Page 1: Sisteme de Aer Conditionat - ABTehnic Profesional · SI COMPRESOARE SCROLL The liquid chillers of the CWFR Series are designed to take advantage of the “free-cooling”, that is

RO EN

Sisteme de Aer Conditionat

Page 2: Sisteme de Aer Conditionat - ABTehnic Profesional · SI COMPRESOARE SCROLL The liquid chillers of the CWFR Series are designed to take advantage of the “free-cooling”, that is

2

NOTE

12

AER APA SOL

APARAT DE CLIMATIZARE''CLOSE CONTROL'' CHILERE FREE COOLING POMPE DE CALDURA GEOTERMALE

Page 3: Sisteme de Aer Conditionat - ABTehnic Profesional · SI COMPRESOARE SCROLL The liquid chillers of the CWFR Series are designed to take advantage of the “free-cooling”, that is

3

Grupurile de racire lichide ale Seriilor CWFR sunt proiectate pentru a lua avantajlul “free cooling”, acesta este suprimarea directain mediul extern a sarcinii termice a camerei conditionate. Aceste sisteme sunt utilizate in camerele unde sarcina termica este mare pe tot parcursul anului, chiar si in timpul iernii.

In acest caz, temperatura exterioara este putin mai mica decat temperatura camerei controlate. Astfel, apa curenta este racitaprintr-o baterie externa, in loc de ciclul frigorific.

In acest fel este atinsa o eficienta ridicata a energiei sezoniere, redu-candu-se consumul de energie la absorbtia ventilatorului.

GRUP RACIRE LICHIDE CU CONDENSATOR RACIT CU AER SI COMPRESOARE SCROLL

The liquid chillers of the CWFR Series are designed to take advantage of the “free-cooling”, that is the direct rejection to the external environment of the thermal load of the conditioned room.These systems are used in rooms where the thermal load is high during all year, even in winter.

In this case, the external temperature is rather lower than the tempe-rature of the controlled room. Thus the supply water is cooled through an external fi nned coil, instead of the refrigerating cycle.

In this way a high seasonal energy effi ciency is achieved, reducing the energy consumptions to the fan absorption.

WATER CHILLER AIR CONDENSER WITH SCROLL COMPRESSORS

CWFR F 320 ST WH

CWFR B 135 ST WH

CARCASA, carcasa din otel galvanizat, vopsita cu pulbere, cubaza de ridicare solida. Culoare RAL 7035.

COMPRESOR SCROLL, cu incalzitor electric cu carter. VAPORIZATOR CU PLACI, placi brazate din otel inoxidabil AISI 316, cu termostat antiinghet si presostat diferential/ comutator debitpentru a protej a circuitul frigorific.

CONDENSATOR CU BATERIE, cu tuburi de cupru si aripioarede aluminiu, protej ate de un grilaj metalic.

CONFIGURATII ALE UNITATII STANDARD

FRAME, galvanized steel frame, powder painting, with solid lifting base. RAL 7035 colour.

SCROLL COMPRESSOR, with crankcase electrical heater. PLATE EVAPORATOR, brazed plates in stainless steel AISI 316, with antifreeze thermostat and pressure differential switch/fl ow switch to protect the refrigerant circuit.

FINNED COIL CONDENSER, with copper tubes and aluminum fi ns, protected by metallic guards.

CONFIGURATION DE L’UNITÉ STANDARD

Page 4: Sisteme de Aer Conditionat - ABTehnic Profesional · SI COMPRESOARE SCROLL The liquid chillers of the CWFR Series are designed to take advantage of the “free-cooling”, that is

4

12

a) Mod de f unctionare pe timpul verii Apa curenta este racita de un ciclu frigorific regulat. Bateria

''''' ' free-cooling' '' este bypasata printr-un ventil 3-cai.

MODURI DE FUNCTIONARE

a) Summer mode The supply water is cooled down by the regular refrigerating cycle.

The free-cooling fi nned coil is by-passed through a 3-way valve.

RUNNING MODES

CWFR B 160 ST WH1 2 3 4 5

IDENTIFICAREA UNITATII IDENTIFICATION DES UNITÉS

SERIE:CWFR – grup racire lichide cu condensatoare racite cu aer,compresoare scroll si vaporizatoare cu placi.

MODEL:M = un singur compresorB = doua compresoare; compresoarele sunt in sistem tandem,

intr-un singur circuit frigorificF = patru compresoare; compresoarele sunt in sistem tandem, in

doua circuite frigorificeS = sase comresoare; compresoarele sunt in sistem tandem, in

VERSIUNI:ST = standardLN = nivel scazut de zgomot

SETARE:WH = fara modul hidrauluicMH = cu modul hidraulicMS = cu modul hidraulic si rezervor tampon

1

2

3

4

SERIE:CWFR – water chiller air condensers with scroll compressors and plate evaporators

MODEL:M = single compressorB = two-compressors; the compressors are in tandem layout, in a

single refrigerating circuitF = four-compressors; the compressors are in tandem layout, in

two refrigerating circuitsS = six-compressors; the compressors are in tandem layout, in two

refrigerating circuits.

VERSION:ST = standardLN = low noise

SET-UP:WH = without hydronic moduleMH = with hydronic moduleMS = with hydronic module and buffer tank.

1

2

3

4

VENTILATOARE AX. IALE. BATERIE CU VENTIL 3-CAI,trei moduri diferite de functionare (a se vedea mai j os).

CIRCUITUL FRIGORIFIC, in conformitate cu directiva PED, este echipat cu ventil termostatic, filtru, vizor de lichid, ventil de inchidere si presostate de inalta si j oasa presiune.

PANOUL ELECTRIC, cu intrerupator si relee fazate.

CONTROLER MICROPROCESOR, 16 bit si panou flash de

AGENT FRIGORIFIC R410A, OPD nul si temperatura mica de alunecare.

AXIAL FANS. WATER FINNED COIL WITH 3-WAY VALVE, downstream the evaporator, it manages the three different running modes (see below).

REFRIGERANT CIRCUIT, according to PED directive, with thermostatic valve, fi lter, liquid sight glass, shut-off valve and high and low pressure switches.

ELECTRICAL BOARD, with master circuit breaker and phase relays.

MICROPROCESSOR CONTROLLER, 16 bit and fl ash memory board.

R410A REFRIGERANT, null ODP and negligible temperature glide.

vaporizator in aval, care dirijeaza

memorie.

doua circuite frigorifice

COMPRESOR

Page 5: Sisteme de Aer Conditionat - ABTehnic Profesional · SI COMPRESOARE SCROLL The liquid chillers of the CWFR Series are designed to take advantage of the “free-cooling”, that is

5

Controlul este un factor cheie pentru un sistem de managementla sarcini partiale. Prin intermediul optiunilor diferite de manage-ment, unitatile FR sunt capabile sa asigure adaptabilitate ridicatala diferite cerinte.Controlul este realizat prin intermediul managementului compresoare-lor si un ventil modulator 3-cai.Managementul compresorului permite optimizarea functionariilor la sarcini partiale.Ventilul modulator 3-cai realizeaza controlul temperaturii apei curente(in cazul functionarii pe timpul iernii).

MOD DE CONTROL

The control logic is a key factor for a system management at part loads. Through various management options, FR units are able to assure the highest adaptation to different requirements.

The control is performed through the management of compressors and 3-way modulating valve.The compressor management allows the optimization of their running at part loads.The 3-way modulating valve performs the control of the supply water temperature (in case of winter running).

CONTROL MODE

b) Mod de f unctionare pe perioada de tranzitie Cand temperatura aerului exterior este mai mica cu 1°C

decat cea a apei curente, ventilul 3-cai alimenteaza bateria '' free-cooling'. Intregul flux de apa este pre-racit, in timp ce compresoarele refuleaza la sarcina partiala pentru a metine conditiile set-point. Acest mod de control este deosebit de important la latitudini medii:

sistemele functioneaza in aceste conditii pentru cea mai mare parte din durata de viata.

c) Mod de f unctionare pe timpul iernii Apa curenta este racita in bateria ' free-cooling', profitand

de temperatura exterioara scazuta. Temperatura apei este contro-lata de un ventil modulator 3-cai. Astfel, consumul de energieeste redus de absorbtia ventilatorului, minimizand eficienta energetica.

b) Intermediate season mode When the external air temperature is 1°C lower than the supply

water, the 3-way valve feeds the free-cooling fi nned coil. The whole water mass fl ow is pre-cooled, while the compressors run at part load, to maintain the set-point conditions.

This control mode is particularly important at mean latitudes: systems operate under these conditions for the largest part of life time.

c) Winter mode The supply water is cooled down in the free-cooling fi nned coil,

taking advantage of the low external temperature. The water temperature is controlled by the 3-way modulating valve. Thus energy consumptions are reduced to the fan absorption, maximizing the energy effi ciency.

COMPRESOR

COMPRESOR

Page 6: Sisteme de Aer Conditionat - ABTehnic Profesional · SI COMPRESOARE SCROLL The liquid chillers of the CWFR Series are designed to take advantage of the “free-cooling”, that is

6

• RCP: Panou de control la distanta• SB5: RS485 tip tablou de serie• ACB: Ceas alarma panou• HLM: Manometru agent frigorific de inalta/ j oasa presiune• CRV: Ventile de aspiratie/ refulare compresor• SVL: Ventil electromagnetic in linia de lichid• RSA: Tampoane de amortizare de cauciuc• SSA: Amortizoare cu arc• AFH: Incalzitoare electrice antianghet• WSP:Pachet Service Wireless pentru service la distanta prin SMS• YFS: Filtru “Y” cu tesatura din otel inoxidabil• PIH: Cap de pompa care creste pana la 400 kPa • BCP: Baterie anticoroziva pentru instalari in medii

corozive• RLD: Vopsire serie “RAL” altele decat cele standard.

ACCESORII

• RCP: Remote control panel• SB5: RS485 type serial board• ACB: Alarm log clock board• HLM: High/low refrigerant pressure gauges• CRV: Compressor suction/discharge valves• SVL: Solenoid valve in the liquid line• RSA: Rubber shock absorbers• SSA: Spring shock absorbers• AFH: Antifreeze electrical heaters• WSP: Wireless Service Pack for remote service via SMS• YFS: “Y” fi lter with stainless steel mesh• PIH: Pump with increased head up to 400kPa• BCP: Battery corrosion proofi ng for installations in aggressive

environments• RLD: Painting “RAL” serie other than standard.

ACCESSORIES

12

CWFRla retea prin intermediul sistemelor de supraveghere. Acesteapermit controlul de la distanta a functiilor principale ale sistemului.In plus, este posibila conectarea unitatilor FR la un sistem BMSprin intermediul convertizoarelor, furnizate optional (ModBus,Echelon, BacNet).

CONTROL DE LA DISTANTA

CWFR units are designed to allow the network connection by means of supervision systems. They allow the remote control of the main functions of the system. In addition, it is possible to connect the FR units to a BMS system by protocol converters, provided as optional (ModBus, Echelon, BacNet).

REMOTE CONTROL

in functie de temperatura aerului extern.In cele ce urmeaza, sunt raportate cateva exemple de consumuride energie lunare a doua unitati cu aceeasi capacitate de racire, cu sifara sistemul ' Free cooling'. Au fost luate in considerare patru orase europene (Milano, Paris, Frankfurt si Stackholm).Economisirea anuala de energie a unei unitati CWFR , poate aj ungela 50% din consumul total de energie, ca pentru ex. din Stackholm.

ECONOMII DE ENERGIE CU '''''FREE COOLING

The Free cooling technique allows remarkable energy savings, depending on the external air temperature.In the following, some examples of monthly energy consumptions of two units of the same cooling capacity, with and without Free cooling, are reported. Four European cities (Milan, Paris, Frankfurt and Stockholm) have been considered.The annual energy saving of a CWFR unit can reach the 50 % of the total energy consumptions, as for Stockholm.

ENERGY SAVING WITH FREE COOLING

Consumul de energie calculat pentru: Energy consumptions calculated for:• Volumul interior al camerei: 300 m3

• Functia medie de tranfer a peretelui: 0,4 W/m2K Economii de energie

• Inside room volume: 300m3 • Average wall transmittance: 0,4 W/m2K Energy saving

• Admisia aerului pe ora: 0,5 Vol/h• Sarcina termica interior: 200 kW

Consumul de energie cu sistemul Free-Cooling

• Hourly air intake: 0,5 Vol/h• Inside thermal load: 200 kW

Energy consumption with Free-Cooling

Unitatile sunt proiectate pentru a permite conexiunea

Mecanismul ' Free cooling' permite economii remarcabile de energie,

Page 7: Sisteme de Aer Conditionat - ABTehnic Profesional · SI COMPRESOARE SCROLL The liquid chillers of the CWFR Series are designed to take advantage of the “free-cooling”, that is

7

TIP - TYPE 040 053 068 080 105 135 160 210 270 320 405 480Capacitate de racire fara FREE-COOLING 1)

Cooling capacity without FREE-COOLING 1) kW 39,4 53,2 68,2 79,8 106,4 136,3 159,6 212,8 272,7 319,1 409,0 478,7

Puterea electrica ceruta fara FREE-COOLING 1)

Electrical power input without FREE-COOLING 1) kW 15,4 21,2 27,5 27,7 37,0 52,4 61,7 82,6 104,4 123,1 159,9 186,1

Capacitate de racire cu FREE-COOLING (T ext = 2°C) Cooling capacity with FREE-COOLING (T ext = 2°C) kW 32,2 50,9 59,6 60,1 64,7 96,8 131,1 186,0 193,6 262,2 368,0 450,0

Cooling capacity with FREE-COOLING (T ext = 5°C) kW 24,7 39,1 45,8 46,2 49,6 74,3 100,0 142,0 148,6 200,0 282,0 344,0

Electrical power input with FREE-COOLING kW 2,7 3,8 5,1 1,5 2,2 7,6 9,4 13,0 14,8 18,4 25,5 29,1

SECTIUNEA RACIRE - COOLING SECTION

Debit de apaWater fl ow m3/h 7,6 10,2 13,1 15,3 20,4 26,1 30,6 40,8 52,2 61,1 81,5 95,2

Cadere de presiune baterie FREE-COOLINGFREE-COOLING fi nned coil pressure drop kPa 27,3 18,4 29,8 20,3 34,2 23,9 38,5 40,8 23,9 38,5 40,8 56,3

Cadere de presiune vaporizatorEvaporator pressure drop kPa 43,4 44,3 39,8 45,4 46,2 46,6 46,0 46,6 46,1 47,1 56,5 45,9

COMPRESOR - COMPRESSOR

Numar / CircuiteNumber / Circuits - 1 / 1 1 / 1 1 / 1 1 / 1 2 / 1 2 / 1 2 / 1 4 / 2 4 / 2 4 / 2 6 / 2 6 / 2

TipType - Ermetico scroll / Hermetic scroll

Numar trepte de comprimareNumber of stages - 1 1 1 1 2 2 2 4 4 4 6 6

SECTIUNEA VENTILATOR - FAN SECTION

Debit de aer nominalNominal air fl ow m3/h 15500 25000 34000 34000 34000 51000 68000 85000 102000 136000 170000 205000

TipType - Centrifugo pale curve indietro con motore tipo EC / Centrifugal backward curve blade with EC type motor

Numar de ventilatoareNumber of fans - 2 2 2 2 2 3 4 5 6 8 10 12

Caderea de presiune admisie ventilatorFan nominal power input kW 1,2 2,3 3,6 3,6 3,6 5,4 7,2 9,0 10,8 14,4 18,0 21,6

Putere de admisie maximaMax power input kW 1,2 2,5 4,0 4,0 4,0 6,0 8,0 10,0 12,0 16,0 20,0 24,0

SECTIUNEA ELECTRIC - ELECTRIC SECTION

Sursa de alimentarePower supply - 400 / 3N / 50Hz

Curent nominal de intrareNominal input current A 24 36 45 49 67 86 94 129 169 183 251 273

Curent de intrare maximMax input current A 38 55 69 83 106 134 162 208 264 320 394 478

Curent de cuplare maximMax inrush current A 198 219 264 324 270 329 403 270 329 403 329 403

NIVELUL DE ZGOMOT - SOUND LEVEL 2)

Nivelul de zgomotSound power level dB(A) 77 78 79 80 81 82 83 83 84 84 85 86

DIMENSIUNI - DIMENTIONS

LungimeLenght (L) mm 1900 2200 2200 2200 2200 3240 4280 5320 4280 5320 6360 7380

AdancimeDepht (W) mm 1100 1100 1100 1100 1100 1100 1100 1100 2200 2200 2200 2200

InaltimeHeight (H) mm 1570 2255 2255 2255 2255 2255 2255 2255 2310 2310 2310 2310

Greutate - DXAWeight - DXA kg 550 850 930 950 970 1600 1850 2050 2580 3380 3600 3800

DATE TEHNICE - TECHNICAL DATA

1) Apa 7-12°C - 51°C condensare/ Water 7-12°C - 51°C condensing; Agent frigorific/Refrigerant fl uid R410A2) Nivelul de zgomot 1 mt in camp liber / sound pressure level @ 1 mt in free fi eld

GRUP RACIRE LICHIDE CU BATERIA FREE COOLING, cu condensator racit cu aer (CWFR)WATER CHILLERS WITH FREE COOLING FINNED COIL, with air condensation (CWFR)

CWFR R410A APA

Capacitate de racire cu FREE-COOLING (T ext = 5°C)

Puterea electrica ceruta cu FREE-COOLING

Page 8: Sisteme de Aer Conditionat - ABTehnic Profesional · SI COMPRESOARE SCROLL The liquid chillers of the CWFR Series are designed to take advantage of the “free-cooling”, that is