shear and flexural characterization of grid- reinforced ... · revised manuscript...
TRANSCRIPT
Revised Manuscript DOI: 10.1617/s11527-013-0207-1
1
Shear and flexural characterization of grid-
reinforced asphalt pavements and relation
with field distress evolution
Francesco Canestrari – Leonello Belogi – Gilda Ferrotti – Andrea Graziani
Università Politecnica delle Marche +39 071 2204780
+39 071 2204510
Abstract
The use of geogrids at the interface of asphalt layers is currently adopted to improve pavement
performance in terms of rutting, fatigue and reflective cracking. Several test methods have been
proposed in order to simulate the complex mechanical behavior of reinforced pavements and assist
practitioners in the selection of the appropriate reinforcement product. A particular subject of
debate is the evaluation of geogrid effects in terms of both flexural strength and interlayer shear
resistance. In this context, an interlaboratory experiment has been organized as part of the RILEM
TC 237-SIB/TG4 with the twofold objective of comparing the predictive effectiveness of different
experimental approaches and analyzing the behavior of different geogrid types. For this purpose
two experimental reinforced test sections have been realized, the first to prepare samples for the
interlaboratory experiment, the second to analyze the geogrid field performance under heavy
traffic conditions. This paper describes the test results obtained by one participating laboratory on
double-layered asphalt samples obtained from the first experimental section and compares them
with the periodic visual observation of the reflective cracking evolution occurred in the second test
section. The laboratory tests were performed following a specific testing protocol that combines
interlayer shear tests, repeated loading tests in a four-point bending configuration and quasi-static
three-point bending tests, in order to investigate the overall performance of double-layered asphalt
systems. Results have shown that geogrid reinforcement does not noticeably influence the flexural
stiffness and strength in the pre-cracking phase, whereas the crack propagation speed can be
significantly reduced and the failure behavior may change from quasibrittle to ductile, depending
on the interlayer shear strength. Laboratory results were confirmed by periodic visual observation
of field performance in terms of reflective cracking evolution.
Keywords: asphalt concrete, interface, geogrid, reinforcement, field performance
Revised Manuscript DOI: 10.1617/s11527-013-0207-1
2
1. Introduction
The increase of traffic volume and axle loads, leading to premature failures in the
in-service road pavement network, is one of the reasons for the worldwide
growing interest on pavement reinforcement. Particularly, the performance of
asphalt pavements can be improved by the installation of a geosynthetic
reinforcement at the interface of asphalt concrete layers. In fact, many research
studies showed that reinforced asphalt systems obtained installing geogrids,
geomembranes and geocomposites, can be appropriately employed in order to
improve rutting resistance (Austin and Gilchrist 1996; Komatsu et al. 1998;
O’Farrell 1996), fatigue resistance (Austin and Gilchrist 1996; Brown et al. 2001;
Lee 2008; Zielínski 2008) and reflective cracking inhibition (Komatsu et al. 1998;
Montestruque et al. 2004; Penman and Hook 2008; Sobhan et al. 2004; Zamora-
Barraza et al. 2011).
However, the structural improvement provided by the installation of a
geosynthetic reinforcement at asphalt interfaces, can be negatively affected and
eventually neutralized by its potential de-bonding effect. In fact, it has been
shown that the installation of a geosynthetic reinforcement can hinder the full
transmission of horizontal shear stress at asphalt layers interfaces and reduce the
overall efficiency of the interlayer system (Brown et al. 2001; Canestrari et al.
2012a; Ferrotti et al. 2011; Zamora-Barraza et al. 2010; Canestrari et al. 2012b).
In order to provide structural improvements and load spreading ability the
reinforcement should also ensure an adequate level of interlayer shear resistance;
however, in such a case it may result in a limited capability in preventing bottom-
up crack propagation and reflective cracking. On the other side, if the
reinforcement is installed on a distressed surface and preventing crack
propagation from the underlying pavement is the main goal, its contribution to the
load carrying capacity of the pavement may be limited, or even negative.
Given this background, the reinforcement of asphalt layers with geosynthetics is
still an important subject of debate.
To investigate the impact of reinforcement installation at the interface of asphalt
layers, RILEM TC 237-SIB/TG4 “Pavement Multilayer System Testing”
organized an interlaboratory experiment, based on the construction of two full-
scale reinforced pavement sections: the first one to prepare samples for
Revised Manuscript DOI: 10.1617/s11527-013-0207-1
3
interlaboratory tests and the second one to perform a real scale analysis of
pavement performance.
This paper presents the results obtained by one laboratory participating to the
interlaboratory experiment and compares them with visual observations of the
distresses occurred in the second test section. The laboratory tests were performed
following a specific testing protocol combining shear and flexural tests on double-
layered asphalt concrete specimens, with reinforced and un-reinforced interface.
Particularly, interlayer bonding was evaluated by means of shear tests, while
flexural behaviour by means of repeated loading four-point bending tests and
quasi-static three-point bending tests. The obtained results were then compared
with periodic visual observations of reflective cracking in the real scale section
subjected to heavy traffic conditions, in order to find possible correlations
between laboratory tests results and field performance.
2. RILEM project description
The study described in this paper is part of the research project: “Advanced
Interface Testing of Geogrids in Asphalt Pavements” promoted by Task Group 4
“Pavement Performance Prediction and Evaluation” of RILEM Technical
Committee 237-SIB “Sustainable and Innovative Bituminous Materials”. The
main goal of this RILEM project is the comparison of experimental procedures
and devices for the mechanical characterization of geogrid reinforced interfaces in
asphalt concrete pavements and the determination of their relationship with the
actual field performance.
In order to meet these challenges, the project is based on the construction of two
full-scale pavement test sections using real scale paving equipment and geogrid
installation techniques. Section A was realized in order to prepare double-layered
asphalt pavement samples to be tested with different devices within the
interlaboratory experiment. Section B was used to evaluate field performance of
reinforced asphalt pavements.
In each experimental section, an unreinforced (UN) and two reinforced (FP and
CF) asphalt interfaces were realized, creating three different double-layered
systems. The same AC mixes were used to construct both sections: in Section A
two lifts having a thickness of 50 mm each were realized, whereas in Section B
the lower lift has a thickness of 40 mm.
Revised Manuscript DOI: 10.1617/s11527-013-0207-1
4
From Section A, slab samples of different sizes (52×52 cm and 65×65 cm) were
cut in order to fit the needs of the laboratories participating to the interlaboratory
test (Fig. 1) whereas Section B was instrumented (Graziani et al. 2011) in order to
evaluate stress and strain at specific locations inside the pavement (currently in
progress). In addition, periodic visual inspections allow to assess distress
evolution in Section B.
3. Objectives
This paper presents the results obtained by one single laboratory which carried out
tests within the RILEM interlaboratory experiment on asphalt specimens sampled
from the Section A.
The objective of this study is the comparison of the effect of two geogrid types on
the flexural and shear behavior of reinforced double-layered systems. The test
protocols were selected to study different aspects of real scale applications where
the structural reinforcement provided by geogrids can be compromised if a
significant shear strength reduction (de-bonding effect) at the interface between
asphalt layers occurs.
In addition, results of laboratory tests were compared to the evolution of reflective
cracking on Section B subjected to real scale heavy traffic and climatic actions.
4. Materials
The Asphalt Concrete (AC) was a typical Italian dense graded mix formulation,
with 12 mm maximum aggregate dimension (AC 12) and 70/100 penetration
bitumen dosed at 5.5 % by aggregate weight. A summary of the quality control
tests performed during and after construction is reported in Table 1 and in
Figure 2.
An SBS polymer-modified tack coat emulsion (Table 2), classified as C 69 BP 3
according to EN 13808, was applied on the surface of the lower layer with a rate
of 0.25 kg/m2 of residual binder in both the reinforced and unreinforced
interfaces.
Two different geogrids were installed (Fig. 3). The Carbon Fiber/Glass geogrid
(CF) is pre-coated with bitumen and characterized by carbon fibers roving in the
transversal direction and glass fibers roving in the longitudinal direction, with a
square 20 mm mesh. The product is sanded on the upper side, whereas a burn off
Revised Manuscript DOI: 10.1617/s11527-013-0207-1
5
film is applied on the underside. The main characteristics of the CF geogrid are
shown in Table 3.The Glass Fiber Reinforced Polymer geogrid (FP) is obtained
by weaving continuous alkaline-resistant pre-tensioned glass fibers, covered with
a thermosetting epoxy resin (vinylester). The grid has flat transversal strands
woven into longitudinal twisted strands, with a square 33 mm mesh (Table 3).
Apart from the constituent material and mesh size, the main difference among the
two geogrids is their torsional rigidity, also called aperture rigidity (Kinney and
Yuan 1995). In particular the FP geogrid is extremely stiff as twisting and
distorting its square mesh is practically impossible, on the contrary the CF geogrid
mesh is extremely flexible and deformable.
5. Testing equipment and laboratory experimental
program
5.1 Testing devices and procedures
5.1.1 Ancona Shear Testing Research Analysis (ASTRA) tests
The ASTRA device (Fig. 4), compliant with the European Standard prEN 12697-
48 and the Italian Standard UNI/TS 11214, is a direct shear box, similar to the
device commonly used in soil mechanics. The whole apparatus is located in a
climatic chamber with temperature and relative humidity control and the specimen
is installed in two half-boxes separated by an unconfined interlayer shear zone
(Canestrari and Santagata 2005). During the test, a constant horizontal
displacement rate of 2.5 mm/min occurs while a constant vertical load,
perpendicular to the interface plane, is applied in order to generate a given normal
stress (σn). This test returns a data-set where interlayer shear stress (τ), horizontal
(ξ) and vertical (η) displacement are reported, allowing the calculation of the
maximum interlayer shear stress (τpeak), for each specimen. Carrying out ASTRA
tests at various stress levels σn, it is possible to obtain a complete assessment of
failure and residual properties (post-peak) of interfaces (Canestrari and Santagata
2005; Canestrari et al. 2005) according, respectively, to the following equations:
pn0peak tanc Φστ ⋅+= (1)
resnres tanΦστ ⋅= (2)
Revised Manuscript DOI: 10.1617/s11527-013-0207-1
6
where τpeak and τres are the peak and the residual interlayer shear resistance,
respectively, c0 is the pure shear resistance, Φp and Φres are the peak and the
residual friction angle, respectively.
5.1.2 Repeated four point bending (4PB) tests
Repeated loading tests were carried out in four-point bending configuration (4PB)
using a device specifically developed to test large beam specimens as required by
geogrid reinforced systems (Fig. 5).
The 4PB device is basically composed by a temperature controlled chamber, a
loading frame and a hydraulic actuator able to apply haversine loading waves up
to a peak load value of 4.0 kN, with a maximum frequency of 5 Hz. The vertical
displacement at the mid-span of the beam is measured during the test through a
strain gauge based extensometer.
The beams tested in this study, cut from double-layered slabs, have a cross section
width W = 90 mm and a total height H = 75 mm (30 mm the lower layer and 45
mm the upper layer).
The performance of double-layered systems in the cyclic 4PB test is analyzed in
terms of permanent deformation and damage associated to crack propagation.
Permanent deformation is measured by means of the accumulated mid-span
deflection at each load cycle. Since reinforced beams often do not reach a
complete collapse during the test, a failure criterion to compare different interface
types (Virgili et al. 2009) was defined by the number of load cycles (or time)
required to reach the flex point in the permanent deformation curve (Fig. 6).
Damage occurring to the tested specimen can be evaluated by the reduction of the
apparent stiffness modulus appE calculated as follows:
app,r
appappE
ε
σ= (3)
where σapp and εr,app are, respectively, the apparent values of stress and recovered
strain, calculated from the linear elastic beam theory, and therefore:
3
223
r,0
0app HW12
)a4L3(LPE⋅⋅
−⋅=
δ (4)
where P0 is the amplitude of the applied haversine load, δr,0 is the amplitude of the
periodic recovered displacement response, H is the beam height, L is the beam
Revised Manuscript DOI: 10.1617/s11527-013-0207-1
7
span, W in the beam width and a is the distance between the beam support and the
point of load application (Fig. 5).
The calculated stiffness modulus is obviously an apparent value for two reasons:
first, the span of the beams is about three times their height (Fig. 5) and therefore
the application of the beam theory is not rigorous; second, equation (4) is applied
also in the post-cracking phase of the tests.
5.1.3 Three Point Bending (3PB) tests
Three Point Bending (3PB) tests were performed on prismatic beams identical to
the specimens used in 4PB tests. A scheme of the Three Point Bending (3PB) test
equipment is shown in Figure 7. During the test, the prismatic beam specimens
are subjected to a bending load under displacement control. Load and beam
deflection at the mid-span of the specimen are measured through a load cell and a
LVDT displacement transducer, respectively.
The performance of double-layered reinforced systems can be evaluated through
the maximum pre-cracking flexural load Pmax, the pre-cracking energy PE and the
fracture energy or toughness T. These parameters are shown in Figure 11: Pmax is
a measure of the flexural strength, PE represents the area under the load-
deflection curve up to the Pmax value is reached and T represents the area under the
entire load-deflection curve (Pasquini et al. 2012).
The pre-cracking energy PE takes into account the crack initiation of the beam,
whereas the toughness T provides an indication of the post-peak deformation
energy and therefore can be used to evaluate the performance of the geogrid
reinforcement in the crack propagation phase (Lee 2008). This kind of test is
appropriate to give information in terms of crack propagation allowing to perform
comparisons between different reinforced systems.
5.2 Test program
The laboratory experimental program focuses on the evaluation of shear and
flexural properties of reinforced and unreinforced double-layered bituminous
systems in order to compare their mechanical behaviour. The three interface types
(UN, CF and FP) were studied in terms of interlayer shear resistance (ASTRA
test) and repeated loading behavior (4PB test), following a specifically prepared
protocol for the investigation of geogrid performance in flexible pavements
Revised Manuscript DOI: 10.1617/s11527-013-0207-1
8
(Ferrotti et al. 2011). Moreover, 3PB tests were performed to study the geogrid
effect on the mechanical strength of the double-layered systems under quasi-static
flexural loading (Lee 2008, Kunst and Kirschner 1993, Kwang et al. 1996). A
summary of the laboratory test program is reported in Table 4.
The ASTRA tests were carried out under three normal stresses (σn = 0.0, 0.2 and
0.4 MPa) in order to obtain the peak and the residual friction envelopes
(Canestrari et al. 2005). Temperature effect on interlayer shear resistance was also
investigated performing tests at three temperatures (T = 10, 20 and 30 °C) on
cylindrical specimens cored from slabs stored in the lab for one year (Table 4).
Moreover, in order to assess the influence of sample age, tests were performed at
T = 20 °C on cores obtained from slabs stored in the lab for two years. Three
repetitions were carried out for each interface type.
The cyclic 4PB tests were carried out at a temperature of 20 °C in load-controlled
mode. A haversine load with a frequency of 1 Hz and three amplitudes (P0 = 1.0,
1.5 and 2.0 kN) was applied in order to obtain information at different stress
levels. A maximum test time of 10 hours was adopted, allowing the application of
up to 36,000 load cycles. Two repetitions were performed for each test type.
The quasi-static 3PB tests were carried out at a temperature of 20 °C in
displacement-controlled mode, with a constant rate of 50.8 mm/min (Judycki
1990, Kunst and Kirschner 1993, Kwang et al. 1996). Three repetitions were
performed for each test type.
6. Laboratory test results and analysis
6.1 ASTRA test results
The peak and friction envelopes of the interlayer shear resistance obtained for the
studied interface types are presented in Figure 9, while the corresponding
envelope parameters (c0, Φp and Φres) and the linear regression determination
coefficients (R2) are reported in Table 5.
In terms of peak values (τpeak), the comparison of the three systems shows that
geogrid-reinforced samples (CF and FP) provide lower interlayer resistance
compared to unreinforced systems (UN), particularly in terms of pure shear
component (c0). This is in accordance with previous experimental investigations,
carried out with various experimental devices (Brown et al. 2001; Ferrotti et al.
Revised Manuscript DOI: 10.1617/s11527-013-0207-1
9
2012; Zamora-Barraza et al. 2010; Zielínski 2008), where a similar interlayer de-
bonding effect was measured after the installation of geogrid reinforcement.
In all test conditions, CF systems provided higher τpeak values respect to FP
systems. This is due to the higher thickness and stiffness of the FP geogrid, which
probably inhibits the achievement of an optimal compaction of the upper AC layer
in the interface proximity, and reduces the interlocking between the two
bituminous layers in contact.
A previous statistical investigation performed on ASTRA test results (Santagata et
al. 2009) showed that τpeak = 0.38 MPa can be considered as minimum reference
value for the interlayer shear resistance of unreinforced AC interfaces, at
T = 20 °C and σn = 0.2 MPa. In this study, improved peak shear resistance values
(0.56 MPa and 0.51 MPa, respectively) were measured with UN and CF systems,
whereas the FP geogrid provided a reduced peak shear resistance (0.34 MPa). As
already showed by Millien et al. (2012), this de-bonding effect is expected to
influence bending behavior of double-layered systems.
As far as the influence of test temperature on τpeak is concerned, Figure 9 shows a
decrease of interlayer shear resistance with increasing temperature, for all
interface types. This indicates that, at higher temperatures, the geogrid influence
tends to vanish and τpeak is controlled mainly by the characteristics of the two AC
layers in contact (Fig. 9c).
The comparison between residual strength envelopes (τres) of the studied interface
types (Fig. 9 and Table 5) shows that, at all temperatures, the three double-layered
systems (UN, CF and FP) are characterized by analogous residual friction angles
(Φres). This confirms the results of previous studies (Ferrotti et al. 2011; Ferrotti et
al. 2012) and indicates that the residual interface resistance, which can be
associated to a purely frictional mechanism, is mainly controlled by the
composition of the two AC layers in contact.
Comparing results of ASTRA tests performed at 20 °C on samples of different
ages (Fig. 10 and Table 5), for all interface types the same increase of peak shear
resistance is observed for two years aged samples respect to one year aged. Since
this increase does not depend on interface type (tack-coat and geogrid) and normal
stress (friction and dilatancy contributions), it can only be explained by means of
an increase of inner cohesion of layer materials (Canestrari et al. 2005), related to
the bituminous binder hardening.
Revised Manuscript DOI: 10.1617/s11527-013-0207-1
10
6.2 Four point bending test results
The influence of load level and interface type on the permanent deformation
resistance of double-layered systems is showed in Figure 11 where the
accumulated mid-span deflection of the beam as a function of load cycles is
reported.
The geogrid improves the permanent deformation resistance of the double-layered
systems respect to the unreinforced specimens which always reach collapse before
the planned test conclusion (36,000 cycles). In particular, at P0 = 2.0 kN, collapse
of UN systems is obtained within the first ten load cycles, thus making unfeasible
their representation in Figure 11c.
On the contrary, CF and FP reinforced systems did not always reach complete
collapse before test conclusion, therefore the flex point of the permanent
deformation curves was used as failure criteria (Virgili et al. 2009). In these cases,
in order to compare grid effectiveness, an Improvement Factor (IF) was calculated
as follows:
UNflex
iflex
N
NIF =
(5)
where iflexN is the number of cycles at the flex point of interface type i (= CF, FP)
and UNflexN is the number of cycles at the flex point of interface type UN. The IF
parameter describes the increment of specimen life, as defined by the flex point
criteria, due to the presence of a geogrid reinforcement. As shown in Figure 12
both FP and CF geogrids produce a remarkable increase of permanent
deformation resistance that leads to high IF values, especially at higher load
levels. These results confirm the positive effect of CF geogrids observed in
previous studies for porous asphalt surfacing (Kim et al. 2009). This performance
improvement could be explained considering that, at each load cycle, part of the
deformation energy provided by the external load is stored by the geogrid
reinforcement itself as reversible deformation. Consequently, the presence of the
reinforcement reduces the load fraction carried by the AC double-layer and
therefore reduces damage accumulation of the AC mixture.
The behavior of double-layered systems was also analyzed in terms of apparent
stiffness modulus (Eapp, equation 3). Initial Eapp values (data measured at the 300th
load cycle) are reported in Figure 13, whereas the Eapp evolution during the test is
Revised Manuscript DOI: 10.1617/s11527-013-0207-1
11
summarized in Figure 14. Experimental data show that geogrid reinforcement
results in a stiffness increase of the double-layered systems, that is more evident
with the FP geogrid, but is also observed for the CF geogrid. The higher flexural
stiffness of the reinforced interfaces during the 4PB test, suggests that double-
layered specimens behave like single-layered systems, highlighting the stiffening
contribution given by the geogrid that works effectively as reinforcement. This
implies that an appreciable level of shear stress is effectively transmitted across
the reinforced interface. Such a result may appear in contrast with the direct shear
tests results which highlighted a marked reduction of peak interlayer strength for
geogrid reinforced interfaces. However, considering the different stress level
applied in the two tests, this may actually indicate that the geogrid de-bonding
effect, particularly evident for the FP grid, is attained only when interface shear
stress reaches failure conditions.
In Figure 14 the flex point position of the permanent deformation curves
(Figure 11) is reported on the corresponding curves representing the Eapp
evolution. It has been shown by previous studies (Virgili et al. 2009, Ferrotti et al.
2011) that the flex point indicates the stage of the test when cracking begins to
significantly propagate. For UN and CF reinforced systems this behavior is
confirmed by the Eapp decrease that follows the flex point, whereas, for FP
reinforced systems, the significant Eapp decrease prior to the flex point suggests a
different failure mechanism, that is confirmed by visual observations of double-
layered specimens at the end of the test. In fact, Figure 15 shows that in CF
systems the crack moves vertically and propagates across the interface and the
geogrid, whereas in FP systems when the crack reaches the interface it starts to
propagate horizontally. This change of crack propagation mode, that is also
visible in 3PB tests (see Section 6.3), can be related to the marked reduction of
peak interlayer shear strength measured by ASTRA tests for FP specimens.
Indeed, this different type of separation mechanism allows for additional energy
dissipation and brings to longer specimen life, in control stress loading mode.
Despite this different crack propagation mode, it is worth noting that both CF and
FP grids provided a considerable increase in terms of permanent deformation
resistance and flexural stiffness of the double-layered system, working effectively
as reinforcement.
Revised Manuscript DOI: 10.1617/s11527-013-0207-1
12
6.3 Three point bending test results
The load-deflection curves obtained in the quasi-static 3PB test are reported in
Figure 16 and the average values of the corresponding characteristic parameters
are summarized in Table 6.
It can be observed that, up to the flexural strength point (Pmax, δP,max) the shape of
the P-δ curves is very similar for the studied double-layered systems, resulting in
similar magnitude of the pre-cracking energy PE values (Table 6). Although the
geogrids lead to somewhat higher values of Pmax, δP,max and PE, results confirm
that these parameters largely depend on the characteristics of the un-damaged AC
mixture. As already shown by 4PB tests, this confirms that, in the pre-cracking
phase, double-layered systems behave like single-layered systems and that
geogrid reinforcement has a minor impact on the crack initiation resistance.
Beyond the flexural strength point (crack initiation), both reinforced and
unreinforced systems show an initial, rapid decrease of load carrying capacity due
to the crack propagation towards the interface. Afterwards, UN systems rapidly
and steadily lose their resistance until complete failure, whereas CF and
particularly FP systems show a post-peak deformation phase, bringing to higher
toughness values (T average values for CF and FP interface types are about 2
times and 6 times higher than the UN interface type, respectively).
In the crack-propagation phase, after the initial rapid load decrease, CF systems
show a short delayed phase (Fig. 16b) and than a rapid evolution toward collapse
(no residual flexural resistance). The FP systems, after the initial rapid load
decrease and the short delayed phase, show an apparent strain-hardening behavior
(Fig. 16c) where the resistance of the double-layered system increases reaching
values similar, or even above the flexural strength Pmax.
The different behavior of the two reinforced systems can be explained by different
failure mechanisms, analogous to that previously described for the repeated
loading 4PB tests. Specifically, when the crack reaches the interface of CF
systems, its bottom-up movement is shortly delayed before it eventually
propagates across the geogrid and brings to specimen collapse (Fig. 17).
Conversely, in FP systems, when the crack reaches the interface its bottom-up
propagation is diverted and it proceeds along the interface allowing additional
energy dissipation (Fig. 18).
Revised Manuscript DOI: 10.1617/s11527-013-0207-1
13
In the first case, a Mode 1 crack propagation (bottom-up opening) can be
identified; in the second case the horizontal crack propagation is probably related
both to the bending of the lower layer, due to the beam curvature (Mode 1), and to
the interlayer shear stress (Mode 2).
In this sense, CF grid seems to be not so effective to prevent crack propagation
across the interface, similarly to UN interface. On the contrary, FP grid
significantly delays the crack propagation, working effectively as anti-reflective
cracking system.
6.4 Relation between flexural and shear properties
In the previous sections the performance of reinforced double-layered AC samples
obtained from Section A was evaluated under different experimental conditions.
Both CF and FP geogrids produced a reduction of interlayer shear resistance
(ASTRA test), an increase of initial stiffness in the pre-cracking phase (4PB test)
and an increase of cyclic and quasi-static bending resistance (4PB and 3PB tests).
In particular the “thin and flexible” CF geogrid provided better interlayer shear
performance respect to the “thick and stiff” FP geogrid for which the ASTRA
tests clearly highlighted a de-bonding effect.
The 4PB and 3PB performance improvement provided by the CF geogrid can be
explained with a delayed Mode 1 crack propagation in the vertical direction
respect to UN systems. Nevertheless, the failure mechanism of CF and UN
specimens is similar and the Fracture Process Zone (FPZ) has similar size; in both
cases tested beams behaved as quasi-brittle structures (RILEM 2004). On the
other side, the FP geogrid brings to a significant horizontal crack propagation
phase (Mixed mode) in 4PB and 3PB tests, because of the reduced interlayer shear
strength. As a consequence, the failure mechanism of the FP double-layered
asphalt systems becomes ductile (or plastic), as the FPZ extends to a large part of
the interface.
7. Comparison with field distress evolution
In this section an attempt is made to relate the results of laboratory tests on
double-layered specimens obtained from Section A to the field performance of the
same double-layered systems on Section B. The comparison is focused on the
Revised Manuscript DOI: 10.1617/s11527-013-0207-1
14
crack-propagation behaviour observed in the lab and on the reflective cracking
performance observed in the field.
In this sense, during the construction of Section B, areas with “simulated” cracks
were prepared in the lower asphalt layer (Fig.19a) in order to evaluate the grids
performance in terms of reflective cracking inhibition. The simulated cracks were
obtained by full-depth saw cuts with an interaxis of 0.4 m (Fig. 19b).
As shown in Figure 20a and Figure 20b, a similar reflective cracking pattern
developed in UN and CF sub-sections, starting about six months after construction
and rapidly growing in the following weeks. In both sub-sections the typical
double-asymmetric crack pattern due to traffic loading developed above
transverse cuts, whereas single cracks developed above longitudinal cuts. One
year later these two zones were completely failed (Fig. 20c and Fig. 20d).
On the other side, after the same 22 months period, a double-asymmetric crack
pattern was barely visible in the FP reinforced sub-section (Fig. 20e) subjected to
the same traffic and environmental conditions, highlighting the ability of the FP
geogrid to extend service life of asphalt surfacings when cracks are present in the
underlying asphalt layers. This capability can be related to the post-cracking
behaviour previously observed in the bending tests where FP systems showed
better performance. In addition, it can be observed that the de-bonding effect
highlighted by ASTRA tests did not reduce the overall pavement performance in
this area.
However, a detailed analysis of the geogrid reinforced systems performance in
Section B is currently in progress, and will consider stress, strain and temperature
data measured by the installed sensors.
8. Conclusions
The research described in this paper focuses on two effects of geogrid
reinforcement on the behavior of asphalt pavements: interlayer shear resistance
and flexural resistance. Three interface types were considered: unreinforced (UN),
Carbon Fiber/Glass pre-bituminised (CF) geogrid and Fiber Reinforced Polymer
(FP) geogrid. Double-layered AC samples were obtained from an experimental
test section where real scale equipment and installation techniques were
employed. ASTRA test carried out to investigate interlayer shear resistance
showed that the presence of a geogrid leads to a peak strength reduction, whereas
Revised Manuscript DOI: 10.1617/s11527-013-0207-1
15
the residual (post-peak) interlayer friction is not influenced by the reinforcement.
The peak de-bonding effect is particularly evident with the FP geogrid which is
characterized by higher thickness and torsional stiffness respect to CF geogrid.
However, the geogrid influence tends to vanish at higher temperatures, where the
interlayer shear resistance appears to be controlled only by the characteristics of
the two AC layers in contact. Binder aging brings to an increase of the peak
strength, especially the pure shear component, for both reinforced and
unreinforced interfaces.
Repeated loading 4PB tests carried out on double-layered systems showed that
geogrids lead to a remarkable increase of permanent deformation resistance,
especially at higher load levels. In the pre-cracking phase, both geogrid types
produce a flexural stiffness increase, which suggests that the de-bonding effect
highlighted by the ASTRA tests, especially for the FP geogrid, is attained only in
proximity of, or at shear failure conditions. On the contrary, at lower number of
cycles, shear stress is effectively transmitted across the reinforced interface. In the
cracking phase, the two geogrid types lead to different failure mechanisms. In
particular, the vertical cracks movement is delayed by the CF geogrid but they
eventually get across the inteface leading to failure, whereas the FP geogrid
induces an horizontal propagation along the interface allowing for additional
energy dissipation and longer specimen life. Despite this different crack
propagation mode, it is worth noting that both CF and FP provided a considerable
increase in terms of permanent deformation resistance and flexural stiffness of the
double-layered system, working effectively as reinforcement.
Quasi-static 3PB tests confirmed that the presence of the geogrid does not
noticeably influence the crack initiation resistance, whereas CF and particularly
FP systems show a post-peak deformation phase, bringing to higher toughness
values. In the crack-propagation phase, similarly to 4PB tests, the two geogrids
induce different failure mechanisms. The CF geogrid shortly delays crack
propagation in the vertical direction but the failure mechanism and the fracture
process zone remains analogous to unreinforced systems. On the other side, due to
the reduced interlayer shear strength, the FP geogrid brings to a significant
horizontal crack propagation phase and consequently the failure mechanism
becomes more ductile. In this sense, CF grid seems to be not so effective to
prevent crack propagation across the interface, similarly to UN interface. On the
Revised Manuscript DOI: 10.1617/s11527-013-0207-1
16
contrary, FP grid significantly delays the crack propagation, working effectively
as anti-reflective cracking system.
Observation of the in-situ performance of the two geogrids revealed a post-
cracking behavior coherent with laboratory test results. In particular a similar
reflective cracking pattern developed in the field in UN and CF reinforced
pavements, whereas the FP geogrid provided an improved reflective cracking
resistance. In addition, the de-bonding effect highlighted by ASTRA test did not
reduce the overall pavement performance, in case of reinforcements installed as
anti-reflective cracking systems.
Acknowledgements
The research described in this paper was partly funded by the Italian Ministry of Instruction,
University and Research (MIUR).
References Austin R.A., Gilchrist A.J.T. (1996). Enhanced performance of asphalt pavements using
geocomposites. Geotext. Geomembranes 14: 175-186.
Brown S.F., Thom N.H., Sanders P.J. (2001). A study of grid reinforced asphalt to combat
reflection cracking. J. Assoc. Asphalt Pav. 70: 543-569.
Canestrari F., Santagata E. (2005). Temperature effects on the shear behaviour of tack coat
emulsions used in flexible pavements. Int. J. Pavement Eng. 6 (1): 39-46.
Canestrari F., Ferrotti G., Partl M.N., Santagata E. (2005). Advanced Testing and Characterization
of Interlayer Shear Resistance. Transp. Res. Record. 1929: 69-78.
Canestrari F., Pasquini E., Belogi L. (2012a). Optimization of geocomposites for double-layered
bituminous systems. Proceedings of the 7th RILEM International Conference on Cracking in
Pavements, Delft, pp. 1229-1239.
Canestrari F., Ferrotti G., Lu X., Millien A., Partl M.N., Petit C., Phelipot-Mardelé A., Piber H.,
Raab C. (2012b). Mechanical Testing of Interlayer Bonding in Asphalt Pavements. RILEM
State-of-the-Art-Report: Advances in Interlaboratory Testing and Evaluation of Bituminous
Materials 9: 303-360. doi: 10.1007/978-94-007-5104-0
Ferrotti G., Canestrari F., Virgili A., Grilli A. (2011). A strategic laboratory approach for the
performance investigation of geogrids in flexible pavements. Constr. Build. Mater. 25 (5):
2343–2348.
Ferrotti G., Canestrari F., Pasquini E., Virgili A. (2012). Experimental evaluation of the influence
of surface coating on fiberglass geogrid performance in asphalt pavements. Geotext.
Geomembranes 34: 11-18.
Revised Manuscript DOI: 10.1617/s11527-013-0207-1
17
Graziani A., Virgili A., Belogi L. (2011). Instrumented Test section for the Evaluation of Geogrids
in Asphalt Pavements. Proceedings of the 5th International Conference on Bituminous Mixtures
and Pavements, Thessaloniki, pp. 1107-1117.
Judycki J. (1990). Bending test of asphaltic mixture under statical loading. Proceedings of the 4th
RILEM International Symposium, Budapest.
Kim H., Sokolov K., Poulikakos L.D., Partl M.N. (2009). Fatigue Evaluation of Carbon FRP-
Reinforced Porous Asphalt Composite System Using a Model Mobile Load Simulator. Transp.
Res. Record. 2116: 108-117 .
Kinney, T.C., Yuan, X. (1995). Geogrid aperture rigidity by in-plane rotation. Proceedings of
Geosynthetics ’95, Nashville, pp. 525-537.
Komatsu T., Kikuta H. Tuji Y., Muramatsu E. (1998). Durability assessment of geogrid-reinforced
asphalt concrete. Geotext. Geomembranes 16: 257-271.
Kunst P.A.J.C., Kirschner R. (1993). Comparative laboratory investigations on polymer asphalt
inlays. Proceedings of Geosynthetics ’93, Vancouver.
Kwang W.K., Yong-Churl P., Kyu-Seok Y. (1996). Tensile reinforcement of asphalt concrete
using polymer coating. Constr. Build. Mater. 10 (2): 141–146.
Lee S.J. (2008). Mechanical performance and crack retardation study of a fiberglass-grid-
reinforced asphalt concrete system. Can. J. Civil Eng. 35 (10): 1042-1049.
Millien A., Dragomir M. L., Wendling L., Petit C., Iliescu M. (2012). Geogrid interlayer
performance in pavements: tensile-bending test for crack propagation. Proceedings of the 7th
RILEM International Conference on Cracking in Pavements, Delft, pp. 1209- 1218.
Montestruque G., Rodrigues R., Nods M., Elsing A. (2004). Stop of reflective crack propagation
with the use of PET geogrid as asphalt overlay reinforcement. Proceedings of the 5th
International RILEM Conference on Reflective Cracking in Pavements, Limoges.
O’Farrell D.J. (1996). The treatment of reflective cracking with modified asphalt and
reinforcement. Proceedings of the 3th International RILEM Conference on Reflective Cracking
in Pavements, Maastricht.
Pasquini E., Bocci M., Ferrotti G., Canestrari F. (2012). Laboratory characterisation and field
validation of geogrid-reinforced asphalt pavements. Road Mater. Pavement. on-line version:
http://dx.doi.org/10.1080/14680629.2012.735797 – doi: 10.1080/14680629.2012.735797.
Penman J., Hook K.D. (2008). The use of geogrids to retard reflective cracking on airport
runways,taxiways and aprons. Proceedings of the 6th RILEM International Conference on
Cracking in Pavements, Chicago, pp. 713-720.
RILEM TC QFS (2004). Quasibrittle fracture scaling and size effect - Final report. Mater. Struct.
37 (272): 547–568.
Santagata, F.A., Ferrotti, G., Partl, M.N., Canestrari, F., (2009). Statistical investigation of two
different interlayer shear test methods. Mater. Struct. 42: 705-714.
Sobhan K., Crooks T., Tandon V., Mattingly S. (2004). Laboratory simulation of the growth and
propagation of reflection cracks in geogrid reinforced asphalt overlay. Proceedings of the 5th
International RILEM Conference on Reflective Cracking in Pavements, Limoges.
Revised Manuscript DOI: 10.1617/s11527-013-0207-1
18
Virgili A., Canestrari F., Grilli A., Santagata F.A. (2009). Repeated load test on bituminous
systems reinforced by geosynthetics. Geotext. Geomembranes 27 (3):187-195.
Zamora-Barraza D., Calzada-Peréz M., Castro-Fresno D., Vega-Zamanillo A. (2010). New
procedure for measuring adherence between a geosynthetic material and a bituminous mixture.
Geotext. Geomembranes 28: 483-489.
Zamora-Barraza D., Calzada-Peréz M., Castro-Fresno D., Vega-Zamanillo A. (2011). Evaluation
of anti-reflective cracking systems using geosynthetics in the interlayer zone. Geotext.
Geomembranes 29: 130-136.
Zielínski P. (2008). Fatigue investigations of asphalt concrete beams reinforced with geosynthetics
interlayer. Proceedings of the 6th RILEM International Conference on Cracking in Pavements,
Chicago, pp. 751-759.
Revised Manuscript DOI: 10.1617/s11527-013-0207-1
19
List of tables
Table 1 Quality control tests on experimental section A
Table 2 Properties of the residual binder of the modified emulsion used as tack-coat
Table 3 Characteristics of CF and FP geogrids
Table 4 Summary of laboratory experimental program
Table 5 Envelope characteristic parameters of ASTRA tests
Table 6 Summary of 3PB test results
Revised Manuscript DOI: 10.1617/s11527-013-0207-1
20
List of figures
Fig. 1 Section A: a) layout of each experimental sub-section; b) detail of prepared slabs from sub-
section UN
Fig. 2 Average grading of the employed AC12 mixture
Fig. 3 Detail of the installed geogrids: a) Glass Fiber Polymer Geogrid (FP); b) Carbon Fiber
geogrid (CF)
Fig. 4 Scheme of ASTRA equipment
Fig. 5 Scheme of Repeated Loading test in Four Point Bending (4PB) configuration
Fig. 6 Analysis of repeated loading 4PB test results
Fig. 7 Scheme of Three Point Bending (3PB) test
Fig. 8 Analysis of 3PB test results: a) Pre-cracking energy (PE); b) Fracture energy (T)
Fig. 9 ASTRA test results – Peak and friction envelopes
Fig. 10 ASTRA test results – Interlayer shear resistances at different ages
Fig. 11 Repeated loading 4PB test results – permanent deformation behavior at load levels: a) 1.0
kN; b) 1.5 kN; c) 2.0 kN
Fig. 12 Increase of permanent deformation resistance in 4PB test respect to the Unreinforced
interface type (UN)
Fig. 13 Initial values of apparent stiffness
Fig. 14 Repeated loading 4PB test results – Apparent stiffness evolution at load levels: a) 1.0 kN;
b) 1.5 kN; c) 2.0 kN
Fig. 15 Failure mechanisms of reinforced specimens in repeated loading 4PB test: a) FP geogrid;
b) CF geogrid
Fig. 16 Three Point Bending test results
Fig. 17 Failure mechanisms of CF reinforced specimens in 3PB test
Fig. 18 Failure mechanisms of FP reinforced specimens in 3PB test
Fig. 19 Section B: a) layout of each experimental sub-section with position of instrumented area,
de-bonding and simulated cracks; b) detail of simulated cracks pattern in the lower layer
Fig. 20 Visual surveys of pavement condition above simulated cracks (section B)
1
Table 1 Quality control tests on experimental Section A
Lower Layer Upper Layer Interface Core Thickness Air Voids Thickness Air Voids ID N. mm % mm % UN 1 51 10.4 50 10.3 UN 2 49 11.4 48 10.4 CF 1 48 9.0 44 11.2 CF 2 56 10.3 43 11.8 CF 3 56 9.0 44 10.6 CF 4 48 10.4 42 11.5 FP 1 65 8.8 53 9.6 FP 2 57 10.3 53 9.9 Average 54 10.1 47 10.7
Table 2 Properties of the residual binder of the modified emulsion used as tack-coat
Penetration @ 25 °C dmm
Viscosity @ 160 °C Pa·s-1
Ring&Ball Temperature °C
Fraass Breaking Point °C
55-65 0.2-0.8 65-75 < -18
Table 3 Characteristics of CF and FP geogrids
Geogrid Direction Material Grid size mm
Tensile Modulus N/mm2
Elongation at rupture %
Tensile force mesh kN/m
CF Longitudinal Glass fiber 20 73,000 3-4.5 111 Transversal Carbon fiber 20 240,000 1.5 249
FP Longitudinal Glass fiber
Reinforced Polymer 33 23,000 3 211
Transversal Glass fiber Reinforced Polymer 33 23,000 3 211
2
Table 4 Summary of laboratory experimental program
Test type ASTRA Repeated loading 4PB Quasi-static 3PB Specimen type Cylindrical core Prismatic Beam Prismatic Beam Specimen dimensions [mm] D = 95 L0=305;W=90;H=75 L0=305;W=90;H=75 Interface type UN – CF – FP UN – CF – FP UN – CF – FP Sample age [years] 1 2 1 1 Test temperature [°C] 10 – 20 – 30 20 20 20 Normal stress σn [MPa] 0.0 – 0.2 – 0.4 0.0 – 0.2 – 0.4 - - Test speed [mm/min] 2.5 2.5 - 50.8 Test Frequency [Hz] - - 1 - Maximum sinusoidal load P0 [kN] - - 1.0 – 1.5 – 2.0 - Repetitions for each test configuration 3 3 2 3 Total number of specimens 81 27 18 9
3
Table 5 Envelope characteristic parameters of ASTRA tests
Interface type Sample age
T c0 φp R2 φres R2
years °C MPa degrees degrees
UN 1 10 0.909 39.09 0.88 40.21 0.98 20 0.374 38.12 0.88 40.52 0.97 30 0.115 39.25 0.96 41.94 0.97
CF 1 10 0.841 39.73 0.83 40.21 0.99 20 0.344 35.10 0.93 40.71 0.99 30 0.106 34.17 0.97 40.55 0.99
FP 1 10 0.404 41.91 0.83 39.52 0.99 20 0.145 38.86 0.92 40.01 0.99 30 0.065 37.25 0.98 40.18 0.99
UN 2 20 0.499 37.14 0.82 44.07 0.97 CF 2 20 0.471 34.67 0.83 42.97 0.92 FP 2 20 0.251 36.45 0.91 44.83 0.87
Table 6 Summary of 3PB test results
Interface type Pmax δP,max PE T kN mm Nm Nm UN 4.24 1.59 4.19 7.88 CF 4.77 1.74 5.01 16.00 FP 4.79 1.75 5.61 44.66
1
a) 65 x 65 cm 65 x 28 cm52 x 52 cm
4.0
m
0.0
m
2.5
m
10.0
m
8.0
m
Slabs
b)
Fig. 1 Section A: a) layout of each experimental sub-section; b) detail of prepared slabs from sub-
section UN
Fig. 2 Average grading of the employed AC12 mixture
2
a)
b)
Fig. 3 Detail of the installed geogrids: a) Carbon Fiber/Glass geogrid (CF); b) Glass Fiber Polymer
Geogrid (FP)
Fig. 4 Scheme of ASTRA equipment
Fig. 5 Scheme of repeated loading test in Four Point Bending (4PB) configuration
3
0
5
10
15
0 10000 20000 30000 40000
Vert
ical
def
lect
ion
[mm
]
Number of load cycles
Flex point
Hardening phase Damage phase
Fig. 6 Analysis of repeated loading 4PB test results
Fig. 7 Scheme of Three Point Bending (3PB) test
a)
Load
Deflection
Experimental dataPre-cracking energy (PE)
Pmax
b)
Load
Deflection
Experimental data
Fracture energy (T)
Pmax
Fig. 8 Analysis of 3PB test results: a) Pre-cracking energy (PE); b) Fracture energy (T)
4
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
0.0 0.2 0.4 0.6
W pea
k[M
Pa]
Vn [MPa]
T=10 °C
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
0.0 0.2 0.4 0.6W p
eak
[MPa
]Vn [MPa]
T=20 °C
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
0.0 0.2 0.4 0.6
W pea
k[M
Pa]
Vn [MPa]
T=30 °C
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
0.0 0.2 0.4 0.6
W pea
k[M
Pa]
Vn [MPa]
T=10 °C
Peak UN Peak CF Peak FPPeak envelope UN Peak envelope CF Peak envelope FPFriction envelope UN Friction envelope CF Friction envelope FP
Fig. 9 ASTRA test results – Peak and friction envelopes
0
0.2
0.4
0.6
0.8
1
0 0.2 0.4 0.6 0.8 1
Peak
she
ar re
sist
ance
-2
year
s ag
ed [M
Pa]
Peak shear resistance - 1 year aged [MPa]
T=20 °C
Fig. 10 ASTRA test results – Interlayer shear resistances at different ages
5
a)
0
5
10
15
0 10000 20000 30000 40000
Vert
ical
def
lect
ion
[mm
]
Number of load cycles
Unreinforced (UN)
Carbon Fiber (CF)
Glass Fiber (FP)
P0 = 1.0 kN
b)
0
5
10
15
0 10000 20000 30000 40000
Vert
ical
def
lect
ion
[mm
]
Number of load cycles
Unreinforced (UN)
Carbon Fiber (CF)
Glass fiber (FP)
P0 = 1.5 kN
c)
0
5
10
15
0 10000 20000 30000 40000
Vert
ical
def
lect
ion
[mm
]
Number of load cycles
Carbon fiber (CF)
Glass fiber (FP)P0 = 2.0 kN
Fig. 11 Repeated loading 4PB test results – permanent deformation behavior at load levels:
a) 1.0 kN; b) 1.5 kN; c) 2.0 kN
6
0
5
10
15
20
1.51.0
Impr
ovem
ent F
acto
r, IF
Load level [kN]
Carbon Fiber (CF)Glass Fiber (FP)
Fig.12 Increase of permanent deformation resistance in 4PB test respect to the Unreinforced
interface type (UN)
0
500
1000
1500
2000
2.01.51.0
Initi
al v
alue
of E
app
[MPa
]
Load level [kN]
Unreinforced (UN)Carbon Fiber (CF)Glass Fiber (FP)
Fig. 13 Initial values of apparent stiffness
7
a)
200
2000
100 1000 10000 100000
Appa
rent
Stif
fnes
s M
odul
us [M
Pa]
Load cycles
Unreinforced (UN) Carbon fiber (CF) Glass Fiber (FP)
flex pointspecimen COLLAPSE
P0 = 1.0 kN
b)
200
2000
100 1000 10000 100000
Appa
rent
Stif
fnes
s M
odul
us [M
Pa]
Load cycles
Carbon Fiber (CF) Unreinforced (UN) Glass Fiber (FP)
flex pointspecimen COLLAPSE
P0 = 1.5 kN
c)
200
2000
100 1000 10000 100000
Appa
rent
Stif
fnes
s M
odul
us [M
Pa]
Load cycles
Carbon Fiber (CF) Glass Fiber (FP)
flex pointspecimen COLLAPSE
P0 = 2.0 kN
Fig.14 Repeated loading 4PB test results – Apparent stiffness evolution at load levels: a) 1.0 kN;
b) 1.5 kN; c) 2.0 kN
8
Bottom-up crackBottom-up crack
FP geogrid strands
Crack propagatesalong the interface
CF geogrid
Crack propagatesacross the interface
Fig. 15 Failure mechanisms of reinforced specimens in repeated loading 4PB test: a) FP geogrid;
b) CF geogrid
9
0
1
2
3
4
5
6
7
0 5 10 15
Load
P[k
N]
Deflection G [mm]
UN
a)
0
1
2
3
4
5
6
7
0 5 10 15
Load
P [k
N]
Deflection G [mm]
CF
b)
0
1
2
3
4
5
6
7
0 5 10 15
Load
P [k
N]
Deflection G [mm]
FP
c)
Fig. 16 Three Point Bending test results
10
0
1
2
3
4
5
6
7
0 5 10 15
Load
P [k
N]
Deflection G [mm]
CF1. Pre-cracking2. Delayed propagation3. Failure
1 2
3
1 2
3G [mm]
Fig. 17 Failure mechanisms of CF reinforced specimens in 3PB test
0
1
2
3
4
5
6
7
0 5 10 15
Load
P [k
N]
Deflection G [mm]
FP
1. Pre-cracking2. Delayed propagation3. Failure
12
3
1 2
3G [mm]
Fig. 18 Failure mechanisms of FP reinforced specimens in 3PB test
11
a)
0.0
m
1.0
m
2.0
m
12.8
m
14.0
m
15.0
m
7.0
m
8.6
m
De-bonding Simulated cracks
Instrumentedarea
3.8
m1.
2 m
5.0
m
0.4 m
0.4
m
Reference Wheel Path
b)
Fig. 19 Section B: a) layout of each experimental sub-section with position of instrumented area,
de-bonding and simulated cracks; b) detail of simulated cracks pattern in the lower layer
12
Fig. 20 Visual surveys of pavement condition above simulated cracks (section B)