WARNINGS:•Do not assemble continuous run on the ground and lift into place. Joints will distort and not create a tight fit. Joining hardware will have to be purchased and replaced.
•Risk of electrical shock or fire, disconnect power during installation or servicing. Read all instructions completely before starting installation. Install and wire in accordance to all national and local codes by a certifi ed electrician. Fixture may be sharp, handle with care. Let fixture cool before main-tenance.
AVERTISSEMENTS •Risque d’électrocution ou d’incendie. Déconnectez l’alimenta-tion durant l’installation ou la maintenance. Lisez attentivement toutes les instructions avant de commencer toute installation. Faites installer et câbler selon les normes Nationales et Lo-cales par un électricien certifi é. Les installations peuvent être coupantes, à manipuler avec précaution. Laissez refroidir les installations avant une opération de maintenance.
ADVERTENCIA Riesgo de descarga eléctrica oun incendio, desconecte la alimentación durante la instalación o servicio. Leer todas las instrucciones completas antes de empesar la instalación. Instalar y cablear en acuerdo a las reglas nacionales y códigos locales por un electricista certifi cado. El accesorio puede estar agudo, agarre con cuidado deje que el acessorio. Enfriar antes
de mantenimiento.
Page 1DISTORT JOINT
Feb 2019
NULITE Lighting Inc. 10770 East 51st Avenue Denver, CO 80430 Phone (303) 287-9646 www.nulite-lighting.com
Lighting SyStem ComponentS
***Every luminaire will have a companion driver enclosure, not all luminaires and driver enclosures are the same, please be sure to pair the proper driver enclosure to the proper luminaire by reading the packaging labels***
Page 2
Installation InstructionsSero / Qub Pendant
RETROFIT CONSTRUCTION- INACCESSIBLE CEILING Mounting Option “GP”
Package Contents•Driver enclosure with bar hanger flange, remove for retrofit applications•Power Canopy Hardware Packet •(1) 5” diameter canopy •(1) Stainless Steel aircraft cable coupler •(1) 48” Plenum Rated Cord Sleeve •(1) 48” or 120” Aircraft Cable •(1) 8.25” Threaded Stem 1/4-20 (For Retrofit Only) •(1) 8.75” Threaded Stem 1/4-20 (New Con struction 5/8” Sheet Rock) •(1) 9.5” Threaded Stem 1/4-20 (for 1 1/4” sheet rock)
1. LUMINAIRE
1. CANOPY/ DRIVER ENCLOSURE
3. NON-POWER MOUNT HANGING HARDWARE
NON POWER
HARDWARE
Package Contents•Notes: Non-Power canopy hardware is only neces-sary for individual and row starter luminaires•Non-Power Canopy Hardware Packet •(1) 3” diameter canopy •(1) Stainless Steel aircraft cable coupler •(1) 48” or 120” aircraft cable
Package Contents•Luminaire•Includes factory installed 4 con-ductor low voltage power cord (48” Aircraft Cable = 78” Power Cord120” Aircraft Cable = 150” Power Cord)•Includes factory installed air-craft cable adjuster(s)
Feb 2019
NULITE Lighting Inc. 10770 East 51st Avenue Denver, CO 80430 Phone (303) 287-9646 www.nulite-lighting.com
Luminaire dimenSionSUnit Lengths
26 1/4” (667mm)
Individual
Continuous Row
Driver
Enclosure
50 1/4” (1276mm)
74 1/4” (1886mm)
98 1/4” (2496mm)
26 1/4” (667mm)
50 1/4” (1276mm)
74 1/4” (1886mm)
98 1/4” (2496mm)
Unit Lengths
26 1/4” (667mm)
Individual
Continuous Row
Driver
Enclosure
50 1/4” (1276mm)
74 1/4” (1886mm)
98 1/4” (2496mm)
26 1/4” (667mm)
50 1/4” (1276mm)
74 1/4” (1886mm)
98 1/4” (2496mm)
driver enCLoSure dimenSionS
Page 3
2 1/4”
4 1/4”
4 1/4”
2 1/4”
SERO
QuB
Installation InstructionsSero / Qub Pendant
RETROFIT CONSTRUCTION- INACCESSIBLE CEILING Mounting Option “GP”
3.51”5.39”
6.74”
2.5”
7.44”
6.74”
4.54”
6.35”8.0
9”
4.35”
6.35”
Feb 2019
5” Dia.
5” Dia.
NULITE Lighting Inc. 10770 East 51st Avenue Denver, CO 80430 Phone (303) 287-9646 www.nulite-lighting.com
inStaLLing an individuaL or row Starter Luminaire
Cut 5” Diameter hole into sheet rock and pull wires though hole
Remove and discard hanger bar flange after removing 3 screws
Remove top access cover and make low dimming wire con-nections if necessary
2
3
Page 4
Installation InstructionsSero / Qub Pendant
RETROFIT CONSTRUCTION- INACCESSIBLE CEILING Mounting Option “GP”
Make line voltage wire connections
4
24” (609mm)48” (1219mm)72” (1828mm)96” (2438mm)
step 1
Purple (Dim)
Grey (Dim)White (Neutral)
Green (Ground)
Black (Hot)
White (Neutral)
Green (Ground)
Black (Hot)
Dimming Circuit
Line Voltage
Low voltage dimming
Feb 2019
NULITE Lighting Inc. 10770 East 51st Avenue Denver, CO 80430 Phone (303) 287-9646 www.nulite-lighting.com
inStaLLing an individuaL or row Starter Luminaire
Rotate two philips screws clock wise to secure brackets to sheet rock
7
Install the smallest threaded rod into center of driver enclo-sure
8
Thread cord, coupler and aircraft cable into canopy as shown
9
Page 5
Installation InstructionsSero / Qub Pendant
RETROFIT CONSTRUCTION- INACCESSIBLE CEILING Mounting Option “GP”
Connect coupler and aircraft cable to threaded stem
10
re-attach splice cover
5
Insert driver enclosure into ceiling
6
Rec
ycle
Rec
ycle
Feb 2019
NULITE Lighting Inc. 10770 East 51st Avenue Denver, CO 80430 Phone (303) 287-9646 www.nulite-lighting.com
inStaLLing an individuaL or rowStarter Luminaire
Screw threaded coupler and non-power canopy onto mount-ing stem to physically hang luminaire
13
On non-power side thread aircraft cable though adjuster on luminaire (level and trim cable as last step)
Page 6
Installation InstructionsSero / Qub Pendant
RETROFIT CONSTRUCTION- INACCESSIBLE CEILING Mounting Option “GP”
14
On power side thread aircraft cable though adjuster on lumi-naire (level and trim cable as last step)
12
Remove driver cartridge by pushing release pin, and make low voltage wire connection, then push driver assembly back into enclosure and attach 5” canopy as shown
11
Red
Red w/white stripe
Blue
Blue w/white stripeRelease
Pin
Feb 2019
NULITE Lighting Inc. 10770 East 51st Avenue Denver, CO 80430 Phone (303) 287-9646 www.nulite-lighting.com
inStaLLing arow-mid or row-end(aFter Starter haS Been inStaLLed, Step 2 or Step 3)
24” (609mm)48” (1219mm)72” (1828mm)96” (2438mm)
24” (609mm)48” (1219mm)72” (1828mm)96” (2438mm)
24” (609mm)48” (1219mm)72” (1828mm)96” (2438mm)
step 1 step 2 step 3
Repeat Steps 1-12 on page 4-6 to install next Grid driver enclosure in the row
***2 cable mounts in first fixture, only one ca-ble mount in each subsequent fixture***
1-12
Page 7
Installation InstructionsSero / Qub Pendant
RETROFIT CONSTRUCTION- INACCESSIBLE CEILING Mounting Option “GP”
13
Row Starter
Row Mid or Row End
Captive Spring Latch joins fixtures
After the “Row Mid” or “Row End” has been suspended at the far end, connect the luminaire to the “Row Start-er” by sliding the luminaires together and then using the spring latch to securely make the final connection.