smc flex parameters1r

7
9/18/08 – Firmware Version 4.002 or later SMC Flex – Complete Parameter List Programming some of these parameters may require advanced knowledge of the application for proper operation. For additional assistance or explanation with regards to these parameters, please contact the Industrial Control Technical Support group at: [email protected] or Phone number 440- 646-5800 Parameter # Description Parameter Numbers and descriptions are valid for SMC-Flex firmware 4.002 or later. 1 Volts Phase A-B Provides the three phase-to-phase supply voltage measurements at all times, including bypass operation. 2 Volts Phase B-C Provides the three phase-to-phase supply voltage measurements at all times, including bypass operation. 3 Volts Phase C-A Provides the three phase-to-phase supply voltage measurements at all times, including bypass operation. 4 Current Phase A Provides the three phase motor current measurement. This measurement is always line current regardless of t he motor connection (Wye or Delta). 5 Current Phase B Provides the three phase motor current measurement. This measurement is always line current regardless of t he motor connection (Wye or Delta). 6 Current Phase C Provides the three phase motor current measurement. This measurement is always line current regardless of t he motor connection (Wye or Delta). 7 Watt Meter Provides the power usage of the connected motor. This value is calculated from the voltage, current and power factor measurements. 8 Kilowatt Hours Provides the power usage over time of the c onnected motor. 9 Elapsed Time Indicates the total time of motor operation in hours. The accumulated time is updated continuously during running. 10 Meter Reset Provides the user the capability to reset the value stored in the elapsed time (9) and k ilowatt hours (8) meters to zero. 11 Power Factor Provides the operational displacement power factor measurement of the connected motor. 12 Mtr Therm Usage Provides the theoretical model of motor heating as a percentage value. At 100% MTU, the controller will f ault on overload. This model is based on the mot or thermal overload calculation. 13 Motor Speed Indicates the operating percentage of motor base speed when linear ramp is selected and an external tachometer is used. 14 SMC Option This a “read-only” parameter that identifies to the user the type of control module installed. 15 Motor Connection This parameter allows the user the abilit y to select the power wiring configuration of the attached motor (WYE or DELTA). A fault controlled means of disconnecting the line should always be use in the DELTA mode. 16 Line Voltage This parameter sets the base voltage for the under / over voltage protective features. For medium voltage applications the controller has internal capabilities set of m ultipliers that correspond to the line voltage dividers. 17 Starting Mode Allows the user to select the t ype of start provided with controller configuration. 18 Ramp Time Allows the user to program the time (0…30 sec) that the controller performs the starting maneuver. The starting maneuver will automatically transition to bypass and full voltage if the controller senses that the motor has reached full speed prior to the ramp time completion. 19 Initial Torque When using the soft start mode, this parameter allows the user to adjust t he initial torque level applied to the motor at the beginning of the start maneuver. 20 Cur Limit Start When using the current limit starting mode, this parameter allows the user to adjust the current level applied to the motor during the start maneuver. 21 Reserved

Upload: sergio-suarez

Post on 02-Jun-2018

219 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SMC Flex Parameters1R

8/10/2019 SMC Flex Parameters1R

http://slidepdf.com/reader/full/smc-flex-parameters1r 1/7

9/18/08 – Firmware Version 4.002 or later

SMC Flex – Complete Parameter List

Programming some of these parameters may require advanced knowledge of the application for properoperation. For additional assistance or explanation with regards to these parameters, please contact theIndustrial Control Technical Support group at: [email protected] or Phone number 440-646-5800

Parameter#

Description

Parameter Numbers and descriptions are valid for SMC-Flex firmware 4.002 or later.

1 Volts Phase A-BProvides the three phase-to-phase supply voltage measurements at all times, including bypass operation. 

2 Volts Phase B-CProvides the three phase-to-phase supply voltage measurements at all times, including bypass operation. 

3 Volts Phase C-AProvides the three phase-to-phase supply voltage measurements at all times, including bypass operation. 

4 Current Phase AProvides the three phase motor current measurement. This measurement is always line current regardless of themotor connection (Wye or Delta).

5 Current Phase BProvides the three phase motor current measurement. This measurement is always line current regardless of the

motor connection (Wye or Delta). 6 Current Phase C

Provides the three phase motor current measurement. This measurement is always line current regardless of themotor connection (Wye or Delta). 

7 Watt MeterProvides the power usage of the connected motor. This value is calculated from the voltage, current and power factormeasurements.

8 Kilowatt HoursProvides the power usage over time of the connected motor.

9 Elapsed TimeIndicates the total time of motor operation in hours. The accumulated time is updated continuously during running.

10 Meter ResetProvides the user the capability to reset the value stored in the elapsed time (9) and k ilowatt hours (8) meters to zero.

11 Power FactorProvides the operational displacement power factor measurement of the connected motor.

12 Mtr Therm UsageProvides the theoretical model of motor heating as a percentage value. At 100% MTU, the controller will fault onoverload. This model is based on the motor thermal overload calculation.

13 Motor SpeedIndicates the operating percentage of motor base speed when linear ramp is selected and an external tachometer isused.

14 SMC OptionThis a “read-only” parameter that identifies to the user the type of control module installed.

15 Motor ConnectionThis parameter allows the user the ability to select the power wiring configuration of the attached motor (WYE orDELTA). A fault controlled means of disconnecting the line should always be use in the DELTA mode.

16 Line VoltageThis parameter sets the base voltage for the under / over voltage protective features. For medium voltage applicationsthe controller has internal capabilities set of multipliers that correspond to the line voltage dividers.

17 Starting ModeAllows the user to select the type of start provided with controller configuration.

18 Ramp TimeAllows the user to program the time (0…30 sec) that the controller performs the starting maneuver. The starting

maneuver will automatically transition to bypass and full voltage if the controller senses that the motor has reached fullspeed prior to the ramp time completion.

19 Initial TorqueWhen using the soft start mode, this parameter allows the user to adjust the initial torque level applied to the motor atthe beginning of the start maneuver.

20 Cur Limit StartWhen using the current limit starting mode, this parameter allows the user to adjust the current level applied to themotor during the start maneuver. 

21 Reserved

Page 2: SMC Flex Parameters1R

8/10/2019 SMC Flex Parameters1R

http://slidepdf.com/reader/full/smc-flex-parameters1r 2/7

9/18/08 – Firmware Version 4.002 or later

22 Kickstart TimeWhen programmed with a non-zero value, this parameter provides a torque pulse for the programmed time period atthe beginning of the starting maneuver.

23 Kickstart LevelWhen the Kickstart Time is programmed, this parameter provides the user with the ability to set the level of the torquepulse applied to the motor (approx. 0 to 90%). 

24 Option Input 2 

Provides the user with the ability to define the function of control Input #2.25 Starting Mode 2

When the dual ramp mode is selected, this parameter allows the user to select the type of ramp mode used for thesecond ramp profile. 

26 Ramp Time 2When the dual ramp mode is selected, this parameter allows the user to program the t ime (0…30 sec) that thecontroller performs the starting maneuver for profile #2. 

27 Initial Torque 2When using the soft start mode for profile #2, this parameter allows the user to adjust the initial torque level applied tothe motor at the beginning of the start maneuver. 

28 Cur Limit Level 2When using the current limit starting mode for profile #2, this parameter allows the user to adjust the current levelapplied to the motor during the start maneuver. 

29 Reserved30 Kickstart Time 2

This parameter provides a torque pulse for the programmed time period at the beginning of the starting maneuver for

ramp profile #2. 31 Kickstart Level2

This parameter provides the user with the ability to set the level of the torque pulse applied to the motor (approx. 0 to90%) for ramp profile #2 

32 Stop ModeAllows the user to select the type of stop provided with the installed controller.

33 Stop TimeAllows the user to select the length of stopping time when a stopping mode is selected.

34 Pump Pedestal – (Only available with Pump Control option)Allows the ability to manually adjust the pump algorithm slightly for different applications. The purpose of thisparameter is to allow the pump stop algorithm to be more aggressive earlier in the ramp. If experiencing overload tripsduring stopping, either reduce the stopping time or try increasing this by units of 5. Try not to exceed a value of 40.

35 Braking CurrentWhen the Smart Motor Braking option is installed, this parameter allows the user the ability to adjust the brakingcurrent level applied to the motor. Smart Motor Braking and Accu-Stop has the capability to apply braking current to themotor from the “at speed” condition. With Smart Motor Braking, the braking maneuver continues until the motor comesto rest, at which point the controller automatically ceases braking action. Note that high braking currents can introduceexcessive vibration to the motor couplings and/or gearing and additional heating in the motor.

36 Braking Time – (Only available with SMB option)This parameter provides the ability to over-ride the SMB function (zero-speed detection) and set an exact time in whichthe braking current is applied to the motor. This can be used for applications where detecting zero speed is difficult orwhen the purpose is to reduce the number of overload trips associated with driving the motor to a complete stop.

Setting this to a specific value will turn off the braking at a set time, each time a stopping maneuver is performed. Anideal setting can be accomplished through trial and error and should always allow for some small coast time. Settingthis value to long will cause braking current to be applied to a stopped motor and likely result in overload trips.

37 Load Type – (Only available with SMB option)Allows the user the ability to modify the braking profile to match a particular load type. This parameter is designed to

only be used with the SMB algorithm and not with timed brake. For the majority of applications the standard profile willwork sufficiently. Adjusting this parameter should really only be used when some type of problem during braking isbeing encountered.

38 High Eff Brake – (Only available with SMB option)This parameter is used to extend the SMB braking time by a percentage of the typical stopping time. The need toadjust this parameter can occur when braking is applied to high efficiency motors and relates to the counter EMFproduced by these motors. This setting should never really exceed 50%. Nuisance overload faults will likely occur isset incorrectly.

Page 3: SMC Flex Parameters1R

8/10/2019 SMC Flex Parameters1R

http://slidepdf.com/reader/full/smc-flex-parameters1r 3/7

9/18/08 – Firmware Version 4.002 or later

39 Slow Speed SelWhen this option is used, this parameter provides the user the ability to select between the “Low” and “High” settingsfor both the Preset Slow Speed and Accu-Stop control options.

40 Slow Speed DirProvides the user the ability to program the motor’s direction of rotation. Note that with the Preset Slow Speed option,the controller has the capability to operate the motor in the reverse direction during slow speed operation without theuse of a reversing contactor. 

41 Slow Accel Cur

Provides the user the ability to program the acceleration current to slow speed operation for both the Preset SlowSpeed and Accu-Stop control options. This setting is typically load dependent.

42 Slow Running CurProvides the user the ability to program the operating current of slow speed operation for both the Preset Slow Speedand Accu-Stop control options. This setting is typically load dependent.

43 Stopping CurrentProvides adjustment capability for the braking intensity from slow speed operation to the “stopped” condition for theAccu-Stop control option.

44 Overload ClassAllows the user to select the t ime-to-trip for the built-in overload. This selection is based on the type of motor beingused and the application it is being applied too.

45 Service FactorThis motor nameplate value is used to determine the ultimate overload trip current.

46 Motor FLCSets the base current for use with all the current based protection features (jam, over / under load, motor overload ).The motor nameplate FLA is to be used regardless of the configuration WYE or DELTA.

47 Overload ResetAllows the user to select between an auto and manual reset mode for all Overload faults.

48 OL Shunt Time – This parameter prevents the overload from accumulating or incrementing the Motor Thermal Usage(%MTU) during the programmed “shunt” time. This function is allowable under some electrical codes for loads whichhave long acceleration times (i.e. High inertia). As a general rule of thumb, this time should never exceed theprogrammed start time. Setting this parameter longer than necessary can result in motor overheating that is not beingaccounted for in the thermal model.

49 OL Trip Enable/Disable – This parameter disables the overload from tripping during slow speed, pump stopping, andbraking maneuvers. Motor Thermal Usage (%MTU) continues to increment during these maneuvers. Setting thisparameter to disable can result in motor overheating or potential damage.

50 Overload A LvlAllows the user to set an overload level (% of motor thermal usage) that will cause an alarm when the level exceedsthe setting.

51 Underload F LvlAllows the user to set a current (% of line FLC) that will cause a fault when the motor current falls below this value. Azero value is the “off” setting.

52 Underload F DlyAllows the user the ability to prevent some nuisance faults by entering a delay period that provides a window that themotor current condition must persist within for the controller to fault.

53 Underload A LvlAllows the user to set a current (% of line FLC) that will cause an Alarm when the motor current falls below this value.A zero value is the “off” setting.  

54 Underload A DlyAllows the user the ability to prevent some nuisance Alarm conditions by entering a delay period that provides awindow that the motor current condition must persist within for the controller to Alarm. 

55 Undervolt F LvlAllows the user to set a voltage (% of line Voltage) that will cause a fault when the voltage falls below this value. A zerovalue is the “off” setting. 

56 Undervolt F Dly

Allows the user the ability to prevent some nuisance faults by entering a delay period that provides a window that thevoltage condition must persist within for the controller to fault. 

57 Undervolt A LvlAllows the user to set a voltage (% of line Voltage) that will cause an Alarm when the voltage falls below this value. Azero value is the “off” setting. 

58 Undervolt A DlyAllows the user the ability to prevent some nuisance Alarms by entering a delay period that provides a window that thevoltage condition must persist within for the controller to Alarm. 

59 Overvolt F LvlAllows the user to set a voltage (% of line Voltage) that will cause a fault when the voltage falls above this value. Azero value is the “off” setting. 

Page 4: SMC Flex Parameters1R

8/10/2019 SMC Flex Parameters1R

http://slidepdf.com/reader/full/smc-flex-parameters1r 4/7

9/18/08 – Firmware Version 4.002 or later

60 Overvolt F DlyAllows the user the ability to prevent some nuisance faults by entering a delay period that provides a window that thevoltage condition must persist within for the controller to fault. 

61 Overvolt A LvlAllows the user to set a voltage (% of line Voltage) that will cause an Alarm when the voltage falls above this value. Azero value is the “off” setting. 

62 Overvolt A DlyAllows the user the ability to prevent some nuisance Alarms by entering a delay period that provides a window that the

voltage condition must persist within for the controller to Alarm. 63 Unbalance F Lvl

Allows the user to set a percentage of line to line Voltages that will cause a fault when the voltage falls above thisvalue. A zero value is the “off” setting. 

64 Unbalance F DlyAllows the user the ability to prevent some nuisance faults by entering a delay period that provides a window that thevoltage unbalance condition must persist within for the controller to fault. 

65 Unbalance A LvlAllows the user to set a percentage of line to line Voltages that will cause an Alarm when the voltage falls above thisvalue. A zero value is the “off” setting. 

66 Unbalance A DlyAllows the user the ability to prevent some nuisance Alarms by entering a delay period that provides a window that thevoltage unbalance condition must persist within for the controller to Alarm. 

67 Jam F LvlAllows the user to set an instantaneous over current level (% of line FLC) that will cause a fault. A zero value is the“off” setting. 

68 Jam F DlyAllows the user the ability to prevent some nuisance faults by entering a delay period that provides a window that themotor over current condition must persist within for the controller to fault. 

69 Jam A LvlAllows the user to set an instantaneous over current level (% of line FLC) that will cause an Alarm. A zero value is the“off” setting. 

70 Jam A DlyAllows the user the ability to prevent some nuisance Alarms by entering a delay period that provides a window that themotor over current condition must persist within for the controller to Alarm. 

71 Stall DelayThis feature allows the user to program the amount of time beyond the initial start maneuver for the motor to be atspeed. A setting of zero means that the stall detection feature is disabled.

72 Gnd Flt EnableEnables ground fault protection when used with an external core balanced ground fault sensor.

73 Gnd Flt LevelAllows the user to set a current (core balance current) that will cause a fault when the current is above this value.

74 Gnd Flt DelayAllows the user the ability to prevent some nuisance faults by entering a delay period that provides a window that theground fault condition must persist within for the controller to fault. 

75 Gnd Flt Inh timeAllow the user the ability to disable ground fault protection for a selected t ime when starting.

76 Gnd Flt A EnableEnables a ground fault protection Alarm when used with an external core balanced ground fault sensor. 

77 Gnd Flt A LevelAllows the user to set a current (core balance current) that will cause an Alarm when the current is above this value. 

78 Gnd Flt A DelayAllows the user the ability to prevent some nuisance Alarms by entering a delay period that provides a window that theground fault condition must persist within for the controller to Alarm. 

79 PTC EnableEnables PTC based over-temperature protection when used with external PTC sensors. 

80 Phase ReversalAllows the user to prevent starting if the incoming line phase sequence is not correct. The incoming power lines areexpected to be in an ABC sequence. The controller will fault if power lines are out of the ABC sequence.

81 Start Per HourLimits the number of starts that can occur in a one-hour period. This feature includes a "sliding window" for the one-hour time period. 

82 Restart AttemptsAllows the user to enable the SMC-Flex to auto-restart for up-to 5 attempts, other than an SCR overtemp or motoroverload fault. The start signal must remain active for a restart to occur. 

83 Restart DelayProvides a delay time between restart attempts to allow for the condition to be removed.

84 Line Fault – This parameter gives the user the ability to selectively disable specific fault codes such as F1, F2, F3 andF41, F42, F43. These faults are used to detect problems with incoming power and the detection of appropriate zero

Page 5: SMC Flex Parameters1R

8/10/2019 SMC Flex Parameters1R

http://slidepdf.com/reader/full/smc-flex-parameters1r 5/7

9/18/08 – Firmware Version 4.002 or later

crosses (i.e. F1) or the firing of the SCR’s based on the current and voltage characteristics associated with the SCRturning off (i.e. F41). These faults can only occur during starting or stopping and are usually related to the incomingpower condition.

85 Emergency Run – This parameter defeats all running faults and is only effective in the “run” mode. It will not overridefaults prior to starting (i.e. shorted SCR). This parameter is reset to “off” when control power is recycled.

86 Current Loss – This parameter allows the user to override a current loss fault. This is indicative of the typical failuremode of a damaged CT.

87 Logic MaskAllows the user to enable or disable control from various serial interface ports (DPI) with a "0" setting. I f a port is set to“1”, the port will be allowed to control the SMC and will product a comm. fault if disconnected. 

88 Data In A116 bit Datalink

89 Data In A216 bit Datalink 

90 Data In B116 bit Datalink 

91 Data In B216 bit Datalink 

92 Data In C116 bit Datalink 

93 Data In C216 bit Datalink 

94 Data In D116 bit Datalink 

95 Data In D216 bit Datalink 

96 Data Out A116 bit Datalink 

97 Data Out A216 bit Datalink 

98 Data Out B116 bit Datalink

99 Data Out B216 bit Datalink 

100 Data Out C116 bit Datalink 

101 Data Out C216 bit Datalink 

102 Data Out D116 bit Datalink 

103 Data Out D216 bit Datalink 

104 Motor IDAllows the user the ability to assign a specific identification number to a motor and controller combination. This can beuseful for network applications where you may need to locate a specific motor/controller based on a network address.

105 CT RatioSets the proper current ratio when an external current transformer is used for Medium Voltage applications. 

106 MV RatioSets the proper feedback scaling when used for Medium Voltage applications. 

107 Aux1 ConfigAllows the user the ability to configure each Auxiliary relay for a specific operation

108 Aux3 Config

Allows the user the ability to configure each Auxiliary relay for a specific operation 109 Aux4 Config

Allows the user the ability to configure each Auxiliary relay for a specific operation 110 Aux2 Config

Allows the user the ability to configure each Auxiliary relay for a specific operation 111 Language

Allows the user to change the text display to one of the available options.

112 Timed Start - This parameter can be used to force the starting profile to complete its entire time period and ignore anearly up-to-speed detection. The default is set to “Disabled”, so that the SMC can determine when the motor is atspeed.

Page 6: SMC Flex Parameters1R

8/10/2019 SMC Flex Parameters1R

http://slidepdf.com/reader/full/smc-flex-parameters1r 6/7

9/18/08 – Firmware Version 4.002 or later

113 I Shut Off LevelThis parameter adjusts the level of current at which the SMC determines that the SCR has turned off. Since thisparameter has the potential to modify the SCR control scheme, it is important that adjustments be made with the helpof Technical Support.

114 UTS LevelThe SMC has the ability to automatically determine if the motor is up to speed. If there is a problem with detecting theup-to-speed condition, this parameter can be modified to compensate. Rule of thumb is this number should beincreased on high efficiency motors experiencing problems. If the SMC is detecting the up-to-speed condition too late(or not at all) this number should be decreased on very low efficiency motors. Note: Be careful when adjusting thislevel. Improper adjustment can cause the SMC to start at full voltage

115 Parameter MgmtAllows the user to load factory default values for all parameters. 

116 Backspin Timer - (Only available with the Pump Control option)Ensures that a specific amount of time passes between a stop and start sequence. Programmable from 0 to 999seconds.

117 VShut Off Level – This parameter provides the user with the ability to manually adjust the level for the controller’svoltage shut off detection. Since this parameter has the potential to modify the SCR control scheme, it is important thatadjustments be made with the help of Technical Support. It is important that you do not disable both parameter 113and this one at the same time, otherwise SCR firing instability can occur.

118 OL Reset Level – Sets the level at which the motor overload is allowed to be reset. Once the TCU% has droppedbelow the program level, the device can be reset manually or will auto reset if programmed for auto-reset operation.

119 Ambient Temp – Provides the ability to compensate for a lower or higher ambient temperature condition. The ambienttemperature programmed should be representative of the actual nominal temperature (or worst case condition) sinceimproper programming can result in nuisance tripping or SCR damage due to true SCR overheating.

120 Notch Position – This parameter allows for the starting control algorithm to be manually modified. It is recommendedthat you do not make changes to this parameter without specifically talking with Technical Support.

121 Notch Maximum – (Used only with Pump Control)This parameter allows for the pump stopping control algorithm to be manually modified. It is recommended that you donot make changes to this parameter without specifically talking with Technical Support.

122 Start Delay – An internal on-delay timer. Ensures that a subsequent start can not be initiated for a preset amount oftime

123 By-pass Delay - For applications that routinely see fast spikes of current or overload conditions (more than 125% ofthe SMC’s frame rating) this parameter can be used to reduce the cycling between SCR and by-pass. This time delayparameter will allow the SMC to stay under SCR control for the duration of t ime programmed.

124 Fault 1Fault buffer #1 will allows display the current fault. A value of 0 indicates that there is no current fault.

125 Fault 2This represents fault history of the device with fault #1 being the current fault and fault #5 being the oldest fault kept inmemory.

126 Fault 3This represents fault history of the device with fault #1 being the current fault and fault #5 being the oldest fault kept inmemory.

127 Fault 4This represents fault history of the device with fault #1 being the current fault and fault #5 being the oldest fault kept inmemory.

128 Fault 5This represents fault history of the device with fault #1 being the current fault and fault #5 being the oldest fault kept inmemory.

129 Ramp Time E – This parameter provides the user with the ability to extend the ramp time beyond the initial range of 0-30 seconds. To use this parameter, parameter 18 must be set to 0. 

Page 7: SMC Flex Parameters1R

8/10/2019 SMC Flex Parameters1R

http://slidepdf.com/reader/full/smc-flex-parameters1r 7/7

9/18/08 – Firmware Version 4.002 or later

130 Ramp Time 2E – Allows for the second ramp time to also be extended. To use this parameter, parameter 26 must beset to 0.

131 Stop Time E– Allows for the stop time be extended beyond the limit of 120 seconds. Parameter 33 must be set to 0 forthis parameter to be active.

132 Option Input 1

Provides the user with the ability to define the function of control Input #1. 

133 Stop InputProvides the user with the ability to define the function of the stop input. 

134 Elapsed Time 2 – This is an additional Elapsed Time Meter that cannot be reset by the user. It increments exactly asthe Elapsed Time but cannot be reset.