Smoke ventilation in common areas of single stair residential
buildings
Some on-going issues and analysis Stewart Miles
International Fire Consultants
The study and results reported are part on-going, personal academic work, and do not necessarily represent the views of any organisation
1
![Page 2: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/2.jpg)
Smoke control in common areas
• Compartmentation is most important element
• Suppression may be significant
• Ventilation generally also required• Can assist means of escape
• Can assist fire service operations
2
![Page 3: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/3.jpg)
Smoke ventilation in single stair buildings
• To help protect stair enclosure• Limit smoke ingress before fire service arrival and during firefighting
• Where there are ‘extended’ corridor travel distances • Purge smoke that enters corridor prior to fire service arrival
• Reduce severity of conditions in corridor during firefighting
3
![Page 4: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/4.jpg)
Current ventilation practice
• Natural ventilation from corridor; or
• Mechanical extract ventilation from corridor• Sometimes augmented with mechanical supply too
• Or sometimes open vents for inlet air
• Open vent at top of stair enclosure (with either of above)
• Air supply / pressurisation in stair enclosure not common
4
![Page 5: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/5.jpg)
Some concerns
• Fire sizes considered are generally restricted to fuel-bed limited condition• i.e. contained fuel area and associated heat release rate
• But, can post-flashover fires actually be more severe?• (and take smoke ventilation system beyond designed capability?)
• Can too much depressurisation in the corridor lead to hazards that are not generally considered?• e.g. smoke drawn under door threshold
• Propensity for ‘backdraught’ conditions during firefighting?
5
![Page 6: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/6.jpg)
Building geometry modelled
6
![Page 7: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/7.jpg)
Apartment and common corridor
7
![Page 8: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/8.jpg)
Smoke ventilation methods analysed
• External wall AOV in corridor• (plus top of stair AOV)
8
![Page 9: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/9.jpg)
Smoke ventilation methods analysed
• Natural smoke shaft to corridor• (plus top of stair AOV)
9
![Page 10: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/10.jpg)
Smoke ventilation methods analysed
• Mechanical extract from corridor• (plus top of stair AOV)
10
![Page 11: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/11.jpg)
Smoke ventilation methods analysed
• Mechanical ‘push/pull’ in corridor• supply & extract in corridor
• (plus top of stair AOV)
11
![Page 12: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/12.jpg)
Smoke ventilation methods analysed
• Mechanical supply to stair• Fresh air into stair
• Pressure-relief damper
• (top of stair AOV omitted)
12
![Page 13: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/13.jpg)
Smoke ventilation methods analysed
• Mechanical supply to stair, plus either:
• External wall AOV in corridor, or
• Mechanical ‘push/pull’ in corridor
13
![Page 14: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/14.jpg)
Post-flashover fire scenario
• Steady-state condition
• Fire distributed across whole floor
• Assume:• Hot gas layer at 800°C & emissivity ~1
• Fuel heat of gasification = 4 000 kJ kg-1
• (ranges from 1 000 to 5000 kJ kg-1 for most fuels)
• Heat of combustion = 20 000 kJ kg-1
• Then• Energy (heat) release rate associated with fuel pyrolysis = 375 kW m-2
• (would be higher if lower heat of gasification adopted)
14
![Page 15: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/15.jpg)
Post-flashover fire scenario
• Fire spread across entire floor area in room of origin• 24m2 → 9 MW heat release
• (assuming all fuel combusts)
• Window/vent 3m by 1.4m• From empirical correlation ~7.5MW
heat release rate can be supported within room• (excess fuel can combust in flames
outside window)
15
![Page 16: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/16.jpg)
Illustration of fire from CFD model
16
![Page 17: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/17.jpg)
Illustration of fire from CFD model
17
![Page 18: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/18.jpg)
Comparison with a real fire
• Flame and smoke dynamics similar to the CFD model
18
![Page 19: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/19.jpg)
Illustration of fire from CFD model – apartment door open
19
![Page 20: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/20.jpg)
Modelling using Fire Dynamics Simulator
• 10cm mesh throughout
• Eddy dissipation combustion• Heat combustion 20 000 kJ kg-1
• 10% soot yield
• ‘Finite volume’ ray-tracing radiation model• 100 rays
• Grey gas absorption sub-model
• 0.35 radiative fraction (from combustion process)
• HVAC sub-model• For mechanical supply & extract boundary conditions
20
![Page 21: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/21.jpg)
Simulations (scenarios) at fire service intervention stage
• Steady (post-flashover) fire source
• Ventilation system running
• Apartment door open
• Stair door (on fire floor) open to 20° angle
• Stair bottom (entrance) door open
• Simulations conducted for two to three minutes or until quasi-steady state reached
21
![Page 22: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/22.jpg)
Simulations (scenarios) prior to fire service arrival
• Steady (post-flashover) fire source
• Ventilation system running
• Apartment door closed• 3mm threshold gap modelled using FDS ‘leak vent’ capability
• Stair door (on fire floor) closed • Unless ‘pulled-open’ as part of ventilation operation
• Stair bottom (entrance) door open
• Simulations conducted for two to three minutes or until quasi-steady state reached
22
![Page 23: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/23.jpg)
Smoke transport at firefighting stage
• No corridor ventilation
23
![Page 24: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/24.jpg)
Smoke transport at firefighting stage
• ADB corridor AOV• ~1m2 aerodynamic free area
• (equivalent to 1.5m2 unobstructed rectangular opening)
24
![Page 25: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/25.jpg)
Smoke transport at firefighting stage
• ADB natural smoke shaft
25
![Page 26: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/26.jpg)
Smoke transport at firefighting stage
• Mechanical extract at 2 m3s-1
26
![Page 27: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/27.jpg)
Smoke transport at firefighting stage
• Mechanical extract at 4 m3s-1
27
![Page 28: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/28.jpg)
Smoke transport at firefighting stage
• Mechanical extract at 6 m3s-1
28
![Page 29: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/29.jpg)
Smoke transport at firefighting stage
• Mechanical ‘push/pull’ at 2 m3s-1
29
![Page 30: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/30.jpg)
Smoke transport at firefighting stage
• Stair supply at 2 m3s-1
• No vent in corridor
30
![Page 31: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/31.jpg)
Smoke transport at firefighting stage
• Stair supply at 2 m3s-1
• Wall vent in corridor
31
![Page 32: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/32.jpg)
Smoke transport at firefighting stage
• Stair supply at 4 m3s-1
• No vent in corridor
32
![Page 33: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/33.jpg)
Smoke transport at firefighting stage
• Stair supply at 4 m3s-1
• Wall vent in corridor
33
![Page 34: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/34.jpg)
Smoke transport at firefighting stage
• Mechanical ‘push/pull’ at 2 m3s-1
• Stair supply at 2 m3s-1
34
![Page 35: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/35.jpg)
Smoke transport at firefighting stage
• Mechanical ‘push/pull’ at 2 m3s-1
• Stair supply at 4 m3s-1
35
![Page 36: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/36.jpg)
Smoke transport prior to fire service arrival
• Mechanical ‘push/pull’ at 2 m3s-1
36
![Page 37: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/37.jpg)
Smoke transport prior to fire service arrival
• Low level mechanical extract • Air leakage into corridor
37
![Page 38: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/38.jpg)
Smoke transport prior to fire service arrival
• Mechanical extract at 2 m3s-1
• ‘Reverse-hung’ stair door part-opening at ~10Pa
38
![Page 39: Smoke ventilation in common areas of single ... - FSMF.UK · Smoke ventilation in common areas of single stair residential buildings Some on-going issues and analysis Stewart Miles](https://reader036.vdocument.in/reader036/viewer/2022081517/5e8758c656527e521a018242/html5/thumbnails/39.jpg)
To conclude
• Various issues relating to smoke ventilation in residential buildings warrants further investigation
• Impact of post-flashover apartment fires
• Potential for smoke and fie gases to be drawn into the corridor
• Possible benefit of supplying air mechanically into the stair is being missed
• For ‘extended corridors’ a combination of mechanical corridor smoke clearance (e.g. ‘push/pull’) and mechanical air supply into the stair may prove productive
• Work reported is very much ‘work in progress’ open for discussion