sfra frax application&product mk 021609
TRANSCRIPT
Sweep FrequencyResponse Analysis
FRAX
Transformer Diagnostics
Diagnostics is about collecting reliable information to make the correct decision
Making the correct decisions saves money
Oil analysis
SFRA
FDS Winding Resistance
SFRA Basics
SFRA history (1)
1960: Low Voltage Impulse Method. First proposed by W. Lech & L. Tyminski in Poland for detecting transformer winding deformation.
1966: Results Published; “Detecting Transformer Winding Damage - The Low Voltage Impulse Method”, Lech & Tyminsk, The Electric Review, ERA, UK
1976: “Frequency Domain Analysis of Responses From L.V.I. Testing of Power Transformers”, A.G. Richenbacher, 43rd Doble Conference
1978: “Transformer Diagnostic Testing by Frequency Response Analysis”, E.P. Dick & C.C. Erven, Ontario Hydro, IEEE Transactions of Power Delivery.
SFRA history (2)
1978: FRA test developed at Ontario Hydro, Canada 1980’s: Further research carried out by Central Electricity
Generating Board in UK 1988 - 1990’s : Proving trials by European utilities, the
technology cascades internationally via CIGRE, EuroDoble and many other conferences and technical meetings
2004: First SFRA standard, ”Frequency Response Analysis on Winding Deformation of Power Transformers”, DL/T 911-2004, is published by The Electric Power Industry Standard of People’s Republic of China
2008: CIGRE report 342, ”Mechanical-Condition Assessment of Transformer Windings Using Frequency Response Analysis (FRA)” is published
Transformer mechanics basics
A transformer is rated to withstand certain mechanical forces.
However, these forces can easily be exceeded • during transportation • short circuits close to the transformer
Transformers mechanical strength weakens as the transformer ages
• Less capability to withstand mechanicalstress
• Greater risk for mechanical problems• Greater risk for insulation problems
Detecting Faults with SFRA
Core movements Faulty core grounds Winding deformations Winding displacements Partial winding collapse Hoop buckling Broken clamping structures Shorted turns and open windings Etc
SFRA = Fingerprinting
SFRA testing basics
Off-line test Transformer is a complex RLC filter circuit Changes in this circuit can be detected and
plotted as a response curve when test signals at different frequencies are applied over a winding
Changes can be compared over time, between test objects or within test objects
The method is unique in its ability to detect core problems, mechanical winding problems and other electrical faults in one test
Test results – always comparisons
Different problems can be seen in different parts of the curve
Software analysis makes it easy to detect deviations
Low frequencies• Core problems and
shorted/open windings
Medium frequencies• Winding deformations
High frequencies• Tap connections and other
winding connection problems
Core + windings
Winding deformations
Taps and connections
Comparative testsTransformer A
Transformer A Transformer B
Time based
Type based
Design based
Comparisons
Time Based (Tests performed on the same transformer over time)
The most reliable test Deviations between curves are easy to detect
Type Based (Tests performed on transformer of same design)
Requires knowledge about test object/versions Small deviations are not necessarily indicating a problem
Design based (Tests performed on winding legs and bushings of identical design)
Requires knowledge about test object/versions Small deviations are not necessarily indicating a problem
Measurement philosophy
New measurement = Reference measurement
Back in Service
New measurement ≠ Reference measurement
Further Diagnostics Required
Reference measurements
When transformer is new• Capture reference data at commissioning of
new transformers
When transformer is in known good condition
• Capture reference data at a scheduled routine test (no issues found)
Save for future referenceStart Your Reference Measurements ASAP!
SFRA measurements – When?
Manufacturing test Commissioning test Transport test Incident test - after incidents where you
suspect electromechanical changes• After transport• Short-circuit faults
Catastrophic events• Earth quakes• Hurricanes, tornadoes
Trigger based test – transformer alarms• Vibration• DGA• High temperature
FRA Methods
Impulse FRA vs. SweepFRA
Impulse FRA Injects a pulse signal and
measure response Convert Time Domain to
Frequency Domain using Fast Fourier Transform (FFT) algorithm
Low resolution in lower frequencies
SFRA Injects a single frequency signal Measures response at the same
frequency No conversion High resoultion at all frequencies
Impulse FRA
Comparing Impulse & SweepFRA
SFRA (Sweep frequency response analysis) provides good detail data in all frequencies
Black = Imported Impulse measurement (Time domain converted to Frequency Domain)
Red = SFRA Measurement
Deviations Low Frequency = Method Deviation High Frequency = Cable practice
Zoom View of impulse vs. SFRA
Impulse instrument sample rate limts frequency resolution to 2kHz.
SFRA Measurements
SFRA test setup
FRAX measurement circuitry
Considerations when performing SFRA Tests
or How do I maximize my investment in time and money when
performing SFRA measurements?
Test results – always comparisons
Reproducibility is of utmost importance!
Core NOT grounded
Core grounded
Example of reproducible results
105 MVA, Single phase Generator Step-up (GSU) transformer
SFRA measurements with FRAX 101 before and after a severe short-circuit in the generator
• Two different test units• Tests performed by two different persons• Test performed at different dates
Before (2007-05-23) and after fault (2007-08-29)
LV winding
HV winding
105 MVA, Single phase GSU
Measurements “before” and “after” were virtually identical
Very good correlation between reference and “after fault”
Conclusion: No indication of mechanical changes in the transformer Transformer can safely be put back in service
Potential compromising factors
Connection qualityShield grounding practice Instrument dynamic range/internal noise
floorUnderstanding core property influence in
lower frequencies in “open” - circuit SFRA measurements
Bad connection
Bad connection can affect the curve at higher frequencies
Good connection
After proper connections were made
FRAX C-Clamp
C-Clamp ensures good contact quality
Penetrates non conductive layers
Solid connection to round or flat busbars
Provides strain relief for cable Separate connector for single
or multible ground braids
Proper ground connection ensures repeatability at high frequencies
Good grounding practice;use shortest braid from cable
shield to bushing flange.
Poor grounding practice
Shield grounding influence
C. Homagk et al, ”Circuit design for reproducible on-site measurements of transfer function on large power transformers using the SFRA method”, ISH2007
FRAX cable set and grounding
Always the same ground-loop inductance on a given bushing
Instrument performance
Small transformers have higher attenuation at first resonance
Inherent instrument noise is often the main limiting source, not necessarily substation static
Test your instruments noise floor by running a sweep with “open cables” (Clamps not connected to transformer)
Internal noise level – ”Noise floor”
”Open”/noise floor measurementsRed = Other brandGreen = FRAX 101
Example of noise floor problem
H1 – H2 (open & short) measurementsBlack = Other brand
Red = FRAX 101
Influence of core
Try to minimize the effect, however, some differences are still to be expected and must be accepted.
Preferably: perform SFRA measurements prior to winding
resistance measurements (or demagnetize the core prior to SFRA measurements)
Use same measurement voltage in all SFRA measurements
Run winding resistance test after SFRA!
After demagnetization
After winding resistance test
40
Effect of applied measurement voltage
2.8 VOmicron
10 VFRAX, Doble and others
41
FRAX has adjustable output voltage!
Omicron (2.8 V)
FRAX, 2.8 V
Field Verification Unit
Field verification unit with known frequency response is recommended in CIGRE and other standards to verify instrument and cables before starting the test
ABB Transformer Diagnostics
Summary
The basis of SFRA measurements is comparison and reproducibility is of utmost importance
To ensure high repeatability the following is important• Use of a high quality, high accuracy instrument with inputs and
output impedance matched to the coaxial cables (e.g. 50 Ohm)• Use same applied voltage in all SFRA measurements• Make sure to get good connection and connect the shields of
coaxial cables to flange of bushing using shortest braid technique.• Make good documentation, e.g. make photographs of
connections.
45
FRAX The Features And Benefits
FRAX 101 – Frequency Response Analyzer
FRAX 101 – Frequency Response Analyzer
BluetoothOn FRAX101
USB PortOn all models
Power Input11-16VDC
Rugged Extruded Aluminum Case
Active Probe Connector on FRAX101
All Connectors Panel Mounted
GeneratorReferenceMeasure Connectors
Not only the smallest, but also the most feature rich and accurate SFRA
unit in the world!
SFRA test setup
Industrial grade class 1 Bluetooth (100m)
USB for redundancy
Optional Internal BatteryOver 8h effective run time
Easy to connect shortest braid cables
Search Database Feature
Data files stored in XML format
Index function stores all relevant data in a small database
Search function can list and sort files in different locations
Import formats
Less points where it takes time to test and where high frequency resolution is not needed
More points wherehigher frequency
resolution is useful
Traditional test about 2 min
vs.FRAX fast test< 40 seconds
Fast testing
Decision support
Unlimited analysis
Unlimited graph control Lots of available graphs Ability to create custom
calculation models using anymathematic formula and themeasured data from all channels
Turn on and off as needed Compare real data with
calculated model data
Mathematical modeling
FRAX 101 transport case
Cable compartment
Padded product bay
Rugged case 14kg/31lbs incl. Cables
FRAX-150
As FRAX-101 except: Internal PC/stand-alone No internal battery option No Bluetooth
FRAX-99
As FRAX 101 except: No internal battery option No Bluetooth Dynamic range > 115 dB Fixed output voltage 9 m cable set No active probes
Active Probes, extending the application
Active Impedance Probe• Measures Transfer functions between
two grounded connections• E.g. between winding and tank or
bushing flange
Active Voltage Probe• Measures objects with higher input
impedance than 50Ω• Allows for longer cables
FRAX product summary
Light weight Rugged Battery operated Wireless communication Accuracy & Dynamic Range/Noise floor Cable Practice Easy-to-use software Export & Import of Data Complies with all SFRA standards and recommend Only unit that is compatible with all other SFRA
instruments
Sweep Frequency Response Analysis
Application Examples
Time Based Comparison - Example
1-phase generator transformer, 400 kVSFRA measurements before and after
scheduled maintenanceTransformer supposed to be in good condition
and ready to be put in service…
Time Based Comparison - Example
”Obvious distorsion” as by DL/T911-2004 standard (missing core ground)
Time Based Comparison – After repair
”Normal” as by DL/T911-2004 standard (core grounding fixed)
Type Based Comparisons (twin-units)
Some parameters for identifying twin-units: Manufacturer Factory of production Original customer/technical specifications No refurbishments or repair Same year of production or +/-1 year for large units Re-order not later than 5 years after reference order Unit is part of a series order (follow-up of ID numbers) For multi-unit projects with new design: “reference” transformer should
preferably not be one of the first units produced
Type Based Comparison - Example
Two 33/11 kV, 10 MVA, manufactured 1977 Put out of service for maintenance/repair or scrapping “Identical” except for slightly different tap-settings
(could not be fixed at site due to missing tool…) SFRA testing and comparing the two transformers
came out OK indicating that there are no electromechanical problems in the transformers (identical problems highly unlikely…)
Type Based Comparison – LV windings
33 kV, 3-phase Ynyn transformer (30 years old) ”Normal” as by DL/T911-2004 standard
-15
-20
-25
-30
-35
-40
-45
-50
Ma
gn
itu
de
(d
B)
1 k 10 k 100 k 1 MFrequency (Hz)
[X1-X0 (open)] [X3-X0 (open)] [X1-X0 (open)] [X3-X0 (2)]
Type Based Comparison – IW tests
33 kV, 3-phase Ynyn transformer (30 years old) ”Normal” as by DL/T911-2004 standard
-20
-25
-30
-35
-40
-45
-50
-55
Ma
gn
itu
de
(d
B)
1 k 10 k 100 k 1 MFrequency (Hz)
[H1-X1 (IW)] [H3-X3 (IW)] [H1-X1 (IW)] [H3-X3 (IW)]
Design Based Comparisons
Power transformers are frequently designed in multi-limb assembly. This kind of design can lead to symmetric electrical circuits
Mechanical defects in transformer windings usually generate non-symmetric displacements
Comparing FRA results of separately tested limbs can be an appropriate method for mechanical condition assessment
Pending transformer type and size, the frequency range for design-based comparisons is typically limited to about 1 MHz
Design Based Comparison - Example
132 kV, 60 MVA transformer, manufactured 2006
New transformer never in serviceNo reference FRA measurements from factorySFRA testing, comparing symmetrical phases
came out OKThe results can be used as fingerprints for
future diagnostic tests
Designed Based Comparison – HV windings
132 kV, 3-phase YNd1 transformer (new) ”Normal” as by DL/T911-2004 standard H1-H0 vs H3-H0
-20
-25
-30
-35
-40
-45
-50
-55
-60
-65
Ma
gn
itu
de
(d
B)
1 k 10 k 100 k 1 MFrequency (Hz)
[H1-H0 (open)] [H3-H0 (open)]
Designed Based Comparison – LV windings
132 kV, 3-phase YNd1 transformer (new) ”Normal” as by DL/T911-2004 standard X2-X1 vs X1-X3
-10
-20
-30
-40
-50
Ma
gn
itu
de
(d
B)
1 k 10 k 100 k 1 MFrequency (Hz)
[X2-X1 (open)] [X1-X3 (new test) (open)]
Designed Based Comparison – IW test
132 kV, 3-phase YNd1 transformer (new) ”Normal” as by DL/T911-2004 standard H1-X1 vs H3-X3
-20
-25
-30
-35
-40
-45
-50
-55
-60
Ma
gn
itu
de
(d
B)
1 k 10 k 100 k 1 MFrequency (Hz)
[H1-X1 (IW)] [H3-X3 (IW)]
Design Based Comparison – After Suspected Fault
Power transformer, 25MVA, 55/23kV, manufactured 1985
By mistake, the transformer was energized with grounded low voltage side
After this the transformer was energized again resulting in tripped CB (Transformer protection worked!)
Decision was taken to do diagnostic test
Design Based Comparison– After Suspected Fault
HV-0, LV open A and C phase OK, large deviation on B-phase (shorted turn?)
-80
-70
-60
-50
-40
-30
-20
-10
0
10 100 1000 10000 100000 1000000
Frequency (Hz)
Res
po
nse
(d
Bs)
Design Based Comparison– After Suspected Fault
HV-0 (LV shorted) A and C phase OK, deviation on B-phase
-60
-50
-40
-30
-20
-10
0
10 100 1000 10000 100000 1000000
Frequency (Hz)
Res
po
nse
(d
Bs)
And how did the mid-leg look like…?
Insulation cylinder
Core limb
LV winding
Sweep Frequency Response Analysis
Standards
SFRA Standards and Recommendations
Frequency Response Analysis on Winding Deformation of Power Transformers, DL/T 911-2004, The Electric Power Industry Standard of People’s Republic of China
Mechanical-Condition Assessment of Transformer Windings Using Frequency Response Analysis (FRA), CIGRE report 342, 2008
IEEE PC57.149™/D4 Draft Trial-Use Guide for the Application and Interpretation of Frequency Response Analysis for Oil Immersed Transformers, 2007 (Draft)
Internal standards by transformer manufacturers, e.g. ABB FRA Standard v.5
SFRA Standards - Summary
Frequency range Dynamic range Accuracy Signal cable grounding
EPIS PRC DL/T 911 1 kHz - 1 MHz -100 to +20 dB ± 1 dB @ -80 dB
Wire, shortest length to transformer core
grounding not stated
Defined correlation in three frequency
bands
CIGRE WG A2.26 min 50 Hz - 2
MHz
-100 to +20 dB measurement
range ± 1 dB @ -100 dBGrounded at both ends
using shortest braidTest circuit with a
known FRA response
Not stated (DL/T 911 recognized as one
standard)
IEEE PC57.149/D4
"Calibrated to an acceptable
standard"Grounded at both ends
using shortest braid
Standard test object with a known FRA
response
Plot inspection, difference plots,
general correlation techniques
ABB FRA Technical Standard v.5 10 Hz - 2 MHz
Better than -100 to +40 dB ± 1 dB @ -100 dB
Grounded at both ends using shortest
wire/braid
"Condition control of FRA device, including
coaxial cables, is strongly
recommended"Plot inspection, difference plots.
StandardInstrumentation
"Suffi cient dynamic range, over the frequency range in order to accommodate all transformer
test objects" (-120 dB…?)
Self-test Analysis
Instrumentation
Frequency range – All major brands are OK Dynamic range
First transformer circuit resonance gives typically a -90 dB response. Smaller transformers may have a first response at -100 dB or lower
Note that CIGRE recommends measurement range down to -100 dB. This implies a “dynamic range”/noise floor at about -120 dB.
Accuracy ± 1 dB at -100 dB fulfills all standards.
All FRAX instruments fulfills all standards for dynamic range and accuracy!
Cable grounding practice
The “shortest wire/braid”-practice is now generally accepted All European equipment manufacturers have adapted to
this practice
Recommended grounding practice (CIGRE) Bad grounding practice (CIGRE)
Instrumentation verification
Verification of instrument including cables• Measurement with “open” cables (at clamp) should give a response
close to the noise floor of the instrument (at lower frequencies, pending cable length)
• Measurement with “shorted” cables (at clamp) should give close to 0 dB response (pending cable length)
• External test device with known response (FTB-101 included in FRAX standard kit)
Calibration at recommended interval• FRAX; Minimum every 3 years, calibration set and SW available
FRAX Field Verification Unit, FTB-101
FRAX - Benchmarking
Measurement voltage and internal noise
Measurement voltage and internal noise/dynamic range for common SFRA test sets
Highest dynamic range, -130 dB
Internal noise (dynamic range)
Internal noise (open) measurementsGreen – FRAX-101
Red – Other SFRA 1Blue – Other SFRA 2
Measurement range
Internal noise (open) measurementsGreen – FRAX-101
Blue – Other SFRA 1
-100 dB measurement(CIGRE standard)Black – FRAX-101
Red – Other SFRA 1
Dynamic Range – Comparison (1)
Neutral to capacitive tapRed – FRAX-101
Black – Other SFRA 1
End-to-end openGreen – FRAX-101
Blue – Other SFRA 1
Dynamic Range – Comparison (2)
H1 – H2 (open) measurementsRed – FRAX-101
Grey – Other SFRA
Dynamic Range – Measurements at first resonance
Blue – FRAXPurple – Other SFRA 3Red – Other SFRA 1
Jiri Velek, “CEPS SFRA Market Research”, October 2006
FRAX - Compatibility
93
FRAX vs Doble (1)
5 MVA, Dyn, H2-H3 measurement
Blue – DobleOrange – Frax
94
FRAX vs Doble (2)
YNd, H1-H0 measurement
Blue – DobleOrange – Frax
95
FRAX vs Tettex and Doble
H1-H0 (short) measurement
Blue – FRAXPurple – TettexRed – Doble(Doble high frequency deviation due to different grounding practice)
Jiri Velek, “CEPS SFRA Market Research”, October 2006
96
Frax-101, 2.8 vs 10 V meas voltage
2.8 V
10 V
97
Frax (2.8V) vs FRAnalyzer
Omicron (2.8 V)
PAX, 2.8 V
Summary - conclusions
SFRA is an established methodology for detecting electromechanical changes in power transformers
Collecting reference curves on all mission critical transformers is an investment!
Ensure repeatability by selecting good instruments and using standardized measurement practices
Select FRAX from Pax Diagnostics, the ultimate Frequency Response Analyzer!