ES-A-2000B-FP
Series 2000BM1-FP/ 2000BM2-FP Double Check Valve Assemblies shall be installed at referenced cross-connections to prevent the backflow of polluted water into the potable water supply. Only those cross-connections identified by local inspec-tion authorities as non-health hazard shall be allowed the use of an approved double check valve assembly.Check with local authority having jurisdiction regarding vertical orientation, frequency of testing or other installation requirements.These valves meet the requirements of ASSE Std. 1015 and AWWA Std. C510 and are approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California.
Series 2000BM1-FP/ 2000BM2-FPDouble Check Valve AssembliesSizes: 1" β 2" (25 β 50mm)
Job Name ββββββββββββββββββββββββββββββββββββββββββββ Contractor ββββββββββββββββββββββββββββββββββββββββββββ
Job Location ββββββββββββββββββββββββββββββββββββββββββ Approval ββββββββββββββββββββββββββββββββββββββββββββββ
Engineer βββββββββββββββββββββββββββββββββββββββββββββ Contractorβs P.O. No. βββββββββββββββββββββββββββββββββββ
Approval βββββββββββββββββββββββββββββββββββββββββββββ Representative βββββββββββββββββββββββββββββββββββββββββ
Ames Fire & Waterworks product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measure-ments, please contact Ames Fire & Waterworks Technical Service. Ames Fire & Waterworks reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on Ames Fire & Waterworks products previously or subsequently sold.
Pressure β TemperatureTemperature Range: 33Β°F β 140Β°F (0.5Β°C β 60Β°C) Maximum Working Pressure: 175psi (12.1 bar)
SpecificationsA Double Check Valve Assembly shall be installed at each noted location. The assembly shall consist of two positive seating check modules with captured springs and rubber seat discs. The check module seats and seat discs shall be replaceable. Service of all internal components shall be through a single access cover secured with stainless steel bolts. The assembly shall also include two resilient seated gear operated slow close isolation valves and four resilient seated test cocks. The assem-bly shall meet the requirements of ASSE Std. 1015 and AWWA Std. C510. Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California. Assembly shall be an Ames Fire & Waterworks Series 2000BM1-FP/ 2000BM2-FP.
Featuresβ’ Ease of maintenance with only one coverβ’ Top entryβ’ Replaceable seats and seat discsβ’ Modular constructionβ’ Compact designβ’ 1" β 2" (25 β 50mm) Cast bronze body constructionβ’ Low pressure dropβ’ No special tools requiredβ’ Gear operated, slow close shutoffsβ’ Pre-wired tamper switch (2) per shutoffβ’ Reversible Wiring Harness with Gear-Operated Ball Valvesβ’ GOBV Can be wired Normally Open or Normally Closed
Approvals β Standardsβ’ Approved by the Foundation for Cross-Connection Control and
Hydraulic Research at The University of Southern California (FCCCHR-USC)
β’ Horizontal and Vertical "Flow-Up" approved on all sizesβ’ ASSE 1048 Listedβ’ UL Classified (US & Canada)β’ FM Approvedβ’ IAPMO/cUPCβ’ AWWA Standard C510 Compliantβ’ CSA B64.5β’ NFPA 13, 14, 15, 16, 20, 22 & 24 Compliantβ’ End Connections Gear-Operated Ball Valves β National Pipe
Thread Taper ANSI/ASME B1.20.1
2000B-FPModels shown
1048 B64.51" - 2"
It is illegal to use this product in any plumbing system providing water for human consumption, such as drinking or dishwashing, in the United States. Before installing standard material product, consult your local water authority, building and plumbing codes.
WARNING!
Dimensions β Weights
MODEL SIZE DIMENSIONS WEIGHT
A B C D E F G H Iin. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kgs.
2000BM1-FP 1 25 131β4 337 41β2 114 31β2 89 1 25 71β2 191 53β4 146 27β8 73 27β8 73 143β8 365 12.2 5.52000BM2-FP 11β4 32 155β8 397 53β8 136 33β4 95 15β8 41 91β2 241 61β16 154 27β8 73 33β16 81 161β2 419 17.3 7.82000BM2-FP 11β2 40 163β8 416 55β8 143 4 102 15β8 41 93β4 248 61β4 159 27β8 73 33β8 86 17 432 19 8.62000BM1-FP 2 50 191β8 486 61β2 165 41β4 108 21β4 54 133β8 340 61β2 165 27β8 73 35β8 92 191β2 495 26.4 12
C H
D G
B F
IA
E
Strainer sold separately
CapacitiesAs compiled from documented Foundation for Cross-Connection Controland Hydraulic Research at the University of Southern California lab tests.*Typical maximum system flow rate (7.5 feet/sec., 2.3 meters/sec.)
βP
* kPa psi 110 16 83 12 69 10 55 8 41 6 28 4 14 2
0 5 10 15 20 25 30 35 40 45 50 55 60 gpm0 19 38 57 76 95 114 133 152 171 190 209 228 lpm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps
βP
* kPa psi 96 14 83 12 69 10 55 8 41 6 28 4 14 2 0 0
0 10 20 30 40 50 60 70 80 90 100 110 120 gpm0 38 76 114 152 190 228 266 304 342 380 418 456 lpm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps
kPa psi 83 12 69 10 55 8 41 6 28 4 14 2 0 0
βP 0 10 20 30 40 50 60 70 80 90 100 110 120 gpm0 38 76 114 152 190 228 266 304 342 380 418 456 lpm
5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps
*
βP
* kPa psi 83 12 69 10 55 8 41 6 28 4 14 2 0 0
0 25 50 75 100 125 150 175 200 gpm0 95 190 285 380 475 570 665 760 lpm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps
1" (25mm)
11β4" (32mm)
11β2" (40mm)
2" (50mm)
Pre
ssur
e Lo
ss
Pre
ssur
e Lo
ssP
ress
ure
Loss
Pre
ssur
e Lo
ss
Flow Rate
Flow Rate
Flow Rate
Flow Rate
NOTICEInquire with governing authorities for local installation requirements
ES-A-2000B-FP 1735 Β© 2017 Ames Fire & Waterworks
USA: Backflow Tel: (978) 689-6066 β’ Fax: (978) 975-8350 β’ AmesFireWater.comUSA: Control Valves Tel: (713) 943-0688 β’ Fax: (713) 944-9445 β’ AmesFireWater.com
Canada: Tel: (905) 332-4090 β’ Fax: (905) 332-7068 β’ AmesFireWater.caLatin America: Tel: (52) 81-1001-8600 β’ AmesFireWater.com
The information contained herein is not intended to replace the full product installation and safety information available or the experience of a trained product installer. You are required to thoroughly read all installation instructions and product safety information before beginning the installation of this product.
NOTICE