® “ ” “ ” G:\Projects\MTZ\2016\MTZ-012-16\MTZ01216-1R2.dwg, 1-INFO, 6/6/2016 8:34:56 AM, ARCH full bleed D (36.00 x 24.00 Inches), 1:1, Plotted by Julius
VASCO PLAZA KIDDIE ACADEMY 1400 N. VASCO ROAD LIVERMORE, CA 94551
AutoCAD SHX Text
1
AutoCAD SHX Text
AS-BUILTS
AutoCAD SHX Text
21-MAR-2016
AutoCAD SHX Text
2
AutoCAD SHX Text
AS-BUILTS
AutoCAD SHX Text
26-MAY-2016
AutoCAD SHX Text
1
AutoCAD SHX Text
SYSTEM INFO
AutoCAD SHX Text
FIRE ALARM SYSTEM NOTES
AutoCAD SHX Text
THIS SYSTEM IS BEING INSTALLED AS PER THE REQUIREMENTS OF NFPA 72, 2013 EDITION. UPON ACTIVATION OF AN INITIATING DEVICE, THE RESPECTIVE DEVICE SHALL CAUSE AN INDICATION OF ALARM, SUPERVISION OR TROUBLE TO BE RECEIVED BY THE FIRE ALARM CONTROL UNIT. THE FACU SHALL CAUSE ALL NOTIFICATION APPLIANCES TO OPERATE. THE RESPECTIVE ZONE/POINT ADDRESS SHALL BE INDICATED AT THE FACU. AN APPROPRIATE SIGNAL SHALL BE TRANSMITTED TO THE RECEIVING STATION FOR DISPOSITION IN ACCORDANCE WITH NFPA 72 CHAPTER 26, 2013 EDITION. THIS SYSTEM SHALL COMPLY WITH THE CALIFORNIA BUILDING CODE 2013 EDITION, CHAPTER 35, CALIFORNIA FIRE CODE 2013 EDITION, SECTION 907, CALIFORNIA ELECTRIC CODE 2013 EDITION, ARTICLE 760, AND NFPA 72 2013 EDITION, AS AMENDED IN CHAPTER 35 OF THE CALIFORNIA BUILDING CODE. A FIRE SPRINKLER MONITORING SYSTEM SHALL COMPLY WITH THE REQUIREMENTS OF THE CALIFORNIA FIRE CODE, 2013 EDITION, SECTION 903.4. AN AUTOMATIC DETECTOR SHALL BE INSTALLED PER THE REQUIREMENTS OF NFPA 72, 2013 EDITION. UPON SENSING OF THE PRODUCTS OF COMBUSTION, THE RESPECTIVE DEVICE SHALL CAUSE AN INDICATION OF ALARM TO BE RECEIVED BY THE FIRE ALARM CONTROL UNIT. THE FACU SHALL CAUSE ALL INDICATING DEVICES TO OPERATE. THE RESPECTIVE ZONE SHALL BE IDENTIFIED AT THE FACU AND AN APPROPRIATE SIGNAL SHALL BE TRANSMITTED TO THE RECEIVING STATION FOR DISPOSITION IN ACCORDANCE WITH NFPA 72, 2013 EDITION. THE MANUAL FIRE ALARM BOX ON THIS SYSTEM IS BEING INSTALLED PER THE REQUIREMENTS OF NFPA 72, 2013 EDITION, SECTION 23.8.5.1.2 UPON ACTIVATION OF A MANUAL FIRE ALARM BOX, THE RESPECTIVE DEVICE SHALL CAUSE AN INDICATION OF ALARM TO BE RECEIVED BY THE FIRE ALARM CONTROL UNIT. THE CONTROL UNIT SHALL CAUSE ALL NOTIFICATION APPLIANCES TO ACTIVATE. THE RESPECTIVE ZONE SHALL BE IDENTIFIED AT THE ANNUNCIATOR AND FACU. THIS SYSTEM IS CONNECTED TO INITIATING DEVICES THAT HAVE BEEN INSTALLED BY OTHER CONTRACTORS. UPON LEAK OR FLOW OF WATER IN EXCESS OF TEN GALLONS PER MINUTE, THE FLOW SWITCH SHALL CLOSE, WITH THE RESPECTIVE DEVICE CAUSING AN INDICATION OF ALARM TO BE RECEIVED BY THE FIRE ALARM CONTROL UNIT. THE RESPECTIVE ZONE OR POINT ADDRESS SHALL BE INDICATED AT THE FACU, AND AN APPROPRIATE SIGNAL SHALL BE TRANSMITTED TO THE RECEIVING STATION FOR DISPOSITION IN ACCORDANCE WITH NFPA 72, 2013 EDITION. INITIATING DEVICES AND JUNCTION BOXES LOCATED OUTSIDE THE BUILDING SHALL MEET THE REQUIREMENTS OF 23.8.5.11.1, NFPA 72, 2013 THROUGH THE USE OF TAMPER RESISTANT FASTENERS. UPON MOVEMENT OF A FIRE PROTECTION SYSTEM CONTROL VALVE FROM AN OPEN POSITION, AND DURING THE FIRST TWO REVOLUTIONS, A SUPERVISORY SIGNAL SHALL BE RECEIVED BY THE FIRE ALARM CONTROL UNIT AND AN APPROPRIATE "VALVE TAMPER" SIGNAL SHALL BE TRANSMITTED TO THE RECEIVING STATION FOR DISPOSITION IN ACCORDANCE WITH NFPA 72, 2013 EDITION. SUPERVISORY DEVICES AND JUNCTION BOXES LOCATED OUTSIDE THE BUILDING SHALL MEET THE REQUIREMENTS OF 23.8.5.11.1, NFPA 72, 2013 THROUGH THE USE OF TAMPER RESISTANT SCREWS. INSPECTOR'S TEST VALVES, SUPERVISORY VALVES, DRAIN VALVES AND OTHER DEVICES THAT WHEN ACTIVATED MAY CAUSE AN ALARM SIGNAL TO BE GENERATED SHALL BE TAGGED WITH A SIGN. THE SIGN OR TAG SHALL READ "WARNING FIRE DEPARTMENT WILL RESPOND IF THIS SPRINKLER SYSTEM IS WORKED ON BEFORE CALLING..." THE NUMBER OF THE SUPERVISING CENTRAL STATION SHALL THEN BE LISTED. THE OCCURRENCE OF ANY TROUBLE OF ANY NATURE SUCH AS A CIRCUIT WIRING BREAK OR GROUND FAULT OCCURRING IN THE DEVICES OR WIRING ASSOCIATED WITH THE PROTECTIVE SIGNALING SYSTEM SHALL CAUSE A "DISTINCTIVE" SIGNAL TO BE RECEIVED BY THE FIRE ALARM CONTROL UNIT. THE TROUBLE SIGNAL SHALL BE LOCATED WHERE LIKELY TO BE HEARD BY A RESPONSIBLE PARTY. WHERE PRACTICAL, THE NOTIFICATION APPLIANCES FOR INDOOR USE SHALL BE INSTALLED FLUSH ON WALLS OR CEILINGS. BACK-BOXES SHALL BE USED. WALL MOUNTED AUDIBLE APPLIANCES SHALL HAVE THEIR TOPS AT HEIGHTS ABOVE THE FINISHED FLOORS OF NOT LESS THAN 90" AND BELOW THE FINISHED CEILINGS OF NOT LESS THAN 6". AUDIBLE SIGNALS SHALL MEET THE REQUIREMENTS OF NFPA 72, 2013 EDITION SECTIONS 18.4.2.1 AND 18.4.2.4. AUDIBLE APPLIANCES SHALL BE SET TO 'HIGH'. WALL MOUNTED VISUAL APPLIANCES SHALL BE MOUNTED SUCH THAT THE ENTIRE LENS IS NOT LESS THAN 80" AND NO GREATER THAN 96" ABOVE THE FINISHED FLOOR. THE DUCT DETECTOR(S) FOR THIS SYSTEM, WERE INSTALLED BY OTHERS. THE POWER FOR THE DUCT DETECTORS IS SUPPLIED BY DIRECT CONNECTION TO 120 VAC, AND NOT FROM THE FACU. UPON DUCT DETECTOR ALARM THE ASSOCIATED AIR-HANDLING UNIT(S) SHALL SHUT DOWN. AN APPROPRIATE SIGNAL SHALL BE TRANSMITTED TO THE SUPERVISING STATION. WHERE IN-DUCT SMOKE DETECTORS ARE INSTALLED IN CONCEALED LOCATIONS, MORE THAN 10 FT (3M) ABOVE FINISHED FLOOR, OR IN ARRANGEMENTS WHERE THE DETECTORS ALARM INDICATOR IS NOT READILY VISIBLE TO RESPONDING PERSONNEL, THE DETECTORS SHALL BE PROVIDED WITH REMOTE ALARM OR SUPERVISORY INDICATION IN A READILY ACCESSIBLE LOCATION AND SHALL BE CLEARLY LABELED TO INDICATE BOTH THEIR FUNCTION (E.G., “IN-DUCT SMOKE DETECTOR IN-DUCT SMOKE DETECTOR ALARM”) AND THE AIR-HANDLING UNIT(S) ASSOCIATED WITH EACH ) AND THE AIR-HANDLING UNIT(S) ASSOCIATED WITH EACH DETECTOR. NFPA 72, 2013 EDITION, SECTION 17.4.7, 17.4.8 AND 17.4.9. ALL EXPOSED WIRING SHALL BE PROTECTED FROM PHYSICAL DAMAGE AND SHALL BE INSTALLED WITHIN APPROPRIATE RACEWAY OR CONDUIT WHEN WITHIN 7 FEET OF THE FLOOR PER CEC, 2013 EDITION. THE COMMUNICATIONS METHOD FOR THIS SYSTEM IS A ONE-WAY RADIO ALARM TRANSMITTER (RAT). THE RADIO ALARM TRANSMITTER SHALL BE INSTALLED PER THE REQUIREMENTS OF NFPA 72, 2013 EDITION, SECTION 26.6.3.3.2. THE RAT SHALL TRANSMIT TO TWO (2) REPEATER SITES. THE EMERGENCY COMMUNICATION SYSTEM (VOICE) IS TO BE INSTALLED AS PER THE REQUIREMENTS OF NFPA 72, 2013 EDITION. UPON ACTIVATION OF THE FIRE ALARM SYSTEM, THE EMERGENCY COMMUNICATION SYSTEM SHALL BE ACTIVATED. PER 2013 NFPA 72 SECTION 24.4.1.3, 2 CYCLES OF AN ALERT TONE (A 3 PULSE TEMPORAL PATTERN IN ACCORDANCE WITH SECTION 2013 NFPA 72 SECTION 18.4.2) SHALL BE USED FOLLOWED BY THE VOICE MESSAGE. THE VOICE MESSAGE WILL BE AS FOLLOWS: "MAY I HAVE YOUR ATTENTION, PLEASE? MAY I HAVE YOUR ATTENTION, PLEASE? A FIRE HAS BEEN REPORTED IN THE BUILDING. A FIRE HAS BEEN REPORTED IN THE BUILDING. PLEASE PROCEED TO THE STAIRWAYS AND EXIT THE BUILDING. DO NOT USE THE ELEVATORS." THE SEQUENCE WILL REPEAT UNTIL THE FIRE ALARM SYSTEM IS DEACTIVATED. A MICROPHONE SHALL BE INTERCONNECTED TO THE SYSTEM. THE MICROPHONE MAY OVERRIDE THE PRERECORDED MESSAGE. PRIMARY POWER SUPPLY SHALL BE PROVIDED BY A DEDICATED BRANCH CIRCUIT RATED AT NO LESS THAN 20 AMPS, AND PROVIDING 120VAC NOMINAL TO THE FIRE ALARM CONTROL UNIT. CIRCUITS AND CONNECTIONS SHALL BE MECHANICALLY PROTECTED, SHALL BE ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL, AND SHALL BE IDENTIFIED AS “FIRE ALARM CIRCUIT CONTROL”. PER NFPA 72, 2013 FIRE ALARM CIRCUIT CONTROL”. PER NFPA 72, 2013 . PER NFPA 72, 2013 EDITION, SECTIONS 10.6.5 SECONDARY POWER SUPPLY TO BE PROVIDED BY INTEGRAL BATTERIES SIZED AS INDICATED. TRANSIENT PROTECTION IS PROVIDED ON ALL SIGNALING SYSTEM CIRCUITS THAT ENTER OR LEAVE THE PROTECTED PREMISE IN ACCORDANCE WITH NFPA 72, 2013 EDITION, 12.2.4.2. THE SYSTEM CIRCUIT DISCONNECTING MEANS SHALL BE PERMANENTLY IDENTIFIED AS "FIRE ALARM." THE LOCATION OF THE BRANCH CIRCUIT DISCONNECTING MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE CONTROL UNIT. THE CIRCUIT DISCONNECTING MEANS SHALL HAVE A RED MARKING IN ACCORDANCE WITH NFPA 72, 2013 EDITION, 10.6.5.2.3. WHEN THE DISCONNECTING MEANS IS VIA A CIRCUIT BREAKER, A LISTED BREAKER LOCKING DEVICE SHALL BE USED IN ACCORDANCE WITH NFPA 72, 2013 EDITION, 10.6.5.4. THE OWNER OF THE FACILITY SHALL BE RESPONSIBLE FOR MAINTAINING REQUIRED UTILITIES SO AS TO PROVIDE FOR THE CONTINUOUS OPERATION OF THE PROTECTION SYSTEM. THIS SHALL INCLUDE DEDICATED PRIMARY POWER SUPPLY BY MEANS OF DEDICATED BRANCH CIRCUIT, WITH SUITABLE LOCKOUT. THE MONITORING COMPANY FOR THIS SYSTEM IS: BAY ALARM COMPANY 60 BERRY DRIVE PACHECO, CA 94553 (800)-470-1000 THE PREPARER OF THESE PLANS SHALL NOT BE RESPONSIBLE FOR OR LIABLE FOR ANY UNAUTHORIZED CHANGES TO OR USES OF THESE PLANS. ALL CHANGES TO THE PLANS MUST BE IN WRITING AND MUST BE APPROVED BY THE PREPARER OF THESE PLANS. (C)BAY ALARM COMPANY 2016 BAY ALARM COMPANY 2016 BAY ALARM COMPANY CENTRAL STATION LISTING # 223646-006 FILE # S576-1, (UUFX) PROTECTIVE SIGNALING SERVICES - CENTRAL STATION.
AutoCAD SHX Text
1.ALL WORK SHALL BE IN COMPLIANCE WITH THE LIVERMORE-PLEASANTON FIRE ALL WORK SHALL BE IN COMPLIANCE WITH THE LIVERMORE-PLEASANTON FIRE DEPARTMENT ORDINANCES, AND THE 2013 EDITIONS OF THE CALIFORNIA BUILDING CODE, CALIFORNIA MECHANICAL CODE, CALIFORNIA ELECTRICAL CODE, CALIFORNIA FIRE CODE AND 2013 EDITION OF NFPA 72. 2.UPON COMPLETION OF THE INSTALLATION OF THE FIRE ALARM SYSTEM, A UPON COMPLETION OF THE INSTALLATION OF THE FIRE ALARM SYSTEM, A SATISFACTORY TEST OF THE ENTIRE SYSTEM SHALL BE MADE IN THE PRESENCE OF A REPRESENTATIVE OF THE LIVERMORE-PLEASANTON FIRE PREVENTION DEPARTMENT. 3.A SIGNED COPY OF THE MONITORING AGREEMENT SHALL BE PROVIDED AT A SIGNED COPY OF THE MONITORING AGREEMENT SHALL BE PROVIDED AT THE TIME OF FINAL INSPECTION. 4.A COPY OF THE UL DOCUMENTATION OF THE CENTRAL STATION FACILITY A COPY OF THE UL DOCUMENTATION OF THE CENTRAL STATION FACILITY SHALL BE PROVIDED AT THE FINAL INSPECTION. 5.A UL CENTRAL STATION SERVICE SHALL MONITOR FIRE ALARM SYSTEMS. A UL CENTRAL STATION SERVICE SHALL MONITOR FIRE ALARM SYSTEMS. SITE DOCUMENTATION SHALL ALSO BE PROVIDED. A SIGNED COPY OF THE MONITORING AGREEMENT SHALL BE PROVIDED AT THE TIME OF FINAL INSPECTION. 6.WATER-FLOW AND TAMPER SUPERVISION AUDIBLE ALARMS SHALL BE WATER-FLOW AND TAMPER SUPERVISION AUDIBLE ALARMS SHALL BE SEPARATE AND DISTINCTIVE. 7.THE SYSTEM SHALL UNDERGO A ONE-HUNDRED PERCENT TEST, AND THE THE SYSTEM SHALL UNDERGO A ONE-HUNDRED PERCENT TEST, AND THE SYSTEM COMPLETION SHALL BE DOCUMENTED AS PER NFPA 72, 2013 EDITION, SECTION 7.5.6 8.A REPRESENTATIVE OF THE LIVERMORE-PLEASANTON FIRE DEPARTMENT SHALL A REPRESENTATIVE OF THE LIVERMORE-PLEASANTON FIRE DEPARTMENT SHALL WITNESS THE ACCEPTANCE TEST OF THE SYSTEM. ALL INSPECTION REQUEST SHALL BE MADE TO THE LIVERMORE-PLEASANTON FIRE DEPARTMENT FORTY-EIGHT HOURS IN ADVANCE. 9.THE INITIATING DEVICE CIRCUITS IF USED ARE CLASS B. THE INITIATING DEVICE CIRCUITS IF USED ARE CLASS B. 10.THE SIGNALING LINE CIRCUITS IF USED ARE CLASS B. THE SIGNALING LINE CIRCUITS IF USED ARE CLASS B. 11.THE NOTIFICATION APPLIANCE CIRCUITS IF USED ARE CLASS B.THE NOTIFICATION APPLIANCE CIRCUITS IF USED ARE CLASS B.
AutoCAD SHX Text
LIVERMORE NOTES
AutoCAD SHX Text
FIRE ALARM SYSTEM EQUIPMENT LIST
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
QTY.
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
MODEL #
AutoCAD SHX Text
CSFM LISTING #
AutoCAD SHX Text
BACKBOX
AutoCAD SHX Text
1
AutoCAD SHX Text
FIRE-LITE FIRE ALARM CONTROL UNIT WITH DACT
AutoCAD SHX Text
MS-9200UDLS
AutoCAD SHX Text
7165-0075:0208
AutoCAD SHX Text
INCLUDED
AutoCAD SHX Text
1
AutoCAD SHX Text
FIRE-LITE 80-CHARACTER LCD ANNUNCIATOR - RED
AutoCAD SHX Text
ANN-80
AutoCAD SHX Text
7120-0075:0211
AutoCAD SHX Text
4" SQUARE/DOUBLE GANG
AutoCAD SHX Text
14
AutoCAD SHX Text
FIRE LITE ADDRESSABLE SMOKE DETECTOR (PHOTO)
AutoCAD SHX Text
SD355
AutoCAD SHX Text
7272-0075:0194
AutoCAD SHX Text
4" SQUARE/DOUBLE GANG
AutoCAD SHX Text
1
AutoCAD SHX Text
FIRE LITE ADDRESSABLE MANUAL FIRE ALARM BOX
AutoCAD SHX Text
BG-12LX
AutoCAD SHX Text
7150-0075:0184
AutoCAD SHX Text
SB-I/O
AutoCAD SHX Text
2
AutoCAD SHX Text
FIRE LITE ADDRESSABLE MONITOR MODULE (DUAL CIRCUIT)
AutoCAD SHX Text
MDF-300
AutoCAD SHX Text
7300-0075:0185
AutoCAD SHX Text
4" SQUARE/DOUBLE GANG
AutoCAD SHX Text
7
AutoCAD SHX Text
FIRE LITE ADDRESSABLE MONITOR MODULE
AutoCAD SHX Text
MMF-300
AutoCAD SHX Text
7300-0075:0185
AutoCAD SHX Text
4" SQUARE/DOUBLE GANG
AutoCAD SHX Text
1
AutoCAD SHX Text
FIRELITE EMERGENCY VOICE/COMMAND CENTER
AutoCAD SHX Text
ECC-50/100
AutoCAD SHX Text
6911-0075:0226
AutoCAD SHX Text
INCLUDED
AutoCAD SHX Text
N/A
AutoCAD SHX Text
1
AutoCAD SHX Text
FIRELITE VOICE CIRCUIT EXPANDER
AutoCAD SHX Text
ECC-CE6
AutoCAD SHX Text
6911-0075:0226
AutoCAD SHX Text
INCLUDED
AutoCAD SHX Text
24
AutoCAD SHX Text
SYSTEM SENSOR MULTI-CANDELA CEILING MOUNT SPEAKER STROBE, WHITE
AutoCAD SHX Text
SPSCW
AutoCAD SHX Text
7320-1653:0201
AutoCAD SHX Text
N/A
AutoCAD SHX Text
2
AutoCAD SHX Text
SYSTEM SENSOR CEILING MOUNT SPEAKER, WHITE
AutoCAD SHX Text
SPCW
AutoCAD SHX Text
7320-1653:0201
AutoCAD SHX Text
N/A
AutoCAD SHX Text
3
AutoCAD SHX Text
SYSTEM SENSOR WEATHERPROOF WALL MOUNT SPEAKER, RED
AutoCAD SHX Text
SPRK
AutoCAD SHX Text
7320-1653:0201
AutoCAD SHX Text
N/A
AutoCAD SHX Text
1
AutoCAD SHX Text
SYSTEM SENSOR MULTI-CANDELA CEILING MOUNT STROBE, WHITE
AutoCAD SHX Text
SCW
AutoCAD SHX Text
7125-1653:0186
AutoCAD SHX Text
4" SQUARE/SINGLE OR DOUBLE GANG
AutoCAD SHX Text
1
AutoCAD SHX Text
AES INTELLINET RF SUBSCRIBER UNIT W/CID
AutoCAD SHX Text
AES 7788FULP
AutoCAD SHX Text
7300-1516:0108
AutoCAD SHX Text
INCLUDED
AutoCAD SHX Text
N/A
AutoCAD SHX Text
1
AutoCAD SHX Text
AES-7794 INTELLIPRO FIRE ALARM REPORTING INTERFACE
AutoCAD SHX Text
7794
AutoCAD SHX Text
7300-1516:0109
AutoCAD SHX Text
MOUNTS INSIDE AES
AutoCAD SHX Text
N/A
AutoCAD SHX Text
1
AutoCAD SHX Text
FIRE ALARM DOCUMENTATION CABINET
AutoCAD SHX Text
DOCCAB
AutoCAD SHX Text
N/A
AutoCAD SHX Text
N/A
AutoCAD SHX Text
N/A
AutoCAD SHX Text
10
AutoCAD SHX Text
TDK FERRITE CORE, SPLIT, 11MM, 40 OHM/100MHZ
AutoCAD SHX Text
ZCAT2132-1130
AutoCAD SHX Text
N/A
AutoCAD SHX Text
N/A
AutoCAD SHX Text
1
AutoCAD SHX Text
WATERFLOW SWITCH (BY OTHERS)
AutoCAD SHX Text
FLOW
AutoCAD SHX Text
INSTALLED BY OTHERS
AutoCAD SHX Text
N/A
AutoCAD SHX Text
1
AutoCAD SHX Text
POST INDICATOR VALVE (BY OTHERS)
AutoCAD SHX Text
PIV
AutoCAD SHX Text
INSTALLED BY OTHERS
AutoCAD SHX Text
N/A
AutoCAD SHX Text
1
AutoCAD SHX Text
BUTTERFLY TAMPER SWITCH (BY OTHERS)
AutoCAD SHX Text
BUTTERFLY
AutoCAD SHX Text
INSTALLED BY OTHERS
AutoCAD SHX Text
N/A
AutoCAD SHX Text
6
AutoCAD SHX Text
DUCT SMOKE DETECTOR (BY OTHERS)
AutoCAD SHX Text
DUCT
AutoCAD SHX Text
INSTALLED BY OTHERS
AutoCAD SHX Text
N/A
AutoCAD SHX Text
N/A
AutoCAD SHX Text
1
AutoCAD SHX Text
STI STOPPER II - MANUAL FIRE ALARM BOX COVER
AutoCAD SHX Text
STI-1200
AutoCAD SHX Text
N/A
AutoCAD SHX Text
N/A
AutoCAD SHX Text
1
AutoCAD SHX Text
120VAC SPRINKLER BELL (BY OTHERS)
AutoCAD SHX Text
BELL
AutoCAD SHX Text
INSTALLED BY OTHERS
AutoCAD SHX Text
N/A
AutoCAD SHX Text
N/A
AutoCAD SHX Text
2
AutoCAD SHX Text
BATTERY, 12-VOLT 7-AMP HOUR
AutoCAD SHX Text
BT127
AutoCAD SHX Text
N/A
AutoCAD SHX Text
N/A
AutoCAD SHX Text
N/A
AutoCAD SHX Text
3
AutoCAD SHX Text
BATTERY, 12-VOLT 10-AMP HOUR
AutoCAD SHX Text
BT1210
AutoCAD SHX Text
N/A
AutoCAD SHX Text
N/A
AutoCAD SHX Text
FACU
AutoCAD SHX Text
FAA
AutoCAD SHX Text
P
AutoCAD SHX Text
P
AutoCAD SHX Text
D
AutoCAD SHX Text
M
AutoCAD SHX Text
VOICE
AutoCAD SHX Text
W
AutoCAD SHX Text
*
AutoCAD SHX Text
C
AutoCAD SHX Text
W
AutoCAD SHX Text
WP
AutoCAD SHX Text
W
AutoCAD SHX Text
*
AutoCAD SHX Text
FAC
AutoCAD SHX Text
WF
AutoCAD SHX Text
SEQUENCE OF OPERATION MATRIX
AutoCAD SHX Text
SMOKE DETECTOR @ FACU
AutoCAD SHX Text
AREA SMOKE DETECTOR
AutoCAD SHX Text
MANUAL FIRE ALARM BOX
AutoCAD SHX Text
WATER FLOW SWITCH
AutoCAD SHX Text
VALVE TAMPER SWITCH
AutoCAD SHX Text
DUCT SMOKE DETECTOR @ HVAC FAN
AutoCAD SHX Text
RADIO COMMUNICATOR TROUBLE
AutoCAD SHX Text
VOICE EVAC PANEL TROUBLE
AutoCAD SHX Text
COMMON SYSTEM TROUBLE: INCLUDING: OPEN CIRCUIT, GROUND, SHORT, AND AC LOSS
AutoCAD SHX Text
INDICATE ALARM @ FACU/KEYPAD/ANNUNCIATOR
AutoCAD SHX Text
X
AutoCAD SHX Text
X
AutoCAD SHX Text
X
AutoCAD SHX Text
X
AutoCAD SHX Text
INDICATE TROUBLE @ FACU/KEYPAD/ANNUNCIATOR
AutoCAD SHX Text
X
AutoCAD SHX Text
X
AutoCAD SHX Text
X
AutoCAD SHX Text
INDICATE SUPERVISORY @ FACU/KEYPAD/ANNUNCIATOR
AutoCAD SHX Text
X
AutoCAD SHX Text
X
AutoCAD SHX Text
ACTIVATE 120VAC SPRINKLER BELL
AutoCAD SHX Text
X
AutoCAD SHX Text
ACTIVATE NOTIFICATION
AutoCAD SHX Text
X
AutoCAD SHX Text
X
AutoCAD SHX Text
X
AutoCAD SHX Text
X
AutoCAD SHX Text
SHUT DOWN ASSOCIATED FAN
AutoCAD SHX Text
X
AutoCAD SHX Text
TRANSMIT OFF-SITE ALARM
AutoCAD SHX Text
X
AutoCAD SHX Text
X
AutoCAD SHX Text
X
AutoCAD SHX Text
X
AutoCAD SHX Text
TRANSMIT OFF-SITE TROUBLE
AutoCAD SHX Text
X
AutoCAD SHX Text
X
AutoCAD SHX Text
X
AutoCAD SHX Text
TRANSMIT OFF-SITE SUPERVISORY
AutoCAD SHX Text
X
AutoCAD SHX Text
X
AutoCAD SHX Text
SCOPE OF WORK
AutoCAD SHX Text
THE INTENT OF REV 2 IS TO SHOW THE AS-BUILTS OF THE SYSTEM AS PER COMMENTS FROM THE AHJ.