Medium Voltage Equipment Range for Substations
-
8/13/2019 Siemens - Medium Voltage Equipment Range for Substations
2/16
2
-
8/13/2019 Siemens - Medium Voltage Equipment Range for Substations
3/16
3
Today, vacuum as an arc
extinguishing medium pro-
vides the most cost-effective
solution for medium-voltage
circuit-breakers. We have op-
timized the vacuum switching
principle to the extent that it
is superior to conventional
technology in all respects.
The most significant
advantages:
Constant dielectric in a
vacuum, there are no decom-
position products and,
because the vacuum inter-
rupter is hermetically sealed,
there are no environmental
influences on it.
Constant contact resistance
the absence of oxidation in
a vacuum keeps the metal
contact surfaces clean. For
this reason, contact resistance
can be assured to remain low
throughout the service life of
the equipment.
Large total current the rated
normal current can be inter-
rupted up to 30,000 times,
and the short-circuit breaking
current an average of 50
times.
Maintenance-free for life
Throughout its entire service
life, the vacuum interrupter
operates reliably at all times
without any form of mainte-
nance. Wear is minimal,
because for instance vacuum
switching requires no cooling.
The arc voltage is thus ex-
tremely low only 20 to 200 V.And, on account of the short
arcing times of max. 15 ms,
the energy consumption in
the contact gap is very low.
That makes for maximum
availability.
Principle of operation
A metal-vapor arc discharge
is initiated by the current to
be interrupted as the contact
pieces open. Current flows
through this metal-vaporplasma until the next current
zero. The arc extinguishes in
the vicinity of the current zero.
The metal vapor loses its con-
ductivity within a few micro-
seconds this very quickly
re-establishes the dielectric
strength of the contact gap.
Depending on the level of the
breaking current, various
contact shapes and sizes are
used:
Radial magnetic field contacts,
with which the arc burns
diffusely up to about 10 kA.
Higher currents burn across
a contracted arc, which is
rotating on the contacts.
Axial magnetic field contacts,
with which the arc remains
diffuse even with high
current levels up to 80 kA.
Vacuum Switching
Arcing with radial and axialmagnetic field contacts
-
8/13/2019 Siemens - Medium Voltage Equipment Range for Substations
4/16
4
3AH Vacuum Circuit-Breakers
3AH standard circuit-breaker15 kV/40 kA
Five circuit-breaker modelscover all possible applications
3AH1the maintenance-freestandard breaker
3AH2the breaker for highoperating frequencies
3AH3
the breaker for highswitching capacities
3AH4the breaker for very highoperating frequencies
3AH5the breaker for maximumcost-effectiveness
3AH breakers are also availablein single and double-pole form,for example for traction powersupply applications
The five with the three bigadvantages: versatility,
cost-effectiveness andhigh performance
Technical data and product range
Rated Vacuum circuit-breaker (Type)voltage at
Rated short-circuit breaking current1) (Rated short-circuit making current)
kV kA kA kA kA kA kA kA kA kA
13.1 16 20 25 31.5 40 50 63 up to 80
(32.8) (40) (50) (63) (80) (100) (125) (160) (225)
7.2 3AH1 3AH1 3AH1 3AH1 3AH3 3AH3
3AH2 3AH2
12 3AH5 3AH5 3AH5 3AH5 3AH1 3AH1 3AH1 3AH3 3AH3
3AH1 3AH2 3AH2
15 3AH1 3AH1 3AH1 3AH1 3AH3 3AH33AH2 3AH2
17.5 3AH1 3AH5 3AH1 3AH1 3AH1 3AH3 3AH3 3AH38*)
3AH2 3AH2
24 3AH1 3AH1 3AH1 3AH3
3AH5 3AH2 3AH4
36 3AH5 3AH3 3AH3
3AH4 3AH4
800A 800A 800A 800A 800A 800A 1250A 2500A 1250A 1250A 1250A 8000A
to to to to to to 2) to to to to
1250A 1250A 2500A 1250A 2500A 2500A 3150A 3150A 4000A 12000A
Rated normal current
1) DC component 36% (higher values on request)
2) 3150 A for rated voltage 17.5 kV
*) 3 switches in parallel
-
8/13/2019 Siemens - Medium Voltage Equipment Range for Substations
5/16
Rated voltage
Rated power-frequency withstand voltage
Rated lightning impulse withstand voltage
Rated frequency
Rated short-circuit breaking current (max.)
Rated short-circuit making current (max.)
Rated short-time withstand current 3 sec. (max.)
Rated normal current
kV
kV
kV
Hz
kA
kA
kA
A
5
NXACT combines the advan-tages of vacuum circuit-breakers with additionalintegrated functions.
More functions
Disconnector, earthingswitch, operator panel andinterlock are integrated in asingle breaker module. Themodule is supplied pretestedand ready for installation.
Ease of integration
For the system builder, thismeans minimum projectplanning, ease of installationeven with subsequentretrofitting, no more testing,simplified logistics - thesefeatures mean that NXACTis unbeatable, even with theoverall cost of the substation.
Its compact design minimizesinstallation and commission-
ing time.
In operation, NXACT is notablefor the clear layout of itscontrol panel, which is alwaysaccessible at the front of theswitchgear.
NXACT Vacuum Circuit-Breaker Module
NXACT vacuum circuit-breakermodule, 12 kV
Technical data
12
28
75
50/60
25
63
25
1250/2500
-
8/13/2019 Siemens - Medium Voltage Equipment Range for Substations
6/16
6
Components for 3AH Vacuum Circuit-Breakers
Vacuum circuit-breakers areavailable in fixed-mounted aswell as withdrawable form.When they are installed insubstations, isolating con-tacts, as well as fixed matingcontacts and bushings arenecessary. With the appropri-ate components, the 3AHvacuum circuit-breakers canbe upgraded to the status ofswitchgear module.
Components
The following componentscan be ordered for thebreaker:
Isolating contacts
Cup-type bushings with fixedmating contacts
Truck with/or withoutinterlocks
Switchgear modul
Components for 12 kV
Up to 2500A /to 40 kA/1 sec. For 800 mm switchgear panel widthwith 3AH1 - 7.2/12 kV breaker 210 mm pole centre distancewith 3AH5 - 12 kV breaker 210 mm pole centre distance
Components for 24 kV
to 2500A /to 25 kA/1 sec. For 1000 mm switchgear panel widthwith 3AH1 - 24 kV breaker 275 mm pole centre distancewith 3AH5 - 24 kV breaker 275 mm pole centre distance
On request: components for 15 kV
to 2500A /to 40 kA/1 sec. For 800 mm switchgear panel widthwith 3AH1 - 15 kV breaker 210 mm pole centre distancewith 3AH5 - 17.5 kV breaker 210 mm pole centre distance
Components for 36 kV
to 1250A/to 16 kA/ 1 sec. For 1200 mm switchgear panel widthwith 3AH5 - 36 kV breaker 350 mm pole centre distance
Technical data
-
8/13/2019 Siemens - Medium Voltage Equipment Range for Substations
7/16
7
Vacuum Circuit-Breakers for Outdoor Applications
The 3AF01 circuit-breaker isespecially suitable for opera-tion in power supply utilitiesand deals with all switchingduties occurring in distributionsystems up to 36 kV. It con-sists of two modules:The lower module comprisesthe steel structure with theoperating mechanism, and theupper module the cross armwith the circuit-breaker poles.
The vacuum interrupters areaccommodated in porcelainhousings.
Advantages at a glance:
Minimal installation andcommissioning time
Minimal maintenancerequired
Suitable for automaticreclosing
Long electrical andmechanical service life
Technical data
Rated voltage 36 kV
Rated frequency 50/60 Hz
Rated lightning impulse withstand voltage 170 kV
Rated power-frequency withstand voltage 70 kV
Rated short-circuit 25 kAbreaking current
Rated short-circuit 63 kAmaking current
Rated normal current 1600 A
-
8/13/2019 Siemens - Medium Voltage Equipment Range for Substations
8/16
Technical data and product range
Vacuum contactor type 3TL61 3TL65 3TL71 3TL81
Rated normal voltage kV 7.2 12 24 7.2
Rated frequency Hz 50/60
Rated normal current A 450 450 800 400
Switching capacity accordingto utilization categoryAC-4 (cos= 0.35)Rated making current A 4500 4500 4500 4000Rated breaking current A 3600 3600 3600 3200
Mechanical life ofcontactor Switching cycles 3 106 1 106 1 106 1 106
Mechanical life ofvacuum interrupter Switching cycles 2 106 1 106 1 106 0.25 106
Electrical life ofvacuum interrupter(Rated normal current) Switching cycles 1 106 0.5 106 1 106 0.25 106
8
3TL Vacuum Contactors
Vacuum contactors are three-pole contactors for medium-voltage substations withsolenoid-operated mechanismfor high switching frequencyand unlimited closing duration.
They are suitable foroperational switching of AC
devices in indoor systemsand can be used for examplefor the following switchingduties:
Switching three-phasemotors in AC-3 und AC-4mode
Switching transformers
Switching capacitors
Switching ohmic loads(e.g. arc furnaces)
3TL6 vacuum contactor
3TL8 vacuum contactor
The 3TL vacuum contactorsare distinguished by thefollowing features:
Small dimensions
Long electrical life (up to106operating cycles))
Maintenance-free
Optional vertical or horizontalmounting
-
8/13/2019 Siemens - Medium Voltage Equipment Range for Substations
9/16
From 1 kV to 40.5 kV:
Vacuum Interrupters
9
Vacuum interrupters for themedium-voltage range areavailable from Siemens forall applications in the inter-national market from 1 kVto 40.5 kV.
Applications
Vacuum circuit-breakers Vacuum switches Vacuum contactors Transformer tap changersCircuit-breakers for tractionpower supplyAuto-reclosersSpecial applications, forexample in nuclear fusion
Compact designs
Siemens vacuum interruptersprovide very high switchingcapacity in very compactdimensions: For example vac-uum interrupters for 15 kV/40 kA with housing dimen-sions of 125 mm diameter by161 mm length, or for 12 kV/13.1 kA with 68 mm diameterby 115 mm length.
Know-how for specialapplications
If necessary, we are preparedat any time to supplementour standard range by way oftailored, customized con-cepts.
Product range (extract)
Interrupters for vacuum circuit-breakers
Rated voltage 7.2 kV - 40.5 kVRated normal current 630 A - 4000 ARated short-circuit breaking current 12.5 kA - 80 kA
Interrupters for vacuum contactors
Rated voltage 1 kV - 24 kVRated normal current 400 A - 800 A
Vacuum interrruptersin new design
-
8/13/2019 Siemens - Medium Voltage Equipment Range for Substations
10/16
10
3CG Vacuum Switches
The 3CG vacuum switchesare multi-purpose switchesconforming to IEC 60265-1and VDE 0670 Part 301.
With these, all loads can beswitched without any restric-tion and with a high degreeof reliability. The electrical andmechanical data are greaterthan for conventional switch-disconnectors. Moreover, the3CG are maintenance-free.
The vacuum switch is there-fore extremely cost-effective.
3CG switches in combinationwith HV HRC-Fuses complywith IEC 60420 and VDE0670 Part 303, when in-stalled in Siemens switch-gear. Maximum ratings forfuses on requests.
Vacuum switches aresuitable for the followingswitching duties:
Overhead linesCablesTransformers
MotorsCapacitorsSwitching under earthfault conditions
Technical data
Rated voltage kV 7.2 12 15 24
Rated lightning impulsewithstand voltage kV 60 75 95 125
Rated short-circuit making current kA 50 50 50 40Rated short-time current (3s) kA 20 20 20 16
Rated normal current A 800 800 800 800
Rated ring-main breaking current A 800 800 800 800
Rated transformer breaking current A 10 10 10 10
Rated capacitor breaking current A 800 800 800 800
Rated cable-charging breaking current A 63 63 63 63
Rated breaking current forstalled motors A 2500 1600 1250 -
Transfer current according to IEC 60420, 1990Inductive switching capacity (cos 0.15) A 5000 3000 2000 2000
Switching capacity:
under earth fault conditionsRated earth fault breaking current A 630 630 630 630Rated cable-charging breaking currentunder earth fault conditions A 63 63 63 63Rated cable-charging breaking currentunder earth fault conditions withsuperimposed load current A 63+800 63+800 63+800 63+800
Number of switching cycles with rated normal current 10 0 00 10 000 10 000 10 000
3CG switch:12 kV/800 A
-
8/13/2019 Siemens - Medium Voltage Equipment Range for Substations
11/16
11
3CJ1 Switch-Disconnectors
Technical data and product range
Rated voltage kV 12 15 24
Rated short-time withstand current (1s) kA 20 26 18
Rated short-timemaking current kA 50 65 45
Rated normal current A 630 630 630
3CJ1 indoor switch-disconnectors are multi-purpose types and complywith all the relevant stand-ards, both in basic form andin combination with (make-proof) earthing switches.
The 3CJ1 switch-disconnectoris notable for the followingfeatures:
Modular system of straight-forward design with all im-portant attachments, such asfuses, (make-proof) earthingswitches, motor operatingmechanism, shunt releasesand auxiliary switches.
Excellent dielectric proper-ties, even under unfavorableclimatic conditions, by virtueof the exclusive use of stand-ard post insulators for insula-tion against earth.
3CJ1 switch-disconnector,12 kV
-
8/13/2019 Siemens - Medium Voltage Equipment Range for Substations
12/16
12
3D disconnecting and earth-ing switches are suitable forindoor installations up to36 kV.
Disconnecting switches areused mainly to protect per-sonnel working on equip-ment, and must therefore beextremely reliable and safe.This is assured even underdifficult climatic conditions,for example in the event of
occasional moisture conden-sation.
For 12 and 24 kV, make-proofearthing switches with a ratedshort-circuit making currentof 50 or 40 kA have been in-cluded in the range.
3D Disconnecting and Earthing Switches
Technical data
Rated voltage kV 12 24 36
Rated short-time kA 20 20 20withstand current (1s) to to to
63 31.5 31.5
Rated peak withstand kA 50 50 50current to to to
160 80 80
Rated normal current A 630 630 630to to to
3000 2500 3000
3DC disconnecting switch,12 kV
-
8/13/2019 Siemens - Medium Voltage Equipment Range for Substations
13/16
13
3GD HV HRC Fuses
Technical data fuse links
Rated voltage kV 7.2 12 24 36
Rated short-circuit kA 63 40 31.5 31.5breaking to to to
current 80 63 40
Rated normal A 6.3 6.3 6.3 6.3current to to to to
250 160 100 40
Technical data fuse bases
HV HRC (high-voltage high-rupturing capacity) fuses areused for short-circuit protec-tion in high-voltage switch-gear. They protect switchgearand components, such astransformers, motors, capac-itors, voltage transformers andcable feeders, from the dy-namic and thermal effects ofhigh short-circuit currents bybreaking them as they occur.
3GH fuse bases
3GH fuse bases are used toaccommodate HV HRC fuse-
links in switchgear.3GH fuse bases are availableas single-phase and three-phase versions. On request,a switching state indicatorwith auxiliary switch can beinstalled.
Fuse basewith 12 kV fuse
Fuse link
Rated voltage kV 3.6/7.2 12 24 36
Rated peak withstand current kA 44 44 44 44
Rated normal current A 400 400 400 400
-
8/13/2019 Siemens - Medium Voltage Equipment Range for Substations
14/16
14
Insulators: 3FA Post Insulators and
3FH/3FM Bushings
Insulators post insulatorsand bushings are used toinsulate live parts from oneanother and from earth andalso to perform mechanicalcarrying and supporting func-tions.
The materials for insulatorsare various cast resins andporcelains.
Innovative solutions, such as
the 3FA4 divider post insulatorfor capacitive voltage indica-tion, provide optimum cus-tomer benefit.
Special designs are also avail-able on request.
Technical data (extract): 3FA1/2 post insulator
Rated voltage kV 3.6 12 24 36
Rated lightning kV 60 65 100 145impulse withstand to to to tovoltage 65 90 145 190
Rated power- kV 27 35 55 75frequency to to to to
withstand voltage 40 50 75 105
Minimum failing load kN 1.8 5 5 5to to to to16 25 25 16
3FH5/6 draw-lead
bushing
3FA1/2 post insulator
-
8/13/2019 Siemens - Medium Voltage Equipment Range for Substations
15/16
15
Current and Voltage Transformers
Measuring transformers areelectrical devices which trans-form primary electrical varia-bles currents or voltages into proportional, in-phasevariables to ensure that theyare safe for connected equip-ment and operating person-nel.
The product range also in-cludes cast-resin insulatedbushing current transformers
and outdoor current andvoltage transformers.
Technical data and product range block type
Current transformers Voltage transformers
Rated voltage kV 12 24 36 12 24 36
Primary rated current A 10 10 10to to to
2500 2500 2000
Max. thermal ratedshort-time current kA 80 80 80
Sec. thermal limit A 5 5 5current to to to
10 13 17
4MA block currenttransformer
4MS4 outdoor voltagetransformer
-
8/13/2019 Siemens - Medium Voltage Equipment Range for Substations
16/16
Surge Arresters
Surge arresters have thefunction of protecting theinsulation of installations orcomponents from impermis-sible strain due to voltagesurges.
The product range includes:
Surge arresters for theprotection of high-voltagemotors and dry-type trans-formers.
Range 3EF for cable networkup to 15 kV.
Plug-in surge arresters forthe protection of distributionnetworks.Range 3EH2 for networks upto 42 kV.
Special arresters for theprotection of rotary machinesand furnaces.Range 3EE2 for networks upto 42 kV.
Technical data and product range
3EF 3EE2 3EH2
For networks of 3.6 4.5 4.7to to to
15 kV 42 kV 42 kV
Rated discharge 1 kA 10 kA 10 kAsurge current
Short-circuit 1 50 16 kA
current strength to to40 kA 300 kA
Powerto the
Si Akti ll h ft Order No E50 001 U229 A4 X 7600
BereichEnergiebertragung und -verteilungGeschftsgebiet MittelspannungP.O. Box 32 20D-91050 Erlangen
http://www.ev.siemens.de
S bj t t h ith t i ti
3EE2 arrester