simple, cost effective and easy to ... - thorn lighting · simple, cost effective and easy to...

20
SensaModular Simple, cost effective and easy to install for single-room lighting control

Upload: others

Post on 15-Sep-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Simple, cost effective and easy to ... - Thorn Lighting · Simple, cost effective and easy to install for single-room lighting control. 2 Introduction 1 2 3 Thorn’s Indoor Lighting

SensaModularSimple, cost effective and easy to install for single-room lighting control

Page 2: Simple, cost effective and easy to ... - Thorn Lighting · Simple, cost effective and easy to install for single-room lighting control. 2 Introduction 1 2 3 Thorn’s Indoor Lighting

2

Introduction

1 2 3

Thorn’s Indoor Lighting Controls portfolio is grouped into three distinct usage types

2. SensaModular is a portfolio of lighting control products designed for single room applications. The ‘modular’ concept allows customers to build-up a set of components tailored specifically to their needs:

• Users can select modules for creating light scenes, enabling daylight-linking, integrating presence detection, switching, scene setting and infra-red control

• Just the components needed are taken and connected to, up to three groups of dimmable luminaires via a controller

1. SensaLite features Thorn luminaires with built-in sensors and remote sensors, offering standard presence detection, daylight-linking and infra-red control. SensaLite is the first step to comfort and energy saving, and is used for small office applications, simple classrooms, corridors etc:

• SwitchLite consists of switching presence detectors and photocells

• RotaryDIM offers precise manual control via a wall plate

• SensaDigital covers both features: Daylight-linked dimming, presence detection and manual override via an infra-red handheld controller

3. SensaAdvanced is a lighting management system for larger projects and those requiring greater levels of comfort:

• For all types of dimmable or switchable ballasts or lamps

• Daylight and Presence link

• Integration of blinds, screens and room partitions

• Different user interfaces like touch panels, wall units or PC

• Scene setting

• Time and Dynamic management

• A/V interface

Page 3: Simple, cost effective and easy to ... - Thorn Lighting · Simple, cost effective and easy to install for single-room lighting control. 2 Introduction 1 2 3 Thorn’s Indoor Lighting

3

What is SensaModular?

iX connection for up to 8 devices (sensors, scene plates, switch inputs, 1 photo cell)

SensaModular controllerwith 3 luminaire outputs(DSI or DALI)

Infra-red handheldcontroller

Scene Plate

Standard double or single momentary action switches to dim/brighten luminaire groups

Photo cell (max. 1)

Multi-sensor

Multi-sensor

ScSceneene PPPllalattee tttt

Unlike traditional dimmer pack or building-wide solutions, it is a simple, cost effective modular solution capable of saving time and labour for all indoor single-room applications with two or three luminaire groups. Its modularity is based on the controller which interfaces with various combinations of scene plates, sensors, switches and receivers to operate groups of luminaires, thus offering users flexibility and comfort with the reassurance that all components integrate fully with each other.

Key benefits are:

1 Different ways of presence linking, allowing SensaModular to be adapted to the required detection pattern, and different operation modes.

2. Three methods of daylight-linking, making it easy to tailor SensaModular to the application, especially in terms of size, usage and ceiling height.

3. Scene setting via: Scene plate, Infra-red handheld control or Switch input device.

4. DSI/DALI auto detection outputs (patented) for controlling luminaire groups, the large SensaModular controller allows three digital outputs, the small controller two.

5. Easy installation via polarity-free 2-wire connections, using standard mains rated installation material.

SensaModular is for everyone looking for a versatile product that is easy to install and understand

Page 4: Simple, cost effective and easy to ... - Thorn Lighting · Simple, cost effective and easy to install for single-room lighting control. 2 Introduction 1 2 3 Thorn’s Indoor Lighting

SensaModular evokes the spirit of Thorn Lighting’s dynamic, results-orientated PEC programme

Performance, Efficiency and Comfort (PEC) – for a better lit environment

The programme is based on the principle that Performance, Efficiency and Comfort determine the effectiveness of lighting, its impact on the people using it, and its impact on the natural environment. SensaModular delivers the right light on the right place at the right time.

Performance: Providing the best visual effectiveness

• Dimming and Scene setting gives flexibility of the lighting configuration, therefore SensaModular ensures good task lighting wherever the task is.

Efficiency: Conserving energy and effort, reducing CO2 emissions and waste, providing lighting that is practical and efficient to install, operate and maintain.

• Presence-link conserves energy by ensuring unnecessary lighting is turned off.

• Daylight-link conserves energy by ensuring the task is lit to the correct level and not over lit, irrespective of the source of light.

• Maintenance control is provided with the SensaModular multi-sensors, i.e. constant task illuminance is given throughout the maintenance cycle of the lighting, conserving energy and easing the maintenance requirements.

• Polarity-free connections make SensaModular quick and easy to install with reduced possibility of errors.

• There are two screwdriver adjustable rotary switches on the front of the controller, which will set the operation mode and off delay time for the presence-link function. This makes commissioning quick, easy and safe being operated from the ground.

• SensaModular gives us a lighting system we can manage effectively and ensures that the whole lighting performs as designed.

Comfort: giving people satisfaction and stimulation

• Personalised light, either with dimming or with scene setting, allows the ambience of the space to be altered to suit the usage requirements.

• SensaModular allows the variability of the light through time, giving a more interesting and stimulating environment.

4

Page 5: Simple, cost effective and easy to ... - Thorn Lighting · Simple, cost effective and easy to install for single-room lighting control. 2 Introduction 1 2 3 Thorn’s Indoor Lighting

5

Energy saving potential

0%-7%

-22%

-42%

-55%

-71%

-61%

-82%

Fluorescent lampand conventional

ballast

Baseline Savings potential

Milestones to energy conservation with modern lighting

Fluorescent lampand low-loss

ballast

Fluorescent lampand electronic

ballast

Fluorescent lampand dimmable

electronic ballast

Fluorescent lampand dimmable

electronic ballast

Manual dimming

Daylight-link

Presence-link

System with T26fluorescent lamps

System with T16fluorescent lamps

The CELMA (Federation of National Manufacturers Associations for Luminaires and Electrotechnical Components for Luminaires in the European Union) highlights the potential energy savings that dimmable electronic ballasts, day-light link and presence-link offer, as shown in the picture above. SensaModular allows the realisation of these energy savings in every single room indoor lighting application.

By conserving energy we give better value for money whilst saving global resources

Page 6: Simple, cost effective and easy to ... - Thorn Lighting · Simple, cost effective and easy to install for single-room lighting control. 2 Introduction 1 2 3 Thorn’s Indoor Lighting

6

Key Benefit - Tailored-fit presence-link

Using one SensaModular multi-sensor per luminaire group

• The SensaModular multi-sensors provide a presence-link function that may be allocated to the luminaire groups individually.

• This option is perfect for applications with zoned lighting, e.g. group offices, and considers the recommendations regarding presence-link stated in EN 15193, asking for zoned presence-link in applications larger than 30m².

Using one SensaModular multi-sensor for all luminaire groups

• This option provides a presence-link function for all luminaire groups connected to the SensaModular controller, and is ideal in small applications where daylight-link and infra-red control are required.

Using one SwitchLite presence detector for all luminaire groups

• Any standard 230 VAC presence detector, e.g. one of the Thorn SwitchLite portfolio, can be used as an alternative to the SensaModular multi-sensors. This can be connected to the dedicated “PD” input of the controller and is allocated to all luminaire groups.

• This option is perfect for any application requiring a different detection pattern to that of the SensaModular multi-sensor, for instance corridors and staircases, and also for applications where no daylight-link and infra-red control is needed.

The most expensive light is the one that is still on in unoccupied rooms or areas. SensaModular enables you to automatically conserve energy whenever people are absent, allowing you to choose between three options:

Page 7: Simple, cost effective and easy to ... - Thorn Lighting · Simple, cost effective and easy to install for single-room lighting control. 2 Introduction 1 2 3 Thorn’s Indoor Lighting

7

Presence- and absence-link (On/Off mode) Lighting is switched On whenever a person is detected by a connected sensor, and is slowly faded to Off, after a set Off delay time, as soon as the sensor detects absence. If several sensors are used then SensaModular will delay fading to Off until all of the sensors have reported absence.

Absence-link (only Off mode) Lighting is slowly faded to Off, after a set Off delay time, as soon as a connected sensor detects absence. If several sensors are used then SensaModular will delay fading to Off until all of the sensors have reported absence. The lighting will never be switched On automatically in this mode and will have to be activated manually, using the scene plate, the momentary action switches or the infra-red handheld control.

Presence-linked Corridor scene (On/Corridor mode) Lighting is switched on whenever a person is detected by a connected sensor, and is slowly faded to a lower corridor illuminance level, after a set Off delay time, as soon as the sensor detects absence. If several sensors are used then SensaModular will delay fading to the corridor illuminance level until all of the sensors have reported absence. The corridor illuminance level is set to 10% light output for all luminaires.

Deactivated presence-link SensaModular allows all connected presence detectors or the presence-link function of all connected SensaModular multi-sensors to be deactivated. This mode also helps when the SensaModular installation is commissioned.

Off Delay time After detecting absence SensaModular will wait for a configurable Off time delay before fading to the absence setting specified with the set operation mode. This time delay can be between 0 seconds and 1 hour.

Note: If a standard presence detector (e.g. SwitchLite) is used, its own Off Delay time is added to that set on the SensaModular controller.

Staircase function By connecting a standard momentary action switch to the SensaModular controller’s presence detector input, a ‘staircase’ function can be realised. Activating the momentary action switch announces presence and the lighting is switched On. After the set Off delay time the lighting is faded to Off, if the operation mode is set to On/Off, or alternatively faded to a corridor illuminance level of 10%, if the mode is set to On/Corridor.

The SensaModular control unit features two inbuilt rotary switches that allow the user to determine the desired operation mode and Off Delay time for the presence-link function. These are easily and quickly set using a screwdriver

On/Off

onlyOffPD

On/Corridor

PD Mode

On/Off

onlyOffPD

On/Corridor

PD Mode Off Delay (min)

0 0.5

1

5

101520

30

45

60 0 0.5

1

5

101520

30

45

60

On/Off

onlyOffPD

On/Corridor

PD Mode

On/Off

onlyOffPD

On/Corridor

Off Delay (min)

On/Off

onlyOffPD

On/Corridor

PD Mode

PD Mode

On/Off

onlyOffPD

On/Corridor

PD Mode

On/Off

onlyOffPD

On/Corridor

PD Mode Off Delay (min)

0 0.5

1

5

101520

30

45

60 0 0.5

1

5

101520

30

45

60

On/Off

onlyOffPD

On/Corridor

PD Mode

On/Off

onlyOffPD

On/Corridor

Off Delay (min)

On/Off

onlyOffPD

On/Corridor

PD Mode

PD Mode

On/Off

onlyOffPD

On/Corridor

PD Mode

On/Off

onlyOffPD

On/Corridor

PD Mode Off Delay (min)

0 0.5

1

5

101520

30

45

60 0 0.5

1

5

101520

30

45

60

On/Off

onlyOffPD

On/Corridor

PD Mode

On/Off

onlyOffPD

On/Corridor

Off Delay (min)

On/Off

onlyOffPD

On/Corridor

PD Mode

PD Mode

On/Off

onlyOffPD

On/Corridor

PD Mode

On/Off

onlyOffPD

On/Corridor

PD Mode Off Delay (min)

0 0.5

1

5

101520

30

45

60 0 0.5

1

5

101520

30

45

60

On/Off

onlyOffPD

On/Corridor

PD Mode

On/Off

onlyOffPD

On/Corridor

Off Delay (min)

On/Off

onlyOffPD

On/Corridor

PD Mode

PD Mode

On/Off

onlyOffPD

On/Corridor

PD Mode

On/Off

onlyOffPD

On/Corridor

PD Mode Off Delay (min)

0 0.5

1

5

101520

30

45

60 0 0.5

1

5

101520

30

45

60

On/Off

onlyOffPD

On/Corridor

PD Mode

On/Off

onlyOffPD

On/Corridor

Off Delay (min)

On/Off

onlyOffPD

On/Corridor

PD Mode

PD Mode

On/Off

onlyOffPD

On/Corridor

PD Mode

On/Off

onlyOffPD

On/Corridor

PD Mode Off Delay (min)

0 0.5

1

5

101520

30

45

60 0 0.5

1

5

101520

30

45

60

On/Off

onlyOffPD

On/Corridor

PD Mode

On/Off

onlyOffPD

On/Corridor

Off Delay (min)

On/Off

onlyOffPD

On/Corridor

PD Mode

PD Mode

Page 8: Simple, cost effective and easy to ... - Thorn Lighting · Simple, cost effective and easy to install for single-room lighting control. 2 Introduction 1 2 3 Thorn’s Indoor Lighting

8

Key Benefit - Tailored-fit daylight-link

Using one ‘look down’ sensor per luminaire group

For daylight-linking one multi-sensor per luminaire group is installed on the ceiling, aimed at the working plane to register the light level.

Advantages:

• Supports the recommendations stated in EN 15193, which ask for daylight-linking of zones smaller than 30m2, thus resulting in a good rating of the installation for ‘building passport’ purposes

• Maintains illuminance despite aging of lamps and dirt on luminaires.

• Ideal for larger, zoned applications, like group offices.

• SensaModular multi-sensor heads combine daylight with presence linking and infra-red control.

Points to consider:

• Measures daylight and artificial light reflected from desktop – therefore influenced by reflecting material and colour.

• Several sensors needed (one per luminaire group), therefore more obtrusive.

• Impact of overlapping detection zones.

Using one ‘look down’ sensor for all luminaire groups

For the daylight-linking of smaller rooms, e.g. a single office or meeting room, one multi-sensor for all luminaire groups is installed on the ceiling, aimed at the working plane to register the light level.

Advantages:

• For applications not requiring zoned areas, visual and physical intrusion on the ceiling is kept to a minimum as only one sensor is needed to register the flow of daylight for up to three individually controlled luminaire groups.

• Maintains illuminance despite aging of lamps and dirt on luminaires.

• The SensaModular multi-sensor head combines daylight with presence-linking and infra-red control.

Points to consider:

• Measures daylight and artificial light reflected from one local desktop – therefore influenced by reflecting material and colour.

• Does not consider the recommendations stated in EN 15193 in applications larger than 30m².

Using one ‘look out’ photocell for all luminaire groups

For daylight-linking one photocell sensor is installed on the ceiling and aimed in the direction of the window to register incoming daylight.

Advantages:

• Visual and physical intrusion on the ceiling is kept to a minimum as only one sensor is needed to register the flow of daylight for up to three individually controlled luminaire groups.

• With only daylight to register measurements are precise, thus maximising daylight saving potential.

• Ideal for applications with luminaire rows and/or ceiling heights of more than 3m, or where zoned presence-link is not required, e.g. classrooms, industrial or sports halls.

Points to consider:

• Does not consider aging of lamps and luminaires becoming dirty.

• SensaModular photocell does not provide presence-linking and infra-red control.

0% 25% 50%

Artificial lightDaylight

500lux

0% 25% 50%

500lux

Artificial lightDaylight

0% 25% 50%

500lux

Artificial lightDaylight

Page 9: Simple, cost effective and easy to ... - Thorn Lighting · Simple, cost effective and easy to install for single-room lighting control. 2 Introduction 1 2 3 Thorn’s Indoor Lighting

9

Key Benefit - Scene setting

Infra-red handheld controlThe SensaModular infra-red handheld controller allows the setting and recalling of three scenes and the Off scene. The whole lighting can be dimmed and brightened via a rocker key, or after using the pre-selection buttons the luminaire groups can be dimmed individually. This device is also used to allocate the SensaModular multi-sensors to the luminaire groups. For the reception either the SensaModular multi-sensors or (if these are not planned in) the SensaModular infra-red sensors can be used.

No application is used for only one activity or task: Therefore SensaModular allows a user to set scenes and to adapt the lighting to the different tasks.

Scene plateWith the wall recessed SensaModular scene plate three scenes as well as the Off scene can be set and recalled. The active scene is visualised with indicator LEDs integrated into the keys. Three pairs of keys are used to dim and brighten the luminaire groups individually and a further pair allow all luminaires to be dimmed or brightened. The scene plate has a brass front in satin steel finish, matching back boxes are available as accessories.

Switch input deviceAs an alternative to the wall-recessed scene plate, standard momentary action switches can be used in conjunction with the SensaModular switch input device to recall three scenes and the Off scene.

Page 10: Simple, cost effective and easy to ... - Thorn Lighting · Simple, cost effective and easy to install for single-room lighting control. 2 Introduction 1 2 3 Thorn’s Indoor Lighting

10

Key Benefit - DSI/DALI auto detection

SensaModular uses DSI/DALI auto detection luminaire outputs (patented), and allows you to connect either:

• Luminaires with electronic ballasts showing DSI (Digital Serial Interface) controllability, e.g. Thorn HFD luminaire versions

• Luminaires with DALI (Digital Addressable Lighting Interface) controllability, e.g. Thorn HFX luminaire versions

• One ballast type, either DSI or DALI, can be connected to each controller output (see table for permitted configurations and quantities)

Every luminaire output of a SensaModular controller will check, individually, the type of ballasts used and automatically adapt its control “language”.

• When wiring the system, the two or three groups of HFD or HFX luminaires are allocated to the momentary action switches for direct manual control = plug & play.

• One intelligent interface (‘iX’ connection) is used for all user interfaces and sensors, e.g. multi-sensor heads or photocell, infra-red sensor, scene plate, momentary action switch input.

• There is no extra commissioning tool required.

• The infra-red handheld controller is used to allocate the multi-sensors to the luminaire groups.

• Regarding installation material; installers benefit from polarity-free connections and the possibility to use standard mains rated wiring.

DSI or DALI wiring, iX wiring

• Polarity-free

• Standard mains wiring, e.g. H05VV-U 2 x 1.5mm² and H05VV-U 2 x 0.75mm²

• For maximum lengths see table below

• Wiring typologies: tree, star, line, radial.

Key Benefit - Easy to Install

Output Grp1 Grp2

HFD luminaires only 50 DSI 50 DSI

HFX luminaires only 25 DALI 25 DALI

HFD or HFX luminaires 25 DSI or DALI 25 DSI or DALI

Output Grp1 Grp2 Grp3

HFD luminaires only 50 DSI 50 DSI 50 DSI

HFX luminaires only 25 DALI 25 DALI 25 DALI

HFD or HFX luminaires 25 DSI or DALI 25 DSI or DALI 25 DSI or DALI

Maximum number of ballasts connected to ‘SensaMod-2DIG’ controller

Maximum number of ballasts connected to ‘SensaMod-3DIG’ controller

Note: A DSI amplifier is available as accessory to increase the number of connectable DSI ballasts (DSI-V, 20975705).

Wire diameter

Maximum length iX and DALI wires

Maximum length DSI wires

2 x 0.5mm² 100m 125m2 x 0.75mm² 150m 125m2 x 1.0mm² 200m 125m2 x 1.5mm² 300m 250m

Page 11: Simple, cost effective and easy to ... - Thorn Lighting · Simple, cost effective and easy to install for single-room lighting control. 2 Introduction 1 2 3 Thorn’s Indoor Lighting

11

How to plan a SensaModular installation

• How are the luminaire groups arranged – in zones (e.g. using recessed louvre luminaires) or in rows (e.g. using suspended linear luminaires)?

• How high is the ceiling?

• Is daylight available and daylight-linking possible?

• Is presence-link also required?

Based on the answers to these questions you decide to select either:

• the SensaModular multi-sensors,

• or the SensaModular photocell perhaps combined with a SwitchLite presence detector.

Now choose any additional modular items:

• Do you want to set scenes? (Note: Scene 1 would be the daylight-linked one).

• If yes, would you prefer:

- The SensaModular Scene Plate, that allows you to brighten and dim the luminaire groups individually and jointly, and to set and recall three scenes plus Off? It also indicates the active scene. This plate is perfect for meeting rooms, retail applications and much more.

- Or an Infra-red handheld control? This would be optimal in any office application. (Note: If you have not chosen a multi-sensor head above, then you will need a Infra-red Sensor as well.)

- Or standard momentary action switches for recalling scenes? These would interface via the SensaModular Switch Input into the system.

The ‘cascading’ diagram below helps you evaluate and chart possible outcomes when seeking the benefits of energy saving and comfort

Com

fort

Ener

gy

Savi

ng

Daylight linked?

Presence linked? Presence linked? Presence linked? Presence linked?

Yes YesNo No

Zones (and ceiling height max. 3m)

Rows in parallel with window (or ceiling higher than 3m)

Multi-sensors (look down)

Multi-sensors (look down, PD)

Multi-sensors (look down)

Photocell (look out)

SwitchLite presence detector

Photocell (look out)

SwitchLite presence detector

Via infra-red handheld control?

Remote Control *

Via wall mounted plate? Via standard switches?

Scene Plate Input for standard switches

Luminaire grouping chosen for application?

ComfortEnergy Saving

Scene setting?

Yes YesYes YesNo NoNo No

Yes Yes Yes

* plus Infra-red Sensor ifno Multi-sensor is used

Page 12: Simple, cost effective and easy to ... - Thorn Lighting · Simple, cost effective and easy to install for single-room lighting control. 2 Introduction 1 2 3 Thorn’s Indoor Lighting

12

Application example - Group Office

Group 3: DSI or DALI out

Group 2: DSI or DALI out

Group 1: DSI or DALI out

L N

Group 1 Group 2 Group 3

Group 1 Group 2 Group 3

Optional

iX Intelligentconnection for sensorsand scene setting devices

Description of application:

Example: Graphic design agencyNumber of users: < 15Size: < 100m²Activities: PC work, desk work, break, cleaningArea of activity: Zone within an area, e.g. a working team’s

desk clusterLuminaire layout: Arranged in three zones, with a group of

recessed luminaires above each desk clusterCeiling height: 2.8m

Needs and requirements

• Light level per zone adaptable to activities

• Saving Energy

• Easy to install and to commission, no need for a specialist or training

Solution

• Multi-sensors detect presence/absence and dim/brighten light according to incoming daylight

• Individual manual dimming is provided via momentary action switches, or optional infra-red handheld controller, to override a zone’s light level if needed

• Infra-red handheld controller used to allocate multi-sensors to the luminaire groups

• Detection mode and Off delay set via rotary switches, illuminance levels programmed via infra-red handheld controller, or via momentary action switch temporarily connected to ‘lux’ input of SensaMod-3DIG.

• Standard mains wiring only, polarity-free DSI/DALI and sensor wires

One of three zones

Page 13: Simple, cost effective and easy to ... - Thorn Lighting · Simple, cost effective and easy to install for single-room lighting control. 2 Introduction 1 2 3 Thorn’s Indoor Lighting

13

Application example - Classroom

L N

iX Intelligentconnection for sensors and scene setting devices

All groups

Presence detectorallocated to all groups

Group 1 Group 2

Group 2: DSI or DALI out

Group 1: DSI or DALI out

Description of application

Example: Primary schoolNumber of users: < 25Size: < 70m²Activities: Lessons, breaks, cleaningArea of activity: RoomLuminaire layout: Arranged in rows, two groups,

parallel to the windowCeiling height: 3m

Needs and requirements

• Saving energy

• Vandal resistant operation, optionally ‘protected’

• Easy to use (especially in shared or ‘public’ rooms)

• Easy to install and to commission, no need for a specialist or training

Solution

• Lighting is linked to the incoming daylight using 1 photocell (looking towards the window) for all luminaire groups

• Wall mounted passive infra-red or unobtrusive Microwave presence detector for all luminaire groups, e.g. one of Thorn’s SwitchLite portfolio

• Manual switching and dimming via standard ‘key operated’ double momentary action switches to override light levels if needed (keys for teachers, facility manager, cleaner)

• Detection mode and Off delay set via rotary switches, illuminance level programmed either via push button built into photocell, or via momentary action switch temporarily connected to ‘lux’ input of SensaMod-2DIG

• Standard mains wiring only, polarity-free DSI/DALI and photocell wires

Page 14: Simple, cost effective and easy to ... - Thorn Lighting · Simple, cost effective and easy to install for single-room lighting control. 2 Introduction 1 2 3 Thorn’s Indoor Lighting

14

Description of application

Example: Swimming pool without large windowsNumber of users: < 50Size: < 500m²Activities: Public swimming, competition, cleaningArea of activity: HallLuminaire layout: Arranged in rows, three groups Ceiling height: 5 to 10m

Needs and requirements

• Light level adaptable to different activities

• Saving energy

• Easy to use

• Easy to install and to commission, no need for a specialist or training

Solution

• A scene plate allows the setting and selection of 3 scenes, thus matching the lighting to the different activities taking place. Light levels can be overridden individually if required.

• Standard mains wiring only, polarity-free DSI/DALI and scene plate wires

Application example - Sports Hall

Group 3: DSI or DALI out

Group 2: DSI or DALI out

Group 1: DSI or DALI out

L N

iX Intelligentconnection forsensors andscene setting devices

Page 15: Simple, cost effective and easy to ... - Thorn Lighting · Simple, cost effective and easy to install for single-room lighting control. 2 Introduction 1 2 3 Thorn’s Indoor Lighting

15

Product details

22154742 SensaMod-3DIGDigital output unit for controlling three luminaire groups, with three control outputs for DSI or DALI compatible lamp control gears (auto detection). Up to 25 DALI or 50 DSI ballasts per output channel are connected via a polarity-free two-wire connection using standard mains rated wiring. Dimming range 1 to 100% (depending on ballasts). The unit shows an intelligent input for the connection of multi-sensors, infra-red sensors, a photocell, scene plates and switch input devices (max. 8 devices in parallel) via a polarity-free two-wire connection using standard mains rated wiring. Additionally standard single or double momentary action switches can be connected to switch, dim and brighten the luminaire groups individually; standard mains rated presence detectors can be connected to link all luminaire groups to presence. Two rotary switches to set presence detection mode and Off delay time. All connections made via screw-terminals. Status LED and test button. Housing made of flame-retardant polycarbonate, halogen free, for installation into distribution cabinets on 35mm DIN rail, according to EN 50022, IP20 degree of protection, ambient temperature 0 to 50°C. Width 140mm (8 units), height 90mm, depth 59mm. Weight 650g.

22154741 SensaMod-2DIGDigital output unit for controlling two luminaire groups, with two control outputs for DSI or DALI compatible lamp control gears (auto detection). Up to 25 DALI or 50 DSI ballasts per output channel are connected via a polarity-free two-wire connection using standard mains rated wiring. Dimming range 1 to 100% (depending on ballasts). The unit shows an intelligent input for the connection of multi-sensors, infra-red sensors, a photocell, scene plates and switch input devices (max. 8 devices in parallel) via a polarity-free two-wire connection using standard mains rated wiring. Additionally standard single or double momentary action switches can be connected to switch, dim and brighten the luminaire groups individually; standard mains rated presence detectors can be connected to link both luminaire groups to presence. Two rotary switches to set presence detection mode and Off delay time. All connections made via screw-terminals. Status LED and test button. Housing made of flame-retardant polycarbonate, halogen free, for installation into distribution cabinets on 35mm DIN rail, according to EN 50022, IP20 degree of protection, ambient temperature 0 to 50°C. Width 70mm (4 units), height 90mm, depth 59mm. Weight 350g.

22154744 SensaX-MULTISENSORMulti-sensor for presence-link, daylight-link and integration of infra-red handheld controllers. Presence-link via passive infra-red sensor, circular detection pattern at 2.5(3)m ceiling height is diameter 6(7)m for seated persons, and diameter 7(9)m for persons in motion. Daylight-link is realised with sensor looking down at task area, measuring the daylight as well as the artificial light reflected from the task area. Connected to and supplied by central control device via a polarity-free two-wire connection using standard mains rated wiring. Either semi-recessed into single Euro ceiling back box, diameter 60mm, or surface-mounted onto ceiling or fully recessed into suspended ceiling (cut out diameter 92mm) with accessory rings provided, mounting height 3m max. Connection made via screwless push-in terminals. Green status LED behind lens for indication. Housing made of flame-retardant polycarbonate, white (RAL 9003), lens made of high density polyethylene, both halogen free. IP40 degree of protection, ambient temperature 0 to 50°C. Weight 50g.

Page 16: Simple, cost effective and easy to ... - Thorn Lighting · Simple, cost effective and easy to install for single-room lighting control. 2 Introduction 1 2 3 Thorn’s Indoor Lighting

16

22154745 SensaX-IRSENSORInfra-red sensor for integration of infra-red handheld controllers. Connected to and supplied by central control device via a polarity-free two-wire connection using standard mains rated wiring. Either semi-recessed into single Euro ceiling back box, diameter 60mm, or surface-mounted onto ceiling or fully recessed into suspended ceiling (cut out diameter 92mm) with accessory rings provided. Connection made via screw less push-in terminals. Status LED behind lens for indication. Housing made of flame-retardant polycarbonate, white (RAL 9003), lens made of high density polyethylene, both halogen free. IP40 degree of protection, ambient temperature 0 to 50°C. Weight 50g.

22154746 SensaX-DAYSENSORPhotocell for daylight-link. Daylight-link is realised with sensor looking from ceiling towards window, measuring the daylight entering a room. Connected to and supplied by central control device via a polarity-free two-wire connection using standard mains rated wiring. Surface-mounted onto ceiling. Connection made via screw-terminals. Status LED behind lens for indication. Integrated test and program button. Housing made of flame-retardant polycarbonate, white (RAL 9003), halogen free. IP20 degree of protection, ambient temperature 0 to 50°C. Weight 40g.

22154743 SensaX-IRCONTROLInfra-red hand held controller for setting and recalling three scenes and Off scene. Controller includes one On/Off key, three scene keys, one dimming rocker key and five keys for pre-selection of luminaire groups. The whole lighting can be dimmed and brightened via the rocker key, or after using the pre-selection keys the luminaire groups can be dimmed and brightened individually. Device additionally used for allocation of multi-sensors to luminaire groups. Status LED for indication. Supplied by 2 batteries type AAA, included. Range up to 10m, IR protocol RSTEP, 38kHz. Housing made of ABS, halogen-free, wall-mounting bracket included, ambient temperature 0 to 40°C.

22154747 SensaX-SCENEScene plate for setting and recalling three scenes and Off scene. Active scenes visualised with indicator LEDs integrated into the keys. Four pairs of keys for dimming and brightening luminaire groups individually as well as jointly. Connected to and supplied by central control device via a polarity-free two-wire connection using standard mains rated wiring. Front plate made of brass in satin steel finish, hiding screws after installation. Wall recessed into back boxes, available as accessories. Connection made via detachable plug with screw-terminals. Connection of protective earth via separate screw-terminal. IP20 degree of protection, ambient temperature 0 to 50°C. Width 145mm, height 86mm. Depth without plate 25mm, depth of plate 4mm. Weight 350g.

Page 17: Simple, cost effective and easy to ... - Thorn Lighting · Simple, cost effective and easy to install for single-room lighting control. 2 Introduction 1 2 3 Thorn’s Indoor Lighting

17

96233754 RBOX2 PS CONTROLITEBack box plastic (polystyrene, halogen-free) 2-gang for the wall recessed installation of the SensaX-SCENE scene plate. Suitable for flush fitted installation into cavity walls. Outside dimensions 134x74mm, depth 36mm (without rim and clamps).

96233752 RBOX2 ST CONTROLITEBack box stainless steel 2-gang for the wall recessed installation of the SensaX-SCENE scene plate. Suitable for flush fitted concealed installation into brick or concrete walls. Outside dimensions 134x74mm, depth 28mm.

22162242 SensaX-4SWITCHSwitch input device to recall three scenes and the Off scene, or alternatively to switch, dim and brighten three luminaire groups individually and jointly, via volt-free standard momentary action switches. Connected to and supplied by central control device via a polarity-free two-wire connection using standard mains rated wiring. Connection of up to four volt-free momentary action switches, switch function, scene recall or group dimming and brightening, set via built-in rotary switch. Recessed into back box behind switches. Connection made via pre-connected wires, length approx. 30cm. Housing made of flame-retardant polycarbonate, transparent, halogen free. IP20 degree of protection, ambient temperature 0 to 50°C. Diameter 53mm, height 13mm. Weight 100g.

22154307 PDAX 500VAPhase dimmer/Reverse phase dimmer (automatic load detection) with DSI interface, controllable via SensaModular output, for continuous dimming of ohmic light sources, LV halogen lamps with magnetic or electronic transformers. A total connected load of 40 to 500VA can be operated. Dimming range 1 to 100%. Connection via screw terminals, housing made of flame-resistant polycarbonate, halogen-free, suited for ceiling recess, ambient temperature 0 to 60°C (max. 300VA)/0 to 45°C (max. 500VA). IP20 degree of protection. Length 167mm, width 42mm, height 31mm. Weight 200g.

Page 18: Simple, cost effective and easy to ... - Thorn Lighting · Simple, cost effective and easy to install for single-room lighting control. 2 Introduction 1 2 3 Thorn’s Indoor Lighting

18

22154306 PDAS 1000VAPhase dimmer/Reverse phase dimmer (automatic load detection) with DSI interface, controllable via SensaModular output, for continuous dimming of ohmic light sources, LV halogen lamps with magnetic or electronic transformers. A total connected load of 40 to 1000VA can be operated. Dimming range 1 to 100%. Connection via screw terminals, housing made of flame-resistant polycarbonate, halogen-free, suitable for installation in switch or distribution cabinets on 35mm DIN rail. Ambient temperature 0 to 40°C. IP20 degree of protection. Width 105mm (6 units), height 90mm, depth 59mm. Weight 400g.

86457873 TE one4all sc 105VADigital, dimmable transformer with DSI/DALI interface; controllable via SensaModular output (identified as DALI ballast), dimming range of 1 to 100%; for operation of 12V low voltage tungsten-halogen lamps with a lamp power of between 20 and 105VA; lamp leads up to 2m; housing made of flame-resistant polycarbonate, halogen-free; suitable for ceiling recess; protection class II; ambient temperature -25 to +60°C. Length 167mm, width 42mm, height 31mm. Weight 180g.

86457874 TE one4all sc 150VADigital, dimmable transformer with DSI/DALI interface; controllable via SensaModular output (identified as DALI ballast), dimming range of 1 to 100%; for operation of 12V low voltage tungsten-halogen lamps with a lamp power of between 50 and 150VA; lamp leads up to 2m; housing made of flame-resistant polycarbonate, halogen-free; suitable for ceiling recess; protection class II; ambient temperature -20 to +50°C. Length 207mm, width 46mm, height 40mm. Weight 290g.

20975705 DSI-VDigital device for amplifying the DSI signal, enables connection of 50 additional DSI compatible operating devices, like digital electronic ballasts, phase dimmers or electronic transformers, to the DSI output of SensaModular after the maximum number of DSI ballasts has been reached. The DSI load of the DSI-V is equivalent to the load of 2 DSI ballasts. Serial connection of up to 5 amplifiers possible. DSI input and output. Connections made with push-in terminals; housing made of flame-resistant polycarbonate, halogen-free, suitable for ceiling-recess, IP20 degree of protection, protection class II with fitted terminal covers, ambient temperature 0 to 60°C.

Page 19: Simple, cost effective and easy to ... - Thorn Lighting · Simple, cost effective and easy to install for single-room lighting control. 2 Introduction 1 2 3 Thorn’s Indoor Lighting

19

Ordering Guide

Description Weight Kg SAP code

SensaModular DSI/DALI Output 3x and 2x

SENSAMOD-3DIG 0.65 22154742

SENSAMOD-2DIG 0.35 22154741

SensaModular multi-sensor, infra-red sensor and photocell

SENSAX-MULTI-SENSOR 0.05 22154744

SENSAX-IRSENSOR 0.05 22154745

SENSAX-DAYSENSOR 0.04 22154746

SensaModular Infra-red Handheld Control

SENSAX-IRCONTROL 0.09 22154743

SensaModular Scene Plate and back boxes, polystyrene and steel

SENSAX-SCENE 0.35 22154747

RBOX2 PS CONTROLITE 0.06 96233754

RBOX2 ST CONTROLITE 0.16 96233752

SensaModular 4-fold scene or group switch input

SENSAX-4SWITCH 0.10 22162242

Accessories: DSI phase/reverse phase dimmers, auto load detection, 40-500VA and 40-1000VA

PDAX 500VA 0.20 22154307

PDAS 1000VA 0.40 22154306

Accessories: DSI/DALI electronic transformers, 12V, 20-105VA and 50-150VA

TE ONE4ALL SC 105VA 0.18 86457873

TE ONE4ALL SC 150VA 0.29 86457874

Accessory: DSI amplifier for 50 additional DSI loads

DSI-V 0.15 20975705

Further DSI out

Further 50 DSI out

FurtherDALI out

DSI in DSI out

DSI in load out

PDAX/PDAS

DSI-V

DALI in load out

TE one4all

Connecting Accessories

Ordering guide

Page 20: Simple, cost effective and easy to ... - Thorn Lighting · Simple, cost effective and easy to install for single-room lighting control. 2 Introduction 1 2 3 Thorn’s Indoor Lighting

Lighting people and places

Thorn Lighting is constantly developing and improving its products. All descriptions, illustrations, drawings and specifications in this publication present only general particulars and shall not form part of any contract. The right is reserved to change specifications without prior notification or public announcement. All goods supplied by the company are supplied subject to the company’s General Conditions of Sale, a copy of which is available on request. All measurements are in millimetres and weights in kilograms unless otherwise stated.

Publication No: 397 (IS) Publication Date: 02/10

Thorn Lighting Main OfficesThorn Academy of Light Green Lane Industrial Estate, Spennymoor County Durham DL16 6HL, UK Tel: (44) 1388 420 042 E-mail: [email protected] Website: www.thornacademyoflight.com

AustraliaThorn Lighting Pty Limited 43 Newton Road, Wetherill Park NSW 2164 Tel: (02) 8786 6000 Fax: (02) 9612 2700 E-mail: [email protected] Website: www.thornlighting.com.au

AustriaThorn Licht GmbH Donau-City-Straße 1, 1220 Wien, Austria Tel: (43) 1 202 66 11 Fax: (43) 1 202 66 11 82712 E-mail: [email protected] Website: www.thornlighting.at

ChinaThorn Lighting (Guangzhou) Operations Ltd, No.12 Lian Yun Road, Eastern Section, GETDD, Guangzhou 510530, China Tel: (86) 20 3228 2706 Fax: (86) 20 3228 1777 E-mail: [email protected]

Thorn Lighting (Tianjin) Co. Ltd 332 Hongqi Road, Tianjin 300190, China Tel: (86) 22 8369 2303 Fax: (86) 22 8369 2302 E-mail: [email protected]

Czech Republic Thorn Lighting CS spol. s.r.o., Na Březince 6/930, 150 00 Praha 5 Czech Republic Tel: (420) 224 315 252 Fax: (420) 233 326 313 E-mail: [email protected] Website: www.thornlighting.cz

DenmarkThorn Lighting A/S Kanonbådsvej 12B, Holmen, 1437 København K, Denmark Tel: (45) 76 96 36 00 Fax: (45) 76 96 36 01 E-mail: [email protected] Website: www.thornlighting.dk

FranceThorn Europhane SA 156 Boulevard Haussmann, Cedex 08, Paris 75379, France Tel: (33) 1 49 53 6262 Fax: (33) 1 49 53 6240 Website: www.thornlighting.fr

Hong Kong Thorn Lighting (Hong Kong) Limited Unit 4301, Level 43, Tower 1, Metroplaza,223 Hing Fong Road, Kwai Chung, N.T., Hong Kong Tel: (852) 2578 4303 Fax: (852) 2887 0247 E-mail: [email protected]

IndiaThorn Lighting India Pvt. Ltd. 501, 5th Floor, Tanishka Opp. Gundecha Industrial Estate Akurli Road, Kandivali (E), Mumbai – 400 101, India Tel: (91) 22-67839100 Fax: (91) 22-67839106 E-mail: [email protected] Website: www.thornlighting.com

International Sales Thorn Lighting Limited Silver Screens, Elstree Way, Borehamwood, Hertfordshire, WD6 1FE, UK Tel: (44) 20 8732 9800 Fax: (44) 20 8732 9819 E-mail: [email protected] Website: www.thornlighting.com

Ireland Thorn Lighting (Ireland) Limited Century House Harolds Cross Road Dublin 6W Tel: (353) 1 4922 877 Fax: (353) 1 4922 724 E-mail: [email protected] Website: www.thornlighting.co.uk

ItalyThorn Europhane Spa Via G Di Vittorio, 2, Cadriano di Granarolo, Bologna 40057, Italy Tel: (39) 051 763391 Fax: (39) 051 763088 E-mail: [email protected] Website: www.thornlighting.it

New ZealandThorn Lighting (NZ) Ltd 399 Rosebank Road, Avondale, Auckland 1026 PO Box 71134, Rosebank, Auckland 1348 Tel: (64) 9 828 7155 Fax: (64) 9 828 7591 E-mail: [email protected] Website: www.thornlighting.co.nz

NorwayThorn Lighting AS Strømsveien 344, 1081 Oslo, Norway Tel: (47) 22 82 07 00 Fax: (47) 22 82 07 01 E-mail: [email protected] Website: www.thornlighting.no

PolandThorn Lighting Polska Sp.z.o.o., Ul. Gazowa 26A, Wrocław 50-513, Poland Tel: (48) 71 7833 740 Fax: (48) 71 3366 029 E-mail: [email protected] Website: www.thornlighting.pl

RussiaThorn Lighting Novoslobodskaya Str., 21, office 406 Business Center “Novoslobodskaya 21”, Moscow 127030, Russia Tel: (7) 495 981 35 41 Fax: (7) 495 981 35 42 E-mail: [email protected] Website: www.thornlighting.ru

Singapore Thorn Lighting (Singapore) Pte Ltd 5 Kaki Bukit Crescent, 04-02 Koyotech Building, 416238 Singapore Tel: (65) 6844 5800 Fax: (65) 6745 7707 E-mail: [email protected]

SwedenThorn Lighting AB Industrigatan, Box 305, SE-261 23 Landskrona, Sweden Tel: (46) 418 520 00 Fax: (46) 418 265 74 E-mail: [email protected] Website: www.thornlighting.se

United Arab EmiratesThorn Lighting Ltd Dubai Al Shoala Building, Office 301, Block E, Airport road, P.O. Box 1200, Deira, Dubai, UAE Tel: (971) 4 2940181 Fax: (971) 4 2948838 E-mail: [email protected] Website: www.thornlighting.com

Thorn Gulf LLC Al Shoala Building, Office 301/2, Block E, Airport road, P.O. Box 22672, Deira, Dubai, UAE Tel: (971) 4 2948938 Fax: (971) 4 2948838 E-mail: [email protected] Website: www.thornlighting.com

United Kingdom Thorn Lighting Limited Silver Screens, Elstree Way, Borehamwood, Hertfordshire, WD6 1FE, UK Tel: (44) 20 8732 9800 Fax: (44) 20 8732 9801 E-mail: [email protected]

Thorn Olympics Sports Lighting Team Tel: 07785 251 438 E-mail: [email protected] Website: www.thornlighting.co.uk

www.thornlighting.com