1. The SIMATIC S7 System Family 2. The SIMATIC Manager 3. Training Units 4. Hardware Configuration 5. Editing Blocks 6. Binary Operations 7. Digital Operations 8. Symbols 9. Test Functions 10. Data Storage in Data Blocks 11. Functions and Function Blocks 12. Troubleshooting 13. Organization Blocks 14. Analog Value Processing 15. Documenting, Archiving, Saving 16. Communication via MPI 17. Solutions 18. Technical Data and Special Features of the S7-400 19. Totally Integrated Automation 20. What’s Next? Information and Training Automation and Drives SIMATIC S7 Programming 1 Course ST-7PRO1 AL: N ECCN: N Export Regulations AL Number of European resp. German export list. Goods with labels not equal to ”N” are subject to export authorization. ECCN Number of US export list (E xport C ontrol C lassification N umber). Goods with labels not equal to ”N” are subject to re-export authorization for export to certain countries. Indication Goods labeled with ”AL not equal to N” (here: technical documentations) are subject to European or German export authorization when being exported out of the EU. Goods labeled with ”ECCN equal to N” (here: technical documentations) are subject to US re-export authorization. Even without a label, or with label ”AL:N” or ”ECCN:N”, authorization may be required due to the final whereabouts and purpose for which the goods are to be used. Decisive are the export labels stated on order acknowledgements, delivery notes and invoices. This document was produced for training purpose. Siemens assumes no responsibility for its contents. The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable to damages. All rights, including rights created by patent grant or registration of a utility model or design, are reserved. © SIEMENS AG 2005 Name: ___________________________ Course: from ____________ to ____________ Instructor: Infoline Tel: 01805 23 56 11 Fax: 01805 23 56 12 Internet: http://www.ad.siemens.de/training ID-Nr.: Release A5.1 (for STEP7 Version 5.x)

Upload: elhamsa

Post on 16-Oct-2014

882 views

Category:

Documents


14 download

TRANSCRIPT

Page 1: siemensCourse ST-7PRO1

1. The SIMATIC S7 System Family

2. The SIMATIC Manager

3. Training Units

4. Hardware Configuration

5. Editing Blocks

6. Binary Operations

7. Digital Operations

8. Symbols

9. Test Functions

10. Data Storage in Data Blocks

11. Functions and Function Blocks

12. Troubleshooting

13. Organization Blocks

14. Analog Value Processing

15. Documenting, Archiving, Saving

16. Communication via MPI

17. Solutions

18. Technical Data and Special Features of the S7-400

19. Totally Integrated Automation

20. What’s Next?

Information and Training Automation and Drives

SIMATIC S7 Programming 1 Course ST-7PRO1 AL: N ECCN: N

Export Regulations AL Number of European resp. German export list. Goods with labels not equal to ”N” are subject to export authorization. ECCN Number of US export list (Export Control Classification Number). Goods

with labels not equal to ”N” are subject to re-export authorization for export to certain countries.

Indication Goods labeled with ”AL not equal to N” (here: technical documentations) are subject to European or German export authorization when being exported out of the EU.

Goods labeled with ”ECCN equal to N” (here: technical documentations) are subject to US re-export authorization.

Even without a label, or with label ”AL:N” or ”ECCN:N”, authorization may be required due to the final whereabouts and purpose for which the goods are to be used. Decisive are the export labels stated on order acknowledgements, delivery notes and invoices.

This document was produced for training purpose. Siemens assumes no responsibility for its contents. The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable to damages. All rights, including rights created by patent grant or registration of a utility model or design, are reserved. © SIEMENS AG 2005

Name: ___________________________ Course: from ____________ to ____________ Instructor:

Infoline Tel: 01805 23 56 11 Fax: 01805 23 56 12 Internet: http://www.ad.siemens.de/training ID-Nr.: Release A5.1 (for STEP7 Version 5.x)

Page 2: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC S7 System FamilyPage 1

Contents Page

SIMATIC Overview .............................................................................................................................. 2S7-200 ................................................................................................................................................. 3S7-200: Modules ........................................................................................................................... 4S7-200: CPU Design .......................................................................................................................... 5S7-300 ................................................................................................................................................. 6S7-300: Modules ........................................................................................................................... 7S7-300: CPU Design .......................................................................................................................... 8S7-400 ................................................................................................................................................. 9S7-400: Modules ........................................................................................................................... 10S7-400: CPU Design (Part 1) .............................................................................................................. 11S7-400: CPU Design (Part 2) .............................................................................................................. 12Programming Devices........................................................................................................................... 13PG/PC Requirements for Installing STEP 7 ………........................................................................... 14Installing the STEP 7 Software ........................................................................................................... 15Result of Installation ...................................................................................................................... 16

Date: 05.12.2005File: PRO1_01E.1

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

The SIMATIC S7 System Family

SIMATICWinCC

SIMATIC PC

SIMATIC DP

SIMATIC Controller

SIMATIC HMI

SIMATIC NET

SIMATICPCS 7

SIMATIC Software

SIMATIC

Page 3: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC S7 System FamilyPage 2

Date: 05.12.2005File: PRO1_01E.2

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

SIMATIC Overview

SIMATIC Controller

SIEMENS

SIMATIC

SFRUNSTOP

Q0.0Q0.1Q0.2Q0.3Q0.4Q0.5

I0.0I0.1I0.2I0.3I0.4I0.5

I0.6I0.7

S7-200

CPU 212

SIMATIC PGSIMATIC PC

PG 740

SIEMENS

7 8 9

4 5 6

1 2 3

0

.D E F

A B C I N SD E L

S H I F T H E L P

E S C

E N T E R

A C K

S I M A T I C O P 1 7

S H I F T

H E L PK 1 K 5 K 6 K 7 K 8K 2 K 3 K 4

K 9 K 1 0 K 11 K 1 2 K 1 3 K 14 K 1 5 K 1 6

SIMATIC HMI

ASIFM

SV

SIMATIC DP

SIMATIC NET

PROFIBUS-DP

Industrial Ethernet PROFIBUS

MPI - Network SIMATIC NET

Introduction The introduction of electronics has resulted in great changes in industrial control engineering. Together with automated machinery, whose application possibilities were expanded through electronic controls, these changes have also led to new technologies and branches.

Controllers In addition to the energy supply, control elements are required for the operation of machines and processes in almost all areas of manufacturing. It must be possible to initiate, control and monitor the operation of any given machine or process.In the past, control tasks were solved with conventional control technology by individually - that is, dependent on the task - wiring contacts and relays. Today programmable logic controls are largely used to solve automation tasks.

Totally Integrated In order for companies to remain competitive, it is not enough to isolatedlyAutomation automate only individual processing stations or machines. The demand for more

flexibility with higher productivity can only then be fulfilled when the individual machines are integrated in the entire system. The information flow between all components is essential for the functioning of the entire system.Production processes are no longer seen as individual partial processes, but rather as integral components of an entire production process. Also, the entire process is also no longer structured centrally as hierarchical. Now the process is structured as distributed and autonomous individual elements.The total integration of the entire automation environment is today made possible with the help of:• common configuring and programming of individual partial

systems• common data management• common communication between all participating automation components.

Page 4: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC S7 System FamilyPage 3

Features • Modular small control system for the lowest performance range,• Performance-graded range of CPUs,• Extensive selection of modules,• Expandable with up to 7 modules,• Backplane bus integrated in the modules,• Can be networked with - RS 485 communication interface or

- PROFIBUS,• Central PG connection with access to all modules,• No slot restrictions,• Own software,• “Total Package” with power supply, CPU, I/O in one unit,• "Micro PLC" with integrated functions.

Date: 05.12.2005File: PRO1_01E.3

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

S7-200

SIEMENS

SIMATIC S7-200

CPU 214SFRUNSTOP

I1.0I1.1I1.2I1.3I1.4I1.5

I0.0I0.1I0.2I0.3I0.4I0.5I0.6I0.7

Q1.0Q1.1

Q0.0Q0.1Q0.2Q0.3Q0.4Q0.5Q0.6Q0.7

EM 221

DI 8 x DC24V

I.0

I.1

I.2

I.3

I.4

I.5

I.6

I.7

Page 5: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC S7 System FamilyPage 4

Expansion • Digital input modules:Modules (EM) - 24V DC

- 120/230V AC• Digital output modules:

- 24V DC- Relais

• Analog input modules:- Voltage- Current- Resistance- Thermocouple

• Analog output modules:- Voltage- Current

Communications The CP 242-2 can be used to connect the S7-200 as Master to an AS-Interface. Processors (CP) As a result, up to 248 binary elements can be controlled via 31 AS-Interface Slaves.

This significantly increases the number of inputs and outputs for theS7-200.

Accessories Bus connector

Date: 05.12.2005File: PRO1_01E.4

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

S7-200: Modules

EM EM

CP242 - 2

CP

Page 6: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC S7 System FamilyPage 5

Mode Selector For manual mode selection:STOP = Stop mode; the program is not executed.TERM = Program execution, read/write access possible from PG.RUN = Program execution, read-only access possible from PG.

Status Indicators SF = Group error; internal CPU error(LEDs) RUN = Run mode; green

STOP = Stop mode; yellowDP = Distributed I/O ( only CPU 215)

Memory Card Slot for memory card. A memory card saves the program contents in the event of a power outage without the need for a battery.

PPI Connection The programming device / text display or another CPU is connected here.

Date: 05.12.2005File: PRO1_01E.5

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

SIEMENS

SIMATIC

SFRUNSTOP

Q0.0Q0.1Q0.2Q0.3Q0.4Q0.5

I0.0I0.1I0.2I0.3I0.4I0.5

I0.6I0.7

S7-200

CPU 212

Potentiometer

Outputs

Inputs Status Indicators for integrated DI/DO

PPI Connection

Mode SelectorMemory Card

Status Indicators

S7-200: CPU Design

Page 7: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC S7 System FamilyPage 6

Features • Modular small control system for the lowest performance range• Performance-graded range of CPUs• Extensive selection of modules• Expandable with up to 32 modules• Backplane bus integrated in the modules• Can be networked with - Multipoint interface (MPI),

- PROFIBUS or- Industrial Ethernet.

• Central PG connection with access to all modules• No slot restrictions• Configuration and parameter setting with the help of the "HWConfig“ tool.

Date: 05.12.2005File: PRO1_01E.6

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

S7-300

Page 8: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC S7 System FamilyPage 7

Signal Modules • Digital input modules: 24V DC, 120/230V AC(SM) • Digital output modules: 24V DC, Relay

• Analog input modules: Voltage, current, resistance, thermocouple

• Analog output modules: Voltage, current

Interface Modules The IM360/IM361 and IM365 make multi-tier configurations possible.(IM) They loop the bus through from one tier to the next.

Dummy Modules The DM 370 dummy module reserves a slot for a signal module whose parameters(DM) have not yet been assigned. It can also be used, for example, to reserve a slot for

installation of an interface module at a later date.

Function Modules Perform “special functions": (FM) - Counting

- Positioning- Closed-loop control.

Communication Provide the following networking facilities:Processors (CP) - Point-to-Point connections

- PROFIBUS- Industrial Ethernet.

Accessories Bus connectors and front connectors

Date: 05.12.2005File: PRO1_01E.7

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

S7-300: Modules

PS(optional)

CPU IM(optional)

SM:DI

SM:DO

SM:AI

SM:AO

FM:- Couting- Positioning- Closed-loop

control

CP:- Point-to-Point- PROFIBUS- Industrial Ethernet

Page 9: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC S7 System FamilyPage 8

Mode Selector MRES = Modul Reset functionSTOP = Stop mode; the program is not executed.RUN = Program execution, read-only access possible from PG.RUN-P = Program execution, read/write access possible from PG.

Status Indicators SF = Group error; internal CPU fault or fault in module with diagnostics(LEDs) capability.

BATF = Battery fault; Battery empty or non-existent.DC5V = Internal 5 V DC voltage indicator.FRCE = FORCE; indicates that at least one input or output is forced.RUN = Flashes when the CPU is starting up, shows a steady light in Run

mode.STOP = Shows a steady light in Stop mode.

Flashes slowly for a memory reset request, Flashes quickly when a memory reset is being carried out,Flashes slowly when a memory reset is necessary because a

memory card has been inserted.

Memory Card A slot is provided for a memory card. The memory card saves the program contents inthe event of a power outage without the need for a battery.

Battery Compartment There is a receptacle for a lithium battery under the cover. The battery provides backup power to save the contents of the RAM in the event of a power outage.

MPI Connection Connection for a programming device or other device with an MPI interface.

DP Interface Interface for direct connection of distributed I/Os to the CPU.

Date: 05.12.2005File: PRO1_01E.8

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

CPU314SIEMENS

SFBATFDC5VFRCERUNSTOP

RUN-PRUNSTOPM RES

SIMATICS7-300

Batterie MPI

CPU315-2 DPSIEMENS

RUN-PRUNSTOPM RES

SIMATICS7-300

Batterie DP

SFBATFDC5VFRCERUNSTOP

MPI

SF DPBUSF

S7-300: CPU Design

Page 10: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC S7 System FamilyPage 9

Features • The Power PLC for the mid to upper performance range,• Performance-graded range of CPUs,• Extensive selection of modules,• Can be expanded by over 300 modules,• Backplane bus integrated in the modules,• Can be networked with - Multipoint interface (MPI),

- PROFIBUS or- Industrial Ethernet,

• Central PG connection with access to all modules,• No slot restrictions,• Configuration and parameter setting with the help of the "HWConfig“ tool,• Multicomputing (up to 4 CPUs can be used in the central rack ).

Date: 05.12.2005File: PRO1_01E.9

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

S7-400

Page 11: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC S7 System FamilyPage 10

Signal Modules • Digital input modules: 24V DC, 120/230V AC(SM) • Digital output modules: 24V DC, Relay

• Analog input modules: Voltage, current, resistance, thermocouple• Analog output modules: Voltage, current.

Interface Modules The IM460, IM461, IM463, IM467 interface modules provide the connection(IM) between various racks:

• UR1 (Universal Rack) with up to 18 modules• UR2 (Universal Rack) with up to 9 modules • ER1 (Extension Rack) with up to 18 modules • ER2 (Extension Rack) with up to 9 modules.

Function Modules Perform “special functions":(FM) • Counting

• Positioning• Closed-loop control.

Communication Provide the following networking facilities:Processors (CP) • Point-to-Point connections

• PROFIBUS• Industrial Ethernet.

Date: 05.12.2005File: PRO1_01E.10

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

S7-400: Modules

PS CPU SM:DI

SM:DO

SM:AI

SM:AO

CP FM SM IM

Page 12: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC S7 System FamilyPage 11

Mode Selector MRES = Modul RESetSTOP = STOP mode, i.e. no program execution and

output disabled ( "OD“ mode= Output Disabled). RUN = Program execution, read-only access possible from PG.RUN-P = Program execution, read/write access possible from PG.

Start-up Type Switch CRST = When you start the CPU with the mode selector STOP / RUN,a “complete restart" is performed (Cold ReSTart).

WRST = When you start the CPU with the mode selector STOP / RUN, a “restart" is performed (Warm ReSTart) The CPU requests the start-up type via the Status LED (selectable with the CRST/WRST switch).

Date: 05.12.2005File: PRO1_01E.11

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

S7-400: CPU Design (Part 1)

EXT.-BATT.

5...15V DC

X3

X1

414 - 2XG00 - 0AB0

CPU 414-2X 2 3 4

INTFEXTF

STOPRUN

CRSTFRCE

CRSTWRST

RUN-PRUN

STOPCMRES

INTFEXTFBUSF

DP

EXT.-BATT.

5...15V DC

X1

421 - 1BL00 - 0AA0

DI 32xDC24VX 2 3 4

INTFEXTF

STOPRUN

CRSTFRCE

CRSTWRST

RUN-PRUN

STOPCMRES

Start-up Type Switch

Mode Selector

e.g. CPU412-1 e.g. CPU416-2DP

* for further CPUs please see catalog

Page 13: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC S7 System FamilyPage 12

EXT-BATT Additional external battery voltage supply (DC 5...15V to backup the RAM, e.g. when the power supply is being replaced).

MPI Connection For the programming device or another device with MPI interface.

DP Interface The 413-2DP, 414-2DP, 416-2DP and 417-2DP CPUs have an integrated DP interface for direct connection of distributed I/Os to the CPU.

Slot for In the S7-400 CPUs you can, depending on your requirements, insert RAM orMemory Cards Flash EPROM cards as external load memory:

• RAM cards with a capacity of: 64KByte, 256KByte, 1MByte, 2MByte.The contents are backed up via the CPU battery.

• Flash EPROM cards with a capacity of:64KByte, 256KByte, 1MByte, 2MByte, 4MByte, 8MByte, 16MByte.The contents are backed up on the integrated EEPROMs.

Date: 05.12.2005File: PRO1_01E.12

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

S7-400: CPU Design (Part 2)

EXT.-BATT.

5...15V DC

X3

X1

414 - 2XG00 - 0AB0

CPU 414-2X 2 3 4

INTFEXTF

STOPRUN

CRSTFRCE

CRSTWRST

RUN-PRUN

STOPCMRES

INTFEXTFBUSF

DP

EXT.-BATT.

5...15V DC

X1

421 - 1BL00 - 0AA0

DI 32xDC24VX 2 3 4

INTFEXTF

STOPRUN

CRSTFRCE

CRSTWRST

RUN-PRUN

STOPCMRES

Fault LEDs for general CPU faults

Slot for Memory Card

MPI interface

External battery supply

Fault LEDs for integrated DP interface

DP interface

Page 14: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC S7 System FamilyPage 13

PG 720 is an industry-standard programming device, powerful and easy to use, especially for maintenance and service, but also for programming and configuration - the ideal tool for shopfloor applications.Features:• Measurements in Notebook format,• Independent of power supply,• AT-compatible,• Powerful hardware,• Equipped with all necessary SIMATIC interface ports.

PG 740 is a portable programming device, ideal for all applications in an automation project, as wellas being an extremely powerful, industry-standard PC.Features:• High-level system performance,• Excellent expansion facilities,• TFT- Farbdisplay,• Highly rugged design,• Equipped with all the necessary SIMATIC interface ports.

PG 760 is a multi-functional desktop programming device for all configuring and programming tasks in the engineering office.Its high-level system performance, flexible expansion capability and comprehensive facilities make it the ideal office tool for all automation projects.

Note A hand-held programming device is also available for programming the S7-200 in STL(PG702 = approx. 230 grams, 144 x 72 x 27mm, 2 x 20-character LC display).

Date: 05.12.2005File: PRO1_01E.13

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Programming Devices

PG720

PG740

PG760

Page 15: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC S7 System FamilyPage 14

Requirements New PGs of the SIMATIC S7 series provide the optimum conditions for the STEP 7software. An MPI card can be installed in PCs which meet the requirements listed above, or they can be connected to the COM interface with the PC-Adapter.

MPI Multi-Point Interface.

Date: 05.12.2005File: PRO1_01E.14

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Hardware/Software Requirements

• Processor 80 486 or higher, Pentium recommended

• Hard Disk (free) Min. 300 MB (for Windows, Swap File, STEP7, Projects)

• RAM >= 32 MB, 64 MB recommended

• Interfaces CP 5611 or MPI card or PC-AdapterProgramming Adapter for Memory Card

• Mouse Yes

• Operating System Windows 95/98/NT

PG/PC Requirements for Installing STEP 7

Page 16: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC S7 System FamilyPage 15

Installation 1. Activate “Setup.exe” by selecting “Add/Remove Programs” in the “Win95->Control Panel”.

2. Choose Options. 3. Choose Language.4. Authorization disk when prompted. 5. Re-boot when prompted.

Notes: 1. As of STEP 7 V4.0, the software is only available on CD-ROM.2. Software Service Packs can also be downloaded from

the Internet.

Software Protection The STEP 7 software is copy-protected and can only be used on one programming device at a time.When you have installed the software, you cannot start using it until you have transferred the authorization to the hard disk from the authorization disk.

Note As of STEP 7 V5.0, the software can also be started without authorization. After aspecific time period has run out, the user will be requested to install an authorization.

Be sure to read the notes in the README.TXT file on the authorizaiton disk. If you donot observe these instructions, you risk losing your authorization.

Service Packs Free-of-ChargeSoftware Service Packs can be downloaded from the Internet via http://www.ad.siemens.de/simatic-cs.

Date: 05.12.2005File: PRO1_01E.15

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

PG 740

SIEMENS

Installing the STEP 7 Software

or

Page 17: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC S7 System FamilyPage 16

Introduction The main tool in STEP 7 is the SIMATIC Manager. There are two ways in which to activate it:

1. via Task bar -> Start -> SIMATIC -> STEP7 -> SIMATIC Manager

2. via the icon "SIMATIC Manager“.

Date: 05.12.2005File: PRO1_01E.16

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Result of Installation

Double-click on Icon

Activate via Start menu

Page 18: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC ManagerPage 1

Contents Page

From Process to Project ...................................................................................................................... 2STEP 7 Tools ……............................................................................................................................... 3Starting the SIMATIC Manager ........................................................................................................... 4SIMATIC Manager Menus and Toolbars ............................................................................................. 5The Toolbar in the SIMATIC Manager ............................................................................................... 6STEP 7 Project Structure ……………….............................................................................................. 7Offline/Online View in the SIMATIC Manager ..................................................................................... 8Storage Location for Projects .............................................................................................................. 9Creating a Project …........................................................................................................................... 10Inserting an S7 Program …................................................................................................................. 11Inserting an S7 Block ……................................................................................................................... 12STEP 7- Help System …..................................................................................................................... 13Context Sensitive Help in STEP 7........................................................................................................ 14Standard Libraries ............................................................................................................................... 15Exercise: Creating a Project ................................................................................................................ 16Exercise: Inserting an S7 Program ...................................................................................................... 17Exercise: Inserting an S7 Block ........................................................................................................... 18Exercise: CPU Memory Reset ............................................................................................................. 19

Date: 05.12.2005File: PRO1_02E.1

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

The SIMATIC Manager

Page 19: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC ManagerPage 2

Date: 05.12.2005File: PRO1_02E.2

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

From Process to Project

FB21

Hardware

Software

Project Management

Process

OB1

SIMATIC Manager

I1.0 I1.1 Q4.0

Process When you take a closer look at a process you want to automate, you will find that it is made up of a multitude of smaller sections and sub-processes, which are all interlinkedand dependent on one another.The first task is therefore to break down the automation process as a whole into separate sub-tasks.

Hardware and Each sub-task defines certain hardware and software requirements which mustSoftware be fulfilled by the automation system:

• Hardware:- Number and type of inputs and outputs- Number and type of modules- Number of racks- Capacity and type of CPU - HMI systems- Networking systems

• Software:- Program structure- Data management for the automation process- Configuration data- Communication data- Program and project documentation.

Project In SIMATIC S7 all the hardware and software requirements of an automation process are managed within a project. A project includes the necessary hardware (+ configuration), network (+ configuration), all the programs and the entire data management for an automation solution.

Page 20: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC ManagerPage 3

Date: 05.12.2005File: PRO1_02E.3

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

STEP 7 Tools

SIMATIC Manager The SIMATIC Manager manages the STEP 7 projects. It is the main program and also appears on the WINDOWS 95 desktop.

Notes "STEP 7 - Readme" provides detailed information about the version, installation procedure, etc.

LAD, STL, FBD Tool for writing STEP 7 user programs in the “Ladder Diagram", “Statement List" or"Function Block Diagram“ programming languages.

Memory Card You can save your user programs on EPROM cards by either using the Parameter programming device or an external prommer.Assignment. Different drivers are required, depending on the application.

Configuring Network configuration is discussed in the chapter on “Communication“.Networks

Setting the PG-PC This tool is used for setting the local node address, the transmission speedInterface and the highest node address in the MPI network.

PID Control The basic STEP 7 software package also includes blocks for solving PIDParameter (closed-loop) control problems. You choose "PID Control ParameterAssignment Assignment" to start the program for assigning parameters to the closed-loop control

blocks.

Converting S5 Files STEP5 programs can be converted into the corresponding STEP 7 programs with the help of the S5/S7 converter.

Configure SIMATIC This option provides facilities for configuring multi-user systems.Workspace

Converting TI Files SIMATIC TI programs can be converted into the corresponding STEP 7 program with the help of the TI/S7 converter.

Page 21: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC ManagerPage 4

Date: 05.12.2005File: PRO1_02E.4

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Starting the SIMATIC Manager

or

Introduction The SIMATIC Manager is a graphic user-interface for online/offline editing of S7 objects(projects, user program files, blocks, hardware stations and tools).With the SIMATIC Manager you can:

• manage projects and libraries,• activate STEP 7 tools,• access the PLC online,• edit memory cards.

Starting the There is an icon "SIMATIC Manager" on the Windows 95 desktop and aSIMATIC Manager "SIMATIC Manager" program item under SIMATIC in the Start menu.

You activate the program just like all other Windows 95 applications by double-clicking on the icon or via the Start menu

START -> SIMATIC ->

User-interface After installation, the main tool is available as an icon on the Windows 95 desktop. TheSIMATIC Manager manages the S7 objects such as projects and user programs.By opening an object, the associated tool for editing is started. A double-click on a program block starts the Program Editor and a block can be edited (object-oriented start)

Note You can always obtain online help for the current window by pressing the F1 function key.

Page 22: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC ManagerPage 5

Date: 05.12.2005File: PRO1_02E.5

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

SIMATIC Manager Menus and Toolbars

Titlebar

Menubar

Toolbar

Statusbar

Taskbar

Titlebar The titlebar contains the window title and the buttons for controlling the window.

Menubar Contains all the menus available for the current window.

Toolbar Contains the most frequently used tasks as symbols. These symbols are self-explanatory.

Statusbar Displays the current status and further information.

Taskbar The taskbar contains all open applications and windows as buttons.The taskbar can be positioned on either side of the screen by using the right mouse button.

Page 23: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC ManagerPage 6

Date: 05.12.2005File: PRO1_02E.6

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

The Toolbar in the SIMATIC Manager

Windows 95 Symbols STEP 7 Symbols

Display Accessible Nodes

S7 Memory Card

Download (to the PLC)

Define Filter

Activate Filter

Simulate Modules (S7-PLCSIM)

Page 24: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC ManagerPage 7

Date: 05.12.2005File: PRO1_02E.7

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

STEP 7 Project Structure

Project Structure Data is stored in a project in the form of objects. The objects in a project are arranged in a tree structure (project hierarchy). The tree structure displayed in the project window is similar to that in the Windows 95 Explorer. Only the icons for the objects are different.

Project Hierarchy 1st. Level: The first level contains the project icon. Each project represents adatabase where all the data relevant to the project is stored.

2nd. Level: • Stations (e.g. S7-300 Station) are where information about the hardware configuration and parameter assignment data

of modules is stored. Stations are the starting point for configuring the hardware.

• S7 Program folders are the starting point for writing programs. All the software for a parameter-assignable

module from the S7 range is stored in an S7 Program folder. This contains further folders for the blocks and source files of the program.

• Subnets (MPI,Profibus, Industrial Ethernet) are part of an overall network.

3rd. and subsequent levels: Depends on the object type of the next-higher level.

Page 25: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC ManagerPage 8

Date: 05.12.2005File: PRO1_02E.8

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Offline / Online View in the SIMATIC Manager

Offline The offline view displays the project structure stored on the hard disk of the programming device. It displays this in the project window of the SIMATIC Manager.The "S7 Program“ folder contains the objects “Source Files" and "Blocks".The "Blocks" folder contains the system data created with HWConfig and the blocks created with the LAD/STL/FBD Editor.

Online The online view displays the project structure stored in the CPU. It displays this in the project window of the SIMATIC Manager.The "S7 Program" folder only contains the object "Blocks".The "Blocks" folder contains:• system data blocks (SDB)• user blocks (OB, FC, FB)• system-own blocks (SFC, SFB).

Switch-over Switching between offline and online view takes place:• via the menu items View -> Offline or View -> Online or• with the corresponding symbol in the toolbar:

Online

Offline.

Page 26: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC ManagerPage 9

Date: 05.12.2005File: PRO1_02E.9

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Storage Location for Projects

Menu Options SIMATIC Manager -> Options -> Customize

“Language" Tab • Language: You can select the language you want to use for the SIMATICManager, menus, dialog boxes, help, etc.Only the languages that have been installed appear in the list.

• Mnemonics: You can select the mnemonics you want to use for programming the S7 blocks.

"General" Tab Basic settings for editing projects and libraries:• Storage location for projects is where you specify the directory in which you want to store your user projects.• Storage location for libraries is where you specifiy the directory in which you want to store your user libraries.• Further options for inserting objects, opening projects and for window

arrangement will be dealt with later.• Deactivated system messages

By pressing the button “Activate“ you can reactivate all system messages that were switched-off in a window when the option “Always display this message….“was chosen.

"View" Tab This is where you specify what is to appear in the online display.

"Columns" Tab This is where you specify which columns are to be displayed when the Detail view is switched-on (see “Help“).

"Archive" Tab The archiving of projects will be discussed in the Chapter “Documenting, Saving, Archiving“.

Page 27: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC ManagerPage 10

Date: 05.12.2005File: PRO1_02E.10

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Creating a Project

Enter project name hereand confirm with "OK"

Creating a Project Select the menu options File -> New or the symbol in the toolbar to open the "New" dialog box for creating a new project or a new library.Enter the project name in the "Name" box and confirm by clicking the "OK“ button.

Notes 1. The “Storage location (path)“ displays the path that was preset in the SIMATIC Manager under Options -> Customize.

2. As of STEP 7 V3.2, there is the 'New Project‘ Wizard to help you create a new project.

Page 28: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC ManagerPage 11

Date: 05.12.2005File: PRO1_02E.11

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Inserting an S7 Program

Inserting a Program Select the menu options Insert -> Program -> S7 Program to insert a new program into the current project.When you insert an object, the system automatically gives it a relevant name, e.g. "S7 Program(1)". You can then change this name if you like.

Note You use the method described above to create a hardware-independent program.Programs assigned to particular hardware are dealt with in the Chapter "Hardware Configuration".

Page 29: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC ManagerPage 12

Date: 05.12.2005File: PRO1_02E.12

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Inserting an S7 Block

Inserting a Block Select the menu options Insert -> S7 Block to display a list of block types:• Organization blocks (OB) are called by the operating system.

They form the interface between operating system and user program.

• Functions (FC) and function blocks (FB) contain the actual user program. They enable a complex program to be divided into small, easy-to-follow units.

• Data blocks contain user data.

After you have chosen the type of block you want, the "Properties" dialog box opens so that you can enter the block number and the programming language you want to use (LAD, STL or FBD).There are other settings you can make, depending on the type of block, but these will be discussed later. When you have made your settings and confirmed them by clicking the "OK" button, the new block is inserted in the current program.

Page 30: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC ManagerPage 13

Date: 05.12.2005File: PRO1_02E.13

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

STEP 7 Help System

Obtaining Help There are various ways of obtaining help:1. The general help is activated via the menu options Help - > Contents.2. The context-sensitive help can be started with the F1 function key or via the

symbol in the toolbar.

Tabs • “Contents" - Displays a list of help topics under general headings.• "Index" - Allows you to access the help information by displaying a list

of terms available in alphabetical order.• “Find" - Enables you to look for certain words or expressions in the

help topics.

Hot words Certain words are hi-lighted in green and are underlined with a broken line in the help texts (so-called "Hot words"). A mouse click on these "Hot words" leads to a further help text with detailed information.

Page 31: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC ManagerPage 14

Date: 05.12.2005File: PRO1_02E.14

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Context-Sensitive Help in STEP 7

Context-Sensitive The context-sensitive help gives application-specific information about hi-lighted objects, blocks, menu commands, dialogs etc.You can jump from the context-sensitive help to the general help via the button "Help on STEP 7".

Note You can find additional information on STEP 7 in the electronic manuals. These can be opened when you choose the menu options Start -> Simatic -> S7 Manuals .

Page 32: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC ManagerPage 15

Date: 05.12.2005File: PRO1_02E.15

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Standard Libraries

Introduction Libraries are used to store blocks without project assignment. These blocks can be created in the library, can be copied into and out of it, but cannot be tested. The library structure is set up as hierarchical just as the project structure.

Standard STEP 7 contains a Standard Library, that was stored in the STEP 7 SoftwareLibrary folder e.g. C:\Siemens\Step7\S7libs\stlib30 after STEP 7 was installed. You can access

these standard blocks from the SIMATIC-Manager with “Open->Libraries".

Communication FCs for communication between the CPU and the distributed I/O viaBlocks communication processors with S7-300.

Organization Blocks Organization blocks (OBs).

S5-S7 Converting Blocks for converting STEP 5 programs.Blocks

TI-S7 Converting Generally usable standard functions such as analog value scalingBlocks

IEC Function Blocks for IEC functions (IEC: International Electrotechnical Commission),Blocks such as for processing time and date, for comparison operations, for string processing

and for selecting maximum and minimum.

PID Control Blocks Function blocks (FBs) for PID closed-loop controls.

System Function System functions (SFCs) and System function blocks (SFBs).Blocks

Note Additional libraries are added when option software are installed.

Page 33: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC ManagerPage 16

Date: 05.12.2005File: PRO1_02E.16

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Creating a Project

Enter project name here and confirmwith "OK"

Remember! A project contains all the programs and data for the entire automation task. It can contain one or more programs which can be used in one or more CPUs.

Goal To delete an existing project and create a new one.

What to Do 1. Open the SIMATIC-Manager.2. Select the menu options File -> Delete -> Projects.3. Select “My Project“ from the list of projects and confirm with OK.4. After the project has been deleted, select the menu options

File -> New -> New Project.5. In the box provided enter the project name "My Project".

Page 34: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC ManagerPage 17

Date: 05.12.2005File: PRO1_02E.17

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Inserting an S7 Program

Remember! An S7 program is a combination of program blocks, data blocks, comments andsymbols which are all connected with an application. When you create a program you create a structure that includes all these program sections.

What to Do 1. In the project "My Project“, select the menu options Insert -> Program -> S7 Program.or (instead of point 1.):

1a.Click the right mouse button. In the menu that appears, select the options Insert New Object -> S7 Program to insert a new program.2. A new S7 program with the name "S7 Program 1“ is created.3. Change the name of the program to “My Program“.4. In the “My Program“ folder you will find the S7 program itself with the objects:

Blocks (user program), Source Files (source programs) and Symbols(symbol table).

Results A new S7 program is created within the project "My Project“. In the SIMATIC Manager you can see the subdirectory “My Program“ in the directory"My Project".An empty OB1 block is automatically created in the user program:

Page 35: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC ManagerPage 18

Date: 05.12.2005File: PRO1_02E.18

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Inserting an S7 Block

Remember! In simple terms, a block in a CPU is a program section that has a particular function and a particular structure. Block OB1 is called cyclically by the operating system and provides access to the S7 program. It can contain both program statements and calls to other blocks.

Goal Inserting an empty block (FC1).

What to Do 1. Select the user program (Blocks) in which you want to create the new block.2. Select the menu options Insert -> S7 Block ->Function.

or (instead of point 2.)2a.Click the right mouse button. In the menu that appears, select the options Insert New Object -> Function to insert a new function.3. Enter the block number in the “Name" box (in this case: FC1), and enter the programming language you want to use (LAD/STL/FBD) in the “Language”box. 4. Enter any additional information, such as Author etc., if required.5. Check all entries and confirm with OK.

Result You have created a new, empty block called FC1.

Page 36: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1The SIMATIC ManagerPage 19

Date: 05.12.2005File: PRO1_02E.19

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: CPU Memory Reset

Manual

RequestMemoryReset

PerformMemoryReset

1. Mode selectorin “STOP” position

2. Hold mode selectorin “MRES” positionuntil the “STOP”LED flashestwice (slowly)

3. Release mode selector (returnsautomatically to the“STOP” position)

1. Hold mode selectorin “MRES” position(“STOP” LED flashesquickly)

2. Release modeselector (returnsautomatically to the“STOP” position)

From the PG

1. Mode selectorin “RUN-P” position

2. Menu options:PLC -> OperatingMode -> Stop

3. Menu options:PLC -> Clear/Reset

1. Confirm MemoryReset by clicking the “OK” button

After inserting a Memory Card

1. Mode selectorin “STOP” position

2. Insert Memory Card

3. “STOP” LED flashesslowly

1. Hold mode selectorin “MRES” position(“STOP” LED flashesquickly)

2. Release modeselector (returnsautomatically to the “STOP” position)

General Before you download the user program to the S7 PLC, you should reset the CPUmemory to make sure there are no “old” blocks left in the CPU.The following takes place during a memory reset:• All user data are erased

(with the exception of the MPI parameter assignment).• Hardware test and initialization• If an EPROM memory card is inserted, the CPU copies the contents of the

EPROM back into the internal RAM after memory reset.• If no memory card is inserted, the set MPI address is retained. If, however, a

memory card is inserted, the MPI address entered on the card is loaded.• The contents of the diagnostic buffer (can be viewed on the PG) are

retained.

Note The CPU must be in the STOP mode for a memory reset:• Mode selector in “STOP” or• Mode selector in “RUN-P” and mode changed to STOP by selecting the menu options PLC -> Operating Mode -> Stop.

Exercise Perform a memory reset of the CPU (with the keyswitch or from the PG).You can check if the memory reset was performed successfully by checking the contents of the block folder in the Online view. Only system blocks (SDB, SFC and SFB) should now exist.

Page 37: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Training UnitsPage 1

Contents Page

Setup of a Training Area with S7-300 ……………………..................................................................... 2Configuration of the Training Unit S7-300 ............................................................................................ 3Setup of a Training Area with S7-400 ……………................................................................................ 4Configuration of the Training Unit S7-400 …......................................................................................... 5The Simulator ………........................................................................................................................... 6The Conveyor Model …….................................................................................................................... 7

Date: 05.12.2005File: PRO1_03E.1

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Training Units

V

Page 38: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Training UnitsPage 2

Date: 05.12.2005File: PRO1_03E.2

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Setup of a Training Area with S7-300

Contents of the The training kit consists of the following components:Training Kit • An S7-300 programmable logic controller with CPU 314 or CPU 315-DP

• Digital input and output modules, analog modules• Simulator with digital and analog sections• Conveyor model

Note:It is quite possible that your training area is not equipped with the conveyor model shown in the slide above, but rather with the conveyor model pictured below.

Page 39: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Training UnitsPage 3

Date: 05.12.2005File: PRO1_03E.3

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Configuration of the S7-300 Training Unit

PS1

CPU2

DI 1640

DI 1654

DO 1668

DO 16712

DI 16816

DO 169

20

AI/AO410

352

Module -->Slot No. -->I/O Address -->

Version A(16 channelI/O modules)

PS1

CPU2

DI 3240

DO 3254

DI8/DO868

AI 27

304

Module -->Slot No. -->I/O Address -->

Version B(32 channelI/O modules)

Configuration The programmable controller is configured with the following modules:of Version A Slot 1: Power Supply 24V/5A

Slot 2: CPU 314 or CPU 315-2 DPSlot 4: Digital input 16x24V Inputs from the simulatorSlot 5: Digital input 16x24V Pushwheel buttonsSlot 6: Digital output 16x24V 0.5A Outputs from the simulatorSlot 7: Digital output 16x24V 0.5A Digital displaySlot 8: Digital input 16x24V Conveyor model inputsSlot 9: Digital output 16x24V 0.5A Conveyor model outputsSlot 10: Analog module 4 AI/4 AO Adjustable from the simulator

Configuration The programmable controller is configured with the following modules:of Version B Slot 1: Power Supply 24V/5A

Slot 2: CPU 314 or CPU 315-2 DP Slot 4: Digital input 32x24V Inputs from the simulator

and pushwheel buttonsSlot 5: Digital output 32x24V/0.5A Outputs from the simulator

and digital displaySlot 6: Digital input and output Conveyor model

module 8X24V/ 8x24V 0.5ASlot 7: Analog input 2 AI Analog section from simulator

Addresses Fixed slot addressing is used for the S7-300 (CPU 312-314). The module addressesare shown in the slide.

The starting addresses of the modules can be set by parameter assignment on the CPU 315-2DP and for S7-400.

Page 40: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Training UnitsPage 4

Date: 05.12.2005File: PRO1_03E.4

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Setup of a Training Area with S7-400

Contents of the The training kit consists of the following components:Training Kit • An S7-400 programmable logic controller with CPU 412 or CPU 413-2DP

• Digital input and output modules, analog modules• Simulator with digital and analog sections• Conveyor model

Note:It is quite possible that your training area is not equipped with the conveyor model shown in the slide above, but rather with the conveyor model pictured below.

Page 41: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Training UnitsPage 5

Date: 05.12.2005File: PRO1_03E.5

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Configuration of the Training Unit S7-400

PS

Default Address:

CPU DI32

28

181716151413121110987654321Slot No.

DI32

32

DO32

36

DO32

40

AI8

1216

Design You can see the design of the training unit S7-400 in the slide above.

Configuration The UR 1 mounting rack is configured with the following modules:Slot 1: Power supply 24V and 5V/20ASlot 2: - " -Slot 3: - " -Slot 4: CPU 412 or otherSlot 5: vacant (when the CPU only has a single width)Slot 6: vacantSlot 7: vacantSlot 8: Digital input 32x24V (from Simulator) Slot 9: Digital input 32x24V (from Conveyor Model) Slot 10: Digital output 32x24V 0.5A (to Simulator)Slot 11: Digital output 32x24V 0.5A (to Conveyor Model)Slot 12: Analog input 8X13 Bit (from Poti on the Simulator)Slot 13: vacantSlot 14: vacant Slot 15:

vacantSlot 16: vacantSlot 17: vacantSlot 18: vacant

Addressing You have the default addresses, as shown in the slide above, as long as no configuration or parameter settings have been carried out.

Page 42: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Training UnitsPage 6

Date: 05.12.2005File: PRO1_03E.6

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

The Simulator

V

0 8 1 5 AI1 AI2 AO1 AO2

AI2AI1

-15V...+15V -15V...+15VAI1

AI2 AO1AO2

V

DI DO

.0

.1

.2

.3

.4

.5

.6

.7

.0

.1

.2

.3

.4

.5

.6

.7

.0

.1

.2

.3

.4

.5

.6

.7

.0

.1

.2

.3

.4

.5

.6

.7

..........

..........

..........

..........

..........

..........

..........

..........

..........

..........

..........

..........

..........

..........

..........

..........

..........

..........

..........

..........

..........

..........

..........

..........

..........

..........

..........

..........

..........

..........

..........

..........

Design The Simulator is connected to the S7-300 or S7-400 training unit by two cables. It is in three sections:

• Binary section with 16 switches/momentary-contact switches and 16 LED's

• Digital section with 4 pushwheel buttons and a digital display. These operate with BCD values,

• Analog section with a voltmeter for displaying the values at analog channels 0 and1 or the analog outputs 0 and 1. You use the selector switch to choose the voltage value you want to monitor. There are two separate potentiometers for setting the values for the analog inputs.

Addressing You use the following addresses to address the inputs and outputs in your user program:

Sensor / Actuator

Switch / M.C. Sw.

LEDs

Pushwheel buttons

Digital display

Analog channels

Version A(DI16, DQ16)

IW 0

QW 8

IW 4

QW 12

PIW 352/354

Version B(DI32, DQ32)

IW 0

QW 4

IW 2

QW 6

PIW 304/306

S7-400(Default addresses)

IW 28

QW 36

IW 30

QW 38

PIW 1216/1230

Page 43: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Training UnitsPage 7

Date: 05.12.2005File: PRO1_03E.7

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

The Conveyor Model

INI 1 to INI 3 (Proximity switches)

M 1 (Motor)

H 1, H 2, H 3, H 4(LEDs)

S 1, S 2, S 3, S 4 (Acknowledgement buttons)

LB1Light barrier

Design The slide shows a diagram of the conveyor model with its sensors and actuators.

Addresses S7-300 S7-300 S7-400Ver. A Ver. B (w/o Sensor / Actuator Symbol(DI16, (DI32, HW DO16) DO32) Config)

I 16.0 I 8.0 I 32.0 Light barrier LB 1 LB1I 16.1 I 8.1 I 32.1 Ackn. switch, Loc 1 S1I 16.2 I 8.2 I 32.2 Ackn. switch, Loc 2 S2I 16.3 I 8.3 I 32.3 Ackn. switch, Loc 3 S3I 16.4 I 8.4 I 32.4 Ackn. switch, Final Assy S4 I 16.5 I 8.5 I 32.5 Proximity switch 1 INI1I 16.6 I 8.6 I 32.6 Proximity switch 2 INI2I 16.7 I 8.7 I 32.7 Proximity switch 3 INI3

Q 20.1 Q 8.1 Q 40.1 LED at Location 1 H1Q 20.2 Q 8.2 Q 40.2 LED at Location 2 H2Q 20.3 Q 8.3 Q 40.3 LED at Location 3 H3Q 20.4 Q 8.4 Q 40.4 LED at Final Assembly H4Q 20.5 Q 8.5 Q 40.5 Conveyor oper. to right K1_CONVRQ 20.6 Q 8.6 Q 40.6 Conveyor oper. to left K2_CONVLQ 20.7 Q 8.7 Q 40.7 Horn HORN

Page 44: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1HW Configuration and Memory ConceptPage 1

Contents Page

Memory Concept of the S7-300 ........................................................................................................................ 2Memory Concept of the S7-400 ........................................................................................................................ 3Loading Blocks into /out of Flash EPROM Memory Card .............................................................................. 4Hardware Configuration and Parameter-assignment ...................................................................................... 5Inserting a Station ............................................................................................................................................ 6Starting HW Config ........................................................................................................................................... 7Generating a Hardware Preset Configuration ............................................................................................... 8Module Address Overview ............................................................................................................................. 9CPU Properties .............................................................................................................................................. 10CPU Properties: General …............................................................................................................................ 11CPU Properties: Startup ................................................................................................................................ 12CPU Properties: Retentive Memory .................................................................................................................. 13CPU Properties: Cycle / Clock Memory .......................................................................................................... 14CPU Properties: Protection .............................................................................................................................. 15CPU Properties: Diagnostics / Clock ................................................................................................................ 16Saving the HW Preset Configuration and Downloading in Module ............................................................... 17Uploading the HW Actual Configuration to the PG ........................................................................................... 18Displaying Hardware Diagnostics in the SIMATIC Manager ............................................................................. 19Possible Problems with Configuration ............................................................................................................ 20Variable Addressing ......................................................................................................................................... 21Accessing the Symbol Table ............................................................................................................................. 22Exercise: Reading Out and Adapting the Actual Configuration ........................................................................ 23Exercise: Assign Parameters to Clock Memory and Test It ............................................................................. 24

Date: 05.12.2005File: PRO1_04E.1

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Hardware Configuration and Memory Concept

Page 45: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1HW Configuration and Memory ConceptPage 2

Load Memory The load memory is part of a programmable module. It contains load objects created on the programming device ( logic blocks, data blocks, additional information).The load memory can either be a plug-in memory card or an integrated RAM.

Work Memory The work memory contains only the data relevant at run time. The RAM work memory is integrated in the CPU and is backed up through the battery.

System Memory The system memory contains the memory areas for:• Process image input and output tables (PII, PIQ)• Bit memories (M)• Timers (T)• Counters (C)• L stack (L).

Retentive Memory The retentive memory is a non-volatile RAM used for backing up bit memories, timers, counters and data blocks even if there is no backup battery. You specify the areas to be backed up when assigning the CPU parameters.

Inserting a When you insert a memory card, the operating system requests a memoryMemory Card reset.(STOP LED flashes slowly). You perform the memory reset by turning the mode

selector to the "MRES" position. The sections of the program relevant for execution are then transferred from the memory card (with load memory function) to the work memory.

The memory card must remain inserted while the program is being executed.

Date: 05.12.2005File: PRO1_04E.2

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Memory Concept of the S7-300

Comments

Symbols

Blocks:• Logic blocks(OB,FC,FB)

• Data blocks(DB)

Flash EPROM Memory Card in PG(subsequently inserted in CPU)

Blocks:• Logic blocks(OB,FC,FB)

• Data blocks(DB)

Additional info.

System memory:• PII, PIQ• M, T, C

• RetentiveM, T, C

• Retent. data blocks

Retentive memory:

With PowerOFF withoutbattery backup

n. reten. reten.

with PowerON without batterybackup

RAM

Blocks:• Logic blocks(OB,FC,FB)

• Data blocks(DB)

Additional info.

Load memory:

Flash-EPROM

Work memory:• OB,FC,FB• DB

n. reten. reten.

Page 46: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1HW Configuration and Memory ConceptPage 3

Load Memory The load memory can either be a plug-in memory card or an integrated RAM. In the S7-400, the memory card (RAM or Flash EPROM) expands the integrated load memory. A memory card is always required, since the integrated load memory only has a limited size.

Work Memory The work memory contains only the data relevant at run time. The RAM work memory is integrated in the CPU and is backed up through the battery.

System Memory The system memory contains the memory areas for:• Process image input and output tables (PII, PIQ)• Bit memories (M)• Timers (T)• Counters (C)• L stack (L).

Memory Card When a RAM memory card is used, the system must be operated with a battey. This is so that the memory card data and those of the internal RAM are backed up if there is a power failure.When an FEPROM memory card is used, the user program is stored in the memory card, power failure safe. The data found in the internal RAM are backed up through the battery.The "Restart" mode is only possible in a backed up system.

Inserting a When you insert a memory card, the operating system requests a memory resetMemory Card (STOP LED flashes slowly). You perform the memory reset by turning the mode

selector to the "MRES" position. The sections of the program relevant for execution are then transferred from the memory card (load memory) to the work memory. The memory card must remain inserted while the program is being executed.

Date: 05.12.2005File: PRO1_04E.3

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Memory Concept of the S7-400

Comments

Symbols

Blocks:• Logic blocks(OB,FC,FB)

• Data blocks(DB)

Flash EPROM Memory Card in PG(subsequently inserted in CPU)

Blocks:• Logic blocks(OB,FC,FB)

• Data blocks(DB)

Additional info.

RAM

Blocks:• Logic blocks(OB,FC,FB)

• Data blocks(DB)

Additional info

Load memory:

Flash-EPROM

System memory:• PII, PIQ• M, T, C

Work memory:• OB,FC,FB• DB

Backupvia battery

Page 47: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1HW Configuration and Memory ConceptPage 4

Introduction When you use an FEPROM card, it is possible to operate the CPU without battery backup. The program is stored in the FEPROM, power failure safe.You can define retentive areas in the HW Configuration. In the S7-300, the retentive data (timers, counters, bit memories, data areas) are stored in a retentive memory area of the CPU (non-volatile RAM).

Insert / Remove When you remove or insert a memory card, the CPU requests a memory reset. When you insert a RAM card, the user program must be reloaded from the PG. When you insert anFEPROM card, its contents are copied into the work memory.

Power Failure After a Power Off without battery backup, the blocks are copied from the memory card into the work memory and with the S7-300, the retentive data are supplied from the non-volatile RAM. Data areas in DBs, that were defined as retentive (only with the S7-300), resume the state they had before power failure. Non-retentive data areas are set to the original values that are stored in the memory card.

Changing the When you make block corrections, the modified blocks are stored in the workProgram memory. When you upload the blocks into the PG, these are retrieved from the work

memory.After a power failure (without battery), the work memory (RAM) is erased. So that the corrected blocks are available once more after a Power On, they have to be:1. saved on the hard disk when you operate without EPROM memory card, 2. saved on the hard disk or on a memory card when you operate with EPROM memorycard.

Loading the You either transfer the blocks onto the memory card (inserted in the PG) throughMemory Card the SIMATIC Manager per drag and drop or with some CPUs, you can write directly into the

CPU using the menu options PLC -> Download to EPROM Memory Card on CPU. The memory card must be erased first. Individual blocks can be reloaded but cannot be deleted or overwritten.

Date: 05.12.2005File: PRO1_04E.4

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Loading Blocks into /out of Flash EPROM Memory Card

Load memoryinternal RAM

"Load"

Load memoryFlash EPROM

"Load in EPROM"

Work memoryRAM

After insertingthe memorycard:memory resetrequestand copyingin workmemorySections

relevant for execution

"Load in PG"

Page 48: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1HW Configuration and Memory ConceptPage 5

Date: 05.12.2005File: PRO1_04E.5

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Hardware Configuration and Parameter Assignment

Actual configuration Actual configuration and parameter assignment of an existing hardware.

Parameter-assignment Establishing the characteristics of parameter-assignable blocks, e.g: startup characteristics, retentive areas, etc.)

Preset configuration Planned hardware configuration and parameter assignment.

Configuration Assignment of racks, blocks and distributed I/O in the Station window of HW Config.You can select the components from a hardware catalog.

HW Configuration The modules are supplied from the factory with preset parameters. If these default settings are OK, a hardware configuration is not necessary.A configuration is necessary:• if you want to modify preset parameters or addresses of a module (e.g.

enable the hardware interrupt of a module)• if you want to configure communication connections• with stations with distributed peripherals (PROFIBUS-DP)• with S7-400 stations with several CPUs (multicomputing) or expansion racks • with fault-tolerant programmable logic controllers (option package).

Preset When you configure a system, a so-called preset configuration is created. ItConfiguration contains a hardware station with the planned modules and the associated parameters.

The PLC system is assembled according to the preset configuration and during commissioning, the preset configuration is downloaded into the CPU.

Actual Configuration In an assembled system, the actual existing configuration and parameter assignment of the modules can be read out of the CPU. A new HW station is thereby set up in the project. This is necessary, for example, if the project structure does not exist locally at the PG. After the actual configuration is read out, the set parameters can be checked and then stored in a project.

Notes With the S7-400, the CPU can be assigned parameters in such a way, that when there are differences between the preset configuration and the actual configuration, the startup of the CPU is interrupted.To call the HW Config tool, a hardware station must exist in the SIMATIC Manager.

Page 49: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1HW Configuration and Memory ConceptPage 6

Insert StationYou insert a new station in the current project by selecting the menu options Insert -> Station -> SIMATIC 300 Station or SIMATIC 400 Station.The name automatically given to this station "SIMATIC 300 (1)" can then be changed by you.

Date: 05.12.2005File: PRO1_04E.6

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Inserting a Station

Page 50: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1HW Configuration and Memory ConceptPage 7

HW Config This tool helps you to configure, assign parameters to and diagnose the hardware.

Starting HW Config To start the HW Config tool:• select a hardware station in the SIMATIC Manager and choose the menu

options Edit --> Open Object or• double-click on the Hardware object.

"Hardware This is a window of the "HW Config“ application which you use for insertingConfiguration" components from the "Hardware Catalog" window.

The title bar of this window contains the name of the project and the station name.

"Hardware Catalog" To open the catalog:• select the menu options View -> Catalog or• click on the icon in the toolbar.If “Standard” is selected as the catalog profile, all racks, modules and interface modules are offered for selection in the "Hardware Catalog" window.You can create your own catalog profiles containing frequently used elements by selecting the menu options Options -> Edit Catalog Profiles.

Profibus Slaves, that do not exist in the catalog, can be added after the fact. To do so, you use so-called GSE files that are supplied by the manufacturer of the slave device.The GSE file contains a description of the device. To include the slave in the hardware catalog, use the menu options Options -> Install New GSE Files and then Options -> Update Catalog. You will find the new devices in the catalog under Profibus additional field devices.

Date: 05.12.2005File: PRO1_04E.7

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Starting HW Config

Page 51: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1HW Configuration and Memory ConceptPage 8

Generating a This means specifying how the modules are to be arranged in the rack. ThisPreset configuration specified by you is referred to as the preset configuration. Configuration

Rack For example, you open a SIMATIC 300 station in the Hardware Catalog. Catalog "RACK-300" contains the icon for a DIN rail. You can insert this in the "Hardware Configuration" window by double-clicking on it (or using drag&drop).Two rack component lists then appear in the two-part window: a plain list in the top part and a detailed view with order numbers, MPI addresses and I/O addresses in the bottom part.

Power Supply If a load current power supply is required, you insert, with a double click or per drag&drop, the appropriate "PS-300" module from the catalog in slot no.1 in the list.

CPU You select the CPU from the "CPU-300" catalog, for example, and insert it in slot no. 2.

Slot No. 3 Slot no. 3 is reserved as the logical address for an interface module (for multi-tier configurations).If this position is also to be reserved in the actual configuration for the later installation of an IM, you must insert a dummy module DM370 (DUMMY).

Signal Modules From slot no. 4 onwards, you can insert a choice of up to 8 signal modules (SM), communications processors (CP) or function modules (FM). You insert modules in the list by selecting the slot and then double-clicking on the module you want in the catalog.You can insert modules anywhere in the list by using drag&drop.

Date: 05.12.2005File: PRO1_04E.8

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Generating a Hardware Preset Configuration

Page 52: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1HW Configuration and Memory ConceptPage 9

R Rack numberS Slot number of the relevant moduleDP only relevant when using Distributed Peripherals (I/O)IF Interface module ID when programming the M7 system (in C++).

Free Address When the CPU 315-2DP is used, you can assign addresses to the modules Assignment independently of the slots in which they are installed:

1. Open HW Config2. Double-click on the module whose address you want to change. The

"Properties" window opens.3. Set the starting address you want on the "Addresses" tab page.

The end address is automatically updated by the system.

Date: 05.12.2005File: PRO1_04E.9

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Module Address Overview

“Address Overview”

Page 53: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1HW Configuration and Memory ConceptPage 10

Assigning You assign parameters to the modules to adapt them to the requirements of theParameters process.

What to do:1. Select a module in the station window.2. Double-click the selected module to open the "Properties" dialog window.3. This dialog window contains 9 tabs in which you can assign parameters

for the various CPU characteristics (see next pages).

Date: 05.12.2005File: PRO1_04E.10

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

CPU Properties

2x

Page 54: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1HW Configuration and Memory ConceptPage 11

"General" Tab The "General" tab page provides information about the type of module, its location and, in the case of programmable modules, the MPI address.

MPI Address If you want to network several PLCs via the MPI interface, you must assign a different MPI address to each CPU.Click the "Properties" button to open the "Properties - MPI Node" dialog window, which contains the two tabs: "General" and "Parameters".

Date: 05.12.2005File: PRO1_04E.11

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

CPU Properties: General

Page 55: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1HW Configuration and Memory ConceptPage 12

Startup The S7-300 and S7-400 CPUs have different startup characteristics.Characteristics For the moment, we shall only look at the startup characteristics of the S7-300. The

special features of the S7-400 will be discussed in a later chapter.

Complete Restart The S7-300 only recognizes the "Complete restart" type of startup. Newer S7-CPUs also have the "Cold restart" startup version .

Monitoring Times • "Ready message from modules (x100ms):"Maximum time for all modules to issue a Ready message after power ON. If the modules do not send a Ready message to the CPU within this time, theactual configuration is not equal to the preset configuration.For example, in a multi-tier configuration, all power supplies can be switched on within this time without paying attention to a particular sequence.

• "Transfer of parameters to modules (x100ms):"Maximum time for "distributing" the parameters to the parameter-assignablemodules (timing begins after "Ready message from modules").If, after the monitoring time has run out, all modules have not been assigned parameters, then the actual configuration is not equal to the preset configuration.

Startup if Preset Only with CPUs with integrated DP interface (and S7-400) can you use theConfiguration Not "Startup if preset configuration not equal to actual configuration" checkbox to Equal to Actual decide whether the CPU should startup if the preset configuration is not theConfiguration same as the actual configuration (number and type of modules installed).

The other S7300 CPUs go into RUN when the preset configuration is not the same as the actual configuration.

Date: 05.12.2005File: PRO1_04E.12

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

CPU Properties: Startup

Page 56: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1HW Configuration and Memory ConceptPage 13

Retentive Memory The "Retentive Memory" tab page is used for specifying the memory areas to be retained after a power failure or on transition from STOP to RUN.A "complete restart" is performed in both cases on the S7-300.

Complete Restart On complete restart, the blocks stored in the battery-backed RAM (OB, FC,with FB, DB) as well as the bit memories, timers and counters defined as retentiveBackup Battery are retained. Only the non-retentive bit memories, timers and counters are reset.

Complete Restart If the RAM is not battery-backed, the information in it is lost. Only the bit without memories, timers and counters defined as retentive and the retentive data blockBackup Battery areas are saved in the non-volatile RAM area.

After a complete restart, the program must be downloaded again:• from the memory card (if inserted) or• from the PG (if no memory card exists).

Date: 05.12.2005File: PRO1_04E.13

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

CPU Properties: Retentive

Only relevant if CPU has no backupbattery

Page 57: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1HW Configuration and Memory ConceptPage 14

Cycle • "Scan cycle monitoring time (ms):"- If this time is exceeded the CPU goes into the STOP mode.

Possible causes why this time is exceeded: Communications processes, frequently from interrupt events, errors in the CPU program.

- If you have programmed an error OB 80, the scan cycle time is doubled. After that, the CPU also goes into the STOP mode.

• "Cycle load from communication (%):"- Communication (e.g. data transmission to another CPU via MPI or test

functions, that was triggered by PG) is restricted to the specified percentage of the current scan cycle time.

- Restricting the cycle load can slow down communication between CPU and PG.- Example: Restricting communication to 20% results in a maximum

communication load of 20ms for a scan cycle time of 100ms.

Size of the With the CPU 318-2 and several S7-400 CPUs, you can specify the size of theProcess Image process image (in bytes). The process image area always begins with input or output

byte 0.

Clock Memory Clock memories are bit memories that change their binary value periodically (mark-to-space ratio 1:1). Each bit in the clock memory byte is assigned a particular period/frequency.Example of a flashing light with a flashing frequency of 0.5Hz:(Period = 2s, light ON = 1s, light OFF = 1s).

Date: 05.12.2005File: PRO1_04E.14

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

CPU Properties: Cycle / Clock Memory

Clock memory bit 7 6 5 4 3 2 1 0

Frequency (Hz) 0.5 0.62 1 1.25 2 2.5 5 10

Period (s) 2 1.6 1 0.8 0.5 0.4 0.2 0.1

Page 58: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1HW Configuration and Memory ConceptPage 15

Preset Option Preset characteristics (protection level 1; no password assigned):The position of the keyswitch on the CPU determines the protection:• Keyswitch in RUN-P position or STOP: no restrictions• Keyswitch in RUN position: read-only access possible!

Password If a protection level was assigned with a password (only valid until a memory reset), a "person who knows the password" has reading and writing access."The person who doesn‘t know the password" has the following restrictions:• protection level 1: corresponds to the preset characteristics• protection level 2: read-only access possible, irregardless of the keyswitch

setting • protection level 3: neither reading nor writing access possible, irregardless

of the keyswitch setting.

Characteristics of a Password-protected Module in OperationExample: if you want to execute the function "Modify Variable", you must enter the password for a module that has been assigned the protection level 2 parameter.

Access Rights You can also enter the password for a protected module in the SIMATICManager:1. Select the protected module or its S7 program2. Enter the password by selecting the menu options PLC -> Access Rights. The access rights, after a password has been entered, is only valid until the last S7 application is completed.

Operation The cycle load for test functions is regulated with this.In Process operation, test functions such as "Monitor" or "Monitor/Modify Variable" are restricted in such a way that the permitted scan cycle time increase that is set cannot be exceeded. Testing with breakpoints and single-step (program execution) cannot be performed.In Test operation, all test functions through the PG/PC can be used without restrictions,even if they cause the scan cycle time to be greatly increased.

Date: 05.12.2005File: PRO1_04E.15

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

CPU Properties: Protection

Page 59: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1HW Configuration and Memory ConceptPage 16

System Diagnostics If the "Record cause of CPU STOP" checkbox is deactivated (not checked), no message is sent to the PG / OP when the CPU goes into Stop mode ("CPU Messages").The cause of the stop is still entered in the diagnostic buffer.

Clock The possibilities of synchronizing the clocks in a device network are discussed in the chapter "Troubleshooting".It is, however, also possible to automatically adjust the time on the clock of a stand-alone device by a specified correction factor.

Correction Factor The correction factor is used for correcting an inaccuracy of the clock over 24 hours.The correction factor can be either positive or negative.Example: If the clock is 3 seconds fast after 24 hours, this can be corrected with the factor "-3000ms".

Note The "Interrupts", "Time-Of-Day Interrupts" and "Cyclic Interrupt" are discussed in the chapter "Organization Blocks".

Date: 05.12.2005File: PRO1_04E.16

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

CPU Properties: Diagnostics / Clock

Page 60: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1HW Configuration and Memory ConceptPage 17

Save You select the menu options Station->Save to save the current configuration in the current project (without generating system data blocks).

Save and Compile When you select the menu options Station->Save and Compile or click theicon in the toolbar, the configuration and parameter assignment data isalso saved in system data blocks.

Consistency Check You select the menu options Station -> Consistency Check to check whether it is possible to generate configuration data from the entries made.

Download in Module You select the menu options PLC -> Download or click the icon in the toolbar to download the selected configuration to the PLC.The PLC must be in "STOP" mode!

System Data Blocks The SDBs are generated and modified when you configure the hardware.System data blocks (SDBs) contain configuration data and module parameters. They are stored in the work memory of the CPU on downloading.This makes it easier to replace modules, because the parameter assignment data is downloaded to the new module from the system data blocks on startup.In the programming device, the system data blocks are saved under: Project \ Station \CPU \ S7_program \ Blocks \ System_data.You double-click the My Briefcase iconto open the list of system data blocks.

If you use a memory card as Flash EPROM, you should save the SDBs there as well.That way, the configuration is not lost if you operate without battery backup and there is a power failure.

Date: 05.12.2005File: PRO1_04E.17

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Saving the HW Preset Configuration and Downloading it in Module

Download(only when CPUis in STOP mode)

Page 61: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1HW Configuration and Memory ConceptPage 18

Introduction A configuration is only necessary in the following cases:• if you want to modify the basic settings of the modules• for stations with distributed I/O• for S7-400 with several CPUs or with expansion racks.

It is possible to read out the actual configuration from the CPU, to look at the set parameters in an existing system.

Actual Configuration During startup, the CPU generates an actual configuration, that is, it saves the arrangement of the modules and allocates the addresses in accordance with a fixed algorithm. If no parameters have been assigned, the default parameters defined at the factory are used.The system stores this actual configuration in system data blocks.

Uploading to PG There are two ways of uploading the actual configuration to the PG:1. In the SIMATIC Manager:

by selecting the menu options PLC -> Upload Station.2. In the HW Config tool:

by selecting the menu options PLC -> Upload or by clicking the icon.

Storage on PG The actual configuration read from the hardware is inserted as a new station in the selected project on the PG.

Note When you read out the actual configuration, the order numbers of the modules cannot be completely identified. For this reason, you should check the configuration and if required, insert the exact module type of the existing modules. To do so, choose the module, and then select the menu options Options -> Specify Module.

Date: 05.12.2005File: PRO1_04E.18

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Uploading the HW Actual Configuration to the PG

Page 62: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1HW Configuration and Memory ConceptPage 19

Introduction With this function, you obtain a quick overview of the state of the PLC. If, for example, there is a hardware fault in a diagnostics-capable module, you can identify, through the use of a symbol, which module is faulty and where it is located. When you double-click on the faulty module, additional information is displayed.

Opening the Tool Select the menu options PLC->Diagnose Hardware in the SIMATIC Manager. A second possibility is to open the station online in the HW Config tool or you can click on the

icon in the toolbar.

Description When you open the system diagnostics, the hardware configuration is read out from the CPU (see left-hand screenshot). In this view, all the modules present (including those in expansion racks or distributed I/O) are displayed.If the CPU is in STOP mode or if there is a fault in a module, this is indicated with symbols.You can double-click the CPU or a faulty module to obtain further diagnostic information (see right-hand screenshot). In the example, there is a power failure in the analog module.

Note If you have selected the menu options Options -> Customize -> View in the SIMATIC Manager and activated (checked) the "Display Quick View when Diagnosing Hardware" checkbox, only a list of faulty modules will be displayed instead of the full "Diagnosing Hardware" window.

Date: 05.12.2005File: PRO1_04E.19

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Displaying Hardware Diagnostics in the SIMATIC Manager

2x

Page 63: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1HW Configuration and Memory ConceptPage 20

Date: 05.12.2005File: PRO1_04E.20

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Possible Problems with Configuration

Configuration cannot be compiledIn S7-300, gaps in configuration

Situation Result/Remedy

CPU goes in Stop mode because of a parameter assignment errorAnalog module in incorrect slot

Analog module signals group errorbecause of incorrect parameterassignment

Incorrect measuring range for analog module

Reload configurationAfter a memory reset, different parameter assignment of modules

Create HW station or "Upload Station"Not possible to open HW Config.

Open the station offlineModule parameters cannot be modified

Configuration cannot be downloadedIncorrect CPU (e.g. CPU 315-2DP instead of CPU 314)

General In the slide you can see several examples of errors that can occur with configuration.

Page 64: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1HW Configuration and Memory ConceptPage 21

Date: 05.12.2005File: PRO1_04E.21

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Variable Addressing

2x

Slot dependent The modules are assigned fixed slot-dependent addresses with the S7-300Addressing (CPUs without DP interface) and S7-400 (without hardware configuration).

Variable With the S7-300 (CPUs with integrated DP interface) and with the S7-400, youAddressing can assign parameters to the starting addresses of the modules.

What to Do When you double-click on a digital or an analog module, the parameter assignment screen is opened. After you choose the "Addresses" tab, you can deselect "System default". You can now define the starting address in the "Start" box. If the address is already used, an error message is triggered.Part process images can only be defined in the S7-400. That way, specific inputs and outputs (e.g. time-critical signals) can be combined into one group. A system function triggers the updating of a part process image in the user program.

Note After a CPU memory reset, the parameters, and therefore also the addresses are lost.This means that with the S7-300 the slot-dependent addresses and with the S7-400 the default addresses are valid once more.

Page 65: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1HW Configuration and Memory ConceptPage 22

Date: 05.12.2005File: PRO1_04E.22

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Accessing the Symbol Table

Once with right

Symbols Symbolic addressing and the editing of symbol tables is discussed in detail in the chapter "Symbols".It is also possible to access the symbol table of the HW station from the "HW Config" tool. The symbol table can be supplemented or modified.After you click the module with the right mouse button, you can open the symbol table by selecting the menu option Edit Symbolic Names … .

Page 66: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1HW Configuration and Memory ConceptPage 23

Task Since a HW station does not yet exist in the project "My Project", you are to read out the actual configuration, check it, and save it in the project.

Step 7 Adjust the following addresses:

Module Slot Address

DI 8 0DI 9 8DO 10 4DO 11 8AI 12 304

Date: 05.12.2005File: PRO1_04E.23

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Reading Out and Adapting the Actual Configuration

Start the SIMATIC Manager

Step What to Do Result

1 The tool is started

2 Open the project "My Project" The project structure is displayed

3 Download the actual configuration withPLC -> Upload

A new HW station is created

4Check whether the correct modules (order numbers) are entered ???

5 Enter the correct order numbers for the modules

The parameter blocks of the CPU are displayed

6Save the configuration as"My Station" and download the configuration

7 If you have an S7-400 training unit,adapt the addresses (see text)

The addresses are the same as theS7-300 training unit, version B

Page 67: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1HW Configuration and Memory ConceptPage 24

Task With the help of a small program test the flashing frequencies preset in the system!

Date: 05.12.2005File: PRO1_04E.24

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Assign Parameters to Clock Memory and Test It

In the CPU assign parameters to a clock memory MB 10

Step What to Do Result

1

3Check the function by programming an OB 1 with the statementsL MB 10, T QB 9 (QB 5)

QB9 (QB5) on thesimulator should flash

Save and download the configuration in the CPU2

MB 10 flashes

Page 68: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Editing BlocksPage 1

Contents Page

The STEP 7 Programming Languages ………….......................................................................... 2Starting the LAD/STL/FBD Editor ...................................................................................................... 3Components of the LAD/STL/FBD Editor ........................................................................................ 4Selecting the Programming Language ............................................................................................ 5Programming in LAD/FBD ............................................................................................................... 6Programming in STL ...................................................................................................................... 7Saving a Block ............................................................................................................................. 8Calling a Block in OB1 .................................................................................................................. 9Downloading Blocks into the PLC ……………............................................................................... 10Simple Program Debugging ............................................................................................................ 11Downloading and Saving Modified Blocks ....................................................................................... 12Exercise: Selecting the Mnemonics ............................................................................................... 13Exercise: Opening and Editing FC 1 .................................................................................................. 14Exercise: Changing the Programming Language ............................................................................ 15Exercise: Saving FC 1...................................................................................................................... 16Exercise: Downloading a Block into the PLC .................................................................................... 17Exercise: Calling FC 1 in OB 1 ....................................................................................................... 18Exercise: Debugging FC 1 (in LAD) ................................................................................................. 19Exercise: Expanding the Program in the FC 1 Block ....................................................................... 20Editor Customization: "Editor" Tab ………..................................................................................... 21Editor Customization : "STL" Tab ……….......................................................................................... 22Editor Customization : "LAD/ FBD" Tab ………................................................................................ 23Editor Customization : "Create Block" Tab ………..…...................................................................... 24Editor Customization : "Source Files" Tab ………. ............................................................................ 25Editor Customization : "Symbol Selection" Tab ………...................................................................... 26

Date: 05.12.2005File: PRO1_05E.1

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Editing Blocks

Page 69: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Editing BlocksPage 2

Introduction There are several programming languages in STEP 7 that can be used depending on preference and knowledge. By adhering to specific rules, the program can be created in Statement List and can then be converted into another programming language.

LAD Ladder Diagram is very similar to a circuit diagram. Symbols such as contacts and coils are used. This programming language appeals to those who ‚grew up‘ with contactors.

STL The Statement List consists of STEP 7 instructions. You can program fairly freely with STL (sometimes to the point of being unable to follow it anymore). This programming language is preferred by programmers who are already familiar with other programming languages.

FBD The Function Block Diagram uses “boxes” for the individual functions. The character in the box indicates the function (e.g. & --> AND Logic Operation). This programming language has the advantage that even a “non-programmer” such as a process engineer can work with it. Function Block Diagram is available as of Version 3.0 of the STEP7 Software.

Date: 05.12.2005File: PRO1_05E.2

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

The STEP7 Programming Languages

A I0.0A I0.1= Q8.0

STL

&Q8.0

=

I0.0

I0.1

FBD

I0.0 I0.1 Q8.0

LAD

Page 70: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Editing BlocksPage 3

Starting the Editor You can start the LAD/STL/FBD Editor by selecting Start -> Simatic -> STEP 7 -> LAD,STL,FBD - Programming S7 Blocks. The following quicker way of starting the Editor is recommended :1. Select the "Blocks" object in the project window of the SIMATIC Manager.2. Double-click any block to open the Editor.

Program When using the LAD and FBD programming languages you can insert simpleElements graphical program elements directly into the program from the toolbar.

You can click the "Program Elements" icon to open another window containing more program elements. The contents of this window depend on the programming language selected (LAD/FBD/STL).

Date: 05.12.2005File: PRO1_05E.3

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Starting the LAD/STL/FBD Editor

2x

Page 71: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Editing BlocksPage 4

Components When you start the LAD/STL/FBD Editor, two windows are automatically opened: the declaration table and the code section. The user can also open a third "Program Elements" window.

Declaration Table The declaration table belongs to the block. It is used for declaring variables and parameters for the block. The declaration table is discussed in detail in the chapter ”Functions and Function Blocks".

Code Section The code section contains the program itself, divided into separate networks if required. Entries are checked for correct syntax.

Program The contents of the "Program Elements" window depends on the programmingElements language selected.

You can double-click elements in the list ("browser") to insert them into the program at the cursor position.You can also insert elements by drag&drop.

Date: 05.12.2005File: PRO1_05E.4

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Components of the LAD/STL/FBD Editor

Browser

DeclarationTable

Code Section

Page 72: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Editing BlocksPage 5

View You choose the View menu to switch from one STEP 7 programming language to another:• LAD (Ladder Diagram)• FBD (Function Block Diagram)• STL (Statement List).

LAD/FBD => STL You can convert program sections that have been written in the graphical programming languages into STL. You should, however, be aware that the result of this conversion is not always the most efficient solution in Statement List.

STL => LAD/FBD It is not always possible to convert program sections written in STL into LAD or FBD. The sections of the program that cannot be converted are left in STL. No sections of the program are lost on conversion.

Date: 05.12.2005File: PRO1_05E.5

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Selecting the Programming Language

Page 73: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Editing BlocksPage 6

Elements Frequently used LAD and FBD elements appear as icons in the toolbar. You click them with the mouse to insert them at the selected position in the program.

Toolbar icons in LAD:

Toolbar icons in FBD:

You can insert other program elements from the browser in the "Program Elements" window:• in any position with drag&drop • in a selected position by double-clicking the element in the browser.

Networks When you click the "New Network“ icon in the toolbar, a new network is added after the current network.

Note If you want to insert a new network before NW1, you must select the block name ("FC1: Plant" in the example above) before you click the "New Network" icon.

Empty Box You can use the Empty Box to insert LAD or FBD elements more quickly. The elements can be inserted directly without having to select them from the browser.

After you have selected the position in the network where you want to insert an element, click on the “Empty Box“ icon in the toolbar.

By entering the first letters of an element name, a list with the elements which start with these letters appears and you can make a selection.

Date: 05.12.2005File: PRO1_05E.6

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Programming in LAD/FBD

Page 74: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Editing BlocksPage 7

Statements The user needs to know the statements for writing a program in STL. You can obtain information about the syntax and functionality from the on-line help: Help -> Help on STL.The following information is available:

"Statement List Instructions", a description of all the statements thatexist in this programming language"Working with Statement List", a description of

Statement List View and General SyntaxEntering and Viewing Constant Data Types of BlocksSwitch Contacts and Signal States

Program Elements When you are using the STL Editor, the "Program Elements" window contains only a list of the existing blocks which can be called from the current block.

Networks Networks are inserted in the same way as in the LAD/FBD Editor (see previous page).

Making Changes You use the "Insert" key to toggle between "Overwrite" and "Insert" mode. The current setting appears in the status bar.

Date: 05.12.2005File: PRO1_05E.7

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Programming in STL

Page 75: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Editing BlocksPage 8

Saving a Block When you have finished editing a block, you can save it on the hard disk of the programming device:• by selecting the menu options File -> Save or • by clicking the disk icon in the toolbar.

.

Date: 05.12.2005File: PRO1_05E.8

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Saving a BlockCurrent project directory with name of block

Page 76: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Editing BlocksPage 9

Date: 05.12.2005File: PRO1_05E.9

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Calling a Block in OB1

Cyclic So that a newly created block is integrated in the cyclic program execution of theExecution CPU, it must be called in OB1.

The simplest way of inserting the block call is through the browser (see picture above).

Page 77: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Editing BlocksPage 10

Downloading You download the blocks into the PLC with the SIMATIC Manager by:• clicking the icon or• selecting the menu options PLC -> Download.

Before you do this, you must select the blocks you want to download:• All blocks: Select the "Blocks" object in the left-hand pane of the

project window.• Several blocks: Hold down the CTRL key and select the blocks you

want.• One block: Select the block.

Date: 05.12.2005File: PRO1_05E.10

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Downloading Blocks into the PLC

Page 78: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Editing BlocksPage 11

Requirements Before you can activate the monitoring mode, you must open the block you want to monitor either offline or online with the LAD/STL/FBD Editor.Note: In order to test a block in the offline mode, it must first be downloaded

into the PLC.

Activation / There are two ways of activating/deactivating the “Monitor" test function:Deactivation

• click the “Spectacles“ icon• select the menu options Debug -> Monitor.

View The program status is displayed in different ways depending on the programming language selected (LAD/STL/FBD).When the monitoring function is activated, you cannot change the programming language in which the block is viewed (LAD/FBD/STL)..

Note You will find more information about testing programs in the chapter "Test Functions".

Date: 05.12.2005File: PRO1_05E.11

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Simple Program Debugging

Page 79: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Editing BlocksPage 12

Date: 05.12.2005File: PRO1_05E.12

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Downloading and Saving Modified Blocks

Open offline

Open online

Save

Download

(Q8.0)

Making Corrections You can make corrections to blocks that have been opened either online orto Blocks offline; however, not in the test mode.

• You normally download the modified block to the PLC, test it, make furthercorrections if necessary and finally save it on the hard disk when it has beenfully debugged.

• If you do not want to test the program straight away, you can just save thechanges on the hard disk to start with. The old version of the block is thenerased in this case.

• If you make corrections to a number of blocks and don't want to overwrite the original version of the program yet, you can download the changed blocks to the CPU first without saving them on the hard disk of the PG.You can save them on the hard disk of the PG when you have tested the whole program successfully.

Insert/Over-write The insert mode is set by default for LAD or FBD. By pressing the „Insert (Ins)“ key, you activate the over-write mode. After that, you can, for example, modify the type of timer for a timer (e.g. change ON delay to OFF delay), without rewiring the inputs and outputs.

Page 80: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Editing BlocksPage 13

Remember ! You can select the language and the mnemonics you want to use in the SIMATICManager.

Goal To select the desired mnemonics.

What to Do 1. Start the SIMATIC Manager, if it is not already open.2. Select the menu options Options -> Customize.3. Choose the language and the desired mnemonics in the “Language” tab and

confirm with “OK”.

Result You will use one of the following representations when writing your program.Example of an STL statement with German mnemonics:

U E 1.0 // UND Eingang 1.0Example of an STL statement with English mnemonics:

A I 1.0 // AND Input 1.0

Date: 05.12.2005File: PRO1_05E.13

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Mnemonics German English (International)

…select the languagefor editing inLAD/STL/FBD

Before you open a program block or a program ...

Exercise: Selecting the Mnemonics

Page 81: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Editing BlocksPage 14

Remember ! You must open the FC 1 block before you can start editing it. So that the block can be executed, it must be called in OB 1.

Goal To open FC 1, which was created in the S7 program "My Program" and to enter the following logic operations in the code section of the block.

What to Do 1. In the SIMATIC Manager, double-click on the “Blocks” folder in the program“My_Program” to open it.

2. Select the menu options View -> Offlineor alternatively:

2a.Click on the Offline icon in the toolbar.3. Open FC 1 (and the LAD/STL/FBD Editor) by double-clicking its block icon.4. Select the menu options View -> LAD in the LAD/STL/FBD Editor.5. Enter the program shown below

in Ladder Diagram using the iconsin the toolbar.

Editing Tips To position the first element, move the cursor to the network line.Position the cursor above the symbol concerned (using the mouse or the TAB key) to enter the addresses.You can use the TAB key to jump from one element to another.

Result I 0.0 I 0.1 Q 8.0 (Q 4.0)

Date: 05.12.2005File: PRO1_05E.14

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Opening and Editing FC 1

Page 82: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Editing BlocksPage 15

Remember ! After you have opened a block for editing or testing, you can choose one of the programming languages LAD, STL or FBD. If you write your program in LAD/FBD and switch to STL view, all your entries will be converted into a list of statements. This method does not always produce the most efficient program code.

Goal To select the programming language for editing a block.

What to Do 1. Open the FC1 block in the LAD/STL/FBD Editor.2. Select your programming language from the View menu.

Result Your program will be displayed in one of the following programming languages:

LAD:I 0.0 I 0.1 Q 8.0 (Q 4.0)

STL: A I 0.0AN I 0.1= Q 8.0 (Q4.0)

FBD:I 0.0 &

Q 8.0 (Q4.0)I 0.1 =

Date: 05.12.2005File: PRO1_05E.15

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

After you have opened a block ...

…choose the programming languageyou want to use.

Exercise: Changing the Programming Language

• Ladder Diagram (LAD)• Statement List (STL)• Function Block Diagram (FBD)

Page 83: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Editing BlocksPage 16

Remember ! After you have created a program block, you should save it on diskette or on the hard disk to prevent it from being lost. You do this with the normal Windows "Save“ facility, using one of the two methods shown above.If you use the menu options File => Save As, you must specify the project, program and block name you want to use. After you have saved the block, you can select, in the SIMATIC Manager, the project/program directory in which the block was saved. When the block is displayed, you can use the SIMATIC Manager like the "Explorer“ to copy the block to severalCPUs or to move it somewhere else.

Goal To save a program block.

What to Do 1. Select the menu options File -> Save or click the “Save” iconor

2. Select the menu options File -> Save As and enter the details.

Result 1. The program block is saved with the block name you specified when you opened it.

2. With Save As, the program block is saved with the new name you enter.

Note When you save a program it is not copied to the CPU.(You do this with the Download option)

Date: 05.12.2005File: PRO1_05E.16

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

To save a block or a filewithout changing the name... select themenu options File -> Save

...or click

Exercise: Saving FC 1

To save a block with a different name or in a different place: File -> Save As

Page 84: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Editing BlocksPage 17

Remember ! After you have created and edited a block, you must transfer it to the CPU in order to be able to test it. You can download the just opened block into the PLC with the LAD/STL/FBD Editor.With the SIMATIC Manager, you can download blocks without opening them.

Goal To download a block (FC 1) with the LAD/STL/FBD Editor.

What to Do With the LAD/STL/FBD Editor open ....1. Select the menu options PLC -> Download or click on the “Download”

icon

2. Answer the question in the dialog box:

If you answer “Yes", the block already in the CPU will be overwritten and lost. If you answer "No", the old block will remain in the CPU and the new one will not be downloaded.Choose “Yes" for this exercise, so that you can then test the block you have edited.

Result Your new program block is written to the CPU.

Date: 05.12.2005File: PRO1_05E.17

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Downloading a Block into the PLC

...or click theDownloadicon...

To transmit a block to the CPU...

Page 85: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Editing BlocksPage 18

Date: 05.12.2005File: PRO1_05E.18

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Calling FC 1 in OB 1

Remember ! The FC 1 function must be called in OB 1 so that it can be executed cyclically.

Goal To call FC 1 in the organization block OB 1.

What to Do 1. In the LAD/STL/FBD Editor, open the OB 1 block from the S7 Program "My Program".2. Select a location in the rung of Network 1.3. Open the "Program Elements" browser by clicking on the icon.

4. Open the "FC Blocks" entry in the browser and using the mouse drag FC 1 to Network 1 in OB 1.5. Save the FC 1 block.6. Download the block to the CPU.

Result The OB 1 block is cyclically executed in the CPU; and therefore also the FC 1 function.

Page 86: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Editing BlocksPage 19

Remember ! To monitor the program execution of a block, it must be open online or offline. If the block is open offline, it must be downloaded to the PLC before you can test it.

Display If the result of a check is positive, the relevant symbol is displayed with solid lines. If not, it is displayed with dashed lines.If the RLO=1, the rung is shown as a solid line. If not, it appears as a dashed line. You can change the thickness and color of the lines in the LAD/STL/FBD Editor by selecting the menu options Options => Customize => LAD/FBD.

Goal To test a block while it is being executed in the CPU.

What to Do 1. Open FC 1 offline. 2. Select the menu options Debug -> Monitor or click on the

“spectacles” icon

Result Depending on the switch settings at inputs I 0.0 and I 0.1, you will see one of the displays shown in the slide.

Date: 05.12.2005File: PRO1_05E.19

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Testing FC 1 (in LAD)

Signalstate

Resultof checkInput

I 0.0

I 0.1

I 0.0

I 0.1

I 0.0

I 0.1

I 0.0

I 0.1

0

0

1

1

1

0

0

1

0

1

1

0

1

1

0

0

I 0.0 I 0.1 Q 8.0 (Q 4.0)

I 0.0 I 0.1 Q 8.0 (Q 4.0)

I 0.0 I 0.1 Q 8.0 (Q 4.0)

I 0.0 I 0.1 Q 8.0 (Q 4.0)

Page 87: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Editing BlocksPage 20

Remember ! You can only make program corrections after the program status has been completed. So that the program corrections can take effect, you have to download the block once more to the CPU.

Goal To expand and test the program in FC 1.

What to Do 1. Deactivate the program status by clicking on the “spectacles“ icon.2. Select the location between the first and the second contact.3. Insert a branch using the icon4. Insert a contact in the parallel branch.5. Close the parallel branch using the icon6. Save the block.7. Download the block in the CPU.8. Test the block with the test function "Program Status".

Result The output can also be controlled with the condition in the parallel branch.

Date: 05.12.2005File: PRO1_05E.20

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Expanding the Program in the FC 1 Block

(Q4.0)

Page 88: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Editing BlocksPage 21

Text You select the font and the size of the text to be used for programming here.

View You can display blocks:• with symbolic or absolute addressing• with or without symbol information• with or without block and network comments• in the language in which they were written or in a preset language

(LAD/STL/FBD).

Data Blocks You can display data blocks in the following views:• declaration view or• data view .

New Block You use the “STL”, “LAD”, “FBD” buttons to select the language in which you want to write a new block.Multi-instance function blocks are discussed in an advanced programming course.

Date: 05.12.2005File: PRO1_05E.21

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Editor Customization : "Editor" Tab

(Q4.0)

Page 89: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Editing BlocksPage 22

Status Fields When you monitor the status of a block in STL, only the status fields you activate in this dialog box will be displayed. The following options are available:• Status Bit The status bit is displayed. • RLO The result of logic operation (RLO) is displayed.• Standard Status A timer word, counter word or the contents of ACCU 1 are

displayed - depending on the operation used. • Address The address registers are used with indirect addressing.

Registers *)

• Accumulator 2 The contents of ACCU 2 are displayed.• DB Registers *) The contents of the relevant data block register are

displayed.• Indirect *) This display is only possible with memory-indirect

addressing.• Status Word The status word is displayed.• Default The “Default” button selects the standard system setting for

the Status field.The status bit, RLO and standard status are displayed.

• Activate New Breakpoints ImmediatelyThis option is only relevant for the the test function

“Breakpoint”.Note*) The topics “Indirect Addressing” , “DB Registers” and the structure of the status word

are discussed in an advanced programming course.

Date: 05.12.2005File: PRO1_05E.22

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Editor Customization : "STL" Tab

Page 90: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Editing BlocksPage 23

Layout Here you select the print format:• DIN A4 Portrait• DIN A4 Landscape• maximum size.

Width of Address You can set the limit for the maximum number of characters in an address nameField to a number between 10 and 24. This changes the width of the program element in LAD

and FBD. With symbolic representation, a line break takes place according to the Width of Address Field.

Element The program elements can be displayed in different ways:Representation • 2-dimensional or

• 3-dimensional.

Line/Color You use this box to choose how you want the following to be displayed• Selected Element (color)• Contacts (line)• Status Fulfilled (color and line)• Status Not Fulfilled (color and line)

Type Check When you edit a block, the type of address entered in bit logic instructions is always checked.You can deactivate the Type Check for Addresses for comparisons, mathematical operations etc. ( for experienced users only! ).

Date: 05.12.2005File: PRO1_05E.23

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Editor Customization : "LAD/FBD" Tab

Page 91: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Editing BlocksPage 24

Generate When you modify blocks and save them, the reference data is automaticallyReference Data updated, if the “Generate Reference Data" option in the “Create Block" tab is checked.

If this option is not checked, the reference data is not updated at first. But the next time you open the “Displaying S7 Reference Data" window, you must decide whether you want to update the reference data and for which blocks.Note: The topic "Reference Data" is discussed in detail in the Chapter“Troubleshooting".

Include The "Include System Attribute S7_server" option is only relevant in conjunctionSystem Attribute... with a process control system (PCS7) and is not dealt with in this course.

Store Process The "Store Process Diagnostics Data" option is only relevant when using theDiagnostics Data "PDIAG" option package and is not dealt with in this course.

Date: 05.12.2005File: PRO1_05E.24

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Editor Customization : "Create Block" Tab

Page 92: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Editing BlocksPage 25

Note Compiling source code blocks is discussed in more detail in the Chapter “Functions and Function Blocks".

Date: 05.12.2005File: PRO1_05E.25

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Editor Customization : "Source Files" Tab

Page 93: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Editing BlocksPage 26

Note Here you select the structure of the symbol selection list.You can activate and deactivate the display of the list when you make entries using the menu options View -> Display ->Symbol Selection in the Program Editor.If the Symbol Selection is activated, a list with the current symbols from the symbol table is displayed when you enter variables in LAD and FBD. In the list that is displayed, the symbol is marked that is best suited to the character chain at the cursor position. It can be accepted by pressing the Return key.

Date: 05.12.2005File: PRO1_05E.26

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Editor Customization : "Symbol Selection" Tab

Page 94: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Binary OperationsPage 1

Contents Page

Cyclical Program Execution …........................................................................................................... 2Process Images .................................................................................................................................... 3Program Structure ................................................................................................................................ 4Types of Program Blocks ................................................................................................................... 5Normally Open and Normally Closed Contacts. Sensors and Symbols............................................... 6Exercise .............................................................................................................................................. 7Addressing of S7-300 Modules ………................................................................................................ 8DI/DO Addressing in Multi-Tier Configurations ................................................................................. 9Binary Logic Operations: AND, OR ................................................................................................... 10Binary Logic Operations: Exclusive OR (XOR) ................................................................................ 11Result of Logic Operation, First Check. Examples…............................................................................. 12Assignment, Setting, Resetting............................................................................................................. 13Setting / Resetting a Flip Flop ........................................................................................................... 14Connector ............................................................................................................................................. 15Instructions that Affect the RLO …………............................................................................................ 16Master Control Relay Function ............................................................................................................ 17Unconditional Jump (Independent of RLO)........................................................................................... 18Conditional Jump (Dependent on RLO) .............................................................................................. 19RLO Edge Detection …........................................................................................................... ........... 20Signal Edge Detection ….................................................................................................................... 21Exercise: Program for a Bottling Plant (Mode Selection) ………….................................................... 22

Date: 05.12.2005File: PRO1_06E.1

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Binary Operations

I0.0 I0.1 Q 8.0

Q 8.1

SRS Q

R

I1.2

I1.3

M0.0Q 9.3

I 1.0

( MCR< )

(MCRA)

Q 8.0

I 0.0

I 1.1( )

Page 95: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Binary OperationsPage 2

Starting The CPU carries out a complete restart (with OB100) when switching on or when switching from STOP --> RUN. During a complete restart, the operating system deletes the non-retentive bit memories, timers and counters, deletes the interrupt stack and block stack, resets all stored hardware interrupts and diagnostic interrupts and starts the scan cycle monitoring time.

Scan Cycle The cyclical operation of the CPU consists of three main sections, as shown in the diagram above:

• The CPU checks the status of the input signals and updates the process-image input table.

• It executes the user program with the respective instructions.

• It writes the values from the process-image output table into the output modules.

Date: 05.12.2005File: PRO1_06E.2

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Execution of the program in OB1 (cyclical execution)

Events (time-of-day interrupt, hardware interrupts etc.) call other OBs, FBs, FCs, etc.

Cyclical Program Execution

OutputModule

A I 0.1A I 0.2= Q8.0

BlockOB 1

Start of the cycle monitoring time

Start-up block (OB 100)Execution once after e.g. power on

Reading the signal states from the modules and saving the data in the process image (PII)

Writing the process-image output table(PIQ) to the output modules

CPU

Cyc

leInputModule

Page 96: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Binary OperationsPage 3

Introduction The CPU checks the status of the inputs and outputs in every cycle. There are specific memory areas in which the module‘s binary data are stored: PII and PIQ. The programaccesses these registers during processing.

PII The process-image input table is found in the CPU‘s memory area. The signal state ofall inputs is stored there.

PIQ The process-image output table contains the output values that result from the program execution. These are sent to the actual outputs (Q) at the end of the cycle.

User Program When you check inputs in the user program with, for example, A I 2.0, the last state from the PII is evaluated. This guarantees that the same signal state is always delivered when there is multiple checking of the input within one cycle.

Date: 05.12.2005File: PRO1_06E.3

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Process Images

Byte 0Byte 1Byte 2:::

CPU Memory Area

Byte 0Byte 1Byte 2:::

PII PIQ

UserProgram

CPU Memory Area

::

A I 2.0= Q 4.3

::::

1

1

Page 97: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Binary OperationsPage 4

Linear Program The entire program is found in one continuous program block. This model resembles a hard-wired relay control, that was replaced by a programmable logic controller. The CPU processes the individual instructions one after the other.

Partitioned The program is divided into blocks, whereby every block only contains the Program program for solving a partial task. Further partitioning through networks is possible

within a block. You can generate network templates for networks of the same type.The organization block OB 1 contains instructions that call the other blocks in a defined sequence.

Structured A structured program contains blocks with parameters, so-called parameter Program assignable blocks. These blocks are designed in such a way that they can be used

universally. When a parameter assignable block is called, it is given current parameters (the exact addresses of inputs and outputs as well as parameter values).Example:• A "pump block" contains instructions for the control of a pump.• The program blocks, that are responsible for the control of special pumps, call the "pump block" and give it information about which pump is to be controlled with which parameters.• When the "pump block" has completed the execution of its instructions, the

program returns to the calling block (e.g. OB 1), which continues with the processing of its instructions.

Date: 05.12.2005File: PRO1_06E.4

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Program Partitioned into Areas Structured Program

Program Structure

All instructions arefound in one block(normally in the organization block OB 1)

The instructions for the indi-vidual functions are found inindividual blocks. OB 1 calls the individual blocks one after theother.

Reuseable functions are loaded into individual blocks.OB 1 (or other blocks) callthese blocks and pass on the pertinent data.

OB 1 OB 1

Recipe A

Recipe B

Mixer

Outlet

OB 1Pump

Outlet

Linear Program

Page 98: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Binary OperationsPage 5

User Blocks User blocks contain the program code and the user program data.In a structured user program, some blocks are called and processed cyclically, others only as required.

System Blocks System blocks are pre-defined functions or function blocks that are integrated in theCPU‘s operating system. These blocks do not occupy additional space in the user memory. System blocks are called from the user program. These blocks have the same interface, the same identifier and the same number throughout the entire system. The user program is thus easily transportable between various CPUs or programmable controllers.

Date: 05.12.2005File: PRO1_06E.5

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Types of Program Blocks

Error FB

FB

FB

FC

SFC

SFB

FB with instancedata block

Legend:

OB

OrganizationBlocks

Cycle

Time

Process

OB = Organization BlockFB = Function BlockFC = FunctionSFB = System Function BlockSFC = System Function

Operating System

Page 99: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Binary OperationsPage 6

Process The use of normally open or normally closed contacts for the sensors in a controlled process depends on the safety regulations for the process.Normally closed contacts are always used for limit switches and safety switches, so that dangerous conditions do not arise if a wire break occurs in the sensor circuit. Normally closed contacts are also used for switching off machinery for the same reason.

Symbols In LAD, a symbol with the name "NO contact" is used for checking for signal state "1" and a symbol with the name "NC contact" to check for signal state "0".It makes no difference whether the process signal “1” is supplied by an activated NO contact or a non-activated NC contact.

Example The result of check for the "NO contact" symbol is "1" if an NC contact in the machine is not activated.

Date: 05.12.2005File: PRO1_06E.6

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Normally Open and Normally Closed Contacts, Sensors and Symbols

Signalstateat input

Check for signal state “1”

Symbol /Instruction

Result ofcheck

Check for signal state “0”

Symbol /Instruction

Result ofcheck

Yes

Voltagepresent atinput?

No

Yes

No

1

0

1

“Yes“1

LAD:

“NO contact”

0&

FBD:

A I x.y

STL:

AN I x.y

STL:

&

FBD:

LAD:

“NC contact”

“No”0

“Yes”1

“No”0

“No”0

“Yes”1

“Yes”1

“No”0

Process Interpretation in PLC program

activated

notactivated

The sensoris ...

activated

notactivated

NOcontact

The sensoris a ...

NCcontact

Page 100: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Binary OperationsPage 7

Exercise Complete the programs above to obtain the following functionality: When switch S1 is activated and switch S2 is not activated, the light should be ON in all three cases.

Note ! The terms "NO contact" and "NC contact" have different meanings depending on whether they are used in the process hardware context or as symbols in the software.

Date: 05.12.2005File: PRO1_06E.7

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

ExerciseTask: In all three examples the light should be on when S1 is activated and S2 is not activated!

I1.0 I1.1 Q 4.0 I1.0 I1.1 Q 4.0

....... I1.0

....... I1.1

....... Q 4.0

Q 4.0

I 1.0

I1.1

&

Q 4.0

I1.0

I1.1

&

Q 4.0

I1.0

I1.1

&

....... I1.0

....... I1.1

....... Q 4.0

....... I1.0

....... I1.1

....... Q 4.0

Software

I1.0

S1

I1.1

S2

I1.0

S1

I1.1

S2

I1.0

S1

I1.1

S2

Q 4.0Programmable controller

LightLight Light

Q 4.0Programmable controller

Q 4.0Programmable controller

FDB

STL

LAD

Hardware

I 1.0 I 1.1 Q 4.0

I 1.0 I 1.1 I 1.0 I 1.1 I 1.0 I 1.1

Page 101: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Binary OperationsPage 8

Slot Numbers The slot numbers in the rack of an S7-300 simplify addressing within the S7-300 environment. The first address on a module is determined by the position of the module in the rack.

Slot 1 Power supply. This is the first slot by default. A power supply module is not absolutely essential. An S7-300 can also be supplied with 24V direct.

Slot 2 Slot for the CPU.

Slot 3 Logically reserved for an interface module (IM) for multi-tier configurations using expansion racks. Even if no IM is installed, it must be included for addressing purposes.You can physically reserve the slot (e.g. for installation of an IM at a later date) by inserting a DM370 dummy module.

Slots 4-11 Slot 4 is the first slot that can be used for I/O modules, communications processors (CP) or function modules (FM). Addressing examples:• A DI module in slot 4 begins with the byte address 0 .• The top LED of a DO module in slot 6 is called Q8.0 .

Note 4 byte addresses are reserved for each slot. When using 16-channel DI/DO modules, two byte addresses are lost in every slot!

Date: 05.12.2005File: PRO1_06E.8

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Addressing of S7-300 Modules

PS CPU SM SM SM SM SM SM SMModules

1 2 4 5 6 7 8 9 10Slot No.

Address 0.0Address 0.7Address 1.0Address 1.7

Page 102: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Binary OperationsPage 9

Multi-Tier The slots also have fixed addresses in a multi-tier configuration.Configurations

Examples:• Q7.7 is the last bit of a 32-channel DO module plugged into slot 5 of rack 0.• IB105 is the second byte of a DI module in slot 6 of rack 3.• QW60 is the first 2 bytes of a DO module in slot 11 of rack 1.• ID80 is all 4 bytes of a 32-channel DI module in slot 8 in rack 2.

Date: 05.12.2005File: PRO1_06E.9

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

DI/DO Addressing in Multi-Tier Configurations

Rack0

Slot 1 2 3 4 5 6 7 8 9 10 11

Rack3

96.0to99.7

100.0to

103.7

104.0to

107.7

108.0to

111.7

112.0to

115.7

116.0to

119.7

120.0to

123.7

124.0to

127.7

IM(Receive)

PS

Rack2

64.0to67.7

68.0to70.7

72.0to75.7

76.0to79.7

80.0to83.7

84.0to87.7

88.0to91.7

92.0to95.7

IM(Receive)

PS

Rack1

IM(Receive)

32.0to

35.7

36.0to

39.7

44.0to

47.7

48.0to

51.7

52.0to

55.7

56.0to

59.7

60.0to

63.7

40.0to

43.7

PS

0.0to3.7

20.0to

23.7

24.0to

27.7

28.0to

31.7

12.0to

15.7

16.0to

19.7

4.0to7.7

8.0to

11.7

IM(Send)

CPUPS

Page 103: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Binary OperationsPage 10

Logic Tables

AND I 0.0 I 0.1 Q 8.0

0 0

0 1

1 0

1 1

OR I 0.2 I 0.3 Q 8.2

0 0

0 1

1 0

1 1

Date: 05.12.2005File: PRO1_06E.10

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

L1(Q 8.0)

S1 (I 0.0)

S2 (I 0.1)

L2 (Q 8.1)

Circuit Diag.

Binary Logic Operations: AND, OR

I 0.2

I 0.3>=1

=Q 8.2 O I0.2

O I0.3= Q 8.2

I0.0 I0.1 Q 8.0

Q 8.1

LAD

=Q 8.0&I 0.0

I 0.1

=Q 8.1

FBD

A I0.0A I0.1= Q 8.0= Q 8.1

STL

I0.2

I0.3

Q 8.2

L3 (Q 8.2)

S3(I 0.2)

S4(I 0.3)OR

AND

Page 104: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Binary OperationsPage 11

Logic Table

XOR I 0.4 I 0.5 Q 8.0

0 0

0 1

1 0

1 1

Rule The following rule is valid for the logic operation of two addresses after XOR: the output has signal state "1", when one and only one of the two checks is fulfilled("one and only one of two" ).

Attention! This rule cannot be generalized to "one and only one of n" ! for the logic operation of several addresses after XOR !!As of the third XOR instruction, the old RLO is gated with the new result of check after XOR.

Date: 05.12.2005File: PRO1_06E.11

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Binary Logic Operations: Exclusive OR (XOR)

X I0.4X I0.5= Q8.0

I 0.4

I 0.5XOR

=Q 8.0

I0.4 I0.5

I0.4 I0.5

Q 8.0

LAD

>=1=

Q 8.0&I 0.4

I 0.5

&I 0.4

I 0.5

FBD STL

A I0.4AN I0.5OAN I0.4A I0.5= Q8.0

Page 105: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Binary OperationsPage 12

Signal State A logic operation is made up of a series of instructions to check the states of signals (inputs (I), outputs (Q), bit memories (M), timers (T), counters (C) or data bits (D) ) and instructions to set Q,M,T,C or D.

Result of Check When the program is executed, the result of check is obtained. If the check condition is fulfilled, the result of check is “1”. If it is not fulfilled, the result of check is “0”.

First Check The result of the first check is stored as the result of logic operation (RLO).

Result of Logic When the next check instructions are executed, the result of logic operation isOperation gated with the result of check and a new RLO is obtained.

When the last check instruction in a logic operation has been executed, the RLO remains the same. A number of instructions using the same RLO can follow.

Note The result of the first check is stored without being subjected to a logic operation. It therefore makes no difference whether you program the first check with an AND or an OR instruction in STL. To enable your program to be converted into one of the other programming languages, you should, however, always program using the correct instruction.

Date: 05.12.2005File: PRO1_06E.12

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Result of Logic Operation, First Check. Examples

A I 1.0

AN I 1.1

A M 4.0

= Q 8.0

= Q 8.1

A I 2.0

Example 1

Sig

nalS

tate

0

0

0

0

Res

ult o

fChe

ck

Res

ult o

f Log

icO

pera

tion

Firs

t Che

ck

Sig

nalS

tate

Res

ult o

fChe

ck

Res

ult o

f Log

icO

pera

tion

Firs

t Che

ck

1

Example 2

1

1

1

Sig

nalS

tate

Res

ult o

fChe

ck

Res

ult o

f Log

icO

pera

tion

Firs

t Che

ck

1

Example 3

0

1

0

Page 106: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Binary OperationsPage 13

Assignment An assignment passes the RLO on to the specified address (Q, M, D). When the RLO changes, the signal state of that address also changes.

Set If RLO= "1", the specified address is set to signal state "1" and remains set until it is reset by another instruction.

Reset If RLO= "1", the specified address is reset to signal state "0" and remains in this state until it is set again by another instruction.

Date: 05.12.2005File: PRO1_06E.13

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Assignment, Setting, Resetting

(S)Q 8.1I 1.2 I 1.3

I 1.2 &

SQ 8.1

I 1.3

A I 1.2A I 1.3S Q 8.1

Set

(R)Q 8.1I 1.4

I 1.4 >=1

RQ 8.1

I 1.5

O I 1.4O I 1.5R Q 8.1Reset I 1.5

( )Q 8.0I 1.0 I 1.1

I 1.0 &

=Q 8.0

I 1.1

A I 1.0A I 1.1= Q 8.0Assignment

LAD FBD STL

Page 107: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Binary OperationsPage 14

Flip Flop A flip flop has a Set input and a Reset input. The memory bit is set or reset, depending on which input has an RLO=1.If there is an RLO=1 at both inputs at the same time, the priority must be determined.

Priority In LAD and FBD there are different symbols for Dominant Set and Dominant Reset functions. In STL, the instruction that was programmed last has priority.

Note If an output is set with a Set instruction, it is reset on a complete restart of the CPU.If M 0.0 in the example above has been declared retentive, it will remain in the set state after a complete restart of the CPU and the reset output Q 9.3 will be be assigned the set state again.

Date: 05.12.2005File: PRO1_06E.14

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Setting / Resetting a Flip Flop

SR

R Q

SI1.2

I1.3

M0.0

=

Q9.3DominantReset

SRS Q

R

I1.2

I1.3

M0.0Q 9.3 A I 1.2

S M 0.0A I 1.3R M 0.0A M 0.0= Q 9.3

RS

S Q

RI1.3

I1.2

M0.0

=

Q9.3

DominantSet

RSR Q

S

I1.3

I1.2

M0.0Q 9.3 A I 1.3

R M 0.0A I 1.2S M 0.0A M 0.0= Q 9.3

LAD FBD STL

Page 108: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Binary OperationsPage 15

Connector A connector is an intermediate assignment element that stores the current RLO at a specified address.When connected in series with other elements, the "Connector" instruction is inserted in the same way as a contact.A connector must never:• be connected to a power rail• directly follow a branch• be used at the end of a branch.You can program a negated connector with the "NOT" element.

Date: 05.12.2005File: PRO1_06E.15

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Connector

LAD

I 1.0 I 1.1

( )M0.0 I 2.0 I 2.1

( )M 1.1

NOT ( )Q 4.0

A I 1.0A I 1.1= M 0.0A M 0.0A I 2.0A I 2.1NOT= M 1.1A M 1.1= Q 4.0

STL

I 1.0

I 1.1

&

&

I 2.0

I 2.1

M0.0

M1.1 Q 4.0

=

FBD

Page 109: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Binary OperationsPage 16

NOT The NOT instruction inverts the RLO.

CLR The CLEAR instruction changes the RLO to "0" (only available in STL at present!).

SET The SET instruction changes the RLO to "1" (only available in STL at present!).

SAVE The SAVE instruction saves the RLO as "BR" in a register (status word).

BR The statement “A BR" can be used to recheck the saved RLO.

Date: 05.12.2005File: PRO1_06E.16

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Instructions, that Affect the RLOLAD FBD STL

A I0.0 A I0.1 NOT = Q8.0

=Q8.0&I0.0

I0.1( ) Q8.0

NOTI0.0 I0.1NOT

Status word15 8 1

BR RLO

not available not availableCLR CLR

not available not availableSET SET

I1.6( SAVE ) SAVE&I1.6SAVE A I1.6

SAVE

=Q8.1

BRBR

( )Q8.1

BR A BR= Q 8.1

Page 110: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Binary OperationsPage 17

MCR The Master Control Relay is a logical master switch for activating and deactivating power flow. An interrupted path represents a sequence that writes a zero value in place of a calculated value or a sequence that does not change the existing memory value.

Examples If the MCR condition is not fulfilled:• "0" is assigned via the output coils• the "Set Coil" and "Reset Coil" instructions do not change the existing value• the “MOVE” instruction transfers the value zero to the specified destination.

MCRA The MCRA instruction activates the Master Control Relay function.

MCR( “MCR(“ opens an MCR area and triggers an instruction that shifts the RLO to (for STL) the MCR stack. The stack can have up to eight entries. This means that up to eight

individual control areas can be nested between the “MCRA” and “MCRD” instructions.

)MCR The “)MCR“ instruction marks the end of an MCR area. (for STL)

MCRD The "Deactivate Master Control Relay” instruction deactivates the MCR function. No more MCR areas can be opened until another “MCRA” instruction is given.

Date: 05.12.2005File: PRO1_06E.17

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Master Control Relay Function

MCR<&A0.0

MCRA

S&A0.4Q16.0

MCR>

& =M5.5 M69.0I4.7

MCRD

& =A0.7Q8.5

M0.6=

FBD

MCRA // Activated

A I0.0 // Enable MCRMCR( // Open MCR

A I0.7 // NO Contact= Q8.5 // Output Coil= M0.6 // Output Coil

A I0.4 // NO ContactS Q16.0 // Set Output

)MCR // Close MCR

AN M5.5 // Emerg.ContactAN I4.7 // Emerg.Contact= M69.0 // Output Coil

MCRD // Deactivate

STLLAD

( MCRA )

I0.7( )Q8.5

( )M0.6

I0.4( S )Q16.0

( )M69.0 I4.7M5.5

( MCR< )

( MCRD )

( MCR> )

I0.0

Page 111: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Binary OperationsPage 18

Jump Instruction In LAD/FBD, the label is entered as an identifier above the coil symbol or assignment symbol. In STL it comes after the Jump instruction. The label can have up to four characters, the first of which must be a letter or the “_”character.The label marks the point where execution of the program is to continue. Any instructions or networks between the jump instruction and the label are not executed.Jumps can be made both forwards and backwards. The jump instruction and the jump destination must both be in the same block (max. jump length = 64kbyte). The jump destination must only be present once in the block.Jump instructions can be used in FBs, FCs and OBs.

Inserting In LAD aund FBD, you use the Program Elements browser to insert a label:a Label Program Elements -> Logic Control / Jump -> Label.

In STL, you enter the label to the left of the statement, from which program exeuction is to continue.

JMP An unconditional jump instruction causes a program jump to a label regardless of the RLO.

Date: 05.12.2005File: PRO1_06E.18

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Unconditional Jump (Independent of RLO)

( JMP )NEW1

Network 1

Network 2::::Network x

NEW1

( )M69.0I4.7M5.5

LAD

NEW1JMP....

NEW1

&M5.5I 4.7 =

M69.0

Network 1

Network 2::::Network x

FBD

Network 1

JU NEW1

Network 2::::Network x

NEW1: AN M5.5AN I4.7= M69.0

STL

Page 112: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Binary OperationsPage 19

JC The conditional jump “JC” is only executed if the RLO is “1”.If the RLO is “0”, the jump is not executed, the RLO is set to “1” and program execution continues with the next instruction.

JCN The conditional jump “JCN” is only executed if the RLO is "0".If the RLO is "1", the jump is not executed and program execution continues with the next instruction.

Note STL provides additional jump operations, which are discussed in another programming course.

Date: 05.12.2005File: PRO1_06E.19

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Conditional Jump (Dependent on RLO)

A I0.0A I0.1JC NEW1

NEW1I 0.0 I 0.1 &I0.0

I0.1 JMPNEW1

(JMP)Jump ifRLO=1

A I0.2A I0.3JCN NEW2JMPN

I0.2

I0.3NEW2NEW2I 0.2 I 0.3Jump if

RLO=0(JMPN)

&

LAD FBD STL

Page 113: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Binary OperationsPage 20

RLO Edge An "RLO edge" is when the result of a logic operation changes.

Positive Edge When the RLO changes from “0” to “1”, the "FP" check instruction results in signal state "1" (e.g. at M 8.0) for one cycle. To enable the system to detect the edge change, the RLO must also be saved in an FP bit memory, or data bit (e.g. M 1.0).

Negative Edge When the RLO changes from “1” to “0”, the "FN" check instruction results in signal state “1” (e.g. at M 8.1) for one cycle. To enable the system to detect the edge change, the RLO must also be saved in an FN bit memory, or data bit (e.g. M 1.1).

Date: 05.12.2005File: PRO1_06E.20

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

RLO - Edge Detection

PI1.0 I1.1 M1.0 M8.0

NI1.0 I1.1 M1.1 M8.1

LAD

I1.0

I1.1 P =

& M1.0 M8.0

I1.0

I1.1 N =

& M1.1 M8.1

FBD

A I1.0A I1.1FP M1.0= M8.0

A I 1.0A I 1.1FN M1.1= M8.1

STL

I1.0

I1.1

RLO

M1.0

M8.0M8.1

M1.1

OB1-Cycle

Example

Page 114: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Binary OperationsPage 21

Signal Edge A "signal edge" is when a signal changes its state.

Example Input I 1.0 acts as a static Enable. Input I 1.1 is to be monitored dynamically and every signal change is to be detected.

Positive Edge When the signal state at I 1.1 changes from “0” to “1”, the "POS" check instruction results in signal state "1" at output Q for one cycle, provided input I 1.0 also has signal state "1" (as in the example above).To enable the system to detect the edge change, the signal state of I 1.1 must also be saved in an M_BIT (bit memory or data bit) (e.g. M 1.0).

Negative Edge When the signal state at I 1.1 changes from “1” to “0” , the "NEG" check instruction results in signal state "1" at output Q for one cycle, provided input I 1.0 has signal state "1" (as in the example above).To enable the system to detect the edge change, the signal state of I 1.1 must also be saved in an M_BIT (bit memory or data bit) (e.g. M 1.1).

Date: 05.12.2005File: PRO1_06E.21

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Signal - Edge Detection

I1.1

=M8.0POS

M_BITM1.0

&I1.0

I1.1

=M8.1NEG

M_BITM1.1

&I1.0

FBD

A I1.0A ( A I1.1FP M1.0)= M8.0A I1.0A (A I1.1FN M1.1)= M8.1

STL

I1.1M8.0

POS

M_BITM1.0

Q

I1.0

I1.1M8.1

NEG

M_BITM1.1

Q

I1.0

LAD

Example

I1.0

I1.1

M1.0

M8.0

M8.1

M1.1OB1-Cycle

Page 115: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Binary OperationsPage 22

Task Write a mode section of a program for a bottling plant to meet the following specifications:• Input I 0.0 (momentary-contact switch with NO function) switches the plant ON.• Input I 0.1 (momentary-contact switch with NC function) switches the plant

OFF.• When the plant is ON, the indicator at output Q 8.1 (Q 4.1) is lit.• When the plant is ON, the operating mode can be selected:

- Manual mode is selected when I 0.4=0 and automatic mode when I 0.4=1.

- The selected mode is adopted with a pulse at input I 0.5 .• The indicators for the selected mode are as follows:

Manual = Q 8.2 (Q 4.2), Automatic = Q 8.3 (Q 4.3).• When the mode is changed or the plant is switched off, the mode previously

selected must be deselected. • In manual mode, the conveyor can be jogged forwards with the momentary-

contact switch I 0.2 (Q 20.5 / Q 8.5) and backwards with I 0.3(Q 20.6 / Q 8.6).

What to Do 1. Draft out the program for controlling the operating modes. Use the I/O addresses and field devices shown in the diagram.

2. Create an S7 program with the name "FILL" in the project "My Project".3. Write the mode section of the program for the bottling plant in block FC 15.4. Open (off-line) the OB1 and enter a call to FC15

(in STL with the statement “CALL FC 15”).5. Save your program, download it and test it on the training unit.

Result It should work.

Date: 05.12.2005File: PRO1_06E.22

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Program for a Bottling Plant (Mode Selection)

Q 20.5 (Q 8.5) Conveyor forwardsQ 20.6 (Q 8.6) Conveyor backwards

BottlesensorI 16.6 (I 8.6)

I 0.0 =I 0.1 =

Start (Mom.-cont. switch with NO function)Stop (Mom.-cont. switch with NC function)

Plant ON/OFF:

I 0.4 = Manual/Automatic (Switch)Adopt mode (Momentary-contact switch, NO function)

Manual/Automatic mode:

I 0.5 =

I 0.2 = Jog forward (M-C sw., NO funct.)Jog backward (M-C sw., NO func.)I 0.3 =

M

Page 116: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Digital OperationsPage 1

Contents Page

Number Formats (16 Bits) ................................................................................................................... 2Number Formats (32 Bits) .................................................................................................................. 3Loading and Transferring Data (1) ……............................................................................................ 4Loading and Transferring Data (2) ……............................................................................................ 5Loading and Transferring Data (3) ……............................................................................................ 6Timers: Time Formats for S5 Timers in STEP 7 ................................................................................. 7Timers: ON Delay (SD) …………....................................................................................................... 8Timers: Stored ON Delay (SS) …………………................................................................................ 9Timers: OFF Delay (SF) …………..................................................................................................... 10Timers: Pulse (SP) ............................................................................................................................. 11Timers: Extended Pulse (SE) …......................................................................................................... 12Timers: Bit Instructions ….................................................................................................................. 13Exercise .............................................................................................................................................. 14S5 Counters in STEP 7 ...................................................................................................................... 15Counters: Bit Instructions ................................................................................................................ 16Counters: Function Diagram ............................................................................................................ 17Exercise: Program for a Bottling Plant (Filling Cycle and Bottle Count) ………….............................. 18Conversion Operations BCD <-> Integer …...................................................................................... 19Conversion Operations I -> DI -> REAL ……..................................................................................... 20Comparision Operations .................................................................................................................... 21Digital Logic Operations .................................................................................................................... 22Basic Mathematical Functions ……………......................................................................................... 23Exercise: Program for a Bottling Plant (Production Data) …….......................................................... 24Exercise: Program for a Bottling Plant (Number of Packaging Units) ……………............................. 25Shift Operations (Word / Doubleword) …........................................................................................... 26Shift Signed Integer to the Right ……………………........................................................................... 27Doubleword Rotation Operations ....................................................................................................... 28

Date: 05.12.2005File: PRO1_07E.1

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Digital Operations

CMP ==I

IN1IN2

IW0IW2

M0.0 Q 9.7

T4S_ODT

TV

S Q

BCD

BI

R

I0.7

I0.5S5T#35s

Q8.5

MW0

QW12

Page 117: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Digital OperationsPage 2

BCD Code Each digit of a decimal number is encoded in four bit positions. Four bits are used because the highest decimal digit, 9, requires at least four bit positions in binary code ( 1001).The decimal digits from 0 to 9 are represented in BCD code in the same way as the binary numbers from 0 to 9.

INTEGER The data type INT is an integer (16 bits). The sign (bit 15) indicates whether the number is positive or negative ("0" = positive, "1" = negative). A 16-bit integer can be between -32 768 and +32 767. In binary format, the negative form of an integer is represented as the twos complement of the positive integer. (The twos complement is obtained by reversing the bit pattern and then adding 1.)In evaluating the bit pattern of a negative number, the zero positions are weighted, then 1 is added to the result and a minus sign is placed in front.

Date: 05.12.2005File: PRO1_07E.2

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Number Formats (16 Bits)

BCD

INTEGER

BCD

28

= 256 +

0 0 0 0 0 0 0 1 0 0 1 0 1 0 0 0

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

25

= 32 +

23

= 8 = 296

0 0 0 0 0 0 1 0 1 0 0 1 0 1 1 0

2 9 6Sign (+)

1 1 1 1 0 1 0 0 0 0 0 1 0 0 1 1

4 1 3Sign (-)W#16#F413

27

= 128 +

1 1 1 1 1 1 1 0 0 1 1 0 0 0 1 1

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

23

= 8+

22

= 4 = 412

28

= 256+

24

= 16+

- (412 + 1) = - 413

NegativeNumbers

INTEGER

PositiveNumbers

W#16#296

+296

-413

PG CPU

Page 118: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Digital OperationsPage 3

DINT 32-bit integers with sign are also referred to as "double integers” or “long integers”.They cover the range from L# -2147483648 to L#+2147483647.

REAL A real number (also known as a floating-point number) is a positive or negative number in the range from -1.175495•10-38 to 3,402823•1038 .Examples: +10.339 or +1.0339E1

-234567 or -2.34567E5. In exponential representation the exponent is specified as a power of 10.A real number takes up two words in memory. The most significant bit indicates the sign. The other bits represent the mantissa and the exponent to the base 2.

Note: The representation of real numbers in STEP 7 is in accordance with the IEEEstandard.

Date: 05.12.2005File: PRO1_07E.3

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Number Formats (32 Bits)

Real No = +1,5 * 2 126-127 = 0,75

DW#16#296

+296

+0.75or

+7.5 E-1

0 0 0 0 0 0 0 1 0 0 1 0 1 0 0 00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 031 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16

28

= 256 +

25

= 32 +

23

= 8 = 296Integer (32 Bit) =

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 00 0 1 1 1 1 1 1 0 1 0 0 0 0 0

Sign ofReal No

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 031 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16

e = Exponent (8 Bit) f = Mantissa (23 Bit)

General Format of a Real Number = (Sign) • (1.f) • (2e-127)

2021222324252627 2-232-1 2-2 2-4 .....2-3

0 0 0 0

0 0 0Sign (+)

00 0 0 0 0 1 0 1 0 0 1 0 1 1 0

2 9 60

0 0 00 0 00 0 0 0 0 0

BCD

DINT

REAL

Page 119: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Digital OperationsPage 4

MOVE (LAD/FBD) If the EN input is active, the value at input “IN” is copied to the address at output “OUT”. “ENO” has the same signal state as “EN”.

L and T (STL) Load and Transfer instructions are executed regardless of the RLO. Data is exchanged via the accumulator. The Load instruction writes the value from the source address right-justified into accumulator 1 and pads the remaining bits (32 bits in all) with "0"s.The Transfer instruction copies some or all of the contents of the accumulator to the specified destination (see next page).

Date: 05.12.2005File: PRO1_07E.4

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Examplesof Load

Loading and Transferring Data (1)

L +5 // 16-bit constant (Integer)

L L#523123 // 32-bit constant (DoubleInteger)

L B#16#EF // byte in hexadecimal form.

L 2#0010 0110 1110 0011 // 16-bit binary value

L 3.14 // 32-bit constant (Real)

MOVE

EN

IN

OUT

ENO

MB5

5

FBD

L +5

T MB5

STL

MOVE

EN

OUT

ENO

MB5

LAD

IN5

Page 120: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Digital OperationsPage 5

ACCU1 ACCU 1 is the central register in the CPU. When a Load instruction is executed, the value to be loaded is written into ACCU 1; for a Transfer instruction the value to be transferred is read from ACCU 1, and the results of the mathematical functions, Shift and Rotate operations, etc. are also entered in ACCU 1.

ACCU2 When a Load instruction is executed, the old contents of ACCU 1 are first shifted to ACCU 2 and ACCU 1 is cleared (reset to “0”) before the new value is written into ACCU 1.

ACCU 2 is also used for comparison operations, digital logic operations, mathematical and Shift operations. These operations will be discussed in detail later on.

Date: 05.12.2005File: PRO1_07E.5

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Loading and Transferring Data (2)

0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0

::L W#16#CAFE

L W#16#AFFE:::

X X X X X X X XC A F E

A F F E

Content ofACCU2

Content ofACCU1Programm

Y Y Y Y Y Y Y YX X X X X X X X

0 0 0 0 C A F E

Page 121: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Digital OperationsPage 6

General Accumulators are auxiliary memories in the CPU for data exchange between various addresses and for comparison and mathematical operations.The S7-300 has 2 accumulators with 32 bits each and the S7-400 has 4 accumulators with 32 bits each.

Load The Load instruction loads the contents of the specified byte, word or double word into ACCU 1.

Transfer When a Transfer instruction is executed, the contents of ACCU 1 are retained. The same information can therefore be transferred to different destinations. If only one byte is transferred, the eight bits furthest to the right are used (see diagram).

RLO In LAD and FBD you can use the Enable input (EN) of the MOVE box to make Load and Transfer operations dependent on the RLO. In STL Load and Transfer operations are always executed, regardless of the RLO, but you can implement RLO-dependent load and transfer by using conditional jumps to skip the Load / Transfer instructions.

Date: 05.12.2005File: PRO1_07E.6

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Loading and Transferring Data (3)

31 23 15 7 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 MB0

31 23 15 7 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 MB1MB0

31 23 15 7 0

MB3MB2MB0 MB1

Load

L MB 0

Program

T QD 4

QD 4

QW 4

QB 4

Transfer

Contents of ACCU1

L MW 0

L MD 0

T QW 4

T QB 4

Page 122: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Digital OperationsPage 7

Time Specifications 1. Fixed time values specified as time constants (e.g.: S5T#100ms, S5T#35s, S5T#5m2s200ms, S5T#2h2m2s50ms).

2. Time values to be changed by the machine operator using pushwheel buttons.3. Process or recipe-dependent time values in memory words or data words.

Timer Cell A special area of memory is reserved for timers in your CPU. This area containsa 16-bit word for each timer address. Bits 0 to 9 of the timer word contain the time value in binary code. When the timer is updated, the time value is decremented by one unit at the interval defined by the time base.

Time Base Bits 12 and 13 of the timer word contain the time base in binary code:0 = 10 ms1 = 100 ms2 = 1 s3 = 10 s.

The time base defines the interval at which the time value is to be decremented by one unit. When the time is specified as a constant (S5T#...), the time base is assigned automatically by the system. If the time is to be specified using pushwheelbuttons or via a data interface, the user must also specify the time base.

L / BI The address at the “BI” output contains the time value in the form of a 10-digit binary number (without time base!).

LC / BCD The address at the “BCD” output contains both the time value as a 3-digit BCD number (12 bits) and the time format (bits 12 and 13).

Note IEC-compliant timers can also be implemented in STEP7.The use of system function blocks for implementing IEC timers is dealt with in an advanced programming course.

Date: 05.12.2005File: PRO1_07E.7

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Timers: Time Formats for S5 Timers in STEP 7

Format for time specifications

Timer cell in system data memory

ACCU contents after “LC T...”

ACCU contents after “L T...”

Time base

102 101 100

Time value (BCD code)

Time base Time value (Binary number)

Time base

102 101 100

Time value (BCD code)

Time value (Binary number)

X X X X

X X

X X X XX X

X X

Page 123: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Digital OperationsPage 8

Start The timer starts when the RLO at the "S" input changes from “0” to “1”. The timer runs starting with the time value specified at the TV input as long as the signal state at input S =1.

Reset When the RLO at Reset input "R" is "1", the current time value and the time base are deleted and output Q is reset.

Digital Outputs The current time value can be read as a binary number at the BI output and as a BCD number at the BCD output. The current time value is the initial value of TV minus the value for the time that has elapsed since the timer was started.

Binary Output The signal at the "Q" output changes to "1" when the timer has expired without error and input "S" has signal state "1".If the signal state at the "S" input changes from "1" to "0" before the timer has expired, the timer stops running. In this case output “Q” has signal state "0".

Date: 05.12.2005File: PRO1_07E.8

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Timers: ON Delay (SD)LAD

T4S_ODT

TV

S Q

BCD

BI

R

I0.7

I0.5S5T#35s

Q8.5

MW0

QW12

FBD

S_ODT

TV

Q

BI

R

I0.7

I0.5

S5T#35s

MW0

QW12

T4

BCD

=Q8.5

S

STL

A I0.7L S5T#35sSD T4A I0.5R T4L T4T MW0LC T4T QW12A T4= Q8.5

Example

RLO at S

RLO at R

Timeroperation

Q

Time value: 0 . . . 999

0,01s <--0,1s <--

1s <--10s <--

0 00 11 01 1

Data type“S5TIME”

Page 124: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Digital OperationsPage 9

Start The timer starts when the RLO at the "S" input changes from "0" to "1". The timer runs starting with the time value specified at input TV and continues to run even if the signal at input "S" changes to "0" during that time.If the signal at the Start input changes from “0” to “1” again while the timer is still running, the timer starts again from the beginning.

Reset When the RLO at Reset input "R" is "1", the current time value and the time base are deleted and output Q is reset.

Binary Output The signal state at output Q changes to "1" when the timer has expired without error, regardless of whether the signal state at the "S" input is still "1".

Date: 05.12.2005File: PRO1_07E.9

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Timers: Stored ON Delay (SS)

STL

A I0.7L S5T#35sSS T4A I0.5R T4L T4T MW0LC T4T QW12A T4= Q8.5

LAD

T4S_ODTS

TV

S Q

BCD

BI

R

I0.7

I0.5S5T#35s

Q8.5

MW0

QW12

FBD

S_ODTS

TV

Q

BI

R

I0.7

I0.5

S5T#35s

MW0

QW12

T4

BCD

=Q8.5

S

Example

RLO at S

RLO at R

Timer operation

Q

Page 125: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Digital OperationsPage 10

Start The timer starts when the RLO at the "S" input changes from “1” to “0”. When the timer has expired, the signal state at output Q changes to "0". If the signal state at the "S" input changes from “0” to “1” while the timer is running, the timer stops and the next time the signal state changes from "1" to "0" it starts again from the beginning.

Reset When the RLO at Reset input "R" is "1", the current time value and the time base are deleted and output Q is reset. If both inputs (S and R) have signal state “1”, output “Q” is not set until the dominant Reset is deactivated.

Binary Output Output "Q" is activated when the RLO at the "S" input changes from “0” to “1”. If input “S” is deactivated, output “Q” continues to have signal state “1” until the programmed time has expired.

Date: 05.12.2005File: PRO1_07E.10

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Timers: OFF Delay (SF)

STL

A I0.7L S5T#35sSF T4A I0.5R T4L T4T MW0LC T4T QW12A T4= Q8.5

LAD

T4S_OFFDT

TV

S Q

BCD

BI

R

I0.7

I0.5S5T#35s

Q8.5

MW0

QW12

FBD

S_OFFDT

TV

Q

BI

R

I0.7

I0.5

S5T#35s

MW0

QW12

T4

BCD

=Q8.5

S

Example

RLO at S

RLO at R

Timer operation

Q

Page 126: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Digital OperationsPage 11

Start The timer starts when the RLO at the “S” input changes from “0” to “1”. Output “Q” isalso set to “1”.

Reset Output “Q” is reset when: • the timer has expired, or • the Start signal changes from “1” to “0”, or• the Reset input “R” has signal state “1”.

Date: 05.12.2005File: PRO1_07E.11

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Timers: Pulse (SP)

FBD

S_PULSE

TV

Q

BI

R

I0.7

I0.5

S5T#35s

MW0

QW12

T4

BCD

=Q8.5

S

RLO at S

RLO at R

Timer operation

Q

Example

STL

A I0.7L S5T#35sSP T4A I0.5R T4L T4T MW0LC T4T QW12A T4= Q8.5

MW0

LAD

T4S_PULSE

TV

S Q

BCD

BI

R

I0.7

I0.5S5T#35s

Q8.5

QW12

Page 127: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Digital OperationsPage 12

Start The timer starts when the RLO at the "S" input changes from “0” to “1”. Output "Q" is also set to “1”. The signal state at output “Q” remains at “1” even if the signal at the "S" input changes to “0”.If the signal at the Start input changes from “0” to “1” again while the timer is running, the timer is restarted.

Reset Output “Q” is reset when: • the timer has expired, or • the Reset input "R" has signal state "1".

Date: 05.12.2005File: PRO1_07E.12

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Timers: Extended Pulse (SE)LAD

T4S_PEXT

TV

S Q

BCD

BI

R

I0.7

I0.5S5T#35s

Q8.5

MW0

QW12

FBD

S_PEXT

TV

Q

BI

R

I0.7

I0.5

S5T#35s

MW0

QW12

T4

BCD

=A8.5

S

RLO at S

RLO at R

Timer Operation

Q

Example

STL

A I0.7L S5T#35sSE T4A I0.5R T4L T4T MW0LC T4T QW12A T4= Q8.5

Page 128: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Digital OperationsPage 13

Bit Instructions All timer functions can also be started with simple bit instructions. The similarities and differences between this method and the timer functions discussed so far are as follows:• Similarities:

- Start conditions at the "S" input- Specification of the time value- Reset conditions at the “R” input- Signal response at output “Q”

• Differences (for LAD and FBD):- It is not possible to check the current time value (there are no BI and

BCD outputs).

Date: 05.12.2005File: PRO1_07E.13

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Timers: Bit Instructions

I0.0 T4SD

S5T#5s

T4 Q 8.0

I0.1 T4R

Network 1:

Network 2:

Network 3:

LAD

& SD

T4

I0.0

S5T#5s

& =Q 8.0

T4

&I0.1

TV

RT4

FBD

A I0.0L S5T#5sSD T4

A T4= Q 8.0

A I0.1R T4

STL

Page 129: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Digital OperationsPage 14

Date: 05.12.2005File: PRO1_07E.14

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise

T4S_PEXT

STVR

BIBCD

Q

I 0.7S5T#5s

I 0.5 Q 8.0

I 0.7

I 0.5

Q8.0

T4S_PULSE

STVR

BIBCD

Q

I 0.7S5T#5s

I 0.5 Q 8.0

I 0.7

I 0.5

Q8.05s

T4S_ODT

STVR

BIBCD

Q

I 0.7S5T#5s

I 0.5 Q 8.0

I 0.7

I 0.5

Q8.0

T4S_ODTS

STVR

BIBCD

Q

I 0.7S5T#5s

I 0.5 Q 8.0

I 0.7

I 0.5

Q8.0

I 0.7

I 0.5

Q8.0

T4S_OFFDT

STVR

BIBCD

Q

I 0.7S5T#5s

I 0.5 Q 8.0

Exercise Complete the function diagrams of the timers in the above slide!

Page 130: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Digital OperationsPage 15

Counter Value A 16-bit word is reserved for each counter in the system data memory. This is used for storing the counter value for the counter (0...999) in binary code.

Count Up When the RLO at the “CU” input changes from “0” to “1” the current counter reading is incremented by 1 (upper limit = 999).

Count Down When the RLO at the “CD” input changes from “0” to “1” the current counter reading isdecremented by 1 (lower limit = 0).

Set Counter When the RLO at the "S" input changes from “0” to “1” the counter is set to the value at the “CV” input.

Reset Counter When RLO = 1 the counter is set to zero. If the Reset condition is fulfilled, the counter cannot be set and counting is not possible.

PV The preset value (0...999) is specified in BCD at the „PV“ input:• as a constant (C#...)• in BCD format via a data interface.

CV / CV_BCD The counter value can be loaded as a binary number or BCD number into the accumulator and transferred from there to other addresses.

Q The signal state of the counter can be checked at output “Q”:• Count = 0 -> Q = 0• Count >< 0 -> Q = 1

Types of Counter • S_CU = Up counter (counts up only)• S_CD = Down counter (counts down only)• S_CUD = Up/Down counter.

Date: 05.12.2005File: PRO1_07E.15

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

S5 Counters in STEP 7STL

A I0.4CU C5A I0.5CD C5A I0.3L C#20S C5A I0.7R C5L C5T MW4LC C5T QW12A C5= Q8.3

LAD FBD

QI 0.4

I 0.5

CU

I 0.7

C#20

S_CUD

CD

SI 0.3

PV

R

Q 8.3

CV

CV_BCD

MW 4

QW 12

C5

Q

Q

I 0.4

I 0.5

CU

I 0.7

C#20

S_CUD

CD

SI 0.3

PV

R

Q 8.3

CV

CV_BCD

MW 4

QW 12

C5

=Q

Page 131: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Digital OperationsPage 16

Bit Instructions All counter functions can also operate with simple bit instructions. The similarities and differences between this method and the counter functions discussed so far are as follows:• Similarities:

- Setting conditions at the "SC" input- Specification of the counter value- RLO change at the "CU" input- RLO change at the "CD" input

• Differences:- It is not possible to check the current counter value

(there are no BI and BCD outputs).- There is no binary output Q in the graphical representation.

.

Note IEC-compliant counters can also be implemented in STEP 7. The use of system function blocks for implementing IEC counters is dealt with in an advanced programming course.

Date: 05.12.2005File: PRO1_07E.16

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Counters: Bit InstructionsSTL

A I0.0L C#20S C5

A I0.1CU C5

A I0.2CD C5

A C5= Q 4.0

LAD

I0.0 C5SC

C#20

Network 1:

C5

Network 2:

I0.1CU

Network 3:

I0.2 C5CD

Network 4:

C5 Q 4.0

FBD

SCC5

I0.0

C#20 CV

CUC5

I0.1

CDC5

I0.2

=Q 4.0

C5

Page 132: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Digital OperationsPage 17

Notes If the counter reaches the value 999 during up counting, or the value 0 during downcounting, then the count remains unchanged even in the case of further counting pulses.

If up counting and down counting is lined up at the same time, the count remains the same.

Date: 05.12.2005File: PRO1_07E.17

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Counters: Function Diagram

CU

CD

S

R

Q

Count

5

4

3

2

1

0

Page 133: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Digital OperationsPage 18

Goal To add new functions to the bottling plant program. In addition to the already programmed manual mode (FC15), a program for the automatic mode is to be created.

Conveyor Control When the conveyor belt motor (Q 20.5 / Q 8.5) is switched on in automatic mode, in Automatic Mode it remains on until it is switched off with the Stop switch (I 0.1) or until the sensor

(I 16.6 / I 8.6) detects a bottle. When the bottle has been filled, the conveyor must automaticallly start moving again and keep moving until another bottle is detected or theStop switch is operated.

Bottle Filling When a bottle is detected under the filling funnel (I 16.6 / I 8.6 =1), filling begins. Filling is simulated for 3 seconds and indicated at output Q 9.0 (Q 5.0).

Bottle Counting Another two sensors are provided for registering the full and empty bottles. Bottle sensor I 16.5 (I 8.5) registers the empty bottles and bottle sensor I 16.7 (I 8.7) registers the full bottles.Both the empty bottles and the full bottles are to be counted from the time when the plant is switched on (C 1 for the empty bottles and C 2 for the full bottles) and the number of full bottles is to be displayed on digital display QW 12 (QW 6).

What to Do 1. Write the program in block FC 16 and program a call to FC 16 in OB 1 (project "MyProject", "FILL“ program).

You must also modify the network in FC 15 containing the “Jog Conveyor Forwards” program.

2. Test your solution on the training unit.

Result It should work.

Date: 05.12.2005File: PRO1_07E.18

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Maincontainer

Q 9.0 (Q 5.0)Filling funnelBottle

sensorI 16.6 (I 8.6)Bottle sensor

I 16.5 (I 8.5)

Bottle sensorI 16.7 (I 8.7)

Exercise: Program for a Bottling Plant (Filling Cycle and Bottle Count)

Q 20.5 (Q 8.5) Conveyor forwardsQ 20.6 (Q 8.6) Conveyor backwards

I 0.0 = Start (NO contact, mom-cont. switch)I 0.1 = Stop (NC contact)

Plant ON/OFF:

I 0.4 = Manual /AutomaticI 0.5 = Adopt mode

Manual/Automatic mode:

I 0.2 = Jog forwards

I 0.3 = Jog backwards

M

Page 134: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Digital OperationsPage 19

Example A user program is to perform mathematical functions using values entered withpushwheel buttons and display the result on a digital display. Mathematical functions cannot be performed in BCD format, so the format must be changed.

Conversion The instruction set of the S7-300/400 supports a multitude of conversionInstructions facilities. The instructions all have the same format:

EN, ENO If RLO is =1 at Enable input EN, the conversion is performed. Enable output ENO always has the same signal state as EN. If this is not the case, it is clearly indicated inthe corresponding instructions.

IN When EN=1, the value at IN is read into the conversion instruction.

OUT The result of the conversion is stored at the address at the OUT output.

BCD_I / BTI (Convert BCD to integer) reads the contents of the IN parameter as a three-digit BCD number (+/- 999) and converts it to an integer value (16 bits).

I_BCD / ITB (Convert integer to BCD) reads the contents of the IN parameter as an integer value(16 bits) and converts this value to a three-digit BCD number (+/- 999). If an overflow occurs, ENO = 0.

BCD_DI / BTD Converts a BCD number (+/- 9999999) to a double integer (32 bits).

DI_BCD / DTB Converts a double integer to a seven-digit BCD number (+/- 9999999). If an overflow occurs, ENO = 0.

Date: 05.12.2005File: PRO1_07E.19

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Conversion Operations BCD <-> Integer

IN

BCD_IEN

ENO

OUT

INIW4

MW20

IN

I_BCDEN

ENO

OUT

INMW10

QW12

FBD

L IW4BTIT MW20

L MW10ITBT QW12

STL

0 8 1 5Numberentered in BCD

Numberdisplayedin BCD

ConversionBCD->Integer

Task

ConversionBCD<-Integer

User program withinteger mathoperations

0 2 4 8

IN

BCD_IEN ENO

OUTINIW4 MW20

I_BCD

IN

EN ENO

OUTMW10 QW12

LAD

Page 135: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Digital OperationsPage 20

Example A user program that works with integers also needs to perform division, which is likely to result in values less than 1. Since these values can only be represented as real numbers, conversion to real numbers is necessary. To do this, the integer must first be converted to a double integer.

I_DI / ITD Converts an integer to a double integer.

DI_R / DTR Converts a double integer to a real number.

Note Other conversion instructions, such as:• INV_I / INVI• NEG_I / NEGI• TRUNC / TRUNC• ROUND / RND• CEIL / RND+• FLOOR / RND-• INV_DI / INVD• NEG_DI / NEGD• NEG_R / NEGR• CAW, CADare discussed in an advanced programming course.

Date: 05.12.2005File: PRO1_07E.20

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Conversion Operations I -> DI -> REAL

AWL

L MW12ITDDTRT MD26

IN

I_DIEN

ENO

OUT

INMW12

MD14

IN

DI_REN

ENO

OUT

INMD14

MD26

FBD

Mathprogramwithreal numbers

Conversion fromdouble integerto real number

Conversion frominteger todouble integer

Task

Data in integer format(16 bits)

LAD

IN

DI_REN ENO

OUTMD14 MD26ININ

I_DIEN ENO

OUTMW12 MD14IN

Page 136: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Digital OperationsPage 21

CMP You can use comparison instructions to compare the following pairs of numerical values:I Compare integers (on the basis of 16 bit fixed-point number)D Compare integers (on the basis of 32 bit fixed-point number)R Compare floating-point numbers (on 32 bit real number basis =

IEEE floating-point numbers).If the result of the comparison is “True", then the RLO of the operation "1", otherwise"0".The values at inputs IN1 and IN2 are compared for conformity with the specified condition:== IN1 is equal to IN2<> IN1 is not equal to IN2> IN1 is greater than IN2< IN1 is less than IN2>= IN1 is greater than or equal to IN2<= IN1 is less than or equal to IN2.

Date: 05.12.2005File: PRO1_07E.21

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Comparison Operations

STL

A M0.0A (L IW0L IW2==I)= Q9.7

LAD

CMP ==I

IN1IN2

IW0IW2

M0.0 Q 9.7

FBD

IN1

IN2

M0.0

IW0

IW2&

=Q9.7

CMP ==I

Page 137: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Digital OperationsPage 22

WAND_W The "AND Word" operation gates the two digital values at inputs IN1 and IN2 bit by bit in accordance with the AND truth table. The result of the AND operation Is stored at the address at output OUT. The instruction is executed when EN = 1. Example: Masking out the 4th decade of the pushwheel buttons :IW4= = 0100 0100 1100 0100W#16#0FFF = 0000 1111 1111 1111MW30 = 0000 0100 1100 0100

WOR_W The "OR Word" operation gates the two digital values at inputs IN1 and IN2 bit by bit in accordance with the OR truth table. The result of the OR operation is stored at the address at output OUT.The instruction is executed when EN = 1. Example: Setting bit 0 in MW32 :MW32 = 0100 0010 0110 1010W#16#0001 = 0000 0000 0000 0001MW32 = 0100 0010 0110 1011

WXOR_W The "Exclusive OR Word" operation gates the two digital values at inputs IN1 and IN2 bit by bit in accordance with the XOR truth table. The result of the OR operation is stored at the address at output OUT. The result of the XOR operation is stored at the address at output OUT. The instruction is executed when EN=1. Example: detecting signal changes in IW0 :IW0 = 0100 0100 1100 1010MW28 = 0110 0010 1011 1001MW24 = 0010 0110 0111 0011

Date: 05.12.2005File: PRO1_07E.22

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Digital Logic Operations

L IW 0

L W#16#5F2A

AW / OW / XOW

T MW10

015

IW0 =

W#16#5F2A =

WAND_W

WXOR_W

WOR_W

EN ENO

IN2 OUTW#16#5F2A MW10

IN1IW0

0 1 1 1 10 0 0 0 0 0 0 0 0 0 0

0 1 1 1 10 0 0 0 0011 1 1 1

XOR

MW10 nach “XOW” 1 1 1 1 1 1 1 0 00000000

OR

MW10 after “OW” 0 1 1 10 0 0 0 01 1 1 1 1 1 1

AND

MW10 after “AW” 0 1 1 10 0 0 0 0 0 0 0 0 0 00

Page 138: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Digital OperationsPage 23

General The instruction set of the S7-300/400 supports a multitude of mathematical functions. All the instructions have the same format :

EN The instruction is executed if RLO is =1 at Enable input EN.ENO If the result is outside the permissible range for the data type concerned, overflow bits

OV=“Overflow” and OS=“Stored Overflow” are set and Enable output ENO=0. This prevents subsequent operations dependent on ENO from being executed.

IN1,IN2 The value at IN1 is read in as the first address and the value at IN2 as the second.

OUT The result of the mathematical operation is stored at the address at output OUT.

Instructions Addition: ADD_I Add integerADD_DI Add double integerADD_R Add real number

Subtraction: SUB_I Subtract integerSUB_DI Subtract double integerSUB_R Subtract real number

Multiplication: MUL_I Multiply integerMUL_DI Multiply double integerMUL_R Multiply real number

Division: DIV_I Divide integerDIV_DI Divide double integerDIV_R Divide real number

Note The advanced mathematical functions (ABS, SQR, SQRT, LN, EXP, SIN, COS, TAN, ASIN, ACOS, ATAN) are discussed in an advanced programming course.

Date: 05.12.2005File: PRO1_07E.23

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

LAD FBD STLBasic Mathematical Functions

Subtrac-tion

Multipli-cation

Division

AdditionL MW4L MW10+ IT MW6MW10

ADD_I

IN2

EN ENO

OUTIN1MW4

MW6 MW10

ADD_I

IN2

EN

ENO

OUTIN1MW4

MW6

SUB_I

IN2

EN ENOIN1MW5

MW11 MW7OUT MW11

SUB_I

IN2

EN

ENO

OUTIN1MW5

MW7L MW5L MW11- IT MW7

MD6MD12

MUL_REN ENOIN1

MD66IN2 MD12

MUL_R

IN2

EN

ENO

OUTIN1MD6

MD66L MD6L MD12* RT MD66

MD40

MD4

EN ENOIN1IN2 MD32OUT

DIV_R

MD4

DIV_R

IN2

EN

ENO

OUTIN1MD40

MD32 L MD40L MD4/ RT MD32

Page 139: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Digital OperationsPage 24

Goal To extend the function of the bottle counting program.The maximum number that can be counted with a counter is 999. To count larger numbers, you would have to connect a number of counters in series.You should therefore use mathematical operations here for counting. The production data shown in the diagram are also required for management.

What to Do 1. Delete the networks for the “bottle counting” function in FC 16 (FILL program).

2. Write an FC 18 for the counting function. When the plant is switched on, the values in MW 100/102/104 are deleted.

When an edge is detected at I 16.5 (I 8.5) or I 16.7 (I 8.7), the bottle count is incremented by adding 1.

The difference between the number of full bottles and the number of empty bottles is stored in MW 104.

3. Program a call to FC18 in OB1.4. Download all the blocks of the S7 program FILL to the CPU and test your

program.

Date: 05.12.2005File: PRO1_07E.24

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Program for a Bottling Plant (Production Data)

Full bottles

Empty bottles

"Broken" bottles

MW 100

MW 102

MW 104

Page 140: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Digital OperationsPage 25

Goal To make the following addition to the program for the production data of the bottling plant :• The full bottles are packed in units of 6. The number of packs required is to

be calculated and displayed at QW12 (QW6).• The program for this task is to be written in FC19.

What to Do 1. Write a program in FC 19 (S7-Program FILL) for dividing the number of full bottles (MW102) by the integer 6.

2. Convert the result to BCD.3. Transfer the BCD value to the digital display (QW12 / QW6).4. In FC 18, delete the network for displaying the full bottles.5. Program a call as well to FC 19 in OB 1.6. Save the program, then download it and test it.

Result The number on the digital display (number of packs required ) is increased by 1 for each multiple of 6 (bottles).

Date: 05.12.2005File: PRO1_07E.25

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise : Program for a Bottling Plant(Number of Packaging Units)

Program entered in STL

Program converted to STL

Program entered in LAD

(QW 6)

Page 141: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Digital OperationsPage 26

Shift The instruction is executed if RLO = 1 at Enable input EN.

SHL_W / SLW The SHL_W operation shifts bits 0 to 15 of ACCU 1 bit-by-bit to the left by the number of places specified at input “N”. The bits on the right are padded with zeros.

SHR_W / SRW The SHR_W operation shifts bits 0 to 15 of ACCU 1 bit-by-bit to the right by the number of places specified at input “N”. The bits on the left are padded with zeros.

ACCU1-H Bits 16 to 31 are not affected.

OUT The result of the shift operation is stored at the address at output OUT.

N The permissible range for N=0...15. If N>=16, OUT=0.

ENO If the instruction is executed (EN = 1), ENO indicates the signal state of the last bit shifted. This means that other instructions dependent on ENO (cascading) are not executed if the signal state of the last bit shifted is "0".

SHL_DW / SLD The procedure for the SHL_DW or SHR_DW operations is the same as that for theSHR_DW / SRD SHL_W or SHR_DW operations, except that the entire contents of ACCU1 ( bits 0 to 31) are

shifted bit-by-bit to the left or right by the specified number of bits.

Date: 05.12.2005File: PRO1_07E.26

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Shift Operations (Word / Doubleword)

L MW8L MW4SLW T MW12

SHL_W

EN

N OUT

ENO

MW12

INMW4

MW8= +2

L MW4SLW 2T MW12

or:

0 0

1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 1

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 0 0 0 0 0 0 0 0 0 0 0 0 1

OUT

IN

Shift Left Word:

0 0

OUT

1 1 1 0 0 0 0 0 0 0 0 0 0 0

11 1 0 0 0 0 0 0 0 0 0 0 0 0 1

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

IN

Shift Right Word:

EN0 =1 EN0 = 0

Page 142: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Digital OperationsPage 27

SHR_I / SSI The Shift Right Signed Integer operation shifts only ACCU1-L (bits 0 to 15) bit by bit to the right. The bits that are vacated are filled with the contents of the sign bit (bit 15).Bits 16 to 31 are not affected. Input N specifies the number of bit positions by which the number is to be shifted. If N is greater than 16, N = 16 is assumed.

EN/ENO If the instruction is executed (EN = 1), ENO indicates the signal state of the bit last shifted (this bit corresponds to the CC1 and RLO bits in the status word). This means that other instructions dependent on ENO (cascading) are not executed if the signal state of the last bit shifted is "0".

SHR_DI / SSD The Shift Right Signed Double Integer operation shifts the entire contents of ACCU 1 (bits 0 to 31) to the right by the specified number of bits.Permissible values for N: 0 to 32.

Note The shift operations are discussed in more detail in an advanced programming course.

Date: 05.12.2005File: PRO1_07E.27

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Shift Right Signed Integer

SHR_I

EN

N OUT

EN0

MW12

INMW4

MW8= +3

L MW8L MW4SSI T MW12

L MW4SSI 3T MW12

or:

Shift a Signed Integer to the Right:

1 1 1

1

1 0 1 0 0 0 0 0 0 0 0 0 1

01 1 0 0 0 0 0 0 0 0 0 1 0 0

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

OUT

INEN0 = 0

0 0 0

1

0 1 1 0 0 0 0 0 0 0 0 0 1

10 1 0 0 0 0 0 0 0 0 0 1 1 0

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

OUT

INEN0 = 1

Page 143: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Digital OperationsPage 28

ROL_DW / RLD The Rotate Left Doubleword operation rotates the entire contents of ACCU 1 to the left. The vacated bits are filled with the signal states of the bits that are pushed out.The last bit rotated is loaded in condition code bit 1 of the status word and also stored at output ENO. This means that other instructions dependent on ENO (cascading) are not executed if the signal state of the last bit rotated is "0".

ROR_DW / RRD Rotate Right Doubleword.

Note The rotation operations are discussed in more detail in an advanced programming course.

Date: 05.12.2005File: PRO1_07E.28

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Doubleword Rotation Operations

OUT

ROL_DW

EN

N OUT

ENO

MD12

INMD2

MW6= +4

L MW6L MD2RLD T MD12

L MD2RLD 4T MD12

or:

Rotate 4 placesto the left :

0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 11 0 1 1 0 0 0 0 0 0 0 0 0 0 0 0

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 031 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16

IN:

1 0 1 10 0 0 0 0 0 0 0 0 0 1 10 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0OUT:

Page 144: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1SymbolsPage 1

Contents Page

Absolute and Symbolic Addressing …........................................................................................... 2Symbolic Addressing - Overview …............................................................................................... 3Opening the Symbol Table ................................................................................................................ 4Edit: Find and Replace ……............................................................................................................. 5View: Filter ….................................................................................................................................... 6View: Sort ……................................................................................................................................ 7Symbol Table: Export ...................................................................................................................... 8Symbol Table: Import ....................................................................................................................... 9Edit Symbols (in the LAD/STL/FBD Editor) ……............................................................................... 10Symbol Information (in the LAD/STL/FBD Editor) ............................................................................. 11Symbol Selection (in the LAD/STL/FBD Editor) ............................................................................... 12“Leading Symbol" ......................................................................................................................... 13Exercise: Creating a Symbol Table for FC 15 .................................................................................. 14

Date: 05.12.2005File: PRO1_08E.1

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Symbols

Page 145: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1SymbolsPage 2

Absolute In absolute addressing, you specify the address (e.g. input I 1.0) direct. In thisAddressing case you don‘t need a symbol table, but the program is harder to read.

Symbolic In symbolic addressing, you use symbols (e.g. MOTOR_ON) instead of the Addressing absolute addresses.

You store the symbols for inputs, outputs, timers, counters, bit memories and blocks in the symbol table.

Note When you enter symbol names, you don‘t have to include quotation marks. The Program Editor adds these for you.

Date: 05.12.2005File: PRO1_08E.2

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Absolute and Symbolic Addressing

A I 0.0

= Q8.0

A I 0.4

= Q20.5

Call FC18

A “PLANT_ON"

= “ON_INDIC"

A "M_FORW"

= "MOTOR_FORW"

Call “COUNT"

Symbol Address Data Type Comment

MOTOR_FORW

COUNT

PLANT_ON

ON_INDIC

M_FORW

Q20.5

FC18

I 0.0

Q8.0

I 0.4

BOOL

FC18

BOOL

BOOL

BOOL

Motor forwards

Count bottles

Switch on plant

Indicator: Plant is “On”

M.-con. switch: Motor forwards

(max. 24 characters) (max. 80 characters)

Page 146: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1SymbolsPage 3

Global Symbols Global symbols declared in the symbol table can be used in all blocks of a program.The name in the symbol table must be unique, that is, a symbolic name must only appear once in the table.

Local Symbols Local symbols are declared in the declaration part of a block. They can only be used within that block.The same symbolic name can be used again in the declaration part of another block.

Date: 05.12.2005File: PRO1_08E.3

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Local Block Data: Declaration part of Program Editor- Block parameters the block- local / temporary data

Jump Labels Code section of Program Editorthe block

Symbolic Addressing - Overview

Where are symbols used? Where are they stored? With what are they created?

Global Data: Symbol Table Symbol Editor- Inputs- Outputs- Bit mem., timers, counters- Peripheral I/O

Data Block Components Declaration part of the DB Program Editor

Block Names: Symbol Table Symbol Editor- OB- FB- FC- DB- VAT- UDT

Page 147: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1SymbolsPage 4

Symbol Table You open the symbol table by selecting the menu options Options -> Symbol Table in the LAD/STL/FBD Editor.You can also open the symbol table from the SIMATIC Manager: Select the program in the left-hand pane of the project window and double-click the “Symbols” object.

Table Structure When you open a symbol table, an additional window is opened. It consists of columns for the symbol name, the address, the data type and a comment for a symbol. Each symbol occupies one line of the table. A blank line is automatically added at the end of the table for defining a new symbol.

Note The symbol table is a common database and can be used by different tools:• LAD/STL/FBD Editor• Monitoring and Modifying Variables• Display Reference Data

Date: 05.12.2005File: PRO1_08E.4

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Opening the Symbol Table

Page 148: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1SymbolsPage 5

Find and Replace A number of options are available for finding and replacing text in the current window:• Find what:

Enter the text you are looking for.• Replace with:

Enter the replacement text. • From cursor down:

Searches downwards to the last line in the symbol table.• From cursor up:

Searches upwards to the first line in the symbol table.• Match case:

Only searches for the specified text with identical use of upper-case and lower-case letters.

• Find whole words only:Searches for the specified text as a separate word, not as part of a longer word.

• All:Searches through the whole symbol table, starting from the cursor position.

• Selection:Searches only the selected symbol lines.

Note When you are looking for addresses, you should insert a wildcard after the address identifier, otherwise the address cannot be found.

Example of Find and Replace (replace all outputs with address 8. with address 4.):

Find what: Replace with:Q*8.* Q 4.

Date: 05.12.2005File: PRO1_08E.5

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Edit: Find and Replace

Page 149: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1SymbolsPage 6

Filter Only the symbols which meet the active filter criteria (“symbol properties") are displayed in the current window. You can apply several criteria at once. The specified filter criteria are linked with one another.

Symbol You can select various filters and link them according to the following properties:Properties Name, Address, Data type, Comment, Operator control and monitoring,

Communication, Message.

Permissible wildcards are * and ?.

Examples Name: M*Only the names that begin with "M“, and that contain any number of additional characters, are displayed in the symbol table.

Name: SENSOR_?Only the names that begin with "SENSOR_" and that contain one other character, are displayed in the symbol table.

Address: E*.*Only the inputs are displayed.

Valid, Invalid The symbols must be unique, that is, a symbol or an address must only exist once in the symbol table.If a symbol or an address appears more than once, the lines in which it appears are displayed in “Bold". If your symbol table is long, and you want to find such ambiguous symbols or addresses more quickly, you can display only these lines of the symbol table by selecting the menu options View -> Filter and the attribute “Invalid".

Date: 05.12.2005File: PRO1_08E.6

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

View: Filter

Page 150: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1SymbolsPage 7

Sort The entries in the symbol table can be displayed in alphabetical order. You use the menu options View -> Sort to specify the column to be used as the point of reference for sorting in the current window.There is an alternative way to sort:1. Click on the column heading for sorting in ascending order in this column.2. Click on the column heading once more for sorting in descending order in this column.

Date: 05.12.2005File: PRO1_08E.7

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

View: Sort

Page 151: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1SymbolsPage 8

General The menu option Symbol Table -> Export enables you to store symbol tables in a different file format so that you can work on them with other programs. You can select the following file formats:• ASCII Format (*.ASC)

- Notepad- Word

• Data Interchange Format (*.DIF)- EXCEL

• System Data Format (*.SDF)- ACCESS

• Assignment List (*.SEQ)- STEP 5 assignment list

Date: 05.12.2005File: PRO1_08E.8

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Symbol Table: Export

Where do you want to store the table ?

In which format do you want to store the table?

Page 152: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1SymbolsPage 9

General The menu option Symbol Table -> Import enables you to import symbol tables that were created with other user programs.What to do:1. Activate the menu options Symbol Table -> Import.2. Select the file format in the “Import” dialog window.

You will find the same formats as for Export.3. Select the directory path in the “Find in:" list box.4. Enter the file name in the “File Name:" box5. Confirm with "OK" .

File Types You can import the following file formats:• ASCII Format (*.ASC)

- Notepad- Word

• Data Interchange Format (*.DIF)- EXCEL

• System Data Format (*.SDF)- ACCESS

• Assignment List (*.SEQ)- STEP 5 assignment list

Date: 05.12.2005File: PRO1_08E.9

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Symbol Table: Import

Select directory path here

Enter file name

Select file format

Page 153: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1SymbolsPage 10

Edit Symbols The menu option Edit -> Symbol, or a click with the right mouse button on the addressand then the menu option Edit Symbol, enables you to assign symbolic names to absolute addresses later on. The assigned names are automatically entered in the symbol table.Names that are already in the symbol table are displayed in a different color. They cannot be used again in the symbol table.

Date: 05.12.2005File: PRO1_08E.10

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Editing Symbols (in the LAD/STL/FBD Editor)

Page 154: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1SymbolsPage 11

Addressing In the LAD/STL/FBD Editor you can choose to display the addresses in one of the following two ways by selecting the menu options View -> Display -> Symbolic Representation:

• Symbolic Addressing or• Absolute Addressing .

You can display the symbolic and absolute address assignments used in the network by selecting the menu options View -> Display -> Symbol Information.The assignments are found under the network in LAD/FBD and in STL they are found in the statement line.

Note If you position the mouse pointer on an address, a "Tooltip" appears with the symbol information for this address.

Date: 05.12.2005File: PRO1_08E.11

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Symbol Information (in the LAD/STL/FBD Editor)

Page 155: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1SymbolsPage 12

Date: 05.12.2005File: PRO1_08E.12

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Symbol Selection (in the LAD/STL/FBD Editor)

Introduction You can use the menu options View -> Display -> Symbol Selection to simplify the writing of a symbolic program.

When you label the adddress, a section of the symbol table pops up, as soon as you enter the first letter of a symbol name. This section contains all symbols which begin with this letter. By clicking on the desired symbol it is taken into your program.

Page 156: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1SymbolsPage 13

Introduction If you want to change the assignments in the symbol table of an already existing program, you can also decide whether the absolute address or the symbolic address has priority.

Selection In the SIMATIC Manager, select, with the right mouse button, the "Blocks" object of an S7 program. Select the menu option Properties and then the "Blocks“ tab.You can choose between "Absolute Value" or "Symbol" in the “Priority" field.

Priority: With this setting, the absolute address of an operand does not change, if youAbsolute Value change the address assignment in the symbol table later on.

In the example above, the output Q8.0 (symbol name “Plant On") was changed to output Q4.0 in the symbol table. With the “Priority: Absolute Value" setting, the program continues to use the output Q8.0.

Priority: Symbol With this setting, the absolute address of the operand is changed to the new entry in the symbol table.In the example above, the output Q8.0 (symbol name “Plant On") was changed to output Q4.0 in the symbol table. With the “Priority: Symbols“ setting, the address is changed from Q8.0 to Q4.0 throughout the entire program.The changed address also keeps its symbol name. That way you can change the absolute addresses in an existing symbolic user program.

Date: 05.12.2005File: PRO1_08E.13

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

"Leading Symbols"

Symbol Table

Old Entry:Plant ON = Q8.0

New Entry:Plant ON = Q4.0

Priority: Absolute Value

Priority:Symbols

Page 157: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1SymbolsPage 14

Goal To create a symbol table representing the first part of the filling application.

What to Do Create a symbol table for the FC 15 function in the S7 program "FILL":1. Open the Symbol Editor in the LAD/STL/FBD Editor by selecting the menu

options Options -> Symbol Table.2. Edit the symbol table, as is shown in the screen above. 3. Save the symbol table by selecting the menu options Symbol Table ->

Save and return to the LAD/STL/FBD Editor.4. Open the FC 15 block5. Select the menu options View -> Display -> Symbolic Representation or click the icon in the toolbar.

6. Look at your program in symbolic representation and then select the menu options View -> Display -> Symbol Information.

Result The symbolic names are now displayed for all the addresses in the program to which you have assigned names. You can return to absolute addresses by deactivating the Symbolic Representation selection in the View menu.

Date: 05.12.2005File: PRO1_08E.14

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Creating a Symbol Table for FC 15

Plant OnManual ModeAutomatic ModeConveyor ForwardConveyor BackwardStartStopJog ForwardJog BackwardAutomatic/ManualEnter Mode

Q 8.1Q 8.2Q 8.3Q 20.5Q 20.6I 0.0I 0.1I 0.2I 0.3I 0.4I 0.5

Q 4.1Q 4.2Q 4.3Q 8.5Q 8.6I 0.0I 0.1I 0.2I 0.3I 0.4I 0.5

Symbol Address(Version A)

Address(Version B)

Page 158: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Test FunctionsPage 1

Contents Page

Debug - Monitor (Status) ............................................................................................................... 2Program Status Modes of Operation ................................................................................................ 3Use of Trigger Points with Program Status …..………..................................................................... 4Selecting the Display Information of the Program Status ............................................................... 5Activating the “Monitor/Modify Variables" Tool ……………........................................................... 6Entering a Variable Table ................................................................................................................ 7Monitoring and Modifying Variables ................................................................................................ 8Setting Trigger Points .................................................................................................................... 9Saving a Variable Table ................................................................................................................ 10Opening a Variable Table ................................................................................................................ 11Establishing a Connection to the CPU ............................................................................................ 12Modifying Outputs in the Stop Mode ............................................................................................... 13Forcing ............................................................................................................................................. 14Breakpoints (Part 1) ......................................................................................................................... 15Breakpoints (Part 2) ......................................................................................................................... 16Exercise: Monitoring and Modifying Variables .............................................................................. 17Exercise: Modifying Variables in the Stop State .............................................................................. 18Exercise: Using Trigger Points for the Modify Variables Function .................................................... 19Exercise: Forcing ........................................................................................................................... 20Exercise: Combining Program Status and Monitor Variable ..................................................... 21

Date: 05.12.2005File: PRO1_09E.1

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Test Functions

Page 159: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Test FunctionsPage 2

Monitor You can activate the “Monitor" ("Status") test mode for the block which is currently open by clicking the Spectacles icon with the mouse or by selecting the menu options Debug -> Monitor. In the test mode, the elements in LAD / FBD are displayed in different colors. You define these by selecting the menu options Options -> Customize.E.g.: • Status fulfilled -> "Element is displayed in green"

• Status not fulfilled -> "Element is displayed in blue"

Notes 1. When the “Monitor" test mode is activated, you cannot make any changes to the program. You cannot change the view of the block (LAD, STL, FBD) either.

2. The status can only be displayed when the instructions are being executed.The status is not displayed when the CPU is in the STOP mode or when the block is not called.

Date: 05.12.2005File: PRO1_09E.2

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Debug - Monitor (Status)

Page 160: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Test FunctionsPage 3

Debug-> Operation There are two modes of operation for the test mode, which differ in their effect on the scan cycle time of the user program:• Process operation and • Test operation.

Process Operation In process operation, the test functions are restricted so that the permissible scan cycle time increase that you select is not exceeded.The status of programmed loops is only determined the first time they are executed.The test functions “Breakpoint” and “Single-step (program execution)” cannot be executed.

Test Operation In test operation, all test functions can be performed without restrictions.The status of programmed loops is determined every time they are executed. The scan cycle time can be increased considerably due to the updating of the test function “program status” with every loop execution.

Parameter The above information only applies if the mode of operation has not alreadyAssignment been defined in the hardware configuration.

The mode of operation can be defined on the “Protection” tab page when assigning the CPU parameters. This setting can then no longer be changed in the “Operation” dialog box.

Date: 05.12.2005File: PRO1_09E.3

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Program Status Modes of Operation

Page 161: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Test FunctionsPage 4

Date: 05.12.2005File: PRO1_09E.4

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Use of Trigger Points with Program Status

Trigger Points After you have selected the menu options Debug -> Call Environment, a dialog box pops up (see slide above). Here you can enter a Call path. This is helpful if a block is called several times in a program and you want to monitor only one specific call.You can also specify data blocks as trigger conditions. The status display of the block begins from the point when the specified DB is opened.

Call Path In the example, FC 1 is called three times (see program structure). So that you can specifically monitor a call, enter the three blocks that are found immediately before the status block. A requirement for this is that the call takes place through different blocks. So that you can monitor the third call, enter in the exampleFC 30 at 3rd Block.

Open Data Blocks In the example, FB 1 is called several times by the same FC 40 block. In this case, the Call path cannot be used for testing. Here you use the opened data block as a trigger for testing. Since, as a rule, an instance DB is also used with an FB, you can use this instance DB in the DB2-number field as the trigger condition. In the example, DB 1 was used for the first call, DB 2 for the second call and DB 3 for the third call. You have to enter DB 2 in order to see the second call.

Note The "Test Operation" mode is a prerequisite for testing with the Call path.

Page 162: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Test FunctionsPage 5

Date: 05.12.2005File: PRO1_09E.5

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Selecting the Display Information of the Program Status

LAD/STL/FBD Editor -> Options ->Customize ... or with running status: right mouse click

on

Introduction In the block status, you can select which information is to be displayed on the screen. By default, you see Status Bit, RLO, and Standard status.If you want to display additional information, select the menu options Options ->Customize -> STL.

Dialog Box In the screen you can see the dialog box for putting together the information.In addition to the information displayed by default, the following is also possible:

• AR1 Address register 1, only meaningful with register indirect addressing• AR2 Address register 2, only meaningful with register indirect addressing• Accumulator 2• DBR1 Data block register 1 (global or first DB opened)• DBR2 Data block register 2 (local or second DB opened)• Indirect, meaningful with memory indirect addressing (shows the contents of MD and DD e.g. with the instruction L IW [MD 100] ).

Note With a running program status, you can hide and show additional information, you can change the representation (decimal, hexadecimal, real) or display separators. To do so, click with the right mouse button on the title RLO, STA .. and choose the menu option you want (see screen).

Page 163: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Test FunctionsPage 6

General “Monitor/Modify Variables" is another STEP 7 tool which enables you to monitor the variables of a program in selectable formats.It also allows you to modify the status or contents of variables in the CPU.

Toolbar You can change the toolbar by selecting the menu options View -> Toolbar. There are three different toolbars which you can activate/deactivate:

• Standard

• View

• Variable

View You can adjust the number of columns in the variable table by selecting the menu optionsView -> Symbol / Symbol Comment / Monitor Format / Monitor Value / Modify Valueor by using the “View" toolbar.

Date: 05.12.2005File: PRO1_09E.6

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Activating the "Monitor/Modify Variables" Tool

Page 164: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Test FunctionsPage 7

Creating a VAT There are two different ways of creating a variable table:1. in the LAD/STL/FBD Editor, by selecting the menu options PLC ->

Monitor/Modify Variables. You can work directly online with this table.2. in the SIMATIC Manager, by selecting the menu options Insert New Object -> Variable Table when the “Blocks” folder is open. This table is created

offline. You can save it and open it again later, switch to online mode and then test it.

Table Each address to be monitored or modified takes up one line of the variable table.The meanings of the columns of the variable table are as follows:

Address The variable‘s absolute address is found in this column.

Symbol The variable‘s symbolic name (identifier) is found here. It is identical to the name entered in the symbol table.

Symbol Comment The symbol comment from the symbol table is displayed in this column.

Monitor Format This column contains a standard setting, e.g. HEX. You can change the format as follows:• click an entry in the format column with the right mouse button. The list of

formats pops up.• or keep clicking on the entry in the format column with the left mouse button

until the format you want appears.

Monitor Value The contents of the variable at the last update is displayed here.

Modify Value You enter the new value for the variable (the modify value) in this column.

Date: 05.12.2005File: PRO1_09E.7

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Entering a Variable Table

Page 165: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Test FunctionsPage 8

Monitor You can monitor variables in two ways:• The monitor values can be updated once by selecting the menu options

Variable -> Update Monitor Values or by clicking on the icon.

• The monitor values can be updated every cycle by selecting the menu options Variable -> Monitor or by clicking on the icon

Modify Procedure for modifying variables:1. With the left mouse button, click the line in the “Modify Value” column for

the variable that you want to modify.2. Enter the value in the correct form for the data type. 3a. To activate the modify values once, select the menu options Variable ->

Activate Modify Values or click the icon (or item 3b).

3b. To activate the modify values every cycle, select the menu options Variable -> Modify or click the icon.

4. Use the “Monitor” test function to check whether the modify value has been entered in the variable.

Modify Value Valid You can make the modify value entered in the table invalid by clicking on the icon.

The invalid value is optically displayed like a comment. You make the modify value “valid” again by clicking on the icon again.Only valid modify values can be activated.

Date: 05.12.2005File: PRO1_09E.8

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Monitoring and Modifying Variables

Page 166: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Test FunctionsPage 9

Trigger You set the trigger points in the “Monitoring and Modifying Variables” tool by selecting the menu options Variable -> Set Trigger... or by clicking the icon.

Trigger Points The “Monitor Trigger Point” specifies when the values of the variables being monitored are to be updated.The “Modify Trigger Point” specifies when fixed values are to be assigned to the variables being modified.

Trigger Frequency The “Monitor Trigger Frequency” specifies whether the values are to be updated once only when the trigger point is reached or every cycle (every time the trigger point is reached). The “Modify Trigger Frequency” specifies whether the new values are to be assigned to the variables being modified once only or every cycle.

Attention ! When the “Monitor Trigger Frequency” is set to “Once”, a click on the icons orhas the same effect: the values are updated once.

When the “Modify Trigger Frequency” is set to “Once”, a click on the icons orhas the same effect: the values are activated once.

When the trigger frequencies are set to “Every Cycle”, the above-mentioned icons have the different effects previously described.

When the same trigger points are set for Monitor and Modify, Monitor has priority, that is, monitoring is done first.

Note For some CPU versions (e.g. CPU 314-1AE03), the modify function is not carried out with every cycle when the “Modify Trigger Frequency" is set to “Every cycle". Remedy: Using the test function "Force".

Date: 05.12.2005File: PRO1_09E.9

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Setting Trigger Points

Start of cyclic program execution

End of cyclicprogram execution

Transition: RUN --> STOP

Cyclicprogramexecution

PII

PIQ

Page 167: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Test FunctionsPage 10

Save When you cancel or finish a test phase, you can save the variable table.The name of a variable table consists of the letters "VAT" followed by a number from 0to 65535 (with no space in between), e.g. "VAT5".

Date: 05.12.2005File: PRO1_09E.10

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Saving a Variable Table

Page 168: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Test FunctionsPage 11

What to Do 1. Activate the menu options Table -> Open.2. Choose the project name in the “Open" dialog window.3. Select the relevant program in the project pane underneath and click the “Blocks” folder.4. Select the table you want in the right-hand pane.5. Confirm with "OK".

Date: 05.12.2005File: PRO1_09E.11

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Opening a Variable Table

Page 169: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Test FunctionsPage 12

PLC The variables in a VAT are variable parts of a CPU program. Before you can monitor or modify the variables, you must establish a connection to the CPU concerned. It is possible to connect each variable table to a different CPU. You select the menu options PLC -> Connect To . . . or click the appropriate icons in the toolbar to establish a connection to one of the following CPUs: • Configured CPU• Direct CPU • Accessible CPU . . .

Configured CPU The variables of the CPU, in whose S7 program (H/W Station) the variable table is stored, are displayed.

Direct CPU The variables of the CPU, which are directly connected to the PG, are displayed.

Accessible CPU The variables of the CPU, which are selected in the dialog box, are displayed.You select the menu options PLC -> Connect To -> Accessible CPU... to establish a connection to an accessible CPU.Thus, you can establish a connection to every CPU in the network.

Date: 05.12.2005File: PRO1_09E.12

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Establishing a Connection to the CPU

ConfiguredCPU

(VAT fromHW Station "Station 2")

Station 2Directly

connectedCPU

Station 1

PG

Station 3

Accessible CPUs

Page 170: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Test FunctionsPage 13

Date: 05.12.2005File: PRO1_09E.13

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Modifying Outputs in the Stop Mode

Overview The “Enable Peripheral Outputs" function switches off the output disable of the peripheral outputs (PQ). This enables you to modify the peripheral output when the CPU is in the STOP mode.

Selection To enable the peripheral outputs, proceed as follows: 1. Select the menu options Table -> Open to open the variable table (VAT) that

contains the peripheral outputs you want to modify, or, activate the window for the relevant variable table.

2. Select the menu options PLC -> Connect to to establish a connection to the CPU you want, so that you can modify the peripheral outputs of the active variable table.3. Select the menu options PLC -> Operating Mode to open the Operating Mode dialog box and switch the CPU to the STOP mode.4. Enter the appropriate values for the peripheral outputs you want to modify in the “Modify Value" column.

Examples: PQB 7 Modify Value: 2#0001000011PQW 2 W#16#0027PQD 4 DW#16#0001

5. You switch on the “Enable Peripheral Outputs" mode by selecting the menu options Variable -> Enable Peripheral Outputs.

6. You modify the peripheral outputs by selecting the menu options Variable -> Activate Modify Values. The “Enable Peripheral Outputs" remains active until you

select the menu options Variable -> Enable Peripheral Outputs again to switch off this function. 7. To assign new values, start again with step 4.

Note • If the CPU changes its operating mode and goes from STOP to RUN orSTARTUP, for example, a message pops up.

• If the CPU is in the RUN mode and the “Enable Peripheral Outputs" function is selected, a message also pops up.

Page 171: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Test FunctionsPage 14

Date: 05.12.2005File: PRO1_09E.14

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Forcing

Forcing You can establish predefined values for user program variables with the Force function. With the S7-400, inputs, outputs, bit memories and peripherals can be forced. With the S7-300, only inputs and outputs.

Notes for Forcing You can only open one Force Values window for a CPU.

• You will find the name of the variable table for the current online connection in the titlebar of the Force Values window.• You will find the date and time of the current force task in the CPU in the

statusbar.• You cannot monitor and modify variables when the Force Values window is

active.

Before you start the "Force" function, you should make sure that no one else is carrying out this function at the same time on the same CPU. You can only cancel or end a force job by selecting the menu options Variable > Stop Forcing.

You cannot cancel the force task by closing the Force Values window or by exiting the “Monitor/Modify Variables" application.

You cannot undo "Forcing" with the menu options Edit -> Undo. Take the time to find out about the differences between forcing variables and modifying variables.

Attention! Please note, that incorrect handling when executing the "Force" function can

• endanger the life or the health of persons or• cause damage to a machine or the entire system.

Note This function is only possible as of a specific version of the CPU(e.g. CPU 314-1AE03).

!

Page 172: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Test FunctionsPage 15

Date: 05.12.2005File: PRO1_09E.15

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Breakpoints (Part 1)

Breakpoints With the help of this test function, you can test a program you have created in the STL programming language in single-step mode. This is only necessary in program creation so that you can, for example, test programmed loops.You can set several breakpoints, depending on the CPU.

Breakpoint You can choose the breakpoint functions in the Program Editor by selecting theFunctions menu option "Test" or through the Breakpoint Bar.

Breakpoint Bar You can activate the breakpoint bar by selecting the menu options View -> Breakpoint Bar in the Program Editor.

Note In order to carry out these test functions, you must have fulfilled the following requirements:

• The "Test Operation" mode must have been assigned parameters.• The block to be tested must be opened online.

Attention! If a breakpoint is activated, the CPU stops at this statement. The outputs are deactivated for safety reasons.

Note This function is only possible as of a specific version of the CPU(e.g. CPU 314-1AE03).

!

Page 173: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Test FunctionsPage 16

Date: 05.12.2005File: PRO1_09E.16

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Break-point

Breakpoints (Part 2)

Next state-ment

Breakpoint BarSet/Delete Breakpoint Breakpoints Active

Show Next Breakpoint

Execute Call

Delete All Breakpoints Resume Next Statement

Set/Delete Breakpoint With “Set/Delete Breakpoint" you determine where the program execution is to be halted. The breakpoint‘s statement is not executed.

Breakpoints Active With “Breakpoints Active" you activate all breakpoints; not only those already set but also those still to be set.

Show Next With “Show Next Breakpoint“, the Editor jumps to the next selected breakpoint,Breakpoint without executing the program.

Resume With “Resume“, the program runs until the next active breakpoint.

Next Statement With "Next Statement“, you execute the program in single-step. If you reach a block call, you jump to the first statement after the block call with "Next Statement".

Execute Call Here, when you reach a block call you branch into the block with “Execute Call". At the end of the block you jump back to the next statement after the block call.

Page 174: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Test FunctionsPage 17

Goal You have already worked with the conveyor model. Now you are to check all the sensors and actuators on the conveyor model.

What to Do • In the S7 program "My Program“ insert a variable table VAT 1. • Enter the addresses that you see in the slide above into the table. The

symbols are only for orientation and are not displayed for you, since you have not as yet created a symbol table for this S7 program.

Note: to save typing, you can use the menu options Insert -> Block, to enter eight lines for e.g. the inputs I 8.0 to I 8.7 in the table.• Save the variable table.• Establish a connection to the CPU.• As the trigger point for monitor and modify select “Start of cycle" and as the

trigger frequncy select “Every cycle".• Activate the “Monitor Variable“ function.• Check all the sensors on the conveyor model.• Exit the monitor function.• With the outputs, enter "1" one after the other in the Modify Value column.

Activate the “Modify“ function. Now you have checked all actuators on the conveyor model.

Result You now know if your conveyor model is fully functional. If it is not, please let your instructor know.

Date: 05.12.2005File: PRO1_09E.17

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Monitoring and Modifying Variables

32 channel Training Unit

16 channel Training Unit

Page 175: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Test FunctionsPage 18

Date: 05.12.2005File: PRO1_09E.18

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Modifying Variables in the Stop Mode

Goal The CPU has gone into the Stop mode because of a fault. Now, your system is to be transitioned into a defined state. You are to move the conveyor model up to the light barrier by using the modify function while in the Stop mode.

What to Do • Switch the CPU to STOP.• In the variable table VAT 1, enter a new line with the address PQB 20

(PQB 8).• Switch the Monitor Format to "BIN".• Enter "00100000" as the Modify Value for the new address.• Use the menu options Variable -> Enable Peripheral Outputs.• Trigger the monitoring function by using the menu options Variable ->

Activate Modify Values.• Move the conveyor model to the right until the bottle reaches the light barrier.• When the light barrier is reached press the "Esc" button to end the modifying of the conveyor model.

Result You can carry out the modify function in the Stop state.

Page 176: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Test FunctionsPage 19

Date: 05.12.2005File: PRO1_09E.19

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Using Trigger Points for the Modify Variables Function

(Q 4.6)

Additional network in OB 1 of the S7 program "My Program"

(Q 4.6)

Goal You are to understand the meanings of the trigger points while using Modify Variables.

What to Do • Enter a new network in OB 1 of the S7 program "My Program" (see slide).• Transfer all blocks from the S7 program "My Program".• Switch the CPU to RUN, if it is still in the STOP mode from the last exercise.• In the variable table VAT 1, enter the additional address Q 8.6 (Q 4.6).• Set the Modify Trigger Point as shown in the slide.• Try to modify the output to "0".• If this is not possible, try it with another trigger point.

Result You now know how the trigger points operate with the Modify Variable function.

Page 177: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Test FunctionsPage 20

Date: 05.12.2005File: PRO1_09E.20

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Forcing

Goal Sensor signals have failed in the system. You are to simulate these using the "Force" test function.

What to Do • In the “Monitor and Modify Variable" tool select the menu options Variable -> Display Force Values.

• In the "Force Values" window, enter the addresses I 0.0 to I 0.2 with the force values (see slide).• Trigger the force function by selecting the menu options Variable -> Force.• Close the "Force Values“ window.• Determine how the CPU behaves.

Result The force values are now assigned to the input signals.

Page 178: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Test FunctionsPage 21

Date: 05.12.2005File: PRO1_09E.21

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Combining Program Status and Monitor Variable

Goal You are to carry out several test functions at the same time.

What to Do • In one window, open the “Monitor and Modify Variable" tool and in another window open the LAD/STL/FBD Editor (with an open FC 1 block, S7 program "My Program").

• Arrange the two windows so that they are both visible at the same time.• In the “Monitor and Modify Variable" window add the addresses I 0.0 to I0.2.• Activate the Monitor Variable function.• In the “LAD/STL/FBD Editor" window activate the program status.• Determine what effect the "Force" test function has on the program in the

FC 1 block.• Cancel the force task by selecting the menu options Variable -> Display Force Values and then Variable -> Stop Forcing.

Result You have now become familiar with working with several windows. This could be helpful in troubleshooting.

Page 179: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Data Storage in Data BlocksPage 1

Contents Page

Storage Areas for Data …………...................................................................................................... 2Data Blocks (DBs) ….......................................................................................................................... 3Overview of Data Types in STEP 7 ................................................................................................. 4Elementary Data Types in STEP 7 .................................................................................................... 5Complex Data Types ………........................................................................................................... 6Example of a Structure ...................................................................................................................... 7Example of an Array .......................................................................................................................... 8Creating a New Data Block ............................................................................................................ 9Entering, Saving, Downloading and Monitoring a Data Block ............................................................ 10Addressing Data Elements …......................................................................................................... 11Accessing Data Elements ............................................................................................................. 12Validity of an Open DB ……............................................................................................................. 13User-Defined Data Type (UDT) …..................................................................................................... 14Entering a UDT Block ..................................................................................................................... 15Creating a Data Block Referencing a Data Type ............................................................................ 16Example: Array from UDTs .............................................................................................................. 17Exercise: Program for a Bottling Plant - Data Storage ……............................................................ 18

Date: 05.12.2005File: PRO1_10E.1

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Data Storage in Data Blocks

Page 180: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Data Storage in Data BlocksPage 2

Overview Apart from program blocks, a user program also consists of data containing information about process states, signals, etc., which are then processed according to the instructions in the user program.Data is stored in variables of the user program, which are uniquely identified by:• Storage location (address: e.g. P, PII, PIQ, bit memory, L stack, DB)• Data type (elementary or complex data type, parameter type) Depending on the accessibility, a distinction is also made between:• Global variables, which are declared in the global symbol table or in global

data blocks• Local variables, which are declared in the declaration part of OBs, FBs and

FCs.Variables can have a permanent storage location in the process image, bit memory area or in a data block or they can be created dynamically in the L stack when a block is being executed.

Local Data Stack The local data stack (L stack) is an area for storing:• temporary variables of a logic block, including OB start information• actual parameters to be passed when calling functions• intermediate logic results in LAD programsThis topic is dealt with in the chapter "Functions and Function Blocks".

Data Blocks Data blocks are blocks used by the logic blocks of the user program for storing values. Unlike the temporary data, the data in data blocks is not overwritten when execution of the logic block is completed or when the DB is closed.

Date: 05.12.2005File: PRO1_10E.2

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Bit memories

PIQ

PII

Storage Areas for Data

Data blocks

DBx

DBy

DBz

. . .

I/O area

L stack

Page 181: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Data Storage in Data BlocksPage 3

Overview Data blocks are used for storing user data. Like the logic blocks, data blocks take up space in the user memory. The data blocks contain variable data (e.g. numeric values) that is used in the user program.The user program can access the data in a data block with bit, byte, word ordoubleword operations. Symbolic or absolute addresses can be used.

Uses You can use data blocks in different ways, depending on their contents. You differentiate between:• Global data blocks: These contain information that can be accessed by all

the logic blocks in the user program.• Instance data blocks: These are always assigned to a particular FB. The

data in each DB should only be used by the assigned FB.Instance data blocks are dealt with in more detail in the chapter "Functions and

Function Blocks“.

Creating DBs You can create global DBs either using the Program Editor or with a “user-defined data type" that you have already created.Instance data blocks are created when an FB block is called.

Registers The CPU has two data block registers, the DB and DI registers. Thus, you can have two data blocks open at the same time.You will find further information in an advanced programming course.

Date: 05.12.2005File: PRO1_10E.3

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Data Blocks (DBs)

FunctionFC10

FunctionFC20

FunctionblockFB1

OB1Global data

DB20

Accessible to all blocks

Instance data

DB5

Instance DB for FB1

Page 182: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Data Storage in Data BlocksPage 4

Overview Data types determine the properties of data, i.e. the way the contents of one or more associated addresses are to be represented and the permissible range of values.The data type also determines which operations can be used.

Elementary Elementary data types are predefined in accordance with IEC 1131-3. The dataData Types type determines the amount of memory space required. For example, the Word data

type takes up 16 bits in the user memory. Elementary data types are never more than 32 bits long and can be loaded into the accumulators of the S7 processor in full and processed with elementary STEP 7 instructions.

Complex Complex data types can only be used in conjunction with variables declared inData Types global data blocks. Complex data types cannot be completely loaded into the

accumulators with load instructions. You use standard blocks from the library ("IEC" S7 Program) to process complex data types.

User-Defined A user-defined data type can be used for data blocks or as a data type in a Data Types variable declaration table.

You create UDTs with the Data Block Editor.The structure of a UDT can contain groups of elementary and/or complex data types.

Date: 05.12.2005File: PRO1_10E.4

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Overview of Data Types in STEP 7

Elementarydata types(up to 32 bits)

Complexdata types(longer than 32 bits)

User-defined data types(longer than 32 bits)

• Bit data types (BOOL, BYTE, WORD, DWORD, CHAR)

• Mathematical data types (INT, DINT, REAL)

• Time types (S5TIME, TIME, DATE, TIME_OF_DAY)

• Time (DATE_AND_TIME)

• Array (ARRAY)

• Structure (STRUCT)

• Character chain (STRING)

Data type UDT (User Defined Type)

Page 183: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Data Storage in Data BlocksPage 5

BOOL, BYTE, WORD Variables of the data type BOOL consist of one bit, variables of data typesDWORD, CHAR BYTE, WORD, DWORD are sequences of 8, 16 and 32 bits respectively. The individual

bits are not evaluted in these data types.Special forms of these data types are the BCD numbers and the count value used in conjunction with the count function, as well as the data type CHAR, which represents a character in ASCII code.

S5TIME Variables of the data type S5TIME are required for specifying timer values in timer functions (S5 Timer functions). You specify the time in hours, minutes, seconds ormilliseconds. You can enter the timer values with an underline (1h_4m) or without an underline (1h4m).Functions FC 33 and FC40 from the library convert S5TIME to TIME format and TIME to S5TIME format.

INT, DINT, REAL Variables of these data types represent numbers which can be used in mathematical operations.

TIME A variable of data type TIME takes up a doubleword. This variable is used, for example, for specifying timer values in IEC timer functions. The contents of the variable are interpreted as a DINT number in milliseconds and can be either positive or negative(e.g.: T#1s=L#1 000, T#24d20h31m23s647msw = L#214748647).

DATE A variable of data type DATE is stored in a word in the form of an unsigned integer. The contents of the variable represent the number of days since 01.01.1990 (e.g.: D#2168-12-31 = W#16#FF62).

TIME_OF_DAY A variable of data type TIME_OF_DAY takes up a doubleword. It contains the number of milliseconds since the beginning of the day (0:00 o‘clock) in the form of an unsigned integer. (e.g.: TOD#23:59:59.999 = DW#16#05265B77).

Date: 05.12.2005File: PRO1_10E.5

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Elementary Data Types in STEP 7

BOOL 1 1 or 0BYTE 8 B#16#A9WORD 16 W#16#12AFDWORD 32 DW#16#ADAC1EF5CHAR 8 ' w '

S5TIME 16 S5T#5s_200ms

INT 16 123DINT 32 65539REAL 32 1.2 or 34.5E-12

TIME 32 T#2D_1H_3M_45S_12MSDATE 16 D#1993-01-20TIME_OF_DAY 32 TOD#12:23:45.12

Keyword Length (in bits) Example of a constant of this type

Page 184: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Data Storage in Data BlocksPage 6

Complex Complex data types (arrays and structures) consist of groups of elementary or Data Types complex data types.

They enable you to create data types to suit your problem, with which you can structure large quantities of data and process it symbolically.Complex data types cannot be processed with STEP 7 instructions all at once (longer than 32 bits), but only one element at a time.Complex data types are predefined. The data type DATE_AND_TIME has a length of 64 bits. The lengths of the data types ARRAY, STRUCT and STRING are defined by the user.Variables of the complex data types can only be declared in global data blocks and as parameters or local variables of logic blocks.

User-Defined User-defined data types represent a self-defined structure. This is stored inData Type UDT blocks (UDT1 ... UDT65535) and can be used as a “template" in another

variable‘s data type.You can save typing time when inputting a data block if you require the same structure several times.Example: You require the same structure 10 times in a data block. First, you define the structure and save it as UDT 1, for example.In the DB, you define a variable "Addresses" as an array with 10 elements of the typeUDT1:

Addresses array[1..10]UDT 1

Thus, you have created 10 data ranges with the structure defined in UDT 1 without additional “typing".

Date: 05.12.2005File: PRO1_10E.6

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Complex Data Types

Keyword Length (in bits) Example

DATE_AND_TIME 64 DT#97-09-24-12:14:55.0

STRING 8 * (number of ´This is a string´(character string with characters +2) ´SIEMENS´max. 254 characters)

ARRAY user-defined Measured values: ARRAY[1..20](Group of elements INT of the same data type)

STRUCT user-defined Motor: STRUCT(Group of elements Speed : INTof different data types) Current: REAL

END_STRUCT

UDT UDT as block UDT as array element(User Defined Data Type = user-defined“Template" consisting of STRUCT Drive: ARRAY[1..4]elementary or complex Speed : INT UDT1data types Current: REAL

END_STRUCT

Page 185: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Data Storage in Data BlocksPage 7

Structure The slide shows an example of a structure with the name "Motor_data". The structure consists of several elements of different data types. The individual elements of a structure can be elementary or complex data types.The access to the individual elements of a structure contains the structure name. The program is thus easier to read.In order to be able to access the elements symbolically, the data block must be given a symbol name, for example, “Drive_1".Examples of accessing individual elements of a structure:

L “Drive_1".Motor_data.rated_current orL “Drive_1".Motor_data.operating_speed

“Drive_1" is the symbol name of the data block, that contains the structure. The structure name is given (separated by a dot) after the symbol name. An element name of the structure follows (separated by a dot) after the structure name.

Define Structure The keyword for a structure is "STRUCT". The end of a structure is indicated in DB by "END_STRUCT". A name is defined for the structure (in the example: "Motor_data").

Date: 05.12.2005File: PRO1_10E.7

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Example of a Structure

Display in the Program Editor (Data block DB 1):

Operating Speed, data type Integer

Rated Current, data type Real

Startup Current, data type Real

Turning Direction, data type Bool

Structure with the name "Motor_data"(several elementswith different data types)

Motor_data

Page 186: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Data Storage in Data BlocksPage 8

Date: 05.12.2005File: PRO1_10E.8

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Example of an Array

1. Measuring_point, data type Real

2. Measuring_point, data type Real

3. Measuring_point, data type Real

10. Measuring_point, data type Real

Array with the name "Measuring_point"(several elementsof the same data type) •

••

Display in the Program Editor (Data block DB 2):

Measuring_point

Array An array consists of several elements of the same data type. In the slide above, you can see the array "Measuring_point" with 10 elements of the data type REAL.Later, various measured values are to be stored in this array.

Define Array in DB The keyword for an array is "ARRAY[n..m]". The first (n) and the last element (m) is specified in the square brackets. In the example, [1..10] means 10 elements, whereby the first element is addressed with the index [1] and the last with the index [10]. Instead of [1..10] you could, for example, define [0..9]. This only affects access to the elements.

Note To create an empty data block, you define an array with the data type you want.

Data View To see which values are stored in the individual elements, you select the menu optionsView -> Data View to switch to another display. In "Data View“, you will find the values stored presently in the column "Actual Value".

Page 187: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Data Storage in Data BlocksPage 9

Program Editor You can open an existing data block or create a new one with the LAD/STL/FBD Editor.

"New" Dialog Box When you click the icon for "New“, the "New" dialog box is displayed. You select the project and the user program and then enter, for example, DB4 for "Object name" (Data Block or All Editable should be selected as the Object type). When you confirm your entries by clicking the "OK" button, the "New Data Block" dialog box appears.

"New Data Block" In this dialog box, you select the type of data block to be created:Dialog Box • Data Block (global data block)

• Data Block Referencing a User-Defined Data Type (creates a data block using the same structure as a UDT block)• Data Block Referencing a Function Block (creates an instance DB for an FB). This item is explained in more detail in the chapter "Functions and Function Blocks".

Date: 05.12.2005File: PRO1_10E.9

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Creating a New Data Block

Page 188: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Data Storage in Data BlocksPage 10

Entering Data You enter the individual data elements in the table. To do so, you select the first empty line in the "Name" column and enter the element‘s description. You can jump to the other columns - Type, Initial Value and Comment - by using the Tab key.

Columns The meanings of the columns are as follows:

• Address - is entered by the Program Editor when you save.It is the first byte address occupied by the variable in the

data block.• Name - symbolic name of the element.• Type - data type (you select this with the right mouse button).• Initial Value - is used for setting a default value for an element. If you do

not make an entry here, zero will be inserted as the initial value. • Comment - for documenting the data element (optional).

Save You save the data block on the hard disk of the programming device using the "Diskette" icon.

Download Just as the logic blocks, you also have to download the data blocks to the CPU.

Monitor To monitor the current values in the data block, you first of all have to switch to the "Data View" view. You can monitor the data block by using the "spectacles" icon in the toobar (permanent display of the actual values of the DB in the CPU).

Date: 05.12.2005File: PRO1_10E.10

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Entering, Saving, Downloading and Monitoring a Data Block

Page 189: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Data Storage in Data BlocksPage 11

Date: 05.12.2005File: PRO1_10E.11

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Addressing Data Elements

078 Bits

Data Byte 0 DBB 0

Data Byte 1 DBW 0

Data Byte 8191

DBD 8188

DBW 8190DBB 8191

Data Byte 2 DBD 0

Data Byte 3

DBX 4.1

General You address the data elements of a data block byte-by-byte, just as you do bit memories.You can load and transfer data bytes, data words or data doublewords. When using data words, you specify the first byte address (e.g. L DBW 2) with the operation. Two bytes are loaded as of this address. With doublewords, 4 bytes are loaded as of the byte address that you enter.

Number, Length The number of data blocks depends on the CPU you use. The maximum block length is 8KByte for the S7-300 and 64KByte for theS7-400.

Note If you access non-existent data elements or data blocks, the CPU goes into the Stopmode, if you did not program an error OB.

Page 190: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Data Storage in Data BlocksPage 12

Opening a DB The instruction “OPN DB..." opens a global data block. If a global DB was already open, it is automatically closed.If a symbol name (e.g: “Values") was defined for the DB, the data block can also be opened with the instruction OPN “Values" .

Accessing a DB The instructions for read (Load) or write (Transfer) access to a DB are shown in the slide.If the DB was already opened, the simple Load or Transfer instruction is enough.The combined instruction, for example, L DB19.DBW2 includes the DB you want. The instruction contains the opening of the data block.

Symbolic Access A symbolic access is only possible if the following requirements are fulfilled: 1. The DB was given a symbolic name in the symbol table.2. The individual data elements in the data block were given symbolic names with the LAD/STL/FBD Editor.Example: The instruction L “Values".Number opens the DB with the name‘Values' and loads the data element with the name ‘Number'.

Note As a rule, you should use the symbolic access of DBs. This has the following advantages:• the program is easier to read,• it guarantees that the correct DB is accessed,• it is easier to make corrections to the data structure in the DB later on.

With absolute accesses to the DB, you must manually correct all program locations with DB accesses. With symbolic accesses, it is easy to make adjustments using a source program.Working with Source Programs is dealt with in an advanced programming course.

Date: 05.12.2005File: PRO1_10E.12

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Accessing Data Elements

0123456789

DB 19(Symbol name: Values)

Data bit 0.0 with theelement name "Start"

or A DB19.DBX0.0 or A “Values".Start

or L DB19.DBW2 or L “Values".Number

or L DB19.DBB5 or L “Values".Loop

TraditionalAccess

symbolic

Fully-qualified Access

1)

OPN DB19L DBW2

Number

OPN DB19A DBX 0.01)

OPN DB19L DBB5

Loop

absolute

Page 191: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Data Storage in Data BlocksPage 13

Date: 05.12.2005File: PRO1_10E.13

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Validity of an Open DB

OB 1

OPN DB 4L DBW2 DB 4

T DBW 2 DB 4

FC 1

DB 4

CALL FC 1

T DBW 4

DB 5OPN DB 5L DBB6

DB 5L DBW 0

T DBW 8

CALL FC 2

FC 2

DB 5

DB 6

OPN DB 6

L DBB6

DB 2T DB2.DBB 0

DB 2L DBW 4

L DBW 10 DB ??

FB 1

CALL FB1, DB1

???!

Introduction An open data block remains open until a new DB is opened or until a combined instruction (e.g. L DB4.DBW6) accesses another DB.

FC Block Calls If an OB block or an FC block is exited because another function is called, the current data block remains valid. When you return to the calling FC, the data block that was valid when you exited is reopened.

FB Block Calls A function block call is different. An instance DB is always assigned to an FB (more information in the chapter "Functions and Function Blocks"). With the call of a function block, the asssigned instance DB is automatically opened. When you return to the calling block, the previously opened global DB is no longer valid. This means that after FB calls, you must reopen the required global DB.

Note You can open a DB by using the relevant instruction e.g. OPN DB. You can also open the DB by passing parameters to parameter-assignable blocks. Thus, you can use "DB 4.DBW6", for example, as the actual parameter. In this case, DB 4 is opened.

Recommendation: If possible, use the fully-qualified access to data blocks.

Page 192: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Data Storage in Data BlocksPage 14

Use User-defined data types are used for:• creating structured data blocks,• creating arrays, that contain the same structure several times,• creating local variables in FC, FB with a given structure (see the chapter

"Functions and Function Blocks").

The user-defined data types are stored as UDT blocks on the hard disk. They are used as “templates", to save you typing when you create a data block.

User-Defined User-defined data types are made up of elementary data types or other user-Data Type (UDT) defined data types.

These data types cannot be stored in the PLC.Example: Storing recipe data (see next pages).

Date: 05.12.2005File: PRO1_10E.14

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Global DB (Example)UDT block as Template

User-Defined Data Type (UDT)

Flour

Milk

Eggs

Yeast

Sugar

Recipe 2

Flour

Milk

Eggs

Yeast

Sugar

Recipe3

Flour

Milk

Eggs

Yeast

Sugar

Flour

Milk

Eggs

Yeast

Sugar

DB created according to UDT

Recipe1

Flour

Milk

Eggs

Yeast

Sugar

Array with3 elementsof type UDT

Page 193: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Data Storage in Data BlocksPage 15

Entering a Data Type You create a UDT in the LAD/STL/FBD Editor by selecting the menu options File - > New and the Object name UDT.. .You then enter the data structure you want.You must fill in the "Name" and "Type" columns, but you can leave the “Initial Value"and “Comment" columns blank.

Saving a Data Type Finally, you save the data structure (mouse click on the "Save“ icon).

Date: 05.12.2005File: PRO1_10E.15

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Entering a UDT Block

Page 194: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Data Storage in Data BlocksPage 16

Creating a DB When you have defined a data type and saved it as a UDT block, you can create several data blocks with the same data structure.

What to DO 1. Select the menu options File - > New in the Program Editor.2. Select the project and user program and a DB.3. Activate the option "Data block referencing a user-defined data type".4. Select the UDT block you want in the “Reference" box.5. Save the data block.

Date: 05.12.2005File: PRO1_10E.16

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Creating a Data Block Referencing a Data Type

Page 195: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Data Storage in Data BlocksPage 17

Example If you need the same structure several times in one data block, you can use a UDT as a data type, in an array, for example.If the data block DB11 was assigned the symbol name “Cake" in the symbol table, a symbolic access from the user program can appear as follows:

L "Cake".Recipe[2].Eggs

Load the “Number of Eggs" from the second recipe from the data block “Cake“.

Notes You have to switch to "Data View" to be able to change the amount of the ingredients. You can then overwrite the initial values in the "Actual Value“ column with the amounts you want.

To change the structure of a UDT block later on, you have to re-create the data blocks that contain UDTs. As well, all accesses to this data block must be updated. The easiest way to do this is by using a source program.

You can also give UDT blocks symbol names.

Date: 05.12.2005File: PRO1_10E.17

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Example: Array of UDTs

Declaration View

Data View

Page 196: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Data Storage in Data BlocksPage 18

Goal In an earlier exercise, you stored the production data (full, empty and broken bottles) in memory words.These memory words are not retentive. The production data is lost if a complete restart is carried out. To prevent this from happening, you should store the production data in a data block.

What to Do 1. Create a data block DB 5 in the S7 program "FILL" containing the specified variables and the data type INT.

2. Change the FC 18 block in such a way, that the production data (full, empty and broken bottles) is stored in memory words in DB 5 instead.

3. Download the blocks and test your solution on the training unit.

Result It should work.

Date: 05.12.2005File: PRO1_10E.18

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Program for a Bottling Plant - Data Storage

Full bottles (MW102)

Empty bottles (MW 100)

"Broken" bottles (MW 104)

Data block DB5

Variable: full

Variable: empty

Variable: broken

Page 197: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Functions and Function BlocksPage 1

Contents Page

Introduction .................................................................................................................................... 2Temporary Variables ........................................................................................................................ 3Local Data Stack Size …............................................................................................................... 4Byte Requirement of a Block in the Local Data Stack ................................................................. 5Total Occupation in the Local Data Stack ...................................................................................... 6Exercise: Use of Temporary Variables …………........................................................................... 7Example of a Message Display Indicating a Problem in the Process ............................................ 8Parameter-assignable Blocks ......................................................................................................... 9Declaration of the Formal Parameters ........................................................................................... 10Editing a Parameter-assignable Block ....................................................................................... 11Calling a Parameter-assignable Block ......................................................................................... 12Using the EN/ENO Parameters with Block Calls ……….............................................................. 13Exercise: Creating a Parameter-assignable FC Block ................................................................... 14Exercise: Calling a Parameter-assignable FC Block ...................................................................... 15Function Blocks (FBs) ................................................................................................................. 16Function Blocks for Message Display …….................................................................................. 17Generating Instance Data Blocks …............................................................................................ 18The Multiple Instance Model .......................................................................................................... 19Inserting/Deleting Block Parameters Later On ……………............................................................ 20Corrections when Calling Modified Blocks ……......................................................................... 21Exercise: Editing a Function Block ................................................................................................ 22Calling a Function Block and Testing It .......................................................................................... 23Converting an FC to an FB using a Source Program (1) .............................................................. 24Converting an FC to an FB using a Source Program (2) .............................................................. 25Exercise: Recognizing Types of Variables ................................................................................... 26Summary: Block Calls …………………....................................................................................... 27

Date: 05.12.2005File: PRO1_11E.1

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Functions and Function Blocks

Page 198: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Functions and Function BlocksPage 2

Date: 05.12.2005File: PRO1_11E.2

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Introduction

Temporary Variables• are deleted after the associated block is executed

• temporary storage in L stack

• useable in OBs / FCs / FBs

Static Variables• are retained even afterthe block is executed

• permanent storage in DBs

• can only be used in FBs

Local Variables / Data(only valid in one block)

Global Variables / Data(valid in the entire program)

• PII / PIQ

• I/ O

• M / T / C

• DB areas

symbolicabsolute

Access

General Up until now, the inputs and outputs in the bottling plant were addressed with their actual parameters. You could not assign parameters to the blocks.You would choose this procedure, for example, for the creation of a program that is only used once with a special machine.For frequently recurring functions in larger systems, you create universally useable, parameter-assignable blocks (FC, FB). These have formal input and output parameters, that are assigned actual parameters when the block is called. The adjustment of block functionality to the hardware takes place with the parameter assignment when the block is called; the “inner life" of the block does not change.

Local Variables Up until now you have used global variables (bit memories and data blocks) to store production data, for example. In this chapter you will find out more about data storage in local variables.

Temporary Variables Temporary variables are variables that are only stored while the block is being executed. They can be used in all blocks (OB, FC, FB).

Static Variables If the data are to be retained even after the block is executed, they must be stored instatic variables.Static variables can only be used in function blocks.

Page 199: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Functions and Function BlocksPage 3

General Temporary variables can be used in all blocks (OB, FC, FB). They are used to temporarily store information while the block is being executed. The data are lost when the block is exited.The data are stored in the L stack (local data stack). It is a separate memory area in the CPU.

Declaration You define the variables in the declaration table of the block. In the line "temp" you enter a variable name and the associated data type.You cannot predefine a start value here.After you have saved the block, the memory location in the L stack is displayed in the "Address" column.

Access In Network 1, you see an example of the symbolic access to a temporary variable.The result of subtracting is stored in the temporary variable “result".You can also make an absolute access (T LW0). You should, however, try to avoid this since the program is difficult to read.

Note Variable names that begin with the special character # are local variables which# are only valid within the block in which they are declared in the declaration table.

The Program Editor automatically enters the special character.

Date: 05.12.2005File: PRO1_11E.3

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Temporary Variables

Page 200: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Functions and Function BlocksPage 4

Local Data Stack The local data stack (L stack) is a memory area that contains the temporary variables(replacement for scratchpad memories in SIMATIC S5) of the blocks.

Local Data Stack When the operating system calls an OB, an L stack area of 256 bytes is openedSize up while the OB and the blocks called in it are executed.

Every priority class is assigned 256 bytes. The L stack of the 313..316 CPUs has a total of 1536 bytes (1.5kByte).

Priority Classes There are a total of eight priority classes with the S7-300. However, no more than 6 priority classes can be active at the same time. If, for example, OB 100 is active (withpriority class 27), then OB1 (priority class 1) can never be active. Furthermore, the error OBs 80 to 87 for asynchronous errors can only then have priority class 28, if the fault occurs in the startup program. In other words, when they interrupt OB100. More information can be found in the chapter "Organization Blocks".

S7-400 With the S7-400 CPUs, you can decide what the size of the local data stack is for the individual priority classes (Tool: HW Config.). You can deselect the priority classes which you do not need. That way, you can make more local data available to the other priority classes.

Date: 05.12.2005File: PRO1_11E.4

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Execution

Local Data Stack Size

For S7-300:

L stack sizePriority class

256 bytes1

27

Entire size:1.5 Kbyte

(CPU 313..316)

Entire size:1.5 Kbyte

(CPU 313..316)

Startup (one-time execution)

Cyclic execution

256 bytes

256 bytes

256 bytes12

3

2Time-controlledexecution

Time-of-Day Interrupt

Time-Delay Interrupt

Cyclic Interrupt

Error handling in scan cycle

256 bytes16

28

26256 bytes

Event-driven execution

Hardware Interrupt

Error handling in startup

Page 201: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Functions and Function BlocksPage 5

Displaying the You can see the exact number of bytes a block requires in the local data stackByte Requirement by going into the block properties.

Activate 1. In the SIMATIC Manager, select the block with the right mouse button and then -> Object Properties. or

2. In the SIMATIC Manager, select the block with the left mouse button and then the menu options Edit -> Object Properties.

Notes The sum of local data for an execution level (OB) is a maximum of 256 bytes with the S7-300. Every OB itself always takes up 20 or 22 bytes.This means that a maximum of 234 bytes can be used in an FC or FB.

If more than 256 bytes of local data are defined in a block, the block cannot be downloaded into the CPU. The transmission is interrupted with an error message “The block could not be copied". Within this error message is a "Details" button. If you click on it, a message box appears with an explanation “Incorrect local data length".

Date: 05.12.2005File: PRO1_11E.5

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Byte Requirement of a Block in the Local Data Stack

rechts

Page 202: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Functions and Function BlocksPage 6

Total Occupation in You can display the number of bytes an entire program requires in the localLocal Data Stack data stack with the "Reference Data" tool. You will become familiar with this tool in the

chapter “Troubleshooting".The total occupation of the local data stack and the number of bytes required per call path is displayed on the screen.

Activate In the SIMATIC Manager you select the block folder and then the menu optionsReference Data Options -> Reference Data -> Display.

Note If the maximum number of local data is exceeded during program execution in the CPU, the CPU goes into the Stop mode. “STOP caused by error when allocating local data" is entered as the cause of error in the diagnostics buffer.

Date: 05.12.2005File: PRO1_11E.6

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

256

Byt

es

Event

Occupation in the L stack

1

OB1

OB 1

1

Operatingsystem

Total Occupation in the Local Data Stack

FC 2

with temp.variables

OB1

FC2

FC1

3

3

OB1

FC1

4

4

OB1

FC1

6

6

FC 3

with temp.variables

OB1

FC3

FC1

5

5

FC 1

with temp.variables

2

OB1

FC1

2

7

OB1

7

Page 203: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Functions and Function BlocksPage 7

Date: 05.12.2005File: PRO1_11E.7

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Use of Temporary Variables

Replace by the temporary variable

"Packages"

Goal You are not to use any bit memories as temporary storage in the FC 19 block of the S7 program "Fill". These are to be replaced by a temporary variable “Packages".If you wrote a program for the block in LAD or FBD, the bit memories were necessary to connect the output of the divider with the input of the code converter. Even if you wrote a program for the block in STL (where no bit memories are necessary) insert the temporary variable “Packages" for storing.

What to Do • Open the FC 19 block in the S7 program "FILL" . • Define a temporary variable with the name “Packages" and the data type

"Integer“ in the declaration table.• Store the number of packages in the temporary variable.• Download the changed program and test it.

Result You now know the use of temporary variables.

Page 204: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Functions and Function BlocksPage 8

Description Problems (disturbances) that occur are to be displayed by an LED on the operator console. When the problem (I1.3) occurs, the LED (Q8.3 or Q4.3) is to flash with 2Hz. The problem is detected at the acknowledge input I 1.2. If the problem is corrected, the LED stops flashing. If the problem continues, the LED switches to a steady light until the problem is corrected.

Program So that even problems that only exist for a short time are not lost, a dominant set flip flop (M40.0) is used. An RLO edge detection of the message signal is also carried out, since the memory is otherwise immediately reset when an existing problem is acknowledged. If the report memory is set (message has not yet been acknowledged), the upper AND logic operation causes the LED to flash. With this, the bit memory M10.3, that was defined as a clock memory when parameter assignment was made in the CPU, is gated. The lower AND logic operation is used to cause a steady light for a problem that is acknowledged but still exists.

Date: 05.12.2005File: PRO1_11E.8

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Example of a Message Display Indicating a Problem in the Process

Disturbance

LED

Acknowledge

Report Memory

Edge Mem. Bit

Disturb. Input

Acknowl.

Flash Freq.

Disturb. Input

Display

RS

&

=

>=1&QS

RP

Report Memory

Report Memory

Solution Suggestion

Task

Page 205: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Functions and Function BlocksPage 9

Introduction You can use parameter-assignable blocks for frequently recurring program sections. This has the following advantages:• the program only has to be created once• the block is only stored in the user memory once and you can call it as often

as you like • the block can be programmed with formal parameters (input, output or in/out

parameters) and only when the block is called is it given the “real“ addresses(actual parameters).

Example When the block is executed, the statement “A Disturbance input" is checked to see which actual parameters are assigned to the formal parameter “Disturbance input". If, when the block is called, I 1.4 is lined up as the actual parameter, then the statement “A I 1.4" is carried out.

FC / FB Parameter-assignable blocks can either be FCs or FBs.

Parameter- In the example, the message display is required ten times in the system. assignable FC20 It is created as a parameter-assignable FC 20 block and is then called ten times with

different actual parameters.

Date: 05.12.2005File: PRO1_11E.9

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Disturb.input

Reportmemory

Acknowledge

Edge mem.bitDisplay

Flash freq.

FC 20

Call

Parameter-Assignable Blocks

A I 1.2

R M 40.0

A I 1.3

FP M 40.1

S M 40.0

A M 40.0

A M 10.3

O

ANM 40.0

A I 1.3

= Q 8.3

Non-parameter-assignable block

Formal parameters

M 40.0

M 40.1I 1.3

I 1.2 A 8.3M 10.3

Actual parameters

A #Acknowledge

R #Report Memory

U #Disturb. input

FP #Edge mem. bit

S #Report memory

A #Report memory

A #Flashing freq.

O

AN #Reportmemory

A #Disturb. input

= #Display

Parameter-assignable block

Program

Page 206: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Functions and Function BlocksPage 10

Date: 05.12.2005File: PRO1_11E.10

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Declaration of the Formal Parameters

Use Graphic Display

Read only To the left of the blockWrite only To the right of the block

Type of parameter

Input parameterOutput parameterIn/out parameter

Declaration

inoutIn_out Read / write To the left of the block

Formal parameters

Declaration table of the FC 20 block

Formal Addresses Before you can create the program for the parameter-assignable block, you have to define the formal parameters in the declaration table.

Type of Parameter In the table in the slide, you can see three possible types of parameters and their uses. Please make sure that when you have a reading and writing access to a formal address that you use an in/out parameter.

Example of the FC20 In the lower section of the slide, you can see the declaration table for the message display (see previous page). Since the report memory is to be accessed reading (set/reset) as well as writing (query), it has to be defined as an in/out parameter.

Notes There is only one row for every type of parameter in the declaration table. Should you need several input parameters, you have to use the "Return" key when you end your inputs in the first row. An additional row for this type of parameter is then opened up. After you have selected a declaration row, you can also use the menu options Insert -> Declaration Row -> Before Selection / After Selection to insert an additional row.

Attention! If you want to insert or delete declaration rows later - after the block has already been called - , you have to update the block calls !

Page 207: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Functions and Function BlocksPage 11

Date: 05.12.2005File: PRO1_11E.11

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Editing a Parameter-assignable Block

Here was, e.g., with a non-parameter-assignable FC:• with absolute addressing: I1.3• with symbolic addressing: “End_left"

Notes It doesn‘t matter whether the names of the formal parameters are written with capital or small letters. The "#" character in front of the name is automatically inserted by the PG. This is to indicate to you that it is a local variable that was defined in the variable declaration table of this block.

It is possible, that when you write the program in LAD / FBD, that the name is not completely displayed in one row. This depends on how you customized the settings in the Program Editor (Options -> Customize -> "LAD/FBD" tab -> Width of address field).

Symbols 1. If you use a symbolic name when you edit a block, the Editor searches the variable declaration table. If it is there, the symbol with the # in front of it is accepted in the program as a local variable.

2. If it cannot be found as a local variable, the Editor searches the symbol tablefor global symbols.If it is found there, the symbol is placed in quotation marks and is accepted in the program.

3. If you specified the same symbolic name as global (in the symbol table) as well as local (in the variable declaration table), the Editor will always insert the

local variable.If, however, you want to work with the global symbol, you must place the symbol name in quotation marks when you make the entry.

Page 208: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Functions and Function BlocksPage 12

Date: 05.12.2005File: PRO1_11E.12

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Calling a Parameter-assignable Block

Network 3: First Call

Network 4: Second Call

Disturb.input

Acknowledge

Flash freq.

Report memory

Edge mem. bit

Display

M40.1

“Positionerror"

ENO

EN

“End left"

....

“Acknow.button"

M10.3

M40.0

FC20

Disturb.input

Acknowledge

Flash freq.

Report memory

Edge mem. bit

Display

M40.3

Q9.4

ENO

EN

“End right"

A8.1

“Acknow.button"

M10.3

M40.2

FC20

symbolic

absolute

Addressing

Symbols Local Symbols --> Formal parameters

Symbol-table

Global Symbols

Call In LAD/FBD, you can select the call from the "Program Elements" browser. Question marks (??.?) are displayed at the input, output and in/out parameters of the block. Here you insert the actual parameters you want.

Note When you call a parameter-assignable FC block, you must assign all block parameters(with the exception of EN and ENO).

Page 209: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Functions and Function BlocksPage 13

Standard FCs The following rules exist for the execution of standard FCs:• If EN=0, the block is not executed and ENO is also =0. • If EN=1, the block is exeucted and if it is executed without errors ENO is also

=1.If an error occurs while the block is being executed, ENO becomes =0.

User FCs It doesn‘t matter whether a user block was written in LAD, FBD or STL, when it is called in LAD/FBD, the parameters EN and ENO are added as well. Thus it is possible to pass on the RLO.EN/ENO do not exist in STL. You can, however, emulate them.You must program -irregardless of the programming language- an error evaluation.

Interconnection In LAD/FBD, several boxes can be grouped together one after the other and linked logically with EN / ENO.

Date: 05.12.2005File: PRO1_11E.13

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

LAD/FBD STL

Using the EN/ENO Parameters with Block Calls

CALL FC 1 NOP 0

Example

?? . ?

FC 1

EN ENO

FC 2

EN ENO

FC 3

EN ENO =

FC 1

EN ENO?? . ?Unconditional call

A I 0.1 JNB _001 CALL FC 1

_001: A BR = Q 9.0

FC 1EN ENOI 0.1 =

Q 9.0

Conditional call

Page 210: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Functions and Function BlocksPage 14

Task Write the program for a message display as a parameter-assignable block. In the slide you can see the declaration table with the input and output parameters and the beginning of the program.

What to Do • Insert an FC 20 block in the S7 program "My Program" .• Write the program in FC 20.• Save FC 20.

Date: 05.12.2005File: PRO1_11E.14

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Declaration table of the FC 20 block

Exercise: Creating a Parameter-assignable FC Block

Non-parameter-assignable block

Parameter-assign-able FC 20 block

A I 1.2R M 40.0A I 1.3FP M 40.1S M 40.0A M 40.0A M 10.3OAN M 40.0A I 1.3= Q 9.3(Q5.3)

A #AcknowledgeR #Report memoryA #Disturb. ...::::::::

2.

1.

Page 211: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Functions and Function BlocksPage 15

Task Call FC 20 in OB 1 twice (with different absolute addresses). Test the functionality of the program.

What to Do • Insert two networks into the OB 1 from the S7 program "My Program".• Create the two calls to FC 20, as given in the slide,• Download the FC20 and OB 1 blocks,• Test the function.Note: During HW Config, you used MB10 for parameter-assignment of the clock memory byte. If you have performed a memory reset in the meantime, you must download the HW configuration once again to cause the M10.3 to flash.

Date: 05.12.2005File: PRO1_11E.15

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Calling a Parameter-assignable FC Block

Disturb. input

Report memory

AcknowledgeEdge mem. bit

Display

Flash freq.Parameter-assignment of FC20 in the 1st. call

M 40.0

M 40.1I 1.3I 1.2 Q 9.3 (Q 5.3)M 10.3

FC 20

Disturb. input

Report memory

AcknowledgeEdge mem. bit

Display

Flash freq.M 40.2

M 40.3I 1.4I 1.2 Q 9.4 (Q 5.4)M 10.3

FC 20

Parameter-assignment of FC20 in the 2nd. call

Page 212: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Functions and Function BlocksPage 16

Special Features Unlike functions (FCs), function blocks (FBs) have a (recall) memory. Thatof FBs means that a local data block is assigned to the function block, the so-called instance

data block. When you call an FB, you also have to specify the number of the instance DB, which is automatically opened. An instance DB is used to save static variables. These local variables can only be used in the FB, in whose declaration table they are declared. When the block is exited, they are retained.

Parameters When the function block is called, the values of the actual parameter are stored in the instance data block. If no actual parameters are assigned to a formal parameter in a block call, then the last value stored in the instance DB for this parameter is used in the program execution.You can specify different actual parameters with every FB call. When the function block is exited, the data in the data block is retained.

FB Advantages • When you write a program for an FC, you must search for empty bit memory address areas or data areas and you must maintain them yourself. The static variables of an FB, on the other hand, are maintained by the STEP 7 software.

• When you use static variables you avoid the risk of assigning bit memory address areas or data areas twice.

• Instead of the formal parameters “Report memory" and “Edge memory marker" of the FC20, you use the static variables “Report memory" and “Edge memory marker" in the FB. This makes the block call simpler since the two formal parameters are dropped.

Date: 05.12.2005File: PRO1_11E.16

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Function Blocks (FBs)

FB 2EN

Disturb. input

Acknowledge Display

Flash freq. ENO

DB 2

OB 1

Declaration table of the function block

Page 213: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Functions and Function BlocksPage 17

Message Display In an earlier exercise you created a parameter-assignable FC 20 block fordisplaying a message (indicating a problem). Instead of bit memories, that were used in the FC20 to save the message signal and its RLO edge detection, you can use so-called static variables in an FB. They are stored in the instance DB referencing the FB.

Instance DB When a DB is generated and references an FB, STEP7 creates the dataStructure structure of the data block using the structure specified in the local declaration table for

the function block. After you save the DB, the data block is created and can then be used as an instance DB.

Date: 05.12.2005File: PRO1_11E.17

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Function Block for Message Display

Declaration table of the functionblock

Instancedata block

Page 214: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Functions and Function BlocksPage 18

Generating an There are two ways of generating a new instance DB: Instance DB • When you call an FB, you specify with which instance DB the FB is to work. The

following message then pops up:"Instance data block DB x does not exist. Do you want to generate it?".

• When you create a new DB, you select the option "Data block referencing a function block".

Notes One instance DB can only reference one FB. However, one FB can be referenced by a different instance DB every time it is called.If you modify the FB (by adding parameters or static variables), you must then also generate the instance DB again.

Date: 05.12.2005File: PRO1_11E.18

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Generating Instance Data Blocks

1. Generate instance DB with FB call 2. Create new instance DB

Page 215: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Functions and Function BlocksPage 19

Multiple Instance Up until now, you had to use a different instance data block for every call of a Model function block. The number of data blocks is limited however, and for that reason there

is a method that allows you to use a common instance DB for several FB calls.

The multiple instance model now enables you to use a single DB for several calls. To do this, you need an additional FB to manage these instances. For every FB call (FB 20), you define a static variable in the higher-level FB (FB 100). With the block call Call Dist_1, you do not then have to specify an instance DB.

The higher-level FB (FB 100) is called, for example, in OB1, the common instance DB(DB 100) is only generated once.

Note Multiple instances are discussed in an advanced programming course.

Date: 05.12.2005File: PRO1_11E.19

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

The Multiple Instance Model

DB10

The Instance Model

FB20

OB 1

Call FB20, DB10Disturb._Input:=Acknowledge:=Flash_Freq:=Display:=

DB11

FB20

Call FB20, DB11Disturb._Input:=Acknowledge:=Flash_Freq:=Display:=

DB12

FB20

Call FB20, DB12Disturb._Input:=Acknowledge:=Flash_Freq:=Display:=

The Multiple Instance Model

FB 100

DB100

Call FB100, DB100OB 1

stat Dist_1 FB20

stat Dist_2 FB20

Parameters andstatic variablesof the 2nd. call of FB20

Call Dist_2Disturb._Input:=Acknowledge:=Flash_Freq:=Display:=

Parameters andstatic variablesof the 1st. call of FB20

Call Dist_1Disturb._Input:=Acknowledge:=Flash_Freq:=Display:=

Page 216: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Functions and Function BlocksPage 20

Date: 05.12.2005File: PRO1_11E.20

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Inserting/Deleting Block Parameters Later On

Save

The Problem When you add additional block parameters later on to a block already called in the program, you must also update the block call. Otherwise, the CPU would either go into Stop or the block function could not be guaranteed since the additional parameters still have to be supplied with actual parameters in the call.In the example, an additional input parameter “Check_lights" was inserted.

Updating the Call When you save the block in which the declaration table was modified, a message pops up warning you of possible problems.

Page 217: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Functions and Function BlocksPage 21

Date: 05.12.2005File: PRO1_11E.21

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Corrections when Calling Modified Blocks

When the calling block is opened:

Once with the right

Updating the Call When the calling block is opened, the following message pops up“Time stamp conflict with at least one block call" and the call is displayed in red.With the right mouse button, click on the block call and select the menu option “Update Call". The block call is then redisplayed and contains, in our example, the additional input parameter “Check_light“. This parameter can then be assigned. In the case of function blocks, the instance DB is then regenerated.

Page 218: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Functions and Function BlocksPage 22

Date: 05.12.2005File: PRO1_11E.22

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Editing a Function BlockDeclaration table of the FB 20 block1.

Program section of FB 20A #AcknowledgeR #Report memoryA #Disturb. ...::

2.

Task The program for displaying a message (indicating a problem) is now to be implemented in a function block. For saving the edge memory bit and the report memory you are to use static variables that are stored in the instance DB of the FB. That way, you do not require any bit memories for saving.In the slide you can see the declaration table with the input and output parameters and the beginning of the program.

What to Do • Insert an FB 20 block into the S7 program "My Program".• Write the program in the FB 20.• Save the FB 20.

Page 219: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Functions and Function BlocksPage 23

What to Do In the S7 program "My Program":• delete both networks by calling the FC20.• write a program for the two calls to the FB 20, as given in the slide.• download the FB20, DB20, DB21 and OB 1 blocks.• test the functionality of the program.

FC -> FB In our example, FB20 was rewritten, even though an FC20 with the same contents already existed. It was not hard to do.If an FC with an extensive program is to be converted into an FB, you go about it differently:1st. possible solution:

• insert a new FB• copy the declaration table of the FC block into the FB and adjust it• copy the networks from the FC into the FB• save the FB.

2nd. possible solution:• generate a source file from the FC block• make the adjustments in the source file• generate a new FB from the source file (see next page).

Date: 05.12.2005File: PRO1_11E.23

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Calling a Function Block and Testing It

(Q 5.3)

(Q 5.3)

Page 220: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Functions and Function BlocksPage 24

Introduction Just as with higher-level programming languages, you can also create blocks using a source program (text file). When you compile this source program, executable blocks are generated. By the same token, a source file can be generated from existing blocks.You are to make use of this to create, with the least amount of work (typing), an FB 20 from an FC 20 block.

What to Do 1. Open a block.2. In the LAD/STL/FBD Editor, choose the menu options Options ->

Customize, then the "Editor“ tab. In the “View" box select the option"Symbolic representation".

3. In the LAD/STL/FBD Editor select the menu options File -> Generate Source File...4. In the "New" window, you can enter a name of your choice for the source file

to be generated in the "Object name" box.5. In the “Generate Source File" window that then appears, select the program

blocks that are to be compiled one after the other in the “Unselected Blocks“window.

6. Click "OK" to start the compilation of the blocks into source code.The compiled blocks are then found in the source file which you named previously, in the “Source Files" folder of the S7 program.

Date: 05.12.2005File: PRO1_11E.24

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Converting an FC to an FB using a Source Program (1)

Page 221: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Functions and Function BlocksPage 25

Sources, What For? • for automatic rewiring using symbols

• for assigning block attributes, for example, block protection

• as data protection of the entire program

• more freedom in editing and processing blocks:- modifying block type- insert / delete network separations- merging program elements and comments into new blocks- creating program sources in other text editors (WORD, WordPad), without having to install STEP7 in the PC- complete symbolic programming without syntax check, etc.

Source Program In the left-hand section of the slide you can see the source program for the FC 20 block. On the right-hand side, the source file is displayed for the program as FB 20. Here, the associated keywords for a function block were entered. In addition to that, static variables for the report memory and the edge memory marker are defined.After a compilation run, an executable FB 20 exists once more.

Note If you do not know the key words, you can insert a block template using the menu options Insert -> Block Template -> FB.

The subject of “Source Files" is discussed in greater detail in an advanced programming course.

Date: 05.12.2005File: PRO1_11E.25

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Converting an FC Block to an FB using a Source Program (2)

::

::

Page 222: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Functions and Function BlocksPage 26

Date: 05.12.2005File: PRO1_11E.26

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Recognizing Types of Variables

Absolute Symbolic Temporary Static ParameterL #Number_1

T #Max_value

T MW 40

Statement

L #Number_2

L #Intermediate_resultL “Number_1"

T #Number_2

Global Local

Goal You are to recognize the differences between the various types of variables.

What to Do In the table, mark the associated data type with an X.

Answer the following question:What is not correct in the statement T#Number_2 ?

.................................................................................

Result You can recognize and use the types of variables.

Page 223: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Functions and Function BlocksPage 27

CALL The "CALL" instruction is used for calling program blocks (FC, FB, SFC, SFB), regardless of the RLO or any other conditions.If you call an FB or SFB with "CALL“, you must also specify the relevant instance DB.You can use either the absolute or the symbolic name for the program block. For example: "CALL FB2, DB2" or "CALL valve, level".The "CALL" operation saves the return address, deactivates dependence on the MCR and creates the local data area for the block to be called.

UC The "UC" instruction is an unconditional call of a block of the type FC or FB without parameter assignment."UC" is otherwise identical to "CALL".

CC The "CC" instruction calls a block of the type FC or FB without parameters if RLO=1."CC" is otherwise identical to "CALL".

Parameters Parameters declared in the declaration table are known as “formal parameters". The addresses or values specified in the call are referred to as “actual parameters".Static and temporary variables are not specified in the call.

Date: 05.12.2005File: PRO1_11E.27

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Summary: Block Calls

• CALL FC1• UC FC1• CC FC1

STL

LAD

FBDFC1

EN

ENO

FC1EN ENO

FC1

( CALL )

FB

W/o param., w/o inst. DB

• UC FB1• CC FB1

FB1EN

ENO

FB1EN ENO

CALL

With parameters

• CALL FC2Par1: ...Par2: ...Par3: ...

FC2EN ENO

Par3

Par1

Par2

FC2EN

ENO

Par1

Par2

Par3

With param., with inst.DB

• CALL FB2, DB3Par1: ...Par2: ...Par3: ...

FB2EN ENO

Par3

Par1

Par2

DB3

FB2EN

ENO

Par3

Par1

Par2

DB3

Without parametersLan-guage

FC

FC1

Page 224: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 1

Contents Page

System Diagnostics - Overview ...................................................................................................... 2Searching for Errors, that Cause the CPU to go into Stop ............................................................. 3-13Logical Errors ................................................................................................................................. 14-27Sporadic Errors ........................................................................................................................... 28-38System Information ........................................................................................................................ 39-46

Date: 05.12.2005File: PRO1_12E.1

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Troubleshooting

Page 225: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 2

What is Diagnostics? Diagnostics is the integral detecting functions and recording functions of the CPU. The area in which the error information is recorded is called the diagnostic buffer. The size of this buffer depends on the type of CPU (e.g. CPU 314 = 100 messages).

What Happens, when When an error or an event, for example a change of operating mode, occurs, thean Error Occurs? following happens:

• A message stamped with the date and time is entered in the diagnostic buffer. The most recent message is stored at the beginning of the buffer. If the

memory is full, older entries are deleted.• Entry of the event in the system status list.• If necessary, the event activates a relevant error OB (Organization block).

Types of Errors With the help of the CPU diagnostics, the following types of errors can be identified:• System error in the CPU or error in a module• Program errors in the CPU.

Troubleshooting In troubleshooting, a distinction is made between the following error classes:• Errors, that cause the CPU to go into the Stop mode.

Troubleshooting with the "Module Information" tool.• Logical errors, that is, the CPU executes the program, but the function is not

fulfilled.Troubleshooting with the "Referece Data" and "Program Status" tools.

• Sporadic errors, that only occur in particular system states. These can either cause the CPU to go into Stop or occur as a logical error.

Troubleshooting with the "CPU Messages" tool or by creating "your own trigger point".

Date: 05.12.2005File: PRO1_12E.2

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

System Diagnostics - Overview

PG 740

SIEMENS

CPU I/O-ModuleCPU diagnostics detectsa system error

CPU diagnostics detectsan error in the user program

ErrorOB

Diagnosticbuffer

CPUmessages

Diagnostics-capable moduledetects anerror andgenerates adiagnosticinterrupt

Diagnosticinterrupt

Systemstatus list

SFC

Page 226: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 3

Date: 05.12.2005File: PRO1_12E.3

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Searching for Errors, that Cause the CPU to Stop

CPU

Contents Page

Calling the "Module Information" Tool ……................................................................................... 4Module Information Tab: "Diagnostic Buffer" ................................................................................. 5Interpreting Error Messages .......................................................................................................... 6Opening a Block Containing an Error .............................................................................................. 7Diagnostics with I Stack, B Stack, L Stack ...................................................................................... 8B Stack ............................................................................................................................................. 9I Stack ............................................................................................................................................. 10L Stack ............................................................................................................................................. 11Exercise: Finding Stop Errors and Eliminating Them …................................................................. 12Exercise: Troubleshooting with I Stack, B Stack .............................................................................. 13

Page 227: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 4

Introduction The information that you need for troubleshooting is stored in all tools in the functionPLC -> Module Information. You can open this function, for example, from the SIMATICManager or through the Program Editor.

SIMATIC Manager If the project structure is not available on the PG, you click on the "Accessible Nodes"icon and then on MPI=x (x = MPI address on the connected CPU).Now select the menu options PLC -> Module Information.If you have opened a project on the hard disk with the SIMATIC Manager, you can select the menu options PLC -> Module Information after you have chosen the S7 program.

Program Editor As soon as you open a block, the information function for troubleshooting appears.

Date: 05.12.2005File: PRO1_12E.4

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Calling the "Module Information" Tool

Page 228: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 5

Diagnostic Buffer The diagnostic buffer is is a FIFO buffer in a battery-backed memory area in the CPUthat cannot even be deleted by a memory reset. It contains all diagnostic events in the order in which they occurred. All events can be displayed on the programming device in plain text and in the sequence in which they occur.

Details on Event When you select an event, additional information is supplied in the "Details on Event" box: • Event ID and event number,• additional information, depending on the event, such as the address of the

instruction that caused the event,• etc.

Help on Event When you click on the box, help on the event selected in the list is opened.(Example: a programming error has occured, the relevant OB (OB121) is not loaded or activated, however.)

Open Block When you click on the box, the block in which the error occurred can be opened in the CPU. (in the above example: "FC number: 10").

Opening the Tool You open the diagnostic buffer by selecting the menu options PLC --> Module Information --> Diagnostic Buffer tab in the SIMATIC Manager or Program Editor.

Date: 05.12.2005File: PRO1_12E.5

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Module Information Tab: "Diagnostic Buffer"

Page 229: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 6

General The last entry appears at the top of the list. The time shows you which error messages belong together (event no. 1 and 2 in the slide).

Interpreting Errors In our example, a complete restart was performed before the error occurred (event no. 3 to 5). After the restart, the error occurred and caused entries no. 1 and 2.Event no. 1: The CPU went into Stop mode because no error OB was

programmed. The "Details on event" box shows the execution level (priority class), e.g. OB1 (cycle) and the location of the error in the program (FC 10, module address 24).

Event no. 2: The actual cause of the error appears here, e.g. BCD conversion error. The "Details on event" box shows that there is an incorrect

value in accumulator 1 and which error OB is responsible for it (OB 121).

Error OBs Type of error Example Error OB

Programming Error Called block not in the CPU OB 121

Access Error Direct access to module that is eitherfaulty or not present

OB 122

Time error Maximum scan cycle time exceeded OB 80

Power supply fault Backup battery failure OB 81

Diagnostic interrupt Wire break at input of diagnostics-capablemodule

OB 82

CPU hardware fault Incorrect signal level at the MPI interface OB 84 1)

Program execution error Error in updating the process image (modulefaulty)

OB 85

Rack failure Distributed rack or DP Slave failure OB 86

Communication error Incorrect frame ID OB 87

Date: 05.12.2005File: PRO1_12E.6

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Interpreting Error Messages

1) only forS7-400

Page 230: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 7

Opening a Block You can open the block containing the error directly by clicking the "Open Block"button. The block is opened online. In STL, the cursor is positioned in front of the instruction where the error occurred. In LAD/FBD, the network containing the error is displayed.

In our example, we tried to convert the value from the pushwheel buttons from BCD to Integer. An invalid BCD number was presumably in accumulator 1. In this case, reading out the I stack (see following pages) will help you to make a more exact error analysis.

The error occurred in FC 10, Network 3.

Date: 05.12.2005File: PRO1_12E.7

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Opening a Block Containing an Error

Page 231: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 8

Introduction To obtain additional information about the error location, you can read out the stack contents (I Stack, B Stack, L Stack). This enables you to determine, for example, which values were stored in the accumulators before the CPU went into the Stop state.

B Stack The B Stack contains a list of all blocks executed up to the transition to the Stop state.

I Stack The I Stack contains the data of the registers at the interrupt location, such as:

• contents of the accumulators and address registers• which data blocks are open• status word contents• program execution level (e.g. cycle)• interrupted block specifying the network and instruction number • next block to be executed

L Stack The L Stack contains the values of the temporary variables of the blocks. You need some experience to evaluate this data.

Date: 05.12.2005File: PRO1_12E.8

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Diagnostics with I Stack, B Stack, L StackProgram structure Block containing error

Error location

You see the contents of the accumulators, registers, status wordetc. (up to time of interruption) in the I Stack.

You see the values of thetemporary variables up totime of interruption in the L Stack.

Error location

You see the blocks executed up to the errorin the B Stack.

Page 232: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 9

Stacks In order to display the stack information, the CPU must have gone into the STOP mode:• because of a program error• because of a STOP instruction• on reaching a breakpoint.

B Stack The block stack (B Stack) is a graphic representation of the call hierarchy, that is, the sequence and nesting of the called blocks up to the interrupt location. The B Stack contains all interrupts through interrupt OBs and error OBs as well as the open DBs. You will find the direct cause of the STOP mode in the block that is displayed last.

In our example, you can see that the error occurred in the first call of the FC 10 block.

Open Block To open a block online, you select the block in the B Stack list and then click on the "Open Block" button. You can then edit this block. The cursor is located after the faulty instruction (at the beginning of the next instruction).

Date: 05.12.2005File: PRO1_12E.9

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

B Stack

Page 233: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 10

I Stack The interrupt stack (I Stack) always refers to an execution level. Before you can open the I Stack, the organization block concerned must be selected in the B Stack.

Register The contents of all relevant registers at the time of the interruption are displayed in the I Stack screen:• Accumulators

You can select the numbers format for displaying the accumulator contents in the "Display format" list.

• Address registerYou can select the numbers format for displaying the address register contents in the "Display format" list.

• Status wordBits 0 to 8 of the status word are displayed. They are identified with abbreviations according to their meaning.

Point of Interruption The "Point of Interruption" field gives you information about:• the interrupted block, with the option of opening it directly (the cursor is then

located directly in front of the faulty instruction),• the priority class of the OB, whose execution level was interrupted,• open data blocks with their number and size.

Error Example From our example, you can see that the hexadecimal number 0000 000F is stored in accumulator 1. This is not a valid BCD number and for this reason a conversion error occurred during the conversion from BCD to Integer (BTI instruction). This error can occur during the switching of the pushwheel button due to the mechanical contacts. To remedy this, confirm the input by pressing a momentary-contact switch before carrying out the conversion.

Date: 05.12.2005File: PRO1_12E.10

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

I Stack

Page 234: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 11

L Stack The current values of the temporary variables for blocks not ended at the time of interruption are contained in the L Stack.The local data displayed in the L Stack window refer to the block selected in the B Stack. The blocks not yet ended when the CPU switched to the STOP mode are listed in the block stack (B Stack).

Error Example In our example, the two temporary variables, variable1 and variable2 are defined in the FC 10 block.

The declaration table of the FC 10 block shows the relative address in the L Stack in the address column. The variable, variable1 is stored in byte 0 and 1 of the L Stack andthe variable, variable2 in byte 2 and 3.

Thus the variable variable1 contains the value 78H, which corresponds to the Integer number 120. The variable was described in the program with the instructions L 120, T variable1 .The variable, variable2 has the value 08H and this is the result of the last error-free conversion from BCD to Integer.

In the following picture, you can see the relevant program section of the FC 10 block:

Date: 05.12.2005File: PRO1_12E.11

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

L Stack

Page 235: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 12

Goal Troubleshooting a faulty program.

What to Do 1. Carry out a CPU memory reset.

2. Copy the S7 program "ERROR" from the project "ERROR_16" or"ERROR_32" into the HW station "My Station".

3. Download all the blocks from the S7 program "ERROR" from the project "My Project" into the CPU.

4. Perform a complete restart.5. Read out the diagnostic buffer by selecting PLC -> Module Information.

You must select the project "My Project" and the S7 program "ERROR", so that the correct comments are displayed.6. Determine the errors and eliminate them.

Result You are now familiar with the diagnostic facilities for troubleshooting. The CPU executes the program, but the function is not yet fulfilled. The logical errors are eliminated in a later exercise.

Date: 05.12.2005File: PRO1_12E.12

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Finding Stop Errors and Eliminating Them

ResultWhat to DoStep

The CPU memory is reset.Carry out a CPU memory reset.1

Copy the S7 program"ERROR" from the project"ERROR _16" ("ERROR _32") into theHW-Station "My Station".

The project structure is displayed.2

The faulty program is downloaded.Download all the blocks from the S7 program "ERROR" into the CPU.3

The CPU goes into STOP mode.Perform a complete restart.4

The CPU remains in RUN.Find and eliminate the errors,that lead to the Stop state.5

Page 236: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 13

Task You are to determine additional error information by reading out the Stacks.

What to Do Carry out the steps in the slide above and answer the following questions:

Date: 05.12.2005File: PRO1_12E.13

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Troubleshooting with I Stack, B Stack

ResultWhat to DoStep

The CPU goes into STOP once more.Switch on the inputs I 1.0 to I 1.2 in sequence.1

Answer the questions in the tablebelow.

Clarify the cause of the error with thehelp of the diagnostic buffer and theStacks.

2

The CPU remains in RUN.Switch the inputs I 1.0 toI 1.2 off again.3

Error 1Questions Error 2 Error 3In which block and at whichinstruction did the erroroccur?

What is the cause of the error?

Which blocks were executedup to the error?

Which values were in the accumulators at the errorlocation?

Why did the error occur?

Which data blocks wereopen?

Page 237: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 14

Contents Page

Displaying Reference Data ............................................................................................................... 15Filtering Reference Data ................................................................................................................... 16Cross References ............................................................................................................................ 17Filtering Cross References .............................................................................................................. 18Reference Data: Find ....................................................................................................................... 19Block Correction using Cross References ........................................................................................ 20Go to Location ………….................................................................................................................. 21Assignment of I,Q,M,T,C ................................................................................................................... 22Unused Symbols / Addresses without Symbols ….......................................................................... 23Program Structure ............................................................................................................................. 24Comparing Blocks (1) ......................................................................................................................... 25Comparing Blocks (2) ... .................................................................................................................. 26Exercise: Eliminating Logical Program Errors .................................................................................. 27

Date: 05.12.2005File: PRO1_12E.14

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Logical Errors

??

Page 238: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 15

Introduction For logical errors, you use the "Program Status" and "Reference Data" tools intensively. In the Program Status you have, for example, recognized that a bit memory is not fulfilled as a condition. Using the Reference Data, you can determine where this bit memory is created.A frequent cause of errors is the multiple assignment of addresses. This means that an address is assigned from several locations in the program. Such errors are easy to find when you use the "Reference Data" tool.

Reference Data The Display Reference Data is triggered in the SIMATIC Manager (with the "Blocks" folder opened offline) by selecting the menu options Options -> Reference Data -> Display or ->Filter…. .

Filter The reference data are displayed as filtered data (regardless of whether the item Display or Filter… was selected in the menu Options.The narrower you define the filter, the faster the reference data is displayed.When you open the Display Reference Data, a message pops up that filtered data will be displayed. For this reason, check how the filter is currently set.

Lists The Reference Data can be found in 6 different lists:

• Cross References• Assignment of I/Q/M• Assignment of T/C• (User) Program Structure• Unused Symbols• Addresses without Symbols

Date: 05.12.2005File: PRO1_12E.15

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Displaying Reference Data

Page 239: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 16

Filter You can open the window for filtering the reference data two different ways:1. In the SIMATIC Manager by selecting the menu options Options ->

Reference Data -> Filter….2. In the SIMATIC Manager by selecting the menu options Options ->

Reference Data -> Display and in the "Display Reference Data" window selecting the menu options View -> Filter or by clicking on theFilter icon

"Customize" Window After you open the tool, the "Customize" window appears.In it, you can select which of the 6 reference data lists are to be opened first.

Date: 05.12.2005File: PRO1_12E.16

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Filtering Reference Data

Page 240: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 17

Cross References You open the cross references in the "Display Reference Data" window by selecting the menu options View -> Cross References or by clicking on the relevant icon.The Cross References is a list of used addresses pertaining to a user program:

- inputs,- outputs,- bit memories,- counters,- timers, etc.(see next page)

Table The cross references list is structured as a table. It has the following columns:Column Contents / Meaning --------------------------------------------------------------------------------------------------------• Address absolute address of the operand(address)• Symbol symbolic name of the address• Block blocks in which the address is used• Type read-only (R) or write-only (W) access• Language programming language in which the block was created • Details instruction with which the address is addressed

Cross Reference When you select an address in the cross references list, you can open a newfor Address window by selecting the menu options View -> Cross Reference for Address. This

window contains only the cross references for the selected address.

Date: 05.12.2005File: PRO1_12E.17

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Cross References

Page 241: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 18

Addresses You determine which type of address is to be listed by activating the appropriate checkbox.

Filter Area The filter area establishes the address area to be displayed. You can also enter several part areas. The filter area entry "10-50; 70; 100-130" means that the address 70 and the address areas from 10 to 50 and from 100 to 130 are to be displayed.

Access Type In the standard setting, all access types are displayed. You can also choose the option"Selected" and then select the access type, for example, W, write-only access, with the checkboxes.

Columns You determine the number and the contents of the columns for the tabular structure of the cross references list using check boxes.

Standard If the settings you have planned are to be accepted for the next start of the application "Display Reference Data", you must activate the checkbox "Save as standard".The basic setting or what you have saved as standard are reproduced using the "Default" button.

Date: 05.12.2005File: PRO1_12E.18

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Filtering Cross References

Page 242: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 19

Find While reference data are displayed, you can start a search for a character string. The window can be found in one of the following views:• Cross References• Assignment• Unused Symbols• Addresses without Symbols.

Note The search is a pure text search, that is, the entries must be "exact - including every dot, dash and space". Additional settings are:• search for address, symbol, block or language,• the character string entered as search term is a whole word or part of a word,• capital/small letters are to be taken into account or ignored,• the search range and the direction of the search can be specified.

Date: 05.12.2005File: PRO1_12E.19

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Reference Data: Find

Page 243: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 20

What to Do With a double-click on an address in the cross references list, you open the LAD/FBD/STL Editor and display the block where the selected address is used. The cursor is located in the network in which the address is used.

Note Please note that the reference data are only formed from the blocks in the offline data management. For that reason, modified blocks are always to be saved.

Date: 05.12.2005File: PRO1_12E.20

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Block Correction using Cross References

2x

Page 244: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 21

Date: 05.12.2005File: PRO1_12E.21

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Go to Location

1xright

Introduction In troubleshooting, it is often only necessary to determine where one address is used or assigned in the program. In this case, it makes more sense to use the "Go to Location" function instead of the cross references list. The Go to Location is called directly from the Program Editor and gives you an excerpt from the cross references list for the specific address.

Handling Select an address in the Program Editor and click on it with the right mouse button. Then choose the menu option Go to Location. In the "Go to Location" window, all program locations are displayed where this address is used in the program. In the "Details" column, you can see whether the address is queried or assigned. In the example, the program location where the output Q 8.2 is set and reset is of interest. After selecting the relevant line, you can jump to this program location by selecting the "Go To" button. By selecting the "Starting Point" button, you return to the starting point.

Access Type By default, all accesses to the address are displayed. By selecting the "Selected"button, you can, for example, display write-only accesses (assignment, set, reset).With the "Overlapping access to memory areas" option, word-by-word accesses to the address are displayed as well, for example.

Page 245: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 22

Assignment I/Q/M You open the Assignment of I/Q/M by selecting the menu options View -> Assignment -> Inputs, Outputs and Bit Memory or by clicking on the relevant icon.This assignment list gives you an overview of which bit is used in which byte of the memory areas input (I), output (Q) and bit memory (M). Every line contains a byte of the memory area, in which the eight bits are identified according to access. You can also see whether the access is byte-oriented, word-oriented or doubleword-oriented.Meanings of the IDs in the Assignment List I/Q/M:

• - the address is not addressed and therefore still free• o bit-oriented access• x byte-, word- or doubleword-oriented access

Assignment T/C You open the Assignment of T/C by selecting the menu options View -> Assignment -> Timers and Counter or by clicking on the relevant icon.This assignment list gives you an overview of which timers and counters are used in the program.Ten timers or counters are displayed in every line.

Filter By selecting "Filter", you can choose the memory areas to be listed and restrict the individual address areas.The same rules as for filtering in the Cross References list apply.

Date: 05.12.2005File: PRO1_12E.22

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Assignment of I,Q,M,T,C

Page 246: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 23

Unused Symbols When you select the menu options View -> Unused Symbols or click on therelevant icon, a list of addresses appears. These addresses are defined in the symbol table but are not used in the S7 user program.

Addresses When you select the menu options View -> Addresses without Symbols or clickwithout Symbols on the relevant icon, a list of addresses appears. These addresses have been used in

the S7 user programm but are not defined in the symbol table.A line consists of the address and the number of times it was used.

Filter You use "Filter" to make selections of detailed information for the display of unused symbols (see slide).

Date: 05.12.2005File: PRO1_12E.23

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Unused Symbols / Addresses without Symbols

Page 247: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 24

Program Structure The program structure describes the call hierarchy of the blocks in an S7 user program.

Filter Depending on the settings of the filter, the program paths are displayed in a Tree structure (see slide) or as "Parent/child structure" (in each case the calling and the called block are displayed).

Symbols The following symbols are only possible in the tree structure display:< maximum : nnn > • the maximum memory requirement (in bytes) of the local data is given in the root

of the tree structure.[ nnn ] • per path, the maximum memory requirement (in bytes) of the local data is

stated at the last block of every program path.

Date: 05.12.2005File: PRO1_12E.24

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Program Structure

Page 248: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 25

Date: 05.12.2005File: PRO1_12E.25

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Comparing Blocks (1)

...see next page

Introduction You can compare blocks between online and offline data management or between two user programs on the hard disk of the PG.With this function, you can determine whether, for example, program corrections were made in the CPU later on and in which network the blocks differ.

What to Do • With the right mouse button, select the block folder of an S7 program.• Select the menu option Compare Blocks.• Choose whether you want to compare online/offline or between 2 offline

programs and acknowledge with the "OK" button.• In the follow-up screen, the blocks that differ are listed.• Select the line in which a difference was determined and then select the

"Details" button.• In the "Compare Blocks - Details" window you can ascertain when the block was modified and if the block length was changed.• After selecting the "Go To..." button, the differing block, for example, is

opened online and offline in two windows and the network, in which the first difference was determined is displayed.

Note: Program corrections can only be made in the offline window.

Page 249: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 26

Date: 05.12.2005File: PRO1_12E.26

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Comparing Blocks (2)

Differences After selecting the "Go To..." button (see previous page), the Program Editor is opened with two windows side-by-side, in which the network with the first difference is displayed.

Example In the above example, M8.5 is used in the offline block and M8.6 is used in the online block as the auxiliary memory marker for the RLO edge detection of I 8.5. That means, that after the block was downloaded into the CPU, a correction was made either to the offline or to the online block.You can identify which of the two blocks was modified last by reading out the the time stamp in the "Compare Blocks - Results" screen (see previous page).

Page 250: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 27

Date: 05.12.2005File: PRO1_12E.27

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Eliminating Logical Program Errors

• Can you select the "Manual" mode?

• Can the conveyor belt be traversed in jog mode?

• Switch on the Automatic mode !

• Does the bottle stop at the bottle sensor for filling?

• Is there a message when the minimum level was exceeded?

• Is the number of packaging units displayed on the digital display?

Goal So far you have corrected all the errors which caused the CPU to go into the Stop mode.Now you are to check the function of the bottling plant and eliminate any remaining logical errors. You are to use the checklist in the slide to do so.The functioning of the plant corresponds to the program which you yourself have created up until now.

What to Do Check the functions of the bottling plant according to the checklist and eliminate the remaining errors. Use the program for troubleshooting (Errors that lead to the Stop mode), which can still be found in the CPU and eliminate the errors.

Result The bottling plant is fully functional.

Page 251: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 28

Contents Page

Displaying CPU Messages ............................................................................................................ 29Writing User Messages in the Diagnostics Buffer ......................................................................... 30Configuring Your Own Message Texts ............................................................................................ 31Calling the SFC 52 Block ................................................................................................................. 32Structure of the EVENTN Parameter of the SFC 52 Block .............................................................. 33Diagnostics-Capable Modules ......................................................................................................... 34Displaying the Hardware Diagnostics in the SIMATIC Manager .............................................. 35Exercise: Enabling Diagnostic Messages ........................................................................................ 36Exercise: Outputting User Messages ............................................................................................. 37Exercise: Enabling Diagnostic Interrupts and Simulating Hardware Faults .................................. 38

Date: 05.12.2005File: PRO1_12E.28

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Sporadic Errors

Page 252: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 29

CPU Messages With this function you can immediately display an error message for sporadic errors in the system on a programming device or an HMI device. A message window pops up on the PG or OP as soon as the connected CPU goes into Stop because of an error (see bottom left of the slide).User messages can also be output with a system function.

Registered Modules The list contains all CPUs called in the SIMATIC Manager with the menu optionsPLC -> CPU Messages. The list is divided into four columns:1. In the first column, an icon displays whether a connection was interrupted by the external partner.2. In the column "W", system diagnostic and user diagnostic messages are

activated /deactivated.3. In the column "A", interrupt messages are activated / deactivated. The"CPU Messages" application checks if the module in question even supports diagnostic and interrupt messages. If this is not the case, a message is output.4. In the column "Module", the name of the module or the path of the S7 program is entered.

Incoming Messages • Top: As soon as a message is received, the "CPU Messages" window pops up on top, the message is displayed and at the same time it is entered in the message archive.

• Background: The receiving of the messages takes place in the background.Messages are displayed in the window, but the window remains in the background. The messages are archived and can be displayed as required.

• Ignore: Messages are neither displayed nor archived.

Archive You can modify the size of the archive (40 to 2000 messages) or empty the archive by selecting the "Archive" button.

Date: 05.12.2005File: PRO1_12E.29

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Displaying CPU Messages

Page 253: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 30

Introduction The FC 52 system function permits you to write your own messages, for example, lower limit for hydraulic pressure violated, in the diagnostic buffer. Parallel to this, the message can also be displayed on the programming device or OP. The diagnostics messages must be enabled for this purpose.

Program The SFC 52 system function is called and assigned parameters in the user program. Certain standard texts are stored in the CPU. A parameter of SFC selects these texts. You will find more information in the Standard and System Functions manual, or in theOnline Help.

Example SFC 52 is called in the program example, if the analog value of peripheral input word352 exceeds the value of 2000 units. The message is output only once as a result of logic edge detection. The block is assigned parameters in such a way that a diagnosticmessage is also output on the PG (SEND = TRUE). The EVENTN parameter determines the text to be output.

L PIW 352 // Read in analog valueL 2000 // analog value >2000>IFP M 30.1 // RLO edge detectionJCN nonecall SFC 52 // User entry in the diagnostic buffer

SEND: TRUEEVENTN: W#16#9B83 // external, incoming, limit value exceededINFO1: MW 100 // Additional information 1INFO2: MD 102 // Additional information 2RETVAL: MW 31 // Return value with error information

none: BE

Date: 05.12.2005File: PRO1_12E.30

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Writing User Messages in the Diagnostic Buffer

SEND =TRUE

1 2

Send buffer

Diagnostic buffer

Sendingasynchronousto user program

Node

e.g. PG, OP

CPU

SFC 52

Page 254: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 31

Date: 05.12.2005File: PRO1_12E.31

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Configuring Your Own Message Texts

Aufruf With the right mouse button, click on an S7 program and select the menu optionsSpecial Object Properties -> Message.

Configuring Message You begin with the "New Message" button. The next free message number, for example, A003 is suggested. In the "Text" tab, you can enter the message text for incoming and outgoing messages.You can change the message number in the "Identification" tab.

Wildcards Up to two wildcards can be inserted in the message text. These values are passed via the parameter "INFO1/INFO2" of the SFC 52.In the example, the value of INFO 2 is output as a real number.To insert a wildcard, you begin with the @ character. This is followed by 1 or 2, depending on whether you want to display the value from INFO1 or INFO2. The format declaration then follows with, for example, %e.

The following format declarations are possible:

• %ix hexadecimal number with i places• %iu unsigned decimal number with i places• %id signed decimal number with i places• %e normalized floating-point number, signed value of the form• %E normalized floating-point number, as for format %e, but an upper-case

letter stands before the exponent (E instead of e)

Page 255: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 32

Date: 05.12.2005File: PRO1_12E.32

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Calling the SFC 52 Block

Network 2: User message when limit value exceeded

ENO

RET_VAL #error_sfc52

SFC 52

EN

SEND

EVENTN

INFO 1

INFO 2#analog value_normalized

#dummy

W#16#A901

M 0.1

M 0.1

P

#analog value_normalized

5.000000e+003

CMP>R

IN1

IN2

>=1

M 90.1

Introduction In the slide you can see a program example, in which a user message is entered in the diagnostic buffer and is displayed through the CPU messages.

Description The SFC 52 block is called conditionally through the input "EN" if the analog value exceeds the limit value of 5000.The "SEND" input has the signal state "1" and as a result, the message is sent to a PG logged-in with CPU Messages.At input "EVENTN" it was specified that the first message of group A is to be displayed as an incoming event.You can enter wildcards in the message text through the inputs "INFO1/INFO2". In the example, the analog value is to be displayed as well.The "RET_VAL" output delivers an error message if:• the message cannot be sent because no node is logged-in or the buffer is full, or• the SFC52 was assigned parameters with invalid values or formats in the call.

Page 256: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 33

Date: 05.12.2005File: PRO1_12E.33

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Structure of the EVENTN Parameter of the SFC 52 Block

Event class

15 14 13 12EVENTN

1..9 are standard texts for the different events(see the Standard and System Functions manual)

A..B free texts, that are specified using Message Configuration

C..F reserved for expansions in the future

Event class

11 10 9 8

Identification

Specifies if it is an incoming or an outgoing event, or, an internalor an external event, for example:

Bit 8= "1" --> incoming messageBit 8= "0" --> outgoing messageBit 10= "1" --> internal faultBit 11= "1" --> external fault

Identification

7 6 5 4 3 2 1 0

Event number

Continuous message number from 1 to 255 within anevent classEvent number

General You can see the structure of the EVENTN parameter in the slide. It is an input parameter of the SFC 52 block, with which you specify which message text is to be entered in the diagnostic buffer.

Page 257: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 34

General The signal modules also have modules with diagnostics capability. Errors on the module or external errors such as wirebreak, are identified and indicated by an "SF"LED on the module. In case of an error, the module triggers a diagnostic interrupt OB 82 on the CPU. You can refer to the technical data in the ST 70 catalog or the manuals to determine which modules have diagnostics capability.

Parameter To activate the diagnostics on a module, click on the box in front of DiagnosticAssignment Interrupt when assigning parameters and specify which channels are to be monitor.

Then the fields with the errors to be monitored, for example, wirebreak, are enabled. The slide shows the example of the diagnostics capable analog module 335, which is used in Version A of the training unit.

Diagnostic Interrupt If no OB 82 is present in the CPU, the CPU goes to the Stop state if there is a module error.The start information for OB 82 contains additional information about the error cause,which can be evaluated by the software (see Online help).

Date: 05.12.2005File: PRO1_12E.34

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Diagnostics-Capable Modules

Assigning parameters for a diagnostics-capable module:

... trigger a diagnosticsinterrupt OB 82when an error occurs

Page 258: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 35

Introduction With this function, you obtain a quick overview of the state of the PLC system. If, for example, there is a hardware fault in a diagnostics-capable module, you can identify, through the use of a symbol, which module is faulty and where it is located. When you double-click on the faulty module, additional information is displayed.

Opening the Tool Select the menu options PLC -> Diagnose Hardware in the SIMATIC Manager or in the HW Config tool, by opening the station online with a click on the icon in the toolbar.

Description When you open the system diagnostics, the hardware configuration is read out from the CPU (see left-hand screenshot). In this view, all modules present (even those in expansion racks or distributed I/O) are displayed. If the CPU is in Stop mode or if there is a fault in a module, this is indicated with symbols.You can double-click the CPU or a faulty module to obtain further diagnostic information(see right-hand screenshot). In the example, there is a power failure in the analog module.

Note If you have selected the menu options Options -> Customize -> View in the SIMATIC Manager and activated (checked) the "Display Quick View when Diagnosing Hardware"checkbox, only a list of faulty modules will be displayed instead of the full "Diagnosing Hardware" window.

Date: 05.12.2005File: PRO1_12E.35

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Displaying Hardware Diagnostics in the SIMATIC Manager

2x

Page 259: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 36

Goal When the CPU goes into STOP because of a sporadic error, a message is to appear immediately on the PG. You then have the chance to carry out an error analysis right away.

What to Do • Switch over to the SIMATIC Manager and choose the S7 program "MyProgram" from the "My Project" project and select the menu options PLC => CPU

Messages.• In the window that now appears "Customize - CPU Messages", activate the "W" option in front of the project.• Now, using the keyswitch, switch the CPU to STOP and monitor the reaction on the PG.

Result A screen pops up with the cause of the Stop.

Date: 05.12.2005File: PRO1_12E.36

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Enabling Diagnostic Messages

Page 260: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 37

Goal A system is to be monitored as to whether and when manual operation was switched on. A message is to be entered in the diagnostics buffer for an edge at the "Manual" flip-flop.

What to Do • Use the reference list for the S7 program "FILL" to determine which output is used as the memory for the manual operating mode.• Insert a new network at the end of FC 15 (S7 program "FILL").• Create a program that enters a message in the diagnostics buffer when the

manual operating mode is switched on (RLO edge detection).The assignment of the SFC 52 system function is shown in the slide (with the

exception of the call condition).• Download the FC 15 to the CPU and test the program.

Result A message is entered in the diagnostic buffer when the manual operating mode is switched on. If the "CPU Messages" tool is still active, the user message is also displayed on the PG.

Date: 05.12.2005File: PRO1_12E.37

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Outputting User Messages

SFC 52

SEND

EVENTN

INFO1

INFO2

RET_VALTRUE

W#16#9101

MW 54

MD 56

MW 52

???*

*

* a contact must be connected to the EN for programming in LAD !

EN

Page 261: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 38

Goal The diagnostics are to be activated at the analog module so that hardware faults, such as power supply failure, can be detected.

What to Do Carry out the steps given in the slide.

Result You obtain additional information about hardware faults through the "Diagnose Hardware" tool.

Date: 05.12.2005File: PRO1_12E.38

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Enabling Diagnostic Interrupts and Simulating HardwareFaults

Step What to Do Result

Enable the diagnostic interrupt at the analog module ! (HW Config.)1 The hardware diagnostic is activated

2 Download the configuration in the CPU

3 Remove the front connector on theanalog module !

The "SF" LED on the analog moduleindicates a hardware fault

4 The configuration is opened onlineActivate the "Diagnose Hardware"tool !

5 The message "Power supply failure" is given as the cause of the error

Clarify the cause of the error with the tool !

Page 262: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 39

Contents Page

System Information - Overview ........................................................................................................ 40Module Information: "Memory" Tab …............................................................................................. 41Module Information: "Scan Cycle Time" Tab ..................................................................................... 42Module Information: "Time System" Tab ........................................................................................ 43Module Information: "Performance Data" Tab ................................................................................. 44Performance Data: Blocks .............................................................................................................. 45Exercise: Reading Out System Information ..................................................................................... 46

Date: 05.12.2005File: PRO1_12E.39

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

System Information

Page 263: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 40

Module Information The display of system information is started in the SIMATIC Manager or in theLAD/STL/FBD Editor by selecting the menu options PLC -> Module Information... . Information about module information is summarized in the following tabs:• General• Diagnostic Buffer• Memory• Scan Cycle Time• Time System• Performance Data• Communication• Stacks

"General" Tab This tab gives you information about:• Module data (Version, Order No.)• Location• Module Status

Date: 05.12.2005File: PRO1_12E.40

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

System Information - Overview

Page 264: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 41

Load Memory The load memory is integrated in the CPU (RAM). The usage is displayed in the left bar graph.If a memory card is inserted in the CPU, the middle bar graph is relevant.Additional information is also stored in the load memory. For that reason, the usage of the load memory is always higher than that of the work memory.

Work Memory Only the information required for program execution in the CPU is stored in the work memory.

Compressing Gaps that exist in the work memory can be eliminated by selecting the "Compress"button.These gaps are caused by program corrections in the CPU. With block corrections, the old blocks are not overwritten, rather they are only declared as invalid. The modified blocks are added to the free end of the memory and thus occupy new memory after every correction.

Compressing is only required with the S7-400. The work memory is automatically compressed with the S7-300.

Date: 05.12.2005File: PRO1_12E.41

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Module Information: "Memory" Tab

Page 265: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 42

General Scan cycle time is defined as the time that the CPU requires to update the process image tables, execute the user program, carry out all diagnostic functions, andcommunicate with the programming devices.

"Scan Cycle Time" The "Scan Cycle Time" tab gives you the following information about cyclicTab program execution:

• Longest cycle time duration since the last switch from STOP to RUN,• Shortest cycle time duration since the last switch from STOP to RUN,• Current / previous cycle time duration,• Display of the Configured scan cycle monitoring time (maximum scan cycle time)and• Display of the Configured minimum scan cycle time (only for S7-400).

That way, you can implement constant cycle times. A new cycle always begins when the minimum scan cycle time has run out.

Date: 05.12.2005File: PRO1_12E.42

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Module Information: "Scan Cycle Time" Tab

Page 266: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 43

Clock This box only displays the data from the integrated real-time clock in the CPU. (See below for notes on setting the time.)

Correction Factor The correction factor for adjusting the clock is entered in the "HW_Config" window (see the chapter "Hardware Configuration").

Clock There are several ways of synchronizing the clock:Synchronization • within a PLC system, for example, with multicomputing,

• on the MPI network between Master and Slave• with MFI (multifunctional interface) for point-to-point connection.

Run-time meter For measuring the operating time of an apparatus.The following system functions exist in the CPU for a run-time meter:• SFC2 set to a default value• SFC3 starting and stopping• SFC4 reading out the current elapsed hours.

The number of run-time meters depends on the type of CPU (max. 8). The value range lies between 0 and 32767 hours.

Set Date and Time There are two ways of setting the date and time on the module:1. In the SIMATIC Manager by selecting the menu options PLC -> Set Date and Time2. Using the system function SFC0 to set the date and time.

Date: 05.12.2005File: PRO1_12E.43

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Module Information: "Time System" Tab

... in the SIMATIC Manager:PLC -> Set Date and

Time

Page 267: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 44

Application The information on the available memory lets you determine before you download your program, whether the program you developed offline can be executed by the target CPU.

Performance Data This tab page contains the following information:• size of the work memory• size of the integrated load memory• size of the maximum slot-in load memory• size of the address areas: process image inputs, process image outputs, bit

memory, timers, counters and local data

Properties You can determine how much memory the user program requires in the CPU by"Block Folder" selecting the Properties of the block folder in the SIMATIC Manager.

Date: 05.12.2005File: PRO1_12E.44

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Module Information: "Performance Data" Tab

... in the SIMATIC Manager:• Blocks folder-> Properties

Page 268: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 45

Blocks When you click on the "Blocks" button, the Performance Data tab also gives you information about which blocks can be downloaded into the available CPU. The following information is displayed:• Organization blocks• System functions• the maximum possible number of FCs, FBs, DBs, and• the maximum length of the blocks.

Date: 05.12.2005File: PRO1_12E.45

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Performance Data: Blocks

Page 269: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1TroubleshootingPage 46

Goal Becoming familiar with the available system information using the menu options PLC -> Module Information.

What to Do 1. In the SIMATIC Manager or in the LAD/STL/FBD Editor, select the menu options PLC -> Module Information.

2. Choose the tab page you want.3. Ascertain how much memory is still available in the work memory.4. Determine what the longest scan cycle time has been up until now.

Result You become familiar with a tool that will give you important diagnostic information when dealing with faults.

Date: 05.12.2005File: PRO1_12E.46

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Reading Out System Information

Page 270: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Organization BlocksPage 1

Contents Page

Overview of the Organization Blocks ……...................................................................................... 2Startup OBs ........................................................................................................................................ 3Interrupting the Cyclic Program …………....................................................................................... 4Time-of-Day Interrupt (OB10) ........................................................................................................... 5Cyclic Interrupt (OB35) ...................................................................................................................... 6Hardware Interrupt (OB40) ................................................................................................................ 7Time-Delay Interrupt (OB20) .............................................................................................................. 8Diagnostic Interrupt, Asynchronous Error Interrupt (OB81...87) ....................................................... 9Asynchronous Error OBs .................................................................................................................. 10Synchronous Errors .......................................................................................................................... 11System Functions for Controlling Interrupt OBs ............................................................................... 12Start Information of OBs .................................................................................................................. 13Exercise: Determing the Type of Startup in OB100 .......................................................................... 14Exercise: Setting the System Time ................................................................................................... 15Exercise: Creating a Flashing Light with Cyclic Interrupt .................................................................. 16Exercise: Writing a Program for a Time-of-Day Interrupt ................................................................. 17

Date: 05.12.2005File: PRO1_13E.1

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Organization Blocks

Operatingsystem

OB1

FC

FB

SFC

SFB

OtherOBs

FC

FB

Page 271: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Organization BlocksPage 2

Date: 05.12.2005File: PRO1_13E.2

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

OB 10...17(Time-of-dayinterrupts)

OB 80...87(Asynchronous errors)

OB 20...23(Time-delay interrupts)

Overview of the Organization Blocks

Periodicprogramexecution

OB 30...38(Cyclic interrupts)

Event-drivenprogramexecution

OB 40...47(Hardware interrupts)

Startup

OB 102

OB 100

OB 101

Cyclicprogramexecution

OB 1

OB 121, 122(Synchronous errors)

Interrupt OBs Error OBs

Startup A startup program is carried out before the cyclic program execution after a power recovery, or a change of operating mode (through the CPU‘s mode selector or by the PG). OB 100 to OB 102 are available for this. In these blocks you can, for example, preset the communications connections.

Cyclic Program The program that is to be continuously executed is stored in the OrganizationExecution Block OB 1. After the user program has been completely executed in OB 1, a new cycle

begins with the updating of the process images and the processing of the first statement in OB 1. The scan cycle time and the response time of the system is a result of these operations. The response time is the total of the executing time of the CPU‘s operating system and the time it takes to execute all of the user program.The response time, that is, how quickly an output can be switched dependent on an input signal, is equal to scan cycle time x 2.

Periodic Program With periodic program execution, you can interrupt the cyclic program executionExecution at fixed intervals. With cyclic interrupts, an OB 30 to OB 37 organization block is

executed after a preset timing code has run out, every 100 ms for example. Control-loop blocks with their sampling interval are called, for example, in these blocks. With time-of-day interrupts, an OB is executed at a specific time, for example every day at 17:00 hours (5:00 p.m.), to save the data.

Event-driven The hardware interrupt can be used to quickly respond to a process event. After Program the event occurs, the cycle is immediately interrupted and an interrupt programExecution is carried out.

The time-delay interrupt reponds after a delayed time period to a process event.With the error OBs you can determine how the system is to behave, for example, if the backup battery fails.

Page 272: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Organization BlocksPage 3

Start Organization blocks are started exclusively by the operating system. There are various starting events that lead to a start of the associated organization blocks in the corresponding priority class.Organization blocks can contain a normal control program, and also a declaration table.

Priorities Every OB program execution can be interrupted by a higher priority event (OB) at command boundaries. Priorities are graduated from 0-27, whereby 0 has the lowest priority and 26 has the highest priority. OBs of the same priority do not interrupt each other, but are started one after the other in the sequence they are recognized.

Startup The S7-300 has the complete restart type of startup. With it, the process images and the non-retentive timers, counters and bit memories are deleted. Program execution in OB 1 starts with the first statement.The S7-400 also has the restart type of startup. All data (bit memories, timers, counters, process images) are retained. Program execution resumes from the point where the interruption occurred.With a complete restart, OB 100 is executed and with a restart, OB 101 is executed.

Cold Restart The 318-2 and 417-4 CPUs also have the cold restart type of startup. You can specify this additional type of startup for a power failure. It is made with the HW Configuration when you assign parameters to the CPU. With a cold restart, all bit memories, timers, counters and the process images are deleted. The data blocks retain their preset values and the program resumes with the first statement in OB 1 after the OB 102 startup block is executed.

Date: 05.12.2005File: PRO1_13E.3

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Read in PII

Execute OB1

Output PIQ

Complete restart

automatic manual

S7-300 / 400

Power ON

S7-300

STOP->RUN

S7-400

STOP->RUN+ CRST

Deleting the process images,non-retentive M, T, C

Execution of OB 100

Enable outputs

Read in PII

Enable outputs

STOPyes

no

Monitoring timefor restart exceeded ?

Delete PIQ (parameter-assignable)

Process residual scan cycle

Execution of OB 101

Execute OB1

Restart (manual)

• only for S7-400 (according to setting in HW Config):STOP -> RUN + WRST

Startup OBs

Output PIQ

CYCLE

CYCLE

Page 273: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Organization BlocksPage 4

OBs Organization blocks (OBs) are the interface between the operating system of the CPU and the user program. OB1 either contains the cyclic program itself or organizes it (by calling other blocks).

Calling Organization blocks cannot be called by other blocks. They are called by the operating system in response to certain events, e.g. :• on CPU startup• at a set time of day• at constant intervals• when a set period of time has elapsed• when errors occur• when hardware interrupts occur

Priority Organization blocks are executed in the order of priority assigned to them (1 = lowest and 29 = highest priority).

Interrupting When another OB is called by the operating system, cyclic program execution isthe Cyclic Program interrupted because OB1 has the lowest priority. Any other OB can therefore interrupt

the main program and execute its own program. Afterwards, execution of OB1 is resumed at the point of interruption.If an OB with a higher priority that the one currently being executed is called, this is interrupted after the current statement has been completed. The operating system then saves the entire register stack for the interrupted block. This register information is restored when the operating system resumes execution of the interrupted block.

Date: 05.12.2005File: PRO1_13E.4

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

E.g. OB82 (Prio.26) =Error handling.Executed in event ofwire break at analoginput PIW 352

E.g. OB10 (Prio.2) =Time-of-day interrupt.Executed once a minute from 9:30

OB1is executed continu-ously .....

OB 1

3Time-of-day interrupt

Cyclic interrupt

1

16Error handling

Cyclic program

Time-delay interrupt

Hardware interrupt

2

12

26 / 28

OB 20

OB 40

OB 10

OB 35

OB 82

OB No. OB Type Priority

E.g. OB20 (Prio.3) =Time-delay interrupt.Execution starts 3.25s after a part is detected.

Interrupting the Cyclic Program

...... until it is interruptedby another OB

Page 274: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Organization BlocksPage 5

Date: 05.12.2005File: PRO1_13E.5

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Time-of-Day Interrupt (OB10)

Time-of-Day Time-of-day interrupts are used for executing a certain program called in OB 10 Interrupts either once only at a certain time or periodically (once a minute, hourly, daily, weekly,

monthly, yearly) starting at that time.You configure time-of-day interrupts with the "HW Config" tool. To select when and how OB10 is to be activated choose the menu options CPU -> Object Properties ->-> “Time-of-Day Interrupts" tab.

"Active" If you check the "Active" checkbox, the time-of-day interrupt OB is executed on every complete restart of the CPU.

Note Time-of-day interrupts can also be controlled by system functions at run time. The following system functions are available:• SFC 28 "SET_TINT" Set starting date, time and period• SFC 29 "CAN_TINT" Cancel time-of-day interrupt• SFC 30 "ACT_TINT" Activate time-of-day interrupt • SFC 31 "QRY_TINT" Query time-of-day interrupt.

S7-400 There are up to eight different time-of-day interrupt OBs (OB 10 to 17) for the S7-400 PLC.

Page 275: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Organization BlocksPage 6

Cyclic Interrupt Cyclic (watchdog) interrupts are used for executing blocks at fixed intervals. The cyclic interrupt OB for the S7-300 is OB 35. The default call interval for OB 35 is 100ms. You can change this to a value within the permitted range from 1ms to 1 minute.

Starting Time When you activate a time-controlled interrupt, you specify the interval in relation to the "starting time". The starting time begins every time the CPU mode changes from STOP to RUN.

Interval You must make sure that the interval you specify is longer than the time required for execution. The operating system calls OB35 at the specified time. If OB35 is still active at this time, the operating system calls OB80 (cyclic interrupt error OB).

Note Cyclic interrupts cannot be controlled by system functions at run time.

S7-400 There are up to nine different cyclic interrupt OBs (OB30 to 38) for the S7-400 PLC.

Date: 05.12.2005File: PRO1_13E.6

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Cyclic Interrupt (OB35)

RUN OB35 OB35 OB35Interval

OOB1 B1OB1 OB1 OB1 OB1 OB1 O B1

Interval Interval

Page 276: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Organization BlocksPage 7

Hardware Interrupt The program in a hardware interrupt OB (OB40) is executed as soon as a certain event occurs. Hardware interrupts can be triggered by various module-specific signals:• For parameter-assignable signal modules (DI, DO, AI, AO) you use the

"HW Config" tool to specify the signal that is to trigger a hardware interrupt.• In the case of CPs and FMs, you specify the interrupt characteristics using the configuration software for the module concerned.

Example In the example above, suitable limit values have been configured for an analog input module. If the measured value exceeds the limit, OB40 is called.This has the same effect as including a comparison operation in OB1 which causes an FB or FC to be called when the upper limit is reached. However, if you use OB40 you don't need to write a program in another block. You can use the program in OB40 for interrupt generation or for process control.

S7-400 There are up to eight different hardware interrupt OBs (OB40 to 47) for theS7-400 PLC.

Date: 05.12.2005File: PRO1_13E.7

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Analog input module

Upper limitvalueLower limitvalue

+27648

0

Hardware Interrupt (OB40)HW Config:

Properties of theanalog input module

Properties of the CPU

Page 277: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Organization BlocksPage 8

Time-Delay The program in a time-delay OB (OB20) is executed with a specified delayInterrupt after a certain event has occurred.

OB20 can only be activated by calling system function SFC32 (SRT_DINT). SFC32 is also used for setting the delay time.

SFC 32 • OB_NR = Number of the OB to be executed with a time delay.• DTIME = Delay time (1 to 60000ms)• SIGN = User-specified signal for starting the time-delay interrupt OB• RET_VAL = Error code, if an error occurs during execution of the time-

delay interrupt OB (See on-line help for meanings of error numbers).

Note Apart from SFC32, the following SFCs are also available for dealing with time-delay interrupts:• SFC33 (CAN_DINT) = Cancel time-delay interrupt• SFC34 (QRY_DINT) = Query time-delay interrupt.

S7-400 There are up to four different time-delay interrupt OBs (OB20 to 23) for theS7-400 PLC.

Date: 05.12.2005File: PRO1_13E.8

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

( P ) ( )I 0.0 M0.1 SFC 32

(SRT_DINT)EN ENO

OB_NR

DTIME

SIGN

RET_VAL20

T#500ms

W#16#01

MW10

M2.0

Time-Delay Interrupt (OB20)

Page 278: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Organization BlocksPage 9

Asynchronous Asynchronous errors are faults in the functionality of the PLC. They occurErrors asynchronously to the execution of the program and cannot be traced to a particular

point in the program (e.g. a diagnostic interrupt from a module).

Response If a fault is detected in RUN mode and the relevant error OB has been programmed, it is called and the program in it is executed. This program could, for example, contain:• instructions for switching on a siren• instructions for data backup, followed by a STOP instruction• a program for recording the frequency with which the fault occurs, without

causing the CPU to go into STOP mode.

Note If the error OB for a particular fault is not present, the CPU automatically goes into STOP mode.

Example Asynchronous error interrupt OB82 is called in the following situations, for example:• Wire break on a module with diagnostic capability• Failure of the power supply to an analog input module• Measuring range of an analog input module exceeded, etc.

Date: 05.12.2005File: PRO1_13E.9

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Analog input module

Wire break

+27648

0

Diagnostic Interrupt, Asynchronous Error Interrupt (OB81...87)HW Config:

Properties of theanalog input module

Propertiesof the CPU

Page 279: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Organization BlocksPage 10

Priority The error OBs called in response to asynchronous errors are executed immediately because they have the highest priority of all interrupt and error OBs:• Priority 26 if the error occurs while an OB with lower priority (<26) is being

executed• Priority 28 if the error occurs while a startup OB (priority 27) is being executed.

Date: 05.12.2005File: PRO1_13E.10

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Asynchronous Error OBs

Type of error Example OB

Time error Maximum scan cycle time exceeded OB80

26 / 28

Priority

26

Power supply fault Backup battery failure OB81

Diagnostic interrupt Wire break at input of diagnostics-capablemodule OB82

Insert / remove interrupt

Removal of a signal module during operation of an S7-400 OB83

CPU hardware fault Incorrect signal level at theMPI interface OB84

Program execution error Error in updating the process image(module defective) OB85

Rack fault Failure of an expansion device or a DP slave OB86

Communication error Error in reading message frame OB87

Page 280: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Organization BlocksPage 11

Synchronous These errors can be traced to a particular point in the program if the error occurredErrors during execution of a particular statement. The error OBs called in response to synchronous

errors are executed as part of the program, with the same priority as the block that was being executed when the error was detected.

Date: 05.12.2005File: PRO1_13E.11

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Synchronous Errors

Type of error Example OB Priority

Same as that of the OBinterrupted as a result of the error

Programming errorA block that is not present in theCPU is called in the program OB121

Access errorA module which is either defectiveor not present is addressed in the program (e.g. direct access to anon-existent I/O module)

OB122

Page 281: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Organization BlocksPage 12

OB's You will find a complete list and a description of the error OBs in the online help:LAD/STL/FBD Editor -> Help -> Contents -> Help on Blocks -> Help on Organization Blocks.

SFC's The system functions and their uses, how to call them and assign parameters to them are discussed in an advanced programming course.

Date: 05.12.2005File: PRO1_13E.12

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

System Functions for Controlling Interrupt OBs

Organization block

Function NumberPriority

in S7-300SFCs for controlling OBs Remarks

Time-of-day interrupt OB 10 ... 17 2 SFC 28 ... 31 Alternative to HW Config

Time-delay interrupt OB 20 ... 23 3 SFC32 ... 34 Mandatory

Hardware interrupt OB 40 ... 47 16 none

Diagnostic interrupt OB 81 ... 87 26 none

Cyclic interrupt OB 30 ... 38 none12

Page 282: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Organization BlocksPage 13

Date: 05.12.2005File: PRO1_13E.13

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

4 / 5

6 / 7

8 / 9

10 / 11

Data formats of L-Bytes 8, 9, 10, 11

Additional info 1 (e.g. start address of interrupt module)

Additional info 2 (e.g. interrupt status)

Additional info 3 (e.g. channel number)

L-Byte

0 / 1

2 / 3

Start event

Priority

Consecutive number

OB No.

12 / 13

14 / 15

16 / 17

18 / 19

Year

Day

Minutes

1/10 Second, 1/100 Second

Month

Hours

Seconds

1 /1000 Second, Weekday

Managementinformation

Startinformation

Starttime

Start Information of OBs

Start Information You have a uniform system start information in the local data stack when the OB is called by the operating system. The start information has a length of 20 bytes and is available after the start of OB execution.

Access to The STEP 7 software makes a standard declaration table available for theStart Information symbolic access to start information (example for OB 81).

Note You can change or supplement the standard declaration table.The meanings of the variables are explained to you in the online help or in the Standardand System Functions manual.

In the example, the variable OB8_FLT_ID contains an identifier, if and which backup battery has failed.

Page 283: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Organization BlocksPage 14

Task: The S7-300 only has the one startup OB 100. If you want to respond accordingly in the program to the type of startup, you have to evaluate the start information in OB 100. The operating system enters the following identifiers in the variable OB100_STRTUP:

• B#16#81 = manual complete restart• B#16#82 = automatic complete restart.

You are to write a program for the OB 100 so that the output Q 8.4 or Q4.4 is set for a manual complete restart and the output Q8.5 or Q 4.5 is set for an automatic complete restart.

Example of an evaluation of a manual complete restart

L OB100_STRTUP //Load startup identifierL B#16#81 //Load hexanumber 81==I //Compare for sameness= Q 8.4 //Display type of startup

What to Do: 1. Open the OB 100 block from the S7 program of the HW-Station "My Station"(Project "My Project")

2. Supplement the program in OB 100.3. Download the block in the CPU and test your program.

Date: 05.12.2005File: PRO1_13E.14

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Step What to Do Result

1You are to insert the OB100 block in the S7 program of the HW-Station "MyStation" and write a program for the OB100 according to the task.

The type of startup is programmedin the startup block

2 Download the OB100 block in the CPU

3 Test your program The LEDs on the simulator light updepending on the type of startup.

Exercise: Determining the Type of Startup in OB100

Page 284: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Organization BlocksPage 15

Task To set the correct system time of the S7 CPU.

What to Do 1. Select the menu options PLC -> Set Date and Time (SIMATIC Manager orProgram Editor).

2. Enter the correct date and the exact time in the dialog box.

Date: 05.12.2005File: PRO1_13E.15

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Setting the System Time

Page 285: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Organization BlocksPage 16

Task You would like to use a flashing frequency of 3 Hz. This frequency is unfortunately not available in the flashing frequency bit memory.Set up a flashing frequency in the bit memory M35.0 with the help of a cyclic interrupt.

Note Use the S7 program of the HW-Station "My Station" in the project "My Project".

Date: 05.12.2005File: PRO1_13E.16

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Creating a Flashing Light with Cyclic Interrupt

You are to assign parameters to the call interval for OB 35 according to the task

Step What to Do Result

1

Create and save OB 35 and download it2

3Check the function Bit memory M 35.0 flashes with 3 Hz

Page 286: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Organization BlocksPage 17

Task As of today, the horn on the conveyor model is always to switch on at the end of the course (ask your trainer).The acoustic message is to be acknowledged using an empty input on the simulator.

Note Use the S7 program of the HW-Station "My Station" in the project "My Project".

Result You will be woken in time to go home.

Date: 05.12.2005File: PRO1_13E.17

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Writing a Program for a Time-of-Day Interrupt

You are to assign parameters to the CPUso that the time-of-day interrupt is executedat the end of the course

Step What to Do Result

1

Create and save OB 10 according to thetask and then download it2

3Check the function At the end of the course, the horn sounds

Deactivate the time-of-day interrupt anddownload the changed configuration.4

Page 287: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Analog Value ProcessingPage 1

Contents Page

Use of Analog Modules ……............................................................................................................ 2Measuring Range Modules .............................................................................................................. 3Analog Module Addresses with S7-300 …....................................................................................... 4Analog Module SM335 (Inputs) …................................................................................................... 5Analog Module SM335 (Outputs) .................................................................................................... 6Analog Input Module SM331 ........................................................................................................... 7Analog Value Representation and Measured Value Resolution ....................................................... 8Analog Value Representation of Different Measuring Ranges ....................................................... 9Scaling Analog Input Values ......................................................................................................... 10Unscaling a Real Number for Analog Output .................................................................................. 11Analog Value Representation for the Analog Outputs ...................................................................... 12Exercise: Assigning Parameters to the Analog Module SM335 ....................................................... 13Exercise: Assigning Parameters to the Analog Module SM331 ....................................................... 14Exercise: Controlling the Level in a Tank …………......................................................................... 15Exercise: Diagnostic Interrupt from an Analog Module ..................................................................... 16

Date: 05.12.2005File: PRO1_14E.1

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Analog Value Processing

Leveltransmitter

High level

Low level

Page 288: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Analog Value ProcessingPage 2

Principle In a production process, there are a variety of physical quantities (pressure, temperature, speed, rotational speed, pH value, viscosity, etc.) that need to be processed in the PLC for automation purposes.

Sensor Measuring sensors respond to changes in the quantity to be measured by linear expansion, angular ductability, alteration of electrical conductivity, etc.

Transducer Measuring transducers convert these above-mentioned changes into standard analog signals, such as: ± 500mV, ± 10V, ± 20mA, 4...20mA.These signals are supplied to the analog input modules.

ADC Before these analog values can be processed in the CPU, they must be converted to digital form. This is done by the ADC (Analog-to-Digital Converter) on the analog input module.The analog-to-digital conversion is performed sequentially, that is, the signals are converted for each analog input channel in turn.

Result Memory The result of the conversion is stored in the result memory and remains there until it is overwritten by a new value. The converted analog value can be read with the Load instruction “L PIW...”.

Analog Output The Transfer instruction “T PQW...” is used to write the analog values calculated by the user program to an analog output module, where a DAC (Digital-to-Analog Converter) converts them to standard analog signals.

Analog Actuators with standard analog input signals can be connected to the analog output modules direct.

Date: 05.12.2005File: PRO1_14E.2

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Use of Analog ModulesProcess

Physical quantity

Standardanalog signal

Sensor Transducer

• Pressure• Temperature• Flow• Speed• pH value• Viscosity• etc.

± 500mV± 1V± 5V± 10V± 20mA4...20mAetc.

DAC

PQW ...PQW ...:::PQW ...

Analog output module

MRmodule ADC

Resultmemory

PIW ...PIW ...:::PIW ...

Analog input module CPU

::::::L PIW 352

T PQW 368:

Analogactuator

Physicalquantity

......................................

Page 289: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Analog Value ProcessingPage 3

Type of Measurement You set the type of measurement and the measuring range by setting coding keys on the measuring range module. Special modules without coding keys have different terminals for voltage and current measurement. Thus, the type of measurement can be set by wiring the appropriate terminal.

Measuring Range The measuring range modules with their coding keys are located on the left-Module hand side of the module. You must set them correctly before installing the module.

The possible settings are “A”, “B”, “C” and “D”. The settings for the various types of measurement and measuring ranges are printed on the module.

Channel Groups On some modules, several channels are grouped together to form a channel group. In this case, the coding key setting applies to the whole channel group.

Date: 05.12.2005File: PRO1_14E.3

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Measuring Range Module

Page 290: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Analog Value ProcessingPage 4

Address Area The S7-300 has a special address area for analog inputs and outputs, which is separate from the process image input and output tables for the digital modules (PII/PIQ).This address area extends from byte 256 to byte 767. Each analog channel occupies 2 bytes.

Access You access the analog modules by means of Load and Transfer instructions.Example: The statement “L PIW256” reads the first channel of the first module in rack 0.

S7-400 On the S7-400, the address area for the analog modules starts at byte 512.

Date: 05.12.2005File: PRO1_14E.4

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Analog Module Addresses with S7-300

IM 256to270

336to350

352to366

368to382

304to318

320to334

272to286

288to302

(Send)

Slot 2 3 4 5 6 7 8 9 10 11

384to398

400to414

432to446

448to462

464to478

480to494

496to510

416to430

Rack 1

R0

PowerSupply

IM(Receive)

PowerSupply CPU

512to526

528to542

544to558

560to574

576to590

592to606

608to622

624to638

Rack 2 IM(Receive)

PowerSupply

Rack 3 640to654

656to670

672to686

688to702

704to718

720to734

736to750

752to766

IM(Receive)

PowerSupply

Page 291: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Analog Value ProcessingPage 5

Diagnostic Interrupt When the diagnostic interrupt is activated and a hardware fault occurs, such as a power supply failure, a diagnostic interrupt (OB 81) is triggered. As well, you must specify in the "Diagnostics" field which inputs are to be monitored. A wire break check is only possible with 4 to 20 mA power inputs.

Scan Cycle Time The scan cycle time is the time it takes for the module to process ("convert") all the activated analog inputs once. The setting for the scan cycle time for A/D conversion can be between 0.5ms and 16ms.When it has processed all the analog inputs, the module can trigger a hardware interrupt (= End of Cycle interrupt) (only if a scan cycle time for conversion longer than 1ms has been selected).

Note Unused inputs must be short-circuited on the hardware and "Deactivated" in the software. Deactivated analog inputs reduce the scan cycle time!

Measuring Range When the type of measurement and the measuring range have been selected, Module the necessary coding key setting on the measuring range module is displayed.

Example: For the measuring ranges selected in the slide above, the measuring range module must be inserted in position “C”.

Resolution The analog inputs of the SM 335 have a resolution of 13 bits + sign, the analog outputs11 bits + sign.

Date: 05.12.2005File: PRO1_14E.5

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Analog Module SM335 (Inputs)

Page 292: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Analog Value ProcessingPage 6

Note Unused output channels must remain open on the hardware (not be short-circuited like the analog inputs) and be “deactivated” in the software.

Date: 05.12.2005File: PRO1_14E.6

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Analog Module SM335 (Outputs)

Page 293: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Analog Value ProcessingPage 7

Parameters You can set two groups of parameters for analog input modules with the “HW Config”tool:

Module as a Whole • Diagnostic Interrupt:If the “Group Diagnosis” checkbox has been activated and a diagnostic event occurs, the relevant information is entered in the diagnostics data area of the module and the diagnostic interrupt (OB82) is triggered.The analog module can detect the following diagnostic events:- Configuration/ parameter assignment errors- Wire break (if "With Wire Break Check" is activated)- Above measuring range- Below measuring range- No load voltage L+

• Hardware Interrupt when Limit Value ExceededIf the input value exceeds the range set by the entries for "Upper Limit Value" and "Lower Limit Value", the module triggers a hardware interrupt.Note: Only the first channel in a group can monitor the input value for violation of the selected limit values!

Individual Inputs • Type of Measurement: When you click this box, the possible types of measurement (voltage, current...) are displayed. For unused channels orchannel groups you select the "deactivated" option. You must connect these channels to chassis ground on the module

• Measuring Range: When you click this box, the possible measuring ranges for the type of measurement selected are displayed.• Coding Key Setting: A very specific setting of the measuring range module

becomes necessary when you select the type of measurement and the measuring range. This is displayed here.

• The integration time and interference frequency suppression are interdependent (see next page).

Date: 05.12.2005File: PRO1_14E.7

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Analog Input Module SM331

Page 294: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Analog Value ProcessingPage 8

Representation Analog values are represented as the two's complement. The value is positive if bit No. 15=0 and negative if bit No.15=1.

Resolution If the resolution of an analog module is less than 15 bits, the analog value is written into the accumulator left-justified. The unused less significant bit positions are filled with “0”s.

Integration Time The resolution is specified indirectly by selecting an integration time with the “HW Config” tool.The following table for the SM331 illustrates the relationship between integration time, resolution and interference frequency suppression:Integration time Resolution Interference frequency suppression

(ms) (in bits) (Hz)2.5 9 + sign bit 40016.6 12 + sign bit 6020 12 + sign bit 50100 14 + sign bit. 10

Accuracy Resolutions of between 8 and 15 bits are possible, depending on the type of module.

Conversion Time The conversion time depends on the conversion procedure used in the module (integrating procedure, successive approximation).The conversion times of the different modules are given in the S7-300 manual. Example: The SM344 has a conversion time of only 5 ms for all 4 input channels.

Date: 05.12.2005File: PRO1_14E.8

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Analog Value Representation and Measured Value Resolution

20212223242526272829210211212213214VZHex.Bit value Dec.

0123456789101112131415Bit no. Units

Reso-lution in bits+ sign

1 11 ******** * * * * * * *15

* = 0 or 1

80 00000001128 ********8

40

20

10

8

4

000000

00000

0000

000

00

02

164

132

116

18

14

12

******** *

******** * *

******** * * *

******** * * * *

******** * * * * *

******** * * * * * *

9

10

11

12

13

14

Page 295: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Analog Value ProcessingPage 9

Voltage, Current Encoding the symmetrical voltage or current ranges(Symmetrical) • ± 80mV • ± 2.5 V • ± 3.2 mA

• ± 250 mV • ± 5V • ± 10 mA• ± 500 mV • ± 10V • ± 20 mA• ± 1 Vresults in a rated range of -27648 to +27648.

Voltage, Current Encoding the asymmetrical voltage or current ranges(Asymmetrical) • 0 to 2 V • 0 to 20 mA

• 1 to 5 V • 4 to 20 mAresults in a rated range of 0 to +27648.

Resistance Encoding the resistance ranges• 0 to 150 Ohm• 0 to 300 Ohm• 0 to 600 Ohmresults in a rated range of 0 to +27648.

Temperature Temperatures are measured with resistance thermometers or thermocouples. Encoding results in a rated range of ten times the temperature range:Sensor: Temperature range: Rated range when encoded:• Pt 100 -200 to + 850 ºC -2000 to + 8500• Ni 100 -60 to + 250 ºC -600 to + 2500• Thermocouple type K -270 to + 1372 ºC -2700 to + 13720• Thermocouple type N -270 to + 1300 ºC -2700 to + 13000• Thermocouple type J -210 to + 1200 ºC -2100 to + 12000• Thermocouple type E -270 to + 1000 ºC -2700 to + 10000.

Date: 05.12.2005File: PRO1_14E.9

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Analog Value Representation of Different Measuring Ranges

Range

Overflow

Overrange

Rated range

Underrange

Underflow

Meas.range± 10V

Voltagee.g.:

>= 11.759

11.7589:

10.0004

10.007.50:

-7.5-10.00

- 10.0004:

- 11.759

<= - 11.76

Units

32767

32511:

27649

2764820736:

-20736-27648

- 27649:

- 32512

- 32768

Meas.range4 .. 20mA

Currente.g.:

>= 22.815

22.810:

20.0005

20.00016.000::

4.000

3.9995:

1.1852

<= 1.1845

Units

32767

32511:

27649

2764820736::

0

- 1:

- 4864

- 32768

Meas.range-200...+850ºC

Temperaturee.g. Pt100

Units

32767

10000:

8501

8500:::

-2000

- 2001:

- 2430

- 32768

>= 1000.1

1000.0:

850.1

850.0:::

-200.0

- 200.1:

- 243.0

<= - 243.1

Meas.range0...300Ohm

Resistancee.g.:

>=352.778

352.767:

300.011

300.000225.000::

0.000

Negative valuesnot possible

Units

32767

32511:

27649

2764820736::

0

- 32768

- 1:

- 4864

Page 296: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Analog Value ProcessingPage 10

Example The level in a tank is to be measured in liters. The measuring transformer was chosen in such a way that 500 liters have an analog value of 10 V.

Scaling The analog module encodes the analog value 10 V as the integer value 27 648. This value now has to be converted to the physical quantity “liters”. This is known as “scaling” the analog value.

Program Standard block FC 105 is used for scaling analog values. FC 105 is supplied with the STEP 7 software in the library "Standard Library" in the S7 Program"TI-S7 Converting Blocks".

IN The analog value at input IN can be read in from the module direct or read from a data interface in INTEGER format.

LO_LIM, HI_LIM Inputs LO_LIM (low limit) and HI_LIM (high limit) are used for specifying the limits for conversion to physical quantity. In the example the reading is scaled to the range 0 to 500 liters.

OUT The scaled value (physical quantity) is stored as a real number at output OUT.

BIPOLAR The input BIPOLAR determines whether negative values are also to be converted. In the above example, memory bit M0.0 has a signal "0" and thus indicates that the input value is unipolar.

RET_VAL The output RET_VAL has the value 0 if execution is free of errors.

Date: 05.12.2005File: PRO1_14E.10

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Scaling Analog Input Values

500,0

0,00 27648

Page 297: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Analog Value ProcessingPage 11

Example The user program calculates an anaolg value in the range 0 to 100.0%. This value is to be output via an analog output module.

Unscaling Standard block FC106 is used for unscaling (conversion of a real number from 0 to 100.0% to a 16-bit integer between 0 and 27648).

OUT The unscaled analog value at output OUT can be transferred in the form of a 16-bit integer to a data interface or to the module direct.

Program FC 106 is supplied with the STEP 7 software in the library "Standard Library" in the S7 Program "TI-S7 Converting Blocks".

Date: 05.12.2005File: PRO1_14E.11

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Unscaling a Real Number for Analog Output

27648

0 0,0 100,0

Page 298: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Analog Value ProcessingPage 12

Voltage, Current For symmetrical voltage or current ranges a rated range ofSymmetrical -27648 to +27648 is converted to:

• ± 10V• ± 20mA.

Voltage, Current For asymmetrical voltage or current ranges a rated range ofAsymmetrical 0 to +27648 is converted to:

• 0 to 10V• 1 to 5V• 0 to 20mA• 4 to 20mA.

Overflow If the value to be converted reaches the overflow range, the analog output module is disabled (0V, 0mA).

Date: 05.12.2005File: PRO1_14E.12

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Analog Value Representation for the Analog Outputs

Range

Overflow

Overrange

Rated range

Underrange

Underflow

Units

>=32767

32511:

27649

27648:

0:

- 6912

- 6913:::

- 27648

- 27649:

- 32512

<=- 32513

Output ranges:

Voltage

0

11.7589:

10.0004

10.0000:0

0 to 10V 1 to 5V

0

5.8794:

5.0002

5.0000:

1.0000

0

11.7589:

10.0004

10.0000:0:::::::

-10.0000

- 10.0004:

- 11.7589

0

± 10V

0 0.9999

0

0

Output ranges:

Current

0

23.515:

20.0007

20.000:0

0 to 20mA 4 to 20mA

0

22.81:

20.005

20.000:

4.000

0

23.515:

20.0007

20.000:0:::::::

-20.000

- 20.007:

- 23.515

0

± 20mA

0 3.9995

0

0

Page 299: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Analog Value ProcessingPage 13

Note Depending on which analog module is in your training unit, you are to do either this exercise or the one on the following page.

Goal To get to know how to change the settings and parameters of analog modules.

What to Do Change the settings of your analog module to correspond to those in the slide.

Date: 05.12.2005File: PRO1_14E.13

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Assigning Parameters to the Analog Module SM335

Page 300: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Analog Value ProcessingPage 14

Note Depending on which analog module is in your training unit, you are to do either this exercise or the one on the previous page.

Goal To get to know how to change the settings and parameters of analog modules.

What to Do Change the settings of your analog module to correspond to those in the slide.

Date: 05.12.2005File: PRO1_14E.14

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Assigning Parameters to the Analog Module SM331

Page 301: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Analog Value ProcessingPage 15

Task The tank has a maximum capacity of 600 liters. The level is measured using a measuring transducer. It has an analog value of 10 V when the maximum level is reached. This analog value is to be converted to a physical quantity (number of liters)using the FC 105 block. If the level goes below the minimum 50 liters, the output Q 9.2 (Q 5.2) is to flash until the level is once more 50 liters or more.

The first potentiometer on the simulator specifies the level.

What to Do 1. Create an FC 20 block in the S7 program "FILL" according to the task.2. Call FC 20 in OB 1 as well.3. Download the FC 20, FC 105 blocks and the OB1.3. Test your program.

Date: 05.12.2005File: PRO1_14E.15

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Controlling the Level in a Tank

Leveltransmitter

Min. level 50 l.When the level falls belowthis, a message is to beoutput at output Q9.2(Q 5.2).

Max. level of 600 l,equals 10 V at analog channel 0

Page 302: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Analog Value ProcessingPage 16

Task Solve the problem shown above using the diagnostic interrupt OB82 and the diagnostics capability of the analog input module.

Note If you want to specifically evaluate which channel is in the overflow range, you have to use a system function here.

What to Do 1. Write a program for OB82 in the S7 program "FILL" according to the task.

2. Supplement the program in OB 1 to control the output Q 9.1 or Q 5.1.

3. Test your program.

Date: 05.12.2005File: PRO1_14E.16

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Diagnostic Interrupt from an Analog Module

Analog input module

When the value measured at an analog channel of the module exceeds the overflow range, OB82 is called, as wellas when it re-enters the range.

Rated range

OverrangeOverflow

Task:Output Q 9.1 (Q 5.1) is to flash as longas one of the encoded values is in the overflow range. .

Page 303: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Documenting, Saving, ArchivingPage 1

Contents Page

Overview of Documentation Facilities ………................................................................................... 2Block Documentation ....................................................................................................................... 3Print Preview ..................................................................................................................................... 4Page Setup ....................................................................................................................................... 5Other Documentation Facilities ….................................................................................................. 6Saving Programs ............................................................................................................................. 7Ascertaining the Size of a Project ..................................................................................................... 8Archiving on Diskette …................................................................................................................... 9Copying a Program onto a Memory Card ........................................................................................ 10Storing Data on the Hard Disk ........................................................................................................... 11Uploading a Program from the CPU to the PG ................................................................................. 12Exercise: Achiving a Project ............................................................................................................. 13

Date: 05.12.2005File: PRO1_15E.1

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Documenting, Saving, Archiving

Page 304: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Documenting, Saving, ArchivingPage 2

Overview The slide shows the different documentation facilities available. All the documentation tools have a print function.

Printer The printer used for documentation is the one installed under Windows. If you want to use a different printer, you must set it up with the Windows Control Panel.

DOCPRO The DOCPRO optional software is also available for superior documentation and for writing wiring manuals.

Date: 05.12.2005File: PRO1_15E.2

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Overview of Documentation Facilities

Network title

Network comment

Statement comment

Program overview

Cross references

Assignment of I/Q/M/T/C

Checklists

Symbol table

Configuration

Network configuration

Page 305: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Documenting, Saving, ArchivingPage 3

Block Comments The slide above shows the different comment facilities available for a program block (OB, FC, FB).

Printing To start the Print function:• Click the printer icon or • Select the menu options File --> Print.

Print Setup You can change the printer settings by selecting the menu options File --> Print Setup.

Date: 05.12.2005File: PRO1_15E.3

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Block Documentation

Page 306: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Documenting, Saving, ArchivingPage 4

Print Preview For a preview of what your printout will look like, select the menu options File -> Print Preview.

Note The appearance of LAD program printouts depends on the settings made with the menu options Options -> Customize. Example: The setting for the length of the address field affects the number of contacts that can appear side by side in the printout and the number of characters of the symbol name that fit on a line above the contacts.

Date: 05.12.2005File: PRO1_15E.4

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Print Preview

Page 307: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Documenting, Saving, ArchivingPage 5

Page Setup When you select the menu options File --> Page Setup a dialog box in which you can select the print format (e.g. A4 Margin) appears.

Headers/Footers In the SIMATIC Manager, you can set, for an entire project, the headers and footers for the documentation with all the tools.Select the menu options File -> Headers and Footers to display a dialog box for entering texts for the headers and footers. Fields for printing out the current date of the printout, the page number or the name of the object are provided in the headers and footers (e.g. {Date} {Time}, Page {Page},{Object}).

Date: 05.12.2005File: PRO1_15E.5

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Page Setup

Page 308: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Documenting, Saving, ArchivingPage 6

Reference Data If you print out the reference data it makes troubleshooting, in particular, easier. You will find more information in the chapter "Troubleshooting".

Symbol Table The symbol table contains the association between absolute address, symbol nameand symbol comment. See the chapter "Symbols" for more information.

Configuration Configuration data generated with the HW Config tool. The printout is in text form. If you want a graphic printout, you can copy the graphics into the clipboard and then insert it in another program e.g. Winword and print it out.

Network Displays in graphic form, the stations of a networked system with the relevantConfiguration configuration data such as the MPI address.

Date: 05.12.2005File: PRO1_15E.6

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Other Documentation Facilities

Reference data

Networkconfiguration

Configuration

Symbol table

Program structure

Cross references

Assignment ofI/Q/M/T/C

Checklists

Unused addresses

Addresses without symbols

Page 309: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Documenting, Saving, ArchivingPage 7

Note With certain CPUs (e.g. CPU 416), you can also describe the memory card in the CPU. To do so, use the menu options PLC -> Download to EPROM Memory Card on CPU.

Date: 05.12.2005File: PRO1_15E.7

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Copying Programs 1. Open two windows in the SIMATIC Manager:onto Memory Cards: One window containing the program to be saved and one

window with S7 Memory Card -> "Memory Card" icon2. Using the mouse, copy the program you want to save into the

"S7 Memory Card" window

Saving Programs

Archiving on 1. Select the menu options File -> Archive in the SIMATIC Diskette Manager

2. Choose the project you want to archive3. Enter the name of the archive file

Uploading Programs 1. Create a new program in the SIMATIC Managerfrom CPU to PG: 2. Click the "Online" icon

3. Open the S7 program and select Blocks4. Select the menu options PLC -> Upload in the SIMATIC

Manager OR1. Select the project in the SIMATIC Manager2. Select the menu options PLC -> Upload Station

Page 310: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Documenting, Saving, ArchivingPage 8

Introduction If a project needs more than 1.44 MB of memory, you can still save it on diskette by archiving (compressing) it first.

Explorer You can find out the size of a project in the Explorer:• Click the project folder with the right mouse button or• Select the project folder and then choose the menu options

File -> Properties.In both cases the "Properties" window opens.

Date: 05.12.2005File: PRO1_15E.8

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Ascertaining the Size of a Project

Page 311: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Documenting, Saving, ArchivingPage 9

Introduction Since the data in a project can take up a lot of memory space and would not fit onto a diskette, an archive function is provided.This compresses the data so that it only takes up approx. 1/8 of the original amount of memory. It uses the normal file compression utilities, such as PKZIP, ARJ, LHARC, RARor WINZIP. One of these programs must be installed on the PG. If you want to use long file names for the projects, you will require PKZIP, WinZip or RAR.The file compression utilities ARJ and PKZIP are supplied with STEP 7. You set the path for the archive program by selecting the menu options Options -> Customize -> Archive in the SIMATIC Manager.

Archiving • The project to be archived must be closed in the SIMATIC Manager.• Select the menu options File --> Archive.• Select the project to be archived in the dialog window.• Select the name for the archive in the next dialog box.• In the last dialog box, you can choose between the following options:

- Disk-crossing archive = Split the archive file onto severaldiskettes or not

- Incremental archiving = Only the files with the ACR attribute(STEP7 files) are archived.

- Reset archive bit = Only archive the files that have been changed since the project was last

archived.- Consistency check = Compare the files to be archived

(only for ARJ)

Retrieving • Select the menu options File -> Retrieve.• Select the archive file.• In the next dialog box, select the target directory for the extracted project.• Use the last dialog box to select options for overwriting and restoring the

storage path.

Date: 05.12.2005File: PRO1_15E.9

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Archiving on Diskette

Page 312: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Documenting, Saving, ArchivingPage 10

Requirements The memory card driver must be installed in the STEP 7 software. If not, click the "Start" button and select Simatic -> STEP 7 -> Memory Card Parameter Assignmentand install the driver. There will then be a Memory Card icon in the toolbar of the SIMATIC Manager.The memory card must be erased before you can copy your program onto it.Open two windows in the SIMATIC Manager:• One containing the user program you want to save• The other with the memory card

Copying Select the blocks you want or the "Blocks" object from the hard disk and drag them into the Memory Card window with the mouse.

Note With certain CPUs (e.g. CPU 416), you can also describe the memory card in the CPU. To do so, use the menu options PLC -> Download to EPROM Memory Card on CPU.

Date: 05.12.2005File: PRO1_15E.10

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Copying a Program onto a Memory Card

Page 313: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Documenting, Saving, ArchivingPage 11

SIMATIC Manager You can obtain an overview of the data of one or more projects with the SIMATIC Manager. The slide shows the project "Syh_32" with all its folders and objects.

Project A project contains all the data created for the project:• One or more user programs• The symbol table• The configuration and parameter assignments of the modules• The network configuration.

Date: 05.12.2005File: PRO1_15E.11

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Storing Data on the Hard Disk

Page 314: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Documenting, Saving, ArchivingPage 12

Uploading a When you have completed the startup phase, you should have a copy of theProgram from final version of the program on the hard disk of the PG. CPU to PG The best way of doing this is to save the program with all its comments and symbols on

the hard disk before starting it up on the PLC. When you make changes to the program, you should always save the modified blocks on the hard disk immediately so that you don't lose the comments and symbols.If the program is not on your PG, you can upload the blocks from the CPU. In this case, the comments and symbols will be missing. Don't forget to upload the system data blocks because they contain configuration and communication data.

What to Do To upload an entire program from the CPU to the PG, carry out the following steps:• Create a new S7 program in the SIMATIC Manager• Click the "ON" online icon in the toolbar• Open the S7 program and select the "Blocks" object (user program)• Select the menu options PLC --> Upload.

Note: The blocks are stored in the "Blocks" folder (user program) on the hard disk of the PG.

Uploading a Station You can also upload an entire station to the PG, i.e. a hardware station is also created in the project. The advantage of this is that you can change the parameters of the hardware immediately.What to do:• Create a new project in the SIMATIC Manager.• Select the menu options PLC -> Upload Station.

Date: 05.12.2005File: PRO1_15E.12

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Uploading a Program from the CPU to the PG

System data blocksSystem data blocks

Page 315: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Documenting, Saving, ArchivingPage 13

Task To archive your project because you have made additions to the program and want to take the project with you on diskette.

What to Do 1. Change to the SIMATIC Manager.2. Close all opened projects.3. Select the menu options File -> Archive -> Project4. Select the project "My Project" in the next dialog box.5. Enter the file name "My_project.zip" in the "Archive - Select Archive" dialog box and click the "Save" button.6. Confirm with "OK" in the "Archive - Options" window.

Date: 05.12.2005File: PRO1_15E.13

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Achiving a Project

Page 316: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Communication via MPIPage 1

Contents Page

Networking via MPI ……………….................................................................................................... 2Connection Options to MPI ............................................................................................................. 3Global Data: Overview ........................................................................................................................ 4GD Circles ………........................................................................................................................... 5Global Data: Configuration Procedure ............................................................................................. 6Global Data: Configuring the Hardware …………............................................................................. 7Editing the GD Table ........................................................................................................................ 8Compiling the GD Table .................................................................................................................. 9Downloading GD Configuration Data ................................................................................................ 10Status of GD Communication ............................................................................................................ 11Exercise: Preparing for Communication .......................................................................................... 12Exercise: Configuring Global Data Communication ........................................................................ 13Exercise: Monitoring Variables in Several Stations .......................................................................... 14Transferring Global Data with SFC 60, 61 ........................................................................................ 15Configuring with NETPRO .................................................................................................................. 16Subnets in SIMATIC …...................................................................................................................... 17S7 Communication Methods ............................................................................................................ 18

Date: 05.12.2005File: PRO1_16E.1

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Communication via MPI

PG 720

Page 317: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Communication via MPIPage 2

Introduction Every programming device has an MPI interface. The MPI interface of the CPU enables all intelligent modules in a PLC to be accessed, e.g. the function modules of a station.Each MPI node needs its own MPI address (between 0 and 126, the default settings are PG=0, OP/TD=1, and CPUs=2).In the S7-300, the MPI bus is looped through on the K bus on a one-to-one basis. This means that every node on the K bus (FMs and CPs) in the S7-300 rack is also an MPI node and needs to have its own MPI address.In the S7-400, communication frames are converted for the internal K bus (10.5 Mbps) via the MPI (187.5 Kbps). In an S7-400 rack, only the CPU has its own MPI address. The other intelligent modules, e.g. FMs and CPs, do not have a separate MPI number.

Connection The main advantage is that several devices can establish a communication linkFacilities with the CPU at the same time.

This means, for example, that a programming device, an HMI device and a link with another PLC can be in operation at the same time. The MPI interface also makes it possible to create a network in which a network administrator has central access with a PG to all the intelligent modules in the stations connected. The number of channels for connection to other communication partners that can be used at the same time depends on the type of CPU. For example, the CPU 314 has four connection resources and the CPU 416 has sixty-four.

Features Main features of the MPI interface:• RS 485 physics• Transmission rate 19.2 Kbps or 187.5 Kbps or 1.5 Mbps• Distances up to 50 m (between 2 neighboring nodes) and with 2 repeaters,

1100 m and 23.8 km with optical fiber and star coupler.• Profibus components (cables, connectors)

Date: 05.12.2005File: PRO1_16E.2

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Networking via MPI

PLC link via MPI

S7-300 or S7- 400

PG connection via MPI

OP connection via MPI

CPU 1 CPU 2

PG 720

S7-300 or S7- 400

01

2

n Default MPI address

Page 318: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Communication via MPIPage 3

Connectors Two types of connector are available for installing an MPI bus system.The connector with PG socket shown on the left is the standard connector used for linking MPI nodes with one another, while also enabling a PG to be connected at the same time.The connector without PG socket shown on the right is used where facilities for connecting a PG are not necessary.On the last bus node, the outgoing bus cable must be replaced by a terminating resistor.

Requirements To connect a programming device/PC to the MPI interface of the PLC, you need:• an MPI module in the PG/PC and a connecting cable• a PC adapter (a connecting cable with integral MPI converter, if there is no

free slot in the PG/PC ). The PC adapter has the following specifications:- Length 5 m- Transmission rate up to adapter 187.5 Kbps

Adapter to PG 19.2 or 38.4 Kbps (adjustable)

Date: 05.12.2005File: PRO1_16E.3

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Connection Options to MPI

Bus connectorBus connector

Connection forPG/HMI

Connection forPG/HMI

To MPIinterfaceofCPU

To MPIinterfaceofCPU

To MPIinterfaceofCPU

To MPIinterfaceofCPU

Switch for terminatingresistor

Switch for terminatingresistor

Page 319: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Communication via MPIPage 4

Global Network In SIMATIC S7, global data communication allows you to establishData communication between distributed PLCs without having to write a single extra line in

your user program.Communication using global data is not programmed but configured. The configuration for data exchange is stored in a table.Global data communication can take place between up to 15 CPUs within a project. It is designed for small quantities of data which are normally transmitted cyclically. The S7-400 CPUs also allow program-controlled and therefore also event-driven data transfer.

Configuring You configure data communication with the "Defining Global Data" tool.First of all, you open the Global Data Table and assign the columns of the table to the CPUs that are going to exchange data. In the lines of the table you then define the variables to be exchanged. Almost all CPU address areas (apart from external inputs and outputs and temporary data) can be used as variables, e.g. bit memories, inputs, outputs, timers, counters and areas in data blocks.

GD Packet Global data, i.e. variables with the same sender/receiver, can be collected in a GD packet and sent together. Each GD packet is identified by a GD packet number and the variables within a packet are identified by variable numbers.

GD Circle The CPUs participating in the exchange of GD packets make up a GD circle. Each GD circle is identified by a GD circle number.

Date: 05.12.2005File: PRO1_16E.4

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Global Data: Overview

Global Data

CPU 1MW 10

CPU 2MW 20

CPU 3MW 30

Page 320: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Communication via MPIPage 5

What is a GD Circle? A GD circle is a fixed distribution list for GD packets. Each CPU in a global data circle can send data to the other CPUs or receive data from another CPU.Types of GD circle:

Global data circle with more than 2 CPUs. One CPU is then the sender of a data packet and all the other CPUs in the GD circle are receivers.

Global data circle with 2 CPUs. Each CPU can both send a data packet to the other CPU and receive a data packet from the other CPU.

Number of Each CPU of an S7-300 can be in up to 4 different GD circles.GD Circles Up to 15 CPUs can exchange data via GD communication in one MPI network.

Example of The diagram above shows an example to illustrate the principle ofa GD Circle communication in GD circles.

Below is an example of the numbering of a GD circle.

Date: 05.12.2005File: PRO1_16E.5

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

2

GD CirclesCPU1 CPU2 CPU3 CPU4 CPU5

GD circle

1

3

4

5

6

S=Sender; R=Receiver; GD x.y=GD Packet y in global data circle x

S GD 1.1R GD 1.2

R GD 1.1S GD 1.2

R GD 2.1 S GD 2.1 R GD 2.1 R GD 2.1 R GD 2.1

S GD 3.1R GD 3.2

R GD 3.1S GD 3.2

R GD 4.1 S GD 4.1 R GD 4.1

S GD 5.1 R GD 5.1 R GD 5.1

R GD 6.1 S GD 6.1 R GD 6.1

Page 321: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Communication via MPIPage 6

Creating Hardware First of all you must create the stations that you want to network in a projectStations using the SIMATIC Manager. When you have done this, open the HW Config tool and

open the stations one after the other.

Setting the MPI When configuring the hardware, you must explicitly define the CPUs to beAddress networked via MPI as "Networked" and assign each of them their own MPI node

address. Save your CPU parameters on the hard disk and then download the configuration data to each CPU separately (point-to-point) ("PLC -> Download").

Networking You then link up the MPI nodes with Profibus cables. When you have done this, it should be possible to establish an online connection to all the CPUs. You can test this with the SIMATIC Manager "Accessible Nodes" function.

Creating the You use the "Defining Global Data" tool to create a global data table in whichGD Table you define the data to be exchanged. You then compile the table twice and download

the relevant configuration data to the CPUs.

Volume of Data S7-300 : One CPU can be in up to 4 GD circles.A CPU can send 1 packet and receive 1 packet maximum per GD

circle.A maximum of 22 data bytes can be transferred with one packet.

S7-400 : One CPU can be in up to 16 GD circles.A CPU can send 1 packet and receive 2 packets maximum per GD

circle.A maximum of 54 data bytes can be transferred with one packet.

Date: 05.12.2005File: PRO1_16E.6

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Global Data: Configuration Procedure

Create hardware stations in a projectwith the "SIMATIC Manager"

Create and download configuration data (MPI address) for the individual CPUs

with the "HW Config" tool

Configure Global Data table with the "Defining Global Data" tool

Create hardware stations in a projectwith the "SIMATIC Manager"

Create and download configuration data (MPI address) for the individual CPUs

with the "HW Config" tool

Configure Global Data table with the "Defining Global Data" tool

Page 322: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Communication via MPIPage 7

What to Do To configure the hardware for global data communication you must carry out the following steps:1. A STEP 7 project must already have been created with the SIMATIC

Manager.2. An MPI network object must be created in this project and assigned

parameters. An MPI network object is automatically created when you create a new S7 project.

3. Configure at least two GD-capable modules in the project (e.g. S7 CPUs).When configuring the CPUs with the "HW Config" tool, explicitly define each CPU as "Networked" (see above) and assign it its own MPI address.

4. Download the configuration data you have entered to each CPU separately. 5. Physically link up the CPU modules with network cables.6. Use the SIMATIC Manager "Accessible Nodes" function to check that you

have networked the stations correctly

MPI Address from PG If several PGs are to be connected to the MPI network, then each PG must be given its own MPI address. Use the "Simatic -> STEP 7 -> Setting the PG/PC Interface" program to set the address.

Date: 05.12.2005File: PRO1_16E.7

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Global Data: Configuring the Hardware

Set MPI address

Network CPUs "Accessible Nodes"

Create stations

Page 323: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Communication via MPIPage 8

Overview The GD table is where you enter the CPUs that are going to exchange data and the address areas of the data to be exchanged.You can also specify the scan rate and a doubleword for the status information.

Opening the Open the GD table as follows:GD Table 1. Open your project and select the MPI network object.

2. Select the menu options Options -> Define Global Data. A new GD table is then generated or an existing GD table is opened.

Filling in the You must enter the address areas to be used in a separate column forGD Table each CPU taking part in GD communication. You do this as follows:

1. First assign each column of the table to a CPU by clicking the column header with the mouse to select it and choosing the menu optionsEdit -> Assign CPU.

2. Select the CPU you want in the dialog box that appears and confirm with "OK".

3. Enter the global data to be transferred in the lines beneath. You can select Edit mode for the individual cells of the table with the F2 key.You can enter a replication factor for the variables to specify transfer of a whole section of data. In the example above: 20 bytes starting from DBB0 of DB100 (Station_3).

4. Define a sender in each line of the GD table by selecting the relevant cell and clicking the icon for "Select as Sender" in the toolbar.

.

Date: 05.12.2005File: PRO1_16E.8

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Editing the GD Table

Define Global Data

Open GD Table

Select CPUs

Replication factorReplication factor

Page 324: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Communication via MPIPage 9

Compiling the You can now compile configuration data from the information you have enteredGD Table in the GD table. The configuration data is generated in two phases:

• Start the first compilation by selecting the menu options GD Table ->Compile. The first time you compile the GD table the individual variables areput into packets and the relevant GD circles are created.The relevant GD circle number, packet number and variable number are displayed in the first column:GD 1.1.1 1st variable in the 1st packet of the 1st GD circleGD 1.2.1 1st variable in the 2nd packet of the 1st GD circle:GD m.3.n nth variable in the 3rd packet of the mth GD circle

• After the first compilation, i.e. when the GD circles and packets have been created, you can define different scan rates or variables for storing status information for the individual packets.

• You must then start the compiler again to include the information about the scan rates and storage of the status information in the configuration data.

Scan Rates You can use the menu options View -> Scan Rates to select a different value (from 1 to 255 for the sender and 1 to 255 for the receiver, 0 for purely event-driven send and receive communication on the S7-400).

Status If you want to be notified whether the data has been transferred with or without errors, you can specify a doubleword for the status information for each data packet by selecting the menu options View -> GD Status. The operating system of the CPU will then enter checkback information in this doubleword.

Date: 05.12.2005File: PRO1_16E.9

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Compiling the GD Table

Compile GD Table

Define scan rates andstatus information

Page 325: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Communication via MPIPage 10

Downloading When you have compiled the configuration data for the second time, you canthe GD Table download it to the CPUs as follows :

1. Switch all the CPUs involved to STOP mode.2. Select the menu options PLC -> Download to transfer the data.3. When you have successfully downloaded the configuration data, switch the

CPUs involved back to RUN mode. Cyclic exchange of global data starts automatically.

GD Exchange Global data is exchanged as follows:• The sending CPU sends the global data at the end of a cycle.• The receiving CPU transfers the data from the communication part of a CPU

to the S7 address area at the beginning of a cycle.You can specify a scan rate to set the number of scan cycles to elapse before the data is sent or received.

Scan cycle checkpoint

Receive GD

PII

OB1 Cyclic program execution

PIQ

Send GD

Date: 05.12.2005File: PRO1_16E.10

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Downloading GD Configuration Data

Download GD configuration data

Page 326: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Communication via MPIPage 11

Status Indication You can specify a status doubleword for each GD packet for each CPU "involved". Status doublewords have the identifier "GDS" in the table.

Status Doubleword If you assign the status doubleword (GDS) to a CPU address (e.g. MD 120), youEvaluation can evaluate the status in the user program or on the PG.

Structure of the The GD status doubleword is bit-oriented. The diagram shows the meanings ofStatus Doubleword the bits if they are set. A bit remains set until it is reset by the user program or by a PG

input.Bits which are not labeled are not used and have no meaning at present.The GD status information requires a doubleword in memory. To make this easier to understand, MD 120 is used in the illustration.

Group Status STEP 7 provides group status information (GST) for all GD packets.This group status information, which is also stored in a doubleword with the same structure as the status doubleword (GDS), is the result obtained by OR-ing all the status words.

Date: 05.12.2005File: PRO1_16E.11

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Range length errorin sender

Status of GD Communication

MB 120

7 6 5 4 5 4 3 2 1 0

MB 121

MD 120

7 6 5 4 3 2 1 0

MB 122

6 5 4 3 2 1

MB 123

7 0

DB does not existin sender

GD packet lostSyntax error in GD packet

GD object missing in GD packet

GD objects in sender and receiverare not the same length

Range length error in receiver

DB does not exist in receiver

Sender has performed a restartReceiver has received new data

0

Page 327: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Communication via MPIPage 12

Date: 05.12.2005File: PRO1_16E.12

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Preparing for Communication

Training Area 2

PG 740

SIEMENS Node No.:.......Station 2

CPU-MPI address: .............

PG 740

SIEMENS Node No.:.......Station 1

CPU-MPI address: .............

Training Area 1

Step 1 Together with your counter-part group define an MPI communication setup.Each group creates a new project "GD Communication" with two hardware stations each (e.g. PLC1 and PLC2) for this purpose.

Step 2 In the above configuration diagram, enter the necessary information and assign in each case the relevant addresses to the PGs (program PG-interface parameter assignment)and the PLCs (CPU parameter, MPI address). Assign parameters to the CPUs of both stations.

Download the configuration to both CPUs using the menu options PLC -> Download.The modules may not yet be physically networked at this time!

Step 3 Connect your system with the Profibus cable.Step 4 Test if both PGs on both PLCs can go online.Step 5 Now configure on one of the two PGs the communication using global data exchange

(see next page).

Page 328: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Communication via MPIPage 13

Task The number, that is set on the pushwheel button of station "PLC1", is to be displayed on the digital display of station "PLC 2" and vice versa.

What to Do • Create a new project "GD Communiation".• Insert two S7-300 stations "PLC1" and "PLC2".• Assign parameters to the stations for networking via MPI.• Create the GD table according to the task and download it.• Test the communication.

Date: 05.12.2005File: PRO1_16E.13

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Configuring Global Data Communication

Station PLC1Station PLC1 Station PLC2Station PLC2

0 8 1 50 8 1 5

4 7 1 1 4 7 1 1

Page 329: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Communication via MPIPage 14

Date: 05.12.2005File: PRO1_16E.14

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Monitoring Variables in Several Stations

Task You are to monitor addresses from both CPUs at the same time using Monitor Variable.

What to Do • Create two variable tables as shown in the slide above.Note: Different addesses result for the training units with 32 channel modules.

• For VAT1, establish an online connection to station "PLC1" and for VAT2 an online connection to station "PLC2".

• Select the menu options Window -> Arrange -> Horizontal.• Switch on the test function and monitor the variables.• Change the value on the pushwheel button of station 2 and check if the value is transferred to station 1.

Page 330: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Communication via MPIPage 15

Introduction You can send and receive global data packets in a program-controlled and therefore event-driven way with SFC60 GD_SND and SFC61 GD_RCV.The scan rate 0 must be specified in the GD table for the purely program-controlled data exchange. You can also use the cyclic-driven and program-controlled modes either separately or combined.

SFC60 "GD_SND" SFC60 collects the data of a GD packet and sends it on its configured way. SFC60 canbe called anywhere in the user program.SFC60 has the CIRCLE_ID (circle no. in which the send packet is found) andBLOCK_ID (packet no. of the packet to be sent) parameters.

SFC61 "GD_RCV" SFC61 fetches the data for exactly one sent GD packet and enters it in the configured area. SFC61 can be called anywhere in the user program.Analog to SFC60, SFC61 has the CIRCLE_ID dnd BLOCK_ID parameters. To guarantee data consistency, all interrupts must be disabled in the user program prior to the SFC60/ 61 calls.For example:

:CALL SFC 39 // "Disable interrupt"CALL SFC 41 // "Delay interrupt"CALL SFC 60/61 // "Send/receive GD"CALL SFC 42 // "Enable delay" CALL SFC 40 // "Enable interrupts" .:

Date: 05.12.2005File: PRO1_16E.15

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Transferring Global Data with SFC 60, 61

Page 331: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Communication via MPIPage 16

Introduction Instead of the configuration method you have been using up to now, you can use the "NETPRO" tool to configure a network (MPI, Profibus or Industrial Ethernet) graphically. This tool makes things clearer, provides you with documentation, and its tools, e.g. hardware configuration, are easy to invoke.

Opening the Tool You open the tool by double-clicking a network icon, e.g. MPI, in the SIMATIC Manager.

Inserting Hardware The catalog contains the components you need, such as subnets and stations,Stations and you can insert them by drag and drop.

Configuring When you have inserted the stations, you double-click to open the "HardwareHardware Configuration" tool. You use this to set the MPI addresses and establish a connection to

the subnet.

Global Data Click the subnet, e.g. MPI, with the right mouse button and select the menu option "Define Global Data". You create the global data table as before.

Date: 05.12.2005File: PRO1_16E.16

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Configuring with NETPRO

Insert hardware stations

Define global data

Page 332: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Communication via MPIPage 17

Overview To meet the different communication requirements at cell level (non-time-critical) and field level (time-critical) SIEMENS offers the following subnets.

MPI The MPI subnet is designed for use at cell level. MPI is the multipoint interface in SIMATIC S7, M7 and C7. The MPI is basically a PG interface, i.e. it is designed for the connection of PGs (for startup and testing) and OPs (human-machine interface). The MPI subnet can, however, also be used for networking a small number of CPUs.

Industrial Ethernet Industrial Ethernet is the network for the plant management and cell levels in the SIMATIC open, manufacturer-independent communication system.Industrial Ethernet is designed for non-time-critical transmission of large quantities of data and provides via Gateways facilities for connection to remote networks.

PROFIBUS PROFIBUS is the network for the cell and field levels in the SIMATIC open, manufacturer-independent communication system. There are two versions:• PROFIBUS is for non-time-critical communication between equal, intelligent

nodes at cell level. • PROFIBUS DP is the fieldbus for time-critical, cyclic data exchange

between intelligent masters and field devices.Point-to-Point Point-to-point connections are primarily used for non-time-critical dataConnection exchange between two stations or for connecting devices such as OPs, printers, bar

code scanners, magnetic stripe ID card readers, etc. to a station.

AS Interface The Actuator-Sensor-Interface is a subnet for the lowest process level in an automation system. It enables binary sensors and actuators to be networked.

Date: 05.12.2005File: PRO1_16E.17

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Subnets in SIMATIC

-SINUMERIK, RCM-TI 505-Other PLCS7-300S7-400 M7-400

OPs

SIMATIC S5

PROFIBUS-DP

ET 200B/LET 200C

DP/AS-I link

ASI (Actuator Sensor Interface)

AS-Isubmodules

Sensors and ActuatorsField device with AS-I ASIC

AS-I power supply

Industrial Ethernet

PROFIBUS

MPI network

Point-to-Point

PCs, OS PGsPG 720

Cell level

Field level

AS-Ilevel

Page 333: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Communication via MPIPage 18

Global Data This communication method enables data to be exchanged between CPUs cyclically via the MPI interface without programming. Data is exchanged at the scan cycle checkpoint when the process image is updated. On the S7-400 data exchange can also be initiated using SFCs.Global data can be inputs, outputs, bit memories, timers, counters and data block areas.Data communication is not programmed, but configured by means of a global data table. None of the connections on the CPU need to be used for global data communication.

Basic This communication method can be used with all S7-300/400 CPUs forCommunication transmitting data via the MPI subnet or within a station on its K bus.

System functions (SFCs), e.g. X_SEND at the Send end and X_RCV at the Receive end, are called in the user program. The maximum amount of user data is 76 bytes.When the system function is called, a connection to the communication partner is established and cleared dynamically. One free connection is required on the CPU.

Extended You can use this communication method with all S7-400 CPUs. Up toCommunication 64KBytes of data can be transmitted via any subnet (MPI, Profibus, Industrial

Ethernet). This is done with system functions (SFBs), which also allow communication with acknowledgement. Data can also be read from or written to an S7-300 (PUT/GET blocks).You can not only transfer data, but also perform control functions, like Stop or Start, on the communication partner. Configured connections (connection table) are required for communication by this method. These connections are established on a complete restart of the station and usually remain in force. Free connections on the CPU are necessary for this.

Date: 05.12.2005File: PRO1_16E.18

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Event-drivenvia

MPI, Profibus or Industrial Ethernet

Event-drivenvia

MPI or K-Bus

S7 Communication Methods

Global DataGlobal Data

Basic communication( non-configured connection )

Basic communication( non-configured connection ) Extended communication

(configured connection )Extended communication(configured connection )

SFCSFC SFCSFC SFBSFB SFBSFB

Op. Sys.of CPU

Op. Sys.of CPU Op. Sys.

of CPUOp. Sys.of CPU

cyclic or event-driven

via MPI

Page 334: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 1

Contents Page

Exercises for the Chapter "The SIMATIC Manager" ........................................................................ 2-5Exercises for the Chapter "Editing Blocks" ...................................................................................... 6-13Exercises for the Chapter "Binary Operations" ............................................................................... 14-15Exercises for the Chapter "Digital Operations" ................................................................................. 16-19Exercises for the Chapter "Symbols" ............................................................................................... 20Exercises for the Chapter "Test Functions“ ..................................................................................... 21-25Exercises for the Chapter "Data Storage in Data Blocks" ............................................................... 26-27Exercises for the Chapter "Functions and Function Blocks" ........................................................... 28-33Exercises for the Chapter "Troubleshooting" ................................................................................... 34-40Exercises for the Chapter "HW-Configuration and Memory Concept" ............................................ 41-42Exercises for the Chapter “Organization Blocks" ............................................................................ 43-46Exercises for the Chapter "Analog Value Processing" ..................................................................... 47-50Exercises for the Chapter "Dokumenting, Saving, Archiving" ......................................................... 51Exercises for the Chapter “Communication via MPI" ....................................................................... 52-54

Date: 05.12.2005File: PRO1_17E.1

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Solutions (Version A)

Page 335: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 2

Date: 05.12.2005File: PRO1_17E.2

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Creating a Project

Note The result of the exercise is displayed in the picture above.

Page 336: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 3

Date: 05.12.2005File: PRO1_17E.3

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Inserting an S7-Program

Note The result of the exercise is displayed in the picture above.

Page 337: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 4

Date: 05.12.2005File: PRO1_17E.4

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Inserting an S7-Block

Note The result of the exercise is displayed in the picture above.

Page 338: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 5

Date: 05.12.2005File: PRO1_17E.5

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: CPU Memory Reset

Note The result of the exercise is displayed in the picture above.

Page 339: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 6

Note The result of the exercise is displayed in the picture above.

Date: 05.12.2005File: PRO1_17E.6

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Selecting the Mnemonics

Page 340: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 7

Note The result of the exercise is displayed in the picture above (for the 16-channel training unit).

Date: 05.12.2005File: PRO1_17E.7

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Opening and Editing FC 1

Page 341: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 8

Note The result of the exercise is displayed in the picture above (for the 16-channel training unit).

Date: 05.12.2005File: PRO1_17E.8

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Changing the Programming Language

Page 342: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 9

Date: 05.12.2005File: PRO1_17E.9

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Saving FC 1

Page 343: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 10

Date: 05.12.2005File: PRO1_17E.10

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Downloading a Block into the PLC

Page 344: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 11

Date: 05.12.2005File: PRO1_17E.11

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Calling FC 1 in OB 1

Note The result of the exercise is displayed in the picture above.

Page 345: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 12

Date: 05.12.2005File: PRO1_17E.12

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Testing FC 1 (in LAD)

Page 346: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 13

Date: 05.12.2005File: PRO1_17E.13

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Expanding the Program in the FC 1 Block

Page 347: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 14

Exercise Complete the programs above to obtain the following functionality: When switch S1 is activated and switch S2 is not activated, the light should be ON in all three cases.

Note ! The terms "NO contact" and "NC contact" have different meanings depending on whether they are used in the process hardware context or as symbols in the software.

Date: 05.12.2005File: PRO1_17E.14

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Normally Open and Normally Closed ContactsTask: In all three examples the light should be on when S1 is activated and S2 is not activated!

I 1.0 I 1.1 Q 4.0 I 1.0 I 1.1 Q 4.0

A I 1.0AN I 1.1= Q 4.0

Q 4.0

I 1.0

I 1.1

&

Q 4.0

I 1.0

I 1.1

&

Q 4.0

I 1.0

I 1.1

&

A I1.0A I1.1= Q 4.0

AN I 1.0A I 1.1= Q 4.0

Software

I1.0

S1

I1.1

S2

I1.0

S1

I1.1

S2

I1.0

S1

I1.1

S2

Q 4.0Programmable controller

LightLight Light

Q 4.0Programmable controller

Q 4.0Programmable controller

FDB

STL

LAD

Hardware

I 1.0 I 1.1 Q 4.0

I 1.0 I 1.1 I 1.0 I 1.1 I 1.0 I 1.1

Page 348: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 15

FC15: Exercise: Program for a Bottling Plant (Mode Section)Network 1: Plant On/Off

Network 2: Manual Mode

SRS

R Q

Q 8.1

I 0.0

I 0.1

SRS

R Q

& Q 8.2

>=1&

Q 8.1

I 0.4

I 0.5

Q 8.1I 0.4

I 0.5

Network 3: Automatic Mode

SRS

R Q

& Q 8.3

>=1&

Q 8.1

I 0.4

I 0.5

Q 8.1I 0.4

I 0.5

Network 4: Conveyor forward (Jog mode)

&Q 8.2

I 0.2

I 0.3=

Q 20.5

Network 5: Conveyor backward (Jog mode)

&Q 8.2

I 0.3

I 0.2=

Q 20.6

Exercise: Program for a Bottling Plant (Mode Section)

Page 349: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 16

Date: 05.12.2005File: PRO1_17E.16

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Timers

T4S_PEXT

STVR

BIBCD

Q

I 0.7S5T#5s

I 0.5 Q 8.0

I 0.7

I 0.5

Q8.0

T4S_PULSE

STVR

BIBCD

Q

I 0.7S5T#5s

I 0.5 Q 8.0

I 0.7

I 0.5

Q8.05s

T4S_ODT

STVR

BIBCD

Q

I 0.7S5T#5s

I 0.5 Q 8.0

I 0.7

I 0.5

Q8.0

T4S_ODTS

STVR

BIBCD

Q

I 0.7S5T#5s

I 0.5 Q 8.0

I 0.7

I 0.5

Q8.0

I 0.7

I 0.5

Q8.0

T4S_OFFDT

STVR

BIBCD

Q

I 0.7S5T#5s

I 0.5 Q 8.0

Note The result of the exercise is displayed in the picture above.

Page 350: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 17

Exercise: Program for a Bottling Plant(Filling Cycle and Bottle Count)

FC16: Exercise: Program for a Bottling Plant (Filling Cycle)Network 1: Filling time for filling bottles

Network 2: Auxiliary memory marker for conveyor operation in automatic mode

Network 3: Count empty bottles

T1

S_PEXT

TV

Q

BI

R

I 16.6

S5T#3s BCD

=

Q 9.0

S

S_CU

PV

Q

BI

R

CV_BCD

S

C 1

C#0

I 16.5 CU

Q 8.1

Network 4: Count full bottles

S_CU

PV

Q

BI

R

CV_BCD

S

C 2

C#0

I 16.7 CU

Q 8.1

QW12

Modified Network 4 for Block FC 15: Conveyor operation forward

&Q 8.2

I 0.2

I 0.3=

Q 20.5>=1

M 50.1

T 1

&Q 8.3=

M 50.1

Page 351: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 18

Exercise: Program for a Bottling Plant (Production Data)

FC18: Exercise: Program for a Bottling Plant (Production Data)Network 1: Delete memory words if Plant On

Network 2: Count empty bottles

Q8.1MOVE

IN

OUT

ENO

ENP

M 4.1

MD100

I16.5ADD_I

IN2 ENO

OUT

ENP

M 8.5

MW100IN1MW100

1

Network 3: Count full bottles

I16.7ADD_I

IN2 ENO

OUT

ENP

M 8.7

MW102IN1MW102

1

Network 4: Calculate number of broken bottles

SUB_I

IN2 ENO

OUT

EN

MW104IN1MW100

MW102

Network 5: Display number of full bottles

I_BCD

IN

OUT

ENO

EN QW12

MW102

0

Page 352: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 19

Date: 05.12.2005File: PRO1_17E.19

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise : Program for a Bottling Plant(Number of Packaging Units)

Page 353: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 20

Date: 05.12.2005File: PRO1_17E.20

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Creating a Symbol Table for FC 15

Page 354: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 21

Date: 05.12.2005File: PRO1_17E.21

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Monitoring and Modifying Variables

Page 355: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 22

Date: 05.12.2005File: PRO1_17E.22

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Modifying Variables in the Stop Mode

Page 356: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 23

Date: 05.12.2005File: PRO1_17E.23

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Using Trigger Points for the Modify Variables Function

(Q 4.6)

Additional network in OB 1 of the S7 program "My Program"

Page 357: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 24

Date: 05.12.2005File: PRO1_17E.24

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Forcing

Page 358: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 25

Date: 05.12.2005File: PRO1_17E.25

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Combining Program Status and Monitor Variable

Page 359: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 26

Date: 05.12.2005File: PRO1_17E.26

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Program for a Bottling Plant - Data Storage (1)

Page 360: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 27

Date: 05.12.2005File: PRO1_17E.27

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Program for a Bottling Plant - Data Storage (2)

Page 361: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 28

Date: 05.12.2005File: PRO1_17E.28

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Using Local Variables

Page 362: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 29

Date: 05.12.2005File: PRO1_17E.29

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Editing a Parameter-assignable FC

Page 363: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 30

Date: 05.12.2005File: PRO1_17E.30

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Calling a Parameter-assignable FC

Page 364: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 31

Date: 05.12.2005File: PRO1_17E.31

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Editing a Function Block

Page 365: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 32

Date: 05.12.2005File: PRO1_17E.32

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Calling a Function Block and Testing It

Page 366: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 33

Date: 05.12.2005File: PRO1_17E.33

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Recognizing Types of Variables

Absolute SymbolicXXXXX

XX

Temporary Static ParameterXX

XX

X

L #Number_1

T #Max_value

T MW 40

Statement

L #Number_2

L #Intermediate_resultL “Number_1"

T #Number_2

Global

XX

LocalXXXX

X

Question What is not correct in the statement T#Number_2 ?

Number_2 is defined as an input parameter and thus read-only accesses are possible

Page 367: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 34

Date: 05.12.2005File: PRO1_17E.34

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Finding Stop Errors and Eliminating Them

Incorrect -> Correct InstructionLocationError

CALL FC 30 -> CALL FC 23OB 1, Network 51

T DB4.DBW 2 -> T DB5.DBW 2FC 23, Network 22

T DB5.DBW 40 -> T DB5.DBW 4FC 23, Network 33

L PIW 362 -> L PIW 352 ( L PIW 304 )FC 20, Network 14

Page 368: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 35

Date: 05.12.2005File: PRO1_17E.35

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Troubleshooting with I Stack, B Stack

Error 1Questions Error 2 Error 3

FC 100, NW 2BTI

In which block and at whichinstruction did the erroroccur?

FC 101, NW 2OPN DB[MW 30] FC 102, NW 2

BCD conversion errorWhat is the cause of the error? Incorrect block numberat OPN DB

I/O accesserror, writing

OB 1, FC 100Which blocks were executedup to the error? OB 1, FC 101 OB 1, FC 102

Accu 1: 8A

Accu 2: 5

Which values were in the accumulators at the errorlocation?

Accu 1: 80

Accu 2: 5

Accu 1: 4868

Accu 2: CAFE

No valid BCD numberin Accu 1Why did the error occur? Incorrect DB number

in MW 30Incorrect I/Oaddress

DB 104Which data blocks wereopen? --- ---

Page 369: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 36

Date: 05.12.2005File: PRO1_17E.36

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Eliminating Logical Program Errors

Incorrect -> Correct InstructionLocationError

A Q 8.1 -> A Q 8.0FC 15, Network 21

= Q 20.5 -> = Q 20.6FC 15, Network 52

A I 16.1 -> A I 16.6FC 16, Network 13

„>R“ -> „<R“FC 20, Network 24

L 0 -> L 6FC 19, Network 15

Page 370: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 37

Date: 05.12.2005File: PRO1_17E.37

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Enabling Diagnostic Messages

Page 371: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 38

Date: 05.12.2005File: PRO1_17E.38

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Outputting User Messages

Page 372: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 39

Date: 05.12.2005File: PRO1_17E.39

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Enabling Diagnostic Interrupts and Simulating HardwareFaults

Page 373: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 40

Date: 05.12.2005File: PRO1_17E.40

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Reading Out System Information

Page 374: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 41

Note The result of the exercise is displayed in the picture above (for the S7-300 16-channel training unit).

Date: 05.12.2005File: PRO1_17E.41

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Reading Out and Adapting the Actual Configuration

Page 375: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 42

Note The result of the exercise is displayed in the picture above.

Date: 05.12.2005File: PRO1_17E.42

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Assign Parameters to Clock Memory and Test It

Page 376: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 43

Date: 05.12.2005File: PRO1_17E.43

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Determing type of Startup in OB 100

Page 377: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 44

Date: 05.12.2005File: PRO1_17E.44

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Setting the System Time

Page 378: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 45

Date: 05.12.2005File: PRO1_17E.45

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Creating a Flashing Light with Cyclic Interrupt

Page 379: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 46

Date: 05.12.2005File: PRO1_17E.46

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Writing a Program for a Time-of-Day Interrupt

Page 380: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 47

Date: 05.12.2005File: PRO1_17E.47

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Assigning Parameters to the Analog Module SM335

Page 381: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 48

Date: 05.12.2005File: PRO1_17E.48

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Assigning Parameters to the Analog Module SM331

Page 382: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 49

Date: 05.12.2005File: PRO1_17E.49

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Controlling the Level in a Tank

Page 383: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 50

Date: 05.12.2005File: PRO1_17E.50

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Diagnostic Interrupt from an Analog Module

Page 384: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 51

Date: 05.12.2005File: PRO1_17E.51

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Achiving a Project

Page 385: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 52

Date: 05.12.2005File: PRO1_17E.52

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Preparing for Communication

Training Area 2

PG 740

SIEMENS Node No.:.......Station 2

CPU-MPI address: 3

PG 740

SIEMENS Node No.:.......Station 1

CPU-MPI address: 2

Training Area 1

Page 386: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 53

Date: 05.12.2005File: PRO1_17E.53

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Configuring Global Data Communication

Page 387: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Solutions (Version A)Page 54

Date: 05.12.2005File: PRO1_17E.54

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Exercise: Monitoring Variables in Several Stations

Page 388: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Appendix: Special Features of S7-400Page 1

Contents Page

Main Differences to the S7-300 ................................................................................................. 2Technical Specifications of the S7-300 CPUs (1) ............................................................................ 3Technical Specifications of the S7-300 CPUs (2) ............................................................................ 4

Technical Specifications of the S7-400 CPUs (1) ............................................................................ 5Technical Specifications of the S7-400 CPUs (2) ............................................................................ 6

Components of the S7- 400 .............................................................................................................. 7Racks of the S7-400 ………………................................................................................................... 8Module Parameters: Logical Addresses .......................................................................................... 9CPU Parameters: Startup ................................................................................................................. 10CPU Parameters: Interrupts ............................................................................................................. 11CPU Parameters: Local Data ........................................................................................................... 12Configuring Multicomputing Operation ............................................................................................. 13SFC 35 for Synchronization in Multicomputing Operation ............................................................... 14Remove and Insert Interrupt ............................................................................................................. 15

Date: 05.12.2005File: PRO1_18E.1

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Appendix: Technical Specifications andSpecial Features of the S7-400

Page 389: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Appendix: Special Features of S7-400Page 2

Introduction In order to be able to rate the technical specifications of the S7-400, you can first of all see the specifications of the S7-300. They are current as of 5.99. For the most current technical specifications, please refer to the ST 70 catalog.

Date: 05.12.2005File: PRO1_18E.2

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Technical Specifications of the S7-300 CPUs (1)CPU

Execution time perBinary instructionLoad/Transfer (Word)16 bit integer (+/-)IEEE flaoting pnt (+/-)

User memoryWork memoryLoad memory integr. Load memory extern

AddressesBit memoriesClock memoriesTimersCounters

Block Types/NumberFBsFCsDB's

Size of process image(inputs/outputs)

max. I/O address area

Integral interfaces

314 IFM

300 ns800 ns1500 ns<50 µs

32 KB48 KB-

2048812864

128128127

124 Byte each

752 Byte each

MPI

315-2 DP

300 ns900 ns1500 ns<35 µs

64 KB96 KB4 MB

2048812864

192192254

128 Byte each

1024 Byte each

MPI, DP

315

300 ns900 ns1500 ns<35 µs

48 KB80 KB4 MB

2048812864

192192254

128 Byte each

768 Byte each

MPI

312 IFM

700 ns2400 ns2400 ns<60 µs

6 KB20 KB-

102486432

3232127

32 Byte each

32 Byte each

MPI

314

300 ns800 nsc1500 ns<50 µs

24 KB40 KB4 MB

2048812864

128128127

128 Byte each

768 Byte each

MPI

313

700 ns2400 ns2400 ns<60 µs

12 KB20 KB4 MB

2048812864

128128127

128 Byte each

32 Byte each

MPI

316-2 DP

300 ns900 ns1500 ns<35 µs

128 KB192 KB4 MB

2048812864

256512511

128 Byte each

1024 Byte each

MPI, DP

318-2 DP

100 ns100 ns100 ns0,6 µs

512 KB64 KB4 MB

81928512512

102410242047

256 Byte each

8192 Byte each

MPI/DP, DP

Page 390: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Appendix: Special Features of S7-400Page 3

Date: 05.12.2005File: PRO1_18E.3

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

313

OB-No.110203540-10080-82, 85, 87121,122

1536 Byte

8 KB8

4

4

1

1

22 bytes

CPU

Organization blocksFree cycleTime-of-day interruptsTime-delay interruptsCyclic interruptsHardware interruptsBackground executionStartupErrors, asynchronous

Errors, synchronous

Local data

max. Block lengthBlock nesting depth

per execution level

Program-controlledcommunication: max. Number of connections

Global Data communication via MPI:GD circles per CPU

Send GD packets perGD circle

Receive GD packets perGD circle

max. user data size of a packet

Technical Specifications of the S7-300 CPUs (2)314 IFM

OB-No.110203540-10080-82, 85, 87121,122

1536 Byte

8 KB8

4

4

1

1

22 bytes

315-2 DP

OB-No.110203540-10080-87

121,122

1536 Byte

16 KB8

4

4

1

1

22 bytes

315

OB-No.110203540-10080-82, 85,87121,122

1536 Byte

16 KB8

4

4

1

1

22 bytes

312 IFM

OB-No.1---40-100-

-

512 Byte

8 KB8

4

4

1

1

22 bytes

316-2 DP

OB-No.110203540-10080-87

121,122

1536 Byte

16 KB8

4

4

1

1

22 bytes

318-2 DP

OB-No.110,1120,2132,3540,4190100,10280-87

121,122

4096 Byte

64 KB16

32

8

1

2

54 bytes

314

OB-No.110203540-10080-82, 85, 87121,122

1536 Byte

8 KB8

4

4

1

1

22 bytes

Page 391: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Appendix: Special Features of S7-400Page 4

CPU Types CPUs are available with the appropriate execution times, sufficient work memory capacity and a suitable number of blocks for every performance range.

Process I/O The logical addresses of the I/O modules are all in a linear address area of appropriate size. The addresses of the slave stations connected to the integral DP interface are also mapped in this linear address area. This enables distributed I/Os to be accessed in the same way as central I/Os in the user program.The address parameters for both central and distributed I/Os are assigned with STEP 7.

Date: 05.12.2005File: PRO1_18E.4

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Technical Specifications of the S7-400 CPUs (1)

*) 1 byte = 8 digital inputs/outputs

2 bytes = 1 analog input/output

CPU

Execution time perBinary instructionLoad/Transfer (word)16-bit integer (+/-)IEEE floating pnt (+/-)

User memory Work memoryLoad memory integr. Load memory extern

Addresses Bit memoriesClock memoriesTimersCounters

Block Types /NumberFBsFCsDB's

Size of Process Image (inputs/outputs)

Max. I/O address area

Integral interfaces

414-1

100 ns100 ns100 ns0.6 µs

128 KB8 KB15 MB

81928256256

51210241023

256 byteseach

2 Kbyte each*)

MPI

416-1

80 ns80 ns80 ns0.48 µs

512 KB16 KB15 MB

163848512512

204820484095

512 byteseach

4 KByteeach *)

MPI

414-2 DP

100 ns100 ns100 ns0.6 µs

128/384 KB8 KB15 MB

81928256256

51210241023

256 byteseach

4 Kbyte each*)

MPI, DP

412-1

200 ns200 ns200 ns1.2 µs

48 KB8 KB15 MB

40968256256

256256511

128 bytes each

0.5 Kbyte each*)

MPI

413-2 DP

200 ns200 nsc200 ns1.2 µs

72 KB8 KB15 MB

40968256256

256256511

128 byteseach

1 Kbyte each*)

MPI, DP

413-1

200 ns200 ns200 ns1.2 µs

72 KB8 KB15 MB

40968256256

256256511

128 bytes each

1 Kbyte each*)

MPI

416-2 DP

80 ns80 ns80 ns0.48 µs

0.8/1.6 MB16 KB15 MB

163848512512

204820484095

512 byteseach

8 KByteeach *)

MPI, DP

417-4

100 ns100 ns100 ns0.48 µs

4...20 MB256 KB64 MB

163848512512

614461448191

1024 bytes each

16 KByteeach*)

MPI,4 x DP

Page 392: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Appendix: Special Features of S7-400Page 5

Communication The S7-400 offers a variety of facilities for communication:1. Integral Multi-Point-Interface (MPI), for connection of PGs/PCs, HMI

systems, M7-300/400 systems and other S7-300/400 systems as active nodes.

2. Integral PROFIBUS-DP interfaces on CPUs 413-2/414-2/416-2/417-4 forconnection of distributed I/O stations (e.g. ET200) to the CPU.

3. Communication processors such as CP443, for connection to the PROFIBUS and Industrial Ethernet bus systems.

4. Communication processors such as CP441, for powerful point-to-point (PtP) communication to other S7 or S5 PLCs or PLCs from other manufacturers.

S7 Functions There are two types of S7 communication functions:S7 basic communication: These services can be used for exchanging small quantities of data (up to 76 bytes) between communication partners (S7-300/400) via MPI orwithin a station (or to intelligent slaves via PROFIBUS-DP). The necessary communication SFCs are integrated in the operating system. You don't need to configure the connections. You assign the communication resources and specify the address of the communication partner direct in the SFC call. S7 extended communication: These services enable larger quantities of data (up to 64KBytes) to be exchanged on any network (MPI, Profibus or Industrial Ethernet). The necessary SFBs are integrated in the operating system of the S7-400 (not S7-300, S7-300 as server only). They need configured connections when called. Configured connections are established in accordance with the connection table on power up and the relevant resources are assigned statically.

Date: 05.12.2005File: PRO1_18E.5

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

CPU

Organization blocksFree cycleTime-of-day interruptsTime-delay interruptsCyclic interruptsHardware interruptsMulticomp. interruptBackground executionStartupErrors, asynchronousErrors, synchronous

Local data

Max. block lengthBlock nesting depth

per execution level

Program-controlled communication: max. number of connections

Global data communication via MPI:GD circles per CPU

Send GD packets per GD circle

Receive GD packets perGD circle

Max. user data size of apacket

Technical Specifications of the S7-400 CPUs (2)414-1

OB No.110-1320-2332-3540-436090100-10280-87121,122

8 KB

64 KB16

32

8

1

2

54 bytes

416-1

OB No.110-1720-2330-3840-476090100-10280-87121,122

16 KB

64 KB16

64

16

1

2

54 bytes

414-2 DP

OB No.110-1320-2332-3540-436090100-10180-87121,122

8 KB

64 KB16

32

8

1

2

54 bytes

412-1

OB No.110,1120,2132,3540,416090100-10280-87121,122

4 KB

64 KB16

8

8

1

2

54 bytes

413-2 DP

OB No.110,1120,2132,3540,416090100-10280-87121,122

4 KB

64 KB16

16

8

1

2

54 bytes

413-1

OB No.110,1120,2132,3540,416090100-10180-87121,122

4 KB

64 KB16

16

8

1

2

54 bytes

416-2 DP

OB No.110-1720-2330-3840-476090100-10280-87121,122

16 KB

64 KB16

64

16

1

2

54 bytes

417-4

OB No.110-1720-2330-3840-476090100-10280-87121,122

24 KB

64 KB24

64

16

1

2

54 bytes

Page 393: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Appendix: Special Features of S7-400Page 6

Differences The main differences between the S7-400 and the S7-300, with which you have been working in this course, are listed above.

Date: 05.12.2005File: PRO1_18E.6

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Main Differences to the S7-300

Larger memory and more I/Q/M/T/C

Addresses of input/output modules selectable

Can connect EUs from S5 and use S5 CP/IP modules

More system functions, e.g. programmed block communication

Block size up to 64KB and twice as many DBs

Complete restart and restart

Preset/actual comparison of configuration on startup

Modules can be removed without disconnecting the power supply

Several part process images

Priorities of OBs are parameter-assignable

Several OBs for cyclic, hardware and time-of-day interrupts

Block nesting up to 16 levels

Size of L Stack selectable for each execution level

4 accumulators

Multicomputimg

Page 394: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Appendix: Special Features of S7-400Page 7

Racks The following racks are available for S7-400 PLCs.• UR1/UR2 are universal racks and can be used as either central racks or

extension racks. They have 18/9 single-width slots with P and K bus.• ER1/ER2 are extension racks without a K bus.• CR2 is a segmented central rack for asymmetrical multicomputing.

S7-CPUs The S7-400 CPUs are upward compatible for all STEP 7 user programs. There are two versions: single-width and double-width with integrated DP master interface. The integrated DP interface enables up to 64 DP slave stations to be addressed. The maximum transmission rate is 12 Mbps.

FMs The FMs for positioning, closed-loop control and counting replace the S5-IP range.

IMs Interface modules can be used for connecting SIMATIC S7 and SIMATIC S5 extension racks to an S7-400 central rack.

CPs CP modules enable a CPU to be hooked up to the following networks:• Industrial Ethernet (CP 443-1)• PROFIBUS (CP 443-5)• Point-to-Point network (CP441-1 and CP441-2).Each CPU also has an MPI interface for connection to an MPI network. Up to 32 nodes can be connected to an MPI network.

Date: 05.12.2005File: PRO1_18E.7

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Components of the S7- 400

CPUsCPUs

CPU 412-1CPU 413-1, 413-2 CPU 414-1, 414-2,CPU 416-1, 416-2CPU 417-4

RacksRacks

- Universal rack (UR 1/2) for use as CR and ER

- Extension rack (ER 1/2)- Segmented central rack (CR2)

Signal modules (SM)Signal modules (SM)

- DI/DO 32,16,8 channels- DO wit h relay output- AI/AO 16,8 channels- diagnostics-capable

modules

Communicationprocessors (CP)

Communicationprocessors (CP)

- Point-to-PointCP441-1, 1- channelCP441-2, 2- channel

- NetworksProfibus Ethernet

Power supplies (PS)Power supplies (PS)

- AC 120V/230V, 4A/10A/20A- DC 24V, 4A/10A/20A

Functionmodules (FM)Function

modules (FM)

- Counting- Positioning- Closed-loop control

Page 395: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Appendix: Special Features of S7-400Page 8

UR 1 / UR 2 UR1/UR2 can be used both as central and as extension rack. They have a parallelPeripheral Bus (P bus) for the high-speed exchange of I/O signals (1.5 microsec./ Byte) and the time critical access of the signal module process data.In addition, UR1 (18 slots) / UR2 (9 slots) have a serial, powerful Communication bus(K bus) for high-speed data exchange (10.5 Mbps) between K bus stations (S7/M7 CPUs, FMs, CPs, ).By separating the P BUS and K BUS, each task is assigned its own bus system. Control and communication have their own separate "data highways". That way, the communication tasks do not slow down the control tasks.

CR2 The segmented rack CR 2 features an I/O bus divided into two segments with 10 and 8 slots. One CPU can be used for each segment. Both CPUs are respectively master for their P bus segment and can only access their own SMs. Operating mode transitions are not synchronized, that is, the CPUs can be in different operating modes. Both CPUs can communicate via the continuous K bus.

Why CR2? All CPUs (max. 4) have the same operating mode in symmetrical multicomputing, e.g.STOP, that is, the operating mode transitions are synchronized.

ER 1 / ER 2 ER1 (18 slots) / ER2 (9 slots) have no K bus, no interrupt lines, no 24 V power supply for the modules and no battery power supply.

No Slot Rules Exception: PS on the far left and Receive IM in the ER on the far right!

Date: 05.12.2005File: PRO1_18E.8

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Racks of the S7 - 400

UR1 / UR2(Universal Rack)

Type of Rack Centralrack

Extensionrack

Usable in

Yes Yes

P busER1 / ER2(Extension Rack)

No Yes

P bus

K bus

CR2(Central Rack)

NoYesP bus, Segment 1

K bus

P bus, Segment 2

Page 396: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Appendix: Special Features of S7-400Page 9

General The S7-400 has default addresses for the I/O modules. These defaults remain active until a configuration is downloaded to the CPU.The system generates these default addresses from the geographic addresses.

Addresses The default settings correspond to the slot-dependent addressing of theS7-300.The address depends on the slot in which the module is inserted in the rack. It is calculated as follows: • digital starting address = [(rack number) x 18 + slot no. -1] x 4• analog starting address = [(rack number) x 18 + slot no. -1] x 64 + 512The rack number is set on the receive-IM (No. 1 to 21). The central rack always has the number 0.Variable (slot-dependent) addresses of the I/O modules are established using the HW Config tool.

Part Process Image In additon to the (full) process image (PII and PIQ), you can assign parameters for up to 8 part process images for an S7-400 CPU (No. 1 to No. 8). You can update each part process image in the user program using SFCs. This means that you can deactivate cyclic updating of the process image and implement event-driven updating of the process image in the user program.

Date: 05.12.2005File: PRO1_18E.9

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Module Parameters: Logical Addresses

Page 397: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Appendix: Special Features of S7-400Page 10

Date: 05.12.2005File: PRO1_18E.10

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

CPU Parameters: Startup

Preset/Actual For specifying whether the CPU should stall start up if the actual I/ODifference configuration differs from the preset configuration.

Delete PIQ!!! The process image output table is deleted in the first residual cycle on hot restart. Always select this if possible.

Restarts On Complete Restart (warm restart), the M/C/Ts are reset and the user program starts from the beginning.On Restart (hot restart), the retentive M/C/Ts are not reset and execution of the user program resumes at the point of interruption.

Actions The operating system performs the following actions on startup:

• deletes stacks (CR)• resets non-retentive bit memories, timers, counter (CR)• resets process image output table PIQ (CR), takes action as instructed by

parameter assignment (R)• resets external output area (CR), takes action as instructed by parameter

assignment (R)• resets interrupts (CR/R) by means of OD• updates system status list (CR/R)• transfers configuration to modules (CR/R)

(CR= complete restart, R= restart).

Page 398: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Appendix: Special Features of S7-400Page 11

Hardware Interrupts This parameter block is for setting the priorities of the hardware interrupt organization blocks. Permissible entries are 0 and the values from 2 to 24(0 = deselect).Priorities range from 1 to 24 and if two interrupts occur at the same time, the one with the higher priority is processed first.There are 8 independent of one another hardware interrupts, each with its own organization block. You assign the interrupt OBs to the interrupt modules when assigning the I/O module parameters.

Time-Delay Interrupts A time-delay interrupt is a delayed one-time call of an organization blockactivated, for example, when a process signal is received.In this parameter block of the Interrupts tab page you can set the priorities of the time-delay interrupts. Permissible entries are 0 and values from 2 to 24 (0 = Deselect). Time-delay interrupts are handled by SFCs 32 to 34.

• SFC32 "SRT_DINT" = Start time-delay interrupt.• SFC33 "CAN_DINT" = Cancel time-delay interrupt• SFC34 "QRY_DINT" = Query status of time-delay interrupt

Communication The arrival of communication data can be indicated by communication interruptsInterrupts to enable the data received to be evaluated as quickly as possible.(coming soon)

• Global Data interrupt (OB50)• SFB communication interrupt (OB51)

Date: 05.12.2005File: PRO1_18E.11

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

CPU Parameters: Interrupts

Page 399: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Appendix: Special Features of S7-400Page 12

Date: 05.12.2005File: PRO1_18E.12

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

CPU Parameters: Local Data

Local Data The system reserves 256 bytes in the local data stack (default setting) for every execution level.If the user program requires little or no local data in several levels, you can specify the local data requirements you want (scratchpad memory) per level (OB).

The maximum amount of local data depends on the type of CPU:CPU 412 -> 4 Kbyte of local dataCPU 413 -> 4 Kbyte of local dataCPU 414 -> 8 Kbyte of local dataCPU 416 -> 16 Kbyte of local dataCPU 417 -> 24 Kbyte of local data

Page 400: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Appendix: Special Features of S7-400Page 13

Date: 05.12.2005File: PRO1_18E.13

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Configuring Multicomputing Operation

Overview Multicomputing operation is the synchronous operation of several CPUs (2 to 4) in an S7-400 central rack. The CPUs startup together, if they have the same startup mode (complete restart or restart) and they also go into the STOP mode together.

Setting Up You can set up a multicomputing operation by inserting several multicomputing-Multicomputing capable CPUs in a suitable rack. The infotext in the "Hardware Catalog" indicates

whether a CPU is multicomputing-capable.The CPUs participating in multicomputing, "divide" a common address area, that is, the adress area of a module is always assigned to a specific CPU.

What to Do You can configure the multicomputing operation as follows:1. Line up all the CPUs necessary for the multicomputing operation.2. Double-click on the CPUs and adjust the CPU number in the

"Multicomputing" tab.3. To assign a module to a specific CPU, proceed as follows:

- Arrange the modules in the rack.- Double-click the modules and select the "Addresses" tab.- In the "CPU Nu.." field select the number of the CPU you want.

For interrupt capable modules, the CPU assignment is displayed as the target CPU in the "Inputs" or "Outputs" tab.

You can make the modules that are assigned to a specific CPU stand out optically in the table by selecting the menu options View -> Filter -> CPU No.x Modules.The parameter assignment data for a station are always downloaded into all participating CPUs; downloading into only one CPU is not possible. That way, inconsistent configurations are avoided.

Page 401: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Appendix: Special Features of S7-400Page 14

Date: 05.12.2005File: PRO1_18E.14

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

SFC 35 for Synchronization in Multicomputing Operation

Parameter Declaration Data type Memory Description

JOB INPUT BYTE I, Q, M, D, L, Const. Task identifier (possible values: 1 to 15)

RET_VAL OUTPUT INT I, Q, M, D, L Return value (error code).

Description The call of SFC 35 "MP_ALM" triggers the multicomputing interrupt. This leads to the synchronized start of OB60 on all relevant CPUs. With single-processor operation and with operation in a segmented rack, OB 60 is only started on the CPU in which you called the SFC 35.You can use the input parameter JOB to identify the cause for the multicomputing interrupt that you wanted. This task identifier is transferred to all relevant CPUs and you can evaluate it in OB 60.You can call SFC 35 (MP_ALM) anywhere in your program. Since this call only makes sense in RUN mode, the multicomputing interrupt is suppressed when it is called in the STARTUP mode. A function value informs you of this.

Error Code If an error occurs while the function is being executed, the return value receives an error code:

W#16#0000: No error has occurred.

W#16#8090: The input parameter JOB contains an invalid value.

W#16#80A0:The OB 60 execution of the preceeding multicomputing interrupt is not yet completed in its own or in another CPU.

W#16#80A1: Incorrect operating mode (STARTUP instead of RUN).

Page 402: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Appendix: Special Features of S7-400Page 15

Date: 05.12.2005File: PRO1_18E.15

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Remove and Insert Interrupt

Module exists

Module available

Remove/Insert interrupt

Parameter assignment of module through the operating system

Removing amodule

Inserting amodule

max.

1smax.

1s

Remove and Insert In the S7-400, it is possible to remove and to insert modules while powered upInterrupt OB83 in RUN or in STOP mode. The exceptions to this are CPUs, PSs, S5 modules in

adapter modules and IMs.After removing a module in the RUN mode, you can - depending on the situation - call the following organization blocks from the CPU‘s operating system:• OB 85-Process image update• OB 122-I/O access error• OB 83- Remove&Insert event. You must take into consideration that OB 83 is only called after approximately 1sec., while the other OBs, as a rule, become active much sooner.After you insert the module, it is checked by the CPU and - if no type error exists - it is assigned parameters. After a correct parameter assignment, the module is available for use.If an error is recognized during parameter assignment, the diagnostic interrupt OB82 is automatically started.

Start Information The following information exists in the local data of OB83:in OB83 • module removed or inserted

• logical address of the module• type of module

Replacement Value You can specify replacement values for the missing process signals of an input module by using a system function.

Page 403: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Totally Integrated AutomationPage 1

Contents Page

Automating with SIMATIC S7 ........................................................................................................... 2The SIMATIC S7/C7/M7 and WinAC Controllers .............................................................................. 3STEP 7- Software for S7/C7/M7 .......................................................................................................... 4Programming Sequence Control Systems with S7- GRAPH ........................................................... 5Programming using the State Diagram Method with S7- HiGraph .............................................. 6Programming in the High Level Language S7- SCL ......................................................................... 7CFC for SIMATIC S7 and SIMATIC M7 .............................................................................................. 8Configuring Sequence Control Systems with S7- SFC ..................................................................... 9Process Diagnosis with S7- PDIAG .................................................................................................... 10Testing User Programs with S7- PLCSIM ……….......................................................................... 11Remote Maintenance and Remote Diagnosis with TeleService ...................................................... 12Creating Plant Documentation with DOCPRO ........................................................................... 13Runtime Software for Closed-loop Control Engineering Tasks ......................................................... 14Borland C/C++, M7- ProC/C++ and M7- SYS RT for M7 Automation Computers .......................... 15Communicating with SIMATIC NET ................................................................................................. 16Operator Control and Process Monitoring with SIMATIC HMI .......................................................... 17Consistent Configuration with SIMATIC ProTool ............................................................................. 18Process Visualization and Operator Control with WinCC .................................................................. 19Process Automation with SIMATIC PCS 7 ....................................................................................... 20Summary ……................................................................................................................................ 21

Date: 05.12.2005File: PRO1_19E.1

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Totally Integrated Automation

SIMATICWinCC

SIMATIC PC

SIMATIC DP

SIMATIC Controller

SIMATIC HMI

SIMATIC NET

SIMATICPCS 7

SIMATIC Software

SIMATIC

Page 404: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Totally Integrated AutomationPage 2

Introduction In the past, the SIMATIC product name was frequently used as a synonym forprogrammable logic controllers.

Today SIMATIC has come to mean much more: SIMATIC is the basic automation system for solving automation tasks in all industries. It consists of standard components in hardware and software, that offer a multitude of possibilities for customer-specific expansions.

Two factors have lead to this solution:• the new, comprehensive SIMATIC software, that has the optimal tool for every phase of an automation project and• the members of the SIMATIC automation family, that are more than just

programmable logic controllers.

TIA Totally Integrated Automation is the new way of uniting production and process control technology. All hardware and software components are thus united in a single system with the name SIMATIC. This total integration is made possible by a threefold integraton:• common data management (data are only entered once),• common configuring and programming (modular software),• common communication (simple and uniform configuration).

In the slide you can see the individual components of TIA.

Date: 05.12.2005File: PRO1_19E.2

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Automating with SIMATIC S7

ASI

PROFIBUS-DP

S7-200 S7/M7-300 S7/M7-400

OP...OS

7 8 9

4 5 6

1 2 3

0

.D E F

A B C INSDELSHIFT HELP

ESC

ENTER

ACK

SIMATIC OP17

SHIFT

HELPK1 K5 K6 K7 K8K2 K3 K4

K9 K10 K11 K12 K13 K14 K15 K16

F1 F5 F6 F7 F8F2 F3 F4

S I M A T I C O P 1 74 x 2 0 Z e i c h e n

6 / 1 1 m m S c h r i f t h ö h e8 x 4 0 Z e i c h e n

Z e i c h e n g r ö ß e n b e l i e b i g m i s c h b a r

Standard Tools

Engineering Tools

Runtime Software

SIMATIC SOFTWARE

WIN CC PCS 7

SIMATIC NET

ET200

FM

SV

Industrial Ethernet PROFIBUS

MPI Network

SIMATIC PGSIMATIC PC

PG 740

SIEMENS

SIMATIC Controller

SIMATIC HMI

SIMATIC DP

WinAC

Page 405: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Totally Integrated AutomationPage 3

SIMATIC S7 The programmable logic controller family consists of the Micro PLC (S7-200) performance range, the lower performance range (S7-300) and the middle/upper performance range (S7-400).

SIMATIC M7 The M7 PLC system brings AT compatible computer performance to the PLC and, vice versa, PLC functionality to the computer user in the computer world while keeping the familiar programming environment.The M7-300 and M7-400 automation computers expand the PLC family by an open hardware and software platform. They consist of an AT compatible computer with the proven real-time multitasking operating system RMOS.M7 is always installed in situations where high computer performance and the demanding tasks of process data management and visualization are required.

SIMATIC C7 This complete system is the combination of a PLC (S7-300) and an operator panel of the HMI operator control and process monitoring system. The integration of programmable logic controller and operator panel in one device makes complete machine controls in the smallest space and at an economical price possible.

WinAC WinAC is a PC-based solution. It is used when various automation tasks (control, visualization, data processing) are to be solved with a PC.

There are 3 different products:

• WinAC Basic as pure software solution (PLC as Windows NT-Task),• WinAC Pro as hardware solution (PLC as PC card),• WinAC FI Station Pro as complete solution (SIMATIC PC FI25)

Date: 05.12.2005File: PRO1_19E.3

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

The SIMATIC S7/C7/M7 and WinAC Controllers

modular

SIMATIC S7 - 400

modular

SIMATIC S7 - 300

modular

SIMATIC M7 - 300

complete

SIMATIC C7 - 620

SIMATIC S7 - 200

compact

modular

SIMATIC M7 - 400

Upper andmiddle performancerange

Lower performancerange

Micro PLC

SIMATIC WinAC Pro

SIMATIC WinAC Basic

Page 406: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Totally Integrated AutomationPage 4

STEP 7 Micro for configuration, service and commissioning of S7-200 logic controllers

STEP 7 Mini for programming, service and commissioning of simple stand-alone applications of S7-300 and C7-620.Unlike STEP 7, there are the following restrictions:• cannot (additionally) load option packages, for example, Engineering Tools.• no communication configuration (CPU - CPU communication) possible.

STEP 7 Basic package for project planning and programming S7-300/400 logic controllers, with interfaces to the option packages.

Options Options are software packages for S7/ M7 for program generation, debugging and commissioning:• S7-SCL = PASCAL-similar high level language.• S7-GRAPH = Graphic programming of sequence control systems. • S7-HiGraph = Graphic programming of machining sequences. • CFC = Graphic configuring and interconnection of blocks.• S7-PLCSIM = Testing the program logic offline on the PG/PC.• S7-Pdiag = Process diagnostics for logic controllers and sequence control systems.• TeleService = Extension of the MPI interface via the telephone network.• HARDPRO = Configuration software for hardware.• DOCPRO = Documentation software.

Closed-loop Control Runtime Software (standard function blocks and parameter assigning tools) for (Engineering) solving closed-loop control engineering tasks:

M7 • Borland C/C++ = Programming environment for M7• M7-ProC/C++ = Integration of Borland C/C++ in STEP 7 (Debugger)• M7-SYS = Operating system for M7

Date: 05.12.2005File: PRO1_19E.4

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

STEP 7 Software for S7/C7/M7

STEP 7 Mini

Standard ToolsEngineering Tools

S7-300 S7-300C7

S7-400C7

M7-300M7-400

M7-SYS

STEP 7

Runtime Software ToolsCFC

DOCPRO

TeleService

S7-PDIAG

S7-PLCSIM

S7-HiGraph

S7-Graph

S7-SCL

PID Control

Fuzzy Control

Neuro Systems

M7-ProC/C++

Borland C/C++

S7-200

STEP 7 MicroLAD / STL

S7-200Support

LAD / STL

Manager

S7-300Support

S7-300Support

S7-400Support

Manager

STL LAD FBD

Page 407: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Totally Integrated AutomationPage 5

S7-GRAPH With the S7-GRAPH programming language, you can clearly and quickly configure and program sequential sequences that you wish to control with an S7 PLC system.The process is thus split into single steps with their own function scope. The sequence is graphically displayed and can be documented with picture and text.The actions to be performed and the transitions, which control the conditions for switching to the next step, are determined in the individual steps. Their definitions, interlocking or monitoring are determined by a subset of the STEP 7 programming language LAD (ladder diagram).S7-GRAPH for S7-300/400 is compatible with the sequence language established in the IEC 1131-3 standard.

Functionality The following functions are offered:• Several sequencers in the same S7-GRAPH function block• Free number assignment of the steps and transitions • Simultaneous branches and alternative branches• Jumps (also to other sequence cascades)• Starting/Stopping of sequence cascades as well as activating/holding of

steps.

Test Functions • Display of active steps or faulty steps• Status display and Modify Variable• Switching between the operating modes: manual, automatic and jogging mode

User Interface • Overview, Single Page and Single-step display• Graphic separation of locking controls and monitoring conditions.

Date: 05.12.2005File: PRO1_19E.5

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

S1

Programming Sequence Control Systems with S7- GRAPH

S7-GRAPH: The tool for programming sequence cascades

Compatible with IEC 1131-3Designed for the requirements ofproduction engineeringGraphic division of the processinto steps and transitionsSteps contain actionsTransitions check the conditions for switching to the next step

The following phases of automation can be optimized with S7-GRAPH:

Planning, ConfiguringProgrammingDebuggingCommissioningMaintenance, Diagnostics

S2

T1

T2

S4

T3

S6

T4

T5

S5

Page 408: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Totally Integrated AutomationPage 6

Overview S7-Higraph allows the asychonous processes to be described using state diagrams. The machine or system to be automated is looked upon as a combination of independent elements, the function units.

Function Units The function units are the smallest mechanical units of a machine or system. As a rule, a function unit is made up of mechanical and electrical basic elements. In programming, a state diagram is assigned to every function unit. In it, the functional, that is, the mechanical and electrical properties of the function unit are mapped.

State Diagram The state diagram describes the dynamic behaviour of a function unit. It describes the states that a function unit can have, as well as the state transitions. State diagrams can be used more than once. State diagrams that were created once for a specific function unit, can be reused in other progam locations.

Diagram Groups By combining parallel running state diagrams, you can describe the completeand Instances functionality of a machine or system.

Advantages This "object-oriented" method of S7-HiGraph is well suited for:• the machine and system manufacturer (mechanical engineering)• the automation specialist (electrical engineering) as common means of

description• the commissioning engineer and the maintenance specialistThe state diagram method helps to optimize the entire process for the creation of a machine or system in the sense of shorter development and turnaround time as well as less commissioning time.

Date: 05.12.2005File: PRO1_19E.6

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Programming using the State Diagram Method with S7- HiGraph

1 2 4

PositionCam-operated switch

Index in

Index out

Counterbearinglock/release

pieceTurn left

Turn right

Motor

IndexCounterbearingMotor

Coordinator

S7-HiGraph: The tool for programming using State Diagrams

Division of the machine intofunctional unitsCreating state diagramsfor every function unitStates contain actionsState diagrams communicateusing messages

The following phases of automation can be optimized with S7-HiGraph:

Planning, ConfiguringProgramming and DebuggingCommissioningMaintenance, DiagnosticsSupports reuseability

Page 409: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Totally Integrated AutomationPage 7

Overview S7-SCL (Structured Control Language) is a PASCAL-similar high level text language for S7 - 300/400 and C7 and simplifies the programming in control technology for mathematical algorithms, data management and organization tasks.S7-SCL has the PLCopen Base Level certificate and is in accordance with the IEC 1131-3 (Structured Text) standard.With S7-SCL, you can formulate time-saving and economical solutions for automation tasks.

Functionality SCL offers the functional scope of a high level language such as:• loops• alternatives• branch distributors, etc.combined with control-specific functions such as:• bit accesses to the I/O, bit memories, timers, counters etc.• access to the symbol table• STEP7 block accesses

Advantages of SCL • simple to learn programming language especially for beginners• easy to read (understandable) programs are generated.• simpler programming of complex algorithms and processing of complex data

structures• integral debugger for symbolic debugging of the source code (single-step,

breakpoints, etc.)• system integration in S7 languages such as STL and LAD.

Date: 05.12.2005File: PRO1_19E.7

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Programming in the High Level Language S7- SCLFUNCTION_BLOCK IntegratorVAR_INPUT

Init : BOOL; // Reset output valuex : REAL; // Input value Ta : TIME; // Sampling interval in msTi : TIME; // Integration time in msolim : REAL; // Output value upper limit ulim : REAL; // Output value lower limit

END_VAR

VAR_OUTPUTy : REAL:= 0.0; // Initialize output value with 0

END_VAR

BEGIN IF TIME_TO_DINT(Ti) = 0 THEN // Division by ?

OK := FALSE;y := 0.0; RETURN;

END_IF;IF Init THEN

y:= 0.0;ELSE

y := y+TIME_TO_DINT(Ta)*x/TIME_TO_DINT(Ti); IF y > olim THEN y := olim; END_IF; IF y < ulim THEN y := ulim; END_IF;

END_IF; END_FUNCTION_BLOCK

S7-SCL: High level language for creating PLC programs

Compatible with IEC 1131-3Text(ST=Structered Text))Certified according to PLCopenBase LevelContains all the typicalelements of a high level language, such asoperands, terms, control statementsPLC specifics are integrated, such as I/O access, timers, counters...)

Advantages:Well structured, easy tounderstand programFor those knowlegeable in highlevel langugagesFor complex algorithms

Page 410: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Totally Integrated AutomationPage 8

Overview With the engineering tool CFC (Continuous Function Chart), you can create SIMATIC S7 or SIMATIC M7 automation tasks by drawing a technology plan - similar to a Function Block Diagram in PLC programming.In this graphic programming method, blocks are positioned in a type of drawing sheet and are graphically interconnected with one another. You can quickly and easily convert technological aspects into complete executable automation programs with CFC.

Scope The following is supplied with CFC:• CFC Editor• Code Generator• Debugger• Standard block libraries

Customer Benefits • The CFC product, as an option package, is smoothly integrated in the STEP 7 architecture with a unified Look&Feel and with common data management. CFC is easy to use, easy to learn and provides consistent data

management.• You can use CFC for simple tasks as well as for very complex tasks.• Simple interconnection technology makes communication between blocks user-friendly to configure.• Manual handling and management of machine resources is no longer

necessary.• User-friendly testing and debugging are supported

Date: 05.12.2005File: PRO1_19E.8

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

CFC for SIMATIC S7 and SIMATIC M7

CFC (Continuous Function Chart):Tool for graphic creation of PLC programs

Blocks are placed on function charts and interconnectedInterconnection is possible:- between I/O fields- also to blocks in

other chartsSources and destinations are managed in themargins

AdvantagesProgram creation fortechnologistsquick creation, testing and commissioning times

Page 411: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Totally Integrated AutomationPage 9

SFC (Sequential SFC is a sequence control system with step by step execution, that was Function Chart) designed especially for the demands of process control systems (process engineering,

process control engineering, etc.).The typical fields of application for sequence control systems of this type are in the areas of discrete production processes. Sequence control systems can, however, also be installed in continuous systems, for example, for startup or shutdown, working point changes as well as state changes due to disturbances etc.With SFC, for example, product manufacturing specifications can be written as event-driven processes.

Principle In the SFC Editor, you generate the flow chart by graphic means. The structureMethod of Operation elements of the plan are thereby placed according to fixed rules. You do not have to

worry about details such as algorithms or the allocation of machine resources, but instead can concentrate on the technological aspects of the configuration.After generating the plan topology, you switch into the detail display (zoom-in configuration) and there assign parameters to the individual elements, that is, you configure the actions (steps) and the conditions (transitions).In the programming of actions, functions of the basis automation, typically generated with CFC, are controlled or selectively processed per operating change and state change.After configuration, you generate the executable machine code through the SFC, download it into the PLC and test it with the SFC test functions.

Date: 05.12.2005File: PRO1_19E.9

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Configuring Sequence Control Systems with S7- SFC

S7-SFC: The tool for programming sequence cascades

Designed for the require-ments of process automationCompatible with IEC 1131-3Steps assign values to blocks in the CFCTransitions check theconditions for switching tothe next stepSyntax check during creation

Direct connection to CFCAcceptance of values using“Drag&Drop”Cross reference selections

Visualization within WinCC

Page 412: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Totally Integrated AutomationPage 10

Process Diagnosis Diagnosis is important in the operating phase of a plant or machine. Diagnosis is usually initiated when a fault leads to standstill or malfunction of the plant or machine. Programmable logic controllers are widely used in many areas. Field experience has proven that over 98% of faults occur in the peripherals (magnet valves, end switches, etc.). The distribution of fault occurrences makes it meaningful for the diagnosis to focus on process faults, since missing messages or faulty functions lead to down-times and the resulting costs. Process diagnosis diagnoses exactly these external components (sensors, actuators, etc.) or sequences in the process of a plant or machine.

S7-PDIAG The S7-PDIAG software package enables a uniform configuration of the process diagnosis for the SIMATIC S7-300/400 controllers in the LAD, FBD and STL programming languages. You can already define signal monitoring routines including first-up signal acquisition and criteria analysis and input the associated message texts while or after creating the user program in the LAD, FBD or STL programming languages. PDIAG automatically generates monitoring blocks which you must call in your user program.At every call, the fault conditions are checked and in case of an error, the relevant process values are acquired and sent to the display device for the criteria analysis. For the configuration of the operator panel, S7-PDIAG stores the process diagnosis data in a shared database. This data can then be accessed by the OP configuration software SIMATIC ProTool with the option package ProAgent and be made available for display on the operator panel.

Date: 05.12.2005File: PRO1_19E.10

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Process Diagnosis with S7- PDIAG

I1.0 I1.1 Q1.0

Message

Process diagnosis: Detection of faults occurring outside the PLC

Sensor/actuator defective, movement faulty, ...

S7- PDIAG: Tool for configuringthe fault definition in STL, LAD, FBD

Integrated in the development environmentSimple formulation of fault monitoring andmessage texts (during and after the program session)Fault detection and criteria analysis are conducted automaticallyComprehensive information for the operator on:

type of faultlocation of faultcause of fault

Reduction of down-time

Page 413: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Totally Integrated AutomationPage 11

S7 - PLCSIM The SIMATIC S7-PLCSIM engineering tool (option package) emulates a complete S7-CPU including addresses and I/O on a PG/PC. S7-PLCSIM thus enables you to test a program offline on the PG/PC. All STEP 7 programming languages (STL, LAD, FBD, S7-Graph, S7-HiGraph, S7-SCL and CFC) can be used.S7-PLCSIM allows you to check the functionality of user programs on the PC/PG, regardless of whether the final hardware is available or not.

Functionality S7-PLCSIM offers the following functions for running a program on a simulated PLC:• An icon in the SIMATIC Manager‘s toolbar switches the Simulation on or off. If the simulation is turned on, every new connection is automatically made to

the simulated PLC.If the simulation is turned off, then every new connection is made to the

"real" PLC. • You can create view objects that allow you to access memory areas, accu-

mulators and tabs of the simulated CPU. You can modify and display all the data in these view objects.

• You can change the CPU‘s operating mode (STOP, RUN and RUN-P) just as with a "real" CPU. The simulation also provides a "Pause" function that allows you to halt the program execution without affecting the state of the program.

Advantages With S7-PLCSIM, you can detect faults early in the development phase and eliminate them. The quality of the user programs is greatly improved and the commissioning costs are lowered.

Date: 05.12.2005File: PRO1_19E.11

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Testing User Programs with S7- PLCSIM

S7-PLCSIM: Simulation software for offline testing of PLC programs

Functional program test on a simulated CPUwith display/modify I/O

Testing of user blocks in LAD, FBD, STL, S7-SCL,S7-GRAPH, S7-HiGraph, CFCS7-PDIAG, WinCC

AdvantagesFaults can be detected early and eliminatedMany tests are already possible in the office without the final hardware

Page 414: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Totally Integrated AutomationPage 12

TeleService With Teleservice, SIMATIC S7- /M7- /C7 PLCs can be remotely maintained with the PG/PC using a telephone network or a radio network. All the while, you have the full functionality of STEP 7 and the Engineering Tools at your disposal.

Configuration A PG/PC is connected to the PLC using standard modems available on the market. The following are supported:• Analog modems• External ISDN adapter/modems• GSM technology (e.g. D1 network)On the plant side, a teleservice-capable TS adapter is inserted between the standard market modem and the MPI network. All stations (nodes) are thus accessible on the MPI network with this connection.

Procedure To set up teleservice operation, you must carry out the following steps:• Assigning parameters to the modem on the PG/PC side (TS adapter with

default parameters for the modem on the plant side) using the teleservice package.

• Establishing a remote connection, supported by an electronic phone book, which includes system management in the form of a file system.

• Carrying out remote maintenance with the full function scope of STEP 7 and the Engineering Tools.

Advantages Through the accessibility of PLCs in remote (other rooms, plants, etc.) locations you can carry out technical services such as maintenance, update services or fault analysis from a central service base cost effectively.

Date: 05.12.2005File: PRO1_19E.12

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

CPU I/O ...

TS adapter

Control room withSTEP7 and TeleService

PG/PCmodem

systemmodem

CPU

MPI bus

Remote Maintenance and Remote Diagnosis with TeleService

TeleService: Makes an onlineconnection to SIMATIC S7/C7 or M7 possible"Extends" the MPI via telephone/radio networks

STEP 7 functionality Market standard modems and TS adapterFault detection, fault eliminationand commissioning from a central location

Advantages:Reduction of maintenance costs Faster upgrading of the system

Page 415: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Totally Integrated AutomationPage 13

DOCPRO DOCPRO is a tool for creating and managing plant documentation. DOCPRO allows you to structure project data, prepare wiring manuals and print out all this information in a uniform format.

Functionality DOCPRO provides you with user-friendly functions for creating and managing the documentation as a wiring manual of the plant:• Creation of wiring manuals and job lists (result of print jobs);

a wiring manual is subdivided into job lists.• Central creation, editing and managing of footer data; the individual jobs can also be assigned footers that contain information about the particular job.• Standard layout templates supplied with the program in different formats as the starting point for your own layouts and coversheets.• Automatic and manual assignment of reference numbers; you can assign the job‘s reference numbers according to your own criteria.• Automatic creation of document indexes of the printed documentation.• Printing of job lists and wiring manuals; the jobs of a job list are printed in the

predefined sequence. You can take a look at the print reports and status list after printing is completed.

Advantages The project data of a project/plant can be clearly documented with DOCPRO. A structured (well-organized) documentation makes additional work on a project as well as service work easier and thus saves time and money.

Date: 05.12.2005File: PRO1_19E.13

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Creating Plant Documentation with DOCPRO

DOCPRO: Creating wiring manuals for plants

Standardized layout templates, can be modified to your needsGenerates reference numbers,generates indexesPrints the entire documentation in one run (e. g. at night)

Advantage:Convenient creation of documents

Layout template..............................................................................................................................................Reference numberProject

Layout template..............................................................................................................................................Reference numberProject

CompanyProject

2/5Company

Project1/5

Page 416: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Totally Integrated AutomationPage 14

Date: 05.12.2005File: PRO1_19E.14

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Runtime Software for Closed-loop Control Engineering Tasks

C7S7-400S7-300 M7S7-200

Standard PID Control

Fuzzy Control

Neuro Systems

Modular PID Control

Basic SW PID Control

PID Controller

FM 355 / 455

Confi-gura-tiontool

No

Yes

Yes

Yes

Yes

Yes

Yes

Overview

Basic SWoroptionpackage

Basic SW

Basic SW

Option

Option

Option

Option

Closed-loop In a closed-loop control system process variables are controlled in such a wayControl Engineering that they reach their new preset values as quickly as possible and that they maintain

these in spite of the effect of disturbances.

Basic Software The STEP 7 basic package already contains a series of function blocks forPID Control solving simple control engineering tasks.

Standard This additional package contains blocks and a parameter assignment tool withPID Control integrated control setting for standard tasks such as temperature controllers, flow rate

regulators, pressure regulators etc.

Modular Through the interconnection of supplied standard function blocks, you can PID Control implement just about every closed-loop control engineering structure, even in the upper

performance range of process engineering.The package contains 27 FBs and a commissioning tool.

Fuzzy Control Fuzzy Systems are used when the mathematic description of a process difficult or even impossible, when a process behaviour is not consistent, when non-linearities occur, but, on the other hand, experience with the process exists.

NeuroSystems Neuronal Systems are used with those problems, whose structure and solution are only partly known.NeuroSystems can be used in all automation levels, from the individual closed-loop controller to the optimization of a plant.

Closed-loop Control The closed-loop control modules FM355 (for S7-300) and FM455 (for S7-400)Modules are intelligent 4 and 16 channel modules for universal closed-loop control tasks in

chemical and process engineering, with rubber and plastics machinery, with heating and cooling units, in the glass, ceramic and paper industry, etc.

Page 417: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Totally Integrated AutomationPage 15

Borland C/C++ The control programs executed on an M7 automation computer can either be generated with CFC or with the integrated development environment Borland C/C++ V5.01. With Borland C/C++ , you can easily edit, compile and integrate C/C++ programs and,at the same time, you can access all project-specific configuration data and symbol data using STEP 7. Within Borland, all Borland C++ tools are available to you: AppExpert, ClassExpert, Project Management, Resource Workshop, Command Line Tools, etc.

M7- ProC/C++ The M7 ProC7C++ option software integrates the Borland C/C++ development environment in STEP 7 and also provides a real-time capable multitasking debugger.Moreover, the M7-ProC7C++, provides the configuration of the Borland development environment, so that no settings for path names for compiler and debugger and no settings for options of compiler and linker are necessary.

M7-SYS RT M7-SYS RT is the runtime system, optimized for the M7 automation computer, for implementing real-time tasks. With it, a powerful software base is available for the various tasks.M7-SYS RT includes in particular:• the real-time and multitasking operating system RMOS32 (32-Bit Real Time

Operating System)• a standard ANSI-C library• the M7-API user interface (Application Programming Interface)• interfaces for loadable drivers, as well as drivers for the serial interface

(e.g. 3964R) and TCP/IP drivers for Industrial Ethernet.

Date: 05.12.2005File: PRO1_19E.15

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Borland C/C++, M7- ProC/C++ and M7- SYS RT for M7-Automation Computers

Borland C/C++Creation of C/C++ programsfor M7

M7- ProC/C++Integration of Borland C/C++in STEP 7Powerful debugger foruser-friendly program testing

M7- SYS RTRMOS operating system

real-time capablemultitasking

Advantage:Technological functions can be programmedExtreme time-critical tasks

SIEMENS

PG 740

STEP7BorlandC/C++M7-ProC/C++

Cfor the computer pro M7-SYS RT

Page 418: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Totally Integrated AutomationPage 16

Date: 05.12.2005File: PRO1_19E.16

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Communicating with SIMATIC NET

Manage-ment level

Cell level

Field level

Actuator-sensorlevel

Industrial Ethernet

PROFIBUS

ActuatorSensor-Interface

SIMATIC NET SIMATIC NET is the name of an entire family of networks.• Industrial Ethernet according to IEEE 802.3 - the international standard for the networking of areas and cells• PROFIBUS according to EN 50170 - the international standard for the field area and the cell network with a limited number of nodes• AS-Interface - for communication with sensors and actuators.

Industrial Ethernet The Industrial Ethernet network is a cell level network according the international standard IEEE 802.3 (Ethernet) and is designed for industrial use. Extensive open network solutions are possible. A high transmission rate is guaranteed with various transmission media. Industrial Ethernet is an industry standard, world-wide tested and accepted. The Industrial Ethernet network functions according to the IEEE 802.3 standardized accessing procedure CSMA/CD (Carrier sense multiple access with collision detection).

Profibus PROFIBUS is the bus system for cell networks with a limited number of nodes. It is based on the European standard EN 50170, Volume 2, PROFIBUS. Since the requirements according to EN 50170 are fulfilled, PROFIBUS guarantees openness for the connection of components from other manufacturers that conform to standards. ThePROFIBUS accessing procedure functions according to the "Token Passing with subordinate Master-Slave" procedure. As a result, a distinction is made between active and passive network participants.

AS-Interface The AS-Interface is a networking system for binary sensors and actuators in the field area. With AS-Interface, binary actuators and sensors become capable of communication, for which a direct field bus connection was not technically possible up until now or was not economical.

Unlike the powerful PROFIBUS, the main area of use for the AS-Interface line is the transmission of small amounts of information such as from switching positions.

Page 419: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Totally Integrated AutomationPage 17

Overview For the SIMATIC S7, there is a field-proven HMI system for user-friendly process control and monitoring available, the SIMATIC HMI. It ranges from the simple textdisplay to the process visualization system.SIMATIC S7 and SIMATIC HMI are completely harmonized and integrated. This simplifies the use of the human-machine interface system SIMATIC HMI considerably.• SIMATIC S7 has already integrated HMI services. The HMI system

requests process data from the SIMATIC S7. Data transmission between SIMATIC S7 and SIMATIC HMI is carried out by the two operating systems and

does not have to be taken into account in the user program.SIMATIC HMI systems can be connected directly to PPI (S7-200) and MPI or Profibus (S7-300 and S7-400). Operation using PROFIBUS makes process control and monitoring even over greater distances possible.

• Numerous features from the uniform database and symbols up to the same user-friendly Windows-oriented user interfaces simplify the use of HMI systems.

Date: 05.12.2005File: PRO1_19E.17

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Process visualizationsystem

SIMATIC WinCC

SIMATIC Panels

Configuration andvisualization software

SIMATIC ProTool

Operator Control and Process Monitoring with SIMATIC HMI

Page 420: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Totally Integrated AutomationPage 18

ProTool SIMATIC ProTool and SIMATIC ProTool/Lite are modern configuration toolsProTool/Lite for configuring SIMATIC Text Displays, Operator Panels, Touch Panels as well as the

HMI portion of the SIMATIC C7 complete system.While you can configure all devices with SIMATIC ProTool, SIMATIC ProTool/Lite, as the economical version, is restricted to the configuration of line oriented devices.Functionally, SIMATIC ProTool/Lite is a subset of SIMATIC ProTool. The operator control and configuration philosophy of both tools is the same.

ProTool/Pro SIMATIC ProTool/Pro upwardly expands the existing product family of SIMATIC ProTool with the Operator Panel OP37/Pro and supplements the panels with a runtime software for a standard PC. ProTool/Pro contains the basic functionality of the graphic display units (OP27, OP37) and thus creates a visualization consistency from the existing graphic OPs up to the PC-based systems.ProTool/Pro stands out with the following features:• Runtime software for various platforms

- OP37/Pro (Windows 95) - Standard-PC (Windows 95/98 and NT 4.0)

• Extensive basic functionality of the graphic OP OP27, OP37• Expanded functional scope to OP27, OP37

Date: 05.12.2005File: PRO1_19E.18

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Text Display Panels

Graphic Display Panels

PC-based Systems

Consistent Configuration with SIMATIC ProTool

ProToolProTool//Lite Lite ProToolProTool

ProToolProTool/Pro/Pro

Page 421: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Totally Integrated AutomationPage 19

WinCC SIMATIC WinCC (Windows Control Center) is the open process visualization systemfrom Siemens. It can be integrated problem free in a new or already existing PLC system.

Function Modules The heart of SIMATIC WinCC is an industry and technology independent basic systemwith all the important functions for operator control and monitoring, such as:• pixel graphic display• measured value acquisition (archiving functions, data compression,

minimum and maximum values etc.)• message display, archiving and reporting• process communication to different PLC systems• standard interfaces, for example, Microsoft programs• documentation of machine and process sequences with individual reports.

Basis of WinCC WinCC is based on the 32-bit standard operating systems Windows 95/98 or Windows NT from Mircrosoft. This platform gives WinCC the following functionality:• use of the Windows operating equipment (printer, driver, etc.)• data exchange with other Windows applications via DDE, ODBC,

OLE and SQL.• API programming interface• use of hardware available in the market

Date: 05.12.2005File: PRO1_19E.19

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Process Visualization and Operator Control with WinCC

anzahl ()float zaebeginif wert > 0 begom zae = zae + 1 endend

Programmier-Schnittstellen

SPSKommunikation

Protokolle

Report Designer(Berichtssystem)

Tag Logging(Archivierung)

Ventil geschlossenKlappe zu

Motor ein

Alarm Logging(Meldesystem)

StandardSchnittstellen

Prozeßvisualisierung

Page 422: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Totally Integrated AutomationPage 20

Date: 05.12.2005File: PRO1_19E.20

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Process Automation with SIMATIC PCS 7

Engineering System Process terminal 1 Process terminal 2 Process terminal 3

Terminal bus

System bus

WinCC OS-ServerWinCC OS

S7-400 ascentral unit

Field devices

FM

SV DP

FM

SV DP

ET 200M

Introduction SIMATIC PCS 7 represents the new control system generation in SIEMENS. It is the consistent, further development and summary of the experiences with TELEPERM M, SIMATIC PCS and SIMATIC S5 based systems. As a result, it is tailored to the process control system tasks in all industries.

Engineering The Engineering System can be designed as its own station in the system. It System can however also be loaded as a software package in the OS components at the same

time.The Engineering System has the following components:• STEP 7 with the SIMATIC Manager, the central database, and with HW

Config for configuring hardware and networks. It also contains the servers, that facilitate consistent configuration between PLC and OS.• SCL (Structured Control Language) as PASCAL-similar higher level

programming language for block generation• CFC (Continuous Function Chart) for graphic configuration of the basic

automation functions• SFC (Sequential Function Chart) for graphic configuration of production

sequences• Expansion of the SIMATIC Manager with a technological hierarchical view• WinCC (Windows Control Center) for OS configuration• DOCPRO for documenting configuration data• Import–/Export wizard for bi-directional data exchange with other CAE

systemsThese components are supplemented by libraries that provide pre-defined blocks for PLC and OS.

Page 423: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1Totally Integrated AutomationPage 21

Totally Integrated The new SIMATIC family unifies all devices and systems, that is, hardware asAutomation well as software, into a uniform, powerful system platform.

In this platform, the system borders that have existed until now, that is, the borders between computer world, PLC world and process control, that is, between operator control and monitoring and control, between central and distributed automation are overcome.

Advantages This totally integrated automation offers you, among other things, the following advantages:• A scalable hardware platform, that is, the optimal (price/performance)

functionality (PLC or computer) can be chosen for the task to be solved.• An open totally integrated automation environment, that is, an existing

system can be easily extended, or existing or future automation solutions can be integrated.

Existing investments retain their value. The transition from an existing SIMATIC, TELEPERM or TI environment can be carried out very easily.

• Powerful software increases the productivity in the implementation of a project and thus reduces the engineering and life cycle costs. In addition, expenses for commissioning, maintenance and service are reduced.

• SIMATIC is based on Windows standards and can thus easily use their applications (standard software) and communication mechanisms.

Date: 05.12.2005File: PRO1_19E.21

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Summary

SIMATIC S7

WinCC PCS 7

Engi

neer

ing

NET

NETInstrum. Drives

M

Page 424: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1What’s Next?Page 1

We'd just like to say a few words...

Contents:

• What's Next ?

• Our Automation and Drives Training

• SIMATIC Training

• Systematic SIMATIC S5 Training

• Upgrade from SIMATIC S5 to SIMATIC S7

• SIMATIC S7 System Training

• SIMATIC S7-200 Training

• SIMATIC S7/M7 Option Packages

• SIMATIC NET

• SIMATIC WinCC

• PLC Technician

Date: 05.12.2005File: PRO1_20E.1

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

SIMATIC NET

SIMATIC HMI

SIMATIC M7

SIMATIC S5

and other courses on PCS7, IT, NC ....

What's Next ?

SIMATIC S7

Page 425: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1What’s Next?Page 2

What are the advantages of our SIMATIC Training for you?

• Fast, effective acquisition of knowledge

• Saves downtimes at your plant

• Ensures quality

• Gives you motivated personnel

• Simplifies and shortens decision-making processes

Note The following pages present just a sample of our extensive range of SIMATIC courses.

On the last page you‘ll find a fax form with the addresses of our course offices.We‘ll gladly send you information about our entire course spectrum !

Look us up in the Internet:http://www.ad.siemens.de/trainingor call our Info Line:Tel: 01805 23 56 11Fax: 01805 23 56 12

Date: 05.12.2005File: PRO1_20E.2

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Training from A&D

Our Automation and Drives Training

Training Courses on site or in200 locations in 60 countries

Future-oriented and Topical Trainingfirst handfrom the market leader

Task-oriented Trainingindividually decided with you

Training for everybody, in all areas ofAutomation and Drives

Page 426: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1What’s Next?Page 3

You have just attended one of our courses and we hope it came up to your expectations.

Above all, we hope you will be able to use the knowledge you obtained at the course to advantage in your work.

We would like to continue to be your partner in training for your career in the future.

For this reason we have outlined some of our current courses for you on the next few pages.

Date: 05.12.2005File: PRO1_20E.3

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

SIMATIC Training

SIMATIC S7

SIMATIC M7

SIMATIC HMI (COROS, ProTool, WinCC)

SIMATIC NET (PROFIBUS, Ethernet)

SIMATIC S5

Page 427: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1What’s Next?Page 4

Date: 05.12.2005File: PRO1_20E.4

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

SIMATIC S7

Upgrade SIMATIC S5 -> S7

ST-7UPPROG 5 days

Configuring/Programming

Good SIMATIC S5 knowledge andSIMATIC S5 programming

experiencePC and Windows knowledge

Upgrade from SIMATIC S5 to SIMATIC S7

ST-7UPPROG Upgrade SIMATIC S5 -> S7Course Contents - Overview of the SIMATIC S7, components, performance features(Excerpt): - The STEP7 programming language and its components

- Using block types and symbols for program structuring and program creation

- Test tools for system information, troubleshooting and diagnostics- Carrying out a hardware configuration of the modules- Communication via MPI interface- Integration of SIMATIC S5- Conversion of S5 programs

Page 428: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1What’s Next?Page 5

Date: 05.12.2005File: PRO1_20E.5

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

SIMATIC S7TroubleshootingST-7STOE 5 days

SIMATIC S7Programming 1ST-7PRO1 5 days

SIMATIC S7System HandlingST-7SYH 5 days

SIMATIC S7Programming 2ST-7PRO2 5 days

Installation/Maintenance

Basic knowledge of control engineering

SIMATIC S7 System Training

SIMATIC NETSIMATIC NET

SIMATIC S7 Option packages SIMATIC S7 Option packages

SIMATIC M7SIMATIC M7

SIMATIC HMISIMATIC HMI

Configuring/Programming

Technical training such as engineer, technician PC/Windows knowledge, Programming experience, Knowledge of digital technology

ST-7PRO1 SIMATIC S7 Programming 1Course Contents - System overview and main performance features(Excerpt): - The STEP7 programming language and its components

- Block types and symbols for program structuring and program creation - Test tools for system information, troubleshooting and diagnostics- Carrying out a hardware configuration of the modules- Communication via MPI interface

ST-7PRO2 SIMATIC S7 Programming 2Course Contents - Ability to use status bit dependent operations, accumulator operations and(Excerpt): expanded real number arithmetic

- Ability to use complex structures with parameters- Using indirect addressing in the program- Ability to integrate system functions (SFC) in the program- Ability to utilize communication function blocks (CFB)

ST-7SYH SIMATIC S7 System HandlingCourse Contents - Ability to configure and install a programmable logic controller(Excerpt): - Hardware and software commissioning of the programmable logic controller

- Overview of the S7-300 software configuration and parameter assignment

ST-7STOE SIMATIC S7 TroubleshootingCourse Contents - Using STEP 7 software for troubleshooting(Excerpt): - Detecting and eliminating software errors, that lead to the Stop state

- Diagnosing program errors with I STACK and B STACK- Troubleshooting in networked PLC systems

Page 429: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1What’s Next?Page 6

Date: 05.12.2005File: PRO1_20E.6

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

SIMATIC S7S7-200 WorkshopST-7MICRO 2 days

Basic knowledge of control engineering PC/Windows knowledge

Configuring/Programming and Installation/Maintenance

SIMATIC S7-200 Training

ST-7MICRO SIMATIC S7, S7-200 WorkshopCourse Contents - Becoming familiar with the performance features of the SIMATIC S7-200 PLCs(Excerpt): and programming devices

- Expansion facilities and addressing of the S7-200- Ability to structure, write, document and start up simple programs for controltasks on SIMATIC S7-200 PLCs

- Ability to use STEP7 Micro/WIN programming tools for program creation,documentation, program test and troubleshooting

Page 430: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1What’s Next?Page 7

Date: 05.12.2005File: PRO1_20E.7

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

SIMATIC M7Programming with CFCST-7CFC 2 days

SIMATIC S7 knowledge equivalent to ST-7PRO1

SIMATIC M7Programming with CST-7MC32 2 Days

SIMATIC M7ServiceST-7MSERV 3 days

PC/Windows knowledge

Programming engineers, Planning engineers and Commissioning engineers

SIMATIC M7System DesignST-7MSYS 3 days

C knowledge equivalent toIT-CKOMP or IT-CEIN

SIMATIC M7 System Training

ST-7MSYS SIMATIC M7, System DesignCourse Contents - Components of M7-300 and M7-400 (hardware and software)(Excerpt): - Interaction of S7 and M7

- Simple programming examples with C and CFC

ST-7MC32 C Programming Interface for M7Course Contents - RMOS API functions (excerpt)(Excerpt): - Priorities, multitasking, messages, ...

- M7 API functions (excerpt)- Access to process I/O, S7 server objects, interrupts, ...

ST-7MSERV SIMATIC M7, ServiceCourse Contents - Interaction of hardware and configuration (BIOS, STEP7)(Excerpt): - CPUs and FMs (properties, rules, limits)

- Standard Interface Modules- Function test and troubleshooting

ST-7CFC SIMATIC M7/S7, Graphic Programming with CFCCourse Contents - Programming tool for graphic programming of SIMATIC S7/M7(Excerpt): - Program configuration

- Interconnection of blocks- Programming user blocks in STEP7- Test and diagnostic facilities, documentation

Page 431: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1What’s Next?Page 8

Date: 05.12.2005File: PRO1_20E.8

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Programming the Inter-face Controller S7-300NC-S7APT 3 days

SIMATIC S7Sequential Control with S7-GRAPHST-7GRAPH 2 days

S7-GRAPHS7-GRAPH

SIMATIC S7HiGraph ProgrammingNC-ZSG 3 days

S7-HiGraphS7-HiGraph

SIMATIC S7Graphic Programming with CFCST-7CFC 2 days

CFCCFC

SIMATIC S7Programming with SCLST-7SCL 2 days

S7-SCLS7-SCL

SIMATIC S7 knowledge equivalent to the ST-7PRO1 or ST-7UPPROG courses

Configuring/Programming

SIMATIC S7/M7 Option Packages

ST-7GRAPH SIMATIC S7, Sequential Control with S7-GRAPHCourse Contents - Programming sequencers(Excerpt): - Program creation with S7-GRAPH

- Comparison of GRAPH 5 to S7-GRAPH- Test and diagnostic facilities, program documentation

NC-S7APT Programming Interface Controller S7-300Course Contents - Overview of the controllers FMNC, 810D and 840D(Excerpt): - Structure of the PLC - NC interface

- Fast data exchange between PLC and NC- Communication structures- Practical exercises on the individual topics

NC-ZSG HIGRAPH Programming SIMATIC S7Course Contents - Programming machine controllers with HiGRAPH. (Excerpt): - Programming tools and their use

- Test and diagnostic facilities- Program documentation, exercises

ST-7SCL SIMATIC S7, Programming with SCLCourse Contents - S7-SCL high level language for SIMATIC S7 controllers(Excerpt): - S7-SCL tools

- Program structure, language structure and program commands- Test and diagnostic facilities, exercises

ST-7CFC SIMATIC M7/S7, Graphic Programming with CFCCourse Contents - Programming tool for graphic programming of SIMATIC S7/M7(Excerpt): - Program configuration

- Interconnection of blocks- Programming user blocks in STEP7- Test and diagnostic facilities, documentation

Page 432: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1What’s Next?Page 9

Date: 05.12.2005File: PRO1_20E.9

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

SIMATIC S7/M7Communication PROFIBUS-FMSKO-7KFMS 2 days

SIMATIC S7Communication with Industrial EthernetKO-7KETHER 3 days

SIMATIC S7Point-to-Point ConnectionST-7PTP 2 days

SIMATIC S7Distributed I/O PROFIBUS-DPKO-7KDP 2 days

SIMATIC S7 knowledge equivalent to the ST-7PRO1 or ST-7UPPROG courses

Configuring/Programming

SIMATIC S7Communicationwith PROFIBUSKO-7KPROFI 4 days

SIMATIC NET

ST-7PTP SIMATIC S7, Point-to-Point ConnectionCourse Contents - Performance features and technical specifications of CP340 and CP441(Excerpt): - Creating configuration and parameter assignments of the communication

processors- Writing user programs for CP340 and CP441- Diagnostic facilities of CP340 and CP441

KO-7KDP SIMATIC S7, PROFIBUS-DPCourse Contents - Structure and functional principle of distributed I/O(Excerpt): - Planning and configuring the DP-Master in SIMATIC S7

- User programming and diagnostic facilities

KO-7KFMS SIMATIC S7, PROFIBUS-FMSCourse Contents - FMS mode of operation(Excerpt): - Configuration software NCM for PROFIBUS

- Programming FMS applications- Diagnostic and test facilities

KO-7KPROFI SIMATIC S7, PROFIBUS-DP/FMSContents of the KO-7KDP and KO-7KFMS courses

KO-7KETHER SIMATIC S7, Industrial EthernetCourse Contents - Mode of operation, properties and components of the Industrial Ethernet bus(Excerpt): system

- ISO and TCP/IP protocols- Configuration using the configuration software NCM-S7 for IndustrialEthernet

- Diagnostic functions

Page 433: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1What’s Next?Page 10

ST-BWINCCS SIMATIC WinCC, WorkshopCourse Contents - WinCC system overview(Excerpt): - Windows 95 (settings), using the standard Windows interfaces

- Creating a project, PLC connections, variable simulation, graphics- Message display, message archiving- Trend display, measured value archiving, user archives- Report system, background processing (Global Scripts)- API open user interface (use and structure)- Practical exercises

ST-BWINCCE SIMATIC WinCC Open System ECourse Contents - Introduction to the WinCC- system architecture (open interfaces and(Excerpt): integration capability, databases, channel DLL, Global Scripts), introduction to

Visual C++, ODK (development environment for API), WinCC-API structuring,using API functions,

- Practical exercises

ST-BWINCCN SIMATIC WinCC Open System NCourse Contents - Brief introduction to the WinCC- system architecture (open interfaces and(Excerpt): integration capability, databases, channel DLL), general introduction to

Global Scripts, accessing WinCC databases with Excel, OLE functions- Practical exercises

Date: 05.12.2005File: PRO1_20E.10

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

SIMATIC WinCCOpen System NST-BWINCCN 1 day

SIMATIC WinCCOpen System EST-BWINCCE 2 days

C knowledge, basic knowledge of

relational databases

Good knowledge of C,Win95/NT knowledge,

Experience with graphic interfaces,e.g. Windows 95/NT

Configuring/Programming

SIMATIC WinCCHuman-Machine Interface, System Training ST-BWINCCS 5 days

SIMATIC WinCC

Page 434: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1What’s Next?Page 11

Date: 05.12.2005File: PRO1_20E.11

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

SIMATIC S7PC Based Control with WinACST-7WINAC 2 days

SIMATIC ProTool/ProProTool/Pro WorkshopST-BPROPRS 3 days

SIMATIC ProTool/ProUpgrade ProTool -> ProTool/ProST-BPROPRU 2 days

SIMATIC S7 knowledge equivalent to the ST-7PRO1 or ST-7UPPROG courses

Experience with graphic interfaces,e.g. Windows 95/NT

Configuring/Programming

SIMATIC - New Courses for 1998/99

ST-7WINAC SIMATIC S7, PC Based Control with WinACCourse Contents - Introduction to PC based control with SIMATIC WinAC(Excerpt): - WinAC hardware components, properties, components

- Use of data-OCX and supplied OCXs- Assigning parameters to the MPI card- Overview of OPC / ActiveX / DCOM for WinAC

ST-BPROPRS SIMATIC ProTool/Pro WorkshopCourse Contents - SIMATIC ProTool/Pro system overview(Excerpt): - Basics of graphic screen creation

- User functions (introduction to VBScript)- Message configuration, message display, message archiving- Trend configuration, trend display, measured value archiving

ST-BPROPRU Upgrade SIMATIC ProTool -> ProTool/ProCourse Contents - Expansions of ProTool/Pro when compared with ProTool(Excerpt): - Graphic screen creation

- User functions- Message archiving and measured value archiving

Page 435: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1What’s Next?Page 12

Date: 05.12.2005File: PRO1_20E.12

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Actuator-Sensor-InterfaceBasic CourseKO-ASIG 1 day

Actuator-Sensor-InterfaceAdvanced CourseKO-ASIA 1 day

SIMATIC S5 and/or SIMATIC S7 knowledge and basic knowledge of data communication

Planning, Programming, and Commissioning engineers, Installation, Maintenance and Service personnel

Actuator-Sensor-Interface - New Courses for 1998/99

KO-ASIG Actuator-Sensor-Interface, Basic CourseCourse Contents - Basics of the Actuator-Sensor-Interface (AS-Interface)(Excerpt): - Structure and configuration

- AS-i Master, supply cables, power supply unit, control and signal modules,motor starter, consumer branch circuits,...

- Diagnostic facilities

KO-ASIA Actuator-Sensor-Interface, Advanced CourseCourse Contents - Function blocks and handling blocks for the extended operation of the Master(Excerpt): modules

- In-depth knowledge of system components- PROFIBUS DP/AS-Interface transitions- Service and diagnosis with SCOPE S1 for AS-Interface

Page 436: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1What’s Next?Page 13

Date: 05.12.2005File: PRO1_20E.13

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

OLE for Process ControlBasic CourseKO-OPC 2 days

S7/PC Communicationvia LAN with TCP/IPKO-S7TCPL 1 day

Internet Communicationof SIMATIC S7KO-S7INTER 1 day

Basic knowledge of data communication / local networks

Planning engineer, Commissioning engineer and User

SIMATIC NET - New Courses for 1998/99

KO-OPC OLE for Process Control, Basic CourseCourse Contents - OPC goals and background(Excerpt): - OLE basics (architecture of the NET software)

- Installation of the NET hardware and software components- Implementation example based on the SIMATIC NET OPC products- S7-OPC Server- DP-OPC Server

KO-S7TCPL S7/PC Communication via LAN with TCP/IPCourse Contents - Industrial Ethernet mode of operation and networking components(Excerpt): - The Internet protocol family

- Comparison of ISO/OSI and TCP/IP- The transport protocols TCP and UDP- TCP/IP with SIMATIC NET

KO-S7INTER Internet Communication of the SIMATIC S7Course Contents - Internet origins and technology(Excerpt): - Using the Internet in automation technology

- Safety concepts- SIMATIC S7 in the Internet - world-wide access for commissioning,testing and maintenance

Page 437: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1What’s Next?Page 14

System Courses System trainingService trainingCompact courses for engineersProgramming courses

Supplementary Project planning/configuringCourses Sequential control with GRAPH 5

Fail-safe and fault-tolerant systems

Digital control engineeringSoftware-based closed-loop controlPositioning with IP246/266

Point-to-point connectionsL1 bus communicationSIMATIC S5, PROFIBUSCP 5431 FMS workshop S5-95/PROFIBUS workshop SIMATIC S5, Industrial Ethernet

Course Contents For full details of the contents of these courses please refer to our ITC catalog. You can obtain this catalog through your trainer or order it yourself from the Course Office direct (see last page for address and fax form).Alternatively you can obtain information via:Internet: http://www.ad.siemens.de/trainingInfo Line: Tel: 01805 23 56 11

Fax: 01805 23 56 12

Date: 05.12.2005File: PRO1_20E.14

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

SIMATIC S5 - System and Supplementary Courses

Basic knowledge of control engineering

Planning engineer/Programming engineer, Installation and Maintenance personnel

SIMATIC S5Service TrainingST-S5SERV 5 days

SIMATIC S5Programming 1ST-S5PRG1 5 days

SIMATIC S5System Training Part 2ST-S5SYS2 5 days

SIMATIC S5System Training Part 1ST-S5SYS1 5 days

SIMATIC S5 - Supplementary Courses

Page 438: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1What’s Next?Page 15

Qualification for Our structured training course for PLC technicians is based on the requirementsPLC Technicians of the VDMA/ZVEI 1).

These requirements define what a skilled PLC technician needs to know and be able to do, regardless of the brand of PLC and from the point of view of the user. Training can take the form of:• distance learning, • evening courses or • daytime courses.

Trainees can take an examination at the end of this training sequence. This normally takes one day and consists of a theory section and a practical section.For further information, please see our ITC catalog or the special information sheet about training for PLC technicians.

1) Association of German Machine and Plant Manufacturers (VDMA)Association of the Electrical and Electronics Industry (ZVEI)

Upgrade PLC technicians who have completed their training with SIMATIC S5 can obtain a further qualification in an upgrade course dealing with the differences between SIMATIC S5 and SIMATIC S7.

Date: 05.12.2005File: PRO1_20E.15

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

PLC Technician SIMATIC S5 and SIMATIC S7

SIMATIC S7PLC Programmer(based on SIMATIC S7)ST-SPSPROF 8 Wochen

SIMATIC S7PLC Technician (based on SIMATIC S7)ST-SPSTEF 6 months

Installation/Maintenance and Service personnel

Evening training course according to VDMA/ZVEI

SIMATIC S5PLC Technician (based on SIMATIC S5)ST-SPSTEA5 14 weeks

SIMATIC S7Upgrade S5 -> S7 ST-7UPSPS 14 weeks

SIMATIC S7PLC Technician (based on SIMATIC S7)ST-SPSTEA7 14 weeks

Distance learning

Page 439: siemensCourse ST-7PRO1

Training Centerfor Automation and Drives

ST-7PRO1What’s Next?Page 16

Now it‘s your turn ...

Date: 05.12.2005File: PRO1_20E.16

SIMATIC S7Siemens AG 1999. All rights reserved.

Information and Training CenterKnowledge for Automation

Still have questions ?

We‘ll help you!

... with the info-line:Tel 01805 23 56 11Fax 01805 23 56 12

... in the Internet:www.ad.siemens.de/training