sequential timer modul st6m1

Upload: ricky-ocktavi-rizky

Post on 03-Jun-2018

399 views

Category:

Documents


36 download

TRANSCRIPT

  • 8/11/2019 Sequential Timer modul ST6M1

    1/3

    EAPLModel ST- 6M1

    ST-6M1 SEQUENTIAL TIMER WITH 6 CHANNELSwww.eaplindia.com

    DIMENSION

    FRONT VIEW

    FUNCTIONOn power application and shorting of S1 & S2terminals, the timing sequence of the 1st channel isinitiated by switching On RLY0 and ontime starts.

    After completion of ontime of RLY0 offtime starts.After completion of the offtime of RLY0, RLY1 comesON and ontime starts followed by offtime, this cyclecontinues for rest of the sequences.

    A1,A2 : Source

    S1-S2 : Start signal for a minimum of 150mS.

    C1-C2 : SHORT Single cycle operation(i.e timerstops at the end of one cycle)

    OPEN Cyclic operation (i.e. timercontinues to operate).

    O1-O2: Cycle Complete Output. This output isavailable after completion of 1 cycle in single cycleoperation mode (C1-C2 shorted).

    I1-I2 : Time Pause Input. By shorting theseterminals timing is temporarily stopped and relaystatus maintained, again by opening timingcontinues.

    COPY : SHORT First channel shall be copied toall 10 channels during program mode.

    OPEN Individual channel shall be

    programmed with different values.

    HOLD MODE: Continue the timing after resumptionof interrupted power.

    RESTART MODE: After the resumption of interruptedpower operation starts from the sequence 0 or waitsfor the start signal if C1C2 is shorted.

    DOC NO.: OD RS YN 18000 0 REV NO.: 00 Dtd: 13/06/13

    Page 1 of 3

    INSTRUCTION MANUAL

  • 8/11/2019 Sequential Timer modul ST6M1

    2/3

    Programming Instruction:

    Timing Example:-CHNL 3 : ONTIME 39.50Min

    OFFTIME 45.30Sec

    Slide RUN/PROG switch to PROG mode; Sequencedisplay shows 0,ON LED glows, Previouslyprogrammed timing & range is displayed.

    Press SEQUENCE button till display shows 3.ON TIME: -

    Press RANGE button till MIN SEC LED glows. Press SELECT button, MSD starts flashing. Press ADVANCE till display shows 3, press

    SELECT again; 2nd

    digit starts flashing. Press ADVANCE till display shows 9. Press SELECT again; 3

    rddigit starts flashing.

    Press ADVANCE till display shows 5. Press SELECT again; 4

    thdigit (LSD) starts flashing.

    Press ADVANCE till display shows 0. Press SELECT again; the SET value is saved in

    memory depending on the selection of COPYterminals.

    OFF TIME:-

    Press ON/OFF switch to select OFF time (OFF LEDglows).

    Press RANGE button till SEC SEC LED glows. Press SELECT button, MSD starts flashing. Press ADVANCE till display shows 4. Press

    SELECT again; 2nd

    digit starts flashing. Press ADVANCE till display shows 5. Press SELECT again; 3

    rddigit starts flashing.

    Press ADVANCE till display shows 3.

    Press SELECT again; 4

    th

    digit (LSD) starts flashing0.

    Press SELECT again; the SET value is saved inmemory depending on the selection of COPYterminals.

    Slide RUN/PROG switch to RUN mode; now the timer is readyfor operation. Same procedure shall be followed for differentranges and for different timing requirement.

    Copy Channel Programming:

    Short copy terminals. Slide RUN/PROG switch to PROG mode. Program the required readings for ON & OFF (1stchannel) as per the

    programming instruction. 1stchannel program is copied to all the channels. Slide the Run/PROG switch back to RUN mode.

    STATUS

    TIMING INPROGRESS(TIP)

    TIMINGCOMPLETION(TC)

    OPERATINGCONDITION/MODE TIMING

    SEQUENCE RELAY LED RELAY LED

    ON TIME RLY1 ON ON - OFF

    SEQUENCE 0

    OFF TIME RLY1 OFF OFF - OFF

    ON TIME RLY2 ON ON - OFF

    SEQUENCE 1

    OFF TIME RLY2 OFF OFF - OFF

    ON TIME RLY3 ON ON - OFF

    SEQUENCE 2

    OFF TIME RLY3 OFF OFF - OFF

    ON TIME RLY4 ON ON - OFFSEQUENCE 3 & so

    on.

    OFF TIME RLY4 OFF OFF - OFF

    DOC NO.: OD RS YN 18000 0 Dtd: 13/06/2013 Page 2 of 3

  • 8/11/2019 Sequential Timer modul ST6M1

    3/3

    HINTS ON CORRECT USAGE

    Use proper gauge wires forconnections. Ensure all terminals are tightly

    screwed.

    Source Voltage should not exceedspecified limits. Itwill damage theunit beyond repair.

    CAUTION

    Shorting of S1-S2 shall be potential free;applying power to these terminals will damagethe timer permanently.

    DISPOSITION

    Once the product life is over, you maysend back the unit to EAPL fordisposition.

    TROUBLE ANALYSIS

    Timing not initiated.

    S1- S2 start signal shall beapplied.

    CONTACT

    Electronic Automation Pvt. Ltd#20, KHB Industrial areaNewtown YelahankaBangalore -106

    Ph:+91-80-28567561/2/42802345

    Email

    :[email protected]

    DOC NO.: OD RS YN 18000 0 Dtd: 13/06/2013 Page 3 of 3