Experion Mx RAE Release R700.1 Software Change Notice 1 Experion Mx RAE R700.1 Software Change Notice Revision Date: April 7, 2017 Document ID: 6510020599

Upload: others

Post on 07-Jul-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Software Change Notice - Honeywell · Assistance Center prior to attempting any software migration from previous releases of this software. Experion Mx RAE Release R700.1 Software

Experion Mx RAE Release R700.1 Software Change Notice 1

Experion Mx RAE R700.1

Software Change Notice

Revision Date: April 7, 2017

Document ID: 6510020599

Page 2: Software Change Notice - Honeywell · Assistance Center prior to attempting any software migration from previous releases of this software. Experion Mx RAE Release R700.1 Software

Experion Mx RAE Release R700.1 Software Change Notice 2

Notices and Trademarks

© Honeywell International Inc. 2017. All Rights Reserved.

While this information is presented in good faith and believed to be accurate, Honeywell disclaims the

implied warranties of merchantability and fitness for a particular purpose and makes no express

warranties except as may be stated in its written agreement with and for its customer.

In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The

information and specifications in this document are subject to change without notice.

Other brand or product names are trademarks of their respective owners.

Honeywell Process Solutions

#151/1, Doraisanipalya,

Bannerghatta Road,

Bangalore, India

+91 80-26588360

www.honeywellprocess.com

Page 3: Software Change Notice - Honeywell · Assistance Center prior to attempting any software migration from previous releases of this software. Experion Mx RAE Release R700.1 Software

Experion Mx RAE Release R700.1 Software Change Notice 3

Symbol Definitions The following table lists those symbols used in this document to denote certain conditions.

Symbol Definition

ATTENTION: Identifies information that requires special consideration.

TIP: Identifies advice or hints for the user, often in terms of performing a task.

REFERENCE -EXTERNAL: Identifies an additional source of information outside of the bookset.

REFERENCE - INTERNAL: Identifies an additional source of information within the bookset.

CAUTION

Indicates a situation which, if not avoided, may result in equipment or work (data) on the system being damaged or lost, or may result in the inability to properly operate the process.

CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. CAUTION symbol on the equipment refers the user to the product manual for additional information. The symbol appears next to required information in the manual.

WARNING: Indicates a potentially hazardous situation, which, if not avoided, could result in serious injury or death. WARNING symbol on the equipment refers the user to the product manual for additional information. The symbol appears next to required information in the manual.

WARNING, Risk of electrical shock: Potential shock hazard where HAZARDOUS LIVE voltages greater than 30 Vrms, 42.4 Vpeak, or 60 VDC may be accessible.

ESD HAZARD: Danger of an electro-static discharge to which equipment may be sensitive. Observe precautions for handling electrostatic sensitive devices.

Protective Earth (PE) terminal: Provided for connection of the protective earth (green or green/yellow) supply system conductor.

Page 4: Software Change Notice - Honeywell · Assistance Center prior to attempting any software migration from previous releases of this software. Experion Mx RAE Release R700.1 Software

Experion Mx RAE Release R700.1 Software Change Notice 4

Symbol Definition

Functional earth terminal: Used for non-safety purposes such as noise immunity improvement. NOTE: This connection shall be bonded to Protective Earth at the source of supply in accordance with national local electrical code requirements.

Earth Ground: Functional earth connection. NOTE: This connection shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements.

Chassis Ground: Identifies a connection to the chassis or frame of the equipment shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements.

Page 5: Software Change Notice - Honeywell · Assistance Center prior to attempting any software migration from previous releases of this software. Experion Mx RAE Release R700.1 Software

Experion Mx RAE Release R700.1 Software Change Notice 5

Contents 1 Introduction ........................................................................................................................ 6

1.1 About Experion MX ........................................................................................................................ 6 1.2 About this Document ..................................................................................................................... 6 1.3 Limitations ...................................................................................................................................... 6 1.4 Technical Assistance ..................................................................................................................... 6

2 Contents of Release ........................................................................................................... 7

3 Getting Started ................................................................................................................... 8

4 Release Overview............................................................................................................... 9 4.1 New Features ................................................................................................................................ 9 4.2 Enhancements ............................................................................................................................... 9 4.3 Obsolete Features ......................................................................................................................... 9

5 Software/Hardware/Firmware Compatibility ................................................................... 11 5.1 Supported Platform hardware for Experion MX R700.1 Release ................................................ 11 5.2 Supported Switches ..................................................................................................................... 11 5.3 Antivirus Software ........................................................................................................................ 12 5.4 Microsoft Office compatibility ....................................................................................................... 12 5.5 Microsoft Security Updates .......................................................................................................... 12

6 Documentation Updates/Additional Information ........................................................... 13

7 Problems Resolved .......................................................................................................... 14

8 Known Issues ................................................................................................................... 14

9 Special Considerations.................................................................................................... 22

10 Third-Party Software Components ................................................................................. 22 10.1 Embedded Software Components ............................................................................................... 22 10.2 External Certified Software Components .................................................................................... 23

Page 6: Software Change Notice - Honeywell · Assistance Center prior to attempting any software migration from previous releases of this software. Experion Mx RAE Release R700.1 Software

Experion Mx RAE Release R700.1 Software Change Notice 6

1 Introduction

1.1 About Experion MX Experion MX™ is Honeywell’s Quality Control System (QCS) for the Pulp, Paper and CWS industry. It provides the industry’s most comprehensive suite of online sensors, combined with fast scanner and data processing speeds, to deliver precise, and high-resolution measurements.

1.2 About this Document This document describes the installation procedure for the Experion MX R700.1 Release. You should read this entire document before proceeding with the installation of this maintenance release. This document is intended for use by manufacturing, project, software and process engineers. This document, assumes that the reader is familiar with the RAE software and Honeywell QCS.

1.2.1 Applicability of Experion MX R700.1 Release This SCN applies to all Experion MX R700.1 Servers and Operator stations, including AllianceViews, and Desktop Servers. This document provides download and installation instructions for the Experion MX R700.1 release, and includes a list of problems resolved and the list of enhancements included in this release.

1.3 Limitations NA.

1.4 Technical Assistance For more information, contact the Global Technical Assistance Center (GTAC) either by telephone at 800-822-7673 (+1-602-293-1882) or by email at [email protected].

Page 7: Software Change Notice - Honeywell · Assistance Center prior to attempting any software migration from previous releases of this software. Experion Mx RAE Release R700.1 Software

Experion Mx RAE Release R700.1 Software Change Notice 7

2 Contents of Release

Table 1 Experion Mx RAE

Product Model Number

EXPERION R500 S/W FOR EXPERION MX R700 QCS-EXPMX-700

LABVIEW 2015 SP1 SOFTWARE 6543210129

The models listed above include the following software and documentation components:

Table 2 EXPERION R500 S/W FOR EXPERION MX R70X

Component Part Number

EXPERION PKS SYSTEM INITIALIZATION DVD 51155966

EXPERION PKS SYSTEM INITIALIZATION UPDATES DVD 51155967

EXPERION PKS INSTALLATION DVD (1) 51155890

EXPERION PKS INSTALLATION DVD (2) 51155891

EXPERION PKS UPDATES DVD 51156133

MICROSOFT SQL SERVER 2014 SP2 DVD 51155894

EXPERION SUPPORT AND MAINTENANCE (ESM) DVD (1) 51155286

EXPERION PKS R500.1 PDF COLLECTION DVD 51155348 Table 3 MEDIA AND LICENSE EXPERION MX R700.1

Component Part Number

MEDIA EXPERION MX R700 EPKS R500 INTERFACE COMP 6543210126

MEDIA EXPERION MX R700 BASE COMPONENTS 6543210127

MEDIA EXPERION MX R700 SUPPORT DVD 6543210134

Table 4 LABVIEW 2015 SP1 SOFTWARE

Component Part Number

S/W MEDIA FOR LABVIEW 2015 SP1 6543210129

LABVIEW 2015 SP1 DEVICE DRIVER REFERENCE 6543210130

S/W MEDIA FOR LABVIEW 2015 SP1 PATCH 5 6543210135

Page 8: Software Change Notice - Honeywell · Assistance Center prior to attempting any software migration from previous releases of this software. Experion Mx RAE Release R700.1 Software

Experion Mx RAE Release R700.1 Software Change Notice 8

3 Getting Started This release includes a new version of the RAE Release and Installation Notes and the RAE Configuration and Maintenance Guide. Refer to these documents before installing this release of Experion MX. It is strongly recommended that the customers contact the Honeywell Technical Assistance Center prior to attempting any software migration from previous releases of this software.

Page 9: Software Change Notice - Honeywell · Assistance Center prior to attempting any software migration from previous releases of this software. Experion Mx RAE Release R700.1 Software

Experion Mx RAE Release R700.1 Software Change Notice 9

4 Release Overview This release of the Experion MX platform software (RAE R700.1 for EPKS R500.1) adds several new features which were not available in the earlier releases.

4.1 New Features This Experion MX R700.1 release enables the following new features:

• Hybrid Display development Support (HMI Based) The Experion MX HMIWeb controls can be used to build specific Experion MX displays as well as to build hybrid displays i.e. displays containing Experion MX HMIWeb controls along with Experion HMI controls. This feature allows building of operator displays for Experion MX in the same way custom displays are built for Experion.

• Web based (Zero Install) display support

QCS web displays are zero install operator displays that can be viewed on a browser. The displays currently support System templates that are based on Zipline CWS template 3001 only. Future releases will provide support for other CWS templates.

For Security Guidelines, refer to the QCS Security Guidelines section in Real-Time Application Environment(RAE) R700.1 for Experion PKS R500.1 Release and Installation Notes, Document # 6510020594.

4.2 Enhancements • Reduced Installation and Setup time

o Through Experion ESIS feature one click installation of Operating System and Experion (No human intervention required)

• Web Reports o Dependency on Adobe Distiller is removed for web reports package

Third party tool PS to PDF replaces Adobe Distiller • DCT and Special Finder Tool integration with R700

o QCS DCT for collecting all the diagnostic logs/files o QCS Special Finder Tool for monitoring QCS files modified post

installation of R700 Auto-baseline creation

• Scanner diagnostics updates for Zipline Scanner

4.3 Obsolete Features • RAE Point server • Quality Server • OptoLink for NI FieldPoint

Page 10: Software Change Notice - Honeywell · Assistance Center prior to attempting any software migration from previous releases of this software. Experion Mx RAE Release R700.1 Software

Experion Mx RAE Release R700.1 Software Change Notice 10

• SRTP Link • S10 and R10L Wyse Thin Clients

Page 11: Software Change Notice - Honeywell · Assistance Center prior to attempting any software migration from previous releases of this software. Experion Mx RAE Release R700.1 Software

Experion Mx RAE Release R700.1 Software Change Notice 11

5 Software/Hardware/Firmware Compatibility This section provides software, hardware and firmware compatibility information for this release. You should only install software which has been qualified for use on your version of RAE. For the most current software compatibility information, see the QCS Compatibility Matrix which is available from the HoneywellProcess.com website or use the following hyperlink: http://www.honeywellprocess.com/library/support/Documents/Experion/qcs-compatibility-matrix.zip. For more information, see Real-Time Application Environment (RAE) R700.1 for Experion PKS R500.1 Release and Installation Notes, Document # 6510020594.

ATTENTION Refer to the Honeywell Process website for detailed information on Honeywell-qualified Third Party Software. The user should be logged into the HoneywellProcess.com site to use the above hyperlink.

5.1 Supported Platform hardware for Experion MX R700.1 Release You should use only the Honeywell qualified specification, variations from the tested configuration may negatively impact and/or performance of the hardware.

5.1.1 Supported Server Platforms The following Server platforms are currently supported with this release:

• DELL PowerEdge R330 Server (24GB RAM) • DELL PowerEdge T330 Server (24GB RAM) • DELL PowerEdge R320 Server (24GB RAM) • DELL PowerEdge T320 Server (24GB RAM) • DELL PowerEdge R730/R430 (64GB RAM) for QCS Virtualization • DELL PowerEdge R720/R320 Server (ESXi Server-64GB RAM) for QCS

Virtualization

5.1.2 Supported Workstation Platforms The following Workstation platforms are supported with this release:

• DELL Precision 5810XL Workstation (16GB RAM) • DELL Precision T3600XL Workstation (16GB RAM)

5.2 Supported Switches

Page 12: Software Change Notice - Honeywell · Assistance Center prior to attempting any software migration from previous releases of this software. Experion Mx RAE Release R700.1 Software

Experion Mx RAE Release R700.1 Software Change Notice 12

The following switches are qualified for Experion MX R700.1: • QCS Only Scenario: CISCO (Catalyst 2960, Catalyst 2960+, and Catalyst 2960x),

HP 2620 Switches • Integrated Scenario: CISCO (Catalyst 2960, Catalyst 2960+, and Catalyst 2960x),

HP 2620 Switches • MxProLine: NetGear FS 108 switches

5.3 Antivirus Software Customers are responsible for providing adequate virus protection or for contracting with Honeywell for an Antivirus protection service program. Antivirus software must be upgraded to the qualified versions.

NOTE: Updates for R700 release in below link will be available by end of April 2017. For more information on the Honeywell qualified version of Antivirus Software and configuration, see the following hyperlink: http://www.honeywellprocess.com/library/support/Documents/Trusted/Experion/anti-virus-software-guidelines.pdf.

5.4 Microsoft Office compatibility For more information on Microsoft Office compatibility with Experion products, see the following hyperlink: http://www.honeywellprocess.com/library/support/Documents/Experion/qcs-compatibility-matrix.zip.

5.5 Microsoft Security Updates Microsoft often issues security updates that are critical to Honeywell’s products. After Microsoft makes a security update available, Honeywell assesses its impact on its products and issues an installation recommendation. Honeywell’s goal is to qualify the applicable updates within seven days of the Microsoft release notification date. Honeywell recommends that you apply the Honeywell qualified security updates that are applicable for your system as soon as practical. For more information on the installing Microsoft Security Updates refer to the Microsoft Security Hot-fixes Qualification matrix on the HoneywellProcess.com website.

NOTE: Updates for R700 release in below link will be available by end of April 2017. You can use the SUIT ISO image to install the latest qualified Microsoft Security updates on all QCS nodes. For more information on the installation of Microsoft Security Updates access the following hyperlink:

Page 13: Software Change Notice - Honeywell · Assistance Center prior to attempting any software migration from previous releases of this software. Experion Mx RAE Release R700.1 Software

Experion Mx RAE Release R700.1 Software Change Notice 13

https://www.honeywellprocess.com/library/support/security-updates/Customer/suit-iso-user-guide.pdf. You can download the latest SUIT ISO from the HoneywellProcess.com website. Click the SUPPORT tab, select See more and then search for (e.g: January 2017 ISO (or use the most recent month and year)), open the Datasheet and click the Download ISO Image. You can download the latest Microsoft-security-hot-fixes-Honeywell-qualification-matrix from the HoneywellProcess.com website. Click the SUPPORT tab, select See more and then search for Microsoft Security Hot fixes. Copy the Microsoft-security-hot-fixes-Honeywell-qualification-matrix and view the HPS recommendations for all recent Microsoft Security Updates (the QCS nodes are on the HQM-Part III sheet).

6 Documentation Updates/Additional Information

Table 5 List of documents Document Part Number

Real-Time Application Environment (RAE) R700.1 for Experion R500.1 - Release and Installation Notes

6510020594

Real-Time Application Environment (RAE) R700.1 for Experion R500.1 - Configuration and Maintenance Guide

6510020593

Experion MX Remote Desktop Services Installation and Configuration Guide 6510020597

Experion MX Computer Cloning User Manual 6510020595

Software Upgrade User Manual 6510020596

Product Manual PDF Collection 6537100023

Experion MX Web Display User Guide 6510020602

Experion MX HMI Web User Guide 6510020601

QCS Specials Finder Tool User Manual 6510020598

QCS Diagnostic Capture Tool 6510020604

PRODUCTION OF QCS ONLY SERVER ON WINDOWS SERVER 2016 (X64) 6510030221

PRODUCTION OF QCS DESKTOP SERVER OR OPERATOR STATION ON WIN10 ENTERPRISE 64 BIT

6510030220

QCS CDA User Manual 6510020603

Page 14: Software Change Notice - Honeywell · Assistance Center prior to attempting any software migration from previous releases of this software. Experion Mx RAE Release R700.1 Software

Experion Mx RAE Release R700.1 Software Change Notice 14

7 Problems Resolved This section provides an overview of the problems resolved in this release.

Table 6 List of issues resolved Sl No.

PAR Description PAR No.

1 EPKS R400 version registry is wrong. During R3XX time it was correct.

Activ00024404

2 Experion MX Scanner down Alarm during Shop mode of FC

Activ00024989

3 Incorrect Distance from edge calculated for Verification packages

Activ00027366

4 Multipoint display does not display correct distances from the edges

Activ00027483

5 Q4000, Optical Caliper Default Signal Delays Activ00029448

6 Installing R800 PMD OPC Data Server in EMx R61x will relocate the PMD Event Log folder

Activ00030159

7 FotoFiber CD-smoothed trend profiles don't exist for new measurements.

Activ00030238

8 Scanner Diagnostics System - System ###, Activities History, Details does not reflect task selection

Activ00030257

9 MssX SS1 Nuclear Alarm Does Not Clear Activ00030318

10 The standardization of RIS -sensor fails during scan Activ00031316

11 Pc rename tool throws exception error popup after first computer restart

Activ00031378

12 PMD ELMO log file size does not get limited when QCS server has remote sessions

Activ00031441

13 Log Head Position, when Job Set Logs the Fault Code

Activ00031631

14 Web report functionality not feasible due to adobe distiller licensing mechanism changes Activ00031730

15 Recipe Maintenance display bottom 5 lines in smaller font Activ00030732

8 Known Issues Based on information and data available, this section describes some currently identified issues related to this release.

Page 15: Software Change Notice - Honeywell · Assistance Center prior to attempting any software migration from previous releases of this software. Experion Mx RAE Release R700.1 Software

Experion Mx RAE Release R700.1 Software Change Notice 15

PAR ID Description Workaround

Activ00029646 When opened Shift and day display for the first time Logged in as Operator in windows, It throws Dot net error telling insufficient security.

None.

Activ00029647 When logged in op station as operator (windows login), When saving the history reels, CSV shows blank page and it works fine with QCSuser login.

None.

Activ00029657 In Multifixed point display, if the variable is frozen and after page refresh event viewer error observed.

None.

Activ00031236 While opening Reel and Shiftday HMI display, station throws error popup

None.

Activ00031468 In Quality summary HMI display, while opening mini profile from measurement hyperlink additional windows popup observed

Press Esc button to Acknowledge the pop up.

Activ00031508 During launch and shutdown RAE, scribe event viewer error observed

None.

Activ00031536 Some of the RAE displays are getting chopped.

None.

Activ00031549 Report print functionality not working for Reel report, shift & day report & Grade report from HMI display.

None.

Activ00031552 Labview display getting shifted in bottom during first time display opening.

Reload the page or navigate to other display and come back.

Activ00031608 In Integrated EPKS QCS server, After FTE network failure recover EPKSCDA link down message observed and icoa not recovered the CDA communication.

None.

Activ00031612 In Integrated EPKS QCS server, After C300 power reboot EPKSCDA link down message observed and icoa not recovered the CDA communication

None.

Activ00031614 In RAE Console, EPKS Server name Environment is not getting updated correctly after RAE Installation.

None.

Activ00031619 During print operation in NT Event viewer display, unhandled exception error observed

None.

Activ00031653 MS Dot Net Framework error message observed on MIS display

None.

Activ00031763 PMD Localization utility crashed and tool is not updated with latest PMD release

None.

Activ00031771 In Integrated EPKS QCS server with PMD DDT OPC server, After FTE network failure recover PMD link down message observed and hcilink executable not recovered the PMD DDT OPC Server communication.

None.

Page 16: Software Change Notice - Honeywell · Assistance Center prior to attempting any software migration from previous releases of this software. Experion Mx RAE Release R700.1 Software

Experion Mx RAE Release R700.1 Software Change Notice 16

PAR ID Description Workaround

Activ00031815 Private byte Memory leak for HSCStationWindow.exe observed when Sensors are disabled

None.

Activ00031826 In operator station and alliance view node, masscompile error observed for AutoPublisherExtension

None.

Activ00031873 In QcsUser, LabVIEW crashes During shutting down the RAE

None.

Activ00031874 In Scanner diagnostic display, if user select any button like new shutdown/edit shutdown or reports and the system throws exception error

None.

Activ00031878 In integrated QCS PMD operator station, under station menu bar print screen, Mini profile and scanner control image is not updating.

None.

Activ00031884 CDA Based HMI, During repeated operation, trend and profile properties window is greyed out and button not visible in HMIweb display builder

None.

Activ00031886 CDA Based HMI, During modification of existing display, failed to create object error popup observed in HMIweb display builder

Refer section 5.1.Troubleshooting in Experion MX HMIWeb User Guide p/n 6510020601 document.

Activ00031887 CDA Based HMI, In HMIweb display builder trend and profile parameters window display call up observed slow

None.

Activ00031891 Remote session of Restricted User not working in AV server and QCS Server with RDS enabled.

None.

Activ00031906 CDA Based HMI, In QCS trend and profile display autoscale check box size too small under scale popup

None.

Activ00031907 CDA Based HMI, In QCS profile display horizontal axis chart lines not properly updating

None.

Activ00031908 CDA Based HMI, In QCS trend and profile display, cursor position functionality not updating properly with respect to user selection.

None.

Activ00031910 CDA Based HMI, In QCS trend display, chart updating out of window with auto scale option.

None.

Page 17: Software Change Notice - Honeywell · Assistance Center prior to attempting any software migration from previous releases of this software. Experion Mx RAE Release R700.1 Software

Experion Mx RAE Release R700.1 Software Change Notice 17

PAR ID Description Workaround

Activ00031913 CDA Based HMI, In QCS trend display chart not updating at starting of the x axis in play mode with 20 min duration.

None.

Activ00031914 CDA Based HMI, In QCS profile display private bytes memory leak observed

None.

Activ00031916 CDA Based HMI, In QCS trend display private bytes memory leak observed

None.

Activ00031917 CDA Based HMI, In QCS profile display, If user hide the variable for 1st,2nd and 3rd then chart grids not formatting properly.

None.

Activ00031922 HTML5 CWS display - Home display crops while switching between tabs

None.

Activ00031935 CDA Based HMI, In QCS trend display If user select the data for more than ten days then station display response is slow and system throws error popup.

None.

Activ00031953 HTML5 CWS - Trend control shows wrong Roll no for selected Roll Data.

None.

Activ00031964 In QCS server, quick builder script failed during RAE interface media installation.

Refer section 17.9 in Real-Time Application Environment (RAE) R700.1 for Experion R500.1 Configuration and Maintenance Guide, P/N 6510020593 document.

Activ00031968 HSCStationWindow.exe process is leaking for ACM display

None.

Activ00031982 CfgBrowser corrupts macro names when reporting errors

None.

Activ00031985 During every RAE launch QCSLoadHMILibraries error seen in event viewer.

None.

Activ00031987 HTML5 CWS- During first time opening HTML Display, Configure button is missing.

Refer section 4.1.Troubleshooting in Experion MX Web Displays User Guide p/n 6510020602 document.

Activ00031990 ZipLine Default Amber-Red Light Wait Time

None.

Activ00031993 HTML5 CWS - Lower Clamp red line is not visible for Actuator chart under Profile control display

None.

Page 18: Software Change Notice - Honeywell · Assistance Center prior to attempting any software migration from previous releases of this software. Experion Mx RAE Release R700.1 Software

Experion Mx RAE Release R700.1 Software Change Notice 18

PAR ID Description Workaround

Activ00031997 After QCS solution pack media installation in Experion server B, MXExperionserverA and B environment variable updating always with Experion B server name irrespective of user input

None.

Activ00031999 Platform - LabVIEW popup flashes momentarily before coming up on the display

None.

Activ00032001 Hitting "Revert to Base" on Navigational Hierarchy pop up will crash Station

None.

Activ00032004 Multi Profile White Display Cursor Functionality not working.

None.

Activ00032009 CDA Based HMI, After station launch, display call up is slow for Experion MX trend and profile control

None.

Activ00032012 HTML5 CWS- Profile control, If profile is freeze, then Horizontal grid lines are added in display for Freeze profile also.

None.

Activ00032017 CDA Based HMI, In Experion MX Trend display chart area not updating with virtual trend configured

None.

Activ00032020 HTML5 CWS- In Trend control, events name are not visible if events are happing nearing time.

None.

Activ00032023 CDA Based HMI, In Experion MX Trend display event info for roll not updating properly and one event for roll ID is missing.

None.

Activ00032024 CDA Based HMI, In Experion MX Trend display, when scanner in offsheet chart is not updating properly with respect to duration.

None.

Activ00032025 CDA Based HMI, In Experion MX Trend display NaN data is replacing to zero in chart area and due to this data inconsistent observed

None.

Activ00032027 HTML5 CWS - Trend Control X-axis time format is not matching with system time format.

None.

Activ00032031 RAE OPC server not working with variable alias configuration and issue observed due to klockwork changes

None.

Page 19: Software Change Notice - Honeywell · Assistance Center prior to attempting any software migration from previous releases of this software. Experion Mx RAE Release R700.1 Software

Experion Mx RAE Release R700.1 Software Change Notice 19

PAR ID Description Workaround

Activ00031704 NI Update Service running on LabVIEW

Refer section 17.6 in Real-Time Application Environment (RAE) R700.1 for Experion R500.1 Configuration and Maintenance Guide, P/N 6510020593 document.

Activ00032048 Experion MX HMI Web control (profile and Trend) not supported with Experion Custom Install Paths scenario (CIP)

None.

Activ00032061 HMX SQL Utility - Backup creates file using current date, but leaves out zeros

None.

Activ00032052 Diagnostic tool(DCT) not collecting logs for New MSS software R202.0, R700 MDCS, Experion MX QCS web and PMDlog folder

None.

Activ00032051 CDA Based HMI, In ExperionMX Trend control, user not able to select HH:MM:SS as 23:59:59 under calendar

None.

Activ00032044 Zipline Diagnostics display R700 None.

Activ00032043 Desktop shortcut icon not updating with domain configuration for operator user

None.

Activ00032039 XMLtoSQL executable not available in R700 and due to this alias.xml to HMXconfiguration upgrade procedure failed

None.

Activ00032038 HTML5 CWS- Trend control forward time selection button should be disabled if system is running in current time

None.

Activ00032037 HTML5 CWS- Profile control Display, Profile shows Blank, if one profile is having no Data

None.

Activ00032022 HTML5 CWS- In High Resolution Profile DisplayMax, Min and setpoint graph functionality not working as per the setting

None.

Activ00032021 CDA Based HMI, In Experion MX Trend display After export the raw data to csv file format,data not available in file

None.

Activ00032019 CDA Based HMI, In Experion MX trend and profile control under scale popup Maximum and Minimum field not accepting negative value from keyboard

None.

Page 20: Software Change Notice - Honeywell · Assistance Center prior to attempting any software migration from previous releases of this software. Experion Mx RAE Release R700.1 Software

Experion Mx RAE Release R700.1 Software Change Notice 20

PAR ID Description Workaround

Activ00032005 HTML5 CWS- Trend control RAW Popup shows blank Data some times in Clients

None.

Activ00031978 HTML CWS - Vertical cursor Tool tip is not matching for Top & Bottom graph for Profile Control display

None.

Activ00031976 HTML5 CWS- In Trend control from calendar is selected for old history and then user tries to select to calendar time it hangs Display for sometime

None.

Activ00031550 Event viewer process error is observed during RAE launch for AutoPublish Setup Changes.vi

None.

Activ00031954 HTML5 CWS - Trend control selected history time and trend X scale time don't match

None.

Activ00031582 RAEcomponentManager - After unregister RAE components, Experion MX third party dynamic-link library still available under HMX components

None.

Activ00031691 PMDELS process memory leak observed during 24 days of system run without MDCS & CDMV controls installed

None.

Activ00031926 HTML5 CWS display - Junk Characters observed on HTML display

None.

Activ00031746 HMI Navigation Bar - Can't identify which display's button is selected

None.

Activ00031766 RTDR.net OpenRtdrOnLocalMachine fails

None.

Activ00031781 Bump Test - Cannot bring up or identify previously saved bumps

None.

Activ00031797 In Multi Production line system configuration, history trend data not available for remote production line under trend plot and history trend display

None.

Activ00031809 In HMXSQL Utility, write scripts functionality is not working and scripts created only to drop the table

None.

Activ00031811 In configuration Browser, relational DB size help information need to change as per SQL 2014 specification

None.

Page 21: Software Change Notice - Honeywell · Assistance Center prior to attempting any software migration from previous releases of this software. Experion Mx RAE Release R700.1 Software

Experion Mx RAE Release R700.1 Software Change Notice 21

PAR ID Description Workaround

Activ00031813 Navigating from QCS HMI to LabVIEW display found No Free Window available message on the station

Close the station and relaunch the station.

Activ00031895 Reel display shows Color code loading as status after recipe loaded and also script error seen on display

None.

Activ00031894 Restrict the User operation due to Print Tray Notification popup coming on the bottom right hand side of the station

None.

Activ00031883 CDA Based HMI, Trend and profile properties functionality not working in HMI display builder

None.

Activ00031858 Invalid license warning popup observed within grace period and system not able to use with temporary license

Install original RAE license.

Activ00031869 In Configuration browser, Quality server information need to remove from configuration Browser help and under New features R700 release deprecated and new options need to be update

None.

Activ00029656 In Configuration Browser, relationdbs is not created as per initial size and user not able to configure less than 4 MB

None.

Activ00030869 RTDR maximum capacity of 128 MB is too small for large MDMV and CDMV systems

None.

Activ00031470 RAE Palettes not available in labview 2015

None.

Activ00031965 QCS solution pack installation got failed due to screen resolution

Set the screen resolution as 1280*1024.

Activ00032067 In AV server, RAE browser throws warning popup continuously with MXDRMAX size as configured 128 MB and 8 thin client connected

None.

Activ00032066 CDA Based HMI, In Experion MX HMI web control (Trend and Profile) exception error popup observed for property window

Close the HMI builder and reopen it again.

Activ00032016 MSS Discovery VI port usage None.

Page 22: Software Change Notice - Honeywell · Assistance Center prior to attempting any software migration from previous releases of this software. Experion Mx RAE Release R700.1 Software

Experion Mx RAE Release R700.1 Software Change Notice 22

9 Special Considerations Auto-launching of RAE on QCS Admin account During auto-launching of RAE on QCS Admin account, UAC pop up will be prompted, click Yes to continue.

Opening Labview vi Whenever you open Labview vi file directly, system displays an error message. Click OK and proceed.

10 Third-Party Software Components You should only install software which has been qualified for use on your version of RAE. For the most current Hardware/ software compatibility information, consult the QCS Compatibility Matrix which is available from the HoneywellProcess.com website or use the following hyperlink: http://www.honeywellprocess.com/library/support/Documents/Experion/qcs-compatibility-matrix.zip.

10.1 Embedded Software Components These software components may have been included with your software installation.

Page 23: Software Change Notice - Honeywell · Assistance Center prior to attempting any software migration from previous releases of this software. Experion Mx RAE Release R700.1 Software

Experion Mx RAE Release R700.1 Software Change Notice 23

Component Verification Mechanism

(Only one option is listed) Adobe Reader 11 11.0.12 version Internet Explorer 11 IE11 Embedded Microsoft Windows 10 Enterprise 2016 LTSB (x64)

Windows Server 2016 Microsoft SQL Server 2014 Express Edition (64-bit)

SP2

MS Office Product 2013 / 2016 Server Administrator 8.4.0 Microsoft .Net Framework Version 4.6.1 Thin Client Z90 with New Image

For more information on QCS-qualified third-party software component versions refer to the RAE & 3rd party Compatibility tab in the QCS Compatibility Matrix spreadsheet which is hosted in the following link. https://www.honeywellprocess.com/en-US/support/Pages/default.aspx.

10.2 External Certified Software Components These 3rd party software applications are supported on nodes running this software release.

Page 24: Software Change Notice - Honeywell · Assistance Center prior to attempting any software migration from previous releases of this software. Experion Mx RAE Release R700.1 Software

Experion Mx RAE Release R700.1 Software Change Notice 24

For the most current 3rd party software applications supported information, consult the QCS Compatibility Matrix which is available from the HoneywellProcess.com website or use the following link: http://www.honeywellprocess.com/library/support/Documents/Experion/qcs-compatibility-matrix.zip.

CAUTION

Note that the user assumes all responsibility for issues resulting from the installation and operation of any components that have not been tested as compatible by Honeywell. In addition, it is the customer’s responsibility to ensure that the combinations of third party components have sufficient resources (e.g. memory, CPU performance, disk space, display space, etc.).

Component Validated Version with EPKS R500.1

SUIT ISO March 2017

McAfee VSE 8.8 Patch 8 and Hotfix

Symantec Endpoint Protection Version 14

Microsoft Office Components Office 2016

Comtrol Device Master RTS Driver 11.08

Touch Screen (Model Number: Elo E874208)

6.8.0.19

VMware vSphere 5.5

VMware Workstation 12 or later versions

Printer Universal Driver

HP Switch 2620

Cisco Switch 2960X and 2960+

KVM Black Box

8 Ports Switch NetGear

Google Chrome Latest Version (50 and above)

Backup and Restore Acronis 12.0