shiri

Upload: mamatha-marri

Post on 04-Apr-2018

221 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/30/2019 Shiri

    1/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 1

    CHAPTER-1

    INTRODUCTION

    The present day electrical power system is a. c. i.e. electric power is generated, transmitted

    and distributed in the form of Alternating current. The electric power is produce at the

    power station, which are located at favorable places, generally quite away from the

    consumers. It is delivered to the consumer through a large network of transmission and

    distribution. At many place in the line of power system, it may be desirable and necessary to

    change some characteristic of electric supply. This is accomplished by suitable apparatus

    called sub-station for example, generation voltage (11KV or 6.6KV) at the power station is

    stepped up to high voltage (Say 220KV to 132KV) for transmission of electric power.

    Similarly near the consumers localities, the voltage may have to be stepped down to

    utilization level. This job is again accomplished by suitable apparatus called As substation

    About the substation 132/33 KV

    The substation near court chowrasta, in karimnagar is one of the power grids in the state of

    Andhra Pradesh .The main source of this substation is coming out from the durshed 220kv

    substation .132/33kv substation, karimnagar charged on date 27-08-1974.

    The 132kv feeding to the substation is from 220kv /132kv durshed substation. This

    substation under the control of superintending Engineer / TL &SS/ Karimnagar &Divisional

    Engineer / TL& SS/karimnagar.

    The following feeders are available in the substation 132/33 kv are

    1. 33KV DHARMARAM

    2. 33KV VAVILALAPALLY

    3. 33KV GANGADHARA

    4. 33 KV BHAGATH NAGAR

    5. 33KV BOINPALLY

    6. 33KV THOTAPALLY

    7. 33KV PADMANAGAR

    8. 33 KV WATER WORKS

    9. 33 KV CHOPPADANDI

  • 7/30/2019 Shiri

    2/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 2

    SINGLE LINE DIAGRAM OF 132/33 KV SUBSTATION

    a one-line diagram or single-line diagram is a simplified notation for representing a three-phase power system. The one-line diagram has its largest application in power flow studies.

    Electrical elements such as circuit breakers, transformers, capacitors, bus bars, and

    conductors are shown by standardized schematic symbols. Instead of representing each of

    three phases with a separate line or terminal, only one conductor is represented. It is a form

    of block diagram graphically depicting the paths for power flow between entities of the

    system. Elements on the diagram do not represent the physical size or location of the

    electrical equipment, but it is a common convention to organize the diagram with the same

    left-to-right, top-to-bottom sequence as the switchgear or other apparatus represented.

  • 7/30/2019 Shiri

    3/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 3

    SYMBOLS OF EQUIPMENTS USED IN A SUBSTATION

  • 7/30/2019 Shiri

    4/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 4

    CHAPTER-2

    SUBSTATION

    1.INTRODUCTION

    A substation may be defined as an assembly of apparatus, which transforms the

    characteristics of electrical energy from one form to another form.

    At generation stations the electric power is produced at low voltages. The electric power

    should not be transmitted at these low voltages due to large amount of line losses andeconomical reasons. To minimize the losses and for economical transmission the low

    voltages are stepped up to high voltages and transmitted to far off place. The

    consumers do not use such higher voltages directly and so they must be transformed to

    low voltages for distribution purpose and done in these substations .So the substation

    may be called as link between generation stations and consumers. The transmission

    voltages are 66KV,110KV,132KV,220KV,400KV etc. The distribution voltages generally

    used are 6.6KV,11KV and 33KV.

    Substations usually contain transformers in order to change voltage levels; they are

    connected to a "bus" via a circuit breaker. Specifically, substations are used for some or

    all of the following purposes: connection of generators, transmission or distribution

    lines, and loads to each other; transformation of power from one voltage level to

    another; interconnection of alternate sources of power; switching for alternate

    connections and isolation of failed or overloaded lines and equipment; controlling

    system voltage and power flow; reactive power compensation; suppression of

    overvoltage; and detection of faults, monitoring, recording of information, power

    measurements, and remote communications. Minor distribution or transmission

    equipment installation is not referred to as a substation.

  • 7/30/2019 Shiri

    5/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 5

    Substations present in the power system performs various operations depends on the

    application such as stepping up the voltage, stepping down the voltage, high voltage

    transmission and switching stations to route the power to desired load center.

    Substations are installed to perform any of the following operations.

    1. To switch ON and OFF the power lines, known as switching operation.

    2. To transform voltage from higher to lower or vice versa, known as voltage

    transformation operation.

    3. To convert A.C, into D.C. or vice versa, known as power converting operation.

    4. To convert frequency from higher to lower or vice-versa ,known as frequency

    converting operation.

    5. To improve the power factor by installing synchronous condenser at the end of

    the line, known as power factor correction operation.

  • 7/30/2019 Shiri

    6/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 6

    1.1 classification of sub-stations

    substations are classified according to service requirement and constructional

    features .

    1.According to service requirement: A substation may be called upon to change

    voltage or improve power factor or convert a. c. power into d. c. power etc.

    According to the service requirement, substations may be classified into

    a. Transformer substation:

    Those substations which change the voltage level of electric supply are called

    transformer substations. These substations receive power at some voltage and deliver it at

    some other voltage. Obviously, transformer will be the main component in such

    substations. Most of the sub stations in the power system are of this type.

    b. switching sub-station : These substations do not change the voltagelevel i.e. incoming and outgoing lines have the same voltage. However ,they

    simply perform the switching operations of power lines. A switching

    substation is a substation which does not contain transformers and operates

    only at a single voltage level. Switching substations are sometimes used as

    collector and distribution stations. Sometimes they are used for switching the

    current to back-up lines or for parallelizing circuits in case of failure

    c. Power factor correction substationThese sub-station which improve the power factor of the system are

    called power factor correction substation. These are generally located at

    receiving end of transmission lines. These substations generally use

    synchronous condensers as the power improvement equipment

    d. Frequency changer sub-station :

    Those sub-stations, which change the supply frequency, are known as

    frequency change sub- stations . Such sub-station may be required for industrial utilization.

    e. Converting sub-station :

    Those sub-station which change a. c. power into d. c. power are called converting

    s/s ignition is used to convert AC to dc power for traction, electroplating, electrical welding

    etc.

    f. Industrial sub-station:

  • 7/30/2019 Shiri

    7/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 7

    Those sub-stations, which supply power to individual industrial concerns are known

    as industrial sub-stations.

    2.According to constructional features : A substation has many components whichmust be housed properly to ensure continuous and reliable service. According to

    constructional features the substations are classified as :

    Indoor substation

    Outdoor substation

    Underground substation

    Pole-mounted substation

    1. Indoor Sub-station :-

    For voltage up to 11KV, the equipment of the s/s is installed indoor because of

    economic consideration. However, when the atmosphere is contaminated with impurities,

    these sub-stations can be erected for voltage up to 66KV.

    2. Outdoor Sub-Station :-

    Outdoor Substations are used for all voltage levels from 52 to 765 kV. They are built

    outside cities, usually at points along the cross-country lines of bulk transmission systems.

    They comprise switchgear like circuit breakers, disconnectors, instrument transformers,

    power transformers, surge arrestors and bus bars. The control and protection equipment is

    housed in central buildings or in small switching bay oriented containers in the

    switchyard .

    For voltage beyond 66KV, equipment is invariably installed outdoor. It is because for such

    Voltage the clearances between conductor and the space required for switches, C.B. and

    other equipment becomes so great that it is not economical to installed the equipment

    indoor.

    3. Under ground sub-station :-

    In thickly populated areas, the space available for equipment and building is limited

    and the cost of the land is high. Under such situations, the sub-station is created

    underground. The design of underground s/s requires more careful consideration.

    The size of the s/s should be as minimum as possible.

  • 7/30/2019 Shiri

    8/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 8

    There should be reasonable access for both equipment & personal.

    There should be provision for emergency lighting and protection against fire.

    There should be good ventilation

    4. Pole-mounted sub-station :-

    This is an outdoor sub-station with equipment installed overhead on double pole or 4-pole

    structure. It is the cheapest from of s/s for voltage not exceeding 11KV (or 33KV in some

    cases). Electric power is almost distributed in localities through such sub-station. The 11KV

    line is connected to the T/F through gang isolator and fuses. The lighting arresters are

    installed on the H.T. Side to protect the sub-station from lighting strokes. The T/F step

    down voltage to 400 V, 3 phase, 4 wire supply. The voltage between any two lines is 400 V

    & between line & neutral is 230V. The oil circuit breaker installed on the L.T. side

    automatically Isolates the mounted sub-station.T/F are generally in the event of faultgenerally 200 KVA T/F is used.

    FUNCTIONS OF SUBSTATION:

    1. Supply of required electrical power.

    2. Maximum possible coverage of the supply network.

    3. Maximum security of supply.

    4. Shortest possible fault-duration

    5. Optimum efficiency of plants and the network.

    6. Supply of electrical power within targeted frequency limits, (49.5 Hz and50.5 Hz).

    7. Supply of electrical power within specified voltage limits.

    8. Supply of electrical energy to the consumers at the lowest cost

    CHAPTER-3

  • 7/30/2019 Shiri

    9/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 9

    EQUIPMENTS IN A SUB-STATION

    The main equipments in a sub-station are:

    1. BUS BARS

    2. INSULATORS

    3. CIRCUIT BREAKER

    4. INSTRUMENT TRANSFORMER

    5. POWER TRANSFORMER

    6. WAVE TRAP

    7. SWITCH GEAR

    8. ISOLATORS

    9. MISCELLONOUS EQUIPMENTS

    10.PROTECTIVE RELAY

  • 7/30/2019 Shiri

    10/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 10

    1. BUS BARS

    When a no. of lines operating at the same voltage have to be directly connected electrically,

    bus-bars are used, it is made up of copper or aluminum bars (generally of rectangular X-

    Section) and operate at constant voltage.Duplicate bus-bar, generally it consist of two bus-bars a main bus-bar and spare bus-

    bar. The incoming and outgoing lines can be connected to either b/b. With the help of a bus-

    bar coupler, which consist of a circuit breaker and isolators. However, in case of repair of

    main bus-bar or fault accusing on it, the continuity of supply to the circuit can be maintain

    by transforming it to the spare bus-bar for voltage exceeding 33KV, Duplicate bus-bar is

    frequently used.

    Bus bars , or buses, are conductors. Or group of conductors, that serve as a common

    connection for two or more circuits. The bus bars experience forces when currents flow in

    them. These forces can be great when short-circuit currents flow. A bus bar must be able towithstand the forces caused by the flow of fault currents. Bur bars are the important

    elements in the electrical substation. Bus bars acts as nodal point in the substation, which

    connects different incoming and outgoing circuits.

    Bus bars used in the substations are generally rectangular or circular cross section bars.

    These bus bars can be either solid or hollow structures. Hollow circular cross section bus

    bars are employs in EHV substations to reduce the corona effect.

    An aluminum or copper conductor supported by insulators that interconnects the loads and

    the sources of electric power in an electric power system. A typical application is the

    interconnection of the incoming and outgoing transmission lines and transformers at an

    electrical substation. Bus-bars also interconnect the generator and the main transformers ina power plant. In an industrial plant such as an aluminum smelter, large bus-bars supply

    several tens of thousands of amperes to the electrolytic process. See also Electric power

    substation.

    The size of the bus bar determines its application and the amount of current that it can carry

    safely. They can be tubular, solid or flat depending on the application and to serve different

    needs.

    Various incoming and outgoing circuits are connected to bus bars. Bus bars receive power

    from incoming circuits and deliver power to outgoing circuits.

  • 7/30/2019 Shiri

    11/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 11

    Bus bars are usually made up of Aluminum or copper and they are able to conduct

    electricity to transmit power from the source of electric power to the load. They are usually

    supported by insulators and conduct electricity within switchboards, substations or other

    electric apparatus. Some typical applications of these devices can be to form the

    interconnectedness of the incoming and outgoing electrical transmission lines and

    transformers at an electrical substation; supplying huge amounts of amperes to the

    electrolytic process in an aluminum smelter by using large bus bars and also interconnecting

    generators to the main transformers in a power plant.

    Different types of bus bar arrangements are employed based on the voltage, reliability of

    the supply, flexibility in transmitting power and cost. The other aspects considering in

    designing the bus bars arrangements are:

    1. Simplicity in the design

    2. Maintenance of different elements without interruption in the power supply

    3. Future expansion feasibility

    4. Economical in cost of installation and operation

    Different bus bar arrangements:

    Some of the switching schemes are bus bar arrangements employed in the substations are

    listed below:

    1. Single Bus-bar arrangement

    2. Double Main Bus-bar scheme

    3. Main and Transfer bus-bar scheme

    4. One and half breaker scheme

    5. Ring Main arrangement scheme

    1) Single Bus-bar scheme:

  • 7/30/2019 Shiri

    12/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 12

    This is the simplest bus bar scheme available which consists of single set of bus bars

    connected to the generators, transformers and load feeders. All the feeders are connected

    by circuit breaker and set of isolators. This arrangement helps to remove the connecting

    elements (Generators, transformers, etc ) for maintenance by opening the circuit breaker

    contacts and further opening the isolators. The entire Sub Station is lost in case of a fault on

    the bus bar or on any bus bar isolator and also in case of maintenance of the bus bar.

    Another disadvantage of this switching scheme is that in case of maintenance of circuit

    breaker, the associated feeder has also to be shutdown.

    Advantages:

    1. This bus bar arrangement enjoys less cost of installation

    2. Less maintenance

    3. simple operation

    Disadvantages:

    1. Fault on the bus bar all the feeders connected to the bus bars should be disconnected

    2. when Bus bar is under maintenance total supply and all feeders should be

    disconnected

    3. Least flexibility and reliability

    2) DOUBLE BUS BAR ARRANGEMENT:

    In this double bus bar arrangement , Each circuit can be connected to either one of these

    bus bars through respective bus bar isolator. Bus coupler breaker is also provided so that

    the circuits can be switched on from one bus to the other on load. This scheme suffers from

    the disadvantage that when any circuit breaker is taken out for maintenance, the associated

    feeder has to be shutdown.

    This Bus bar arrangement was generally used in earlier 220 kV sub stations

    3) Main and Transfer Bus bar Scheme:

    Main and Transfer bus bar scheme is similar to single bus bar arrangement with

    additional transfer bus connected. Tie circuit breaker is provided to tie both the main and

    transfer bus. During normal operation all the circuits are connected to the main bus. When

    circuit breaker connected to the circuit (transmission line) is required to trip for

  • 7/30/2019 Shiri

    13/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 13

    maintenance, tie circuit breaker connecting the main and transfer bus is closed. The relay

    protection for the circuits connected to the transfer bus is taken care by the tie circuit

    breaker.

    Advantages:

    1. Low initial cost

    2. Any breaker can be taken of circuit for maintenance

    Disadvantages:

    1. Requires one extra breaker for bus tie

    2. Switching is somewhat complicated when breaker is under maintenance

    4) One and Half breaker Bus bar scheme:

    In One and half breaker scheme, two circuits are connected between the three

    circuit breakers. Hence One and Half breaker name was coined for this type of arrangement.

    Under normal operating conditions all the breakers are closed and both the bus bars are

    energized. Any Circuit fault will trip two circuit breakers and no other circuit will be affected

    in this arrangement. When a bus bar fault occur only breakers adjacent to bus bars trips and

    no circuit will loose power. Two bus bars can also be taken out of service without affectingthe power flow if the power source circuit ( alternator circuit) and receiving circuit

    (transmission line) available in the same bay.

    Advantages:

    1. Most flexible operation possible

    2. High reliability

    3. Bus failure will not remove any circuit from service

    Disadvantages:

    1. High cost

    2. Relaying is somewhat complicated since the middle breaker must responsible for both

    the circuits on either direction and should operate

    5) Ring bus bar scheme:

    In this ring main bus bar scheme arrangement, breakers are connected in ring and

    circuits are connected between the breakers. There will be same number of circuits as the

    number of breakers in the arrangement. During normal operation all the breakers are

  • 7/30/2019 Shiri

    14/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 14

    closed. During circuit fault two breakers connecting the circuit trips. During breaker

    maintenance the ring is broken but all the lines remain in service.

    Advantages:

    1. Low cost

    2. Flexible operation for breaker maintenance

    3. Any breaker can be taken out of service without interrupting load

    4. Power can be fed from both the direction

    Disadvantages:

    1. Fault occur during maintenance will break the ring

    2. Relaying is complex

    3. Breaker failure during fault will trip one additional circuit

    Major Type of Bus bar

    The major types are

    (1) Rigid bus-bars, used at low, medium, and high voltage

    The rigid bus-bar is an aluminum or copper bar, which is supported by porcelain insulators.

    The rigid bus-bar provides a quick and qualified installation, the necessary compensation of

    linear thermal deformations of buses and minor errors in the installation of bus-barsupports

    (2) Strain bus-bars, used mainly for high voltage

    The strain bus-bar is a flexible, stranded conductor which is strung between substation

    metal structures and held by suspension-type insulators.

    (3) Insulated-phase bus-bars, used at medium voltage

    The insulated-phase bus-bar is a rigid bar supported by insulators and covered by agrounded metal shield. The main advantage of this system is the elimination of short circuits

    between adjacent phases.

    (4) Sulfur hexafluoride (SF6)-insulated bus-bars, used in medium- and high-

    voltage systems

    The sulfur hexafluoride-insulated bus-bar is a rigid aluminum tube, supported by insulators

    and installed in a larger metal tube, which is filled with high-pressure sulfur hexafluoride

    gas.

  • 7/30/2019 Shiri

    15/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 15

    Advantages of Bus barView

    Fitting of any modular device with the same mounting height Components interchangeable at any time

    Compact energy distribution up to max. 150A

    Full scope for the future

    Completely touch proof

    http://www.ustudy.in/node/6355http://www.ustudy.in/node/6355http://www.ustudy.in/node/6355
  • 7/30/2019 Shiri

    16/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 16

    Circuit breaker

    A circuit breaker is an automatically operated electrical switch designed to protect

    an electrical circuit from damage caused by overload or short circuit. Its basic function is to

    detect a fault condition and, by interrupting continuity, to immediately discontinue electrical

    flow. Unlike a fuse, which operates once and then has to be replaced, a circuit breaker can be

    reset (either manually or automatically) to resume normal operation. Circuit breakers are

    made in varying sizes, from small devices that protect an individual household appliance up

    to large switchgear designed to protect high voltage circuits feeding an entire city.

    Fig 1.1.1 An air circuit breaker forlow voltage (less than 1000 volts) power distribution switchgear

    Operation

    http://wiki.ask.com/Electricity?qsrc=3044http://wiki.ask.com/Switch?qsrc=3044http://wiki.ask.com/Electrical_network?qsrc=3044http://wiki.ask.com/Overcurrent?qsrc=3044http://wiki.ask.com/Short_circuit?qsrc=3044http://wiki.ask.com/Fuse_%28electrical%29?qsrc=3044http://wiki.ask.com/Switchgear?qsrc=3044http://wiki.ask.com/Switchgear?qsrc=3044http://wiki.ask.com/Fuse_%28electrical%29?qsrc=3044http://wiki.ask.com/Short_circuit?qsrc=3044http://wiki.ask.com/Overcurrent?qsrc=3044http://wiki.ask.com/Electrical_network?qsrc=3044http://wiki.ask.com/Switch?qsrc=3044http://wiki.ask.com/Electricity?qsrc=3044
  • 7/30/2019 Shiri

    17/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 17

    All circuit breakers have common features in their operation, although details vary

    substantially depending on the voltage class, current rating and type of the circuit breaker.

    The circuit breaker must detect a fault condition; in low-voltage circuit breakers this is

    usually done within the breaker enclosure. Circuit breakers for large currents or high voltages

    are usually arranged with pilot devices to sense a fault current and to operate the trip opening

    mechanism. The trip solenoid that releases the latch is usually energized by a separate

    battery, although some high-voltage circuit breakers are self-contained with current

    transformers, protection relays, and an internal control power source.

    Once a fault is detected, contacts within the circuit breaker must open to interrupt

    the circuit; some mechanically-stored energy (using something such as springs or compressed

    air) contained within the breaker is used to separate the contacts, although some of the energy

    required may be obtained from the fault current itself. Small circuit breakers may be

    manually operated; larger units have solenoids to trip the mechanism, and electric motors to

    restore energy to the springs.The circuit breaker contacts must carry the load current without

    excessive heating, and must also withstand the heat of the arc produced when interrupting

    (opening) the circuit. Contacts are made of copper or copper alloys, silver alloys, and other

    highly conductive materials. Service life of the contacts is limited by the erosion of contact

    material due to arcing while interrupting the current. Miniature and molded case circuit

    breakers are usually discarded when the contacts have worn, but power circuit breakers and

    high-voltage circuit breakers have replaceable contacts.

    When a current is interrupted, an arc is generated. This arc must be contained, cooled,

    and extinguished in a controlled way, so that the gap between the contacts can again

    withstand the voltage in the circuit. Different circuit breakers use vacuum, air, insulating gas,

    or oil as the medium in which the arc forms. Different techniques are used to extinguish the

    arc including:

    Lengthening / deflection of the arc

    Intensive cooling (in jet chambers)

    Division into partial arcs

    Zero point quenching (Contacts open at the zero current time crossing of the AC

    waveform, effectively breaking no load current at the time of opening. The zero crossing

    occurs at twice the line frequency i.e. 100 times per second for 50Hz and 120 times per

    second for 60Hz AC)

    http://wiki.ask.com/Relay?qsrc=3044http://wiki.ask.com/Solenoid?qsrc=3044http://wiki.ask.com/Solenoid?qsrc=3044http://wiki.ask.com/Electric_arc?qsrc=3044http://wiki.ask.com/Vacuum?qsrc=3044http://wiki.ask.com/Insulating_gas?qsrc=3044http://wiki.ask.com/Transformer_oil?qsrc=3044http://wiki.ask.com/Transformer_oil?qsrc=3044http://wiki.ask.com/Insulating_gas?qsrc=3044http://wiki.ask.com/Vacuum?qsrc=3044http://wiki.ask.com/Electric_arc?qsrc=3044http://wiki.ask.com/Solenoid?qsrc=3044http://wiki.ask.com/Solenoid?qsrc=3044http://wiki.ask.com/Relay?qsrc=3044
  • 7/30/2019 Shiri

    18/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 18

    Connecting capacitors in parallel with contacts in DC circuits

    Finally, once the fault condition has been cleared, the contacts must again be closed to restore

    power to the interrupted circuit.

    Arc interruption

    Miniature low-voltage circuit breakers use air alone to extinguish the arc. Larger

    ratings will have metal plates or non-metallic arc chutes to divide and cool the arc. Magnetic

    blowout coils or permanent magnets deflect the arc into the arc chute.

    In larger ratings, oil circuit breakers rely upon vaporization of some of the oil to blast a jet of

    oil through the arc. Gas (usually sulfur hexafluoride) circuit breakers sometimes stretch the

    arc using a magnetic field, and then rely upon the dielectric strength of the sulfur

    hexafluoride (SF6) to quench the stretched arc. Vacuum circuit breakers have minimal arcing

    (as there is nothing to ionize other than the contact material), so the arc quenches when it is

    stretched a very small amount (

  • 7/30/2019 Shiri

    19/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 19

    installed in. Therefore, circuit breakers must incorporate various features to divide and

    extinguish the arc.

    In air-insulated and miniature breakers an arc chute structure consisting (often)

    of metal plates or ceramic ridges cools the arc, and magnetic blowout coils deflect the arc

    into the arc chute. Larger circuit breakers such as those used in electrical power distribution

    may use vacuum, an inert gas such as sulphur hexafluoride or have contacts immersed in oil

    to suppress the arc.

    The maximum short-circuit current that a breaker can interrupt is determined by

    testing. Application of a breaker in a circuit with a prospective short-circuit current higher

    than fault. In a worst-case scenario the breaker may successfully interrupt the fault, only to

    explode when reset. Miniature circuit breakers used to protect control circuits or small

    appliances may not have sufficient interrupting capacity to use at a panelboard; these circuit

    breakers are called "supplemental circuit protectors" to distinguish them from distribution-

    type circuit breakers.

    CLASSIFICATION OF CIRCUIT BREAKERS:

    1.Air-break circuit breakers

    2.Oil circuit breakers

    3.Air-blast circuit breakers

    4.SF6 circuit breakers

    5.vacuum circuit breakers

    3.1 SF6 gas Circuit breakers

    In this circuit breaker, sulphurhexaflouride ( SF6 ) gas is used as the arc

    quenching medium. The SF6 gas is an electro negative gas and has a strong tendency to

    absorb free electrons. The contacts of the breaker are opened in a high pressure flow of SF6

    gas and an arc is struck between them. The conducting free electrons in the arc are rapidly

    captured by the gas to form relatively immobile negative ions. This loss of conducting

    electrons in the arc quickly builds up enough insulation strength to extinguish the arc. The

    SF6 circuit breakers are very effective for high power and high voltage service.

    Construction: Fig 15 shows the parts of a typical SF6 circuit breaker. It consists of fixed

    and moving contacts enclosed in a chamber called arc interruption chamber containing SF 6

    http://wiki.ask.com/Magnetic_blowout?qsrc=3044http://wiki.ask.com/Power_distribution?qsrc=3044http://wiki.ask.com/Vacuum?qsrc=3044http://wiki.ask.com/Inert?qsrc=3044http://wiki.ask.com/Gas?qsrc=3044http://wiki.ask.com/Sulphur_hexafluoride?qsrc=3044http://wiki.ask.com/Oil?qsrc=3044http://wiki.ask.com/Oil?qsrc=3044http://wiki.ask.com/Sulphur_hexafluoride?qsrc=3044http://wiki.ask.com/Gas?qsrc=3044http://wiki.ask.com/Inert?qsrc=3044http://wiki.ask.com/Vacuum?qsrc=3044http://wiki.ask.com/Power_distribution?qsrc=3044http://wiki.ask.com/Magnetic_blowout?qsrc=3044
  • 7/30/2019 Shiri

    20/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 20

    gas. This chamber is connected to SF6 gas reservoir. When the contacts of breaker are opened

    the valve mechanism permits a high pressure SF6 gas from the reservoir to flow towards the

    arc interruption chamber. The fixed contact is a hollow cylindrical current carrying contact

    fitted with an arc horn. The moving contact is also a hollow cylinder with rectangular holes in

    the sides to permit the SF6 gas to let out through these holes after flowing along and across

    the arc. The tips of fixed contact, moving contact and arcing horn are coated with copper-

    tungsten arc resistant material. Since SF6 gas is costly, its reconditioned and reclaimed by a

    suitable auxiliary system after each operation of the breaker.

    Working:

    In t closed position of the breaker the contacts remained surrounded by SF6 gas at a pressure

    heof about 2.8 kg/cm2. When the breaker operates the moving contact is pulled apart and an

    arc is struck between the contacts. The movement of the moving contact is synchronized with

    the opening of a valve which permits SF6 gas at 14 kg/cm2

    pressure from the reservoir to the

    arc interruption chamber.

    The high pressure flow of SF6 rapidly absorbs the free electrons in the arc path to

    form immobile negative ions which are ineffective as charge a carriers. The result is that the

    medium between the contacts quickly builds up high dielectric strength and causes the

    extinction of the arc. After the breaker operation the valve is closed by the action of a set of

    springs.

    Advantages over oil and air circuit breakers:

    a.Due to superior arc quenching property of SF6 , such breakers have very short arcing time

  • 7/30/2019 Shiri

    21/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 21

    b.Dielectric strength of SF6 gas is 2 to 3 times that of air, such breakers can interrupt much

    larger currents.

    c.Gives noiseless operation due to its closed gas circuit

    d.Closed gas enclosure keeps the interior dry so that there is no moisture problem

    e.There is no risk of fire as SF6 is non inflammable

    f.There are no carbon deposits

    g.Low maintenance cost, light foundation requirements and minimum auxiliary equipment

    h.SF6 breakers are totally enclosed and sealed from atmosphere, they are particularly su h.

    SF6 breakers are totally enclosed and sealed from atmosphere, they are particularly suitable

    where explosion hazard exists

    Disadvantages:

    SF6 breakers are costly due to high cost of SF6

    B. SF6 gas has to be reconditioned after every operation of the breaker, additional

    equipment is required for this purpose

    Applications:

    SF6 breakers have been used for voltages 115kV to 230 kV, power ratings 10 MVAto 20 MVA and interrupting time less than 3 cycles

    SF6 gas circuit breakers are the most widely used ones today. SF6 is an

    electronegative gas and is excellent for use as an arc quenching medium. The principle is

    similar to that of ABCBs. SF6 gas breakers have many advantages such as compactness, less

    maintenance, efficient arc interruption and low cost. Owing to the above advantages it has

    now replaced all other breakers in Medium Voltage, High Voltage, Extra High Voltage and

    Ultra High Voltage ranges. The operating voltage range is from 52kV to 765kV

    Sulfur hexafluoride (SF6) is an excellent gaseous dielectric for high voltage power

    applications. It is used extensively in high voltage circuit breakers and other switchgear

    employed by the power industry.

  • 7/30/2019 Shiri

    22/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 22

    The combined electrical, physical, chemical and thermal properties offer many

    advantages when used in power switchgear. Some of the properties of SF6 which make its

    use in power applications desirable are:

    High dielectric strength

    Unique arc-quenching ability

    High thermal stability

    Good thermal conductivity

    Electro negative gas

    Vacuum circuit breaker: Vacuum circuit breaker:

    In this breaker, vacuum is being used as the arc quenching medium. Vacuum offers

    highest insulating strength, it has far superior arc quenching properties than any othermedium. When contacts of a breaker are opened in vacuum, the interruption occurs at first

    current zero with dielectric strength between the contacts building up at a rate thousands of

    times that obtained with other circuit breakers.

    Principle:

    When the contacts of the breaker are opened in vacuum (10 -7 to 10 -5 torr), an arc is

    produced between the contacts by the ionization of metal vapours of contacts. The arc is

    quickly extinguished because the metallic vapours, electrons, and ions produced during arccondense quickly on the surfaces of the circuit breaker contacts, resulting in quick recovery

    of dielectric strength. As soon as the arc is produced in vacuum, it is quickly extinguished

    due to the fast rate of recovery of dielectric strength in vacuum.

    Construction:

    Fig 16 shows the parts of a typical vacuum circuit breaker. It consists of fixed

    contact, moving contact and arc shield mounted inside a vacuum chamber. The movable

    member is connected to the control mechanism by stainless steel bellows .This enables thepermanent sealing of the vacuum chamber so as to eliminate the possibility of leak .A glass

    vessel or ceramic vessel is used as the outer insulating body. The arc shield prevents the

    deterioration of the internal dielectric strength by preventing metallic vapours falling on the

    inside surface of the outer insulating cover.

  • 7/30/2019 Shiri

    23/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 23

    Working: Working:

    When the breaker operates the moving contacts separates from the fixed contacts and

    an arc is struck between the contacts. The production of arc is due to the ionization of metal

    ions and depends very much upon the material of contacts. The arc is quickly extinguished

    because the metallic vapours, electrons and ions produced during arc are diffused in short

    time and seized by the surfaces of moving and fixed members and shields.

    Since vacuum has very fast rate of recovery of dielectric strength, the arc extinction in

    a vacuum breaker occurs with a short contact separation.

    Advantages:

    a. They are compact, reliable and have longer life.

    b. There are no fire hazards

    c. There is no generation of gas during and after operation

    d. They can interrupt any fault current. The outstanding feature of a VCB is that it can break

    any heavy fault current perfectly just before the contacts reach the definite open position.

    e. They require little maintenance and are quiet in operation

    f. Can withstand lightning surges

    g. Low arc energy

    h. Low inertia and hence require smaller power for control mechanism.

    4.2Applications:

  • 7/30/2019 Shiri

    24/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 24

    For outdoor applications ranging from 22 kV to 66 kV. Suitable for majority of

    applications in rural area.

    Fig 4.2 vacuum circuit breaker

  • 7/30/2019 Shiri

    25/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 25

  • 7/30/2019 Shiri

    26/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 26

    3.CIRCUIT BREAKERS3 Oil circuit breaker

    Oil circuit breakers are further classified as

    Bulk oil Circuit Breakers (BOCB)

    Minimum oil Circuit breakers (MOCB)

    In BOCBs the interrupting Chambers is placed in tank of oil at earth potential and the

    incoming and outgoing conductors are connected through insulator bushings and in MOCBs

    the interrupting units are placed in insulating chambers at live potential.

    In oil circuit breaker the arc drawn across the contacts is contained inside the interrupting

    pot and thus the hydrogen bubble, formed by the vaporised oil (gas) is also contained inside

    the chamber. As the contacts continue to move and whenever the moving contact rod

    separates itself from the orifice at the bottom of the chamber, an exit similar to a nozzle

    becomes available for exhausting the hydrogen that is trapped inside the interrupting

    chamber. The operating voltage range is up to 132kV[1]

    .

  • 7/30/2019 Shiri

    27/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 27

    The oil in OCBs serves two purposes. It insulates between

    the phases and between the phases and the ground, and it provides the medium for the

    extinguishing of the arc. When electric arc is drawn under oil, the arc vaporizes the oil and

    creates a large bubble that surrounds the arc. The gas inside the bubble is around 80%

    hydrogen, which impairs ionization. The decomposition of oil into gas requires energy that

    comes from the heat generated by the arc. The oil surrounding the bubble conducts the heat

    away from the arc and thus also contributes to deionization of the arc. Main disadvantage of

    the oil circuit breakers is the flammability of the oil, and the maintenance necessary to keep

    the oil in good condition (i.e. changing and purifying the oil)

    4.3.1 Bulk Oil Circuit Breakers

    Bulk oil circuit breakers are enclosed in metal-grounded weatherproof tanks that are

    referred to as dead tanks. The original design of bulk OCBs was very simple and inexpensive.Example of such a breaker, called plain break oil circuit breaker, is in

    The arc was drawn directly inside of the container tank without any additional arc

    extinguishing but the one provided by the gas bubble surrounding the arc. Plain break

    breakers were superceded by arc controlled oil breakers.

    The arc controlled oil breakers have an arc control device surrounding the breaker

    contacts. The purpose of the arc control devices is to improve operating capacity, speed up

  • 7/30/2019 Shiri

    28/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 28

    the extinction of arc, and decrease pressure on the tank. The arc control devices can be

    classified into two groups: cross-blast and axial blast interrupters.

    In cross blast interrupters, the arc is drawn in front of several lateral vents. The gas

    formed by the arc causes high pressure inside the arc control device. The arc is forced to bow

    into the lateral vents in the pot, which increases the length of the arc and shortens the

    interruption time. The axial blast interrupters use similar principle as the cross blast

    interrupters. However, the axial design has a better dispersion of the gas from the interrupter.

    Figure 12 illustrates a typical 69 kV breaker of 2500 MVA breaking capacity. All

    three phases are installed in the same tank. The tank is made of steel and is grounded. This

    type of breaker arrangement is called the dead tank construction. The moving contact of each

    phase of the circuit breaker is mounted on a lift rod of insulating material. There are two

    breaks per phase during the breaker opening. The arc control pots are fitted over the fixed

    contacts. Resistors parallel to the breaker contacts may be installed alongside the arc control

    pots. It is customary and convenient for this type of breakers to mount current transformers

    in the breaker bushings.

  • 7/30/2019 Shiri

    29/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 29

  • 7/30/2019 Shiri

    30/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 30

    The oil in OCBs serves two purposes. It insulates between the phases and

    between the phases and the ground, and it provides the medium for the extinguishing of the

    arc. When electric arc is drawn under oil, the arc vaporizes the oil and creates a large bubblethat surrounds the arc. The gas inside the bubble is around 80% hydrogen, which impairs

    ionization. The decomposition of oil into gas requires energy that comes from the heat

    generated by the arc. The oil surrounding the bubble conducts the heat away from the arc and

    thus also contributes to deionization of the arc. Main disadvantage of the oil circuit breakers

    is the flammability of the oil, and the maintenance necessary to keep the oil in good condition

    (i.e. changing and purifying the oil)

    4.3.1 Bulk Oil Circuit Breakers

    Bulk oil circuit breakers are enclosed in metal-grounded weatherproof tanks that are

    referred to as dead tanks. The original design of bulk OCBs was very simple and inexpensive.

    Example of such a breaker, called plain break oil circuit breaker, is in

    The arc was drawn directly inside of the container tank without any additional arc

    extinguishing but the one provided by the gas bubble surrounding the arc. Plain break

    breakers were superceded by arc controlled oil breakers.

    The arc controlled oil breakers have an arc control device surrounding the breaker

    contacts. The purpose of the arc control devices is to improve operating capacity, speed up

    the extinction of arc, and decrease pressure on the tank. The arc control devices can be

    classified into two groups: cross-blast and axial blast interrupters.

    In cross blast interrupters, the arc is drawn in front of several lateral vents. The gas

    formed by the arc causes high pressure inside the arc control device. The arc is forced to bow

    into the lateral vents in the pot, which increases the length of the arc and shortens the

    interruption time. The axial blast interrupters use similar principle as the cross blast

    interrupters. However, the axial design has a better dispersion of the gas from the interrupter.

    Figure 12 illustrates a typical 69 kV breaker of 2500 MVA breaking capacity. All

    three phases are installed in the same tank. The tank is made of steel and is grounded. This

    type of breaker arrangement is called the dead tank construction. The moving contact of each

    phase of the circuit breaker is mounted on a lift rod of insulating material. There are two

  • 7/30/2019 Shiri

    31/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 31

    breaks per phase during the breaker opening. The arc control pots are fitted over the fixed

    contacts. Resistors parallel to the breaker contacts may be installed alongside the arc control

    pots. It is customary and convenient for this type of breakers to mount current transformers

    in the breaker bushings.

    1 bushing 6 plunger guide

    2 oil level indicator 7 arc control device3 vent 8 resistor

    4 current transformer 9 plunger bar

    5 dashpot

  • 7/30/2019 Shiri

    32/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 32

    At voltages higher than 115 kV, it is customary to use separate tanks for each phase.

    The practical limit for the bulk oil breakers is 275 kV. Figure 13 shows 220 kV one phase

    dead tank circuit breaker.

    1 bushing 7 arc control unit

    2 oil level indicator 8 parallel contact

    3 vent 9 resistor

    4 linear linkage 10 plunger bar

    5 dashpot 11 impulse cushion

    6 guide block

    The oil circuit breakers are usually installed on concrete foundations at the ground

    level. During interruption of heavy fault currents the breakers tend to move. To minimize the

    damage to the breakers, breakers with very high interrupting capacity have an impulse

    cushion is provided at the bottom of the breakers. The cushion is filled with an inert gas, for

    example nitrogen.

  • 7/30/2019 Shiri

    33/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 33

  • 7/30/2019 Shiri

    34/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 34

    1

    bushing 7 arc control unit

    2 oil level indicator 8 parallel contact3 vent 9 resistor

    4 linear linkage 10 plunger bar

    5 dashpot 11 impulse cushion

    6 guide block

    The oil circuit breakers are usually installed on concrete foundations at the ground

    level. During interruption of heavy fault currents the breakers tend to move. To minimize the

    damage to the breakers, breakers with very high interrupting capacity have an impulse

    cushion is provided at the bottom of the breakers. The cushion is filled with an inert gas, for

    example nitrogen.

    4.3.2 Minimum Oil Breakers

    In the bulk oil breakers, the oil serves as both arcs extinguishing medium and main

    insulation. The minimum oil breakers were developed to reduce the oil volume only to

  • 7/30/2019 Shiri

    35/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 35

    amount needed for extinguishing of the arc about 10% of the bulk- oil amount. The arc

    control for the minimum oil breakers is based on the same principle as the arc control devices

    of the bulk oil breakers. To improve breaker performance, oil is injected into the arc.

    The interrupter containers of the minimum oil breakers are made of insulating

    material and are insulated from the ground. This is usually referred to as live tank

    construction. For high voltages (above 132 kV), the interrupters are arranged in series. It is

    essential to ensure that each interrupter carries its share of the duty. Care must be taken that

    all breaks occur simultaneously, and that the restriking voltage is divided equally across the

    breaks during the interrupting process. The natural voltage division depends on stray

    capacitances between the contacts and to the ground, and therefore is in very uneven. This is

    corrected by connecting capacitances or resistors in parallel with the interrupting heads.

  • 7/30/2019 Shiri

    36/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 36

    5.1 Oil circuit breaker

  • 7/30/2019 Shiri

    37/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 37

    5.1 Representation of electrical arc in oil circuit breaker

    In oil circuit breakers, the arc is drawn in oil inside a special compartment of the interrupting

    chamber called the explosion pot. The intense heat of the arc decomposes the oil and

    produces gases, mainly composed of hydrogen, generating high pressure that produces a fluid

    flow through the arc and out of the

    explosion pot through vents situated on its walls. Thus extending the arcs column and

    carrying its energy away until its total extension see Fig 3.

    At transmission voltages below 345 kV, oil breakers used to be popular. They are

    increasingly losing ground to gas-blast circuit breakers such as air-blast breakers and SF6

    circuit breakers.

    5.2 Air-blast circuit breaker

    In air-blast circuit breakers, compressed air at a pressure of 20-30kg/cm2 is employed as an

    arc quenching medalhemicium.These breakers are suitable for operating voltage of 132kv and

    above. When the contacts part, a blast valve is opened to discharge the high-pressure air to

    the ambient, thus creating a very-high-velocity flow near the arc to dissipate the energy.

    ADVANTAGES:

  • 7/30/2019 Shiri

    38/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 38

    i.cheapness and free availability of the interrupting medium,chemical stability and inertness

    of air

    ii.high speed operation

    iii.elimination of fire hazard

    iv.less maintanence

    v.suitability for frequent operation

    vi.facility for high speed reclosure

    DISADVANTAGES:

    i.An air compressor plant has to be installed and maintained

    ii.problem of current chopping

    iii.problem of restriking voltage

    This breaker is classified into 2 types

    1.Cross blast circuit breakers

    2.Axial blast circuit breakers

    A circuit breaker is an automatically operated electrical switch designed to protect an

    electrical circuit from damage caused by overload or short circuit. Its basic function is to

    detect a fault condition and, by interrupting continuity, to immediately discontinue

    electrical flow. Unlike a fuse, which operates once and then must be replaced, a circuit

  • 7/30/2019 Shiri

    39/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 39

    breaker can be reset (either manually or automatically) to resume normal operation. Circuit

    breakers are made in varying sizes, from small devices that protect an individual household

    appliance up to large switchgear designed to protect high voltage circuits feeding an entire

    city.

    Circuit-breakers are used to make or break electric currents in circuits during normal

    operation of the system, during system faults and during system disturbances. Most high

    voltage circuit breakers are physically located in the switchyard but are operated from

    panels provided in the control room.

    Acircuit-breaker is expected to have the following characteristics.

    It must be capable of closing on to and carrying full load currents.

    It must have an appropriate mechanism to automatically disconnect the

    Load under prescribed conditions.

    It must be able to successfully interrupt short-circuit currents flowing

    through the lines controlled by it.

    The gaps between its contacts must not flash-over when the circuit breaker

    is open.

    The circuit breaker, when closed on to a circuit in which a fault exists,

    must be able to reopen to isolate the faulted section without being

    damaged.

    It must be capable of withstanding the flow of short-circuit currents until

    they are interrupted by an adjoining circuit breaker. It must be capable of withstanding the electro-magnetic forces and thermal stresses

    caused by the flow of short-circuit currents.

  • 7/30/2019 Shiri

    40/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 40

    Circuit breaker

    Different types of circuit breakers are used in the substations which depends upon

    maximum voltage level, maximum continuous current carrying capacity and maximum

    interrupting capacity.

    Low Voltage Circuit Breaker:

    These breakers are made for direct current (DC) applications and are commonly used in

    domestic, commercial, and industrial fields. They can be installed in multi-tiers in LV

    switchboards or switchgear cabinets. Low voltage circuit breakers are usually placed in

    draw-out enclosures that permit removal and interchange without dismantling the

    switchgear. Miniature circuit breakers (MCB) and molded case circuit breakers (MCCB) are

    some common types of low voltage circuit breakers.

    Medium Voltage Circuit Breakers:

    These breakers can be assembled into metal enclosed switchgear line used for indoor

    applications, or as individual components for outdoor applications like substations. Medium

    voltage circuit breakers use discrete current sensors and protection relays, and can be

    attached into the circuit by bolted connections to bus bars or wires. Vacuum circuit

    breakers, air circuit breakers and SF6 circuit breakers are some examples of medium voltage

    circuit breakers.

  • 7/30/2019 Shiri

    41/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 41

    High Voltage Circuit Breakers:

    These breakers help in protecting and controlling electrical power transmission networks.

    They are solenoid operated and are employed with current sensing protective relays that

    function through current transformers.

    Magnetic Circuit Breakers :

    These breakers use a three dimensional electromagnetic coil whose pulling force increases

    with the current. The contacts are held closed by a latch so that when the current in the coil

    goes beyond the rating of the circuit breaker, the coil's pull releases the latch which allows

    the contacts to open with a spring action.

    Thermal Circuit Breakers:

    These breakers employ heat to break the circuit current flow and consist of a bimetallic

    strip, made of two types of materials welded together. At high heat levels, this strip bends

    at an angle that pulls the lever down and breaks the connection between the circuit

    breaker's contact plate and the stationary contact plate.

    Rated circuit breakers, common trip breakers, Earth leakage circuit breakers are another

    type. One of the most important difference between circuit breakers and fuses is that circuit

    breakers can be reset either manually or automatically to resume normal operation,

    whereas fuses once used, have to be replaced.

  • 7/30/2019 Shiri

    42/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 42

    4.INSTRUMENT TRANSFORMER

    A current transformer (CT) is used for measurement of electric currents. Current

    transformers, together with voltage transformers (VT) (potential transformers (PT)), areknown as instrument transformers.

    Main information on the state of the power system and the substation equipment is

    acquired by measuring various parameters. The measuring, monitoring, control and

    protection devices measure and use parameters such as current. voltage. power factor.

    frequency. active power, reactive power. direction of power flow. load balance. and phase

    angles. These parameters are measured by using two types of analog sensors. current

    transformers (CT) and voltage transformers (VT). These transducers provide the

    instantaneous values of currents and voltages. The remaining parameters are derived from

    these measurements. Older substations have instruments that are operated by analog

    signals from the transducers. In modem substations, currents and voltages are acquired inthe form of quantized samples using analog to digital converters. The samples are then

    processed by digital signal processors to estimate the desired parameters.

    Instrument transformers are used for measuring voltage and current in electrical power

    systems, and for power system protection and control. Where a voltage or current is too

    large to be conveniently used by an instrument, it can be scaled down to a standardized low

    value. Instrument transformers isolate measurement, protection and control circuitry from

    the high currents or voltages present on the circuits being measured or controlled.

    Current TransformerA current transformer is essentially a step-down transformer which steps-down the current

    in a known ratio, the primary of this transformer consist of one or more turn of thick wire

    connected in series with the line, the secondary consist of thick wire connected in series

    with line having large number of turn of fine wire and provides for measuring instrument,

    and relay a current which is a constant faction of the current in the line. The current

    transformer (CT) is often treated as a black box. It is a transformer that is governed by the

    laws of electromagnetic induction: = k AcNf

    Where

    = Induced voltage

    = Flux density

    Ac = Core cross-sectional area

    N = Turns

    f = Frequency

    k = Constant of proportionality

    Current transformers are basically used to take the readings of the currents entering the

    substation. This transformer steps down the current from 800 amps to 1 amp. This is

    done because we have no instrument for measuring of such a large current. The main use of

  • 7/30/2019 Shiri

    43/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 43

    this transformer is (a) distance protection; (b) backup protection; (c) measurement.

    A current transformer is a transformer designed to provide a current in its secondary coil

    proportional to the current flowing in its primary coil.

    When current in a circuit is too high to directly apply to measuring instruments, a current

    transformer produces a reduced current accurately proportional to the current in the

    circuit, which can be conveniently connected to measuring and recording instruments. A

    current transformer also isolates the measuring instruments from what may be very high

    voltage in the monitored circuit. Current transformers are commonly used in metering

    and protective relays in the electrical power industry.

    Current transformers are used extensively for measuring current and monitoring the

    operation of the power grid. Along with voltage leads, revenue-grade CTs drive the electrical

    utility's watt-hour meter on virtually every building with three-phase service and single-

    phase services greater than 200 amps.

    The CT is typically described by its current ratio from primary to secondary. Often, multiple

    CTs are installed as a "stack" for various uses. For example, protection devices and revenue

    metering may use separate CTs to provide isolation between metering and protection

    circuits, and allows current transformers with different characteristics (accuracy, overload

    performance) to be used for the devices.

    Current transformer

  • 7/30/2019 Shiri

    44/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 44

    Voltage Transformer:

    It is essentially a step - down transformer and step down the voltage in known ratio. The

    primary of these transformer consist of a large number of turn of fine wire connected across

    the line. These secondary winding consist of a few turns and provides for measuring

    instruments and relay a voltage which is known fraction of the line voltage.Voltage transformers (VTs), also referred to as "potential transformers" (PTs), are designed

    to have an accurately known transformation ratio in both magnitude and phase, over a

    range of measuring circuit impedances. A voltage transformer is intended to present a

    negligible load to the supply being measured. The low secondary voltage allows protective

    relay equipment and measuring instruments to be operated at a lower voltages.

    Both current and voltage instrument transformers are designed to have predictable

    characteristics on overloads. Proper operation of over-current protective relays requires

    that current transformers provide a predictable transformation ratio even during a short-

    circuit.

    A capacitor voltage transformer (CVT), or capacitance coupled voltage transformer (CCVT)

    is a transformer used in power systems to step down extra high voltage signals and provide

    a low voltage signal, for measurement or to operate a protective relay. In its most basic

    form the device consists of three parts: two capacitors across which the transmission line

    signal is split, an inductive element to tune the device to the line frequency, and

    a transformer to isolate and further step down the voltage for the instrumentation or

    protective relay. The tuning of the divider to the line frequency makes the overall division

    ratio less sensitive to changes in the burden of the connected metering or protection

    devices. The device has at least four terminals: a terminal for connection to the high voltage

    signal, a ground terminal, and two secondary terminals which connect to the

    instrumentation or protective relay. CVTs are typically single-phase devices used for

    measuring voltages in excess of one hundred kilovolts where the use of wound primary

    voltage transformers would be uneconomical. In practice, capacitor C1 is often constructed

    as a stack of smaller capacitors connected in series. This provides a large voltage drop across

    C1 and a relatively small voltage drop across C2.

    The CVT is also useful in communication systems. CVTs in combination with wave traps are

    used for filtering high frequency communication signals from power frequency. This formsa carrier communication network throughout the transmission network.

    The standards define a voltage transformer as one in which "the secondary voltage is

    substantially proportional to the primary voltage and differs in phase from it by an angle

    which is approximately zero for an appropriate direction of the connections.

  • 7/30/2019 Shiri

    45/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 45

    Voltage transformer

  • 7/30/2019 Shiri

    46/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 46

    5.WAVE TRAP

    Line traps prevent the transmission of high frequency carrier signals on high voltage

    transmission lines to unwanted directions without a loss of energy at power frequency.

    Line traps are a key component in PLC (Power Line Carrier) systems used for remote control

    signals, voice communication, remote metering and control between substations in the

    electrical T&D network. The Alstom Grid line trap is reliable and lightweight and requires

    little or no maintenance. Line trap also is known as Wave trap.

    Wave traps are provided in the substation because, there are multiple reasons for this,

    depending on the configuration. If the wave traps are on different lines, they are likely

    tuned to different carrier frequencies and are used to filter out the carrier for the line they

    are installed on. If they are installed on the same line, there may be multiple carrier

    frequencies used, or carrier is applied to multiple phases if on different phases.

    Line Trap consists of Inductive coil usually connected in the outdoor yard incoming line. Line

    traps are usually mounted above Capacitor Voltage Transformer (CVT) or on separate

    structure.

    30 kHz to 500 kHz frequency range

    Operational up to 800 kV, the line trap can be used within the 30 kHz to 500 kHz frequency

    range. It complies with IEC, ANSI or the equivalent standards.

    Lightweight, reliable, and maintenance-free

    Line traps are air core, dry types, with mounting flexibility and can withstand high, short-

  • 7/30/2019 Shiri

    47/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 47

    circuits. They are lightweight, can be used outdoors, and are doted with a reliable, open-

    style and maintenance-free design. The line traps provide excellent cooling, are equipped

    with extremely reliable tuning devices and have a self-resonance frequency greater than 50

    kHz.

  • 7/30/2019 Shiri

    48/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 48

    5. POWER TRANSFORMER

    Power transformer is a static electrical device, involving no continuously moving parts, used

    in electric power systems to transfer power between circuits through the use of

    electromagnetic induction. The term power transformer is used to refer to those

    transformers used between the generator and the distribution circuits, and these

    are usually rated at 500 kVA and above. Power systems typically consist of a large number of

    generation locations, distribution points, and interconnections within the system or with

    nearby systems, such as a neighboring utility. The complexity of the system leads to a

    variety of transmission and distribution voltages. Power transformers must be used at each

    of these points where there is a transition between voltage levels. Power transformers

    are selected based on the application, with the emphasis toward custom design being

    more apparent the larger the unit.

    Power transformers are available for step-up operation, primarily used at the generator and

    referred to as generator step-up (GSU)transformers, and for step-down operation, mainly

    used to feed distribution circuits. Power transformers are available as single-phase or three-

    phase apparatus. Transformer is a vital link in a power system which has made possible the

    power generated at low voltages (6600 to 22000 volts) to be stepped up to extra high

    voltages for transmission over long distances and then transformed to low voltages for

    utilization at proper load centers. This flux induces an electro-motive force in the secondary

    winding too. When load is connected across this winding, current flows in the secondary

    circuit. This produces a demagnetizing effect, to counter balance this the primary winding

    draws more current from the supply so that

    IP NP=IS NS

  • 7/30/2019 Shiri

    49/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 49

    Electrical Power Transformer is a static device which transforms electrical energy from one

    circuit to another without any direct electrical connection and with the help of mutual

    induction between to windings. It transforms power from one circuit to another without

    changing its frequency but may be in different voltage level.

    Power transformer takes the AC mains (wall) supply voltage and converts it into one or

    more AC voltages that are more convenient for our needs. For a valve amp this usually

    means a low voltage for the heaters and a high voltage for the anode supply, at the veryleast.

    Working Principle of transform

    The working principle of transformer is very simple. It depends upon Faraday's laws of

    Electromagnetic Induction. Actually mutual induction between two or more winding is

    responsible for transformation action in an electrical transformer.

    er

  • 7/30/2019 Shiri

    50/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 50

    Faraday's laws of Electromagnetic Induction

    According to these Faraday's laws, Rate of change of flux linkage with respect to time is

    directly proportional to the induced EMF in a conductor or coil".

    An Ideal Transformer is an imaginary transformer which does not have any loss in it,

    means no core losses, copper losses and any other losses in transformer. Efficiency of this

    transformer is considered as 100%.

    Types of Transformer

    Transformers can be categorized in different ways, depending upon their purpose, use,

    construction etc. The types of transformer are as follows,

    Step Up Transformer & Step Down Transformer - Generally used for stepping up and

    down the voltage level of power in transmission and distribution power network.

    Transformer & Single Phase Transformer - Former is generally used in three phase power

    system as it is cost effective than later but when size matters it is preferable to use bank

    of three Single Phase Transformer as it is easier to transport three single phase unit

    separately than one single three phase unit.

    Electrical Power Transformer, Distribution Transformer & Instrument Transformer -

    Transformer generally used in transmission network is normally known as PowerTransformer, distribution transformer is used in distribution network and this is lower

    rating transformer and current transformer & potential transformer, we use for relay and

    protection purpose in electrical power system and in different instruments in industries

    are called Instrument Transformer.

    Two Winding Transformer & Auto Transformer - Former is generally used where ratio

    between High Voltage and Low Voltage is greater than 2. It is cost effective to use later

    where the ratio between High Voltage and Low Voltage is less than 2.

    Outdoor Transformer & Indoor Transformer - Transformers designed for installing atoutdoor is Outdoor Transformer and Transformers designed for installing at indoor is

    Indoor Transformer.

    EHV power transformers are usually oil immersed with all three phases in one tank. Auto

    transformers can offer advantage of smaller physical size and reduced losses. The different

    classes of power transformers are:

    Oil immersed, natural cooling

    Oil immersed, air blast cooling

    Oil immersed, oil circulation forced

  • 7/30/2019 Shiri

    51/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 51

    Oil immersed, oil circulation forced, air blast cooling

    Power transformers are usually the largest single item in a substation. For economy of

    service roads, transformers are located on one side of a substation, and the connection to

    switchgear is by bare conductors. Because of the large quantity of oil, it is essential to take

    precaution against the spread of fire. Hence, the transformer is usually located around asump used to collect the excess oil.

    Transformers that are located and a cell should be enclosed in a blast proof room.

    Power transformers

  • 7/30/2019 Shiri

    52/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 52

    7. SWITCH GEAR

    One of the basic functions of switchgear is protection, which is interruption of short-circuit

    and overload fault currents while maintaining service to unaffected circuits. Switchgear also

    provides isolation of circuits from power supplies. Switchgear is also used to enhance

    system availability by allowing more than one source to feed a load.

    In an electric power system, switchgear is the combination of electrical disconnect

    switches, fuses or circuit breakers used to control, protect and isolate electrical equipment.

    Switchgear is used both to de-energize equipment to allow work to be done and to clear

    faults downstream. This type of equipment is important because it is directly linked to the

    reliability of the electricity supply.

    The very earliest central power stations used simple open knife switches, mounted on

    insulating panels of marble or asbestos. Power levels and voltages rapidly escalated, making

    opening manually operated switches too dangerous for anything other than isolation of a

    de-energized circuit. Oil-filled equipment allowed arc energy to be contained and safely

    controlled. By the early 20th century, a switchgear line-up would be a metal-enclosed

    structure with electrically operated switching elements, using oil circuit breakers. Today, oil-

    filled equipment has largely been replaced by air-blast, vacuum, or SF6 equipment, allowing

    large currents and power levels to be safely controlled by automatic equipment

    incorporating digital controls, protection, metering and communications.High voltage switchgear was invented at the end of the 19th century for operating motors

    and other electric machines. The technology has been improved over time and can be used

    with voltages up to 1,100 kV.

    Typically, the switchgear in substations is located on both the high voltage and the low

    voltage side of large power transformers. The switchgear on the low voltage side of the

    transformers may be located in a building, with medium-voltage circuit breakers for

    distribution circuits, along with metering, control, and protection equipment. For industrial

    applications, a transformer and switchgear line-up may be combined in one housing, called

    a unitized substation or USS.

    There are many different types of switch gears. To the common types of switchgears are

    included vacuum switch gears, oil insulated switch gears ,and gas insulated switchgears.

    Also there are simple open air switchgears.

    The vacuum circuit Switch gear is the type of Switchgears that has minimal arcing. when the

    arc is stretched to less than 2 to 3 mm ,it quenches. They are frequently used in modern

    medium voltage switch gear of up to 35000 volts.

    The oil insulated switchgear depends on the oil vaporization blast through its arc.

    The gas insulated switchgear stretches the arc with a magnetic field. it also depends on the

    dielectric strength of the gas to quench the stretched arc.

  • 7/30/2019 Shiri

    53/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 53

    The open air switch gear circuit breakers use compressed air to blow out the arc.whe the

    displaced air is trying to escape, it blows out the arc.

    Switch gear

  • 7/30/2019 Shiri

    54/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 54

    8.ISOLATORS

    Isolating switches are also called isolators. disconnects, disconnecting switches.

    Isolators are provided for isolation from live parts for the purpose of maintenance. Isolatorsare located at either side of the circuit breaker. Isolators are operated under no load.

    Isolator does not have any rating for current breaking or current making. Isolators are

    interlocked with circuit breakers

    Disconnector or isolator switch is used to make sure that an electrical circuit can be

    completely de-energized for service or maintenance. Such switches are often found

    in electrical distribution and industrial applications where machinery must have its source of

    driving power removed for adjustment or repair. High-voltage isolation switches are used in

    electrical substations to allow isolation of apparatus such as circuit

    breakers and transformers, and transmission lines, for maintenance.

    Function of Isolators :

    Isolating switches are used to disconnect circuit-breakers. sections of bus bars and

    parts of the system.

    An isolator is used to open a circuit only after the flow of current has been

    interrupted by another device.

    These switches are slow moving devices but are inexpensive compared to loadswitches and circuit breakers.

    These switches are also used to transfer circuits from one bus bar to another and to

    provide flexibility during system operation

    These switches must be able to:

    carry normal load currents continuously,

    carry fault currents until they are cleared by an interrupting device and,

    make and break small currents when the voltage difference across their

    terminals is not significant.

    The open and closed status of an isolator can be visually verified. Often, videocameras are

    placed at strategic locations in a switchyard to visually inspect the operation of an

    isolator

    without leaving the control room. These cameras are remotely controlled and can be

    pointed towards selected equipment in the substation.

    In substation , it is often desired to disconnect a part of the system for general

    maintenance and repairs. This is accomplished by an isolating switch or isolator. An

  • 7/30/2019 Shiri

    55/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 55

    isolator is a switch and is design to often open circuit under no load, in other words,

    isolator switches are operate only when the line is which they are connected carry

    no load.

    The major difference between an isolator and a circuit breaker is that an isolator is

    an off-loaddevice intended to be opened only after current has been interrupted by

    some other control device. Safety regulations of the utility must prevent any attempt

    to open the disconnector while it supplies a circuit.

    For example, consider that the isolator are connected on both side of a cut breaker, if the

    isolators are to be opened, the C.B. must be opened first.

  • 7/30/2019 Shiri

    56/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 56

    frequently used in different Electrical Isolators (Outdoor Isolators) are used to protect from

    the direct contact of electricity. They are the very essential part of electrical equipments.

    We offer different types of electrical Isolators which include Electric Fence Isolators and

    Electric Current Isolators. All these types are of supreme quality. They are made shock proof

    by special technology. They are being industries with total comfort. We are among the

    leading Electric Current Isolators Suppliers in India who supply all the famous brands of

    electric switches.

  • 7/30/2019 Shiri

    57/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 57

    MISCELLONOUS EQUIPMENTS

    Metering and Indicating Instrument:

    There are several metering and indicating Instrument (e.g.Ammeters, Volt-meters, energymeter etc.) installed in a Sub-Station tomaintain which over the ckt quantities. The

    instrument transformer areinvariably used with them for satisfactory operation.

  • 7/30/2019 Shiri

    58/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 58

    Surge Arrestors or Lightning Arrester:

    A lightning arrester is a device used on electrical power systems to protect the insulation on

    the system from the damaging effect of lightning. The typical lightning arrester also known

    as surge arrester has a high voltage terminal and a ground terminal. When a lightning surge

    or switching surge travels down the power system to the arrester, the current from thesurge is diverted around the protected insulation in most cases to earth.

    Surge Arresters or Lightning Arresters discharge the over voltage surges to earth and

    protect the equipment insulation from switching surges and lightning surges. Surge

    arresters are generally connected between phase conductor and ground. In a Substation

    surge arrester is located at the starting of the substation as seen from incoming

    transmission lines and is the first equipment of the substation. Surge arresters are also

    provided near the transformer terminals phase to ground. Two type of surge arresters are

    available 1) Gapped Arresters 2) Gapless Zinc Oxide arresters.

    Lightning Arrester or Surge Arreseter

    Air-Break Switch

    an electric switch in which the opening and closing of contacts and extinguishing of the

    electric arc are accomplished by means of compressed air. An air-break switch consists of

    three basic structural elements: a reservoir with a supply of compressed air, an arc

    extinguisher, and an electro pneumatic actuator.

    The principal advantages of air-break switches lie in the fact that they are fireproof and

    explosion proof, have rapid connect and disconnect operation, and are relatively simple in

    design. The presence of equipment for the production and storage of compressed-air

    supplies is a disadvantage. Air-break switches at currents up to 750 kV, which are generally

    used at high-voltage power plants and substations, are manufactured in the USSR.

    Modern air-break switches are provided with an enclosed isolating switch whose contacts

    are housed in an insulated casing that fills with compressed air upon disconnection . Air-

    break switches at currents of 110 kV and higher (up to 750 kV) are manufactured with air-

    filled isolating switches..

  • 7/30/2019 Shiri

    59/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 59

    An air break switch comprising one or more fixed contacts and one or more movable

    contacts which are movable between open and closed positions, and a coil which,

    preferably in conjunction with

    The function of a switch is to open or close a path for electricity.

    Low voltage kife switch

    A knife switch has a simple handle that swings back and forth to open or close a circuit. The

    switch itself is not covered with insulation. It is easy to see if the switch is open (on) or

    closed (off). The knife switch in the photos below could be used to turn off a power tool or

    other equipment.

    A simple knife switch is good for doing experiments with electricity of low voltage. Dry cells

    have low voltage and are often used for these experiments. If you touch the metal of the

    switch, you should not get hurt when using very low voltage with dry cells!

    Earth Switch:

    Station Earthing System includes Earth Mat and Earth electrodes placed below ground level.

    These Earth Mat and Earth electrode is connected to the equipment structures, neutral

    points for the purpose of Equipment earthing and neutral point earthing.

    Function earthing system is to provide low resistance earthing for

    1. Discharging currents from the surge arresters, overhead shielding, earthing switches

    2. For equipment body earthing

    3. For safe touch potential and step potential in substation.

  • 7/30/2019 Shiri

    60/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 60

    Earth Switch is used to discharge the voltage on the circuit to the earth for safety. Earth

    switch is mounted on the frame of the isolators. Earth Switch is located for each incomer

    transmission line and each side of the bus bar section.

    BatteryA battery is a device that converts the chemical energy contained in its active materials

    directly into electric energy by means of an electrochemical oxidation-reduction

    (redox)reaction. In the case of a rechargeable system, the battery is recharged by a reversal

    of the process.

    Batteries RoomBatteries are very important part of the grid. It works as a standby storage device, that

    provides D.C power to the grids dc supply equipment in case of failure of A.C supply.Different protection devices i.e relays, circuit breakers and other control equipment of relay

    room, 11KVcontrol room, 132KV control room and yard operates on 110 D.C volt supply that

    is normally supplied by a rectifier. In case of failure of A.C power batteries works as a

    standby source of 110 D.C supply. No. of cells installed = 552 Volt/cell, 150 AH Total Output

    Voltage = 110 Volt. Recommended Float Voltage = 202 Volt/cell at 25 CRecommended Boost

    Voltage = 2.4 Volt/cell Minimum2.8 Volt/cell Maximum Total Float Voltage = 121 Volt

    Capacitor

    Capacitors are used in substation to improve power factor.

    Series Reactors

    Series reactors are used to limit short circuit current and to limit current surges associated

    with fluctuating loads. Series reactors are located at the strategic locations such that the

    fault levels are reduced.

  • 7/30/2019 Shiri

    61/67

    132/33 KV SUBSTATION EQUIPMENTS MINI PROJECT

    SREE CHAITANYA COLLEGE OF ENGINEERING 61

    Series Reactors

    Lightning Protection:

    Ligh