smart grid monitoring of transformers by dga by michel duval

65
1 Smart Grid Monitoring of Transformers by DGA Michel Duval CIGRE Thailand, Bangkok 2013

Upload: vuthuy

Post on 02-Jan-2017

291 views

Category:

Documents


17 download

TRANSCRIPT

Page 1: Smart Grid Monitoring of Transformers by DGA by Michel Duval

1

Smart Grid Monitoring of Transformers

by DGA

Michel Duval

CIGRE Thailand, Bangkok 2013

Page 2: Smart Grid Monitoring of Transformers by DGA by Michel Duval

2

Electric Power

Page 3: Smart Grid Monitoring of Transformers by DGA by Michel Duval

3

Power Transformers

Page 4: Smart Grid Monitoring of Transformers by DGA by Michel Duval

4

Catastrophic Failures

Page 5: Smart Grid Monitoring of Transformers by DGA by Michel Duval

55

Failures in Service

- The failure rate of power transformers in service (internal

failures needing repairs) typically is 0.3% per year.

- For a population of 2000 transformers, this means 6

transformers will fail in the next year.

- Less than 1 will fail catastrophically.

- 1994 will not fail.

- 200 (i.e., 10% of the population at or above IEEE/IEC

condition 1) will form abnormal amounts of gases because

of faults.

Page 6: Smart Grid Monitoring of Transformers by DGA by Michel Duval

66

The Monitoring Dilemma

- Nobody knows which 6 of the 2000 transformers will fail

next year.

- To identify them, all the transformers need to be monitored,

including the 1800 operating normally, just for the purpose of

detecting the 6 that will fail and need repairs and the less

than 1 that may eventually fail catastrophically.

- In economic terms, the cost of monitoring is justified as long

as it does not exceed the cost of not detecting the 6 failures

and the catastrophic one (typically, >20M$).

Page 7: Smart Grid Monitoring of Transformers by DGA by Michel Duval

77

Smart Grid Monitoring

- A smart grid is a modernized electrical grid that uses

information and communications technology in an

automated fashion to improve the efficiency, reliability and

sustainability of the production and distribution of electricity.

- It implies a re-engineering of the electricity services industry.

- It requires monitoring tools for evaluating on a real-time

basis the condition of electrical equipment, so as to optimize

asset utilization, system reliability and load capabilities

Page 8: Smart Grid Monitoring of Transformers by DGA by Michel Duval

88

Monitoring Tools

-General tools for monitoring oil temperature, oil pressure,

partial discharges, etc, in transformers are available.

-However, for the early detection of faults and failures and

evaluating the condition of transformers, the main

monitoring tool is dissolved gas analysis (DGA).

-More than 1 million DGA analyses are performed by ~600

laboratories and ~ 40,000 on-line gas monitors each year

worldwide.

Page 9: Smart Grid Monitoring of Transformers by DGA by Michel Duval

99

Basic Types of Faults

Detectable by DGA

-PD: partial discharges of the corona-type in voids in paper

insulation, as a result of poor drying or impregnating with oil.

-D1: low-energy discharges, such as partial discharges of

the sparking-type in oil or paper, tracking on paper, small

arcing, arc-breaking activity in LTCs.

-D2: high-energy discharges, e.g., flashovers, high-energy

arcing, short-circuits with power follow through, with

Buccholz alarms and tripping.

Page 10: Smart Grid Monitoring of Transformers by DGA by Michel Duval

1010

Basic Types of Faults

Detectable by DGA

-T1: thermal faults of low temperature T < 300ºC, because

of overloading, insufficient cooling, design problems.

-T2: thermal faults of 300 <T< 700ºC, because of defective

contacts, welds, with carbonization of paper.

-T3: thermal faults of high temperature T >700ºC, because

of high circulating currents in core and coil, short circuits in

laminations, often in oil only.

Page 11: Smart Grid Monitoring of Transformers by DGA by Michel Duval

1111

Additional Sub-Types of Faults

Detectable by DGA

-S: stray gassing of oil (in oil only) at T <200ºC, because of

the chemical instability of oils produced since ~ 2000.

-O: overheating of oil or paper at T <250ºC, therefore

without carbonization of paper.

-R: catalytic reactions of water with e.g., galvanized steel.

-these low-temperature faults, including corona PDs, are of

little concern in transformer.

Page 12: Smart Grid Monitoring of Transformers by DGA by Michel Duval

1212

Additional Sub-Types of Faults

Detectable by DGA

-T3/T2 in oil only: at T >700/ 300ºC, of minor concern as

long as they do not evolve into faults D1, D2 or C.

-C: carbonization of paper at T >300ºC, potentially more

dangerous (loss of insulating properties of paper).

Page 13: Smart Grid Monitoring of Transformers by DGA by Michel Duval

1313

DGA Diagnosis Methods

-Key Gas, Rogers and IEC methods. Limitations are high %

of wrong diagnosis (50%) or undiagnosed cases (30%),

respectively.

-Duval Triangle 1, allowing to detect the 6 basic types of

faults (PD, D1, D2, T3, T2, T1 + DT).

-Duval Triangles 4 and 5, allowing to detect the 5 sub-types

of faults (S, O, R, T3/T2 in oil, C), and to distinguish

between faults of lesser concern in oil and more serious

faults in paper.

Page 14: Smart Grid Monitoring of Transformers by DGA by Michel Duval

1414

Duval Triangles 1, 4 and 5

Triangle 1

Triangle 4 Triangle 5

Page 15: Smart Grid Monitoring of Transformers by DGA by Michel Duval

151515

Use of Triangles 4 and 5

-Triangles 4 and 5 should never be used in case of faults

identified with Triangle 1 as faults D1 or D2.

-Triangle 4 should be used only for faults identified first

with Triangle 1 as low temperature faults PD, T1 or T2, or

when there is a high level of H2.

-Triangle 5 should be used only for faults identified first

as high temperature thermal faults T2 or T3.

15

Page 16: Smart Grid Monitoring of Transformers by DGA by Michel Duval

16

Mixtures of Faults

-mixtures of faults sometimes occur rather than « pure »

faults and may be more difficult to identify with certainty.

-for instance, mixtures of faults D1 and T3 may appear as

faults D2 in terms of gas formation.

Page 17: Smart Grid Monitoring of Transformers by DGA by Michel Duval

17

New Faults vs. Old Faults:

-when a new fault appears, as evidenced by a change in

gas pattern, a more precise identification of the new fault

may be obtained by subtracting the gas concentrations

corresponding to the old fault from those corresponding to

the new one (incremented values).

-this, however, introduces additional uncertainty on the

subtracted value.

Page 18: Smart Grid Monitoring of Transformers by DGA by Michel Duval

1818

Interpretation of CO and CO2

-Until recently, CO and CO2 were considered as good

indicators of paper involvement in faults. Recent

investigations at CIGRE, however, have shown that this is

not always the case.

-High concentrations of CO (>1000 ppm) and/or low

CO2/CO ratios (<3), WITHOUT the formation of significant

amounts of hydrocarbon gases, are NOT an indication of a

fault in paper, particularly in closed transformer, but are

rather due to oil oxidation under conditions of limited supply

of O2.

Page 19: Smart Grid Monitoring of Transformers by DGA by Michel Duval

191919

CO2

and CO from Closed Transformers

Ref: I.Hoehlein, CIGRE TF15 (2010)

56 MVA, 220kV

Manufactured 2006

Rubber Bag

19

Page 20: Smart Grid Monitoring of Transformers by DGA by Michel Duval

2020

Interpretation of CO and CO2

-High concentrations of CO (>1000 ppm) and low CO2/CO

ratios (<3), TOGETHER WITH the formation of significant

amounts of hydrocarbon gases, may be an indication of a

fault in paper (to be confirmed with Triangles 4 or 5 and

furans).

-High concentrations of CO2 (>10,000 ppm), high CO2/CO

ratios (>20) and high values of furans (>5 ppm) are an

indication of the slow degradation of paper at relatively low

temperatures (<140°C), down to low degrees of

polymerization (DP) of paper.

Page 21: Smart Grid Monitoring of Transformers by DGA by Michel Duval

2121

Interpretation of CO and CO2

-Low concentrations of CO and CO2, below condition 1 of

IEC or IEEE (750 and 7500 ppm, respectively), correspond

to normal gassing in transformers without faults.

-Intermediate concentrations of CO, CO2 and CO2/CO ratios

may indicate a slow degradation of paper and intermediate

DPs of paper, of no concern at all for the normal operation

of the transformer.

Page 22: Smart Grid Monitoring of Transformers by DGA by Michel Duval

2222

Interpretation of CO and CO2

-Zero or very low rates of change of CO and CO2 do not

necessarily mean the absence of a fault in paper. Localized

faults in paper often do not produce detectable amounts of

CO and CO2 against the usually high background of these

gases in service.

-However, they do produce significant amounts of the other

hydrocarbon gases, allowing the detection of faults in paper

with Triangles 4 or 5.

Page 23: Smart Grid Monitoring of Transformers by DGA by Michel Duval

2323

Example of a Localized Fault in Paper

Page 24: Smart Grid Monitoring of Transformers by DGA by Michel Duval

242424

24

CIGRE Risk of Failure vs. CO2

-The risk of failure is very low at high CO2 values, which are

strongly correlated with paper degradation and low DPs of

paper, suggesting that the risk of failure at low DPs of paper is

also very low, not very high as generally mentioned.

-Indeed, large numbers of transformers have been observed at

CIGRE to operate quite normally with DPs of paper < 200.

-And no cases have been reported so far of transformers with

DPs < 200 that failed because of the mechanical weakness of

paper, even when subjected to external short-circuits.

24

Page 25: Smart Grid Monitoring of Transformers by DGA by Michel Duval

252525

25

Transformers at Risk of Failure

-So, in a large majority of cases, low DPs of paper do not

mean the « end-of-life » of transformers as generally

assumed.

-The main concern with low DPs of paper is the shrinkage of

paper and loosening of windings, not the mechanical (tensile)

strength of paper. This can be mitigated by reclamping

transformers.

-Transformers most at risk of failure are gassing transformers

that cannot be fixed.

25

Page 26: Smart Grid Monitoring of Transformers by DGA by Michel Duval

26

-Type of fault (electrical, thermal)

-Location of fault (paper, oil)

-Gas concentrations, gassing rates (conditions 1 to 4)

Factors Influencing the Interpretation

of DGA Results

Page 27: Smart Grid Monitoring of Transformers by DGA by Michel Duval

27

Typical / Condition 1 Values

-Typical /condition 1 values of IEC/ IEEE correspond to a

given percentile (90%) of the population of DGA results

-They mean that 90% of DGA results for dissolved gases

are below these 90% Typical values

-They are used to concentrate maintenance efforts on the

10% of the population with the highest gas levels and

therefore most at risk

Page 28: Smart Grid Monitoring of Transformers by DGA by Michel Duval

28

Typical / Condition 1 Values

-Below typical/ condition 1 values, gas formation is

considered not to be a concern for the equipment.

-Below these values, it is recommended to use “normal”

sampling frequency (monthly, semi-annual, etc.,..) and not

to attempt a diagnosis.

-Above these values, it is recommended to use „increased‟

sampling frequency (e.g., monthly or weekly) and a DGA

diagnosis may be attempted.

Page 29: Smart Grid Monitoring of Transformers by DGA by Michel Duval

29

90% Typical (Condition 1) Values

for Concentrations at IEC (2007), in ppm

(vs. source)

Page 30: Smart Grid Monitoring of Transformers by DGA by Michel Duval

30

90% Typical (Condition 1) Values

for Concentrations at IEEE (2013), in ppm

(vs. kV, MVA, age, %O2)

Page 31: Smart Grid Monitoring of Transformers by DGA by Michel Duval

313131

90% Typical (condition 1) Values for

Gassing Rates, in ppm/month

31

Page 32: Smart Grid Monitoring of Transformers by DGA by Michel Duval

32

Pre-failure (Condition 4) Values

-CIGRE has evaluated the probability of having a failure-

related event (PFS) in service vs. gas concentration and

gassing rate.

-Based on these PFS curves, pre-failure (condition 4)

values have thus been established, as well as intermediate

conditions 2 and 3.

Page 33: Smart Grid Monitoring of Transformers by DGA by Michel Duval

333333

33

Risk of Failure vs. Gases Formed

(PFS = Probabilityof Failure in Service)

33

Page 34: Smart Grid Monitoring of Transformers by DGA by Michel Duval

343434

CIGRE/IEC Sampling Intervals vs.

Concentrations in Service, in ppm

34

Page 35: Smart Grid Monitoring of Transformers by DGA by Michel Duval

353535

CIGRE/ IEC Sampling intervals vs.

Gassing Rates in Service, in ppm/month

35

Page 36: Smart Grid Monitoring of Transformers by DGA by Michel Duval

36

Actions Recommended by IEC at

Conditions 1-4

-Condition 1: increase oil sampling frequency for DGA

-Conditions 2-3: consider complementary tests

(infrared scans, acoustic tests, PD tests, effect of load).

-Conditions 3-4: consider transformer inspection.

-Condition 4: consider transformer repair or replacement.

Page 37: Smart Grid Monitoring of Transformers by DGA by Michel Duval

37

Transformer Parameters Influencing

Conditions 1-4

-CIGRE (2006)/ IEEE (2013):

-Operating conditions (load, climate)

-Age (new, old)

-Type (power, core, shell, instrument, reactor).

-MVA, voltage

-Open or closed

-CIGRE WG47 (2013):

-Fault type

Page 38: Smart Grid Monitoring of Transformers by DGA by Michel Duval

3838

Occurrence of Faults in Service at CIGRE

Page 39: Smart Grid Monitoring of Transformers by DGA by Michel Duval

3939

Effect of Type of Thermal Fault

on Condition 1 Values at CIGRE

(ppm)

(ppm)

Page 40: Smart Grid Monitoring of Transformers by DGA by Michel Duval

4040

Effect of Type of Electrical Fault

on Condition 1 Values at CIGRE:

(ppm)

(after deletingC2H2 < 2 ppm)

(ppm)

Page 41: Smart Grid Monitoring of Transformers by DGA by Michel Duval

4141

Effect of Type of Fault

on Condition 4 values at CIGRE:

(in ppm, using previous adjustment factors)

Page 42: Smart Grid Monitoring of Transformers by DGA by Michel Duval

4242

Comparison with Cases of High Gas Levels

without Failure at CIGRE:

(in ppm)

Page 43: Smart Grid Monitoring of Transformers by DGA by Michel Duval

4343

Monitoring with DGA

-Monitoring off-line (by manual or laboratory DGA) is mostly

used but cannot detect faults occurring between two oil

samplings (e.g., every year, month or week).

-On-line multi-gas or hydrogen monitors can detect abnormal

and/or quick-developing faults occurring within days or hours

between oil samplings.

Page 44: Smart Grid Monitoring of Transformers by DGA by Michel Duval

4444

Abnormal and Quick-Developing Faults

-Abnormal gassing (above condition 1 for concentrations

and gassing rates) will occur in 200 of the 2000

transformers.

-Quick-developing faults (above condition 4 for gassing

rates) will typically occur in 20 to 40 of them.

Page 45: Smart Grid Monitoring of Transformers by DGA by Michel Duval

4545

Detection of Quick-Developing Faults with a Multi-

Gas Monitor in a 3-Phase GSU Transformer

Day 2 – 16:00

Day 2 – 20:00

Day 3 – 00:00

Day 3 – 04:00

Day 2 – 12:00

Day 3 – 12:00

Day 3 – 16:00

Day 3 – 08:00

Day 23 – 04:00 to Day 24 – 08:00 Followed by transformer failure

C2H2 = 800 ppm/day!

Page 46: Smart Grid Monitoring of Transformers by DGA by Michel Duval

4646

700 MVA Transformer

C2H2 = 45 ppm/day!

Page 47: Smart Grid Monitoring of Transformers by DGA by Michel Duval

4747

336 MVA Transformer(Placed in Service -1969)

C2H4 = 300 ppm/day!

Page 48: Smart Grid Monitoring of Transformers by DGA by Michel Duval

4848

1100 MVA Transformer

C2H4 = 300 ppm/day!

Page 49: Smart Grid Monitoring of Transformers by DGA by Michel Duval

4949

-Gassing rates were all significantly above condition 4

values in the previous 4 examples.

-The corresponding transformers were removed from

service 1 to 3 days after looking at monitor readings, before

potential catastrophic failure.

-However, it might have been better to remove them from

service earlier.

-Without an on-line monitor, these transformers would

possibly have suffered catastrophic failures.

Page 50: Smart Grid Monitoring of Transformers by DGA by Michel Duval

5050

On-Line Monitoring with Multi-Gas Monitors

- Multi-gas monitors will detect all types of faults, even in

their early stages at condition 1, and without false alarms.

However, they are more expensive than hydrogen only

monitors.

- The recommendation of CIGRE (TB # 409, 2010) is

therefore to use multi-gas monitors in critical transformers

(GSU, nuclear, transmission) and in abnormally gassing

transformers.

Page 51: Smart Grid Monitoring of Transformers by DGA by Michel Duval

5151

Fault Detection with Hydrogen Monitors

Note: for faults T3 in paper (C), curve for H2 is a bit higher.Ref: Duval, TSUG 2013.

Page 52: Smart Grid Monitoring of Transformers by DGA by Michel Duval

5252

Fault Detection with Hydrogen Monitors

-Hydrogen monitors are most sensitive to stray gassing of

oil S (occurring in ~ 25% of cases), and to corona partial

discharges PD (occurring in only 0.3% of cases).

-Such faults will commonly produce thousands of ppm of H2

without being a concern for the transformers. If the limit in

hydrogen monitors is set at average condition 1 values for

H2 (100 ppm or 7 ppm/month), this may result into many

false alarms.

Page 53: Smart Grid Monitoring of Transformers by DGA by Michel Duval

5353

Fault Detection with Hydrogen Monitors

-Faults D1/D2 at dangerous condition 4 of CIGRE will

produce 0.5 ppm/day of C2H2 together with only 1 or 2

ppm/day of H2.

-If the limit for H2 in the monitor is set at average condition 1

(100 ppm), the monitor will detect these faults only in their

late stages (condition 3 or 4), when dangerous levels of 25

to 50 ppm of C2H2 have already formed.

-If it is set at 5 ppm over a period of 3 days, this may result

into many false alarms.

Page 54: Smart Grid Monitoring of Transformers by DGA by Michel Duval

5454

Fault Detection with Hydrogen Monitors

- In case of thermal faults T3/T2/T1/O the main gas formed is

C2H4, CH4 or C2H6, together with 3 to 10 times less of H2. If

the limit for H2 is set at 100 ppm, the monitor will detect

these faults only in their late stages (condition 3 or 4).

- Decreasing the limit for H2 in the monitor (e.g., to 50 or 20

ppm) will increase the number of false alarms due to faults

S or corona PD of lesser concern.

- The recommendation of CIGRE (in TB # 409, 2010) is

therefore to use hydrogen monitors in non-critical

transmission and distribution transformers, and in

transformers with no previous gassing history.

Page 55: Smart Grid Monitoring of Transformers by DGA by Michel Duval

55

Examples of On-Line Gas Monitors

Page 56: Smart Grid Monitoring of Transformers by DGA by Michel Duval

56

Multi-Gas Monitors

Monitors of the chromatographic type:

-after gas extraction, will separate individual gases on a GC

column, then measure them with GC detectors.

-TM8, TM3 (Serveron)

-Calisto 9 (Morgan Schaffer)

Page 57: Smart Grid Monitoring of Transformers by DGA by Michel Duval

57

Monitors of the Chromatographic-Type:

-use the same standardized, NIST-traceable technique

as laboratories.

-provide automatic recalibration at fixed intervals as

laboratories do.

-require some maintenance (change of carrier gas,

calibration gas mixture, GC columns every 3 to 5 years).

Page 58: Smart Grid Monitoring of Transformers by DGA by Michel Duval

58

Monitors of the Infrared-Type:

-after gas extraction, will measure directly individual gases with

an infrared detector, and H2 with a solid state sensor

-Transfix 8, Transport-X 7 (GE-Kelman) use a photo-acoustic

(PAS) detector.

-LumaSense 9 uses a non-dispersive IR detector.

Page 59: Smart Grid Monitoring of Transformers by DGA by Michel Duval

59

Monitors of the infrared type:

-do not require change of carrier gas and gas mixture.

-cannot measure H2 , O2 by infrared, requiring the use of

relatively inaccurate solid state sensors for that purpose.

-some may need recalibration because of contaminations

in the ambient air (SF6, oil vapours, solvents) and lamp

fade with time; some cannot be recalibrated in the field.

-require change of infrared lamp ~ every 5 years.

-contain several moving parts.

Page 60: Smart Grid Monitoring of Transformers by DGA by Michel Duval

60

Hydrogen Monitors

-Hydran (GE): measures 100% of the H2 + 18% of the CO

present in oil with a PTFE membrane and fuel cell detector.

-Calisto 2 (Morgan Shaffer): measures H2 only with a PTFE

membrane, GC and TCD detector.

-TM1, Qualitrol, Weidmann: measure H2 with an inorganic

membrane and an H2Scan Pd solid state sensor.

-TM1 (Serveron): improved version of H2Scan.

Page 61: Smart Grid Monitoring of Transformers by DGA by Michel Duval

6161

Other Applications of DGA

-DGA can also be used to detect faults in LTCs, using for

example Duval Triangle 2 for compartment types, and Triangles

2a to 2e for in-tank types.

-it can also be used for oils other than mineral oils, such as

natural esters (FR3, BioTemp), synthetic esters (Midel) and

silicone oils, using for example Duval Triangles 3.

Page 62: Smart Grid Monitoring of Transformers by DGA by Michel Duval

6262

DGA in LTCs at IEC/ IEEE:

Duval Triangle 2 for compartment types Duval Triangles 2 for in-tank typesN1 (MR types M, D)N3 (MR types VR, VV)N4 (MR types R, V)N5 (MR types G, UZD)

Page 63: Smart Grid Monitoring of Transformers by DGA by Michel Duval

636363

Duval Triangles 3 for Non-Mineral oils

Mineral oil

FR363

Page 64: Smart Grid Monitoring of Transformers by DGA by Michel Duval

646464

64

DGA in wind farm transformers at CIGRE

64

-Because they are usually Padmount transformers not

designed for that purpose, many tend to form lots of gases,

as a result of:

-Corona PDs, because of poor oil impregnation.

-Stray gassing of oil, because of abnormal overheating.

Page 65: Smart Grid Monitoring of Transformers by DGA by Michel Duval

656565

65

Stray gassing of oil at CIGRE

-With mineral oil, H2 at T<120C and CH4, C2H6 at

T>200C.

-With vegetable oils (e.g.,FR3), H2 at T<70C and C2H6

at higher temperatures (Triangles 6 and 7).

-With silicone oils, H2 at T>200C.

65