significant changes and amendments - columbia, missouri...requirements as dictated in the irc. this...
TRANSCRIPT
Significant Changes and Amendments
Permit Posting
R202 Definitions
Structure: Add exception for existing decks being replaced the same size will not be considered a structure for zoning (setback/yard)purposes.
R106.2 Site Plan
By amendment--Projects where more than two single family dwellings, multiple duplexes, and/or townhomes on one lot shall require commercial civil/site documents per IBC 107.2.5 and must be sealed by a professional engineer licensed in the state of Missouri.
Sunrooms-referenced standards Manufacturer’s specifications required to verify;
Smoke Alarms in Alterations-Amendments
R314.4 Add to exception, “In alterations smoke alarms shall not be required to be interconnected if the dwelling is no more than 2 stories.”
R314.6 Add exception #3, “Smoke alarms in
alterations shall be permitted to be battery operated if the dwelling is no more than 2 stories.”
Guards Adjacent to Fixed Seating
Site Address—R319 Characters must be 4” minimum.
Numbers shall not be spelled out.
Where access is by means of a private road and the
building address cannot be viewed from the public way, a monument, pole or other sign or means shall be used to identify the structure.
R403.1.6 R403.1.6-- Add to the end of the section just before the exceptions; The connection of the foundation walls to floors shall be per the alternatives labeled 1.1, 1.2, 1.3, 1.4, 2.1, 2.1, 3.1, 3.2, or 4.
Alternative 1.1
Alternative 1.2
Alternative 1.3
Alternative 1.4
Alternative 2.1
Alternative 2.2
Alternative 3.1
Alternative 3.2
Alternative 4
R404 Retaining Walls in Excess of 48” Retaining walls that are not laterally supported at the top and that retain in excess of 48” of unbalance fill, or retaining walls exceeding 24” in height that resist lateral loads in addition to soil, shall be designed in accordance with accepted engineering practice. Exception: Walls integral to the house foundation meeting the parameters of Alternative 4.
Retaining Wall Failures
Table R602.3(5)— Size, Height and Spacing of Wood Studs
The process for determining whether wall studs, a wall,
or a story must be engineered based on wall height now checks:
1. Table R602.3(5) Limits laterally unsupported wall height to 10 feet. 2. Section R602.10 (Wall bracing), and if necessary 3 . Section 602.3.1, Exception 2
602.3.1-Stud size, height and spacing Exception 2 Section R602.3.1 Amend as follows: Where snow loads are less than or equal to 25 pounds per square foot, and the ultimate design wind speed is less than or equal to 130 mph, 2-inch by 6-inch studs supporting a roof load with not more than 6 feet of tributary length shall have a maximum height of 18 feet where spaced at 16 inches on center, or 20 feet where spaced at 12 inches on center. Studs shall be a minimum No. 2 grade lumber. Alternatively 2-inch by 6-inch No. 2 grade studs supporting a roof and floor load with not more than 10 foot of tributary length shall have a maximum stud height of 14 feet.
Prescriptive Energy Compliance
R-10 Rigid Insulation Required at Slab Foundation-Protection of Insulation must extend 6” below grade (N1101.11.1)
Slab R-Value & Depth—Zone 4 Equivalent U-Factors
Slab Insulation Methods
Slab Insulation Protection If a monolithic slab and foundation is being used, the required insulation would obviously need to be installed on the exterior and then either extended to the required depth OR turned out to the exterior and be protected either by some type of pavement or a minimum of 10 inches of soil.
Slab Insulation Protection Protection of exposed foundation insulation. Insulation applied to the exterior of the slab on grade floors shall have a rigid, opaque and weather resistant covering to prevent the degradation of the insulation’s thermal performance. The protective covering shall extend not less than 6 inches below grade.
Easy does It !!!!
N1102.1.5—Total UA Alternative—Thermal Envelope
If the total building thermal envelope UA (sum of U-factor times assembly area) is less than or equal to the total UA resulting from using the U-factors in Table 1102.1.4 (multiplied by the same assembly area as in the proposed building), the building shall be considered in compliance with Table N1102.1.2.
Total UA alternative-Cont. The UA calculation shall be done using a method consistent with the ASHRAE Handbook of Fundamentals and shall include the thermal bridging effects of framing materials. The SHGC requirements shall be met in addition to UA compliance. (REScheck may be used w/Certified home energy rater) This allows significant design flexibility.
Accepted third party analysis HERS Index and Energy Codes HERS-Home Energy
Rating System Certified Residential Energy Services Network Rater Design Professional Registered in the State of Missouri
Calculations must be submitted for approval
Energy Efficiency Certificate
Appendix U-Solar Ready Requirements Applies to new detached one and two family dwellings and townhouses with not less than 600 square foot of roof area oriented between 110 degrees and 270 degrees of true north. U103.3 Solar Ready Zone Area. The total solar ready zone area shall
be not less than 300 square feet. Townhouses less than 2,000 square feet the zone may be reduced to 150 square feet. The zone shall be composed of areas not less than 5 feet in width and not less than 80 square feet.
U103.4 Solar ready zones shall be free from obstructions—including but not limited to vents, chimneys, roof mounted equipment, dormers.
U103.5 Roof load requirements are met when built to IRC for our
zone.
Solar Ready Requirements-Cont. U103.6 Construction documents shall indicate pathways for routing
of conduit to the electrical service panel.
U103.7 The main electrical service panel shall have reserved space to allow installation of a dual pole circuit breaker-shall be labeled---“For Future Solar Electric”--- The reserved space shall be positioned at the opposite end from the input feeder location or main circuit location.
U103.8 A permanent certificate indicating the solar ready zone and other requirements shall be posted.
Reaction so far?
Solar Ready Provisions-Solar Ready Zone
IMPORTANT DISTINCTION Residential Building. For this code , includes detached
one- and two-family dwellings and multiple single family dwellings (townhouses) as well as group R-2, R-3 and R-4 buildings three stories or less in height above grade plane.
This means buildings meeting this definition will be required to meet the same residential energy efficiency requirements as dictated in the IRC. This will include duct and air leakage rate testing. The residential energy codes requirement diagram may be used for compliance. Solar ready provisions must be met.
Pressure Test Gauges must 100 psi max at the highest end of the scale.
Several fairly significant electrical code provisions/amendments. 210.8 Ground-Fault Circuit-Interrupter Protection for Personnel. Deletions. The following requirements for GFCI-protection have been deleted by ordinance from the 2014 NEC: Kitchen dishwashers in dwelling units Kitchen appliances, such as garbage disposals or
refrigerators, located within 6-feet of dwelling unit sinks.
Dwelling unit laundry areas, e.g. clothes washers.
210.17 Electrical Vehicle Branch Circuit. Outlets installed for the sole purpose of charging electric vehicles shall be supplied by a separate, individual branch circuit, having no other outlets.
210.52 (G)(1) Receptacles in Garages. In each attached garage, and in each detached garage with electric power, at least one receptacle shall be installed for each car space.
230.28 Overhead Service Conductors. Service Masts Used as
Supports. (B) Attachment. Service-drop or overhead service conductors shall not be attached to a service mast between a weather-head and a coupling, where the coupling is located above the last point of securement to the building, or is located above the building.
Very Significant Change NEC 250.104(B) Bonding of Metal Piping Systems and
Exposed Structural Metal. Corrugated Stainless Steel Tubing (CSST, or Wardflex/Gastite), gas piping systems shall be bonded to the electrical service grounding electrode system. The bonding jumper shall connect to a metallic pipe or fitting between the point of delivery and the first downstream CSST fitting. The bonding jumper shall not be smaller than 6 AWG copper wire or equivalent, and shall not be more than 75 feet in length. Gas piping systems that contain one or more segments of CSST shall be bonded in accordance with this section.
Bonding Diagram
Last One !!!!! 690.12 Rapid Shut-down of PV Systems on
Buildings. New requirement for a ‘Kill-Switch’ for PV systems on building roofs, so that PV source circuits will be de-energized from all sources within 10 seconds of when the utility supply is interrupted, or when the PV disconnecting means is opened.
This incorporates a significant improvement in
safety for roof top PV systems based on the safety concerns of the first and second responders of the emergency and fire service communities.
PV Rapid Shutdown Diagram
Thanks for All You Do!!