siemens heating controls residential product selection...

52
Siemens Heating Controls Residential Product Selection Guide s

Upload: donhan

Post on 31-Jan-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

Siemens Heating Controls

Residential Product

Selection Guide

s

Introduction

Adding controls to your heating system can reduce running costs by 40%*

Siemens Heating Controls are one of theWorld’s leading suppliers of products forthe safe and efficient control of heatingsystems in residential installations. Ourreputation is second to none, we aim tomaintain this reputation through ourcommitment to design and product quality,backed by a dedicated technical supportteam.

Our highly trained and knowledgeableteam can be contacted on a local ratenumber 0870 850 0184 from anywhere inthe UK.

Siemens Heating Controls is part of one ofthe largest global electrical andengineering groups.

Throughout a 160 year history of provenresearch and engineering talent, with morethan 50,000 active patents, Siemens hascontinuously provided its customers withinnovations in the areas of healthcare,energy, industry, and infrastructure –globally and locally.

*Recent independent tests by the University of Salford comparing a conventional heating system with no controlsagainst the same system with a room thermostat and TRVs added.

Energy used(%)

Heating

HotWater

Cooking

Appliances

Lighting

With a 40% saving onyour heating you couldachieve a 25% drop inyour overall energy bills

A high quality electronicroom thermostat will turn

off the boiler when thehouse is warm enough.

Choosing a suitableprogrammer will allow youto adjust heating times to

match your lifestyle.

Thermostatic radiatorvalves (TRVs) ensure thatyou only heat the rooms

you need.

A properly installed heating controlsystem will maintain suitabletemperatures in every room in yourhome, prevent wasted heat and makesure your boiler runs efficiently.

Heating controls from Siemens are costeffective and readily available.

They are also easy to fit and can beinstalled with minimal disruption.

40%SAVING

Contents 3

Room Thermostats

RDD100 • RDD100.1 • RDD100.1DHW • RDH10-GBRAA20LD-GB • RAA21-GB • RAA31.16 • RAA11

Programmable Room Thermostats

RDE100 • RDE100.1 • RDE100.1DHW • RDJ10-GB REV13 • REV17 • REV24 • RAV11.1 • RAV11.7

Wireless Thermostats

RDH10RF/SET-GB • RDJ10RF/SET-GB • RDH10RF/SET-CYL • RDD100.1RFSRDE100.1RFS • REV24RF/SET • RDE-MZ6 • RDD100.1RF • RDE100.1RF

Cylinder, Pipe and Frost Thermostats

RAM1 • RAM1T • RAA11

Motorised Valves

CZV... • CMV... • Demountable Actuator

Thermostatic Radiator and By-pass Valves

MTN51GB • Trade TRV • Trade TRV2 • BPV22 • TRV packs and value packs

Product interchange and wiring guide

Time Controls

RWB27 • RWB27Si • RWB29 • RWB29Si • RWB30e • RWB2e RWB1001 • RWB1007 • RWB2001 • RWB2007

4-7

8-11

12-15

16-19

20-21

22

23-26

28-51

Product selection guide index 27

For technical specifications and further information please refer to our website www.siemens.co.uk/residential-controls

3

Time Controls at-a-glance

For technical specifications and further information please refer to our website www.siemens.co.uk/residential-controls

4

RWB27

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

RWB29

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

RWB27Si

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

RWB29Si

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

RWB30e

g

g

g

g

g

g

g

g

g

g

RWB2e

g

g

g

g

g

g

g

g

g

RWB1001

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

RWB1007

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

RWB2001

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

RWB2007

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

Menu drivenprogramming

Large backlitdisplay

Simple operation

Daily programming

Daily, weekday/weekendprogramming

Two or threeON/OFFsper day

Two ON/OFFsper day

Clock with autosummer/winterchangeover

Holidayprogramming

LED ‘ON’ light

Advance facility

1 hour boost facility

Up to 3 hour boostfacility

Override facility

Service IntervalFunction

Visual servicereminder

Audible servicereminder

Independent timingfor hot water andcentral heating

Combination Boilers

Gravity or fullypumped systems

Direct replacementusing industrystandard backplate

365 Battery back up

Volt free contacts

For technical specifications and further information please refer to our website www.siemens.co.uk/residential-controls

RWB27 Timer

RWB29 Programmer

5

Time Controls RWB27 • RWB27Si • RWB29 • RWB29Si

RWB29Si Programmer

RWB27Si Timer

Same functionality as RWB29 but withthe following additional feature:

■ Service interval function

Operating voltage: AC230V ± 10%

Contact rating: 6A Resistive 2A Inductive

Dimensions: 145mm x 90mm x 34mm

■ Unique menu driven programming

■ Easy to read, larger than averagebacklit display

■ Daily, weekday/weekend or7 day programming

■ Advance and up to 3 hour boost facility

■ 2/3 ON/OFFs per day

■ Holiday programming

■ LED ‘ON’ lamps

■ Battery back-up

■ Industry standard backplate

■ Ideal for Gravity or fully pumped systems

Operating voltage: AC230V ± 10%

Contact rating: 6A Resistive 2A Inductive

Dimensions: 145mm x 90mm x 34mm

■ Unique menu driven programming

■ Easy to read, larger than averagebacklit display

■ Daily, weekday/weekend or7 day programming

■ Advance and up to 3 hour boost facility

■ 2/3 ON/OFFs per day

■ Holiday programming

■ LED ‘ON’ lamp

■ Battery back-up

■ Volt free contacts 12-250V

■ Industry standard backplate

■ Ideal for Combination Boilers

Operating voltage: AC230V ± 10%

Contact rating: 6A Resistive 2A Inductive

Dimensions: 145mm x 90mm x 34mm

Same functionality as RWB27 but withthe following additional feature:

■ Service interval function

Operating voltage: AC230V ± 10%

Contact rating: 6A Resistive 2A Inductive

Dimensions: 145mm x 90mm x 34mm

Time Controls RWB30e • RWB2e

RWB30e Traditional Daily Timer

RWB2e Traditional Daily Programmer

■ Daily programming

■ Advance and 1 hour boost facility

■ 2 ON/OFFs per day

■ All day option

■ Override facility

■ LED ‘ON’ lamps

■ Industry standard backplate

■ Ideal for gravity or fully pumped systems

Operating voltage: AC230V ± 10%

Contact rating: 6A Resistive 2A Inductive

Dimensions: 145mm x 90mm x 50mm

For technical specifications and further information please refer to our website www.siemens.co.uk/residential-controls

6

■ Daily programming

■ Advance and 1 hour boost facility

■ 2 ON/OFFs per day

■ All day option

■ Override facility

■ LED ‘ON’ lamp

■ Volt free contacts 12-250V

■ Industry standard backplate

■ Ideal for Combination boilers

Operating voltage: AC230V ± 10%

Contact rating: 6A Resistive 2A Inductive

Dimensions: 145mm x 90mm x 50mm

Time Controls RWB1001 • RWB1007 • RWB2001 • RWB2007

For technical specifications and further information please refer to our website www.siemens.co.uk/residential-controls

RWB1001 Timer

RWB1007 Timer

RWB2001 Programmer

RWB2007 Programmer

7

■ Easy to read backlit display

■ Daily programming

■ Advance and 1 hour boost facility

■ 2/3 ON/OFFs per day

■ Clock with auto summer/winterchangeover

■ Clock supplied preset to correct timeand date

■ LED ‘ON’ lamp

■ Service interval capable

■ Audio and visual service reminder

■ Battery back-up

■ Volt free contacts 12-250V

■ Industry standard backplate

■ Ideal for Combination boilers

Operating voltage: AC230V ± 10%

Contact rating: 6A Resistive 2A Inductive

Dimensions: 145mm x 85mm x 34mm

■ Easy to read backlit display

■ Daily, weekday/weekend or 7 day

■ Advance and 1 hour boost facility

■ 2/3 ON/OFFs per day

■ Clock with auto summer/winterchangeover

■ Clock supplied preset to correct timeand date

■ LED ‘ON’ lamp

■ Service interval capable

■ Audio and visual service reminder

■ Battery back-up

■ Volt free contacts 12-250V

■ Industry standard backplate

■ Ideal for Combination boilers

Operating voltage: AC230V ± 10%

Contact rating: 6A Resistive 2A Inductive

Dimensions: 145mm x 85mm x 34mm

■ Easy to read backlit display

■ Daily programming

■ Advance and 1 hour boost facility

■ 2/3 ON/OFFs per day

■ Clock with auto summer/winterchangeover

■ Clock supplied preset to correct timeand date

■ LED ‘ON’ lamps

■ Service interval capable

■ Audio and visual service reminder

■ Battery back-up

■ Industry standard backplate

■ Ideal for gravity or fully pumped systems

Operating voltage: AC230V ± 10%

Contact rating: 6A Resistive 2A Inductive

Dimensions: 145mm x 85mm x 34mm

■ Easy to read backlit display

■ Daily, weekday/weekend or7 day programming

■ Advance and 1 hour boost facility

■ 2/3 ON/OFFs per day

■ Clock with auto summer/winterchangeover

■ Clock supplied preset to correct timeand date

■ LED ‘ON’ lamps

■ Service interval capable

■ Audio and visual service reminder

■ Battery back-up

■ Industry standard backplate

■ Ideal for gravity or fully pumped systems

Operating voltage: AC230V ± 10%

Contact rating: 6A Resistive 2A Inductive

Dimensions: 145mm x 85mm x 34mm

Room Thermostats at-a-glance

For technical specifications and further information please refer to our website www.siemens.co.uk/residential-controls

8

RAA20LD-GB

g

g

g

g

g

g

g

g

g

g

RAA21-GB

g

g

g

g

g

g

g

g

g

RAA31.16

g

g

g

g

g

g

g

g

g

g

RAA11

g

g

g

g

g

g

g

g

g

g

RDD100

g

g

g

g

g

g

g

g

g

g

RDD100.1

g

g

g

g

g

g

g

g

g

g

RDD100.1DHW

g

g

g

g

g

g

g

g

g

RDH10-GB

g

g

g

g

g

g

g

g

Combination Boilers

Gas filled bellows

24 - 250V

Changeover contacts

Setting range 5°C - 30°C

Setting range 5°C - 35°C

Limiting or locking facility

Setback temperature 5°C - 35°C

Double Insulated (no earth required)

Electronic display

LED ‘ON’ light

Heating or cooling operation

Tamperproof

5 Amp rated

6 Amp rated

ON/OFF switch

Room Thermostats RDD100 • RDD100.1 • RDD100.1DHW

For technical specifications and further information please refer to our website www.siemens.co.uk/residential-controls

9

RDD100 Digital Room Thermostat with LCD

RDD100.1 Digital Room Thermostat with LCD

RDD100.1DHW

■ Room temperature control

■ Double insulated (no earth required)

■ Comfort, economy and frostprotection mode

■ 2-position control with ON/OFFcontrol output

■ Mains Powered

■ Volt free contacts

■ Ideal for Combination Boilers

Power supply: AC230V

Dimensions: 85mm x 106mm x 21.5mm

■ Room temperature control

■ Double insulated (no earth required)

■ Comfort, economy and frostprotection mode

■ 2-position control with ON/OFFcontrol output

■ Battery Powered

■ Volt free contacts

■ Ideal for Combination Boilers

Power supply: DC 3 V 2 x 1.5 V AAA batteries

Dimensions: 85mm x 106mm x 21.5mm

■ Room temperature control

■ Double insulated (no earth required)

■ Comfort, economy and frostprotection mode

■ 2-position control with ON/OFFcontrol output

■ Battery Powered

■ Volt free contacts

■ Independent ON/OFF control of DHW

Power supply: DC 3V 2 x 1.5V AAA batteries

Dimensions: 85mm x 127mm x 21.5mm

RAA21-GB Standard Room Thermostat

RAA20LD-GB Large Dial Room Thermostat

RAA31.16 Room Thermostat with LED ‘ON’ Light

Room Thermostats RDH10-GB • RAA20LD-GB • RAA21-GB • RAA31.16

For technical specifications and further information please refer to our website www.siemens.co.uk/residential-controls

10

■ Gas bellows type operation(no neutral required)

■ Double insulated (no earth required)

■ Ideal for Combination Boilers

■ Volt free contacts

Temperature range:

8°C - 30°C (lockable)

Contacts: 6(2.5)A SPDT

Nominal voltage: 24 - 250V

Dimensions: 105mm x 124mm x 44mm

■ Gas bellows type operation(no neutral required)

■ Double insulated (no earth required)

■ Ideal for Combination Boilers

■ Volt free contacts

Temperature range: 8°C - 30°C (lockable)

Contacts: 6(2.5)A SPDT

Nominal voltage: 24 - 250V

Dimensions: 96mm x 97mm x 35mm

■ Gas bellows type operation

■ Double insulated (no earth required)

■ Manual ON/OFF switch

■ Neutral required for indicator light

Temperature range: 8°C - 30°C (lockable)

Contacts: 6(2.5)A SPDT

Nominal voltage: 230V ± 10%

Dimensions: 96mm x 97mm x 35mm

RDH10-GB Digital Room Thermostat

■ Large, easy to read display

■ Double insulated (no earth required)

■ Large dial for settings

■ Battery Powered

■ Volt free contacts

Power supply: 2 x 1.5V AA batteries

Current rating: 5(2)A

Dimensions: 90mm x 120mm x 35mm

For technical specifications and further information please refer to our website www.siemens.co.uk/residential-controls

11

Room Thermostats RAA11

RAA11 Tamperproof Double Insulated Room Thermostat

■ Gas bellows type operation(no neutral required)

■ Double insulated (no earth required)

■ Tamperproof

■ Suitable for use as a frost thermostat

■ Ideal for Combination Boilers

Temperature range:8°C - 30°C (lockable)

Contacts: 6(2.5)A SPDT

Nominal voltage: 24 - 250V

Dimensions: 96mm x 97mm x 35mm

Programmable Room Thermostats at-a-glance

For technical specifications and further information please refer to our website www.siemens.co.uk/residential-controls

12

RDJ10-GB

g

g

g

g

g

g

g

g

g

g

RAV11.1

g

g

g

g

g

g

g

g

g

g

g

g

RAV11.7

g

g

g

g

g

g

g

g

g

g

g

g

REV13

g

g

g

g

g

g

g

g

g

g

g

g

g

REV17

g

g

g

g

g

g

g

g

g

g

g

g

g

REV24

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

RDE100

g

g

g

g

g

g

g

g

g

g

g

g

g

g

RDE100.1

g

g

g

g

g

g

g

g

g

g

g

g

g

g

RDE100.1DHW

g

g

g

g

g

g

g

g

g

g

g

g

g

Combination Boilers

Underfloor heating

Self-learning logic

Digital display

Programmable awayfrom backplate

PID (TPI) control

24 - 250V

Analogue clock

Daily programming

Weekday/weekendprogramming

7 day programming

Lockable display

Holiday programming

Setback facility

Frost protection

Changeover contacts

Party mode (up to 9 hour boost)

5 Amp rated

6 Amp rated

8 Amp rated

For technical specifications and further information please refer to our website www.siemens.co.uk/residential-controls

13

RDJ10-GB Programmable Room Thermostat

RDE100.1 Programmable Room Thermostat

RDE100 Programmable Room Thermostat

Programmable Room ThermostatsRDE100 • RDE100.1 • RDE100.1DHW • RDJ10-GB

■ Large, easy to read LCD display

■ Double insulated (no earth required)

■ Large dial for settings

■ Daily programming

■ Battery powered

■ Volt free contacts

■ Ideal for combination boilers

Power supply: 2 x 1.5V AA batteries

Current rating: 5(2)A

Dimensions: 90mm x 120mm x 35mm

RDE100.1DHW

■ Room temperature control

■ Double insulated (no earth required)

■ Daily, weekday/weekend or7 day programming

■ Comfort, economy andfrost protection mode

■ 2-position control with ON/OFFcontrol output

■ Holiday programming

■ Battery powered

■ Volt free contacts

■ Ideal for combination boilers

Power supply: 2 x 1.5V AAA batteries

Current rating: 5(2)A

Dimensions: 85mm x 127mm x 21.5mm

■ Room temperature control

■ Double insulated (no earth required)

■ Daily, weekday/weekend or7 day programming

■ Comfort, economy andfrost protection mode

■ 2-position control with ON/OFFcontrol output

■ Holiday programming

■ Battery Powered

■ Volt free contacts

■ Independent ON/OFF control of DHW

Power supply: DC 3V 2 x 1.5V AAA batteries

Dimensions: 85mm x 127mm x 21.5mm

■ Room temperature control

■ Double insulated (no earth required)

■ Daily, weekday/weekend or7 day programming

■ Comfort, economy andfrost protection mode

■ 2-position control with ON/OFFcontrol output

■ Holiday programming

■ Mains powered

■ Volt free contacts

■ Ideal for combination boilers

Power supply: AC230V

Current rating: 5(2)A

Dimensions: 85mm x 127mm x 21.5mm

Programmable Room ThermostatsREV13 • REV17 • REV24

For technical specifications and further information please refer to our website www.siemens.co.uk/residential-controls

14

REV24 Programmable Room Thermostat

REV17 Programmable Room Thermostat

REV13 Programmable Room Thermostat

■ Room temperature control

■ Double insulated (no earth required)

■ Large, easy to read LCD display

■ Slider settings and text instructions

■ Daily programming

■ Comfort, economy, energy saving andfrost protection mode

■ 2-position control with ON/OFFcontrol output

■ Up to 9 hour boost

■ PID (TPI) Control

■ Battery powered

■ Volt free contacts

■ Ideal for combination boilers

Power supply: 2 x 1.5V AAA batteries

Current rating: 6(2)A

Dimensions: 130mm x 94mm x 30mm

■ Room temperature control

■ Double insulated (no earth required)

■ Large, easy to read LCD display

■ Slider settings and text instructions

■ Weekday/weekend programming

■ Comfort, economy, energy saving andfrost protection mode

■ 2-position control with ON/OFFcontrol output

■ Up to 9 hour boost

■ PID (TPI) Control

■ Battery powered

■ Volt free contacts

■ Ideal for combination boilers

Power supply: 2 x 1.5V AAA batteries

Current rating: 6(2)A

Dimensions: 134.5mm x 94mm x 30mm

■ Room temperature control

■ Double insulated (no earth required)

■ Large, easy to read LCD display

■ Slider settings and text instructions

■ Daily, weekday/weekend or7 day programming

■ Comfort, economy, energy saving andfrost protection mode

■ 2-position control with ON/OFFcontrol output

■ Up to 9 hour boost

■ PID (TPI) Control

■ Holiday programming

■ Battery powered

■ Volt free contacts

■ Ideal for combination boilers

Power supply: 2 x 1.5V AAA batteries

Current rating: 6(2)A

Dimensions: 134.5mm x 94mm x 30mm

Battery Operated Programmable Room ThermostatsRAV11.1 • RAV11.7

For technical specifications and further information please refer to our website www.siemens.co.uk/residential-controls

15

RAV11.7 Analogue Programmable Room Thermostat

RAV11.1 Analogue Programmable Room Thermostat

■ Room temperature Control

■ Double insulated (no earth required)

■ Easy to read display

■ Daily programming

■ Comfort, economy, energy saving andfrost protection mode

■ 2-position control with ON/OFFcontrol output

■ PID (TPI) Control

■ Battery powered

■ Ideal for combination boilers

Power supply: 2 x 1.5V AA batteries

Current rating: 8(3.5)A

Dimensions: 128mm x 104mm x 37mm

■ Room temperature Control

■ Double insulated (no earth required)

■ Easy to read display

■ 7 day programming

■ Comfort, economy, energy saving andfrost protection mode

■ 2-position control with ON/OFFcontrol output

■ PID (TPI) Control

■ Battery powered

■ Ideal for combination boilers

Power supply: 2 x 1.5V AA batteries

Current rating: 8(3.5)A

Dimensions: 128mm x 104mm x 37mm

RF (Wireless) Thermostats at-a-glance

For technical specifications and further information please refer to our website www.siemens.co.uk/residential-controls

16

Combination Boilers

Underfloor heating

24 - 250V voltfree contacts

Large digital display

Backlit display

Setback facility

Changeover contacts

Advance

Daily programming

Weekday/weekendprogramming

7 day programming

Large control dial

PID (TPI) control

433Mhz

868Mhz

Double insulated

Holiday programming

Frost protection

Override

Manual overrideswitch (on receiver)

Party mode(up to 9 hour boost)

RF signal strengthindicator

RDJ10RF/SET-GB

g

g

g

g

g

g

g

g

g

g

g

g

g

g

RDH10RF/SET-GB

g

g

g

g

g

g

g

g

g

RDD100.1RFS

g

g

g

g

g

g

g

g

g

g

RDE100.1RFS

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

REV24RF/SET

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

RDE-MZ6

g

g

g

g

g

g

g

RDD100.1RF

g

g

g

g

g

g

g

g

g

g

RDE100.1RF

g

g

g

g

g

g

g

g

g

g

g

g

g

g

g

RDHRF/SET-CYL

g

g

g

g

g

g

g

Wireless Thermostats RDH10RF/SET • RDJ10RF/SET • RDH10RF/SET-CYL

RDH10RF/SET-CYL Wireless cylinderthermostat and receiver

RDH10RF/SET-GB Wireless digital roomthermostat and receiver

RDJ10RF/SET-GB Wireless programmable roomthermostat and receiver

For technical specifications and further information please refer to our website www.siemens.co.uk/residential-controls

17

■ Large, easy to read LCD display

■ Double insulated (no earth required)

■ Large dial for settings

■ Manual override

■ Battery powered

■ Volt free contacts

■ Range 20 metres line of sight between transmitter and receiver

Power supply: 2 x 1.5V AA batteries

Current rating: 8(3)A

Dimensions: 90mm x 120mm x 35mm

■ Large, easy to read LCD display

■ Double insulated (no earth required)

■ Large dial for settings

■ Manual override

■ Daily programming

■ Battery powered

■ Volt free contacts

■ Range 20 metres line of sight between transmitter and receiver

Power supply: 2 x 1.5V AA batteries

Current rating: 8(3)A

Dimensions: 90mm x 120mm x 35mm

■ Large, easy to read LCD display

■ Double insulated (no earth required)

■ Large dial for settings

■ Manual override

■ Battery powered

■ Volt free contacts

■ Range 20 metres line of sight between transmitter and receiver

Power supply: 2 x 1.5V AA batteries

Current rating: 8(3)A

Dimensions: 90mm x 120mm x 35mm

Wireless Thermostats RDD100.1RFS • RDE100.1RFS • REV24RF/SET

RDD100.1RFS Wireless digital roomthermostat and receiver

RDE100.1RFS Wireless programmableroom thermostat and receiver

REV24RF/SET Wireless programmable roomthermostat and receiver

For technical specifications and further information please refer to our website www.siemens.co.uk/residential-controls

18

■ Room temperature control

■ Double insulated (no earth required)

■ Comfort, economy and frost protection mode

■ Battery powered

■ Volt free contacts

■ Unique RF signalling

■ Range 20 metres line of sight between transmitter and receiver

Power supply: 2 x 1.5V AAA batteries

Current rating: 8(3)A

Dimensions: 85mm x 106mm x 22mm

■ Double insulated (no earth required)■ Daily, weekday/weekend or 7 day programming■ Slider settings and text instructions■ Signal strength indicator■ PID (TPI) control■ Comfort, economy and frost protection mode■ Automatic summer/winter changeover■ Up to 9 hour boost■ Holiday programming■ Battery powered■ Volt free contacts■ Ideal for combination boilers■ Range 20 metres line of sight between transmitter and receiverPower supply: 2 x 1.5V AA batteriesCurrent rating: 16(2)ADimensions: 134.5mm x 94mm x 30mm

■ Room temperature control■ Double insulated (no earth required)■ Daily, weekday/weekend or 7 day programming■ Comfort, economy and frost protection mode■ 2-position control with ON/OFF control output■ Holiday programming■ Battery powered■ Volt free contacts■ Ideal for combination boilers■ Unique RF signalling■ Range 20 metres line of sight between transmitter and receiverPower supply: 2 x 1.5V AAA batteriesCurrent rating: 8(3)ADimensions: 85mm x 127mm x 22mm

Wireless Thermostats RDE-MZ6 • RDD100.1RF • RDE100.1RF

RDD100.1RF Wireless programmableroom thermostat

RDE100.1RF Wireless programmableroom thermostat

For technical specifications and further information please refer to our website www.siemens.co.uk/residential-controls

19

RDE-MZ6 Wireless multizone receiver

■ For use with RDE-MZ6 multizone receiver

■ Room temperature control

■ Double insulated (no earth required)

■ Daily, weekday/weekend or 7 day programming

■ Comfort, economy and frost protection mode

■ 2-position control with ON/OFF control output

■ Holiday programming

■ Battery powered

■ Range 20 metres line of sight between transmitter and receiver

Power supply: 2 x 1.5V AA batteries

Dimensions: 85mm x 127mm x 21.5mm

■ For use with RDE-MZ6 multizone receiver

■ Room temperature control

■ Double insulated (no earth required)

■ Comfort, economy and frost protection mode

■ Battery powered

■ Range 20 metres line of sight between transmitter and receiver

Power supply: 2 x 1.5V AA batteries

Dimensions: 85mm x 106mm x 21.5mm

Only for use in conjunction with RDD100.1RF and RDE100.1RF roomthermostats (to be ordered separately)

■ Up to 6 devices can be connected for independent control ofeach room/zone

■ Easy and quick installation due to new design and easily identifiableterminal markings

■ Simple pairing of operation helps reduce installation time

■ Indication of operating status via LEDs

■ External antenna for multizone installation inside a metal enclosureor weak wireless connectivity (provided free)

Current rating: 8(2)A

Dimensions: 280mm x 76mm x 36.5mm

Cylinder, Pipe and Frost Thermostats at-a-glance

For technical specifications and further information please refer to our website www.siemens.co.uk/residential-controls

20

RAM1

g

g

g

g

RAM1-T

g

g

g

g

g

RAA11

g

g

g

g

g

Bi-metallic sensing

Gas bellows sensor

15°C - 90°C

8°C - 30°C

SPDT contacts

Can be used on pipe up to 41mm

Tamperproof cover

Can be used as a Frost thermostat

■ Bi-metallic

Temperature setting range: 15°C - 90°C

Contacts: 15A, SPDT

Can be used as a pipe thermostat up to 41mm diameter

Dimensions: 50mm x 116mm x 59mm

Cylinder, Pipe and Frost Thermostats RAM1 • RAM1T • RAA11

RAM1 Cylinder/Pipe Thermostat

■ Bi-metallic

■ Tamperproof

Temperature setting range: 15°C - 90°C

Contacts: 15A, SPDT

Can be used as a pipe thermostat up to 41mm diameter

Dimensions: 50mm x 116mm x 59mm

RAM1.T Tamperproof Cylinder/Pipe Thermostat

For technical specifications and further information please refer to our website www.siemens.co.uk/residential-controls

21

RAA11 Tamperproof Frost Thermostat

■ Gas bellows type operation(no neutral required)

■ Double insulated (no earth required)

■ Tamperproof

■ Volt free contacts

Temperature range: 8°C - 30°C (lockable)

Contacts: 6(2.5)A SPDT

Nominal voltage: 24 - 250V

Dimensions: 96mm x 97mm x 35mm

Motorised valves

CZV... 22mm and 28mm 2-port motorised valves

Demountable actuator

For technical specifications and further information please refer to our website www.siemens.co.uk/residential-controls

22

■ Demountable actuator(power head)

■ Replaceable motor

■ Wedge type actuator

■ Spring return operation

■ Motor open

■ Volt free 24-240V switching

■ Manual lever for flushing orfilling the system

■ Industry standard wiring

■ Standard motor voltage: 230V 50Hz

Part numbers:CZV222 - 22mm 2-port valveCZV228 - 28mm 2-port valve

■ Demountable actuator(power head)

■ Replaceable motor

■ Wedge type actuator

■ Spring return operation

■ Manual lever for flushing orfilling the system

■ Industry standard wiring

■ Standard motor voltage:230V 50Hz

Part numbers:CMV322 - 22mm 3-port valveCMV328 - 28mm 3-port valve

CMV... 22mm and 28mm 3-port motorised valves

■ Replaceable motor

■ Wedge type actuator

■ Spring return operation

■ Manual lever for flushing orfilling the system

■ Industry standard wiring

■ Standard motor voltage:230V 50Hz

Part numbers:DVA2/5 - Actuator for CZV222DVA2/6 - Actuator for CZV228DVA3 - Actuator for CMV322

and for CMV328

TRVs and By-pass valve

MTN51GB Thermostatic Radiator Valve (TRV)

Trade TRV 2 Thermostatic Radiator Valve

Trade TRV Thermostatic Radiator Valve

For technical specifications and further information please refer to our website www.siemens.co.uk/residential-controls

23

■ Allows for constant water circulation through the boiler/system

when TRVs close

■ Reduces pump burn out

■ Reduces system and boiler noise

■ Improves system efficiency

■ 22mm fittings only

Automatic By-pass valve BPV22

■ Liquid sensor

■ Reverse flow fitting allows installation in either flow or returnwithout regard to head position

■ Supplied complete with 10 and 15mm fittings

■ Temperature limiters

■ Frost protection setting

■ EN215 approval

*We recommend the installation of an Automatic By-pass valveto achieve maximum efficiency from the system

■ Liquid sensor

■ Reverse flow fitting allows installation in either flow or returnwithout regard to head position

■ Supplied complete with 10 and 15mm fittings

■ Temperature limiters

■ Frost protection setting

■ EN215 approval

■ Also available with push fit elbow MTN51GBL

*We recommend the installation of an Automatic By-pass valveto achieve maximum efficiency from the system

■ Wax sensor offers sensitivity and accuracy

■ Reverse flow fitting allows installation in either flow or return

without regard to head position

■ Supplied complete with 10 and 15mm fittings

■ Temperature limiters

■ Frost protection setting

■ EN215 approval

*We recommend the installation of an Automatic By-pass valveto achieve maximum efficiency from the system

TRV pack 4

■ TRV

■ Angled 10/15mm body

■ Lockshield & Cap

■ Push fit elbows

■ Drain off

TRV pack 3

■ TRV

■ Angled 10/15mm body

■ Lockshield & Cap

■ Push fit elbows

TRV pack 2

■ TRV

■ Angled 10/15mm body

■ Lockshield & Cap

■ Drain off

TRV pack 1

■ TRV

■ Angled 10/15mm body

■ Lockshield & Cap

For technical specifications and further information please refer to our website www.siemens.co.uk/residential-controls

24

TRV Packs

For technical specifications and further information please refer to our website www.siemens.co.uk/residential-controls

25

TRV pack 5

■ TRV

■ Straight 10/15mm body

■ Lockshield & Cap

■ Push fit elbows

■ Drain off

TRV Packs

TRV pack 9

TRV pack 10

■ Drain off valve

TRV pack 11

■ Angled 10/15mm body

■ Lockshield/Wheelhead & Caps

■ Drain off

■ MTN51GB

■ TRV body

■ Lockshield/Wheelhead & Caps

■ Drain off valve

For technical specifications and further information please refer to our website www.siemens.co.uk/residential-controls

26

TRV pack 12

TRV Packs

■ 2 x TRV bodies angled 10/15mm bodies

■ 2 x Lockshield/Wheelhead & Caps

■ Drain off valve

Product Selection Guide Index

Time Controls

At-a-glance 4RWB27 5RWB27Si 5RWB29 5RWB29Si 5RWB2e 6RWB30e 6 RWB1001 7RWB1007 7RWB2001 7RWB2007 7

Room Thermostats

At-a-glance 8RDD100 9RDD100.1 9 RDD100.1DHW 9RAA20LD-GB 10RAA21-GB 10RAA31.16 10RDH10-GB 10RAA11 11

Programmable RoomThermostats

At-a-glance 12RDE100 13RDE100.1 13RDE100.1DHW 13RDJ10-GB 13REV13 14REV17 14REV24 14RAV11.1 15RAA11.7 15

Wireless Thermostats

At-a-glance 16RDH10RF/SET-GB 17RDJ10RF/SET-GB 17RDH10RF/SET/CYL 17RDD100.1RFS 18RDE100.1RFS 18REV24RF/SET 18RDE-MZ6 19RDD100.1RF 19RDE100.1RF 19

Motorised Valves

CZV22 22CZV28 22CMV22 22CMV28 22Demountable Actuator 22

Cylinder, Pipe & FrostThermostats

At-a-glance 20RAM1 21RAM1T 21RAA11 21

Thermostatic Radiator (TRVs)& By-pass valves

MTN51-GB 23Trade TRV 23Trade TRV 2 23BPV22 23TRV Packs 24, 25, 26

For technical specifications and further information please refer to our website www.siemens.co.uk/residential-controls

27

28

Product comparison guide 29

Programmers 30-32

Timeswitches 33-34

Room thermostats 35

Cylinder thermostats 35

Programmable room thermostats 36

Motorised valves 37-38

Mid-Position, fully pumped schematic 39-40

Mid-Position system fault finding 41

Mid-Position system fault finding table 42

Zone control schematic 43-44

Zone control system fault finding 45

Zone control system fault finding table 46

Gravity hot water, pumped central heating system Schematic 47

Gravity system fault finding 48

Gravity system fault finding table 48

Timeswitches for combination boiler installations 49

Programmable thermostats for combination boiler installations 50

Thermostats terminal numbering 51

Product Interchange and Wiring Guide

29

Product Comparison Guide

*To replace a diverter valve with a mid-position valve, replace old brown wire with grey and white together and make the orange safe.

Product Description Siemens Danfoss Randall Drayton Honeywell Horstmann Myson Pegler Potterton Sunvic

Daily electromechanicalprogrammer10 or 16 way

Daily electromechanicaltimeswitch 10 or 16 way

Daily electronicmini-programmer

Daily electronicprogrammer10 or 16 way

Weekday/weekendelectronic programmer

7 day electronicprogrammer

Daily electronictimeswitch

Weekday/weekend electronic timeswitch

7 day electronictimeswitch

Daily programmableroom thermostat

Weekday/weekendprogrammable roomthermostat

7 day programmable room thermostat

Room thermostat

Cylinder thermostat

Mid-position 3-portmotorised valve 22mm

Mid-position 3-portmotorised valve 28mm

2-port motorised zone valve 22mm

2-port motorised zone valve 28mm

Diverter 3-port motorised

TRV angle valve10/15mm

RWB2E

RWB30E

RWB29

RWB29RWB2001

RWB29RWB2007

RWB29RWB2007

RWB27RWB1001

RWB27RWB1007

RWB27RWB1007

REV13

REV24

REV24REV24RF

RAA20

RAM1

*CMV322

*CMV328

CZV222

CZV228

*

MTN51GB

3020P30604033

SET3M

103

102ES102E7SET2E102E5

CP715FP715SET3EFP975

CP715FP715FP975

CP715FP715FP975

TS715SET1E

TS715TS975

TS715TS975

TP4

TPSTP6000TP500

TP700

RET24RET230RMT24

RMT230

ATC

HSV3B 22HSV3

HSV3B 28HS3

HPV228HPV22

HPV288HPV29

HSV3DHS3DB

RAS-C2

400805600SM2

300SM1

-

LP112LP241

Tempus 3Tempus 6

LPS22Tempus 6

LP722Tempus 7

LP111Tempus 1

Tempus 2

LP711Tempus 2

Digistat 2Digistat 4

-

Digistat 3

RTS8

HTS3PTS1

MA1/6793679H

340-0L0

779H340-30L0

679H308-0L1

ZA6/779779H

335-30L0

-

RT111

-

-

ST6200AST9400A

ST699ST9400A

-

ST799ST6400

ST9400C

ST6100

-

ST6100

CM61CM901

-

CM67CM907

T6360

L641

V4073A109

V4073A1088

V4043H1056

V4043H1106

V4044C1288

VT117EVT15

VT200

H425 TiaraH425 Diadem

H425 Coronet

-

Centaurplus C21H21XL

-

Centaurplus C27H27XL

Centaurplus C11H11XL

-

Centaurplus C17H17XL

PRT1AS1

Centaurstat 1

-

Centaurstat 7

HRT1HRT2

HCT1

Z322XL

-

Z222XL

Z228XL

-

Thermoplus XL

-

-

-

MEP2c

MEP2c

MEP2c

MEP1c

MEP1c

MEP1c

-

-

MPRT

MRT1

MCT1

MPE322

MPE328

MPE222

MPE228

MPE322DV

-

TMP2

TMP1

-

TP2

-

-

TP1

-

-

-

-

-

TRT1

TCT1

TMPV22

TMPV28

TZV22

TSZ28

-

-

-

-

-

EP2000

EP2002

EP3002EP6002

EP4000

EP4002

EP5002

-

-

-

PRT2PRT100ST

PTT100

PMV3MSV322

-

PMV2MSV222

-

-

-

MP2

-

-

Simplex 200Select 207XL

Select 207XL

Select 207XL

Simplex 100Select 107XL

Select 107XL

Select 107XL

-

-

TLX6501

TLX2251/2259TLX2356/2357/2358TLX3101/TLX5101TLX920/TLM2802

SA2452

SDV2211SDMV2304

SDMV2320

SZV2212SZMV2305SMV2217

SZV2228SZMV2323

SDV2291

TRV400

30

HW HTG HW HTGMains Off Off On On

Manufacturer Model(s) E N L 1 2 3 4 Wiring

RWB29, RWB2e, RWB2001 & RWB2007 Programmers

Siemens RWB29 E N L 1 2 3 4 -

RWB2E E N L 1 2 3 4 -

RWB2001 E N L 1 2 3 4 -

RWB2007 E N L 1 2 3 4 -

A.C.L. Drayton 2000 - N L HW OFF HTG OFF HW ON HTG ON Links between L-C-C not required

FP - 2 1 8 11 6 10 Links between 1-5-7 not required

LP112 N L 1 2 3 4 Direct replacement

LP241, LS241 N L 1 2 3 4 Direct replacement

LP522, LS522 N L 1 2 3 4 Direct replacement

LP722, LS722 N L 1 2 3 4 Direct replacement

MP 2 1 - - 6 10 Links between 1&4 and 6&11 not required

Tempus 3, 4, 6 & 7 E N L 1 2 3 4 Need to replace backplate

A.M.F. (Venner) All models Contact Siemens helpline 0870 850 0184

Barlo EPR1 E N L 1 2 3 4

Boss Therm RPF7 E N L 1 2 3 4 Direct replacement

RP24 E N L 1 2 3 4 Direct replacement

BUP/BUP2 E N L 1 2 3 4 Direct replacement

Danfoss Randall 102, 102E5, 102E7 E 5 6 - - 1 2 Links between 6-3 not required

105 E 5 6 - 2 3 1

701, 702 E N L 4 2 3 1 Links between L-5-6 not required

922, 972 E N L 1 4 3 6 Links between L-5-6 not required

3002 E N L 3 - 1 4 Links between 6-3 not required

3020p E 1&7 6 - - 4 2 If terminal 3 wired keep cables together in

separate block/if no room stat terminals

2-3 may have been linked

3033 E(8) 1&7 6 5 3 4 2 Terminal 8 earth

3060 E(8) 1&7 6 - - 4 2 terminal 3 wired keep cables together in

separate block/if no room stat terminals

2-3 may have been linked

4033 E 7 1&6 5 3 4 2

CP15, CP75, CP715, - N L 1 2 3 4 Direct replacement

FP15, FP50C,

FP715, MP15, MP75

FP975 E N L 3 6 1 4 Links between L-2-5 not required/can be

volt free (9 way backplate)

R6 MK2 E 3 1&2 - - 4 5 If room stat fitted wires in terminal 6

connect in separate block

Set2/Set2e, Set3/ E N L 3 6 1 4 Link between L-2-5 not required

Set3e, Set3m, Set5

TSR/2P E 3 1 - - 5 7 Links between 1-2 & 5-6 not required

TSR/3+3 E 3 1 2 5 1 4

Eberle All models Contact Siemens helpline 0870 850 0184

Glowworm Mastermind - N L 1 2 3 4 Direct replacement

If the manufacturer or model you are replacing is not listed above, please contact the Siemens helpline on 0870 850 0184.

Siemens RWB29 E N L 1 2 3 4 -

RWB2E E N L 1 2 3 4 -

RWB2001 E N L 1 2 3 4 -

RWB2007 E N L 1 2 3 4 -

Honeywell ST499A - N L - - 6 3 Links between L-2-5 not required/Zone systems only

ST1000 E N L 3 6 1 4 Links between L-2-5 not required

ST6200A 1009 - N L 1 2 3 4 Need to replace backplate

ST6300A 1007 - N L 1 2 3 4 Need to replace backplate

ST6400A 1003 - N L 1 2 3 4 Need to replace backplate

ST6400B 1003 - N L 1 2 3 4 Need to replace backplate

ST6400C 1003 - N L 1 2 3 4 Need to replace backplate

ST6450B 1017 - N L 1 2 3 4 Need to replace backplate

ST699B 1002 - N L 7 4 6 3 Links between L-5-8 not required

ST699C - N L 7 4 6 3 Links between L-5-8 not required

ST7000A 1002 - - L 2 - 3 4 Battery powered will need neutralconnection to operate modern units

ST7100 - N L HW OFF HTG OFF HW ON HTG ON Links between L-3-6 not required

ST7100A 1000 - N L 7 4 8 5 Links between L-3-6 not required

ST799A 1003 - N L 7 4 6 3 Links between L-5-8 not required

ST9400 - N L 1 2 3 4 Change backplate

Horstmann Amethyst 7 & 10 - 2&3 1 4 6 5 7

Amethyst 423 E 2 1 4 6 5 7 Link between 2-3 not required

Centaur Plus C121 E N L 1 2 3 4 Direct replacement

Centaur Plus C21 E N L 1 2 3 4 Direct replacement

Centaur Plus C27 E N L 1 2 3 4 Direct replacement

Centaur Plus C127 E N L 1 2 3 4 Direct replacement

Centaur Plus H21, - N L 3 6 1 4 Links between L-2-5 not required

Centaur Plus H27

Centaur TC1/TC7 - N L 1 2 3 4 Direct replacement

Channel Plus H121/ E N L 3 6 1 4 Links between L-2-5 not required

H21/ H27

Coral 423/424 - 2 1 - - 8 4 Links between 7-8 not required

Diadem 425 E N L 3 6 1 4 Links between L-2-5 not required

Diamond 423, E N L - - 2 4 Links between L-1-3 not required terminal

Diamond 424 5 spare if used keep wires together in

separate block

Tiara 425, 525 E N L 3 6 1 4 Links between L-2-5 not required

IFLO 985627 E N L 1 2 3 4 Direct replacement

Landis & Gyr RWB1 - N L 1 2 3 4 Direct replacement: Note if terminals 1 & 2

have been used these wires should be

removed and placed in separate connectors

RWB2 - N L - - 3 4 Direct replacement

RWB20 - - L 1 2 3 4 Direct replacement, but check neutral

connected and fit if required

RWB40 - N L 1 2 3 4 Direct replacement

RWB102 - N L - - 3 4 Direct replacement (Use 10 mode)

RWB200, RWB252, - N L 1 2 3 4 Direct replacement

RWB270, RWBXP

31

HW HTG HW HTGMains Off Off On On

Manufacturer Model(s) E N L 1 2 3 4 Wiring

RWB29, RWB2e, RWB2001 & RWB2007 Programmers

If the manufacturer or model you are replacing is not listed above, please contact the Siemens helpline on 0870 850 0184.

32

HW HTG HW HTGMains Off Off On On

Manufacturer Model(s) E N L 1 2 3 4 Wiring

RWB29, RWB2e, RWB2001 & RWB2007 Programmers

If the manufacturer or model you are replacing is not listed above, please contact the Siemens helpline on 0870 850 0184.

Siemens RWB29 E N L 1 2 3 4 -

RWB2E E N L 1 2 3 4 -

RWB2001 E N L 1 2 3 4 -

RWB2007 E N L 1 2 3 4 -

Myson Microtimer Seven - N L 7 4 6 3

MEP2C - N L 1 2 3 4 Backplate will need replacing

Potterton EP2000, EP2001, - N L 1 2 3 4 Link between L & 5 not required

EP2002, EP3000,

EP3001, EP3002

EP6000, EP6002

Miniminder, - N L 1 2 3 4 Direct replacement

Miniminder E

Sangamo All Models Contact Siemens helpline 0870 850 0184

Satchwell, DHP2201 E N L 8 5 6 3 Links between L-4-7 not required

Sunvic ET1401, ET1451 - N L 8 5 7 4 Links between 2-3-6 not required

& Pegler Libra E N L 8 5 6 3 Links between 2-4-7 not required

MP2 E N L HW OFF - HW ON CH ON

Select 207, 207XL, - N L 1 2 3 4 Direct replacement

Simplex

SP25, SP30 - N L 1 - 2 5

SP50, SP100 E N L 1 4 2 5 Link between L-3 not required

Smiths Industries All Models Contact Siemens helpline 0870 850 0184

Sopac All Models Contact Siemens helpline 0870 850 0184

Switchmaster SM320, SM350 E N&2 L - - 3 1 Link L-4 not required (RWB must be set to

10 mode)

SM400, SM600 E N L - 4 3 1

SM800, SM805, E N L 4 2 3 1

SM905

SM900, SM9000, E N L 4 2 3 1 A,B,C spare terminals

SM9001

Tower/Grasslin/ 2000, T2003, - E L HW OFF HTG OFF HW ON HW ON

Towercron T2003Q

T2002, T2002Q - E L - - HW ON HTG ON

DP72 - E L HW OFF HTG OFF HW ON HW ON Direct replacement

FP - 2 1 8 11 6 10 Links between 1-5-7 not required

MP - 2 1 - - 6 10 3,7 & 8 spare terminals, links between

1 & 4 and 5 & 11 not required

QE2 E N L 1 2 3 4 Direct replacement

Wickes RWB2/6832 - N L 1 2 3 4 Direct replacement

RWB200.cw - N L 1 2 3 4 Direct replacement

RWB252.cw - N L 1 2 3 4 Direct replacement

RWB2E.cw - N L 1 2 3 4 Direct replacement

RWB9.cw - N L 1 2 3 4 Direct replacement

HW HTG HW HTGMains Off Off On On

Manufacturer Model(s) E N L 1 2 3 4 Wiring

RWB27, RWB30e, RWB1001 & RWB1007 Timeswitches

Siemens RWB27 E N L 1 2 3 4 -

RWB30E E N L 1 2 3 4 -

RWB1001 E N L 1 2 3 4 -

RWB1007 E N L 1 2 3 4 -

A.C.L. Drayton LP111, LS111, - N L - 1 2 4 Replace link L-1 onto L-2 only if fitted

Lifestyle, LS711 - N L - 1 2 3 Replace link L-1 onto L-2 only if fitted

LP711 E N L 4 1 2 3 Replace link L-1 onto L-2 only if fitted

Towercron TC - 2 1 - - - 7 Replace link 4-6 onto L-2 only if fitted

Tempus 1 & 2 E N L 4 1 2 3 Replace link L-1 onto L-2 only if fitted

(new models)

Tempus 1 & 2 - N L 4 1 3 2 Replace link L-1 onto L-2 only if fitted

(old models)

SM1 E N L - 1 2 3 Replace link L-1 onto L-2 only if fitted

A.M.F. (Venner) All models Contact Siemens 0870 850 0184

Boss Therm RT7, RT24, BUT/BUT2 E N L - 2 3 4 Direct replacement

RTF7 - N L 1 2 3 4 Direct replacement

Danfoss Randall 103, 103 E5, E 5 6 2 3 - 1 Replace link 6-3 onto L-2 only if fitted

103 E7

151 E 5 6 - 3 2 1 Replace link 6-3 onto L-2 only if fitted

911, 971 E N L - 5 4 6 Replace link L-5 onto L-2 only if fitted

3001 E N L - 5 2 4 Replace link L-5 onto L-2 only if fitted

3020 E 1&7 6 - - - 4 Insert link L-2 on RWB backplate

Set 1 , Set 1e, E N L - 5 6 4 Replace link L-5 onto L-2 only if fitted

Set 4

TS15, TS75 E N L - 1 2 4 Replace link L-1 onto L-2 only if fitted

TS715 - N L 3 1 2 4 Replace link L-1 onto L-2 only if fitted

TS975 E N L 1:2:3 5 6 4 Replace link L-5 onto L-2 only if fitted

TSR/2 E 2&3 L - - - 5 Insert link L-2 on RWB backplate

Eberle All models Contact Siemens 0870 850 0184

Honeywell ST6100A 1001, - N L - 1 2 4 Replace link L-1 onto L-2 only if fitted

ST6100C 1009

ST7000B 1001 E N L - - 2 3 Need to connect Neutral

ST9001 - N L 1 2 3 4 Change backplate

Horstmann 517 E N L - 5 6 4 Replace link L-1 onto L-2 only if fitted

Centaur Plus C11, E N L 1 2 3 4 Replace link L-5 onto L-2 only if fitted

Centaur Plus C17

Centaur Plus H11, E N L - 5 6 4 Replace link L-5 onto L-2 only if fitted

Centaur Plus H17

Centaur SC1, E N L 4 1 2 3 Replace link L-1 onto L-2 only if fitted

Centaur SC7

Channel Plus H11, E N L 1:2:3 5 6 4 Replace link L-5 onto L-2 only if fitted

Channel Plus H17

IFLO 985626 E N L 4 1 2 3 Replace link L-1 onto L-2 only if fitted

33

If the manufacturer or model you are replacing is not listed above, please contact the Siemens helpline on 0870 850 0184.

Siemens RWB27 E N L 1 2 3 4 -

RWB30E E N L 1 2 3 4 -

RWB1001 E N L 1 2 3 4 -

RWB1007 E N L 1 2 3 4 -

Landis & Gyr RWB3 E N L - - 3 4 Insert link between L and 2

RWB7, RWB30, E N L - 2 3 4 Direct replacement

RWB50, RWB100,

RWB152, RWB170,

RWBXT

Myson MEP1C - N L - - 2 4 Replace link L-2 on RWB backplate

Potterton EP4000, EP4001, E N L ABCD 5 2 4 Replace link L-5 onto L-2 only if fitted

EP 4002

EP5000, EP5001 - N L - 5 2 4 Replace link L-5 onto L-2 only if fitted

EP5002 E N L ABCD 2 - 4 Replace link L-5 onto L-2 only if fitted

Miniminder ES E N - 2 3 4 Insert link L-2 on RWB backplate

Salus EP101 - N L 4 1 2 3 Replace link L-4 onto L-2 only if fitted

Sangamo All models Contact Siemens 0870 850 0184

Smiths Industries All models Contact Siemens 0870 850 0184

Sopac All models Contact Siemens 0870 850 0184

Sunvic SP20 E N L - 3 - 5 Replace link L-3 onto L-2 only if fitted

(Satchwell) SP35 E N L - 3 4 5 Replace link L-3 onto L-2 only if fitted

Select 107 - N L - 1 2 3 Replace link L-1 onto L-2 only if fitted

Switchmaster SM300 E N L - 4 - 1 Replace link L-4 onto L-2 only if fitted

SM950 E N L ABC - 2 1 Insert link L-2 on RWB backplate

SM980 - N L - 4 1 1 Replace link L-4 onto L-2 only if fitted

Tower/Grasslin/ 2000C, 2000CQ, E N L - - - 7

Towercron T2001/2001Q

2001C, 2001CQ - N L - 4 - 7

DT71 - N L - 3 2 4 Replace link L-3 onto L-2 only if fitted

Towercron DP71 E N L - - 2 4

Towercron DT71 E N L - 3 2 4 Replace link L-3 onto L-2 only if fitted

Towercron TC E 2 1 - - - 7

Towercron QE1 E N L - 3 2 4 Replace link L-3 onto L-2 only if fitted

Towercron QM1 E N L - 3 2 4 Replace link L-3 onto L-2 only if fitted

Wickes RWB7.cw E N L - 2 3 4 Direct replacement

RWB152.cw E N L - 2 3 4 Direct replacement

34

HW HTG HW HTGMains Off Off On On

Manufacturer Model(s) E N L 1 2 3 4 Wiring

RWB27, RWB30e, RWB1001 & RWB1007 Timeswitches

If the manufacturer or model you are replacing is not listed above, please contact the Siemens helpline on 0870 850 0184.

Siemens RAA21GB L Y1 Y2 - - -

ACL TA350/1 1 3 - - - -TS142 1 2 - L 4 E

ACL Drayton RTS1, RTS/2, RTS 3 L - 3 - N -RTC 3 1 2 L N -RTE 4 1 2 3 - -RTS4/6 1 3 2 L N -

Boss Therm BRT 1 2 3 - - EBRTMKL2 1 2 3 - * -

Danfoss Randall RMT230 1 2 3 - N -

Honeywell T6360B 1 3 - - 2 -T6160B 1 3 4 - 2 -

Horstmann HRT2 1 2 - - 4 -

IFLO 985628 L - 3 - * -

Landis & Gyr RAA02 1 2 3 - - ERAD1 1 2 3 - - ERAD2 1 2 - - N ERAD5R6521 6 2 - - 4 -

Myson MRT1 1 3 2 - 4 -

Pegler (Terrier) TRT 1 3 4 - 2 -

Potterton PRT1, PRT100 L H - - N -

Randall RD3 1 2 - - 4 -

Satchwell or Sunvic TLM2206, TLM 2253 1 3 - - 4 ETLX2259, TLX2284, TLX2357 3 1 - - 4 ETLX2322, TLX2356 3 1 2 - 4 E

Sopac TA350/351 1 3 - - - E

Switchmaster SRT2 1 3 - - - 5

35

Manufacturer Model(s) COM DEM SAT L N E

Room Thermostats

Manufacturer Model(s) COM DEM SAT L N E

Cylinder Thermostats

Siemens RAM1 1 2 3 - - E

ACL Drayton HTS3 C 1 2 - - -

Barlo CT1 RED BLK YEL - - -

Boss Therm BCT 1 2 3 - - E

Danfoss Randall CN4, ATC 1 2 3 - - E

Drayton CS1 1 2 3 - - E

Drayton Pipe Stat PTS1 1 2 4 - - E

Honeywell L641A C 1 2 - - -

Horstmann HCT1 1 2 3 - - E

IFLO 985629 C 1 2 - - -

Landis & Gyr RAM1 1 2 3 - - ERAM2 RED BLK GREY - - -

Potterton PTT100 L H C - - E

Satchwell/Sunvic SA1452, 2451 3 1 2 - - E

Sopac SAY C 1 2 - - E

Switchmaster SCT1 1 2 3 - - E

If the manufacturer or model you are replacing is not listed above, please contact the Siemens helpline on 0870 850 0184.

*= Neutral not required, make safe

Siemens REV13 L L1 L2 - - -

REV11/REV12 L L1 - - - -

REV10 Q1 Q2 - - - -

RDJ10 LX L1 L2 - - -

RDJ10RF LX L1 L2 L N -

RDE100 Q11 Q14 Q12 L N -

RDE100.1 Q11 Q14 Q12 - - -

RDE100.1RFS Q11 Q14 Q12 L N -

ACL Drayton PT271 1 3 2 - - -

Digistat 2/4 1 3 2 - - -

Digistat +2 C ON OFF - - -

Digistat +2RF C 3 2 - - -

Boss Therm BPS242/BPS242RF LX L1 L2 - - -

Danfoss Randall TP2 1 3 2 - - -

TP4 1 3 2 - - -

Honeywell CM61 A B C - - -

CM6901 A B C - - -

Horstmann Centaurstat 1 2 3 - - -

IFLO 263942 C ON OFF - - -

263939 1 3 2 - - -

Sunvic TLX6501 1 2 3 - - -

36

Manufacturer Model(s) COM DEM SAT L N E

Daily programmable thermostat

Programmable Room Thermostats

Manufacturer Model(s) COM DEM SAT L N E

Weekday/weekend programmable thermostat

Manufacturer Model(s) COM DEM SAT L N E

Siemens REV23 L L1 L2 - - -

REV23RF L L1 L2 - - -

REV24 L L1 L2 - - -

REV24RF LX L1 L2 L N -

ACL Drayton Digistat 3 1 3 2 - - -

Digistat RF 3 1 3 2 L N -

Danfoss Randall TP75 3 5 6 - - -

TP700 1 2 3 - - -

TP75RF 2 3 4 L N -

TP7000RF 1 2 3 L N -

Honeywell CM67 A B C - - -

CM67RF A B C L N -

CM901 A B C - - -

Horstmann Centaurstat 7 1 2 3 - - -

If the manufacturer or model you are replacing is not listed above, please contact the Siemens helpline on 0870 850 0184.

Siemens REV17 L L1 L2 - - -

REV21 Q1 Q2 Q3 - - -

REV22 L L1 L2 - - -

REV23 L L1 L2 - - -

ACL Drayton Digistat 3 1 3 2 - - -

ACL Lifestyle CT171 1 3 2 - - -

Danfoss Randall TP3 1 3 2 - - -

TP5 1 3 2 - - -

TP75 3 5 6 - - -

TP5000 B C A - - -

Honeywell CM67 A B C - - -

Horstmann Centaurstat 7 1 2 3 - - -

7 Day programmable thermostat

37

3-Port Mid-Position 22mm and 28mm

Motorised Valves

Siemens/L&S MA-V322

ACL 679H340

Danfoss DMV3M

Drayton Flowshare

Honeywell V4073A

Tower MP3

Landis & Gyr SK3

Potterton PMV3

Randell HSA3

Sunvic SD1701

HOT WATER ON

HOT WATER OFF

HEATING ON

NEUTRAL

EARTH

Orange

Grey

White or Brown

Blue

Green/Yellow

Orange

Grey

White

Blue

Green/Yellow

HOT WATER ON

HOT WATER OFF

HEATING ON

NEUTRAL

EARTH

Orange

Grey

White or Brown

Blue

Green/Yellow

Orange

Grey

White

Blue

Green/Yellow

Flowminder CMV322, CMV328

2-Port Zone22mm and 28mm

ACL 6799H308

Danfoss DMV2C

Honeywell V4043H

Landis & Gyr ZA-V222

Tower MV2

ACL 679H308

Landis & Gyr SK2

Potterton PMV2

Randell HP2

Sunvic SZ1326

PERMANENT LIVE

SWITCHED LIVE

MOTOR OPEN

NEUTRAL

EARTH

Grey

Orange

Brown

Blue

Green/Yellow

Grey

Orange

Brown

Blue

Green/Yellow

PERMANENT LIVE

SWITCHED LIVE

MOTOR OPEN

NEUTRAL

EARTH

Grey

Orange

Brown

Blue

Grey

Orange

Brown

Blue

Green/Yellow

Zoneminder CZV322, CZV328

In the event of motor failure all CMV and CZV products can be replaced without drain down using DVA actuators (see next page)

38

3-Port Mid-Position 22mm and 28mm

Motorised Valves

Switchmaster VB1

HOT WATER ON

HOT WATER OFF

HEATING ON

NEUTRAL

EARTH

RedOrange

White

Yellow

Blue

Green/Yellow

Orange

Grey

White

Blue

Green/Yellow

Flowminder CMV322, CMV328

LINK

Switchmaster valve is not sprung return hence the extra wire (orange) to move the paddle into the hot water ON position.Insert link on junction box between red and orange of old valve and wire orange to orange.

Diverter Valve

Siemens DAV322

ACL 679H314

Danfoss DMV3D

Honeywell V4044C

MOTOR OPEN

NEUTRAL

EARTH

Brown

Blue

Green/Yellow

Grey/White

Blue

Green/Yellow

Flowminder CMV322, CMV328

To replace a diverter valve with a mid-position valve, replace old brown wire with grey and white together and make the orange safe.

MAKE ORANGE SAFE

Replacing Demountable actuators

E

D

Removing actuator

First isolate from electrical mains supply,

disconnect cable from junction box taking note

of position and colour of wires and replace with

new actuator cable (it may be advisable to

replace wire for wire to ensure accuracy), pull

actuator from brass body.

Attaching valve actuator

Engage drive shaft D with actuator E and push

down firmly until spring clips engage fully with

valve body. When all work has been carried out

reconnect electrical supply.

7

Mid-position system, fully pumped

N L 1 2 3 4

N1

L2

E3 4

S/L5 6 7 8 9 10

JB1JunctionBox

Room ThermostatCylinder Thermostat

3AFUSE

N L E

RWB2 Channel Programmer

Mid-Position ValveFLOWMINDER

CMV322/CMV328

Boiler and Pumpconnections

Please refer to note 1.3 Amp Fused Spur

240 volt input

BG/Y

Gr W

O

2 3 1 RAM

Y1 L RAA21

RWB Terminal Configuration1. Off - Hot Water2. Off - Central Heating3. On - Hot Water4. On - Central Heating

Flowminder Colour CodesG/Y = Green/YellowB = BlueO = OrangeGr = GreyW = White

NOTE 1

L

S/L

N

E

P/L onboiler

Live (2)

Switched Live (5)

Neutral (1)

Earth (3)

Pump Live

(5) Boiler Live & Pump Live

(1) Neutral

(3) Earth

Boiler requiringPump overrun

Basic Boiler

MID-POSITION FULLY PUMPED SYSTEM FORBOILERS WITH OR WITHOUT PUMP OVERRUN

For systems up to 8 radiators.

Time and temperature control of CentralHeating and Hot Water.

Selector to 16 programmers.

Possible to have Central Heating only, HotWater only or both together.

39

40

Three Port Valve System CMV32..

NO DEMAND

Only Grey ofmotorised valve islive (PermanentLive).

HOT WATERONLY

DEMAND

Cylinder thermostatfires boiler, defaultof valve is to allowflow to hot water.

HOT WATER ANDCENTRAL HEATING

DEMAND

Motorised valve ismoved to mid-position via White ofmotorised valve,cylinder thermostatcontinues to fireboiler.

CENTRAL HEATING ONLY

DEMAND

Power to Grey andWhite wires ofmotorised valvemoves valve over tocentral heating onlyand Orangebecomes live tocontinue firing ofboiler.

M M

CMV3..

BOILER

PUMP

COM CALL

COM CALL

HWOFF

HWON

PL

RAA

RAMSATISFIED

GREY

WHITE

ORANGE

M M

CMV3..

BOILER

PUMP

COM CALL

COM CALL

HWOFF

HWON

PL

RAA

RAMSATISFIED

GREY

WHITE

ORANGE

M

BOILER

PUMP

COM CALL

COM CALL

HWOFF

HWON

PL

RAA

RAMSATISFIED

GREY

WHITE

ORANGE

M

CMV3..

M

BOILER

PUMP

COM CALL

COM CALL

HWOFF

HWON

PL

RAA

RAMSATISFIED

GREY

WHITE

ORANGE

M

CMV3..

41

Mid-Position system fault finding

The fault finding table enables quick electrical checksto be carried out on installed Mid-Position systems. Itwill help in commissioning and pinpointing the sourceof any electrical problems.

Only suspect faulty components after you havechecked the wiring and you are satisfied that thewiring is correct.

Fault Finding Identification

ProgrammerCheck links are in place (where relevant).Check mains supply to terminal L.

Suspect programmera. After you have checked that the

switching times are correctly set (referto user manual), and the programmertime is set within a switching period.

b. If live does not appear at JB terminal 8when HW only is selected ON, ONCEor ALL DAY

c. If live does not appear at JB terminal10 when CH only is selected ON,ONCE or ALL DAY.

To carry out the following checks setprogrammer HW and CH to 24h, ON orCONTINUOUS.

RAM1 Cylinder ThermostatCheck wiring against relevant wiringdiagram, disconnect mains supply,remove wire from terminals 2 and 3 andmake safe separately. Re-connect supply.Check mains supply is live to terminal 1.

Suspect RAM1a. If terminal 2 is not live when calling

for heat turn thermostat to maximum.b. If terminal 3 is not live when satisfied

turn thermostat to minimum.

Room ThermostatCheck wiring against relevant wiringdiagram, disconnect mains supply,remove wire from terminal Y1 and makesafe, reconnect supply. Check mainssupply to terminal L.

Suspect RAA21a. If terminal Y1 is not live when calling

for heat turn thermostat to maximum.b. If terminal Y2 is not live when satisfied

turn thermostat to minimum.

CMV3.. Mid-Position ValveSuspect valve if, in any of the followingchecks the valve does not operate asdescribed. Switch programmer to ONposition.

Check A Heating OnlyDisconnect mains supply. DisconnectGrey and White wires from JB terminals 6& 9. Connect Grey and White wires to JBterminal 2.

Reconnect mains supply, valve shouldopen to port A. The boiler and pump willfire and the pipe from port A will getprogressively warmer.

Check B Hot Water OnlyDisconnect mains supply. Valve willreturn to open port B and close port A.Disconnect White wire and make safe i.e.use spare JB terminal 7. Connect boilerand pump wire from JB terminal 5 to JBterminal 2. Switch on mains supply. Theboiler and pump will fire and the pipefrom port B will get progressivelywarmer.

Check C Heating and Hot WaterDisconnect mains supply. Remove Greywire from JB terminal 2 and make safe.Connect White wire to JB terminal 2.Switch on mains supply.

The valve will motor to the mid-positionand stop. Both ports A & B are open. Theboiler and pump will fire and the pipesfrom ports A & B will get progressivelywarmer.

Disconnect mains supply. ReconnectWhite wire to JB terminal 9, Grey wire toJB terminal 6 and the boiler and pumplive to JB terminal 5.

42

Programmer settingcentral heating only ON Hot water only ON Central heating and hot water ON

Mid-Position system fault finding table

Systemcomponent

Programmer Live on terminals L, 1 & 4 and Live on terminals L, 2 & 3 and Live on terminals L, 3 & 4 and

RWB2/9/20/29/ junction box terminal 10. junction box terminal 8 junction box terminals 8 & 10

40/200/252/270 (see note 7). (see note 7).

RAM1 Live on terminals 2 & 3. Turn set temperature up to call for Turn set temperature up to call for

Cylinder Terminal 2 only live when valve opens Hot Water. Hot Water.

Thermostat and boiler fires. Live on terminals 1 & 2 and junction Live on terminals 1 & 2 and junction

Live also on junction box terminals box terminals 5 & 8 box terminals 5 & 8

5 & 6. (see notes 2 & 6). (see notes 2 & 6).

RAA21 Turn set temperature up to call Turn set temperature up to call Turn set temperature up to call

Room for heating. for heating. for heating.

Thermostat Live on terminals L & Y1 and junction No live terminals. Live on terminals L & Y1 and junction

box terminals 9 & 10. For junction box terminals box terminals 9 & 10.

(see notes 2 & 5). (see notes 2 & 5).

CMV3.. Live on White, Live on Orange. Live on White & Orange wires.

Mid-Position Grey & Orange wires. Valve opens port B only. Valves move to mid-position.

Valve Valve opens port A only. Junction box terminal 5 live Junction box terminals 5 & 9 live

Junction box terminals 5, 6, (see notes 2 & 6). (see notes 2, 5 & 6).

9 & 10 live (see note 5).

Boiler & Pump Boiler & Pump fired from Orange wire. Boiler & Pump fired from Orange wire. Boiler & Pump fired from Orange wire.

Live on junction box terminal 5. Live on junction box terminal 5. Live on junction box terminal 5.

Mains Input Live on junction box terminal 2. Live on junction box terminal 2. Live on junction box terminal 2.

‘Live’ when referred to above means 240V AC.

Notes

1. Checks to be conducted by a qualified electrician.

2. Low AC voltage may appear on certain wires or terminals due to back feed from CMV3.. valve. If in doubt switch off supply, disconnect Grey or White

wire as appropriate, switch on supply and check again. Alternatively check with a meter with low voltage capacity.

3. Terminals marked E on RAM must be connected to earth, JB terminal 3.

4. Blue wire on CMV3.. must be connected to JB terminal 4 permanent neutral.

5. For this condition the room thermostat RAA.. must be turned up to call for heat.

6. For this condition the cylinder thermostat RAM1 must be turned up to call for heat.

7. If RAM1 cylinder thermostat is satisfied then terminal 1 on programmer RWB will be live.

8. Please ensure all Earths are connected where applicable.

43

7

Zone Control system

N L 1 2 3 4

N1

L2

E3

N4 7 9 10

JB1JunctionBox

Room ThermostatCylinder Thermostat

3AFUSE

N L E

RWB2 Channel Programmer

ZONEMINDERCZV222

ZONEMINDERCZV222

Boiler and Pumpconnections

Please refer to note 1.3 Amp Fused Spur

240 volt input

G/Y

1 2 RAM

Y1 L RAA21

RWB Terminal Configuration1. Off - Hot Water2. Off - Central Heating3. On - Hot Water4. On - Central Heating

Zoneminder Colour CodesG/Y = Green/YellowB = BlueO = OrangeGr = GreyBr = Brown

NOTE 1

L

S/L

N

E

P/L onboiler

Live (2)

Switched Live (5)

Neutral (1)

Earth (3)

Pump Live

(5) Boiler Live & Pump Live

(1) Neutral

(3) Earth

Boiler requiringPump overrun

Basic Boiler

ZONE CONTROL SYSTEM FOR BOILERS WITHOR WITHOUT PUMP OVERRUN

Increased flexibility over mid-position system.

Able to have several CH and HW controlledindependently.

Time and temperature control of CentralHeating and Hot Water.

Possible to have Central Heating only, HotWater only or both together.

G/Y

8S/L5 6

B B

O

O

Gr Gr

Br

Br

44

Two Port Valve System CZV22..

M

M

M

CZV2..

CZV2..

BOILER

PUMPCOM CALL

COM CALL

M

M

M

CZV2..

CZV2..

BOILER

PUMPCOM CALL

COM CALL

RAM

RAD

HW

CW

M

M

M

CZV2..

CZV2..

BOILER

PUMPCOM CALL

COM CALL

RAM

RAD

HW

CW

NO DEMAND

Only Grey ofmotorised valve islive (PermanentLive).

HOT WATERONLY

DEMAND

Cylinder thermostatdrives valve openvia Brown wire ofmotorised valve,micro switch isactivated allowingGrey to switch outon Orange and fireboiler.

HOT WATER ANDCENTRAL HEATING

DEMAND

Cylinder and roomthermostats drivevalves open viaBrown wire ofmotorised valve,micro switches areactivated allowingGrey to switch outon Orange and fireboiler.

45

The fault finding table enables quick electrical checksto be carried out on installed Zone Control systems. Itwill help in commissioning and pinpointing the sourceof any electrical problems.

Only suspect faulty components after you havechecked the wiring and you are satisfied that thewiring is correct.

Fault Finding Identification

ProgrammerCheck links are in place (where relevant).Check mains supply to terminal L.

Suspect programmera. After you have checked that the

switching times are correctly set (referto user manual), and the programmertime is set within a switching period.

b. If live does not appear at JB terminal 7when HW only is selected ON, ONCEor ALL DAY

c. If live does not appear at JB terminal10 when CH only is selected ON,ONCE or ALL DAY.

To carry out the following checks setprogrammer HW and CH to 24h, ON orCONTINUOUS.

RAM1 Cylinder ThermostatCheck wiring against relevant wiringdiagram, disconnect mains supply,remove wire from terminal 2. Re-connect supply.Check mains supply is live to terminal 1.

Suspect RAM1a. If terminal 2 is not live when calling

for heat turn thermostat to maximum.b. If terminal 3 is not live when satisfied

turn thermostat to minimum.

RAA21 Room ThermostatCheck wiring against relevant wiringdiagram, disconnect mains supply,remove wire from terminal Y1. Re-connect supply. Check mains supply is live t o terminal L.

Suspect RAA21a. If terminal Y1 is not live when calling

for heat turn thermostat to maximum.b. If terminal Y2 is not live when satisfied

turn thermostat to minimum.

CZV2.. Zone ValveThis fault finding applies to eitherHeating or Hot Water Zone valves. Checkthat there are no faults on either of thethermostats. Suspect the valve is faultyonly:

1. If the motor fails to run when therelevant thermostat is turned tomaximum. The motor is held in thisposition until the thermostat issatisfied. Turn the thermostatto minimum and the valve will closeunder spring return.

2. If the Orange wire does not becomelive when the actuator is fully opened(the Grey wire should be connected toa permanent live. See note 2).

3. Any auxiliary equipment connected tothe valve i.e. boiler/pump, continues tooperate when the cylinder thermostatand/or room thermostat is satisfied, orthe programmer is in the OFFposition.

Zone Control system fault finding

46

Programmer settingcentral heating only ON Hot water only ON Central heating and hot water ON

Zone Control system fault finding table

Systemcomponent

Programmer Live on both terminals L & 4 and Live on both terminals L & 3 and Live on both terminals L, 3 & 4 and

junction box terminal 10. junction box terminal 7. junction box terminals 7 & 10.

RAM1 No live terminals on cylinder Turn set temperature up to call for Turn set temperature up to call for

Cylinder thermostat. Hot Water. Hot Water.

Thermostat Live on terminals 1 & 2 and junction Live on terminals 1 & 2 and junction

box terminals 7 & 8. box terminals 7 & 8.

RAA21 Turn set temperature up to call No live terminals on room thermostat. Turn set temperature up to call

Room for heating. for heating.

Thermostat Live on terminals L & Y1 and junction Live on terminals L & Y1 and junction

box terminals 9 & 10. box terminals 9 & 10.

CZV2.. Live on Brown, Orange & Grey wires Live on Orange & Grey wires & junction Live on Brown, Orange & Grey wires

Heating Valve and junction box terminals 5, 6 & 9. box terminals 5 & 6 (see note 5). and junction box terminals 5, 6 & 9.

CZV2.. Live on Orange & Grey wires & Live on Brown, Orange & Grey wires Live on Brown, Orange & Grey wires

Hot Water Valve junction box terminals 5 & 6 and junction box terminals 5,6 & 8. and junction box terminals 5, 6 & 8.

(see note 5).

Boiler & Pump Boiler & Pump fired from Orange wire. Boiler & Pump fired from Orange wire. Boiler & Pump fired from Orange wire.

Live on junction box terminal 5. Live on junction box terminal 5. Live on junction box terminal 5.

Mains Input Live on junction box terminals 2 & 6. Live on junction box terminal 2 & 6. Live on junction box terminals 2 & 6.

‘Live’ when referred to above means 240V AC.

Notes

1. Checks to be conducted by a qualified electrician.

2. Grey wire on both heating and hot water valves must be connected to a permanent live – JB terminal 6. Insert link from terminal 2 to terminal 6.

3. Blue wire on both heating and hot water valves must be connected to a permanent neutral – JB terminal 4.

4. Terminals marked E on RAM must be connected to earth – JB terminal 3.

5. Orange wire only becomes live when either 2 port valve has opened.

6. Please ensure all Earths are connected where applicable.

47

Gravity hot water, pumped central heating system

N L 1 2 3 4

1 2 3 4 5 6 7 8 9 10

JB1JunctionBox

ROOMSTAT

3AFUSE

240VINPUT

E N L

PUMP

E N L

BOILER

N L E

RWB BACKPLATE

BASIC SYSTEM, GRAVITY FED HOT WATER

Move selector to 10 programmes.

Cheap installation but inefficient.

No control of HW other than boiler thermostat.

Room thermostat controls pump switching.

48

Gravity system fault finding

Is there L & N onthe backplate

YES

Check fuse.

Switch HW to ON.

Boiler stat live?

YES

Has boiler lit?

YES

Switch CH to ON.

Live on 4?

YES

Live on room stat L & Y2.Turn stat up.

Live on L & Y1.

YES

Pump runs?

YES

Turn room stat down.

Pump stops

NO

Check programmer.NO

Turn up the boiler stat.

Boiler lights?

NO

Check pump.NO

Boiler at fault.NO

YES

Programmer setting Programmer settingcentral heating only ON Central heating and hot water ON

Gravity system fault finding table

Systemcomponent

Programmer Live on terminal L & 3 and junction box terminal 5. Live on terminals L, 3 & 4 and junction box terminals 5 & 10.

RAA21 Room Thermostat No live terminals on room thermostat. Turn set temperature up to call for heating.

Live on terminals L & Y1 and junction box terminals 5, 9 & 10

(see note).

Boiler Live on junction box terminal 5. Live on junction box terminal 5.

Pump Live on junction box terminal 9.

‘Live’ when referred to above means 240V AC.

For technical specifications and further information please refer to our website www.siemens.co.uk/residential-controls

49

Timeswitches for combination boilers

Manufacturer Model Mains Mains Not used Common Off On

Siemens RWB27 N L 1 2 3 4

RWB30E N L 1 2 3 4

RWB1001 N L 1 2 3 4

RWB1007 N L 1 2 3 4

Baxi Maxflow FS N L - 1 - 2

Maxflow WM N L - 1 - 2

Ferroli Optimax 255, 25C, 240V N L - 4 - 5

F23, F24 N L - 3 - 4

Glowworm XTRAFAST 96 N L - *E - *E

XTRAFAST 120 N L - *E - *E

XTRAMAX 24Ci, 30Ci, 35Ci, N L - *E - *E24Cxi, 30Cxi, 38Cxi, 18Si, 30Si(Note remove link E-E)

Halstead Ace, Ace High, Finest, Platinum N L - L1 - L3

Ideal C80, 95FF N L - R1 - R2

Response 80, 100, 120 N L - R1 - R*

Potterton Performance range N L - 1 - 2

Saunier Duval Classic range (Remove link *-*) N L - * - *

Vaillant N L - 3 - 4

Worcester 24, 24i Junior N L - LS - LR

Cdi 24, 28, Si, R25HE, R30HE N L - LS - LR

RWB Timeswitches terminals

Manufacturer Model Mains Mains Not used Common Off On

Boiler terminals *These two terminals are numbered as below by the boiler manufacturer

If boiler you are using is not shown above please refer to the manufacturers instructions

50

Programmable thermostats for combination boilers

Manufacturer Model Common Off On

Siemens REV13 L - L1

REV17 L - L1

REV24 L - L1

RDJ10 Lx - L1

RDD10.1 Q11 - Q14

Baxi Maxflow FS 1 - 2

Maxflow WM 1 - 2

Ferroli Optimax 255, 25C, 240V 4 - 5

F23, F24 3 - 4

Glowworm XTRAFAST 96 *E - *E

XTRAFAST 120 *E - *E

XTRAMAX 24Ci, 30Ci, 35Ci, *E - *E24Cxi, 30Cxi, 38Cxi, 18Si, 30Si(Note remove link E-E)

Halstead Ace, Ace High, Finest, Platinum L1 - L3

Ideal C80, 95FF R1 - R2

Response 80, 100, 120 R1 - R*

Potterton Performance range 1 - 2

Saunier Duval Classic range (Remove link *-*) * - *

Vaillant 3 - 4

Worcester 24, 24i Junior LS - LR

Cdi 24, 28, Si, R25HE, R30HE LS - LR

Programmable thermostat terminals

Manufacturer Model Common* Off On*

Boiler terminals *These two terminals are numbered as below by the boiler manufacturer

If boiler you are using is not shown above please refer to the manufacturers instructions

51

Thermostat terminal numbering

Type Model COM DEM SAT L N E

Standard RAA02.1N 1 2 3 - - E

RAA02.16N (Neon) 1 2 3 - 6 E

RAA10 (Tamperproof) L Y1 Y2 - - -

RAA20 L Y1 Y2 - - -

RAD1F (Frost) 1 2 3 - - E

RAA21 L Y1 Y2

RAA11 (Frost/Tamperproof) L Y1 Y2

Digital Display RDD10 (Mains operated) Q11 Q14 Q12 L N -

RDD10.1 (Battery operated) Q11 Q14 Q12 - - -

RDD100 (Mains operated) Q11 Q14 Q12 L N -

RDD100.1 (Battery operated) Q11 Q14 Q12 - - -

Programmable Analog RAV11 (Battery operated) L L1 L2 - - -

Programmable Digital REV12 L L1 - - - -

REV22 L L1 L2 - - -

REV23 L L1 L2 - - -

REV23RF LX L1 L2 L N -

RDE100 (mains operated) Q11 Q14 Q12 L N -

RDE100.1 (Battery operated) Q11 Q14 Q12 - - -

RDE200.1 (Battery operated) Q11 Q14 Q12 - - -

Daily Programmable REV13 L L1 L2 - - -

RDJ10 LX L1 L2 - - -

RDJ10RF L L1 L2 L N -

Weekday/weekendProgrammable

REV17 L L1 L2 - - -

7 Day Programmable REV24 L L1 L2 - - -

REV24RF LX L1 L2 L N -

Digital RDH10 LX L1 L2 - - -

The information in this document contains general descriptions of technical options available,which do not always have to be present in individual cases. The required features should thereforebe specified in each individual case at the time of closing the contract.

© Siemens plc • Order no. Product Selection Guide V1 • Printed in the UK.

www.siemens.co.uk/residential-controls

Siemens plcBuilding Technologies DivisionSiemens Heating ControlsSir William Siemens SquareFrimleyCamberleySurreyGU16 8QD

Technical helpline: 0870 850 0184

e-mail: [email protected]

Our world is undergoing changes that force us to thinkin new ways: demographic change, urbanisation, globalwarming and resource shortages. Maximum efficiencyhas top priority – and not only where energy is concerned.In addition, we need to increase comfort for the well beingof users. Also, our need for safety and security is constantlygrowing. For our customers, success is defined by howwell they manage these challenges.

Siemens has the answers.