZ......-PS......-PK......

    -PM......

    304 Stainless steel housing. IP65 with DIN43650 plug and socket connector316 Stainless steel housing. IP65 with DIN43650 connector304 Stainless steel housing. IP66 with M20 electrical connection316 Stainless steel housing. IP66 with M20 electrical connection304 Stainless steel housing. IP67 with cable connection. (3 metres standard)If other cable length is required please specify as PK5 for 5 metres etc.304 stainless steel housing. IP67 with M12x1 thread and connector

    Process connections

    -GB...-N4....-GA...-C 7/16

    -CR.....-X......

    G1/2” Male in line type - SS316 wetted parts1/4” NPT Female in line type - SS316 wetted partsG1/4” Male in line type - SS316 wetted partsManifold flange, SS316L wetted parts with 316 stainless steel diaphragm and 2 x 1/4” NPT female process connectionsC 7/16 type process rotated through 90°Diaphragm seal

    40 Bar max40 Bar max40 Bar max250 Bar with 320 & 420 Bar option

    Options

    -IS

    -BCZ-BCS-BF-VDC-HA-AU

    Ex II 1/2G Ga/Gb Ex ai IIC T4/T5/T6, I M1 Ex ia I, II 1D Ex ia D20 T105COnly for transmitters with 4 - 20mA output2” pipe & wall mounting bracket for process connection “C” zinc plated steel2” pipe & wall mounting bracket for process connection “C” stainless steel25mm pipe mounting bracket for attaching for process connection “P”0 - 10 V DC output - Power supply 15 - 36 V DCHastelloy C276 DiaphragmGold Plated Diaphragm

    Transmitter PYRD-28Process connection GA type1/4” BSPP male connsStatic pressure limit 40 bar

    Transmitter PYRD-28Version with N4 type process connection. Static pressure limit 40 bar

    Transmitter PYRD-28 – version with type C and CR process connection to be mounted together with a valve manifold. Static pressure limit 250 or 320 bar

  • Our products are designed to work in demanding and hazardous environments which require fast and cost effective solutions in instrumentation

    and control. Pyropress control sensors provide safe and

    reliable electrical switching of alarm or control circuits in response to changes in temperature, pressure, differential

    pressure,vacuum, fluid, flow and level conditions.

    ABOUTPYROPRESS QUALITY

    To support the design of state of the art products the company has invested heavily in the latest CNC technology.

    We are able to produce our own components to a high degree of aaccuracy assuring a reliable and

    consistent quality product.

    T: +44 (0)1752 333933 | [email protected] www.pyropress.com PPSSC1087 | issue 2

    Output signal

    4...20 mA, two wire transmission

    0...10 V, three wire transmission

    Power supply

    8 - 36 V DC (Ex 9...28V)

    - two wire transmission

    13 - 30 V DC - three wire transmission

    Load resistance R [Ω] ≤(for current output)

    Load resistance R 20 ≥ kΩ(for supply output)

    Error due to supply voltage changes0.005% (FSO) / 1V

    Usup [V] - 8V

    0.02A

    Overpressure LimitStatic Pressure Limit(repeated, without hysteresis)

    Any measuring range0 -25 mBar to 0 - 25 Bar

    Measuring Range

    100 mBar 1 Bar 2 Bar 25 Bar

    250 Bar (option 320 and 420 Bar)(40 Bar for inline type process connection)

    0.4% 0.25%

    0.2% / year 0.1% / year

    Typically 0.3% / 10°CMax 0.4% / 10°C

    Typically 0.2% / 10°CThermal error

    Accuracy

    Long term stability

    Zero shift error for static pressure* 0.1% / 10 Bar* Applying static pressure & zeroing 0.1% / 10 Bar the transmitter can eliminate this error

    PAGE 27PYRD-28

  • P7.*Printed 11/2017. ©2017 Pyropress.

    All rights reserved. PPSSC1089 issue 2

    Pyropress Engineering,Bell Close, Plympton, Plymouth, Devon, PL7 4JH, EnglandSales : +44 (0)1752 333933 | Admin : +44 (0)1752 333939 | Fax : +44 (0)1752 [email protected] | www.pyropress.com

    Distribution partners *(at time of print - full details on website)

    DENMARK - Tormatic AS

    FRANCE - AI2C sas

    INDONESIA - Farnam Oil & Gas Sdn Bhd

    ITALY

    KOREA

    KUWAIT

    INDIA

    MALAYSIA

    NETHERLANDS

    NORWAY

    OMAN

    ONLINE SALES (EUROPE)

    SAUDI ARABIA

    SINGAPORE

    SPAIN

    TURKEY

    UAE – Dubai, Sharjah

    UAE – Abu Dhabi, Al Ain

    UNITED KINGDOM

    USA (LA, OK & TX)

    - Eisenbau S.r.l

    - Smar tline Ltd

    - ESCO Trading Ltd

    - Spectrum Offshore & Onshore Services PVT Ltd- Farnam Oil & Gas Sdn Bhd

    - PandID B.V.

    - Tormatic AS

    - Vanguard Engineering & Oilfield services

    - Valves Online Ltd

    - Al Mutawa Instruments

    - Baypore Private Ltd

    - Hispa Controls

    - Ram Olcu Ve Kontrol Sistemleri Dis Ticaret Ltd Sti.

    - Omega Engineering

    - Peninsula Engineering Services

    - Fluidic Ltd. - North West UK, Scotland and Nuclear related projects

    - Process Instrument Sales - East UK

    - Pyropress Engineering - All other areas

    - Protos Inc.

    (Full details of above companies can be found on our website)