Main Features• Two isolated addressable loops - ring connection• Apollo XP, Discovery and System Sensor (Notifier) protocols• Single or redundant Hot back up configuration• Hot swap card replacement• EN54-2 Certified• SIL-2 Certified according to IEC61508-2 and IEC61508-3• OnLine configuration via Web Browser• Modbus TCP/IP communication protocol• CIP Safety (Rockwell) communication protocol for SIL application• Customizable third party protocol• 1 slot space into 19” rack
SM-ALM
Tag Colour FunctionTX-RX Blinking Interface Communication LED
COM Loop Polling LED
MCU Blinking CPU Normal Operation
FAULTSystem is Normal
Common Loop Fault Ch1 or Ch2 Device or Loop
LKGSystem Isolated from Ground
Ground Detection Fault
ALARMSystem is Normal
Common Alarm Ch1 or Ch2 devices
DISSystem is Normal
Common Disable Ch1 or Ch2 devices
SFLTOff System is Normal
Card Fault (blinking is in programming mode)
32V 32Vdc Power supply
24V-1 24Vdc Channel 1
24V-2 24Vdc Channel 2
5V 5Vdc Power supply
3V3M 3Vdc Communication Module (Optional)
3V3 3Vdc Microprocessor
Front Card LEDs Indication
Loop Cable Specifi cationsThe Addressable loop cable shall be twisted shielded pair with maximum 50 Ohm resistance and 1uF capacity.In the loop design, the following limitations shall be considered:
Limits on single channel with 150 mA consumption Maximum resistance 50 Ohm
Limits on single channel with 250 mA consumption Maximum resistance 28 Ohm
Limits on single channel with 500 mA consumption Maximum resistance 12 Ohm
Limits on single channel with 1000 mA consumption Maximum resistance 6 Ohm
Optional redundantSM-ALM
MainSM-ALM
Tag cable label Description Connector PIN
A1+ OUT POSITIVE LOOP1 JA 8
A1- OUT NEGATIVE LOOP1 JA 7
B1+ RETURN POSITIVE LOOP1 JA 10
B1- RETURN NEGATIVE LOOP1 JA 11
A2+ OUT POSITIVE LOOP2 JA 5
A2- OUT NEGATIVE LOOP2 JA 3
B2+ RETURN POSITIVE LOOP2 JA 1
B2- RETURN NEGATIVE LOOP2 JA 6
- NOT USED JA 12
- NOT USED JA 2
- NOT USED JA 4
- NOT USED JA 9
Card Wiring
*JA connection according to the ALM position into the rack
JA JA JA JA JA JA JA JA JA
JA
Confi guration & Connection
loop 1
loop 2
NOTIFIER DEVICES• 99 AUTOMATIC DETECTORS• 99 MODULES (CONTROL, MONITOR, MANUAL CALL POINT)ORAPOLLO DEVICES XP95 - DISCOVERY• 126 DEVICES (DETECTOR, MODULE, SOUNDER, BEACON, MANUAL CALL POINT)
SMOKE DETECTOR
SMOKE DETECTOR
HEATDETECTOR
HEATDETECTOR
MANUAL CALL POINT
MANUAL CALL POINT
FIREBEACON
FIREBEACON
DISCHARGE HORN
DISCHARGE HORN
CONTROL MODULE
CONTROL MODULE
MONITOR MODULE
MONITOR MODULE
RELAYMODULE
RELAYMODULE
NOTIFIER DEVICES• 99 AUTOMATIC DETECTORS• 99 MODULES (CONTROL, MONITOR, MANUAL CALL POINT)ORAPOLLO DEVICES XP95 - DISCOVERY• 126 DEVICES (DETECTOR, MODULE, SOUNDER, BEACON, MANUAL CALL POINT)
RELAY CONTACT:• common fi re• common fault
Web BrowserConnecting laptop directly to the RJ45 lan port (password required) is possible to visualize devices status and to confi gure the general and detail parameter of the cards. Standard Windows browser is used for online confi guration.
From the confi guration page is possible to:• Assign the IP address of the card• Confi gure Network• Display Ch1 or Ch2 device status• Download Ch1 or Ch2 device confi guration program
Device Status Page
Network Confi guration Page
SAFCO Engineering S.p.A.Via Caduti del Lavoro, 10/A - 20096 Pioltello (MI) ItalyT. +39 02 95327396 - F. +39 02 [email protected]
SAFCO Engineering S.R.L - Abu Dhabi10th Street - Al Fahim Building, 4th Floor, Offi ce 411P.O. Box 27212 - Mussafah - Abu Dhabi – UAET. +971 (2) 5558006 - F. +971 (2) [email protected]
www.safcoengineering.com