siprotec 5 v7.00 and higher overcurrent … 5 v7.00 and higher overcurrent protection 7sj82/7sj85...

154
SIPROTEC 5 V7.00 and higher Overcurrent Protection 7SJ82/7SJ85 Technical Data Extract from manual C53000-G5040-C017-6, chapter 11 Energy Automation

Upload: hoangdieu

Post on 29-Apr-2018

234 views

Category:

Documents


1 download

TRANSCRIPT

SIPROTEC 5 V7.00 and higherOvercurrent Protection 7SJ82/7SJ85

Technical Data

Extract from manual C53000-G5040-C017-6, chapter 11

Energy Automation

iiNOTE

For your own safety, observe the warnings and safety instructions contained in this document, if available.

Disclaimer of LiabilityThis document has been subjected to rigorous technicalreview before being published. It is revised at regular inter-vals, and any modifications and amendments are includedin the subsequent issues. The content of this documenthas been compiled for information purposes only. AlthoughSiemens AG has made best efforts to keep the documentas precise and up-to-date as possible, Siemens AG shallnot assume any liability for defects and damage whichresult through use of the information contained herein.This content does not form part of a contract or of businessrelations; nor does it change these. All obligations ofSiemens AG are stated in the relevant contractual agree-ments.Siemens AG reserves the right to revise this documentfrom time to time.Document version: C53000-G5040-C017-6.01Edition: 11.2015Version of the product described: V7.00 and higher

CopyrightCopyright © Siemens AG 2015. All rights reserved.The disclosure, duplication, distribution and editing of thisdocument, or utilization and communication of the contentare not permitted, unless authorized in writing. All rights,including rights created by patent grant or registration of autility model or a design, are reserved.Registered TrademarksSIPROTEC®, DIGSI®, SIGUARD®, SIMEAS®, and SICAM®

are registered trademarks of Siemens AG. Any unauthor-ized use is illegal. All other designations in this documentcan be trademarks whose use by third parties for their ownpurposes can infringe the rights of the owner.

Preface

Purpose of the ManualDocument

This manual describes the protection, automation, control, and supervision functions of the SIPROTEC 5device functions for distance protection and line differential protection.This document describes a single protection, automation, control, or supervision function of the SIPROTEC 5device functions. The document shall thus be considered as part of the main device manual.

Target Audience

Protection system engineers, commissioning engineers, persons entrusted with the setting, testing and main-tenance of automation, selective protection and control equipment, and operational crew in electrical installa-tions and power plants.

Scope

This manual applies to the SIPROTEC 5 device family.

Further Documentation

[dwprefdm-221012-01.tif, 3, en_US]

• Device manualsEach Device manual describes the functions and applications of a specific SIPROTEC 5 device. Theprinted manual and the online help for the device have the same informational structure.

• Hardware manualThe Hardware manual describes the hardware building blocks and device combinations of theSIPROTEC 5 device family.

SIPROTEC 5, Overcurrent Protection, Manual 3C53000-G5040-C017-6, Edition 11.2015

• Operating manualThe Operating manual describes the basic principles and procedures for operating and assembling thedevices of the SIPROTEC 5 range.

• Communication protocol manualThe Communication protocol manual contains a description of the protocols for communication withinthe SIPROTEC 5 device family and to higher-level network control centers.

• Product informationThe Product information includes general information about device installation, technical data, limitingvalues for input and output modules, and conditions when preparing for operation. This document isprovided with each SIPROTEC 5 device.

• Engineering GuideThe Engineering Guide describes the essential steps when engineering with DIGSI 5. In addition, theEngineering Guide shows you how to load a planned configuration to a SIPROTEC 5 device and updatethe functionality of the SIPROTEC 5 device.

• DIGSI 5 online helpThe DIGSI 5 online help contains a help package for DIGSI 5 and CFC.The help package for DIGSI 5 includes a description of the basic operation of software, the DIGSI princi-ples and editors. The help package for CFC includes an introduction to CFC programming, basic exam-ples of working with CFC, and a reference chapter with all the CFC blocks available for the SIPROTEC 5range.

• SIPROTEC 5/DIGSI 5 TutorialThe tutorial on the DVD contains brief information about important product features, more detailed infor-mation about the individual technical areas, as well as operating sequences with tasks based on prac-tical operation and a brief explanation.

• SIPROTEC 5 catalogThe SIPROTEC 5 catalog describes the system features and the devices of SIPROTEC 5.

• Selection guide for SIPROTEC and ReyrolleThe selection guide offers an overview of the device series of the Siemens protection devices, and adevice selection table.

Indication of Conformity

This product complies with the directive of the Council of the European Communi-ties on harmonization of the laws of the Member States relating to electromagneticcompatibility (EMC Council Directive 2004/108/EC – valid until April, 19th of 2016,EMC Council Directive 2014/30/EU – valid from April, 20th of 2016) and concerningelectrical equipment for use within specified voltage limits (Low Voltage Directive2006/95/EG – valid until April, 19th of 2016, Low Voltage Directive 2014/35/EU –valid from April, 20th of 2016).This conformity has been proved by tests performed according to the Council Direc-tive in accordance with the product standard EN 60255-26 (for EMC directive) andwith the product standard EN 60255-27 (for Low Voltage Directive) by Siemens AG.The device is designed and manufactured for application in an industrial environ-ment.The product conforms with the international standards of IEC 60255 and theGerman standard VDE 0435.

Other Standards

IEEE Std C 37.90The technical data of the product is approved in accordance with UL.For more information about the UL database, see www.ul.comSelect Online Certifications Directory and enter E194016 as UL File Number.

Preface

4 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

IND. CONT. EQ.69CA

[ul_listed_c_us, 1, --_--]

Additional Support

For questions about the system, please contact your Siemens sales partner.

Support

Our Customer Support Center provides a 24-hour service.

Phone: +49 (180) 524-7000Fax: +49 (180) 524-2471E-Mail: [email protected]

Training Courses

Inquiries regarding individual training courses should be addressed to our Training Center:

Siemens AGSiemens Power Academy TD Humboldtstraße 5990459 NürnbergGermany Phone: +49 (911) 433-7415Fax: +49 (911) 433-7929E-Mail: [email protected]: www.siemens.com/poweracademy

Notes on Safety

This document is not a complete index of all safety measures required for operation of the equipment(module or device). However, it comprises important information that must be followed for personal safety, aswell as to avoid material damage. Information is highlighted and illustrated as follows according to the degreeof danger:

! DANGERDANGER means that death or severe injury will result if the measures specified are not taken.

² Comply with all instructions, in order to avoid death or severe injuries.

! WARNINGWARNING means that death or severe injury may result if the measures specified are not taken.

² Comply with all instructions, in order to avoid death or severe injuries.

Preface

SIPROTEC 5, Overcurrent Protection, Manual 5C53000-G5040-C017-6, Edition 11.2015

! CAUTIONCAUTION means that medium-severe or slight injuries can occur if the specified measures are not taken.

² Comply with all instructions, in order to avoid moderate or minor injuries.

NOTICENOTICE means that property damage can result if the measures specified are not taken.

² Comply with all instructions, in order to avoid property damage.

iiNOTE

Important information about the product, product handling or a certain section of the documentation whichmust be given particular attention.

Qualified Electrical Engineering Personnel

Only qualified electrical engineering personnel may commission and operate the equipment (module, device)described in this document. Qualified electrical engineering personnel in the sense of this manual are peoplewho can demonstrate technical qualifications as electrical technicians. These persons may commission,isolate, ground and label devices, systems and circuits according to the standards of safety engineering.

Proper Use

The equipment (device, module) may be used only for such applications as set out in the catalogs and thetechnical description, and only in combination with third-party equipment recommended and approved bySiemens.Problem-free and safe operation of the product depends on the following:• Proper transport

• Proper storage, setup and installation

• Proper operation and maintenance

When electrical equipment is operated, hazardous voltages are inevitably present in certain parts. If properaction is not taken, death, severe injury or property damage can result:• The equipment must be grounded at the grounding terminal before any connections are made.

• All circuit components connected to the power supply may be subject to dangerous voltage.

• Hazardous voltages may be present in equipment even after the supply voltage has been disconnected(capacitors can still be charged).

• Operation of equipment with exposed current-transformer circuits is prohibited. Before disconnecting theequipment, ensure that the current-transformer circuits are short-circuited.

• The limiting values stated in the document must not be exceeded. This must also be considered duringtesting and commissioning.

Preface

6 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Technical Data

12.1 General Device Data 1291

12.2 Protection Interface and Protection Topology 130012.3 Date and Time Synchronization 1302

12.4 Analog-Units Function Group 130312.5 Overcurrent Protection, Phases 1304

12.6 Voltage-Dependent Overcurrent Protection, Phases 131512.7 Overcurrent Protection, Ground 1317

12.8 Directional Time-Overcurrent Protection, Phases 132812.9 Directional Time-Overcurrent Protection, Ground 133112.10 Inrush-Current Detection 133612.11 Arc Protection 1337

12.12 Instantaneous High-Current Tripping 133812.13 Instantaneous Tripping at Switch onto Fault 1339

12.14 Overcurrent Protection, 1-Phase 134012.15 Overcurrent Protection, 1-Phase (Fast Stage) 1345

12.16 Non-Directional Intermittent Ground-Fault Protection 134612.17 Directional Intermittent Ground-Fault Protection 1348

12.18 Sensitive Ground-Fault Detection 135012.19 Undercurrent Protection 135612.20 Negative-Sequence Protection 135812.21 Directional Negative-Sequence Protection with Definite-Time Delay 136112.22 Thermal Overload Protection 1362

12.23 Unbalanced-Load Protection 136512.24 Current-Unbalance Protection for Capacitors, 3-Phase 1367

12.25 Current-Unbalance Protection for Capacitors, 1-Phase 136912.26 Voltage-Differential Protection for Capacitor Banks 1371

12.27 Differential Protection for Capacitor Banks 137212.28 Overvoltage Protection with 3-Phase Voltage 1374

12.29 Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage 137612.30 Overvoltage Protection with Positive-Sequence Voltage 1378

12.31 Overvoltage Protection with Negative-Sequence Voltage 137912.32 Overvoltage Protection with Any Voltage 1380

12.33 Peak Overvoltage Protection for Capacitors 138212.34 Undervoltage Protection with 3-Phase Voltage 1384

12

SIPROTEC 5, Overcurrent Protection, Manual 1289C53000-G5040-C017-6, Edition 11.2015

12.35 Undervoltage Protection with Positive-Sequence Voltage 1387

12.36 Undervoltage Protection with Any Voltage 138912.37 Overfrequency Protection 1391

12.38 Underfrequency Protection 139212.39 Rate of Frequency Change Protection 1393

12.40 3-Phase Power Protection (P,Q) 139412.41 Reverse-Power Protection 1395

12.42 Overexcitation Protection 139612.43 Undervoltage-Controlled Reactive-Power Protection 1398

12.44 Circuit-Breaker Failure Protection 140012.45 Circuit-Breaker Restrike Protection 1402

12.46 Restricted Ground-Fault Protection 140312.47 External Trip Initiation 1405

12.48 Automatic Reclosing 140612.49 Fault Locator 1407

12.50 Temperature Supervision 140812.51 Current-Jump Detection 1409

12.52 Voltage-Jump Detection 141012.53 Synchronization Function 141112.54 Voltage Controller 141312.55 Current-Balance Supervision 141512.56 Voltage-Balance Supervision 141612.57 Current-Sum Supervision 141712.58 Voltage-Sum Supervision 141812.59 Current Phase-Rotation Supervision 141912.60 Voltage Phase-Rotation Reversal 142012.61 Trip-Circuit Supervision 142112.62 Analog Channel Supervision via Fast Current Sum 142212.63 Measuring-Voltage Failure Detection 1423

12.64 Voltage-Transformer Circuit Breaker 142512.65 Operational Measured Values and Statistical Values 142612.66 Energy Values 1430

12.67 Phasor Measurement Unit 143112.68 Circuit-Breaker Wear Monitoring 1432

12.69 CFC 1433

Technical Data

1290 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

General Device Data

Analog Inputs

Current Inputs

All current, voltage, and power data are specified as RMS values.Rated frequency frated 50 Hz, 60 Hz

Protection-class current trans-formers

Rated current Irated Measuring range ofthe modular devices

Measuring range of thenon-modular devices

5 A1 A

0 A to 500 A0 A to 100 A

0 A to 250 A0 A to 50 A

Instrument transformers 5 A1 A

0 A to 8 A0 A to 1.6 A

0 A to 8 A0 A to 1.6 A

Power consumption per currentcircuit at rated current

Approx. 0.1 VA

Thermal rating(protection and instrument trans-formers)

500 A for 1 s150 A for 10 s20 A continuously25 A for 3 min30 A for 2 min

Dynamic load-carrying capacity 1250 A one half wave

Voltage Input

All current, voltage, and power data are specified as RMS values.Rated frequency frated 50 Hz, 60 Hz

Input and output modules IO202/IO208/IO211/IO214 IO215Measuring range 0 V to 200 V 0 V to 7.07 VInput impedance 200 kΩ 7 kΩThermal rating 230 V continuously 20 V continuously

Measuring-Transducer Inputs (via Module ANAI-CA-4EL)

Connector type 8-pin multiple contact stripDifferential current input channels 4Measuring range DC -24 mA to +24 mAFault < 0.5 % of measuring rangeInput impedance 140 ΩConversion principle Delta-sigma (16 bit)Permissible potential differencebetween channels

DC 20 V

Galvanic separation from ground/housing

DC 700 V

Permissible overload DC 100 mA continuouslyMeasurement repetition 200 ms

Measuring-Transducer Inputs (via Module ARC-CD-3FO)

Connector type AVAGO AFBR-4526ZNumber of transceivers 3

12.1

12.1.1

Technical Data12.1 General Device Data

SIPROTEC 5, Overcurrent Protection, Manual 1291C53000-G5040-C017-6, Edition 11.2015

Fiber type Polymer Optical Fiber (POF) 1 mmReceiverMaximum -10 dBm ± 2 dBmMinimum -40 dBm ± 2 dBmSpectrum 400 nm to 1100 nmAttenuation In the case of plastic optical fibers, you can expect a path attenuation of

0.2 dB/m Additional attenuation comes from the plug and sensor head.Optical budget 1 Minimal 25 dBAnalog sampling rate 16 kHzADC type 10-bit successive approximationTransmitterType LEDWavelength λ = 650 nmTransmit power Minimum 0 dBm

Maximum 2 dBmNumerical aperture 0.5 2

Signal rate connection test 1 pulse per secondPulse duration connection test 11 μsComment:1 All values in combination with sensors approved by Siemens.2 Numerical aperture (NA = sin θ (launch angle))

High-Speed Measuring-Transducer Inputs, Voltage/Current (via IO212)

iiNOTE

Due to possible EMC interference, pay attention to ensure that only the connections for current or forvoltage are used on the device.Use shielded cables.

Table 12-1 High-Speed Measuring-Transducer Inputs, Voltage

Differential voltage input channels 828

Measuring range DC -10 V to +10 VFault < 0.5 % of the measuring rangeInput impedance 48 kΩConversion principle Delta-sigma (16 bit)Permissible potential differencebetween channels

DC 3.5 kV

Galvanic separation from ground/housing

DC 3.5 kV

Permissible overload DC 20 V continuouslyMeasurement repetition 62.5 μs

Table 12-2 High-Speed Measuring-Transducer Inputs, Current

Differential current input channels 829

Measuring range DC -20 mA to +20 mA

28 The IO212 has 8 high-speed measuring-transducer inputs. They can be used either as a voltage or as current input.29 The IO212 has 8 high-speed measuring-transducer inputs. They can be used either as a voltage or as current input.

Technical Data12.1 General Device Data

1292 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Fault < 0.5 % of the measuring rangeInput impedance, current 12 ΩConversion principle Delta-sigma (16 bit)Permissible potential differencebetween channels

DC 3.5 kV

Galvanic separation from ground/housing

DC 3.5 kV

Permissible current overload DC 100 mA continuouslyMeasurement repetition 62.5 μs

Supply Voltage

Integrated Power SupplyFor modular devices, the following printed circuit-board assemblies have a power supply:PS201 – Power supply of the base module and of the 1st device rowPS203 – Voltage supply of 2nd device rowCB202 – Plug in module assembly with integrated power supply, for example, to accommodate communica-tion modulesPermissible voltageranges(PS201, PS203, CB202)

DC 19 V to DC 60 V DC 48 V to DC 300 VAC 80 V to AC 265 V, 50 Hz/60 Hz

Auxiliary rated voltage VH

(PS201, PS203, CB202)DC 24 V/DC 48 V DC 60 V/DC 110 V/DC 125 V/DC 220 V/

DC 250 V orAC 100 V/AC 115 V/AC 230 V, 50 Hz/60 Hz

Permissible voltageranges (PS101)

DC 19 V to DC 60 V DC 48 V to 150 V DC 88 V to DC 300 VAC 80 V to AC 265 V,50 Hz/60 Hz

Auxiliary rated voltage VH

(PS101)DC 24 V/DC 48 V DC 60 V/DC 110 V/

DC 125 VDC 110 V/ DC 125 V/DC 220 V/DC 250 VorAC 100 V/AC 115 V/AC 230 V, 50 Hz/60 Hz

Superimposed alternating voltage, peak-to-peak,IEC 60255-11

≤ 15% of the DC auxiliary rated voltage (applies onlyto direct voltage)

Inrush current ≤ 18 ARecommended external protection Miniature circuit breaker 6 A, characteristic C

according to IEC 60898Internal fuse– DC 24 V to DC 48 V DC 60 V to DC 125 V DC 24 V to DC 48 V

AC 100 V to AC 230 VPS101 4 A intert, AC 250 V,

DC 150 V,UL recognizedSIBA type 179200 orSchurter type SPT 5x20

2 A time-lag, AC 250 V, DC 300 V, UL recognizedSIBA type 179200 or Schurter type SPT 5x20

PS201, PS203, CB202 2 A time-lag, AC 250 V, DC 300 V, UL recognizedSIBA type 179200 or Schurter type SPT 5x20

Power consumption (life relay active)– DC AC 230 V/50 Hz AC 115 V/50 Hz

12.1.2

Technical Data12.1 General Device Data

SIPROTEC 5, Overcurrent Protection, Manual 1293C53000-G5040-C017-6, Edition 11.2015

Integrated Power Supply1/3 base module, non-modularWithout plug-in modules

7.0 W 16 VA 12.5 VA

1/3 base module, modularWithout plug-in modules

13 W 33 VA 24 VA

1/6 expansion module 3 W 6 VA 6 VA1/6 plug-in moduleassembly without plug-inmodules (modulesCB202)

3.5 W 14 VA 7 VA

Plug-in module for basemodule or plug-in moduleassembly (for example,communication module)

< 5 W < 6 VA < 6 VA

Stored-energy time for auxiliary voltage outage orshort circuit, modular devices

For V ≥ DC 24 V ≥ 50 msFor V ≥ DC 110 V ≥ 50 msFor V ≥ AC 115 V ≥ 50 ms

Stored-energy time for auxiliary voltage outage orshort circuit, non-modular devices

For V ≥ DC 24 V ≥ 20 msFor V ≥ DC 60 V/DC 110 V ≥ 50 msFor V ≥ AC 115 V ≥ 200 ms

Binary Inputs

Rated voltage range DC 24 V to 250 VThe binary inputs of SIPROTEC 5 are bipolar with the exception of thebinary inputs on the IO230 and on the IO231.

Current consumption, excited Approx. DC 0.6 mA to 1.8 mA (independent of the operating voltage)Power consumption, max. 0.6 VAPickup time Approx. 3 msDropout time Approx. 4 msSwitching thresholds Adjustable with DIGSI 5

Range 1 for 24 V, 48 V, and 60 VOperating voltage

Vlow ≤ DC 10 VVhigh ≥ DC 19 V

Range 2 for 110 V and 125 VOperating voltage

Vlow ≤ DC 44 VVhigh ≥ DC 88 V

Range 3 for 220 V and 250 VOperating voltage

Vlow ≤ DC 88 VVhigh ≥ DC 176 V

Maximum permitted voltage DC 300 VThe binary inputs contain interference suppression capacitors. In order to ensure EMC, use the terminalsshown in the terminal diagrams/connection diagrams to connect the binary inputs to the common potential.

Relay Outputs

Standard Relay (Type S)

Switching capacity On: 1000 W/VAOff: 30 VA; 40 W ohmic;30 W/VA at L/R ≤ 40 ms

12.1.3

12.1.4

Technical Data12.1 General Device Data

1294 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

AC and DC contact voltage 250 VPermissible current per contact (continuous) 5 APermissible current per contact (switching on andholding)

30 A for 1 s (make contact)

Short-time current across closed contact 250 A for 30 msTotal permissible current for contacts connected tocommon potential

5 A

Switching time OOT (Output Operating Time)Additional delay of the output medium used

≤ 10 ms

Max. rated data of the output contacts in accordancewith UL certification

DC 24 V, 8 A, General PurposeDC 48 V, 0.8 A, General PurposeDC 240 V, 0.1 A, General PurposeAC 240 V, 5 A, General PurposeAC 120 V, 1/3 hpAC 250 V, 1/2 hpB300R300

Interference suppression capacitors across thecontacts

4.7 nF, ± 20 %, AC 250 V

Fast Relay (Type F)

Switching capacity On: 1000 W/VAOff: 30 VA; 40 W ohmic;30 W/VA at L/R ≤ 40 ms

AC and DC contact voltage 250 VPermissible current per contact (continuous) 5 APermissible current per contact (switching on andholding)

30 A for 1 s (make contact)

Short-time current across closed contact 250 A for 30 msTotal permissible current for contacts connected tocommon potential

5 A

Switching time OOT (Output Operating Time)Additional delay of the output medium used

Closing time, typical: 4 msOpening time, typical: 2 msMaximum: ≤ 5 ms

Rated data of the output contacts in accordance withUL certification

AC 120 V, 8.5 A, General PurposeAC 277 V, 6 A, General PurposeAC 277 V, 0.7 hpAC 347 V, 4.5 A, General PurposeB300R300

Interference suppression capacitors across thecontacts

4.7 nF, ± 20 %, AC 250 V

Supervision 2-channel activation with cyclic testing (only for makecontact)

High-Speed Relay with Semiconductor Acceleration (Type HS)

Switching capacity On/Off: 1000 W/VAContact voltage AC 200 V, DC 250 VPermissible current per contact (continuous) 5 A

Technical Data12.1 General Device Data

SIPROTEC 5, Overcurrent Protection, Manual 1295C53000-G5040-C017-6, Edition 11.2015

Permissible current per contact (switching on andholding)

30 A for 1 s (make contact)

Short-time current across closed contact 250 A for 30 msTotal permissible current for contacts connected tocommon potential

5 A

Switching time OOT (Output Operating Time)Additional delay of the output medium used

Closing time, typical: 0.2 msOpening time, typical: 6 msMaximum: ≤ 9 ms

Rated data of the output contacts in accordance withUL certification

B150Q300

Power Relay (for Direct Control of Motor Switches)

Switching capacity for permanent and periodic operation250 V/4.0 A220 V/4.5 A110 V/5.0 A60 V/5.0 A48 V/5.0 A24 V/5.0 A

1000 W1000 W550 W300 W240 W120 W

In order to prevent any damage, the external protec-tion circuit must switch off the motor in case the rotoris blocked.

Turn on switching power for 30 s, recovery time until switching on again is 15 minutes.For short-term switching operations, an impulse/pause ratio of 3 % must be considered.100 V/9.0 A60 V/10.0 A48 V/10.0 A24 V/10.0 A

1000 W600 W480 W240 W

Continuous and inching operation is not permitted.In order to prevent any damage, the external protec-tion circuit must switch off the motor in case the rotoris blocked.

AC and DC contact voltage 250 VPermissible continuous current per contact 5 APermissible current per contact (switching on andholding)

30 A for 1 s

Short-time current across closed contact 250 A for 30 msTotal permissible current for contacts connected tocommon potential

5 A

Switching time OOT (Output Operating Time)Additional delay of the output medium used

≤ 16 ms

Rated data of the output contacts in accordance withUL certification

DC 300 V, 10 A, ResistiveDC 250 V, 1 hp motor - 30 s ON, 15 min OFFDC 110 V, 3/4 hp motor - 30 s ON, 15 min OFFDC 60 V, 1/2 hp motor - 30 s ON, 15 min OFFDC 48 V, 1/3 hp motor - 30 s ON, 15 min OFFDC 24 V, 1/6 hp motor - 30 s ON, 15 min OFF

Interference suppression capacitors across thecontacts

4.7 nF, ± 20 %, AC 250 V

The power relays operate in interlocked mode, that is, only one relay of each switching pair picks up at atime thereby avoiding a power-supply short circuit.

Technical Data12.1 General Device Data

1296 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Design Data

Masses

Device SizeWeight of the Modular Devices

Type of construction 1/3 1/2 2/3 5/6 1/1Flush-mounting device 4.8 kg 8.1 kg 11.4 kg 14.7 kg 18.0 kgSurface-mounted device with inte-grated on-site operation panel

7.8 kg 12.6 kg 17.4 kg 22.2 kg 27.0 kg

Surface-mounted device withdetached on-site operation panel

5.1 kg 8.7 kg 12.3 kg 15.9 kg 19.5 kg

Size WeightDetached on-site operation panel 1/3 1.9 kgDetached on-site operation panel 1/6 1.1 kg

Device SizeWeight of the Non-Modular Devices 7xx82

Type of construction 1/3Flush-mounting device 3.7 kgBracket for non-modular surface-mounting variant

1.9 kg

Dimensions of the Basic and 1/3 Modules

Type of Construction (Maximum Dimensions) Width over all x Height over all x Depth 30(in Inches)Flush-mounting device 150 mm x 268 mm x 229 mm (5.91 x 10.55 x 9.02)Surface-mounted device with integrated on-site oper-ation panel

150 mm x 314 mm x 337 mm (5.91 x 12.36 x 13.27)

Surface-mounted device with detached on-site opera-tion panel

150 mm x 314 mm x 230 mm (5.91 x 12.36 x 9.06)

Dimensions of Device Rows

Type ofConstruction(MaximumDimensions)

Width over all x Height over all x Depth 31(in Inches)

Type ofconstruction

1/3 1/2 2/3 5/6 1/1

Flush-mountingdevice

150 mm x268 mm x229 mm (5.91 x10.55 x 9.02)

225 mm x268 mm x229 mm (8.86 x10.55 x 9.02)

300 mm x268 mm x229 mm(11.81 x10.55 x 9.02)

375 mm x268 mm x229 mm (14.76 x10.55 x 9.02)

450 mm x268 mm x229 mm (17.72 x10.55 x 9.02)

Surface-mounted devicewith integratedon-site operationpanel

150 mm x314 mm x337 mm (5.91 x12.36 x 13.27)

225 mm x314 mm x337 mm (8.86 x12.36 x 13.27)

300 mm x314 mm x337 mm (11.81 x12.36 x 13.27)

375 mm x314 mm x337 mm (14.76 x12.36 x 13.27)

450 mm x314 mm x337 mm (17.72 x12.36 x 13.27)

12.1.5

30 Width and depth rounded to whole numbers in mm31 Width and depth rounded to whole numbers in mm

Technical Data12.1 General Device Data

SIPROTEC 5, Overcurrent Protection, Manual 1297C53000-G5040-C017-6, Edition 11.2015

Type ofConstruction(MaximumDimensions)

Width over all x Height over all x Depth 31(in Inches)

Surface-mounted devicewith detachedon-site operationpanel

150 mm x314 mm x230 mm (5.91 x12.36 x 9.06)

225 mm x314 mm x230 mm (8.86 x12.36 x 9.06)

300 mm x314 mm x230 mm (11.81 x12.36 x 9.06)

375 mm x314 mm x230 mm (14.76 x12.36 x 9.06)

450 mm x314 mm x230 mm (17.72 x12.36 x 9.06)

Expansion Module Dimensions

Type of Construction (Maximum Dimensions) Width x Height x Depth 32 (in Inches)Flush-mounting device 75 mm x 268 mm x 229 mm (2.95 x 10.55 x 9.02)Surface-mounted device with integrated on-site oper-ation panel

75 mm x 314 mm x 337 mm (2.95 x 12.36 x 13.27)

Surface-mounted device with detached on-site opera-tion panel

75 mm x 314 mm x 230 mm (2.95 x 12.36 x 9.06)

Plug-In Module Dimensions

Type of Construction (Maximum Dimensions) Width x Height x Depth (in Inches)USART-Ax-xEL, ETH-Bx-xEL 61 mm x 45 mm x 120.5 mm (2.4 x 1.77 x 4.74)USART-Ax-xFO, ETH-Bx-xFO (without protectioncover)

61 mm x 45 mm x 132.5 mm (2.4 x 1.77 x 5.22)

ANAI-CA-4EL 61 mm x 45 mm x 119.5 mm (2.4 x 1.77 x 4.7)ARC-CD-3FO 61 mm x 45 mm x 120.5 mm (2.4 x 1.77 x 4.74)

Minimum Bending Radii of the Connecting Cables Between the On-Site Operation Panel and the Base Module

Fiber-optic cable R = 50 mmPay attention to the length of the cable protectionsleeve, which you must also include in calculations.

D-Sub cable R = 50 mm (minimum bending radius)

Degree of Protection to IEC 60529

For equipment in the surface-mounting housing IP50For equipment in the flush-mounting housing Front IP51

Back side of the modular devices IP50Back side of the non-modular devices IP40

For operator protection IP2x for current terminal (installed removed)IP1x for voltage terminal (removed/without cover)IP2x for voltage terminal (removed/with cover)IP2x for voltage terminal (installed)

Degree of pollution, IEC 60255-27 2Maximum altitude above sea level 2000 m (6561.68 ft)

31 Width and depth rounded to whole numbers in mm32 Width and depth rounded to whole numbers in mm

Technical Data12.1 General Device Data

1298 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

UL Note

Type 1 if mounted into a door or front cover of an enclosure.When expanding the device with the 2nd device row, then they must be mounted completely inside anenclosure.

Tightening Torques for Terminal Screws

Type of Line Current Terminal Voltage Terminal withSpring-Loaded Terminals

Voltage Terminal withScrew Connection

Litz wire with ring-type lug 2.7 Nm No ring-type lug No ring-type lugStranded wires with boot-lace ferrules or pin-typelugs

2.7 Nm 1.0 Nm 0.6 Nm

Solid conductor, bare(2 mm2)

2.0 Nm 1.0 Nm –

iiNOTE

Use copper cables only.

Torques for Other Screw Types

Screw Type TorqueM4 x 20 1.2 NmM4 x 8 1.2 NmM2.5 x 6 0.39 NmCountersunk screw, M2.5 x 6 0.39 NmCountersunk screw, M2.5 x 8 0.39 NmCollar screw, M4 x 20 0.7 Nm

Technical Data12.1 General Device Data

SIPROTEC 5, Overcurrent Protection, Manual 1299C53000-G5040-C017-6, Edition 11.2015

Protection Interface and Protection Topology

Setting Values

Mode OnOff

PPS Synchronization Telegr. and PPSTelegr. or PPSPPS synchronization off

Blocking of the unbalancedruntimes

YesNo

Maximum signal runtime threshold 0.1 ms to 30.0 ms Increments of 0.1 msMaximum runtime difference 0.000 ms to 3.000 ms Increments of 0.001 msFailure indication after 0.05 s to 2.00 s Increments of 0.01 sFailure indication after 0.0 s to 6.0 s Increments of 0.1 sMax. error rate/h 0.000 % to 100.000 % Increments of 0.001 %Max. error rate/min 0.000 % to 100.000 % Increments of 0.001 %PPS failure indication after 0.5 s to 60.0 s Increments of 0.1 s

Transmission Rate

Direct connection:Transmission rate 2048 kbit/sConnection via communication networks:Supported network interfaces G703.1 with 64 kBit/s

G703-T1 with 1.455 MBit/sG703-E1 with 2.048 MBit/sX.21 with 64 kBit/s or 128 kBit/s or 512 kBit/sPilot wires with 128 kbit/s

Transmission rate 64 kBit/s at G703.11.455 MBit/s at G703-T12.048 MBit/s at G703-E1512 kBit/s or 128 kBit/s or 64 kBit/s at X.21128 kBit/s for pilot wires

Transmission Times

Priority 1Response time, total approx.For 2 ends Minimum 8 ms

Typical 10 msFor 3 ends Minimum 10 ms

Typical 14 msFor 6 ends Minimum 15 ms

Typical 18 msDropout times, total approx.For 2 ends Typical 20 msFor 3 ends Typical 20 msFor 6 ends Typical 26 ms

12.2

Technical Data12.2 Protection Interface and Protection Topology

1300 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Priority 2Response time, total approx.For 2 ends Minimum 9 ms

Typical 16 msFor 3 ends Minimum 12 ms

Typical 18 msFor 6 ends Minimum 17 ms

Typical 23 msDropout times, total approx.For 2 ends Typical 24 msFor 3 ends Typical 25 msFor 6 ends Typical 32 ms

Priority 333

Response time, total approx.For 2 ends Minimum

Typical 100 msFor 3 ends Minimum

Typical 150 msFor 6 ends Minimum

Typical 200 msDropout times, total approx.For 2 ends Typical 100 msFor 3 ends Typical 150 msFor 6 ends Typical 200 ms

33 Times cannot be determined because the signals are transmitted in fragments.

Technical Data12.2 Protection Interface and Protection Topology

SIPROTEC 5, Overcurrent Protection, Manual 1301C53000-G5040-C017-6, Edition 11.2015

Date and Time Synchronization

Date format DD.MM.YYYY (Europe)MM/DD/YYYY (USA)YYYY-MM-DD (China)

Time source 1, time source 2 NoneIRIG-B 002(003)IRIG-B 006(007)IRIG-B 005(004) with extension according toIEEE C37.118-2005DCF77PI (protection interface)34

SNTPIEC 60870-5-103DNP3IEEE 1588

Time zone 1, time zone 2 LocalUTC

Failure indication after 0 s to 3600 sTime zone and daylight saving time Transfer of PC settings

Manually setting the time zonesTime zone offset with respect to GMT -720 min to 840 minSwitching over to daylight saving time Active

InactiveBeginning of daylight saving time Input: day and timeEnd of daylight saving time Input: day and timeOffset daylight saving time -120 to 120 [steps of 15]

12.3

34 If provided

Technical Data12.3 Date and Time Synchronization

1302 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Analog-Units Function Group

20-mA Unit Ether.

Max. number of connected 20-mA units 4Max. number of channels per 20-mA unit 12

20-mA Unit Serial

Max. number of connected 20-mA units 4Max. number of channels per 20-mA unit 12

RTD Unit (Ziehl TR1200)

Max. number of connected RTD units 4Max. number of sensors per RTD unit 12Sensor type Pt 100 as per EN 60751

RTD Unit (Ziehl TR1200) IP

Max. number of connected RTD units 4Max. number of sensors per RTD unit 12Sensor type Pt 100 as per EN 60751; connection of Ni 100 and

Ni 120 sensors possible. The measured values mustbe converted in the evaluation unit.

Temperature Measured Values

Unit of measurement for temperature °C or °F, can be adjustedPt 100 -199 °C to 850 °C (-326 °F to 1472 °F)Resolution 1 °C or 1 °FTolerance ±0.5 % of the measured value ±1 K

12.4

Technical Data12.4 Analog-Units Function Group

SIPROTEC 5, Overcurrent Protection, Manual 1303C53000-G5040-C017-6, Edition 11.2015

Overcurrent Protection, Phases

Definite Time-Overcurrent Protection, Phases

Setting Values

Method of measurement Fundamental componentRMS value

Threshold value35 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Dropout ratio 0.90 to 0.99 Increments of 0.01Time delay 0.00 s to 60.00 s Increments of 0.01 sDropout delay 0.00 s to 60.00 s Increments of 0.01 sPickup delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-rent functionality.Minimum absolute dropout differenceProtection-class current transformer 15 mA sec. (Irated = 1 A) or

75 mA sec. (Irated = 5 A)

Instrument current transformer 0.5 mA sec. (Irated = 1 A) or2.5 mA sec. (Irated = 5 A)

Times

Operate time with time delay = 0 ms Approx. 25 ms + OOT 36 at 50 HzApprox. 22 ms + OOT at 60 Hz

Extension of the operate time during operation withtransformer inrush-current detection

Approx. 10 ms

Dropout time Approx. 20 ms + OOT

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances

10 Hz ≤ f < 0.9 frated

1.1 frated < f ≤ 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Active

12.5

12.5.1

35 If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 lrated,sec.36 OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays

Technical Data12.5 Overcurrent Protection, Phases

1304 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Tolerances

Currents, method of measurement = fundamentalcomponent

1 % of the setting value or 5 mA (Irated = 1 A)or 25 mA (Irated = 5 A), (frated ± 10 %)

Currents, method of measurement = RMS value(33 % harmonics, in relation to fundamental component)Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)

or 25 mA (Irated = 5 A), (frated ± 10 %)

Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)or 100 mA (Irated = 5 A), (frated ± 10 %)

Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)or 100 mA (Irated = 5 A), (frated ± 10 %)

Time delays 1 % of the setting value or 10 ms

Variables Influencing the Thresholds

Transient excess pickup in method of measurement = fundamental component,for τ > 100 ms (with complete unbalance)

< 5 %

Inverse Time-Overcurrent Protection, Phases

Setting Values

Method of measurement Fundamental componentRMS value

Threshold value 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Dropout Disk emulationInstantaneous

Time multiplier 0.00 to 15.00 Increments of 0.01Pickup delay 0.00 s to 60.00 s Increments of 0.01 sMinimum time of the curve 0.00 s to 1.00 s Increments of 0.01 sAdditional time delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout Ratio

Disk emulation Approx. 0.90 ⋅ threshold valueInstantaneous Approx. 1.05 ⋅ threshold value

Approx. 0.95 ⋅ pickup value

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

12.5.2

Technical Data12.5 Overcurrent Protection, Phases

SIPROTEC 5, Overcurrent Protection, Manual 1305C53000-G5040-C017-6, Edition 11.2015

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-rent functionality.Minimum absolute dropout differenceProtection-class current transformer 15 mA sec. (Irated = 1 A) or

75 mA sec. (Irated = 5 A)

Instrument current transformer 0.5 mA sec. (Irated = 1 A) or2.5 mA sec. (Irated = 5 A)

Operate Curves and Dropout-Time Characteristic Curves according to IEC

Extension of the operate time during operation with transformer inrush-current detection

Approx. 10 ms

Technical Data12.5 Overcurrent Protection, Phases

1306 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

[dwocpki1-080213-01.tif, 1, en_US]

Figure 12-1 Operate Curves and Dropout-Time Characteristic Curves according to IEC

Technical Data12.5 Overcurrent Protection, Phases

SIPROTEC 5, Overcurrent Protection, Manual 1307C53000-G5040-C017-6, Edition 11.2015

[dwocpki2-080213-01.tif, 1, en_US]

Figure 12-2 Operate Curves and Dropout-Time Characteristic Curves According to IEC

Technical Data12.5 Overcurrent Protection, Phases

1308 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE

[dwocpka1-080213-01.tif, 1, en_US]

Figure 12-3 Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE

Technical Data12.5 Overcurrent Protection, Phases

SIPROTEC 5, Overcurrent Protection, Manual 1309C53000-G5040-C017-6, Edition 11.2015

[dwocpka2-080213-01.tif, 1, en_US]

Figure 12-4 Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE

Technical Data12.5 Overcurrent Protection, Phases

1310 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

[dwocpka3-080213-01.tif, 1, en_US]

Figure 12-5 Tripping Characteristic Curves and Dropout Characteristic Curves According to ANSI/IEEE

Technical Data12.5 Overcurrent Protection, Phases

SIPROTEC 5, Overcurrent Protection, Manual 1311C53000-G5040-C017-6, Edition 11.2015

[dwocpka4-080213-01.tif, 1, en_US]

Figure 12-6 Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances

10 Hz ≤ f < 0.9 frated

1.1 frated < f ≤ 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Active

Tolerances

Currents, method of measurement = fundamentalcomponent

1 % of the setting value or 5 mA (Irated = 1 A)or 25 mA (Irated = 5 A), (frated ± 10 %)

Currents, method of measurement = RMS value(33% harmonics, in relation to fundamental component)Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)

or 25 mA (Irated = 5 A), (frated ± 10 %)

Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)or 100 mA (Irated = 5 A), (frated ± 10 %)

Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)or 100 mA (Irated = 5 A), (frated ± 10 %)

Operate time for 2 ≤ I/I threshold value ≤ 20 5 % of the setting value or +2 % current tolerance or30 ms

Dropout time for I/I threshold value ≤ 0.90 5 % of the setting value or +2 % current tolerance or30 ms

Technical Data12.5 Overcurrent Protection, Phases

1312 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Variables Influencing the Thresholds

Transient excess pickup in method of measurement = fundamental component,for τ > 100 ms (with complete unbalance)

< 5 %

Overcurrent Protection, Phases with User-Defined Characteristic Curve

Setting Values

Method of measurement Fundamental componentRMS value

Threshold value 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Dropout Disk emulationInstantaneous

Time multiplier 0.05 to 15.00 Increments of 0.01Number of value pairs for the operate curve 2 to 30 Increments of 1X values of the operate curve 1.00 to 66.67 p. u. Increments of 0.01 p.u.Y values of the operate curve 0.00 s to 999.00 s Increments of 0.01 sNumber of value pairs for the dropout characteristiccurve

2 to 30 Increments of 1

X values of the dropout characteristic curve 0.05 to 0.95 p. u. Increments of 0.01 p.u.Y values of the dropout characteristic curve 0.00 s to 999.00 s Increments of 0.01 s

Dropout Ratio

Disk emulation Approx. 0.90 * threshold valueInstantaneous Approx. 1.05 * threshold value

Approx. 0.95 * pickup value

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-rent functionality.Minimum absolute dropout differenceProtection-class current transformer 15 mA sec. (Irated = 1 A) or

75 mA sec. (Irated = 5 A)

Instrument current transformer 0.5 mA sec. (Irated = 1 A) or2.5 mA sec. (Irated = 5 A)

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances

10 Hz ≤ f < 0.9 frated

1.1 frated < f ≤ 80 HzSlightly expanded tolerances

12.5.3

Technical Data12.5 Overcurrent Protection, Phases

SIPROTEC 5, Overcurrent Protection, Manual 1313C53000-G5040-C017-6, Edition 11.2015

f < 10 Hzf > 80 Hz

Active

Tolerances

Currents, method of measurement = fundamentalcomponent

1 % of the setting value or 5 mA (Irated = 1 A)or 25 mA (Irated = 5 A), (frated ± 10 %)

Currents, method of measurement = RMS value(33 % harmonics, in relation to fundamental component)Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)

or 25 mA (Irated = 5 A), (frated ± 10 %)

Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)or 100 mA (Irated = 5 A), (frated ± 10 %)

Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)or 100 mA (Irated = 5 A), (frated ± 10 %)

Operate time for 2 ≤ I/I threshold value ≤ 20 5 % of the setting value or +2 % current tolerance or30 ms

Dropout time for I/I threshold value ≤ 0.90 5 % of the setting value or +2 % current tolerance or30 ms

Variables Influencing the Thresholds

Transient excess pickup in method of measurement = fundamental component,for τ > 100 ms (with complete unbalance)

< 5 %

Operate Curves and Dropout-Time Characteristic Curves according to IEC

Extension of the operate time during operation with transformer inrush-current detection

Approx. 10 ms

Technical Data12.5 Overcurrent Protection, Phases

1314 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Voltage-Dependent Overcurrent Protection, Phases

Setting Values for All Stage Types

Method of measurement Fundamental componentRMS value

Overcurrent thresholdvalue

For Irated = 1 A 0.030 A to 35.000 A Increments of 0.001 A

For Irated = 5 A 0.15 A to 175.00 A Increments of 0.01 A

Time delay 0.10 s to 60.00 s Increments of 0.01 s

Setting Values for Inverse-Time Overcurrent Stages

Method of measurement Fundamental componentRMS value

Dropout ratio of undervoltage37 1.01 to 1.20 Increments of 0.01Undervoltage threshold value37 0.300 V to 175.000 V Increments of 0.001 VDropout Disk emulation

instantaneous–

Time multiplier 0.05 to 15.00 Increments of 0.01

Setting Values for Definite-Time Overcurrent Stages

Seal-in voltage 0.300 V to 175.000 V Increments of 0.001 VPhase-to-phase voltage 0.300 V to 175.000 V Increments of 0.001 VNegative-sequence voltage V2 0.300 V to 200.000 V Increments of 0.001 VTime delay 0.00 s to 60.00 s Increments of 0.01 sDuration of V-seal-in time 0.10 s to 60.00 s Increments of 0.01 s

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overcurrent/overvoltage and of 105 %for undercurrent/undervoltage functionality.Minimum absolute dropout differenceProtection-class current transformer 15 mA sec. (Irated = 1 A) or

75 mA sec. (Irated = 5 A)

Instrument current transformer 0.5 mA sec. (Irated = 1 A) or2.5 mA sec. (Irated = 5 A)

Voltage transformer 150 mV sec.

Operate Curves and Dropout-Time Characteristic Curves According to IEC

Extension of the operate time during operation withinrush-current detection

Approx. 10 ms

The operate curves and dropout-time characteristic curves according to IEC can be found in the chapterTechnical Data under Inverse-Time Overcurrent Protection.

12.6

37 The setting value is for the inverse-time overcurrent voltage-released stage.

Technical Data12.6 Voltage-Dependent Overcurrent Protection, Phases

SIPROTEC 5, Overcurrent Protection, Manual 1315C53000-G5040-C017-6, Edition 11.2015

Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE

The operate curves and dropout-time characteristic curves according to IEC can be found in the chapterTechnical Data under Inverse-Time Overcurrent Protection.

Frequency Operating Range

0.9 f/frated to 1.1 f/frated According to specified tolerances

10 Hz to 0.9 f/frated

1.1 f/frated to 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Inactive

Tolerances

Currents, method of measurement = fundamentalcomponent

1 % of the setting value or 5 mA (Irated = 1 A) or 25mA (Irated = 5 A), (frated ± 10 %)

Currents, method of measurement = RMS value(33 % part of harmonic in relation to fundamentalcomponent)

Up to 30th harmonic1 % of the setting value or 5 mA (Irated = 1 A)or 25 mA (Irated = 5 A), (frated ± 10 %)

Up to 50th harmonic, frated = 50 Hz3 % of the setting value or 20 mA (Irated = 1 A)or 100 mA (Irated = 5 A), (frated ± 10 %)

Up to 50th harmonic, frated = 60 Hz4 % of the setting value or 20 mA (Irated = 1 A)or 100 mA (Irated = 5 A), (frated ± 10 %)

Voltage 0.5 % of the setting value or 0.05 VOperate time for 2 ≤ I/I threshold value ≤ 20 5 % of the setting value

or +2 % current tolerance or 30 msDropout time for I/I threshold value ≤ 0.90 5 % of the setting value

or +2 % current tolerance or 30 ms

Influencing Variables for Thresholds

Transient excess pickup in method of measurement = fundamental component, for τ >100 ms (with complete unbalance)

< 5 %

Technical Data12.6 Voltage-Dependent Overcurrent Protection, Phases

1316 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Overcurrent Protection, Ground

Definite-Time Overcurrent Protection, Ground

Setting Values

Method of measurement Fundamental componentRMS value

Threshold value38 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Dropout ratio 0.90 to 0.99 Increments of 0.01Time delay 0.00 s to 60.00 s Increments of 0.01 sDropout delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-rent functionality.Minimum absolute dropout differenceProtection-class current transformer 15 mA sec. (Irated = 1 A) or

75 mA sec. (Irated = 5 A)

Instrument current transformer 0.5 mA sec. (Irated = 1 A) or2.5 mA sec. (Irated = 5 A)

Times

Operate time with time delay = 0 ms Approx. 25 ms + OOT39 at 50 HzApprox. 22 ms + OOT at 60 Hz

Extension of the operate time during operation withtransformer inrush-current detection

Approx. 10 ms

Dropout time Approx. 20 ms + OOT

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances

10 Hz ≤ f < 0.9 frated

1.1 frated < f ≤ 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Active

12.7

12.7.1

38 If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 lrated,sec.39 OOT (Output Operating Time) additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs

Technical Data12.7 Overcurrent Protection, Ground

SIPROTEC 5, Overcurrent Protection, Manual 1317C53000-G5040-C017-6, Edition 11.2015

Tolerances

3I0 measured via I440, method of measurement =fundamental component

1 % of the setting value or 5 mA (Irated = 1 A)or 25 mA (Irated = 5 A), (frated ± 10 %)

3I0 measured via I441, method of measurement = RMS value(33 % harmonics, in relation to fundamental component)Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)

or 25 mA (Irated = 5 A), (frated ± 10 %)

Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)or 100 mA (Irated = 5 A), (frated ± 10 %)

Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)or 100 mA (Irated = 5 A), (frated ± 10 %)

Time delays 1 % of the setting value or 10 ms

Influencing Variables for Thresholds

Transient excess pickup in method of measurement = fundamental component,for τ > 100 ms (with complete unbalance)

< 5 %

Inverse-Time Overcurrent Protection, Ground

Setting Values

Method of measurement Fundamental componentRMS value

Threshold value42 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Dropout Disk emulationInstantaneous

Time multiplier 0.00 to 15.00 Increments of 0.01Minimum time of the curve 0.00 to 1.00 s Increments of 0.01 sAdditional time delay 0.00 to 60.00 s Increments of 0.01 s

Dropout Ratio

Disk emulation Approx. 0.90 * threshold valueInstantaneous Approx. 1.05 * threshold value

Approx. 0.95 * pickup value

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

12.7.2

40 Slightly expanded tolerances will occur during the calculation of 3I0, maximum factor of 241 Slightly expanded tolerances will occur during the calculation of 3I0, maximum factor of 242 If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 lrated,sec.

Technical Data12.7 Overcurrent Protection, Ground

1318 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-rent functionality.Minimum absolute dropout differenceProtection-class current transformer 15 mA sec. (Irated = 1 A) or

75 mA sec. (Irated = 5 A)

Instrument current transformer 0.5 mA sec. (Irated = 1 A) or2.5 mA sec. (Irated = 5 A)

Operate Curves and Dropout-Time Characteristic Curves According to IEC

Extension of the operate time during operation with transformer inrush-current detection

Approx. 10 ms

Technical Data12.7 Overcurrent Protection, Ground

SIPROTEC 5, Overcurrent Protection, Manual 1319C53000-G5040-C017-6, Edition 11.2015

[dwocpki1-080213-01.tif, 1, en_US]

Figure 12-7 Operate Curves and Dropout-Time Characteristic Curves According to IEC

Technical Data12.7 Overcurrent Protection, Ground

1320 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

[dwocpki2-080213-01.tif, 1, en_US]

Figure 12-8 Operate Curves and Dropout-Time Characteristic Curves According to IEC

Technical Data12.7 Overcurrent Protection, Ground

SIPROTEC 5, Overcurrent Protection, Manual 1321C53000-G5040-C017-6, Edition 11.2015

Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE

[dwocpka1-080213-01.tif, 1, en_US]

Figure 12-9 Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE

Technical Data12.7 Overcurrent Protection, Ground

1322 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

[dwocpka2-080213-01.tif, 1, en_US]

Figure 12-10 Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE

Technical Data12.7 Overcurrent Protection, Ground

SIPROTEC 5, Overcurrent Protection, Manual 1323C53000-G5040-C017-6, Edition 11.2015

[dwocpka3-080213-01.tif, 1, en_US]

Figure 12-11 Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE

Technical Data12.7 Overcurrent Protection, Ground

1324 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

[dwocpka4-080213-01.tif, 1, en_US]

Figure 12-12 Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances

10 Hz ≤ f < 0.9 frated

1.1 frated < f ≤ 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Active

Tolerances

3I0 measured via I443, method of measurement =fundamental component

1 % of the setting value or 5 mA (Irated = 1 A)or 25 mA (Irated = 5 A), (frated ± 10 %)

3I0 measured via I444, method of measurement = RMS value(33 % harmonics, in relation to fundamental component)Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)

or 25 mA (Irated = 5 A), (frated ± 10 %)

Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)or 100 mA (Irated = 5 A), (frated ± 10 %)

Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)or 100 mA (Irated = 5 A), (frated ± 10 %)

Operate time for 2 ≤ I/I threshold value ≤ 20 5 % of the setting value or +2 % current tolerance or30 ms

43 Insignificantly increased tolerances will occur during the calculation of 3I0, maximum factor of 244 Insignificantly increased tolerances will occur during the calculation of 3I0, maximum factor of 2

Technical Data12.7 Overcurrent Protection, Ground

SIPROTEC 5, Overcurrent Protection, Manual 1325C53000-G5040-C017-6, Edition 11.2015

Dropout time for 2 ≤ I/threshold value I ≤ 0.90 5 % of the setting value or +2 % current tolerance or30 ms

Influencing Variables for the Thresholds

Transient excess pickup in method of measurement = fundamental component,for τ > 100 ms (with complete unbalance)

< 5 %

Overcurrent Protection, Ground with User-Defined Characteristic Curve

Setting Values

Method of measurement Fundamental componentRMS value

Threshold value 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Dropout Disk emulationInstantaneous

Time multiplier 0.05 to 15.00 Increments of 0.01Number of value pairs for the operate curve 2 to 30 Increments of 1X values of the operate curve 1.00 to 66.67 p. u. Increments of 0.01 p.u.Y values of the operate curve 0.00 s to 999.00 s Increments of 0.01 sNumber of value pairs for the dropout characteristiccurve

2 to 30 Increments of 1

X values of the dropout characteristic curve 0.05 to 0.95 p. u. Increments of 0.01 p.u.Y values of the dropout characteristic curve 0.00 s to 999.00 s Increments of 0.01 s

Dropout Ratio

Disk emulation Approx. 0.90 * threshold valueInstantaneous Approx. 1.05 * threshold value

Approx. 0.95 * pickup value

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-rent functionality.Minimum absolute dropout differenceProtection-class current transformer 15 mA sec. (Irated = 1 A) or

75 mA sec. (Irated = 5 A)

Instrument current transformer 0.5 mA sec. (Irated = 1 A) or2.5 mA sec. (Irated = 5 A)

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances

12.7.3

Technical Data12.7 Overcurrent Protection, Ground

1326 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

10 Hz ≤ f < 0.9 frated

1.1 frated < f ≤ 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Active

Tolerances

3I0 measured via I445, method of measurement =fundamental component

1 % of the setting value or 5 mA (Irated = 1 A)or 25 mA (Irated = 5 A), (frated ± 10 %)

3I0 measured via I446, method of measurement = RMS value(33 % harmonics, in relation to fundamental component)Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)

or 25 mA (Irated = 5 A), (frated ± 10 %)

Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)or 100 mA (Irated = 5 A), (frated ± 10 %)

Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)or 100 mA (Irated = 5 A), (frated ± 10 %)

Operate time for 2 ≤ I/I threshold value ≤ 20 5 % of the setting value or +2 % current tolerance or30 ms

Dropout time for I/I threshold value ≤ 0.90 5 % of the setting value or +2 % current tolerance or30 ms

Influencing Variables for the Thresholds

Transient excess pickup in method of measurement= fundamental component, for τ > 100 ms (withcomplete unbalance)

< 5 %

Operate Curves and Dropout-Time Characteristic Curves According to IEC

Extension of the operate time during operation withtransformer inrush-current detection

Approx. 10 ms

45 Insignificantly increased tolerances will occur during the calculation of 3I0, maximum factor of 246 Insignificantly increased tolerances will occur during the calculation of 3I0, maximum factor of 2

Technical Data12.7 Overcurrent Protection, Ground

SIPROTEC 5, Overcurrent Protection, Manual 1327C53000-G5040-C017-6, Edition 11.2015

Directional Time-Overcurrent Protection, Phases

Setting Values for the Function

Rotation angle of the referencevoltage

-180o to +180o Increments of 1o

Setting Values for All Stage Types

Directional mode ForwardBackward

Method of measurement Fundamental componentRMS value

Threshold value47 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Setting Values for the Definite Time-Overcurrent Protection Stage Type

Dropout ratio 0.90 to 0.99 Increments of 0.01Time delay 0.00 s to 60.00 s Increments of 0.01 sDropout delay 0.00 s to 60.00 s Increments of 0.01 s

Setting Values for the IEC/ANSI Characteristic Curve Stage Type (Inverse-Time)

Type of characteristic curve Characteristic curves according to IEC (see Table 12-3) andANSI (see Table 12-4)

Dropout Disk emulationInstantaneous

Time multiplier 0.00 to 15.00 Increments of 0.01Minimum time of the curve 0.00 to 1.00 s Increments of 0.01 sAdditional time delay 0.00 to 60.00 s Increments of 0.01 s

Dropout Ratio for the IEC/ANSI Characteristic Curve Stage Type (Inverse-Time)

Disk emulation Approx. 0.90 * threshold valueTime multiplier Approx. 1.05 * threshold value

Approx. 0.95 * pickup value

Setting Values for Stage Type with User-Defined Characteristic Curve (Inverse Time)

Time multiplier 0.05 to 15.00 Increments of 0.01Number of value pairs for the operatecharacteristic curve

2 to 30 Increments of 1

X values of the operate curve 1.00 to 66.67 p. u. Increments of 0.01 p.u.Y values of the operate curve 0.00 s to 999.00 s Increments of 0.01 sNumber of value pairs for the dropoutcharacteristic curve

2 to 30 Increments of 1

X values of the dropout characteristiccurve

0.05 to 0.95 p. u. Increments of 0.01 p.u.

12.8

47 If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 lrated,sec.

Technical Data12.8 Directional Time-Overcurrent Protection, Phases

1328 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Y values of the dropout characteristiccurve

0.00 s to 999.00 s Increments of 0.01 s

Dropout Ratio for Stage Type with User-Defined Characteristic Curve (Inverse Time)

Disk emulation Approx. 0.90 * threshold valueTime multiplier Approx. 1.05 * threshold value

Approx. 0.95 * pickup value

Tripping and Dropout Characteristic Curves

You can select from the following tripping and dropout characteristic curves:

Table 12-3 Standard characteristic curves to IEC

Normal inverse: type A See chapter 12.5.2 Inverse Time-Overcurrent Protec-tion, Phases , Figure 12-1Very inverse: type B

Extremely inverse: type C See chapter 12.5.2 Inverse Time-Overcurrent Protec-tion, Phases , Figure 12-2Long time inverse:

Table 12-4 Standard characteristic curves to ANSI/IEEE

Inverse: type C See chapter 12.5.2 Inverse Time-Overcurrent Protec-tion, Phases , Figure 12-3Short inverse

Long inverse See chapter 12.5.2 Inverse Time-Overcurrent Protec-tion, Phases , Figure 12-4Moderately inverse

Very inverse See chapter 12.5.2 Inverse Time-Overcurrent Protec-tion, Phases , Figure 12-5Extremely inverse

Definite inverse See chapter 12.5.2 Inverse Time-Overcurrent Protec-tion, Phases , Figure 12-6

Direction Determination

Type With externally generated voltagesWith voltage memory 2 s

Forward range Vref,rot ±88o

Dropout differential forward/reverse range 1o

Directional sensitivity Unlimited for 1 and 2-phase short circuitsDynamically unlimited, stationary for 3-phase shortcircuitsApprox. 13 V phase-to-phase

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-rent functionality.Minimum absolute dropout differenceProtection-class current transformer 15 mA sec. (Irated = 1 A) or

75 mA sec. (Irated = 5 A)

Technical Data12.8 Directional Time-Overcurrent Protection, Phases

SIPROTEC 5, Overcurrent Protection, Manual 1329C53000-G5040-C017-6, Edition 11.2015

Instrument current transformer 0.5 mA sec. (Irated = 1 A) or2.5 mA sec. (Irated = 5 A)

Times

Operate time with time delay = 0 ms Approx. 37 ms + OOT 48 at 50 HzApprox. 22 ms + OOT at 60 Hz

Extension of the operate time during operation withtransformer inrush-current detection

Approx. 10 ms

Dropout Time Approx. 20 ms + OOT

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances

10 Hz ≤ f < 0.9frated

1.1 frated < f ≤ 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Active

Tolerances

Currents, method of measurement = fundamentalcomponent

1 % of the setting value or 5 mA (Irated = 1 A)or 25 mA (Irated = 5 A), (frated ± 10 %)

Currents, method of measurement = RMS value(33 % harmonics, in relation to fundamental component)Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)

or 25 mA (Irated = 5 A), (frated ± 10 %)

Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)or 100 mA (Irated = 5 A), (frated ± 10 %)

Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)or 100 mA (Irated = 5 A), (frated ± 10 %)

Definite-time operate time 1 % of the setting value or 10 msInverse-time operate time according to IEC, ANSI,user-defined characteristic curve

5 % of the setting value or +2 % current tolerance or10 ms

Inverse-time dropout time according to IEC, ANSI,user-defined characteristic curve

5 % of the setting value or +2 % current tolerance or10 ms

Direction-determination angle error 1o

Influencing Variables for Thresholds

Transient excess pickup in method of measurement = fundamental component,for τ > 100 ms (with complete unbalance)

< 5 %

48 OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays

Technical Data12.8 Directional Time-Overcurrent Protection, Phases

1330 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Directional Time-Overcurrent Protection, Ground

Setting Values for the Function Direction Determination

Method for direction determination Zero sequenceNegative sequence

Minimum V0 or V2 threshold 0.150 V to 20.000 V 0.001 VRotation angle of the reference voltage -180° to 180° 1°Forward range 0° to 180° 1°

Setting Values for All Stage Types

Direction mode ForwardReverse

Method of measurement Fundamental componentRMS value

Threshold value 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A1 A @ 1.6 Irated 0.030 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.15 A to 8.000 A Increments of 0.001 A

Setting Values for Stage Type Definite Time-Overcurrent Protection

Dropout ratio 0.90 to 0.99 Increments of 0.01Operate delay 0.00 s to 60.00 s Increments of 0.01 sDropout delay 0.00 s to 60.00 s Increments of 0.01 s

Setting Values for Stage Type Inverse Time-Overcurrent Protection (IEC/ANSI)

Type of characteristic curve Characteristic curves according to IEC and ANSIDropout Disk emulation

Instantaneous–

Time multiplier 0.00 to 15.00 Increments of 0.01Minimum time of the curve 0.00 to 1.00 s Increments of 0.01 sAdditional time delay 0.00 to 60.00 s Increments of 0.01 s

Dropout Values for Stage Type Inverse Time-Overcurrent Protection (IEC/ANSI)

Disk emulation Approx. 0.90 * threshold valueInstantaneous Approx. 1.05 * threshold value

Approx. 0.95 * pickup value

Characteristic Curves for Stage Type Inverse Time-Overcurrent Protection (IEC/ANSI)

Standard Characteristic Curves According to IEC

Normal inverse: type A Refer to the respective picture of the technical data for the non-dir-OC-ground function 12.7.2 Inverse-Time Overcurrent Protec-tion, Ground

Very inverse: type BExtremely inverse: type CLong-time inverse

Standard Characteristic Curves According to ANSI/IEEE

12.9

Technical Data12.9 Directional Time-Overcurrent Protection, Ground

SIPROTEC 5, Overcurrent Protection, Manual 1331C53000-G5040-C017-6, Edition 11.2015

Extremely inverse: type C Refer to the respective picture of the technical data for the non-dir-OC-ground function 12.7.2 Inverse-Time Overcurrent Protec-tion, Ground

Long-time inverse: type BLong-time inverseModerately inverseVery inverseExtremely inverseUniformly inverse

Setting Values for Stage Types Logarithmic Inverse Time-Overcurrent Protection

Characteristic curve: see Figure 12-13Threshold value multiplier 1.00 to 4.00 Increments of 0.01Time multiplier 0.05 to 15.00 Increments of 0.01Minimum time of the characteristic curve 0.000 s to 60.000 s Increments of 0.001 sMaximum time of the characteristic curve 0.000 s to 60.000 s Increments of 0.001 sAdditional time delay 0.000 s to 60.000 s Increments of 0.001 s

[dwloginv-300913, 2, en_US]

Figure 12-13 Operate Curve of Logarithmic Inverse-Time Characteristic

Dropout value for Stage Types Logarithmic Inverse Time-Overcurrent Protection

Dropout ratio Approx. 1.05 * threshold valueApprox. 0.95 * pickup value

Setting Values for Stage Type Logarithmic Inverse Time with Knee-Point Overcurrent Protection

Characteristic curve: see Figure 12-14Minimum time of the characteristic curve 0.00 s to 30.00 s Increments of 0.01 sKnee-point time of the curve 0.00 s to 100.00 s Increments of 0.01 s

Technical Data12.9 Directional Time-Overcurrent Protection, Ground

1332 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Maximum time of the characteristic curve 0.00 s to 200.00 s Increments of 0.01 sKnee-point value 0.030 A to 25.000 A 0.001 ACurrent at minimum time of the curve 0.030 A to 25.000 A 0.001 ATime factor 0.05 to 15.00 Increments of 0.01

[dwdrloinkn-171013, 1, en_US]

Figure 12-14 Operate Curve of the Logarithmic Inverse Time with Knee-Point Characteristic (In theExample of Threshold = 0.004 A)

Dropout value for Stage Type Logarithmic Inverse Time with Knee-Point Overcurrent Protection

Dropout ratio Approx. 0.95 * threshold value

Setting Values for Stage Type User-Defined Characteristic Curve Overcurrent Protection

Time multiplier 0.05 to 15.00 Increments of 0.01X values of the operate curve 1.00 p. u. to 66.67 p. u. Increments of 0.01 p. u.Y values of the operate curve 0.00 s to 999.00 s Increments of 0.01 sNumber of value pairs for the dropoutcharacteristic curve

2 to 30 Increments of 1

X values of the dropout characteristiccurve

0.05 p. u. to 0.95 p. u. Increments of 0.01 p. u.

Y values of the dropout characteristiccurve

0.00 s to 999.00 s Increments of 0.01 s

Dropout Values for Stage Type User-Defined Characteristic Curve Overcurrent Protection

Disk emulation Approx. 0.90 * threshold value

Technical Data12.9 Directional Time-Overcurrent Protection, Ground

SIPROTEC 5, Overcurrent Protection, Manual 1333C53000-G5040-C017-6, Edition 11.2015

Instantaneous Approx. 1.05 * threshold valueApprox. 0.95 * pickup value

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-rent functionality.Minimum absolute dropout differenceProtection-class current transformer 15 mA sec. (Irated = 1 A) or

75 mA sec. (Irated = 5 A)

Instrument current transformer 0.5 mA sec. (Irated = 1 A) or2.5 mA sec. (Irated = 5 A)

Times

The maximum pickup time with operatedelay = 0 ms

Approx. 30 ms + OOT at 50 HzApprox. 25 ms + OOT at 60 Hz

Extension of the operate time during oper-ation with inrush-current detection

Approx. 10 ms

Dropout time Approx. 20 ms + OOT

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances

10 Hz ≤ f < 0.9 frated

1.1 frated < f ≤ 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Active with reduced sensitivity

Tolerances

Currents, method of measurement = fundamentalcomponent

1 % of setting value or 5 mA (Irated = 1 A) or 25 mA(Irated = 5 A)

Currents, method of measurement = RMS value(33 % part of harmonic, referring to fundamental compo-nent)

Up to 30th harmonic1 % of setting value or 5 mA (Irated = 1 A)or 25 mA (Irated = 5 A), (frated ± 10 %)

Up to 50th harmonic, frated = 50 Hz3 % of setting value or 20 mA (Irated = 1 A)or 100 mA (Irated = 5 A), (frated ± 10 %)

Up to 50th harmonic, frated = 60 Hz4 % of setting value or 20 mA (Irated = 1 A)or 100 mA (Irated = 5 A), (frated ± 10 %)

Definite-time operate time 1 % of the setting or 10 msInverse-time operate time to IEC, ANSI, logarithmicinverse-time characteristic, logarithmic inverse time withknee-point characteristic, and user-defined character-istic curve

5 % of setting value or +2 % current tolerance or30 ms

Technical Data12.9 Directional Time-Overcurrent Protection, Ground

1334 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Inverse-time dropout time to IEC, ANSI, logarithmicinverse-time characteristic, logarithmic inverse time withknee-point characteristic, and user-defined character-istic curve

5 % of setting value or +2 % current tolerance or30 ms

Direction-determination angle error 1º

Influencing Variables for Thresholds

Transient excess pickup in method of measurement =fundamental component, for τ > 100 ms (with completeunbalance)

< 5 %

Technical Data12.9 Directional Time-Overcurrent Protection, Ground

SIPROTEC 5, Overcurrent Protection, Manual 1335C53000-G5040-C017-6, Edition 11.2015

Inrush-Current Detection

Setting Values

Operat.-range limit Imax 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Content 2nd harmonic 10 % to 45 % Increments of 1 %Duration of the cross-blocking 0.03 s to 200.00 s Increments of 0.01 s

Times

Pickup times Approx. 29 ms

Dropout Ratios

Harmonic: I2nd Harm/I1st harm 0.95

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-rent functionality.Dropout differenceProtection-class current transformer 15 mA sec. (Irated = 1 A) or

75 mA sec. (Irated = 5 A)

Instrument current transformer 0.5 mA sec. (Irated = 1 A) or2.5 mA sec. (Irated = 5 A)

Operating Range

10 Hz to 80 Hz According to specified tolerancesBehavior outside 10 Hz to 80 Hz Inactive

Tolerances

Current measurement lmax 1 % of the setting value or 5 mA

Harmonic: I2nd Harm/I1st Harm 1 % of the setting valuefor settings of l2nd Harm/1st Harm

Time delays 1 % of the setting value or 10 ms

12.10

Technical Data12.10 Inrush-Current Detection

1336 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Arc Protection

Setting Values

Threshold value I> 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Threshold value 3I0> 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

External trip initiation YesNo

Operating mode Light onlyCurrent and light

Channel Possible settings, application-dependent

Dropout Ratio

Threshold value About 0.90

Times

Shortest operate timeOperating mode = light only

Approx. 2.6 ms + OOT 49.

Shortest operate timeOperating mode = Current andlight

Approx. 4.0 ms + OOT at 50 HzApprox. 3.8 ms + OOT at 60 Hz

12.11

49 OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays, see chapter12.1.4 Relay Outputs

Technical Data12.11 Arc Protection

SIPROTEC 5, Overcurrent Protection, Manual 1337C53000-G5040-C017-6, Edition 11.2015

Instantaneous High-Current Tripping

Setting Values

Threshold value 1 A @ 100 Irated 0.030 A to 35.000 A Increments of 0.001 A5 A @ 100 Irated 0.15 A to 175.00 A Increments of 0.01 A1 A @ 50 Irated 0.030 A to 35.000 A Increments of 0.001 A5 A @ 50 Irated 0.15 A to 175.00 A Increments of 0.01 A1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Dropout Ratio 0.50 to 0.90 Increments of 0.01

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-rent functionality.Minimum absolute dropout differenceProtection-class current transformer 15 mA sec. (Irated = 1 A) or

75 mA sec. (Irated = 5 A)

Instrument current transformer 0.5 mA sec. (Irated = 1 A) or2.5 mA sec. (Irated = 5 A)

Times

Operate time for current > 2·√2·threshold value Approx. 8 ms + OOT50

Operating Range

frated ± 10 % According to specified tolerances

Behavior outside the operating range Active starting at f ≥ 36.3 Hz

Tolerances

Response tolerance, current 5 % of setting value or 10 mA at Irated = 1 A5 % of setting value or 50 mA at Irated = 5 A

Time delays 1 % of the setting value or 10 ms

12.12

50 OOT (Output Operating Time) additional delay of the output medium used, see chapter 12.1.4 Relay Outputs

Technical Data12.12 Instantaneous High-Current Tripping

1338 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Instantaneous Tripping at Switch onto Fault

Setting Values

Tripping delay 0.00 s to 60.00 s Increments of0.01 s

Tolerances

Times < 1 % of the setting value or 10 ms

12.13

Technical Data12.13 Instantaneous Tripping at Switch onto Fault

SIPROTEC 5, Overcurrent Protection, Manual 1339C53000-G5040-C017-6, Edition 11.2015

Overcurrent Protection, 1-Phase

Overcurrent Protection, 1-Phase (Stage with Definite Time-OvercurrentProtection)

Setting Values

Method of measurement Fundamental componentRMS value

Threshold value51 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Dropout ratio (fixed) 0.95 –Time delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-rent functionality.Minimum absolute dropout differenceProtection-class current transformer 15 mA sec. (Irated = 1 A) or

75 mA sec. (Irated = 5 A)

Instrument current transformer 0.5 mA sec. (Irated = 1 A) or2.5 mA sec. (Irated = 5 A)

Times

Operate time with time delay = 0 ms Approx. 15 ms + OOT52 at 50 HzApprox. 14 ms + OOT at 60 Hz

Extension of the operate time during operation withtransformer inrush-current detection

Approx. 10 ms

Dropout time Approx. 20 ms + OOT at 50 HzApprox. 17 ms + OOT at 60 Hz

Frequency Operating Range

0.9 f/frated to 1.1 f/frated According to specified tolerances

10 Hz to 0.9 f/frated

1.1 f/frated to 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Active

12.14

12.14.1

51 If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 lrated,sec.52 OOT (Output Operating Time) additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs

Technical Data12.14 Overcurrent Protection, 1-Phase

1340 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Tolerances

Currents, method of measurement = fundamentalcomponent

1 % of the setting value or 5 mA (Irated = 1 A)or 25 mA (Irated = 5 A), (frated ± 10 %)

Currents, method of measurement = RMS value(33 % harmonics, in relation to fundamental component)Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)

or 25 mA (Irated = 5 A), (frated ± 10 %)

Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)or 100 mA (Irated = 5 A), (frated ± 10 %)

Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)or 100 mA (Irated = 5 A), (frated ± 10 %)

Time delays 1 % of the setting value or 10 ms

Influencing Variables for Thresholds

Transient excess pickup in method of measurement = fundamental component,for τ > 100 ms (with complete unbalance)

< 5 %

Overcurrent Protection, 1-Phase (Stage Inverse Time-Overcurrent Protection)

Setting Values

Method of measurement Fundamental componentRMS value

Threshold value53 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Dropout Disk emulationInstantaneous

Time multiplier 0.05 to 15.00 Increments of 0.01

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-rent functionality.Minimum absolute dropout differenceProtection-class current transformer 15 mA sec. (Irated = 1 A) or

75 mA sec. (Irated = 5 A)

Instrument current transformer 0.5 mA sec. (Irated = 1 A) or2.5 mA sec. (Irated = 5 A)

12.14.2

53 If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 lrated,sec.

Technical Data12.14 Overcurrent Protection, 1-Phase

SIPROTEC 5, Overcurrent Protection, Manual 1341C53000-G5040-C017-6, Edition 11.2015

Operate Curves and Dropout-Time Characteristic Curves According to IEC

Extension of the operate time during operation with transformer inrush-current detection

Approx. 10 ms

The tripping characteristic curves and dropout characteristic curves according to IEC can be found in theTechnical Data chapter under Inverse Time-Overcurrent Protection.

Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE

The tripping characteristic curves and dropout characteristic curves according to ANSI/IEEE can be found inthe Technical Data chapter under Inverse Time-Overcurrent Protection.

Frequency Operating Range

0.9 f/frated to 1.1 f/frated According to specified tolerances

10 Hz to 0.9 f/frated

1.1 f/frated to 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Active

Tolerances

Currents, method of measurement = fundamentalcomponent

1 % of the setting value or 5 mA (Irated = 1 A)or 25 mA (Irated = 5 A), (frated ± 10 %)

Currents, method of measurement = RMS value(33 % harmonics, in relation to fundamental component)Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)

or 25 mA (Irated = 5 A), (frated ± 10 %)

Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)or 100 mA (Irated = 5 A), (frated ± 10 %)

Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)or 100 mA (Irated = 5 A), (frated ± 10 %)

Operate time for 2 ≤ I/I threshold value ≤ 20 5 % of the setting value or +2 % current tolerance or30 ms

Dropout time for I/I threshold value ≤ 0.90 5 % of the setting value or +2 % current tolerance or30 ms

Influencing Variables for Thresholds

Transient excess pickup in method of measurement = fundamental component,for τ > 100 ms (with complete unbalance)

< 5 %

Overcurrent Protection, 1-Phase with User-Defined Characteristic Curve

Setting Values

Method of measurement Fundamental componentRMS value

Threshold value 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

12.14.3

Technical Data12.14 Overcurrent Protection, 1-Phase

1342 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Dropout Disk emulationInstantaneous

Time multiplier 0.05 to 15.00 Increments of 0.01Number of value pairs for the operate curve 2 to 30 Increments of 1X values of the operate curve 1.00 to 66.67 p. u. Increments of 0.01 p.u.Y values of the operate curve 0.00 s to 999.00 s Increments of 0.01 sNumber of value pairs for the dropout characteristiccurve

2 to 30 Increments of 1

X values of the dropout characteristic curve 0.05 to 0.95 p. u. Increments of 0.01 p.u.Y values of the dropout characteristic curve 0.00 s to 999.00 s Increments of 0.01 s

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-rent functionality.Minimum absolute dropout differenceProtection-class current transformer 15 mA sec. (Irated = 1 A) or

75 mA sec. (Irated = 5 A)

Instrument current transformer 0.5 mA sec. (Irated = 1 A) or2.5 mA sec. (Irated = 5 A)

Frequency Operating Range

0.9 f/frated to 1.1 f/frated According to specified tolerances

10 Hz to 0.9 f/frated

1.1 f/frated to 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Active with less sensitivity

Tolerances

Currents, method of measurement = fundamentalcomponent

1 % of the setting value or 5 mA (Irated = 1 A)or 25 mA (Irated = 5 A), (frated ± 10 %)

Currents, method of measurement = RMS value(33 % harmonics, in relation to fundamental component)Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)

or 25 mA (Irated = 5 A), (frated ± 10 %)

Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)or 100 mA (Irated = 5 A), (frated ± 10 %)

Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)or 100 mA (Irated = 5 A), (frated ± 10 %)

Operate time for 2 ≤ I/I threshold value ≤ 20 5 % of the setting value or +2 % current tolerance or30 ms

Dropout time for I/I threshold value ≤ 0.90 5 % of the setting value or +2 % current tolerance or30 ms

Technical Data12.14 Overcurrent Protection, 1-Phase

SIPROTEC 5, Overcurrent Protection, Manual 1343C53000-G5040-C017-6, Edition 11.2015

Influencing Variables for Thresholds

Transient excess pickup in method of measurement = fundamental component,for τ > 100 ms (with complete unbalance)

< 5 %

Operate Curves and Dropout-Time Characteristic Curves According to IEC

Extension of the operate time during operation with transformer inrush-current detection

Approx. 10 ms

Technical Data12.14 Overcurrent Protection, 1-Phase

1344 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Overcurrent Protection, 1-Phase (Fast Stage)

Setting Values

Threshold value 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Dropout ratio (fixed) 0.90 to 0.99 Increments of 0.01Time delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-rent functionality.Minimum absolute dropout differenceProtection-class current transformer 15 mA sec. (Irated = 1 A) or

75 mA sec. (Irated = 5 A)

Instrument current transformer 0.5 mA sec. (Irated = 1 A) or2.5 mA sec. (Irated = 5 A)

Times

Operate time with time delay = 0 ms Approx. 8 ms + OOT54

Dropout time Approx. 25 ms + OOT

Frequency Operating Range

0.9 f/frated to 1.1 f/frated According to specified tolerances

10 Hz to 0.9 f/frated

1.1 f/frated to 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Active

Tolerances

Pickup tolerance, current 5 % of the setting value or 10 mA (Irated = 1 A)or 50 mA (Irated = 5 A)

Time delays 1 % of the setting value or 10 ms

12.15

54 OOT (Output Operating Time) additional time delay of the output medium used, for example, 5 ms with fast relay

Technical Data12.15 Overcurrent Protection, 1-Phase (Fast Stage)

SIPROTEC 5, Overcurrent Protection, Manual 1345C53000-G5040-C017-6, Edition 11.2015

Non-Directional Intermittent Ground-Fault Protection

Setting Values

Threshold value3I0> interm.

For current transformer type protec-tion and Irated = 1 A

0.030 A to 35.000 A Increments of 0.001 A

For current transformer type protec-tion and Irated = 5 A

0.15 A to 175.00 A Increments of 0.01 A

For IN transformertype sensitiveand IN-rated = 1 A

For Iph-rated = 1 A 0.001 A to 35.000 A Increments of 0.001 A

For Iph-rated = 5 A 0.001 A to 175.000 A Increments of 0.001 A

For IN transformertype sensitiveand IN-rated = 5 A

For Iph-rated = 1 A 0.005 A to 35.000 A Increments of 0.001 A

For Iph-rated = 5 A 0.005 A to 175.000 A Increments of 0.001 A

Number of pickups until intermittent ground fault 2 to 10 Increments of 1Pickup extension time 0.00 s to 10.00 s Increments of 0.01 sSum of extended pickup times 0.00 s to 100.00 s Increments of 0.01 sReset time 1.00 s to 600.00 s Increments of 0.01 s

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-rent functionality.Minimum absolute dropout differenceProtection-class current transformer 15 mA sec. (Irated = 1 A) or

75 mA sec. (Irated = 5 A)

Instrument current transformer 0.5 mA sec. (Irated = 1 A) or2.5 mA sec. (Irated = 5 A)

Times

Operate time with time delay = 0 ms Approx. 25 ms + OOT55 at 50 HzApprox. 23 ms + OOT at 60 Hz

Dropout time Approx. 25 ms + OOT at 50 HzApprox. 22 ms + OOT at 60 Hz

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances

10 Hz ≤ f < 0.9 frated

1.1 frated < f ≤ 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Active with less sensitivity

12.16

55 OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays

Technical Data12.16 Non-Directional Intermittent Ground-Fault Protection

1346 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Tolerances

Currents -3I0 via protection-class current transformers:1 % of setting value or 5 mA (Irated = 1 A)or 25 mA (Irated = 5 A)

-3I0 via sensitive current transformer:1 % of setting value or 0.1 mA (Irated = 1.6 A)or 0.5 mA (Irated = 8 A)

Times 1 % of the setting value or ± 10 ms

Technical Data12.16 Non-Directional Intermittent Ground-Fault Protection

SIPROTEC 5, Overcurrent Protection, Manual 1347C53000-G5040-C017-6, Edition 11.2015

Directional Intermittent Ground-Fault Protection

Setting Values

Threshold value 3I0> For current transformer typeprotection and Irated = 1 A

0.030 A to 35.000 A Increments of 0.001 A

For current transformer typeprotection and Irated = 5 A

0.15 A to 175.00 A Increments of 0.01 A

For IN transformertype sensitive andIN-rated = 1 A

For Iph-rated = 1 A 0.001 A to 35.000 A Increments of 0.001 A

For Iph-rated = 5 A 0.001 A to 175.00 A Increments of 0.001 A

For IN transformertype sensitive andIN-rated = 5 A

For Iph-rated = 1 A 0.005 A to 35.000 A Increments of 0.001 A

For Iph-rated = 5 A 0.005 A to 175.00 A Increments of 0.001 A

Number of pulses until intermittent groundfault

2 to 10 Increments of 1

Pickup extension time 0.00 s to 10.00 s Increments of 0.01 sSum of extended pickup times 0.00 s to 100.00 s Increments of 0.01 sReset time 1.00 s to 600.00 s Increments of 0.01 sNumber of pulses for operate 2 to 100 Increments of 1

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-rent functionality.Minimum absolute dropout differenceProtection-class current transformer 15 mA sec. (Irated = 1 A) or

75 mA sec. (Irated = 5 A)

Instrument current transformer 0.5 mA sec. (Irated = 1 A) or2.5 mA sec. (Irated = 5 A)

Times

Pickup time Approx. 30 ms + OOT56 at 50 HzApprox. 23 ms + OOT at 60 Hz

Dropout time Approx. 25 ms + OOT at 50 HzApprox. 22 ms + OOT at 60 Hz

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances

10 Hz ≤ f < 0.9 frated

1.1 frated < f ≤ 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Active with less sensitivity

12.17

56 OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays

Technical Data12.17 Directional Intermittent Ground-Fault Protection

1348 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Tolerances

Currents 3I0 via protection-class current transformers:1 % of the setting value or 5 mA (Irated = 1 A) or 25 mA (Irated = 5 A)

3I0 via sensitive current transformer:1 % of the setting value or 0.1 mA (Irated = 1.6 A) or 0.5 mA (Irated = 8 A)

Times 1 % of the setting value or ± 10 ms

Technical Data12.17 Directional Intermittent Ground-Fault Protection

SIPROTEC 5, Overcurrent Protection, Manual 1349C53000-G5040-C017-6, Edition 11.2015

Sensitive Ground-Fault Detection

General

Setting Values

Decay time V0 0.06 s to 0.20 s Increments of 0.01 sDropout delay 0.00 s to 60.00 s Increments of 0.01 sCore balancecurrent transformercurrent 1Core balancecurrent transformercurrent 2

Protection-classcurrent trans-formers

For Iph-rated = 1 A 0.030 A to35.000 A

Increments of 0.001 A

For Iph-rated = 5 A 0.15 A to 175.00 A Increments of 0.01 A

For IN transformertype sensitive andIN-rated = 1 A

For Iph-rated = 1 A 0.001 A to35.000 A

Increments of 0.001 A

For Iph-rated = 5 A 0.001 A to175.000 A

Increments of 0.001 A

For IN transformertype sensitive andIN-rated = 5 A

For Iph-rated = 1 A 0.005 A to35.000 A

Increments of 0.001 A

For Iph-rated = 5 A 0.005 A to175.000 A

Increments of 0.001 A

Core balance current transformer angle correction F1Core balance current transformer angle correction F2

0.0° to 5.0° Increments of 0.1°

Frequency Operating Range

0.9 f/frated to 1.1 f/frated According to specified tolerances

10 Hz to 0.9 f/frated

1.1 f/frated to 80 HzSlightly expanded tolerances 57

f < 10 Hzf > 80 Hz

Active with less sensitivity 58

Tolerances

Currents -3I0 via sensitive current transformer:1 % of the setting value or 0.1 mA (Irated = 1.6 A)or 0.5 mA (Irated = 8 A, frated ± 10 %)

-3I0 via protection-class current transformers:1 % of the setting value or 5 mA (Irated = 1 A)or 25 mA (Irated = 5 A, frated ± 10 %)

Voltages 1 % of the setting value or 0.05 VTimes 1 % of the setting value or ±10 msDirection-calculation angle error ≤ 1° at 3I0 > 5 mA, V0 = 0.6 V

≤ 2° at 3I0 ≤ 5 mA, V0 = 0.6 V

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

12.18

12.18.1

57 Transient ground-fault stage is inactive58 Transient ground-fault stage is inactive

Technical Data12.18 Sensitive Ground-Fault Detection

1350 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overcurrent/overvoltage and of 105 %for undercurrent/undervoltage functionality.Minimum absolute dropout differenceProtection-class current transformer 15 mA sec. (Irated = 1 A) or

75 mA sec. (Irated = 5 A)

Instrument current transformer 0.5 mA sec. (Irated = 1 A) or2.5 mA sec. (Irated = 5 A)

Voltage transformer 150 mV sec.

Overvoltage Protection Stage with Zero-Sequence System/Residual Voltage

You can find the the Technical data of the overvoltage protection stage with zero-sequence system/residualvoltage chapter 12.29 Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage .

Directional Overcurrent-Protection Stage with cos φ or sin φ Measurement

Setting Values

Direction method of measurement cos φsin φ

Threshold value3I0>Minimum direc-tional 3I0> fordirection deter-mination

Protection-class currenttransformers

For Iph-rated = 1 A 0.030 A to 35.000 A Increments of 0.001 A

For Iph-rated = 5 A 0.15 A to 175.00 A Increments of 0.01 A

For IN transformer typesensitive and IN-rated = 1A

For Iph-rated = 1 A 0.001 A to 35.000 A Increments of 0.001 A

For Iph-rated = 5 A 0.001 A to 175.000 A Increments of 0.001 A

For IN transformer typesensitive and IN-rated = 5A

For Iph-rated = 1 A 0.005 A to 35.000 A Increments of 0.001 A

For Iph-rated = 5 A 0.005 A to 175.000 A Increments of 0.001 A

Threshold value V0> 0.300 V to 200.000 V Increments of 0.001 VTime delay of the direction determination 0.00 s to 60.00 s Increments of 0.01 sα1 constraint of the direction rangeα2 constraint of the direction range

1° to 15° Increments of 1°

Angle correction φ -45° to 45° Increments of 1°Tripping delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-rent functionality.Minimum absolute dropout differenceProtection-class current transformer 15 mA sec. (Irated = 1 A) or

75 mA sec. (Irated = 5 A)

Instrument current transformer 0.5 mA sec. (Irated = 1 A) or2.5 mA sec. (Irated = 5 A)

12.18.2

12.18.3

Technical Data12.18 Sensitive Ground-Fault Detection

SIPROTEC 5, Overcurrent Protection, Manual 1351C53000-G5040-C017-6, Edition 11.2015

Times

Operate time with time delay = 0 ms Approx. 32 ms + OOT59 at 50 HzApprox. 29 ms + OOT at 60 Hz

Extension of the operate time during operation with transformer inrush-current detection

Approx. 10 ms

Dropout time Approx. 32 ms + OOT at 50 HzApprox. 27 ms + OOT at 60 Hz

Directional Overcurrent-Protection Stage with 3I0-φ(V,I) Measurement

Setting Values

Threshold value3I0>

Protection-classcurrent transformers

For Iph-rated = 1 A 0.030 A to 35.000 A Increments of 0.001 A

For Iph-rated = 5 A 0.15 A to 175.00 A Increments of 0.01 A

For IN transformer typesensitive and IN-rated

= 1 A

For Iph-rated = 1 A 0.001 A to 35.000 A Increments of 0.001 A

For Iph-rated = 5 A 0.001 A to 175.000 A Increments of 0.001 A

For IN transformer typesensitive and IN-rated

= 5 A

For Iph-rated = 1 A 0.005 A to 35.000 A Increments of 0.001 A

For Iph-rated = 5 A 0.005 A to 175.000 A Increments of 0.001 A

Min. V0> for direction determination 0.300 V to 200.000 V Increments of 0.001 VTime delay of the direction determination 0.00 s to 60.00 s Increments of 0.01 sRotation angle of the reference voltage -180° to 180° Increments of 1°Forward range +/- 0° to 90° Increments of 1°Tripping delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-rent functionality.Minimum absolute dropout differenceProtection-class current transformer 15 mA sec. (Irated = 1 A) or

75 mA sec. (Irated = 5 A)

Instrument current transformer 0.5 mA sec. (Irated = 1 A) or2.5 mA sec. (Irated = 5 A)

Times

Operate time with time delay = 0 ms Approx. 23 ms + OOT60 at 50 HzApprox. 21 ms + OOT at 60 Hz

Extension of operate time during operation with transformerinrush-current detection

Approx. 10 ms

Dropout time Approx. 21 ms + OOT at 50 HzApprox. 20 ms + OOT at 60 Hz

12.18.4

59 OOT (Output Operating Time) additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs60 OOT (Output Operating Time) additional delay of the output medium used, see chapter 12.1.4 Relay Outputs

Technical Data12.18 Sensitive Ground-Fault Detection

1352 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Directional Overcurrent-Protection Stage with B0 or G0 Measurement(Admittance)

Setting Values

Direction method of measurement B0G0

ReleaseThreshold value3I0>

Protection-classcurrent transformers

For Iph-rated = 1 A 0.030 A to 35.000 A Increments of 0.001 A

For Iph-rated = 5 A 0.15 A to 175.00 A Increments of 0.01 A

For IN transformer typesensitive and IN-rated =1 A

For Iph-rated = 1 A 0.001 A to 35.000 A Increments of 0.001 A

For Iph-rated = 5 A 0.001 A to 175.000 A Increments of 0.001 A

For IN transformer typesensitive and IN-rated =5 A

For Iph-rated = 1 A 0.005 A to 35.000 A Increments of 0.001 A

For Iph-rated = 5 A 0.005 A to 175.000 A Increments of 0.001 A

Threshold value V0> 0.300 V to 200.000 V Increments of 0.001 VThreshold value Y0> 0.10 mS to 100.00 mS Increments of 0.01 mSTime delay of direction determination 0.00 s to 60.00 s Increments of 0.01 sα1 constraint of direction rangeα2 constraint of direction range

1° to 15° Increments of 1°

Angle correction φ -45° to 45° Increments of 1°Tripping delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overvoltage and of 105 % for under-voltage functionality.Minimum absolute dropout difference 150 mV sec.

Times

Operate time with time delay = 0 ms Approx. 32 ms + OOT61 at 50 HzApprox. 29 ms + OOT at 60 Hz

Extension of operate time during opera-tion with transformer inrush-currentdetection

Approx. 10 ms

Dropout time Approx. 32 ms + OOT at 50 HzApprox. 27 ms + OOT at 60 Hz

Tolerances

Admittance 1 % of the setting value or 0.05 mS (Irated = 1.6 A) or 0.25 mS(Irated = 8 A), (frated = ± 10 %)

12.18.5

61 OOT (Output Operating Time) additional delay of the output medium used, see chapter 12.1.4 Relay Outputs

Technical Data12.18 Sensitive Ground-Fault Detection

SIPROTEC 5, Overcurrent Protection, Manual 1353C53000-G5040-C017-6, Edition 11.2015

Sensitive Ground-Current Protection with Y0

Setting Values

V0> threshold value 0.300 V to 200.000 V Increments of 0.001 VThreshold Y0> 0.10 mS to 100.00 mS Increments of 0.01 mSPickup delay 0.00 s to 60.00 s Increments of 0.01 sOperate delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overvoltage and of 105 % for under-voltage functionality.Minimum absolute dropout difference 150 mV sec.

Times

Operate time with time delay = 0 ms Approx. 32 ms + OOT62 at 50 HzApprox. 29 ms + OOT at 60 Hz

Extension of operate time during operationwith transformer inrush-current detection

Approx. 10 ms

Dropout time Approx. 32 ms + OOT at 50 HzApprox. 27 ms + OOT at 60 Hz

Tolerances

Admittance 1 % of the setting value or 0.05 mS (Irated = 1.6 A) or 0.25 mS(Irated = 8 A), (frated = ± 10 %)

Transient Ground-Fault Stage

Setting Values

Threshold value3I0>

Protection-classcurrent transformers

For Iph-rated = 1 A 0.030 A to 35.000 A Increments of 0.001 A

For Iph-rated = 5 A 0.15 A to 175.00 A Increments of 0.01 A

For IN transformertype sensitive and IN-

rated = 1 A

For Iph-rated = 1 A 0.001 A to 1.600 A Increments of 0.001 A

For Iph-rated = 5 A 0.005 A to 8.000 A Increments of 0.001 A

For IN transformertype sensitive and IN-

rated = 5 A

For Iph-rated = 1 A 0.001 A to 1.600 A Increments of 0.001 A

For Iph-rated = 5 A 0.005 A to 8.000 A Increments of 0.001 A

Threshold value V0> 0.300 V to 200.000 V Increments of 0.001 VTripping delay 0.00 s to 60.00 s Increments of 0.01 s

12.18.6

12.18.7

62 OOT (Output Operating Time) additional delay of the output medium used, see chapter 12.1.4 Relay Outputs

Technical Data12.18 Sensitive Ground-Fault Detection

1354 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Times

Operate time with time delay = 0 ms Approx. 115 ms + OOT63 at 50 HzApprox. 112 ms + OOT at 60 Hz

Dropout time Approx. 20 ms + OOT at 50 HzApprox. 15 ms + OOT at 60 Hz

Sensitive Ground-Current Protection with 3I0

Setting Values

Method of Measurement Fundamental componentRMS value

Threshold value3I0>

Protection-classcurrent transformers

For Iph-rated = 1 A 0.030 A to 35.000 A Increments of 0.001A

For Iph-rated = 5 A 0.15 A to 175.00 A Increments of 0.01 A

For transformer typeI-sensitive andIN-rated = 1 A

For Iph-rated = 1 A 0.001 A to 35.000 A Increments of 0.001A

For Iph-rated = 5 A 0.001 A to 175.000 A Increments of 0.001A

For transformer typeI-sensitive andIN-rated = 5 A

For Iph-rated = 1 A 0.005 A to 35.000 A Increments of 0.001A

For Iph-rated = 5 A 0.005 A to 175.000 A Increments of 0.001A

Pickup delay 0.00 s to 60.00 s Increments of 0.01 sTripping delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-rent functionality.Minimum absolute dropout differenceProtection-class current transformer 15 mA sec. (Irated = 1 A) or

75 mA sec. (Irated = 5 A)

Instrument current transformer 0.5 mA sec. (Irated = 1 A) or2.5 mA sec. (Irated = 5 A)

Times

Operate time with time delay = 0 ms Approx. 25 ms + OOT64 at 50 HzApprox. 23 ms + OOT at 60 Hz

Extension of the operate time during operation with trans-former inrush-current detection

Approx. 10 ms

Dropout time Approx. 25 ms + OOT at 50 HzApprox. 22 ms + OOT at 60 Hz

12.18.8

63 OOT (Output Operating Time) additional delay of the output medium used, see chapter 12.1.4 Relay Outputs64 OOT (Output Operating Time) additional delay of the output medium used, see chapter 12.1.4 Relay Outputs

Technical Data12.18 Sensitive Ground-Fault Detection

SIPROTEC 5, Overcurrent Protection, Manual 1355C53000-G5040-C017-6, Edition 11.2015

Undercurrent Protection

Setting Values

Method of measurement Fundamental componentRMS value

Threshold value I< 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Time delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-rent functionality.Minimum absolute dropout differenceProtection-class current transformer 15 mA sec. (Irated = 1 A) or

75 mA sec. (Irated = 5 A)

Instrument current transformer 0.5 mA sec. (Irated = 1 A) or2.5 mA sec. (Irated = 5 A)

Times

Operate time Approx. 25 ms + OOT65 at 50 HzApprox. 22 ms + OOT at 60 Hz

Dropout time Approx. 25 ms + OOT at 50 HzApprox. 22 ms + OOT at 60 Hz

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 f/frated According to specified tolerances

10 Hz to 0.9 f/frated

1,1 f/frated to 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Inactive

Tolerances

Currents, method of measurement = fundamentalcomponent

1 % of setting value or 5 mA (Irated = 1 A)or 25 mA (Irated = 5 A), (frated ± 10 %)

Currents, method of measurement = RMS value(33 % portion harmonic, referring to fundamental component)Up to 30th harmonic 1 % of setting value or 5 mA (Irated = 1 A)

or 25 mA (Irated = 5 A), (frated ± 10 %)

12.19

65 OOT (Output Operating Time) additional delay of the output medium used, for example, 5 ms with fast relays, see Chapter RelayOutputs

Technical Data12.19 Undercurrent Protection

1356 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Up to 50th harmonic, frated = 50 Hz 3 % of setting value or 20 mA (Irated = 1 A)or 100 mA (Irated = 5 A), (frated ± 10 %)

Up to 50th harmonic, frated = 60 Hz 4 % of setting value or 20 mA (Irated = 1 A)or 100 mA (Irated = 5 A), (frated ± 10 %)

Time delays 1 % of the setting value or 10 ms

Technical Data12.19 Undercurrent Protection

SIPROTEC 5, Overcurrent Protection, Manual 1357C53000-G5040-C017-6, Edition 11.2015

Negative-Sequence Protection

Stage with Definite-Time Characteristic Curve

Setting Values

Reference value for I2 (Iref) Rated object current Irated, obj.

Positive-sequence current I1Pickup value 5.0 % to 999.9 % l2/lref Increments of 0.1

Dropout ratio 0.40 to 0.99 Increments of 0.01 Time delay 0.00 s to 60.00 s Increments of 0.01 sRelease current(minimum currentrelease)

1 A @ 50 and 100 Irated 0.030 A to 10.000 A Increments of 0.001 A5 A @ 50 and 100 Irated 0.15 A to 50.00 A Increments of 0.01 A1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Maximum phasecurrent (maximumcurrent limiting)

1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:• Dropout difference derived from the parameter Dropout ratio• Dropout difference of 3 % of the object rated current

Times

Pickup time Approx. 40 ms + OOT66 at 50 HzApprox. 35 ms + OOT at 60 Hz

Dropout time Approx. 35 ms + OOT

Current Operating Range

Current range At least one phase current ≥ setting value Irelease

All phase currents ≤ setting value Iph, max

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances

10 Hz ≤ 0.9 frated

1.1 frated< f ≤ 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Inactive

12.20

12.20.1

66 OOT (Output Operating Time) additional delay of the output medium used, see chapter 12.1.4 Relay Outputs

Technical Data12.20 Negative-Sequence Protection

1358 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Tolerances

Pickup valueI2/Irated, obj Approx. 2 % of the setting value or 0.8 % of the absolute value

I2/I1 Approx. 2 % of the setting value or 4 % of the absolute value (I1 > 50mA (Irated = 1 A) or 250 mA (Irated = 5 A))

Time delays 1 % of the setting value or 10 ms

Stage with Inverse-Time Characteristic Curve

Setting Values

Reference value for I2 (Iref) Rated object current Irated,obj.

Positive-sequence current I1Pickup value 5.0 % to 999.9 % l2/lref Increments of 0.1

Dropout Disk emulationInstantaneous

Time multiplier 0.05 to 15.00 Increments of 0.01Release current(minimum currentrelease)

1 A @ 50 and 100 Irated 0.030 A to 10.000 A Increments of 0.001 A5 A @ 50 and 100 Irated 0.15 A to 50.00 A Increments of 0.01 A1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Maximum phasecurrent (maximumcurrent limiting)

1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:• Dropout difference derived from the parameter Dropout ratio• Dropout difference of 3 % of the object rated current

Times

Pickup time Approx. 40 ms + OOT67 at 50 HzApprox. 35 ms + OOT at 60 Hz

Dropout time Approx. 35 ms + OOT

Dropout Ratio

Disk emulation Approx. 0.90 ⋅ threshold valueInstantaneous Approx. 1.05 ⋅ threshold value

Approx. 0.95 ⋅ pickup value

Operate and Dropout Characteristic Curves

You can select from the following operate and dropout characteristic curves:

12.20.2

67 OOT (Output Operating Time) additional delay of the output medium used, see chapter 12.1.4 Relay Outputs

Technical Data12.20 Negative-Sequence Protection

SIPROTEC 5, Overcurrent Protection, Manual 1359C53000-G5040-C017-6, Edition 11.2015

Table 12-5 Standard Characteristic Curves to IEC

Normal inverse: type A See chapter 12.5.2 Inverse Time-Overcurrent Protection, Phases ,Figure 12-1Very inverse: type B

Extremely inverse: type C See chapter 12.5.2 Inverse Time-Overcurrent Protection, Phases ,Figure 12-2Long-time inverse: type B

Table 12-6 Standard Characteristic Curves to ANSI

Inverse: type C See chapter 12.5.2 Inverse Time-Overcurrent Protection, Phases ,Figure 12-3Short inverse

Long inverse See chapter 12.5.2 Inverse Time-Overcurrent Protection, Phases ,Figure 12-4Moderately inverse

Very inverse See chapter 12.5.2 Inverse Time-Overcurrent Protection, Phases ,Figure 12-5Extremely inverse

Definite inverse See chapter 12.5.2 Inverse Time-Overcurrent Protection, Phases ,Figure 12-6

Extension of the Operating Time

Extension of the operate timeduring operation with transformerinrush-current detection

Approx. 10 ms

Current Operating Range

Current range at least one phase current ≥ setting value Irelease

all phase currents ≤ setting value Iph, max

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances

10 Hz ≤ 0.9 frated

1.1 frated< f ≤ 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Inactive

Tolerances

Reference value = rated currentPickup value Approx. 2 % of the setting value or 0.8 % of the absolute valueOperate time for 2 ≤ I/I thresholdvalue ≤ 20

5 % of the setting value or + 2 % of the current tolerance or 30 ms

Dropout time for I/I threshold value≤ 0.90

5 % of the setting value or + 2 % of the current tolerance or 30 ms

Reference value = pos. seq. currentPickup value Approx. 2 % of the setting value or 4 % of the absolute value (I1 > 50

mA (Irated = 1 A) or 250 mA (Irated = 5 A))

Operate time for 2 ≤ I/I thresholdvalue ≤ 20

5 % of the setting value or + 2 % of the current tolerance or 30 ms

Dropout time for I/I threshold value≤ 0.90

5 % of the setting value or + 2 % current tolerance or 30 ms

Technical Data12.20 Negative-Sequence Protection

1360 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Directional Negative-Sequence Protection with Definite-Time Delay

Setting Values

Directional mode Forward, backward, non-directionalStabilization with phase currents 0 % to 30 % Increments of 1 %

Threshold value (pickup value) at IN-rated = 1 A 0.030 A to 35.000 A Increments of 0.001 A

Threshold value (pickup value) at IN-rated = 5 A 0.15 A to 175.00 A Increments of 0.01 A

Extension time of the blocking after a 1-pole pause 0.00 s to 60.00 s Increments of 0.01 s

Setting Values for Direction Determination

Minimum negative-sequence system voltage V2 0.150 V to 20.000 V Increments of 0.001 VMinimum negative-sequence systemcurrent I2

For Irated = 1 A 0.030 A to 10.000 A Increments of 0.001 A

For Irated = 5 A 0.15 A to 50.00 A Increments of 0.01 A

Upper limit angle forward, β 0o to 360o Increments of 1o

Lower limit angle forward, α 0o to 360o Increments of 1o

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:• Dropout difference derived from the parameter Dropout ratio• Dropout difference of 3 % of the object rated current

Times

Operate time with time delay = 0 ms Approx. 40 ms + OOT68 at 50 HzApprox. 40 ms + OOT at 60 Hz

Dropout time Approx. 39 ms + OOT

Operating Range

10 Hz to 80 Hz According to specified tolerancesOutside 10 Hz to 80 Hz Not active

Tolerances

Threshold values:Negative-sequence voltage V2 1 % of the setting value or 0.5 VNegative-sequence current I2 2 % of the setting value or 10 mA at Irated = 1 A

1 % of the setting value or 5 mA at Irated = 5 A

Times:Independent time delays 1 % of the setting value or 10 ms

Limit angle in determining the direction 5o

12.21

68 OOT (Output Operating Time) additional delay of the output medium used, see chapter 12.1.4 Relay Outputs

Technical Data12.21 Directional Negative-Sequence Protection with Definite-Time Delay

SIPROTEC 5, Overcurrent Protection, Manual 1361C53000-G5040-C017-6, Edition 11.2015

Thermal Overload Protection

Setting Values/Increments

Threshold current warning 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Threshold thermal warn. 50% to 100% Increments of 1 %Dropout threshold operate 50% to 99% Increments of 1 %Emerg. start T overtravel 0 s to 15 000 s Increments of 10 sK-factor acc. to IEC 60225-8 0.10 to 4.00 Increments of 0.01Thermal time constant 10 s to 60 000 s Increments of 1 sCooling time constant 10 s to 60 000 s Increments of 1 sImax thermal 1 A @ 50 and 100 Irated 0.030 A to 10.000 A Increments of 0.001 A

5 A @ 50 and 100 Irated 0.15 A to 50.00 A Increments of 0.01 A1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Imin cooling 1 A @ 50 and 100 Irated 0.000 A to 10.000 A Increments of 0.001 A5 A @ 50 and 100 Irated 0.00 A to 50.00 A Increments of 0.01 A1 A @ 1.6 Irated 0.000 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.000 A to 8.000 A Increments of 0.001 A

temperature rise at Irated 40 K to 200 K Increments of 1 KDefault temperature -55°C to 55°C Increments of 1°CMinimal temperature -55°C to 40°C Increments of 1°C

Dropout Ratios

Tripping threshold (fixed at 100 %) Dropout if value drops below operate indication dropoutthreshold

Thermal warning threshold About 0.99 of the setting valueCurrent warning threshold About 0.95 of the setting value

Frequency Range of the Input Signals

The function captures input signals up to the 50th harmonic.

Tolerances

With reference to k* Irated For Irated = 1 A 2 % or 10 mA, class 2 % acc. to IEC 60255-8

For Irated = 5 A 2 % or 50 mA, class 2 % acc. to IEC 60255-8

With reference to operate time 3 % or 1 s, class 3 % acc. to IEC 60255-8 for I/(k *Irated) > 1.25

Operate Curve

Operate curve

12.22

Technical Data12.22 Thermal Overload Protection

1362 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

The following meaningsapply:

t Operate timeτth Time constant

I Current load currentIpreload Preload current

k Setting factor according to VDE 0435 part 3011or IEC 60255-8 (K factor)

Irated, obj Rated current of the protected object

Technical Data12.22 Thermal Overload Protection

SIPROTEC 5, Overcurrent Protection, Manual 1363C53000-G5040-C017-6, Edition 11.2015

[dwauslke-100611-01.tif, 1, en_US]

Figure 12-15 Operate Curve of Overload Protection

Technical Data12.22 Thermal Overload Protection

1364 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Unbalanced-Load Protection

Setting Values

Maximum continuously perm. I2 3.0 % to 30.0 % l2/lrated,machine Increments of 0.1 %

Unbalanced load factor K 1.0 s to 100.0 s Increments of 0.1 sWarning delay 0.0 s to 60.0 s; ∞ Increments of 0.1 sCooling time thermal replica 0 s to 50 000 s Increments of 1 s

Dropout Ratio

Maximum continuously perm. I2 Approx. 0.95

Operate Characteristics

Characteristic of the thermal replica

Where: tI2Perm Permissible application time of the negative-sequence current

K Unbalanced load factor KI2/Irated,machine Unbalanced load (negative-sequence current/

rated current of the machine)

[dwunbaop-300913, 1, en_US]

Figure 12-16 Thermal Characteristic for Unbalanced Load Protection

Times

Pickup time of the warning stage Approx. 60 ms + OOT69 at 50 HzApprox. 50 ms + OOT at 60 Hz

Dropout time Approx. 50 ms or better

12.23

69 OOT (Output Operating Time) additional delay of the output medium used, for example, 5 ms with fast relays

Technical Data12.23 Unbalanced-Load Protection

SIPROTEC 5, Overcurrent Protection, Manual 1365C53000-G5040-C017-6, Edition 11.2015

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances

10 Hz ≤ f < 0.9 frated

1.1 frated < f ≤ 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Inactive

Tolerances

Negative-sequence current I2 Approx. 3 % of setting value or 0.030 A at Irated = 1 AApprox. 3 % of setting value or 0.150 A at Irated = 5 A

Warning delay 1 % of the setting value or 10 msTime for 2 ≤ I2/I2Perm ≤ 20 5 % of reference (calculated) value or 100 ms ±

(1 % current tolerance or 10 mA) at Irated = 1 A5 % of reference (calculated) value or 100 ms ±(1 % current tolerance or 50 mA) at Irated = 5 A

Influencing Variables for the Thresholds

Harmonics– Up to 10 % 3rd harmonic– Up to 10 % 5th harmonic

≤ 1 %≤ 1 %

Technical Data12.23 Unbalanced-Load Protection

1366 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Current-Unbalance Protection for Capacitors, 3-Phase

Setting Values for the Function

Automatic compensation YesNo

Time between switch off and switch on 0.00 s to 60.00 s Increments of 0.01 sNormalization with Ic Yes

NoThreshold of defectiveC-element

1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Setting Values (Overcurrent-Protection Stage I>)

Measured value compensatednon-compensated

Iunbal. 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A

Iunbal. 1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Operate delay 0.00 s to 60.00 s Increments of 0.01 s

Setting Values (Counter Stage)

Type of counting groups segregatedsum

Max. no. of def. elem. phs A 1 to 1000 Increments of 1Max. no. of def. elem. phs B 1 to 1000 Increments of 1Max. no. of def. elem. phs C 1 to 1000 Increments of 1Operate delay 0.00 s to 10000.00 s Increments of 0.01 s

Dropout Ratio

Threshold for defective C-element Approx. 0.95 of the current thresholdThreshold for overcurrent-protection stage I> Approx. 0.95 of the current threshold

Times

Operate time with time delay = 0 ms Approx. 32 ms + OOT70 at 50 HzApprox. 29 ms + OOT at 60 Hz

Dropout time Approx. 32 ms + OOT at 50 HzApprox. 27 ms + OOT at 60 Hz

Frequency Operating Range

0.9 f/frated to 1.1 f/frated According to specified tolerances

10 Hz to 0.9 f/frated

1.1 f/frated to 80 HzSlightly expanded tolerances

12.24

70 OOT (Output Operating Time) additional delay of the output medium used, see chapter 12.1.4 Relay Outputs

Technical Data12.24 Current-Unbalance Protection for Capacitors, 3-Phase

SIPROTEC 5, Overcurrent Protection, Manual 1367C53000-G5040-C017-6, Edition 11.2015

f < 10 Hzf > 80 Hz

Active

Tolerances

Currents Ic, Iunbal.

Protection-class current transformers1 % of the setting value or 5 mA (Irated = 1 A)or 25 mA (Irated = 5 A), (frated ± 10 %)

Currents Iunbal.

Sensitive current transformer1 % of the setting value or 0.1 mA (Irated = 1.6 A)or 0.5 mA (Irated = 8 A), (frated ± 10 %)

Time delays 1 % of the setting value or 10 ms

Technical Data12.24 Current-Unbalance Protection for Capacitors, 3-Phase

1368 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Current-Unbalance Protection for Capacitors, 1-Phase

Setting Values for the Function

Automatic compensation YesNo

Time between switch off and switch on 0.00 s to 60.00 s Increments of 0.01 sNormalization with Ic Yes

NoThreshold of defectiveC-element

1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Setting Values (Overcurrent-Protection Stage I>)

Current threshold Iunbal. 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A5 A @ 50 and 100 Irated 0.150 A to 175.000 A Increments of 0.01 A1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.005 A

Operate delay 0.00 s to 60.00 s Increments of 0.01 sMeasured value compensated

non-compensated

Setting Values (Counter Stage)

Type of counting groups segregatedsum

Type of counting phases segregatedsum

Max. no. of def. elem. phs A 1 to 1000 Increments of 1Max. no. of def. elem. phs B 1 to 1000 Increments of 1Max. no. of def. elem. phs C 1 to 1000 Increments of 1Max. no. of def. elem. 1 to 1000 Increments of 1Operate delay 0.00 s to 10000.00 s Increments of 0.01 s

Dropout Ratio

Threshold for defective C-element Approx. 0.95 of the current thresholdThreshold for overcurrent-protection stage I> Approx. 0.95 of the current threshold

Times

Operate time with time delay = 0 ms Approx. 32 ms + OOT71 at 50 HzApprox. 29 ms + OOT at 60 Hz

Dropout time Approx. 32 ms + OOT at 50 HzApprox. 27 ms + OOT at 60 Hz

Frequency Operating Range

0.9 f/frated to 1.1 f/frated According to specified tolerances

12.25

71 OOT (Output Operating Time) additional delay of the output medium used, see chapter 12.1.4 Relay Outputs

Technical Data12.25 Current-Unbalance Protection for Capacitors, 1-Phase

SIPROTEC 5, Overcurrent Protection, Manual 1369C53000-G5040-C017-6, Edition 11.2015

10 Hz to 0.9 f/frated

1.1 f/frated to 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Active

Tolerances

Currents Ic, Iunbal.

Protection-class current transformers1 % of the setting value or 5 mA (Irated = 1 A)or 25 mA (Irated = 5 A), (frated ± 10%)

Currents Iunbal.

Sensitive current transformer1 % of the setting value or 0.1 mA (Irated = 1.6 A)or 0.5 mA (Irated = 8 A), (frated ± 10%)

Time delays 1 % of the setting value or 10 ms

Technical Data12.25 Current-Unbalance Protection for Capacitors, 1-Phase

1370 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Voltage-Differential Protection for Capacitor Banks

Setting Values (General Functionality)

Voltage matching factor k 0.5000 to 2000.0000 Increments of 0.0001

Setting Values (Protection Stage Vdiff>)

Threshold 0.005 p.u. to 1.000 p.u. Increments of 0.001 p.u.Operate delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout Ratio

Threshold value Approx. 0.95

Times

Operate time with time delay = 0 ms Approx. 30 ms + OOT (Output Operating Time) at 50 HzApprox. 27 ms + OOT (Output Operating Time) at 60 Hz

Dropout time Approx. 20 ms + OOT (Output Operating Time) at 50 HzApprox. 18 ms + OOT (Output Operating Time) at 60 Hz

Tolerances

Threshold 1 % of the setting value or 0.05 VTime delays 1 % of the setting value or 10 ms

Frequency Operating Range

0.9 ≤ f/ frated ≤ 1.1 According to specified tolerances

10 Hz ≤ f ≤ 0.9 frated

1.1 frated ≤ f ≤ 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Active

12.26

Technical Data12.26 Voltage-Differential Protection for Capacitor Banks

SIPROTEC 5, Overcurrent Protection, Manual 1371C53000-G5040-C017-6, Edition 11.2015

Differential Protection for Capacitor Banks

Setting Values

Operate CurveThreshold value I/IratedObj 0.05 to 2.00 Increments of 0.01

Gradient 1 0.00 to 0.80 Increments of 0.01Intersection 1 Irest I/IratedObj 0.00 to 5.00 Increments of 0.01

Gradient 2 0.25 to 0.95 Increments of 0.01Intersection 2 Irest I/IratedObj 1.00 to 20.00 Increments of 0.01

Startup RecognitionStartup threshold value I/IratedObj 0.1 to 2.0 Increments of 0.1

Characteristic-curve increase factor 1.0 to 5.0 Increments of 0.1Maximum starting time 0.1 s to 180.0 s Increments of 0.1 sDC-Component RecognitionCharacteristic-curve increase factor DC 1.0 to 5.0 Increments of 0.1Inrush-current detectionContent 2nd harmonic 10 % to 45 % Increments of 1 %Duration of crossblk. 2. har. 0.00 s to 200.00 s or

∞Increments of 0.01 s

Recognition of External FaultsAdditional stabilization threshold value I/IratedObj 1.00 to 20.00 Increments of 0.01

Additional stabilization duration 0.00 s to 5.00 s or ∞ Increments of 0.01 sOperate curve See Figure 12-17

Idiff Fast

Threshold value I/IratedObj 0.5 to 35.0 Increments of 0.1

Tripping delay 0.00 s to 60.00 s Increments of 0.01 s

Dropout Ratio

Idiff stage Approx. 0.7Idiff fast stage Approx. 0.8

Response Tolerance

For preset characteristic-curve parameters; for 2 sides with one measuring point eachIdiff stage and characteristic curve 2 % of the setting valueIdiff fast stage 2 % of the setting value

Time Delays

Idiff stage 0.00 s to 60.00 s Increments of 0.01 sIdiff fast stage 0.00 s to 60.00 s Increments of 0.01 sTimer tolerance 1 % of the setting value or 10 ms

12.27

Technical Data12.27 Differential Protection for Capacitor Banks

1372 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

[dwdifaus-030912-01.tif, 1, en_US]

Figure 12-17 Operate Curve of the Differential Protection

Operating Times

Operate times for infeed on one sideIdiff stage, min 50 Hz

60 Hz23 ms + OOT72

20 ms + OOT1)

Idiff fast stage, min 50 Hz60 Hz

8 ms + OOT1)

8 ms + OOT1)

Dropout time, approx. 50 Hz60 Hz

29 ms26 ms

Frequency Operating Range

Frequency tracking 10 Hz to 80 Hz

72 Refer to protection functions, for example, Overcurrent protection

Technical Data12.27 Differential Protection for Capacitor Banks

SIPROTEC 5, Overcurrent Protection, Manual 1373C53000-G5040-C017-6, Edition 11.2015

Overvoltage Protection with 3-Phase Voltage

Setting Values for Stage Type Definite Time-Overvoltage Protection

Measured value Phase-to-phasePhase-to-ground

Method of measurement Fundamental componentRMS value

Pickup value73 0.300 V to 340.000 V Increments of 0.001 VTime delay 0.00 s to 60.00 s Increments of 0.01 sDropout ratio 0.90 to 0.99 Increments of 0.01

Setting Values for Stage Type Inverse Time-Overvoltage Protection

Measured value Phase-to-phasePhase-to-ground

Method of measurement Fundamental componentRMS value

Pickup value 0.300 V to 340.000 V Increments of 0.001 VPickup factor 1.00 to 1.20 Increments of 0.01Characteristic constant k 0.00 to 300.00 Increments of 0.01Characteristic constant α 0.010 to 5.000 Increments of 0.001Characteristic constant c 0.000 to 5.000 Increments of 0.001Time multiplier 0.05 to 15.00 Increments of 0.01Additional time delay 0.00 s to 60.00 s Increments of 0.01 sReset time 0.00 s to 60.00 s Increments of 0.01 s

Operate Curve for Stage Type Inverse Time-Overvoltage Protection

WhereTop Operate delayTinv Inverse-time delayTadd Additional time delay (parameter Additional time delay)

WhereTinv Inverse-time delayTp Time multiplier (parameter Time dial)V Measured voltageVthresh Threshold value (parameter Threshold)k Curve constant k (parameter Charact. constant k)α Curve constant α (parameter Charact. constant α)

12.28

73 If you have selected the method of measurement = RMS value, do not set the threshold value under 10 V.

Technical Data12.28 Overvoltage Protection with 3-Phase Voltage

1374 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

c Curve constant c (parameter Charact. constant c)

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overvoltage and of 105 % for under-voltage functionality.Minimum absolute dropout difference 150 mV sec.

Times

Operate time with time delay = 0 ms Approx. 25 ms + OOT74 at 50 HzApprox. 22 ms + OOT at 60 Hz

Dropout time Approx. 20 ms + OOT

Frequency Operating Range

0.9 f/frated to 1.1 f/frated According to specified tolerances

10 Hz to 0.9 f/frated

1.1 f/frated to 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Active

Tolerances for Stage Type Definite Time-Overvoltage Protection

Voltages 0.5 % of the setting value or 0.05 VTime delays 1 % of the setting value or 10 ms

Tolerances for Stage Type Inverse Time-Overvoltage Protection

Voltages 0.5 % of the setting value or 0.05 VOperate time for1.2 ≤ V/V threshold value ≤ 20

5 % of the setting value or 30 ms

Reset time delay 1 % of the setting value or 10 ms

74 OOT (Output Operating Time) additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs

Technical Data12.28 Overvoltage Protection with 3-Phase Voltage

SIPROTEC 5, Overcurrent Protection, Manual 1375C53000-G5040-C017-6, Edition 11.2015

Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage

Setting Values

Method of Measurement RMS valueFundamental componentFundamental componentover 2 cycle filters

Block. on measuring-voltage outage YesNo

Determ. ph. aff. by grd. flt. YesNo

Threshold value75 0.300 V to 340.000 V Increments of 0.001 VTime delay 0.00 s to 60.00 s Increments of 0.01 sPickup delay 0.00 s to 320.00 s Increments of 0.01 sDropout Ratio 0.90 to 0.99 Increments of 0.01V< faulty ph-gnd vltg. 0.300 V to 200.000 V Increments of 0.001 VV> healthy ph-gnd. vltg. 0.300 V to 200.000 V Increments of 0.001 V

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overvoltage and of 105 % for under-voltage functionality.Minimum absolute dropout difference 150 mV sec.

Times

Operate time with time delay = 0 msStandard filter, true RMS Approx. 25 ms + OOT76 at 50 Hz

Approx. 22 ms + OOT at 60 Hz2 cycle filters Approx. 45 ms + OOT at 50 Hz

Approx. 39 ms + OOT at 60 HzDropout TimeStandard filter, true RMS Approx. 20 ms + OOT at 50 Hz

Approx. 16.6 ms + OOT at 60 Hz2 cycle filters Approx. 31.06 ms + OOT at 50 Hz

Approx. 27.06 ms + OOT at 60 Hz

Frequency Operating Range

0.9 f/frated to 1.1 f/frated According to specified tolerances

10 Hz to 0.9 f/frated

1.1 f/frated to 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Active

12.29

75 If you have selected the method of measurement = RMS value, do not set the threshold value under 10 V.76 OOT (Output Operating Time) additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs

Technical Data12.29 Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage

1376 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Tolerances

Voltages 0.5 % of the setting value or 0.05 VTime delays 1 % of the setting value or 10 ms

Technical Data12.29 Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage

SIPROTEC 5, Overcurrent Protection, Manual 1377C53000-G5040-C017-6, Edition 11.2015

Overvoltage Protection with Positive-Sequence Voltage

Setting Values

Pickup value 0.300 V to 200.000 V Increments of 0.001 VTime delay 0.00 s to 60.00 s Increments of 0.01 sDropout ratio 0.90 to 0.99 Increments of 0.01

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overvoltage and of 105 % for under-voltage functionality.Minimum absolute dropout difference 150 mV sec.

Times

Operate time with time delay = 0 ms Approx. 25 ms + OOT77 at 50 HzApprox. 22 ms + OOT at 60 Hz

Dropout time Approx. 20 ms + OOT

Frequency Operating Range

0.9 f/frated to 1.1 f/frated According to specified tolerances

10 Hz to 0.9 f/frated

1.1 f/frated to 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Active

Tolerances

Voltages 0.5 % of the setting value or 0.05 VTime delays 1 % of the setting value or 10 ms

12.30

77 OOT (Output Operating Time) additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs

Technical Data12.30 Overvoltage Protection with Positive-Sequence Voltage

1378 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Overvoltage Protection with Negative-Sequence Voltage

Setting Values for the Function

Measuring window 1 cycle to 10 cycles Increments of 1 cycle

Setting Values

Pickup value of V2 0.300 V to 200.000 V Increments of 0.001 VOperate delay 0.00 s to 60.00 s Increments of 0.01 sDropout ratio 0.90 to 0.99 Increments of 0.01

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overvoltage and of 105 % for under-voltage functionality.Minimum absolute dropout difference 150 mV sec.

Times

Pickup times 55 ms to 210 ms + OOT 78

(depends on the measuring-window length) at 50 Hz48 ms to 185 ms + OOT(depends on the measuring-window length) at 60 Hz

Dropout time 20 ms to 70 ms + OOT(depends on the measuring-window length)

Frequency Operating Range

0.9 f/frated to 1.1 f/frated According to specified tolerances

10 Hz to 0.9 f/frated

1.1 f/frated to 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Inactive

Tolerances

Voltages 0.50 % of the setting value or 0.050 VTime delays 1.00 % of the setting value or 10 ms

12.31

78 OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays

Technical Data12.31 Overvoltage Protection with Negative-Sequence Voltage

SIPROTEC 5, Overcurrent Protection, Manual 1379C53000-G5040-C017-6, Edition 11.2015

Overvoltage Protection with Any Voltage

Setting Values

Measured value79 Measured phase-to-ground voltage VA

Measured phase-to-ground voltage VB

Measured phase-to-ground voltage VC

Measured phase-to-phase voltage VAB

Measured phase-to-phase voltage VBC

Measured phase-to-phase voltage VCA

Measured voltage VNMeasured phase-to-phase voltage VAB

Measured phase-to-phase voltage VBC

Measured phase-to-phase voltage VCA

Calculated voltage V0Method of measurement Fundamental component

RMS valuePickup value80 0.300 V to 340.000 V Increments of 0.001 VTime delay 0.00 s to 60.00 s Increments of 0.01 sDropout ratio 0.90 to 0.99 Increments of 0.01

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overvoltage and of 105 % for under-voltage functionality.Minimum absolute dropout difference 150 mV sec.

Times

Operate time with time delay =0 ms

Approx. 25 ms + OOT81 at 50 HzApprox. 22 ms + OOT at 60 Hz

Dropout time Approx. 20 ms + OOT

Frequency Operating Range

0.9 f/frated to 1.1 f/frated According to specified tolerances

10 Hz to 0.9 f/frated

1.1 f/frated to 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Active

Tolerances

Voltages 0.5 % of the setting value or 0.05 V

12.32

79 If the function Overvoltage protection with any voltage is used in a 1-phase function group, the measured-value parameter is notvisible.80 If you have selected the method of measurement = RMS value, do not set the threshold value under 10 V.81 OOT (Output Operating Time) additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs

Technical Data12.32 Overvoltage Protection with Any Voltage

1380 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Time delays 1 % of the setting value or 10 ms

Technical Data12.32 Overvoltage Protection with Any Voltage

SIPROTEC 5, Overcurrent Protection, Manual 1381C53000-G5040-C017-6, Edition 11.2015

Peak Overvoltage Protection for Capacitors

Setting Values

Threshold valueInverse-time stageDefinite-time stageUser-defined characteristic curve

0.80 to 3.00 p.u.0.80 to 10.00 p.u.0.80 to 3.00 p.u.

Increments of 0.01Increments of 0.01Increments of 0.01

Tripping delay 0.01 s to 3600.00 s Increments of 0.01 sDropout delay 0.00 s to 3600.00 s Increments of 1.00 sDown integration time 1 min to 1500 min Increments of 1 minTime multiplier 0.05 to 15.00 Increments of 0.01Number of value pairs for the operate curve 30 Increments of 1X values of the operate curve 1.00 p.u. to 4.00 p.u. Increments of 0.01 p.u.Y values of the operate curve 0.00 s to 9999.99 s Increments of 0.01 sNumber of value pairs for the dropout characteristiccurve

30 Increments of 1

X values of the dropout characteristic curve 0.01 p.u. to 0.95 p.u. Increments of 0.01 p.u.Y values of the dropout characteristic curve 0.00 s to 9999.99 s Increments of 0.01 s

Inverse-Time Characteristic Curve (IEC/IEEE)

[dw_pecinv-230813, 2, en_US]

Figure 12-18 Inverse-Time Characteristic Curve

The points on the characteristic curve defined in the standards result from a threshold setting of 1.1. Thesesingle points are connected via semi-logarithmic line segments.

12.33

Technical Data12.33 Peak Overvoltage Protection for Capacitors

1382 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Table 12-7 Peak Overvoltage Inverse-Time Characteristic (for Threshold Setting 1.1)

Measurand Û/Vc,rated Time Delay Curve Point According to

<1.15 ∞ (no pickup) Siemens definition1.15 1800.00 s IEC 60871-1:20051.2 300.00 s IEC 60871-1:20051.3 60.00 s IEC 60871-1:2005, IEEE Std 1036-20101.4 15.00 s IEEE Std 1036-20101.7 1.00 s IEEE Std 1036-20102 0.25 s IEEE Std 1036-20102.2 0.1 s IEEE Std 1036-2010>2.2 0.01 s IEEE Std 1036-2010

Times

Pickup time Approx. 35 ms + OOT at 50 Hz1

Approx. 25 ms + OOT at 60 Hz1

Dropout Time Depending on settings1 OOT (Output Operating Time) additional delay of the output medium used, for example, 5 ms with fastrelays

Frequency Operating Range

0.9 f/frated to 1.1 f/frated According to specified tolerances

10 Hz to 0.9 f/frated

1.1 f/frated to 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Active

Tolerances

Peak overvoltage(33 % harmonics, with reference to fundamental component)Up to 30th harmonicUp to 50th harmonic, frated = 50 HzUp to 50th harmonic, frated = 60 Hz

1 % of the setting value or 0.005 p.u. (frated ± 10%)3 % of the setting value or 0.02 p.u. (frated ± 10%)4 % of the setting value or 0.02 p.u. (frated ± 10%)

Time delaysMeasured value of inverse-time stage 5 % of the setting value +1 % of the measured value

or 30 msMeasured value of definite-time stage 1 % of the setting value or 10 msDown integration time 5 % of the setting value or 30 ms

Technical Data12.33 Peak Overvoltage Protection for Capacitors

SIPROTEC 5, Overcurrent Protection, Manual 1383C53000-G5040-C017-6, Edition 11.2015

Undervoltage Protection with 3-Phase Voltage

Setting Values for Stage Type Definite Time-Undervoltage Protection

Measured value Phase-to-phasePhase-to-ground

Method of measurement Fundamental componentRMS value

Current-flow criterion OnOff

Threshold value I> 1 A @ 50 and 100Irated

0.030 A to 10.000 A Increments of 0.001 A

5 A @ 50 and 100Irated

0.15 A to 50.00 A Increments of 0.01 A

1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Pickup value82 0.300 V to 175.000 V Increments of 0.001 VTime delay 0.00 s to 60.00 s Increments of 0.01 sDropout ratio 1.01 to 1.20 Increments of 0.01

Setting Values for Stage Type Inverse Time-Undervoltage Protection

Measured value Phase-to-phasePhase-to-ground

Method of measurement Fundamental componentRMS value

Current-flow criterion OnOff

Threshold value I> 1 A @ 50 and 100Irated

0.030 A to 10.000 A Increments of 0.001 A

5 A @ 50 and 100Irated

0.15 A to 50.00 A Increments of 0.01 A

1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Threshold 0.300 V to 175.000 V Increments of 0.001 VPickup factor 0.80 to 1.00 Increments of 0.01 Characteristic constant k 0.00 to 300.00 Increments of 0.01 Characteristic constant α 0.010 to 5.000 Increments of 0.001 Characteristic constant c 0.000 to 5.000 Increments of 0.001 Time multiplier 0.05 to 15.00 Increments of 0.01Additional time delay 0.00 s to 60.00 s Increments of 0.01 sReset time 0.00 s to 60.00 s Increments of 0.01 s

Operate Curve

Top=TInv+Tadd

Where:Top Operate delayTInv Inverse-time delay

12.34

82 If you have selected the method of measurement = RMS value, do not set the threshold value under 10 V.

Technical Data12.34 Undervoltage Protection with 3-Phase Voltage

1384 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Tadd Additional time delay (Parameter Additional time delay)

[fo_UVP3ph_inverse, 1, en_US]

Where

TInv Inverse-time delayTp Time multiplier (Parameter Time dial)V Measured undervoltageVThresh Threshold value (Parameter Threshold)k Curve constant k (Parameter Charact. constant k)α Curve constant α (Parameter Charact. constant α)c Curve constant c (Parameter Charact. constant c)

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overvoltage and of 105 % for under-voltage functionality.Minimum absolute dropout difference 150 mV sec.

Times

Pickup time Approx. 25 ms + OOT83 at 50 HzApprox. 22 ms + OOT at 60 Hz

Dropout time Approx. 20 ms + OOT

Frequency Operating Range

0.9 f/frated to 1.1 f/frated According to specified tolerances

10 Hz to 0.9 f/frated

1.1 f/frated to 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Inactive, maintained;Dropout of the pickup induced by blocking or by increasing themeasurand beyond the dropout threshold

Tolerances for Stage Type Definite Time-Undervoltage Protection

Voltages 0.5 % of the setting value or 0.05 VCurrents 1 % of the setting value or 5 mA (Irated = 1 A) or 25 mA (Irated = 5

A, frated ± 10 %), valid for protection-class current transformers

1 % of the setting value or 0.1 mA (Irated = 1.6 A) or 0.5 mA (Irated

= 8 A, frated ± 10 %), valid for instrument transformers

Time delays 1 % of the setting value or 10 ms

83 OOT (Output Operating Time) additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs

Technical Data12.34 Undervoltage Protection with 3-Phase Voltage

SIPROTEC 5, Overcurrent Protection, Manual 1385C53000-G5040-C017-6, Edition 11.2015

Tolerances for Stage Type Inverse Time-Undervoltage Protection

Voltages 0.5 % of the setting value or 0.05 VCurrents 1 % of the setting value or 5 mA (Irated = 1 A) or 25 mA (Irated = 5

A, frated ± 10 %), valid for protection-class current transformers

1 % of the setting value or 0.1 mA (Irated = 1.6 A) or 0.5 mA (Irated

= 8 A, frated ± 10 %), valid for instrument transformers

Operate time for 0 < V/VThresh < 0.9 5 % of the setting value or 30 ms

Reset time delay 1 % of the setting value or 10 ms

Technical Data12.34 Undervoltage Protection with 3-Phase Voltage

1386 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Undervoltage Protection with Positive-Sequence Voltage

Setting Values

Measured value Phase-to-phasePhase-to-ground

Method of measurement Fundamental componentRMS value

Current-flow criterion OnOff

Threshold value I> 1 A @ 50 and 100Irated

0.030 A to 10.000 A Increments of 0.001 A

5 A @ 50 and 100Irated

0.15 A to 50.00 A Increments of 0.01 A

1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Pickup value 0.300 V to 200.000 V Increments of 0.001 VTime delay 0.00 s to 60.00 s Increments of 0.01 sDropout ratio 1.01 to 1.20 Increments of 0.01

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overvoltage and of 105 % for under-voltage functionality.Minimum absolute dropout difference 150 mV sec.

Times

Operate time Approx. 25 ms + OOT 84 at 50 HzApprox. 22 ms + OOT at 60 Hz

Dropout Time Approx. 20 ms + OOT

Frequency Operating Range

0.9 f/frated to 1.1 f/frated According to specified tolerances

10 Hz to 0.9 f/frated

1.1 f/frated to 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Inactive, maintained;Dropout of the pickup induced by blocking or by increasing themeasurand beyond the dropout threshold

Tolerances

Voltages 0.5 % of the setting value or 0.05 VCurrents 1 % of the setting value or 5 mA (Irated = 1 A) or 25 mA (Irated = 5 A, frated ± 10

%), valid for protection-class current transformers1 % of the setting value or 0.1 mA (Irated = 1.6 A) or 0.5 mA (Irated = 8 A, frated ±10 %), valid for instrument transformers

12.35

84 OOT (Output Operating Time) additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs

Technical Data12.35 Undervoltage Protection with Positive-Sequence Voltage

SIPROTEC 5, Overcurrent Protection, Manual 1387C53000-G5040-C017-6, Edition 11.2015

Time delays 1 % of the setting value or 10 ms

Technical Data12.35 Undervoltage Protection with Positive-Sequence Voltage

1388 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Undervoltage Protection with Any Voltage

Setting Values

Measured value Measured phase-to-ground voltage VA

Measured phase-to-ground voltage VB

Measured phase-to-ground voltage VC

Measured phase-to-phase voltage VAB

Measured phase-to-phase voltage VBC

Measured phase-to-phase voltage VCA

Measured voltage VNCalculated phase-to-phase voltage VAB

Calculated phase-to-phase voltage VBC

Calculated phase-to-phase voltage VCA

Calculated voltage V0Method of measurement Fundamental component

RMS valuePickup value85 0.300 V to 340.000 V Increments of 0.001 VTime delay 0.00 s to 60.00 s Increments of 0.01 sDropout ratio 1.01 to 1.20 Increments of 0.01

Dropout

The greater dropout difference (= | pickup value – dropout value |) of the following 2 criteriaapplies:

Dropout difference derived from the parameter Dropout ratioIf this parameter is not available, a dropout ratio of 95 % applies for overvoltage and of 105 % for under-voltage functionality.Minimum absolute dropout difference 150 mV sec.

Times

Operate time with time delay = 0 ms Approx. 25 ms + OOT86 at 50 HzApprox. 22 ms + OOT at 60 Hz

Dropout time Approx. 20 ms + OOT

Frequency Operating Range

0.9 f/frated to 1.1 f/frated According to specified tolerances

10 Hz to 0.9 f/frated

1.1 f/frated to 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Inactive, maintained;Dropout of the pickup induced by blocking or by increasing themeasurand beyond the dropout threshold

Tolerances

Voltages 0.5 % of the setting value or 0.05 V

12.36

85 If you have selected the method of measurement = RMS value, do not set the threshold value under 10 V.86 OOT (Output Operating Time) additional delay of the output medium used, see chapter 12.1.4 Relay Outputs

Technical Data12.36 Undervoltage Protection with Any Voltage

SIPROTEC 5, Overcurrent Protection, Manual 1389C53000-G5040-C017-6, Edition 11.2015

Time delays 1 % of the setting value or 10 ms

Technical Data12.36 Undervoltage Protection with Any Voltage

1390 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Overfrequency Protection

Setting Values

Pickup values f> 40.00 Hz to 70.00 Hz Increments of 0.01 HzDropout differential 20 mHz to 2 000 mHz Increments of 10 mHzTime delay T 0.00 s to 600.00 s Increments of 0.01 sMinimum voltage 3.000 V to 175.000 V Increments of 0.001 V

Times

Pickup times f> Angle difference method50 Hz60 Hz

Approx. 70 ms + OOT 87

Approx. 60 ms + OOTFiltering method50 Hz60 Hz

Approx. 75 ms + OOTApprox. 75 ms + OOT

Dropout times f> 60 ms to 80 ms

Dropout Ratio

Minimum voltage About 1.05

Operating Ranges

Voltage range 5 V to 230 V (phase-phase)Frequency range Angle difference method 10 Hz to 80 Hz

Filtering method 25 Hz to 80 Hz

Tolerances

Frequency f>frated - 0.20 Hz < f < frated + 0.20 Hz ± 5 mHz at V = Vrated

frated - 3.0 Hz < f < frated + 3.0 Hz ± 10 mHz at V = Vrated

Time delay T(f>) 1 % of the setting value or 10 msMinimum voltage 1 % of the setting value or 0.5 V

12.37

87 OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays, see chapter12.1.4 Relay Outputs

Technical Data12.37 Overfrequency Protection

SIPROTEC 5, Overcurrent Protection, Manual 1391C53000-G5040-C017-6, Edition 11.2015

Underfrequency Protection

Setting Values

Pickup values f< 40.00 Hz to 70.00 Hz Increments of 0.01 HzDropout differential 20 mHz to 2 000 mHz Increments of 10 mHzTime delay T 0.00 s to 600.00 s Increments of 0.01 sMinimum voltage 3.000 V to 175.000 V Increments of 0.001 V

Times

Pickup times f< Angle difference method50 Hz60 Hz

Approx. 70 ms + OOT 88

Approx. 60 ms + OOTFiltering method50 Hz60 Hz

Approx. 75 ms + OOTApprox. 75 ms + OOT

Dropout times f< 60 ms to 80 ms

Dropout Ratio

Minimum voltage Approx. 1.05

Operating Ranges

Voltage range 5 V to 230 V (phase-phase)Frequency range Angle difference method 10 Hz to 80 Hz

Filtering method 25 Hz to 80 Hz

Tolerances

Frequency f<frated - 0.20 Hz < f < frated + 0.20 Hz ± 5 mHz at V = Vrated

frated - 3.0 Hz < f < frated + 3.0 Hz ± 10 mHz at V = Vrated

Time delay T(f<) 1 % of the setting value or 10 msMinimum voltage 1 % of the setting value or 0.5 V

12.38

88 OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays, see chapter12.1.4 Relay Outputs

Technical Data12.38 Underfrequency Protection

1392 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Rate of Frequency Change Protection

Setting Values for the Function

Minimum voltage 3.000 V to 175.000 V Increments of 0.001 VMeasuring window 2 periods to 5 periods Increments of 1 period

Setting Values for Stage Types

Threshold 0.1 Hz/s to 20.0 Hz/s Increments of 0.1 Hz/sDropout differential 0.02 Hz/s to 0.99 Hz/s Increments of 0.01 Hz/sOperate delay 0.00 s to 60.00 s Increments of 0.01 s

Times

Pickup time Approx.165 ms to 225 ms (depends on measuring window length)Dropout time Approx.165 ms to 225 ms (depends on measuring window length)

Dropout Ratio

Dropout ratio for minimum voltage Approx. 1.05

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances

10 Hz ≤ f < 0.9 frated

1.1 frated < f ≤ 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Inactive

Tolerances

Threshold,measuring window > 3 periods

Approx. 3 % or 0.06 Hz/s

Threshold,measuring window ≤ 3 periods

Approx. 5 % or 0.06 Hz/s

Minimum voltage 1 % of the setting value or 0.5 VTime delays 1 % of the setting value or 10 ms

12.39

Technical Data12.39 Rate of Frequency Change Protection

SIPROTEC 5, Overcurrent Protection, Manual 1393C53000-G5040-C017-6, Edition 11.2015

3-Phase Power Protection (P,Q)

Setting Values

Measured value Positive sequence powerPower of phase APower of phase BPower of phase C

Threshold value -200.0 % to +200.0 % Increments of 0.1Tilt-power characteristic -89.0° to +89.0° Increments of 0.1°Dropout delay time 0.00 s to 60.00 s Increments of 0.01 sTime delay 0.00 s to 60.00 s Increments of 0.01 sDropout ratio Upper stage: 0.90 to 0.99

Lower stage: 1.01 to 1.10Increments of 0.01Increments of 0.01

Times

Pickup times Approx. 55 ms + OOT89 at 50 HzApprox. 45 ms + OOT at 60 Hz

Dropout times Approx. 55 ms + OOT at 50-HzApprox. 45 ms + OOT at 60 Hz

Tolerances

Power 0.5 % Srated ± 3 % of setting value(Srated: rated apparent power)

Time delays 1 % of the setting value or 10 ms

Variables That Influence Pickup Values

Auxiliary DC voltage in the range 0.8 ≤ VAux/VAuxRated ≤ 1.15 ≤ 1 %

Frequency in the range 0.95 ≤ f/frated ≤ 1.05 ≤ 1 %

Harmonics- Up to 10 % of 3rd harmonics- Up to 10 % of 5th harmonics

≤ 1 %≤ 1 %

12.40

89 OOT (Output Operating Time) additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs

Technical Data12.40 3-Phase Power Protection (P,Q)

1394 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Reverse-Power Protection

Setting Values

Reverse power Preverse (p.u.) -0.30 % to -30.00 % Increments of 0.01 %

Tripping delay 0.00 s to 60.00 s Increments of 0.01 sDropout ratio 0.40 to 0.99 Increments of 0.01

Times

Pickup times Approx. 360 ms at f = 50 HzApprox. 300 ms at f = 60 Hz

Dropout times Approx. 360 ms at f = 50 HzApprox. 300 ms at f = 60 Hz

Frequency Operating Range

0.9 f/frated to 1.1 f/frated According to specified tolerances

10 Hz to 0.9 f/frated

1.1 f/frated to 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Inactive

Tolerances

Reverse power 0.15 % Srated or 5 % of the setting value when Q < 0.5 Srated

Time delays 1 % or 10 ms

12.41

Technical Data12.41 Reverse-Power Protection

SIPROTEC 5, Overcurrent Protection, Manual 1395C53000-G5040-C017-6, Edition 11.2015

Overexcitation Protection

Setting Values

Threshold value(Characteristic curve dependent onpickup)

1.00 to 1.20 Increments of 0.01

Threshold value(Characteristic curve independent onpickup)

1.00 to 1.40 Increments of 0.01

Time delay (warning delay and tripping delay) 0.00 s to 60.00 s Increments of 0.01 sCharacteristic value pairs 2 to 30

Value ranges V/Hz 1 p.u. to 10 p.u. Increments of 0.01p.u.

t 0 s to 100 000 s Increments of 1 sCooling time therm. replica 0 s to 100 000 s Increments of 1 s

Frequency Operating Range

Frequency tracking 10 Hz to 80 Hz

Operating Times

Operate times/dropout timesOperate time at frequency 50 Hz 60 HzMinimum 33 ms + OOT1 30 ms + OOT90

Dropout time 10 ms + OOT1 10 ms + OOT1

Dropout Ratios

Warning, tripping (independent stage) Approx. 0.98

Operate Curve

Thermal replica For default setting refer to the followingcharacteristic curve Figure 12-19

Tolerances

V/Hz pickup 2 % of the setting valueTime delays 1 % of the setting value or 10 ms (min. of

1.5 cycles)Thermal replica 5 % based on V/Hz ± 600 msMeasurement accuracy of voltage 0.5 % of the setting value or 0.5 V in the

range fn ± 10 %)Measurement accuracy of frequency 1.0 % of the setting value or 1.0 Hz in the

frequency range 10 Hz to 80 Hz

Influencing Quantities

Auxiliary direct voltage in the 0.8 range ≤ 1 %Time delays ≤ 0.5 %/10 KThermal replica ≤ 1 %

12.42

90 Refer to protection functions, for example overcurrent protection

Technical Data12.42 Overexcitation Protection

1396 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Harmonicsup to 10 % of 3rd harmonicsup to 10 % of 5th harmonics

≤ 1 %≤ 1 %

[dwrsasuf-070513-01.tif, 1, en_US]

Figure 12-19 Operate Curve from the Thermal Replica of the Overexcitation Protection (Default Setting)

Technical Data12.42 Overexcitation Protection

SIPROTEC 5, Overcurrent Protection, Manual 1397C53000-G5040-C017-6, Edition 11.2015

Undervoltage-Controlled Reactive-Power Protection

Setting Values

Threshold value Power Q 1.00 % to 200.00 % Increments of 0.01 %Voltage of protectionstage

3.000 to 175.000 Increments of 0.001 V

Voltage of reclosurestage

3.000 V to 340.000 V Increments of 0.001 V

Current I1 release threshold 1 A @ 50 and 100 Irated 0.030 A to 10.000 A Increments of 0.001 A5 A @ 50 and 100 Irated 0.15 A to 50.00 A Increments of 0.01 A1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Operate delay 0.00 s to 60.00 s Increments of 0.01 sRelease time delay of reclosure stage 0.00 s to 3600.00 s Increments of 0.01 s

Dropout Ratio

Protection stageReactive-power flow Q Approx. 0.95Voltage Approx. 1.05Release current Approx. 0.95

Reclosure stageVoltage Approx. 0.95Release current Approx. 0.95

Times

Pickup time Approx. 55 ms + OOT91 at 50 HzApprox. 45 ms + OOT at 60 Hz

Dropout time Approx. 55 ms + OOT at 50 HzApprox. 45 ms + OOT at 60 Hz

Tolerances

Current I1 1 % of the setting value or 5 mA (Irated = 1 A)or 25 mA (Irated = 5 A)

Voltage 0.5 % of the setting value or 0.05 VPower Q 0.5 % Srated ± 3 % of the setting value

(Srated: rated apparent power)

Time delays 1 % of the setting value or 10 msReclosure time delay 1 % of the setting value or 10 ms

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances

10 Hz ≤ f < 0.9 frated

1.1 frated < f ≤ 80 HzSlightly expanded tolerances

12.43

91 OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays

Technical Data12.43 Undervoltage-Controlled Reactive-Power Protection

1398 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

f < 10 Hzf > 80 Hz

Function is blocked

Technical Data12.43 Undervoltage-Controlled Reactive-Power Protection

SIPROTEC 5, Overcurrent Protection, Manual 1399C53000-G5040-C017-6, Edition 11.2015

Circuit-Breaker Failure Protection

Starting Conditions

For circuit-breaker failure protection 3-pole internal or external tripping92

Setting Values

Phase-current thresholdvalues

1 A @ 100 Irated 0.030 A to 35.000 A Increments of 0.001 A1 A @ 50 Irated5 A @ 100 Irated 0.15 A to 175.00 A Increments of 0.01 A5 A @ 50 Irated1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Ground-current thresholdvalue

1 A @ 100 Irated 0.030 A to 35.000 A Increments of 0.001 A1 A @ 50 Irated5 A @ 100 Irated 0.15 A to 175.00A Increments of 0.01 A5 A @ 50 Irated1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Supervision time of release signal 0.06 s to 1.00 s Increments of 0.01 sTime delays 0.05 s to 60.00 s Increments of 0.01 s

Dropout Ratios

Current threshold values Approx. 0.95

Circuit-Breaker Supervision

Position supervision of circuit-breaker auxiliary contactsFor 3-pole CB tripping 1 input each for make contact and break contact

iiNOTE

The circuit-breaker failure protection can also work without the circuit-breaker auxiliary contacts stated.Auxiliary contacts are required for circuit-breaker failure protection in cases where the current flow isabsent or too low for tripping (for example with a transformer or a Buchholz protection).

Times

Pickup time, in the case of an internal startPickup time, in the case of an external start

< 1 ms< 5 ms

Dropout time93 via the current-flow criterion, for sinus-oidal quantities

< 10 ms

Dropout time, via the current-flow criterion, under allconditions

< 15 ms

Dropout time, via circuit-breaker auxiliary-contactcriterion

< 5 ms

12.44

92 Via binary inputs93 The dropout time is the time required by the CBFP function to detect that the CB is open. The time for mechanically switching acontact is not included.

Technical Data12.44 Circuit-Breaker Failure Protection

1400 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Tolerances

Threshold values, dropout thresholds 2 % of the setting value or 1 % of the rated currentTimes 1 % of the setting value or 10 ms

Technical Data12.44 Circuit-Breaker Failure Protection

SIPROTEC 5, Overcurrent Protection, Manual 1401C53000-G5040-C017-6, Edition 11.2015

Circuit-Breaker Restrike Protection

Setting Values

Threshold value 1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Monitoring duration 1.00 s to 600.00 s Increments of 0.01 sPosition recognition delay 0.00 s to 60.00 s Increments of 0.01 sDropout delay 0.00 s to 60.00 s Increments of 0.01 sTrip delay time 0.05 s to 60.00 s Increments of 0.01 sRetrip delay time 0.00 s to 60.00 s Increments of 0.01 sMinimum operate (trip) time 0.00 s to 60.00 s Increments of 0.01 s

Dropout Ratio

Current threshold Approx. 0.95

Times

Operate time with time delay = 0 ms Approx. 25 ms + OOT at 50 HzApprox. 22 ms + OOT at 60 Hz

Dropout time Approx. 20 ms + OOT

Frequency Operating Range

0.9 ≤ f/frated ≤ 1.1 According to specified tolerances

10 Hz ≤ f < 0.9 frated

1.1 frated < f ≤ 80 HzSlightly expanded tolerances

f < 10 Hzf > 80 Hz

Active

Tolerances

Threshold 1 % of the setting value or 5 mA (Irated = 1 A) or 25mA (Irated = 5 A)

Time delays 1 % of the setting value or 10 ms

12.45

Technical Data12.45 Circuit-Breaker Restrike Protection

1402 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Restricted Ground-Fault Protection

Setting Values

Threshold value94 0.05 A to 2.00 A Increments of 0.01A

Gradient 0.00 to 0.95 Increments of 0.01Operate curve See figurePickup tolerance(for preset characteristic curve settings; for 2 sides with 1 meas-uring point each)

2 %

Tripping delay 0.00 s to 60.00 s or∞ (no tripping)

Increments of 0.01 s

Timer tolerance 1 % of the setting value or 10 ms

Dropout Ratio

Threshold value 0.7

Times

7UT82/7UT85/7UT86/7UT87Frequency 50 Hz 60 Hz

Operate time Operate timeAt 1,5 · setting value threshold valueAt 2.5 · setting value threshold value

33 ms + OOT27 ms + OOT

32 ms + OOT26 ms + OOT

Dropout time approx. 80 ms 67 msDropout ratio 0.7

12.46

94 The specified setting limit can be dynamically further limited, depending on the transformer adaptation factor, (for this refer to Chapter6.39.4 Application and Setting Notes ).

Technical Data12.46 Restricted Ground-Fault Protection

SIPROTEC 5, Overcurrent Protection, Manual 1403C53000-G5040-C017-6, Edition 11.2015

[dwausken-170712-01.tif, 1, en_US]

Figure 12-20 Operate Curve of the Restricted Ground-Fault Protection Depending on the Phase AngleBetween I 0* and I 0** at |I 0*| = |I 0**| (180° = External Fault)

Technical Data12.46 Restricted Ground-Fault Protection

1404 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

External Trip Initiation

Setting Values

Tripping delay 0.00 s to 60.00 s Increments of 0.01 s

Times

Operate time with time delay = 0 ms- At initiation via binary input signal

Approx. 10 ms + OOT 95.

Tolerance

Sequence tolerance for delay times 1 % of the setting value or 10 ms

12.47

95 OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays, see chapter12.1.4 Relay Outputs

Technical Data12.47 External Trip Initiation

SIPROTEC 5, Overcurrent Protection, Manual 1405C53000-G5040-C017-6, Edition 11.2015

Automatic Reclosing

Function specifications Cyclic automatic reclosing functionAutomatic reclosing function with adaptive dead time (ADT)Operation with External Automatic Reclosing Function

Number of reclosings Max. 8, per individual settingsType (depending on the ordervariation)

1-pole, 3-pole, or 1-/3-pole

Operating mode of the automaticreclosing function

With trip command, without action timeWith trip command, with action timeWith pickup, without action timeWith pickup, with action time

Reclaim time after reclosing 0.50 s to 300.00 s Increments of 0.01 sBlocking time after dynamicblocking

0.5 s -

Blocking time after manual closure 0.00 s to 300.00 s Increments of 0.01 sStart supervision time 0.01 s to 300.00 s Increments of 0.01 sCircuit-breaker supervision time 0.01 s to 300.00 s Increments of 0.01 sEvolving-fault detection With trip command

with PickupReaction to evolving faults Blocks automatic reclosing function

Start, evolving fault, dead timeAction times (separated for allcycles)

0.00 s to 300.00 s or oo (ineffec-tive)

Increments of 0.01 s

Dead times after trip command(separated for all types and allcycles)

0.00 s to 1 800.00 s or oo (ineffec-tive)

Increments of 0.01 s

Dead time after evolving-faultdetection (separated for all cycles)

0.00 s to 1 800.00 s Increments of 0.01 s

Synchrocheck after 3-pole deadtime

NoneInternalExternal

Transmission delay, inter closecommand

0.00 s to 300.00 s or oo (ineffec-tive)

Increments of 0.01 s

Dead-line check/reduced deadtime

WithoutReduced dead time (VWE)Dead line checking

Voltage supervision warning time 0.10 s to 30.00 s Increments of 0.01 sLimiting value for fault-free line 0.3 V to 340.0 V Increments of 0.1 VLimiting value for zero potential 0.3 V to 340.0 V Increments of 0.1 V

12.48

Technical Data12.48 Automatic Reclosing

1406 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Fault Locator

Setting Values

Reactance per unit length of the line per kilometer or per mileLine length for the correct output of the fault distance as a percentage of the line lengthThe residual compensation factors in the setting format Kr and Kx or K0 and angle (K0)Consideration of the load current for 1-pole groundfaults

Correction of the X value, for connection and discon-nection

Fault Distance

Output of the fault distance (line length) In Ω primary and secondaryIn km, miles or in percent. 96

Tolerances

Measuring tolerances during sinusoidal measurandsand error duration> 25 ms at 60 Hz or> 30 ms at 50 Hz

1.5 % from fault location at VK/Vrated ≥ 0.01 and oneof the following scenarios:• Metal fault• Non-metallic fault for one-side infeed without

load

12.49

96 The output of the fault distance in km, miles and percent presupposes a homogenous line.

Technical Data12.49 Fault Locator

SIPROTEC 5, Overcurrent Protection, Manual 1407C53000-G5040-C017-6, Edition 11.2015

Temperature Supervision

Setting Values

Pickup value -50 °C to 250 °C-58 °F to 482 °F

Increments of 1°CIncrements of 1°F

Time delay 0 s to 60 sor ∞

Increments of 1 s

Dropout Conditions

Dropout differential 3 °C or 6 °F

Tolerances

Tripping delay ±1 % of the setting value or ±10 msMeasured temperature value ±0.5 % of the setting value or ±1 °C or ±2 °F

12.50

Technical Data12.50 Temperature Supervision

1408 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Current-Jump Detection

Times

Pickup time Approx. 10 ms + OOT97 at 50 HzApprox. 8 ms + OOT at 60 Hz

Operating Range

10 Hz to 80 Hz Function activeBehavior outside the operating range Function inactive

Tolerances

Currents 3 % of setting value or 10 mA (Irated = 1 A) or50 mA (Irated = 5 A), (frated ± 10 %)for amplitude changes of sinusoidal measurands

Pulse time 1 % of the setting value or 10 ms

12.51

97 OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays

Technical Data12.51 Current-Jump Detection

SIPROTEC 5, Overcurrent Protection, Manual 1409C53000-G5040-C017-6, Edition 11.2015

Voltage-Jump Detection

Times

Pickup time Approx. 10 ms + OOT98 at 50 HzApprox. 8 ms + OOT at 60 Hz

Working area

10 Hz to 80 Hz Function activeBehavior outside the operating range Function inactive

Tolerances

Voltages 2 % of the setting value or 0.100 Vfor amplitude changes of sinusoidal measurands

Pulse time 1 % of the setting value or 10 ms

12.52

98 OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays

Technical Data12.52 Voltage-Jump Detection

1410 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Synchronization Function

Operating Modes

SynchrocheckSwitching synchronous systemsSwitching asynchronous systemsDe-energized switchingDirect closing command

Setting Values

Supervision/Delay times:Max. Duration of synchronizationprocess

0.00 s to 3 600.00 s or ∞ (ineffec-tive)

Increments of 0.01 s

Supervision time de-energizedswitching

0.00 s to 60.00 s Increments of 0.01 s

Closure delay 0.00 s to 60.00 s Increments of 0.01 sVoltage threshold values:Upper voltage limit Vmax 0.300 V to 340.000 V (phase-to-

phase)Increments of 0.001 V

Lower voltage limit Vmin 0.300 V to 340.000 V (phase-to-phase)

Increments of 0.001 V

V<, for off-circuit conditionsV>, for voltage present

0.300 V to 170.000 V (phase-to-phase)0.300 V to 340.000 V (phase-to-phase)

Increments of 0.001 VIncrements of 0.001 V

Differential values, changeover thresholds asynchronous/synchronous:Voltage differencesV2 > V1; V2 < V1

0.000 V to 170.000 V Increments of 0.001 V

Frequency difference f2 > f1;f2 < f1

0.000 Hz to 2.000 Hz (synchro-nous)0.000 Hz to 4.000 Hz (asynchro-nous)

Increments of 0.001 Hz

Angular difference α2 > α1;α2 < α1

0o to 90o Increments of 1o

Δf threshold ASYN <-> SYN 0.010 Hz to 0.200 Hz Increments of 0.001 HzAdjustments of the sides:Angle adjustment 0.0o to 360.0o Increments of 0.1o

Voltage adjustment 0.500 to 2.000 Increments of 0.001Circuit breakerClosing time of the circuit breaker 0.01 s to 0.60 s Increments of 0.01 s

Dropout Ratio

Min./max. operating limit 1 % of the setting valueVoltage differential 10 % of the setting value or 0.5 VDe-energized/energized 5 % of the setting valueFrequency difference 3 mHzAngular difference 0.1o

12.53

Technical Data12.53 Synchronization Function

SIPROTEC 5, Overcurrent Protection, Manual 1411C53000-G5040-C017-6, Edition 11.2015

Measured Values of the Synchronization Function

Reference voltage V1 • Range• Tolerance at rated frequency

In kV primary, in V secondary or in % Vrated

Display always as phase-to-phase voltage10 % to 120 % of Vrated

≤ 1% of the measured value or 0.5% Vrated

Voltage to be synchronized V2 • Range• Tolerance at rated frequency

In kV primary, in V secondary or in % Vrated

Display always as phase-to-phase voltage10 % to 120 % of Vrated

≤ 1% of the measured value or 0.5% Vrated

Frequency of the voltage V1f1• Range• Tolerance at rated frequency

f1 in Hz25 Hz ≤ f ≤ 70 Hz1 mHz

Frequency of the voltage V1f2• Range• Tolerance at rated frequency

f2 in Hz25 Hz ≤ f ≤ 70 Hz1 mHz

Voltage difference V2-V1 • Range• Tolerance at rated frequency

In kV primary, in V secondary or in % Vrated

Display always as phase-to-phase voltage in relationto side 110 % to 120 % of Vrated

≤ 1% of the measured value or 0.5% Vrated

Frequency difference f2-f1• Range• Tolerance at rated frequency

In mHzfrated ± 10 %1 mHz

Angular difference λ2-λ1• Range• Tolerance at rated frequency

In o

-180o to +180o

0.5o

Times

Measuring time, after switching on the variables Approx. 80 ms

Operating Range

Voltage 20 V to 340 VFrequency frated -4 Hz ≤ frated ≤ frated +4 Hz

Tolerances

Tolerances of the voltage settings 2 % of the pickup value or 1 VVoltage difference V2>V1; V2<V1 1 VFrequency difference f2>f1; f2<f1 10 mHzAngular difference α2>α1; α2<α1 1o

Tolerance of all time settings 10 msMax. phase displacement angle 5o for Δf ≤ 1 Hz

10o for Δf > 1 Hz

Technical Data12.53 Synchronization Function

1412 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Voltage Controller

Setting Values

General InformationI reference for % values 0.20 A to 100 000.00 A Increments of 0.01 AV reference for % values 0.20 kV to 1 200.00 kV Increments of

0.01 kVVolt. cont. 2WTarget voltage 1

40.00 kV to 1 360.00 kV Increments of0.01 kV

Target voltage 2Target voltage 3Target voltage 4Volt. cont. 3W and GCTarget voltage 1 w1

40.00 kV to 1 360.00 kV Increments of0.01 kV

Target voltage 2 w1Target voltage 3 w1Target voltage 4 w1Target voltage 1 w2Target voltage 2 w2Target voltage 3 w2Target voltage 4 w2Volt. cont. 2W, 3W, and GCBandwidth 0.2 % to 10.0 % Increments of 0.1 %T1 delay 5 s to 600 s Increments of 1 sT1 Inverse Min 5 s to 100 s Increments of 1 sT2 delay 0 s to 100 s Increments of 1 sFast step down limit 0.0 % to 50.0 % Increments of 0.1 %Fast step down T delay 0.0 s to 10.0 s Increments of 0.1 sFast step up limit -50.0 % to 0.0 % Increments of -0.1 %Fast step up T delay 0.0 s to 10.0 s Increments of 0.1 sFunction monitoring 1 min to 120 min Increments of 1 minLine compensation LDC-ZTarget voltage rising 0.0 % to 20.0 % Increments of 0.1 %Max load current 0.0 % to 500.0 % Increments of 0.1 %Line compensation LDC-X and RR line 0.0 Ω to 30.0 Ω Increments of 0.1 ΩX line -30.0 Ω to 30.0 Ω Increments of 0.1 ΩLimiting valuesVmin threshold 40.00 kV to 1 360.00 kV Increments of

0.01 kVVmin time delay 0 s to 20 s Increments of 1 sVmax threshold 40.00 kV to 1 360.00 kV Increments of

0.01 kVVmax time delay 0 s to 20 s Increments of 1 sBlockingsV< Threshold 40.00 kV to 1 360.00 kV Increments of

0.01 kVV< Time delay 0 s to 20 s Increments of 1 s

12.54

Technical Data12.54 Voltage Controller

SIPROTEC 5, Overcurrent Protection, Manual 1413C53000-G5040-C017-6, Edition 11.2015

I> Threshold 10 % to 500 % Increments of 1 %I> Time delay 0 s to 20 s Increments of 1 sI< Threshold 3 % to 100 % Increments of 1 %I< Time delay 0 s to 20 s Increments of 1 s

Dropout Ratio

Threshold of the voltage limit About 0.99 of the setting valueThreshold of the current limit About 0.99 of the setting value

Technical Data12.54 Voltage Controller

1414 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Current-Balance Supervision

Setting Values

Release threshold 1 A @ 100 Irated 0.030 A to 35.000 A Increments of 0.001 A1 A @ 50 Irated5 A @ 100 Irated 0.15 A to 175.00 A Increments of 0.01 A5 A @ 50 Irated1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Threshold value min/max 0.10 to 0.95 Increments of 0.01Tripping delay 0.00 s to 100.00 s Increments of 0.01 s

Dropout Ratio

Overcurrent dropout ratio About 0.97Undercurrent dropout ratio About 1.05

Times

Tripping time Approx. 500 msDropout time Approx. 500 ms

12.55

Technical Data12.55 Current-Balance Supervision

SIPROTEC 5, Overcurrent Protection, Manual 1415C53000-G5040-C017-6, Edition 11.2015

Voltage-Balance Supervision

Setting Values

Release threshold value 0,300 V to 170,000 V Increments of 0.001 VThreshold value min/max 0.58 to 0.95 Increments of 0.01Tripping delay 0.00 s to 100.00 s Increments of 0.01 s

Dropout Ratio

Overvoltage dropout ratio Approx. 0.97Undervoltage dropout ratio Approx. 1.05

Times

Tripping time Approx. 500 msDropout time Approx. 500 ms

12.56

Technical Data12.56 Voltage-Balance Supervision

1416 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Current-Sum Supervision

Setting Values

Slope of the characteristic curve 0.00 to 0.95 Increments of 0.01Threshold 1 A @ 50 and 100

Irated0.030 A to 10.000 A Increments of 0.001 A

5 A @ 50 and 100Irated

0.15 A to 50.00 A Increments of 0.01 A

1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Tripping delay 0.00 s to 100.00 s Increments of 0.01 s

Dropout Ratio

Dropout ratio About 0.97

Times

Tripping time Approx. 500 msDropout time Approx. 500 ms

12.57

Technical Data12.57 Current-Sum Supervision

SIPROTEC 5, Overcurrent Protection, Manual 1417C53000-G5040-C017-6, Edition 11.2015

Voltage-Sum Supervision

Setting Values

Threshold value 0.300 V to 170.000 V Increments of 0.001 VTripping delay 0.00 s to 100.00 s Increments of 0.01 s

Dropout Ratio

Dropout ratio Approx. 0.97

Times

Tripping time Approx. 500 msDropout time Approx. 500 ms

12.58

Technical Data12.58 Voltage-Sum Supervision

1418 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Current Phase-Rotation Supervision

Setting Values

Tripping delay 0.00 s to 100.00 s Increments of 0.01 sPhase-rotation direction A B C

A C B

Dropout Ratio

Dropout ratio Approx. 0.97

Times

Tripping time Approx. 500 msDropout time Approx. 500 ms

12.59

Technical Data12.59 Current Phase-Rotation Supervision

SIPROTEC 5, Overcurrent Protection, Manual 1419C53000-G5040-C017-6, Edition 11.2015

Voltage Phase-Rotation Reversal

Setting Values

Tripping delay 0.00 s to 100.00 s Increments of 0.01 sPhase-rotation direction A B C

A C B

Dropout Ratio

Dropout ratio Approx. 0.97

Times

Tripping time Approx. 500 msDropout time Approx. 500 ms

12.60

Technical Data12.60 Voltage Phase-Rotation Reversal

1420 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Trip-Circuit Supervision

Setting Values

Number of monitored circuits per circuit-breaker function group 1 to 3Operating mode per circuit With 1 binary input

With 2 binary inputsPickup and dropout time About 1 s to 2 sAdjustable indication delay with 1 binary input 1.00 s to 600.00 s Increments of 0.01 sAdjustable indication delay with 2 binary inputs 1.00 s to 600.00 s Increments of 0.01 s

12.61

Technical Data12.61 Trip-Circuit Supervision

SIPROTEC 5, Overcurrent Protection, Manual 1421C53000-G5040-C017-6, Edition 11.2015

Analog Channel Supervision via Fast Current Sum

Times

Pickup times Approx. 2 ms (faster than the fastest protection function)Dropout time Approx. 100 ms

Blockings

Blocked functions All functions that process the measured values from this current meas-uring point (for example, differential protection).

12.62

Technical Data12.62 Analog Channel Supervision via Fast Current Sum

1422 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Measuring-Voltage Failure Detection

Setting Values

3ph.fail. - VA,VB,VC < 0.300 V to 340 000 V Increments of 0.001 V3ph.fail. -phs.curr.release

1 A @ 50 and 100Irated

0.030 A to 35.000 A Increments of 0.001 A

5 A @ 50 and 100Irated

0.15 A to 175.00 A Increments of 0.01 A

1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

3ph.fail. - phs.curr. jump 1 A @ 50 and 100Irated

0.030 A to 35.000 A Increments of 0.001 A

5 A @ 50 and 100Irated

0.15 A to 175.00 A Increments of 0.01 A

1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Asym.fail. - time delay 0.00 s to 30.00 s Increments of 0.01 sSO 3ph.fail. - time delay 0.00 s to 30.00 s Increments of 0.01 s

Dropout Ratio

Overvoltage About 0.95Undervoltage About 1.05

Times

Times Approx. 10 ms + OOT99 at 50 HzApprox. 10 ms + OOT at 60 Hz

Dropout Time Approx. 20 ms + OOT

Times

Use in function group type LineTimes Approx. 10 ms + OOT100 at 50 Hz

Approx. 9 ms + OOT at 60 Hz

Use in other function group typesTimes Approx. 20 ms + OOT101 at 50 Hz

Approx. 18 ms + OOT at 60 Hz

Operating Range

10 Hz to 80 Hz According to specified tolerancesBehavior outside the operating range Active

12.63

99 OOT (Output Operating Time) additional delay of the output medium used, see chapter 12.1.4 Relay Outputs100 OOT (Output Operating Time) additional delay of the output medium used, for example, 5 ms with fast relays, see chapter12.1.4 Relay Outputs101 OOT (Output Operating Time) additional delay of the output medium used, for example, 5 ms with fast relays, see chapter12.1.4 Relay Outputs

Technical Data12.63 Measuring-Voltage Failure Detection

SIPROTEC 5, Overcurrent Protection, Manual 1423C53000-G5040-C017-6, Edition 11.2015

Tolerances

Currents 1 % of the setting value or 5 mA (Irated = 1 A)or 25 mA (Irated = 5 A), (frated ± 10%)

Voltages 0.5 % of the setting value or 0.5 VTime delays 1 % of the setting value or 10 ms

Technical Data12.63 Measuring-Voltage Failure Detection

1424 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Voltage-Transformer Circuit Breaker

Setting Values

Response time 0.000 s to 0.030 s Increments of 0.001 s

12.64

Technical Data12.64 Voltage-Transformer Circuit Breaker

SIPROTEC 5, Overcurrent Protection, Manual 1425C53000-G5040-C017-6, Edition 11.2015

Operational Measured Values and Statistical Values

Voltages

VA, VB, VC

Voltage rangeV secondary< 200 V secondary

Secondary rated voltageMeasuring rangeFrequency range

100 V to 125 V(0.8 to 2) · Vrated

49 Hz to 51 Hz at frated = 50 Hz59 Hz to 61 Hz at frated = 60 Hz

Tolerance 0.1 % of the measured value in the above mentionedmeasuring range

Frequency range (expanded) 40 Hz to 60 Hz at frated = 50 Hz50 Hz to 70 Hz at frated = 60 Hz

Tolerance 0.3 % of the measured value in the above mentionedmeasuring range

VAB, VBC, VCA

Voltage rangeV secondary< 200 V

Secondary rated voltageMeasuring rangeFrequency range

100 V to 125 V(0.8 to 2) · Vrated

49 Hz to 51 Hz at frated = 50 Hz59 Hz to 61 Hz at frated = 60 Hz

Tolerance 0.1 % of the measured value in the above mentionedmeasuring range

Frequency range (expanded) 40 Hz to 60 Hz at frated = 50 Hz50 Hz to 70 Hz at frated = 60 Hz

Tolerance 0.3 % of the measured value in the above mentionedmeasuring range

Currents, Instrument Transformers

IA, IB, IC, 3l0Current range

A secondary< 1.6 Irated

Rated currentsMeasuring rangeFrequency range

1 A, 5 A(0.1 to 1.6) · Irated

49 Hz to 51 Hz at frated = 50 Hz59 Hz to 61 Hz at frated = 60 Hz

Tolerance 0.1 % of the measured value in the above mentioned measuring rangeFrequency range(expanded)

40 Hz to 60 Hz at frated = 50 Hz50 Hz to 70 Hz at frated = 60 Hz

Tolerance 0.3 % of the measured value in the above mentioned measuring range

Currents, Protection-Class Current Transformer

IA, IB, IC, 3l0Current range

A secondary< 100 Irated

12.65

Technical Data12.65 Operational Measured Values and Statistical Values

1426 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Rated currentsMeasuring rangeFrequency range

1 A, 5 A0.1 to 25 A49 Hz to 51 Hz at frated = 50 Hz59 Hz to 61 Hz at frated = 60 Hz

Tolerance 0.1 % of the measured value in the above mentioned measuring rangeFrequency range(expanded)

40 Hz to 60 Hz at frated = 50 Hz50 Hz to 70 Hz at frated = 60 Hz

Tolerance 0.3 % of the measured value in the above mentioned measuring range

Currents, Protection-Class Current Transformer

IA, IB, IC, 3l0Current range

A secondary< 50 Irated

Rated currentsMeasuring rangeFrequency range

1 A, 5 A0.1 to 25 A49 Hz to 51 Hz at frated = 50 Hz59 Hz to 61 Hz at frated = 60 Hz

Tolerance 0.13 % of the measured value in the above mentioned measuring rangeFrequency range(expanded)

40 Hz to 60 Hz at frated = 50 Hz50 Hz to 70 Hz at frated = 60 Hz

Tolerance 0.6 % of the measured value in the above mentioned measuring range

Currents, Sensitive Ground-Current Transformer

3I0Current range

A secondary< 1.6 Irated

Rated currentsMeasuring rangeFrequency range

1 A, 5 A(0.1 to 1.6) · Irated

49 Hz to 51 Hz at frated = 50 Hz59 Hz to 61 Hz at frated = 60 Hz

Tolerance 0.1 % of the measured value in the above mentioned measuring rangeFrequency range(expanded)

40 Hz to 60 Hz at frated = 50 Hz50 Hz to 70 Hz at frated = 60 Hz

Tolerance 0.3 % of the measured value in the above mentioned measuring range

Phase Angle

ΦV °Frequency range 47.5 Hz to 52.5 Hz at frated = 50 Hz

57.5 Hz to 62.5 Hz at frated = 60 Hz

Tolerance ΦV 0.2 ° at rated voltageΦI °Frequency range 47.5 Hz to 52.5 Hz at frated = 50 Hz

57.5 Hz to 62.5 Hz at frated = 60 Hz

Tolerance ΦI 0.2 ° at rated current

Power Values

Active power P W secondary

Technical Data12.65 Operational Measured Values and Statistical Values

SIPROTEC 5, Overcurrent Protection, Manual 1427C53000-G5040-C017-6, Edition 11.2015

Measuring rangeVoltage rangeCurrent rangeFrequency range

|cosφ| ≥ 0.01(0.8 to 1.2) · Vrated

(0.1 to 2) · Irated

49 Hz to 51 Hz at frated = 50 Hz59 Hz to 61 Hz at frated = 60 Hz

Tolerance 0.3 % of the measured value in the above mentionedmeasuring range

Frequency range (expanded) 40 Hz to 69 Hz at frated = 50 Hz50 Hz to 70 Hz at frated = 60 Hz

Tolerance 0.5 % of the measured value in the above mentionedmeasuring range

Reactive power Q var secondaryMeasuring rangeVoltage rangeCurrent rangeFrequency range

|cosφ| ≥ 0.984(0.8 to 1.2) · Vrated

(0.1 to 2) · Irated

49 Hz to 51 Hz at frated = 50 Hz59 Hz to 61 Hz at frated = 60 Hz

Tolerance 1.0 % of the measured value in the above mentionedmeasuring range

Frequency range (expanded) 40 Hz to 69 Hz at frated = 50 Hz50 Hz to 70 Hz at frated = 60 Hz

Tolerance 1.5 % of the measured value in the above mentionedmeasuring range

Apparent power S VAMeasuring rangeVoltage rangeCurrent rangeFrequency range

(0.01 to 2) · Srated

(0.8 to 1.2) · Vrated

(0.01 to 2) · Irated

49 Hz to 51 Hz at frated = 50 Hz59 Hz to 61 Hz at frated = 60 Hz

Tolerance 0.3 % of the measured value in the above mentionedmeasuring range

Frequency range (expanded) 40 Hz to 69 Hz at frated = 50 Hz50 Hz to 70 Hz at frated = 60 Hz

Tolerance 0.5 % of the measured value in the above mentionedmeasuring range

Frequency

Frequency f HzRange frated - 0.20 Hz < frated + 0.20 Hz

Tolerance ± 5 mHz in the Vrated range

Range frated - 3.00 Hz < frated + 3.00 Hz

Tolerance ± 10 mHz in the Vrated range

Frequency range(expanded)

25 Hz to 80 Hz; operational measured values10 Hz to 80 Hz; functional measured values, system frequency

Tolerance 20 mHz in the range frated ± 10 % for rated values

Technical Data12.65 Operational Measured Values and Statistical Values

1428 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Statistic Values of the Device

Device Operating Hours hRange 0 to 9999999 hTolerance 1 h

Statistic Values of the Circuit Breaker

Op.cnt. (operation counter)Range 0 to 999999999Tolerance None∑I Off (sum of the primaryoutgoing currents)

A, kA, MA, GA, TA, PA primary

Range 0 to 9.2e+15Operating hours hRange 0 to 9999999 hTolerance 1 hCB open hours hRange 0 to 9999999 hTolerance 1 h

Statistic Values of the Disconnector

Op.cnt. (operation counter)Range 0 to 999999999Tolerance None

Technical Data12.65 Operational Measured Values and Statistical Values

SIPROTEC 5, Overcurrent Protection, Manual 1429C53000-G5040-C017-6, Edition 11.2015

Energy Values

Setting Values

Active energy Wp

Reactive energy Wq

kWh, MWh, GWhkvarh, Mvarh, Gvarh

Range ≤ 2% for I > 0.1 Irated,V > 0.1 Vrated

|cosφ| ≥ 0.707Tolerance at rated frequency 1 %

12.66

Technical Data12.66 Energy Values

1430 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Phasor Measurement Unit

Accuracy

As per IEEE Std C37.118.1a-2013

Synchrophasor Standard

IEEE Std C37.118.1-2011

12.67

Technical Data12.67 Phasor Measurement Unit

SIPROTEC 5, Overcurrent Protection, Manual 1431C53000-G5040-C017-6, Edition 11.2015

Circuit-Breaker Wear Monitoring

Setting Values

Threshold value ΣIx-method stage 0 to 10 000 000 Increments of 12P-method stage 0 to 10 000 000 Increments of 1I2t-method stage 0.00 I/Ir*s to 21 400 000.00 I/Ir*s Increments of 0.01

CB opening time 0.001 s to 0.500 s Increments of 0.001 sCB break time 0.001 s to 0.600 s Increments of 0.001 sCB make time 0.001 s to 0.600 s Increments of 0.001 sExponent for the ΣIx method 1.0 to 3.0 Increments of 0.1Switching cycles at Irated 100 to 1 000 000 Increments of 1

Rated short-circuit breaking current Isc 10 to 100 000 Increments of 1

Switching cycles at Isc 1 to 1000 Increments of 1

Level of warning 1 1 % to 100 % Increments of 1 %Level of warning 2 1 % to 100 % Increments of 1 %Operating currentthreshold

1 A @ 50 and 100Irated

0.030 A to 35.000 A Increments of 0.001 A

5 A @ 50 and 100Irated

0.15 A to 175.00 A Increments of 0.01 A

1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A

Delay correction time -0.050 s to 0.050 s Increments of 0.001 s

Tolerances

Tolerance of the measured value make time ± 2 ms

12.68

Technical Data12.68 Circuit-Breaker Wear Monitoring

1432 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

CFC

Typical response times and maximum number of ticks of the CFC task levels:

Task Level Time (in ms) Ticks for Non-Modular Deviceswith CP100

Ticks for ModularDevices with CP200

Ticks for ModularDevices with CP300

Fast Event-Triggered

<1 500 500 1000

Event-Triggered <10 12 367 12757 14702Interlocking <10 117 564 in total 121 537 in total 141 398 in totalMeasurement 250

The times describe the response time of a typical CFC chart at the respective task level. The maximumnumber of ticks applies to a typical load for the device based on the application template Directional time-overcurrent protection, grounded electrical power system. The maximum number can be lower in case ofextensive protection applications.The task level Measurement runs in cycles every 500 ms. All other task levels are event-triggered.In order to estimate the tick consumption of a CFC chart, you can use the following formula:

Tchart = 5 ∙ nInp + 5 ∙ nOutp + TTLev + ∑i Tint + ∑j TBlock

where:

nInp Number of indications routed as input in the CFC chartnOutp Number of indications routed as output in the CFC chartTTLev 101 Ticks in Fast Event-Triggered Level

104 Ticks in Event-Triggered Level54 Ticks in Measurement Level74 Ticks in Interlocking Level

Tint Number of internal connections between 2 CFC blocks in one chartTBlock Used ticks per CFC block (see Technical Data)

Table 12-8 Ticks of the Individual CFC Blocks

Element TicksABS_D 2.3ABS_R 1.5ACOS_R 6.9ADD_D4 3.4ADD_R4 3.3ADD_XMV 6.4ALARM 1.8AND_SPS 1.1AND10 2.9APC_DEF 1.2APC_EXE 1.0ASIN_R 1.3ATAN_R 1.2BLINK 1.3BOOL_CNT 2.0BOOL_INT 1.5BSC_DEF 1.3

12.69

Technical Data12.69 CFC

SIPROTEC 5, Overcurrent Protection, Manual 1433C53000-G5040-C017-6, Edition 11.2015

Element TicksBSC_EXE 1.1BUILD_ACD 2.9BUILD_ACT 2.2BUILD_BSC 1.2BUILD_DPS 1.4BUILD_ENS 1.3BUILD_Q 0.8BUILD_SPS 0.6BUILD_XMV 1.1BUILDC_Q 3.0CHART_STATE 5.9CMP_DPS 1.5CON_ACD 0.7CON_ACT 0.5CONNECT 0.4COS_R 2.5CTD 1.8CTU 1.6CTUD 2.3DINT_REAL 3.0DINT_UINT 3.0DIV_D 2.9DIV_R 1.6DIV_XMV 2.2DPC_DEF 0.4DPC_EXE 0.4DPC_INFO 1.1DPC_OUT 1.3DPS_SPS 1.0DRAGI_R 1.7EQ_D 1.0EQ_R 1.9EXP_R 1.5EXPT_R 2.7F_TRGM 0.3F_TRIG 0.3FF_D 0.9FF_D_MEM 1.4FF_RS 0.7FF_RS_MEM 1.2FF_SR 0.8FF_SR_MEM 1.1GE_D 0.9GE_R 1.1GT_D 0.9GT_R 1.2HOLD_D 1.1

Technical Data12.69 CFC

1434 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015

Element TicksHOLD_R 1.0INC_INFO 0.9LE_D 1.1LE_R 1.1LIML_R 1.5LIMU_R 1.5LN_R 3.3LOG_R 1.2LOOP 1.5LT_D 0.9LT_R 0.9MAX_D 0.9MAX_R 1.4MEMORY_D 0.9MEMORY_R 1.1MIN_D 0.7MIN_R 1.3MOD_D 1.5MUL_D4 2.5MUL_R4 2.7MUL_XMV 2.8MUX_D 1.2MUX_R 0.9NAND10 3.5NE_D 0.9NE_R 0.9NEG 1.2NEG_SPS 0.8NLC_LZ 7.1NLC_XMV 4.4NLC_ZP 3.0NOR10 3.2OR_DYN 1.1OR_SPS 1.3OR10 2.6R_TRGM 0.4R_TRIG 0.4REAL_DINT 3.0REAL_SXMV 3.0SIN_R 0.8SPC_DEF 0.4SPC_EXE 0.4SPC_INFO 0.4SPC_OUT 0.4SPLIT_ACD 3.4SPLIT_ACT 1.0SPLIT_BSC 1.3

Technical Data12.69 CFC

SIPROTEC 5, Overcurrent Protection, Manual 1435C53000-G5040-C017-6, Edition 11.2015

Element TicksSPLIT_DPS 1.0SPLIT_Q 0.7SPLIT_SPS 0.8SPLIT_XMV 0.8SQRT_R 0.6SUB_D 1.3SUB_R 1.6SUB_XMV 2.4SUBST_B 1.0SUBST_BQ 1.5SUBST_D 1.0SUBST_R 1.0SUBST_XQ 1.4SXMV_REAL 3.0TAN_R 1.1TLONG 2.2TOF 1.0TON 1.1TT 2.5TSHORT 1.9UINT_DINT 3.0

Technical Data12.69 CFC

1436 SIPROTEC 5, Overcurrent Protection, ManualC53000-G5040-C017-6, Edition 11.2015