COMcheck Software Version 4.0.5.1 Envelope Compliance Certificate Project Title: 90.1 (2010) Standard Project Type: New Construction Vertical Glazing / Wall Area: 34% Location: Round Rock, Texas Climate Zone: 2a Construction Site: Owner/Agent: MN Capital Strategies 2204 Lakeshore Drive Suite 450 Birmingham, AL 35209 205-484-2836 Designer/Contractor: Migre Engineers 1200 W SR 434 Suite 301 Longwood, FL 32750 407-636-7999 Project Information Energy Code: Round Rock Apartments - Bldg Type 1 Building Area Floor Area 1-Bldg Type 1 (Multifamily) : Residential 76551 Envelope Assemblies Assembly Cavity R-Value Cont. R-Value Proposed U-Factor Budget U- Factor(a) Gross Area or Perimeter Roof 1: Attic Roof with Wood Joists, [Bldg. Use 1 - Bldg Type 1] 21373 38.0 0.0 0.027 0.027 Exterior Wall 1: Wood-Framed, 16" o.c., [Bldg. Use 1 - Bldg Type 1] 8410 13.0 0.0 0.089 0.089 Window 2: Vinyl/Fiberglass Frame:Operable, Perf. Specs.: Product ID NA, SHGC 0.35, PF 0.30, VT 0.76, [Bldg. Use 1 - Bldg Type 1] (b) 2849 --- --- 0.350 0.750 Exterior Wall 2: Wood-Framed, 16" o.c., [Bldg. Use 1 - Bldg Type 1] 2664 13.0 0.0 0.089 0.089 Window 3: Vinyl/Fiberglass Frame:Operable, Perf. Specs.: Product ID NA, SHGC 0.35, VT 0.76, [Bldg. Use 1 - Bldg Type 1] (b) 276 --- --- 0.350 0.750 Exterior Wall 3: Wood-Framed, 16" o.c., [Bldg. Use 1 - Bldg Type 1] 8410 13.0 0.0 0.089 0.089 Window 4: Vinyl/Fiberglass Frame:Operable, Perf. Specs.: Product ID NA, SHGC 0.35, PF 0.30, VT 0.76, [Bldg. Use 1 - Bldg Type 1] (b) 3816 --- --- 0.350 0.750 Exterior Wall 4: Wood-Framed, 16" o.c., [Bldg. Use 1 - Bldg Type 1] 2664 13.0 0.0 0.089 0.089 Window 5: Vinyl/Fiberglass Frame:Operable, Perf. Specs.: Product ID NA, SHGC 0.35, VT 0.76, [Bldg. Use 1 - Bldg Type 1] (b) 588 --- --- 0.350 0.750 Semi-Exterior Wall 1: Wood-Framed, 16" o.c., [Bldg. Use 1 - Bldg Type 1] 2440 11.0 0.0 0.094 0.089 Semi-Exterior Wall 2: Wood-Framed, 16" o.c., [Bldg. Use 1 - Bldg Type 1] 370 11.0 0.0 0.094 0.089 Semi-Exterior Wall 3: Wood-Framed, 16" o.c., [Bldg. Use 1 - Bldg Type 1] 270 11.0 0.0 0.094 0.089 Floor 1: Slab-On-Grade:Unheated, [Bldg. Use 1 - Bldg Type 1] (c) 670 --- --- 0.730 0.730 (a) Budget U-factors are used for software baseline calculations ONLY, and are not code requirements. (b) Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation. Project Title: Data filename: Round Rock Apartments - Bldg Type 1 X:\16056\CALC\HVAC\Ecalcs\Building 1.cck 11/17/16 Report date: 22 1 of Page

Upload: others

Post on 15-Aug-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Software Version 4.0.5.1 Envelope Compliance Certificate · Birmingham, AL 35209 205-484-2836 Designer/Contractor: Migre Engineers 1200 W SR 434 Suite 301 Longwood, FL 32750 407-636-7999

COMcheck Software Version 4.0.5.1

Envelope Compliance Certificate

Project Title:

90.1 (2010) Standard

Project Type: New ConstructionVertical Glazing / Wall Area: 34%

Location: Round Rock, TexasClimate Zone: 2a

Construction Site: Owner/Agent:MN Capital Strategies2204 Lakeshore DriveSuite 450Birmingham, AL 35209205-484-2836

Designer/Contractor:Migre Engineers1200 W SR 434Suite 301Longwood, FL 32750407-636-7999

Project Information

Energy Code:

Round Rock Apartments - Bldg Type 1

Building Area Floor Area

1-Bldg Type 1 (Multifamily) : Residential 76551

Envelope Assemblies

Assembly CavityR-Value

Cont.R-Value

ProposedU-Factor

Budget U-Factor(a)

Gross Areaor

Perimeter

Roof 1: Attic Roof with Wood Joists, [Bldg. Use 1 - Bldg Type 1] 21373 38.0 0.0 0.027 0.027Exterior Wall 1: Wood-Framed, 16" o.c., [Bldg. Use 1 - Bldg Type 1] 8410 13.0 0.0 0.089 0.089Window 2: Vinyl/Fiberglass Frame:Operable, Perf. Specs.: Product IDNA, SHGC 0.35, PF 0.30, VT 0.76, [Bldg. Use 1 - Bldg Type 1] (b)

2849 --- --- 0.350 0.750

Exterior Wall 2: Wood-Framed, 16" o.c., [Bldg. Use 1 - Bldg Type 1] 2664 13.0 0.0 0.089 0.089Window 3: Vinyl/Fiberglass Frame:Operable, Perf. Specs.: Product IDNA, SHGC 0.35, VT 0.76, [Bldg. Use 1 - Bldg Type 1] (b)

276 --- --- 0.350 0.750

Exterior Wall 3: Wood-Framed, 16" o.c., [Bldg. Use 1 - Bldg Type 1] 8410 13.0 0.0 0.089 0.089Window 4: Vinyl/Fiberglass Frame:Operable, Perf. Specs.: Product IDNA, SHGC 0.35, PF 0.30, VT 0.76, [Bldg. Use 1 - Bldg Type 1] (b)

3816 --- --- 0.350 0.750

Exterior Wall 4: Wood-Framed, 16" o.c., [Bldg. Use 1 - Bldg Type 1] 2664 13.0 0.0 0.089 0.089Window 5: Vinyl/Fiberglass Frame:Operable, Perf. Specs.: Product IDNA, SHGC 0.35, VT 0.76, [Bldg. Use 1 - Bldg Type 1] (b)

588 --- --- 0.350 0.750

Semi-Exterior Wall 1: Wood-Framed, 16" o.c., [Bldg. Use 1 - Bldg Type1]

2440 11.0 0.0 0.094 0.089

Semi-Exterior Wall 2: Wood-Framed, 16" o.c., [Bldg. Use 1 - Bldg Type1]

370 11.0 0.0 0.094 0.089

Semi-Exterior Wall 3: Wood-Framed, 16" o.c., [Bldg. Use 1 - Bldg Type1]

270 11.0 0.0 0.094 0.089

Floor 1: Slab-On-Grade:Unheated, [Bldg. Use 1 - Bldg Type 1] (c) 670 --- --- 0.730 0.730

(a) Budget U-factors are used for software baseline calculations ONLY, and are not code requirements.(b) Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation.

Project Title:Data filename:

Round Rock Apartments - Bldg Type 1X:\16056\CALC\HVAC\Ecalcs\Building 1.cck

11/17/16Report date:221 ofPage

Page 2: Software Version 4.0.5.1 Envelope Compliance Certificate · Birmingham, AL 35209 205-484-2836 Designer/Contractor: Migre Engineers 1200 W SR 434 Suite 301 Longwood, FL 32750 407-636-7999

(c) Slab-On-Grade proposed and budget U-factors shown in table are F-factors.

Envelope Compliance StatementCompliance Statement: The proposed envelope design represented in this document is consistent with the building plans,specifications, and other calculations submitted with this permit application. The proposed envelope systems have beendesigned to meet the 90.1 (2010) Standard requirements in COMcheck Version 4.0.5.1 and to comply with any applicablemandatory requirements listed in the Inspection Checklist.

Greg H. KlebanoffName - Title Signature Date

Envelope PASSES: Design 2% better than code

Project Title:Data filename:

Round Rock Apartments - Bldg Type 1X:\16056\CALC\HVAC\Ecalcs\Building 1.cck

11/17/16Report date:222 ofPage

11-18-16

Page 3: Software Version 4.0.5.1 Envelope Compliance Certificate · Birmingham, AL 35209 205-484-2836 Designer/Contractor: Migre Engineers 1200 W SR 434 Suite 301 Longwood, FL 32750 407-636-7999

COMcheck Software Version 4.0.5.1

Interior Lighting Compliance Certificate

Project Title:

90.1 (2010) Standard

Project Type: New Construction

Construction Site: Owner/Agent:MN Capital Strategies2204 Lakeshore DriveSuite 450Birmingham, AL 35209205-484-2836

Designer/Contractor:Migre Engineers1200 W SR 434Suite 301Longwood, FL 32750407-636-7999

Project Information

Energy Code:

Round Rock Apartments - Bldg Type 1

Allowed Interior Lighting Power

AArea Category

BFloor Area

(ft2)

CAllowed

Watts / ft2

DAllowed Watts

(B X C)

1-Bldg Type 1 (Multifamily) 76551 0.60 45931

45931Total Allowed Watts =

Proposed Interior Lighting PowerE

(C X D)D

FixtureWatt.

AFixture ID : Description / Lamp / Wattage Per Lamp / Ballast

BLamps/Fixture

C# of

Fixtures

1-Bldg Type 1 (Multifamily)Type A: Type A: Corridor Wall Sconce: LED A Lamp 12W: 1 60 12 720Type C: Type C: Corridor Ceiling: LED Panel 19W: 1 120 12 1440Type D: Type D: 4' Striplight: LED Linear 33W: 1 24 31 744

2904Total Proposed Watts =

Interior Lighting Compliance StatementCompliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans,specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have beendesigned to meet the 90.1 (2010) Standard requirements in COMcheck Version 4.0.5.1 and to comply with any applicablemandatory requirements listed in the Inspection Checklist.

Michael L. DodaneName - Title Signature Date

Interior Lighting PASSES: Design 94% better than code

Project Title:Data filename:

Round Rock Apartments - Bldg Type 1X:\16056\CALC\HVAC\Ecalcs\Building 1.cck

11/17/16Report date:223 ofPage

11-18-16

Page 4: Software Version 4.0.5.1 Envelope Compliance Certificate · Birmingham, AL 35209 205-484-2836 Designer/Contractor: Migre Engineers 1200 W SR 434 Suite 301 Longwood, FL 32750 407-636-7999

COMcheck Software Version 4.0.5.1

Exterior Lighting Compliance Certificate

Project Title:

90.1 (2010) Standard

Project Type: New Construction

Construction Site: Owner/Agent:MN Capital Strategies2204 Lakeshore DriveSuite 450Birmingham, AL 35209205-484-2836

Designer/Contractor:Migre Engineers1200 W SR 434Suite 301Longwood, FL 32750407-636-7999

Project Information

Energy Code:

Round Rock Apartments - Bldg Type 1

2 (Residentially zoned area)Exterior Lighting Zone

Allowed Exterior Lighting Power

AArea/Surface Category

BQuantity

CAllowed

Watts / Unit

DTradableWattage

EAllowed Watts

(B X C)

Exterior Entries (Entry canopy) 236 ft2 0.25 Yes 59

Total Tradable Watts (a) =Total Allowed Watts =

Total Allowed Supplemental Watts (b) =

59

59

600

(a) Wattage tradeoffs are only allowed between tradable areas/surfaces.(b) A supplemental allowance equal to 600 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.

Proposed Exterior Lighting PowerE

(C X D)D

FixtureWatt.

AFixture ID : Description / Lamp / Wattage Per Lamp / Ballast

BLamps/Fixture

C# of

Fixtures

Exterior Entries ( Entry canopy 236 ft2): Tradable WattageType B1: Type B1: Exterior Wall Sconce: LED A Lamp 12W: 1 6 12 72Type F: Type F: Exterior Canopy: LED A Lamp 12W: 1 3 12 36

108Total Tradable Proposed Watts =

Exterior Lighting Compliance StatementCompliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans,specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have beendesigned to meet the 90.1 (2010) Standard requirements in COMcheck Version 4.0.5.1 and to comply with any applicablemandatory requirements listed in the Inspection Checklist.

Michael L. DodaneName - Title Signature Date

Exterior Lighting PASSES: Design 84% better than code

Project Title:Data filename:

Round Rock Apartments - Bldg Type 1X:\16056\CALC\HVAC\Ecalcs\Building 1.cck

11/17/16Report date:224 ofPage

11-18-16

Page 5: Software Version 4.0.5.1 Envelope Compliance Certificate · Birmingham, AL 35209 205-484-2836 Designer/Contractor: Migre Engineers 1200 W SR 434 Suite 301 Longwood, FL 32750 407-636-7999

COMcheck Software Version 4.0.5.1

Mechanical Compliance Certificate

Project Title:

90.1 (2010) Standard

Project Type: New Construction

Location: Round Rock, TexasClimate Zone: 2a

Construction Site: Owner/Agent:MN Capital Strategies2204 Lakeshore DriveSuite 450Birmingham, AL 35209205-484-2836

Designer/Contractor:Migre Engineers1200 W SR 434Suite 301Longwood, FL 32750407-636-7999

Project Information

Energy Code:

Round Rock Apartments - Bldg Type 1

Mechanical Systems List

Quantity System Type & Description

Heating: 1 each - Central Furnace, Electric, Capacity = 8200 kBtu/h No minimum efficiency requirement appliesCooling: 1 each - Split System, Capacity = 11000 kBtu/h, Air-Cooled Condenser, No Economizer, Economizer exception: LowCapacity Residential Proposed Efficiency = 14.00 EER, Required Efficiency: 9.70 EER (9.4 IPLV)Fan System: Unspecified

39 AHU/CU-A (Single Zone):

Heating: 1 each - Central Furnace, Electric, Capacity = 13100 kBtu/h No minimum efficiency requirement appliesCooling: 1 each - Split System, Capacity = 15600 kBtu/h, Air-Cooled Condenser, No Economizer, Economizer exception: LowCapacity Residential Proposed Efficiency = 14.00 EER, Required Efficiency: 9.70 EER (9.4 IPLV)Fan System: Unspecified

14 AHU/CU-B (Single Zone):

Heating: 1 each - Central Furnace, Electric, Capacity = 14500 kBtu/h No minimum efficiency requirement appliesCooling: 1 each - Split System, Capacity = 14100 kBtu/h, Air-Cooled Condenser, No Economizer, Economizer exception: LowCapacity Residential Proposed Efficiency = 14.00 EER, Required Efficiency: 9.70 EER (9.4 IPLV)Fan System: Unspecified

6 AHU/CU-C (Single Zone):

Heating: 1 each - Central Furnace, Electric, Capacity = 15200 kBtu/h No minimum efficiency requirement appliesCooling: 1 each - Split System, Capacity = 20400 kBtu/h, Air-Cooled Condenser, No Economizer, Economizer exception: LowCapacity Residential Proposed Efficiency = 14.00 EER, Required Efficiency: 9.70 EER (9.4 IPLV)Fan System: Unspecified

1 AHU/CU-CL (Single Zone):

Electric Storage Water Heater, Capacity: 50 gallons Proposed Efficiency: 0.95 EF, Required Efficiency: 0.86 EF

20 Water Heater 1:

Electric Storage Water Heater, Capacity: 40 gallons Proposed Efficiency: 0.95 EF, Required Efficiency: 0.88 EF

20 Water Heater 2:

Project Title:Data filename:

Round Rock Apartments - Bldg Type 1X:\16056\CALC\HVAC\Ecalcs\Building 1.cck

11/17/16Report date:225 ofPage

Page 6: Software Version 4.0.5.1 Envelope Compliance Certificate · Birmingham, AL 35209 205-484-2836 Designer/Contractor: Migre Engineers 1200 W SR 434 Suite 301 Longwood, FL 32750 407-636-7999

Quantity System Type & Description

Electric Storage Water Heater, Capacity: 30 gallons Proposed Efficiency: 0.95 EF, Required Efficiency: 0.89 EF

20 Water Heater 3:

Electric Instantaneous Water Heater, Capacity: 4 gallons No minimum efficiency requirement applies

1 Water Heater 4:

Mechanical Compliance StatementCompliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,specifications, and other calculations submitted with this permit application. The proposed mechanical systems have beendesigned to meet the 90.1 (2010) Standard requirements in COMcheck Version 4.0.5.1 and to comply with any applicablemandatory requirements listed in the Inspection Checklist.

Greg H. KlebanoffName - Title Signature Date

Project Title:Data filename:

Round Rock Apartments - Bldg Type 1X:\16056\CALC\HVAC\Ecalcs\Building 1.cck

11/17/16Report date:226 ofPage

11-18-16

Page 7: Software Version 4.0.5.1 Envelope Compliance Certificate · Birmingham, AL 35209 205-484-2836 Designer/Contractor: Migre Engineers 1200 W SR 434 Suite 301 Longwood, FL 32750 407-636-7999

COMcheck Software Version 4.0.5.1

Envelope Compliance Certificate

Project Title:

90.1 (2010) Standard

Project Type: New ConstructionVertical Glazing / Wall Area: 24%

Location: Round Rock, TexasClimate Zone: 2a

Construction Site:Round Rock, TX

Owner/Agent:MN Capital Strategies2204 Lakeshore DriveSuite 450Birmingham, AL 35209205-484-2836

Designer/Contractor:Migre Engineers1200 W SR 434Suite 301Longwood, FL 32750407-636-7999

Project Information

Energy Code:

Round Rock Apartments - Bldg Type 2

Building Area Floor Area

1-Bldg Type 2 (Multifamily) : Residential 74834

Envelope Assemblies

Assembly CavityR-Value

Cont.R-Value

ProposedU-Factor

Budget U-Factor(a)

Gross Areaor

Perimeter

Roof 1: Attic Roof with Wood Joists, [Bldg. Use 1 - Bldg Type 2] 20472 38.0 0.0 0.027 0.027Exterior Wall 1: Wood-Framed, 16" o.c., [Bldg. Use 1 - Bldg Type 2] 8340 13.0 0.0 0.089 0.089Window 1: Vinyl/Fiberglass Frame:Operable, Perf. Specs.: Product IDNA, SHGC 0.35, PF 0.30, VT 0.76, [Bldg. Use 1 - Bldg Type 2] (b)

952 --- --- 0.350 0.750

Exterior Wall 2: Wood-Framed, 16" o.c., [Bldg. Use 1 - Bldg Type 2] 2620 13.0 0.0 0.089 0.089Window 2: Vinyl/Fiberglass Frame:Operable, Perf. Specs.: Product IDNA, SHGC 0.35, VT 0.76, [Bldg. Use 1 - Bldg Type 2] (b)

552 --- --- 0.350 0.750

Exterior Wall 3: Wood-Framed, 16" o.c., [Bldg. Use 1 - Bldg Type 2] 10800 13.0 0.0 0.089 0.089Window 3: Vinyl/Fiberglass Frame:Operable, Perf. Specs.: Product IDNA, SHGC 0.35, PF 0.30, VT 0.76, [Bldg. Use 1 - Bldg Type 2] (b)

3856 --- --- 0.350 0.750

Exterior Wall 4: Wood-Framed, 16" o.c., [Bldg. Use 1 - Bldg Type 2] 2570 13.0 0.0 0.089 0.089Window 4: Vinyl/Fiberglass Frame:Operable, Perf. Specs.: Product IDNA, SHGC 0.35, VT 0.76, [Bldg. Use 1 - Bldg Type 2] (b)

548 --- --- 0.350 0.750

Semi-Exterior Wall 1: Wood-Framed, 16" o.c., [Bldg. Use 1 - Bldg Type2]

2350 11.0 0.0 0.094 0.089

Semi-Exterior Wall 2: Wood-Framed, 16" o.c., [Bldg. Use 1 - Bldg Type2]

380 11.0 0.0 0.094 0.089

Semi-Exterior Wall 3: Wood-Framed, 16" o.c., [Bldg. Use 1 - Bldg Type2]

280 11.0 0.0 0.094 0.089

Floor 1: Slab-On-Grade:Unheated, [Bldg. Use 1 - Bldg Type 2] (c) 692 --- --- 0.730 0.730

(a) Budget U-factors are used for software baseline calculations ONLY, and are not code requirements.(b) Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation.

Project Title:Data filename:

Round Rock Apartments - Bldg Type 2X:\16056\CALC\HVAC\Ecalcs\Building 2.cck

11/17/16Report date:221 ofPage

Page 8: Software Version 4.0.5.1 Envelope Compliance Certificate · Birmingham, AL 35209 205-484-2836 Designer/Contractor: Migre Engineers 1200 W SR 434 Suite 301 Longwood, FL 32750 407-636-7999

(c) Slab-On-Grade proposed and budget U-factors shown in table are F-factors.

Envelope Compliance StatementCompliance Statement: The proposed envelope design represented in this document is consistent with the building plans,specifications, and other calculations submitted with this permit application. The proposed envelope systems have beendesigned to meet the 90.1 (2010) Standard requirements in COMcheck Version 4.0.5.1 and to comply with any applicablemandatory requirements listed in the Inspection Checklist.

Greg H. KlebanoffName - Title Signature Date

Envelope PASSES: Design 2% better than code

Project Title:Data filename:

Round Rock Apartments - Bldg Type 2X:\16056\CALC\HVAC\Ecalcs\Building 2.cck

11/17/16Report date:222 ofPage

11-18-16

Page 9: Software Version 4.0.5.1 Envelope Compliance Certificate · Birmingham, AL 35209 205-484-2836 Designer/Contractor: Migre Engineers 1200 W SR 434 Suite 301 Longwood, FL 32750 407-636-7999

COMcheck Software Version 4.0.5.1

Interior Lighting Compliance Certificate

Project Title:

90.1 (2010) Standard

Project Type: New Construction

Construction Site:Round Rock, TX

Owner/Agent:MN Capital Strategies2204 Lakeshore DriveSuite 450Birmingham, AL 35209205-484-2836

Designer/Contractor:Migre Engineers1200 W SR 434Suite 301Longwood, FL 32750407-636-7999

Project Information

Energy Code:

Round Rock Apartments - Bldg Type 2

Allowed Interior Lighting Power

AArea Category

BFloor Area

(ft2)

CAllowed

Watts / ft2

DAllowed Watts

(B X C)

1-Bldg Type 2 (Multifamily) 74834 0.60 44900

44900Total Allowed Watts =

Proposed Interior Lighting PowerE

(C X D)D

FixtureWatt.

AFixture ID : Description / Lamp / Wattage Per Lamp / Ballast

BLamps/Fixture

C# of

Fixtures

1-Bldg Type 2 (Multifamily)Type A: Type A: Corridor Wall Sconce: LED A Lamp 12W: 1 60 12 720Type C: Type C: Corridor Ceiling: LED Panel 19W: 1 120 12 1440Type D: Type D: 4' Striplight: LED Linear 33W: 1 24 31 744

2904Total Proposed Watts =

Interior Lighting Compliance StatementCompliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans,specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have beendesigned to meet the 90.1 (2010) Standard requirements in COMcheck Version 4.0.5.1 and to comply with any applicablemandatory requirements listed in the Inspection Checklist.

Michael L. DodaneName - Title Signature Date

Interior Lighting PASSES: Design 94% better than code

Project Title:Data filename:

Round Rock Apartments - Bldg Type 2X:\16056\CALC\HVAC\Ecalcs\Building 2.cck

11/17/16Report date:223 ofPage

11-18-16

Page 10: Software Version 4.0.5.1 Envelope Compliance Certificate · Birmingham, AL 35209 205-484-2836 Designer/Contractor: Migre Engineers 1200 W SR 434 Suite 301 Longwood, FL 32750 407-636-7999

COMcheck Software Version 4.0.5.1

Exterior Lighting Compliance Certificate

Project Title:

90.1 (2010) Standard

Project Type: New Construction

Construction Site:Round Rock, TX

Owner/Agent:MN Capital Strategies2204 Lakeshore DriveSuite 450Birmingham, AL 35209205-484-2836

Designer/Contractor:Migre Engineers1200 W SR 434Suite 301Longwood, FL 32750407-636-7999

Project Information

Energy Code:

Round Rock Apartments - Bldg Type 2

2 (Residentially zoned area)Exterior Lighting Zone

Allowed Exterior Lighting Power

AArea/Surface Category

BQuantity

CAllowed

Watts / Unit

DTradableWattage

EAllowed Watts

(B X C)

Exterior Entries (Entry canopy) 236 ft2 0.25 Yes 59

Total Tradable Watts (a) =Total Allowed Watts =

Total Allowed Supplemental Watts (b) =

59

59

600

(a) Wattage tradeoffs are only allowed between tradable areas/surfaces.(b) A supplemental allowance equal to 600 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.

Proposed Exterior Lighting PowerE

(C X D)D

FixtureWatt.

AFixture ID : Description / Lamp / Wattage Per Lamp / Ballast

BLamps/Fixture

C# of

Fixtures

Exterior Entries ( Entry canopy 236 ft2): Tradable WattageType B1: Type B1: Exterior Wall Sconce: LED A Lamp 12W: 1 6 12 72Type F: Type F: Exterior Canopy: LED A Lamp 12W: 1 3 12 36

108Total Tradable Proposed Watts =

Exterior Lighting Compliance StatementCompliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans,specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have beendesigned to meet the 90.1 (2010) Standard requirements in COMcheck Version 4.0.5.1 and to comply with any applicablemandatory requirements listed in the Inspection Checklist.

Michael L. DodaneName - Title Signature Date

Exterior Lighting PASSES: Design 84% better than code

Project Title:Data filename:

Round Rock Apartments - Bldg Type 2X:\16056\CALC\HVAC\Ecalcs\Building 2.cck

11/17/16Report date:224 ofPage

11-18-16

Page 11: Software Version 4.0.5.1 Envelope Compliance Certificate · Birmingham, AL 35209 205-484-2836 Designer/Contractor: Migre Engineers 1200 W SR 434 Suite 301 Longwood, FL 32750 407-636-7999

COMcheck Software Version 4.0.5.1

Mechanical Compliance Certificate

Project Title:

90.1 (2010) Standard

Project Type: New Construction

Location: Round Rock, TexasClimate Zone: 2a

Construction Site:Round Rock, TX

Owner/Agent:MN Capital Strategies2204 Lakeshore DriveSuite 450Birmingham, AL 35209205-484-2836

Designer/Contractor:Migre Engineers1200 W SR 434Suite 301Longwood, FL 32750407-636-7999

Project Information

Energy Code:

Round Rock Apartments - Bldg Type 2

Mechanical Systems List

Quantity System Type & Description

Heating: 1 each - Central Furnace, Electric, Capacity = 8200 kBtu/h No minimum efficiency requirement appliesCooling: 1 each - Split System, Capacity = 11000 kBtu/h, Air-Cooled Condenser, No Economizer, Economizer exception: LowCapacity Residential Proposed Efficiency = 14.00 EER, Required Efficiency: 9.70 EER (9.4 IPLV)Fan System: Unspecified

27 AHU/CU-A (Single Zone):

Heating: 1 each - Central Furnace, Electric, Capacity = 13100 kBtu/h No minimum efficiency requirement appliesCooling: 1 each - Split System, Capacity = 15600 kBtu/h, Air-Cooled Condenser, No Economizer, Economizer exception: LowCapacity Residential Proposed Efficiency = 14.00 EER, Required Efficiency: 9.70 EER (9.4 IPLV)Fan System: Unspecified

26 AHU/CU-B (Single Zone):

Heating: 1 each - Central Furnace, Electric, Capacity = 14500 kBtu/h No minimum efficiency requirement appliesCooling: 1 each - Split System, Capacity = 14100 kBtu/h, Air-Cooled Condenser, No Economizer, Economizer exception: LowCapacity Residential Proposed Efficiency = 14.00 EER, Required Efficiency: 9.70 EER (9.4 IPLV)Fan System: Unspecified

3 AHU/CU-C (Single Zone):

Electric Storage Water Heater, Capacity: 50 gallons Proposed Efficiency: 0.95 EF, Required Efficiency: 0.86 EF

15 Water Heater 1:

Electric Storage Water Heater, Capacity: 40 gallons Proposed Efficiency: 0.95 EF, Required Efficiency: 0.88 EF

15 Water Heater 2:

Electric Storage Water Heater, Capacity: 30 gallons Proposed Efficiency: 0.95 EF, Required Efficiency: 0.89 EF

20 Water Heater 3:

Electric Instantaneous Water Heater, Capacity: 4 gallons No minimum efficiency requirement applies

6 Water Heater 4:

Project Title:Data filename:

Round Rock Apartments - Bldg Type 2X:\16056\CALC\HVAC\Ecalcs\Building 2.cck

11/17/16Report date:225 ofPage

Page 12: Software Version 4.0.5.1 Envelope Compliance Certificate · Birmingham, AL 35209 205-484-2836 Designer/Contractor: Migre Engineers 1200 W SR 434 Suite 301 Longwood, FL 32750 407-636-7999

Mechanical Compliance StatementCompliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,specifications, and other calculations submitted with this permit application. The proposed mechanical systems have beendesigned to meet the 90.1 (2010) Standard requirements in COMcheck Version 4.0.5.1 and to comply with any applicablemandatory requirements listed in the Inspection Checklist.

Greg H. KlebanoffName - Title Signature Date

Project Title:Data filename:

Round Rock Apartments - Bldg Type 2X:\16056\CALC\HVAC\Ecalcs\Building 2.cck

11/17/16Report date:226 ofPage

11-18-16

Page 13: Software Version 4.0.5.1 Envelope Compliance Certificate · Birmingham, AL 35209 205-484-2836 Designer/Contractor: Migre Engineers 1200 W SR 434 Suite 301 Longwood, FL 32750 407-636-7999

REScheck Software Version 4.6.3

Compliance Certificate

Project Round Rock Apartments - Building Type 3

Energy Code: 2012 IECCLocation: Round Rock, TexasConstruction Type: Multi-familyProject Type: New ConstructionConditioned Floor Area: 52,335 ft2Glazing Area 10%Climate Zone: 2 (1688 HDD)Permit Date:

Construction Site:Round Rock, TX

Owner/Agent:MN Capital Strategies2204 Lakeshore DriveSuite 450Birmingham, AL 35209205-484-2836

Designer/Contractor:Migre Engineers LLC1200 W SR 434Suite 301Longwood, FL 32750407-636-7999

Permit Number:

Compliance: Passes using UA trade-off1.1% Better Than Code Maximum UA: 2415 Your UA: 2388

The % Better or Worse Than Code Index reflects how close to compliance the house is based on code trade-off rules.It DOES NOT provide an estimate of energy use or cost relative to a minimum-code home.

Compliance: Maximum SHGC: 0.25 Your SHGC: 0.25

Envelope Assemblies

AssemblyGross Area

orPerimeter

CavityR-Value

Cont.R-Value U-Factor UA

Ceiling 1: Flat Ceiling or Scissor Truss 52,335 38.0 0.0 0.030 1570

Wall 1: Wood Frame, 16" o.c. 5,240 13.0 0.0 0.082 385

Window 1: Vinyl/Fiberglass Frame:Single Pane SHGC: 0.25

550 0.350 193

Floor 1: Slab-On-Grade:Unheated Insulation depth: 0.0'

230 0.0 1.042 240

Name - Title Signature Date

Compliance Statement: The proposed building design described here is consistent with the building plans, specifications, and othercalculations submitted with the permit application. The proposed building has been designed to meet the 2012 IECC requirements inREScheck Version 4.6.3 and to comply with the mandatory requirements listed in the REScheck Inspection Checklist.

Project Title: Round Rock Apartments - Building Type 3Data filename: X:\16056\CALC\HVAC\Ecalcs\Building Type 3.rck Page 1 of 1

11/16/16Report date:

GREG H. KLEBANOFF 11-18-16

Page 14: Software Version 4.0.5.1 Envelope Compliance Certificate · Birmingham, AL 35209 205-484-2836 Designer/Contractor: Migre Engineers 1200 W SR 434 Suite 301 Longwood, FL 32750 407-636-7999

2012 IECC EnergyEfficiency Certificate

Insulation Rating R-Value

13.00Above-Grade Wall

0.00Below-Grade Wall

0.00Floor

38.00Ceiling / Roof

_______Ductwork (unconditioned spaces):

Glass & Door Rating SHGCU-Factor

0.250.35Window

Door

Heating & Cooling Equipment Efficiency

_______Heating System:_________________________

_______Cooling System:_________________________

_______Water Heater:___________________________

Name: Date:Comments

Page 15: Software Version 4.0.5.1 Envelope Compliance Certificate · Birmingham, AL 35209 205-484-2836 Designer/Contractor: Migre Engineers 1200 W SR 434 Suite 301 Longwood, FL 32750 407-636-7999

COMcheck Software Version 4.0.5.1

Envelope Compliance Certificate

Project Title:

90.1 (2010) Standard

Project Type: New ConstructionVertical Glazing / Wall Area: 20%

Location: Round Rock, TexasClimate Zone: 2a

Construction Site:Round Rock, TX

Owner/Agent:MN Capital Strategies2204 Lakeshore DriveSuite 450Birmingham, AL 35209205-484-2836

Designer/Contractor:Migre Engineers1200 W SR 434Suite 301Longwood, FL 32750407-636-7999

Project Information

Energy Code:

Round Rock Apartments - Building Type 4a - Clubhouse

Building Area Floor Area

1-Clubhouse (Convention Center) : Residential 5975

Envelope Assemblies

Assembly CavityR-Value

Cont.R-Value

ProposedU-Factor

Budget U-Factor(a)

Gross Areaor

Perimeter

Roof: Attic Roof with Wood Joists, [Bldg. Use 1 - Clubhouse] 6025 38.0 0.0 0.027 0.027Floor 1: Slab-On-Grade:Unheated, [Bldg. Use 1 - Clubhouse] (c) 358 --- --- 0.730 0.730

NORTHExterior Wall 3: Wood-Framed, 16" o.c., [Bldg. Use 1 - Clubhouse] 1402 13.0 0.0 0.089 0.089Window 3: Vinyl/Fiberglass Frame:Operable, Perf. Specs.: Product IDNA, SHGC 0.35, VT 0.76, [Bldg. Use 1 - Clubhouse] (b)

395 --- --- 0.350 0.750

EASTExterior Wall 4: Wood-Framed, 16" o.c., [Bldg. Use 1 - Clubhouse] 576 13.0 0.0 0.089 0.089

SOUTHExterior Wall: Wood-Framed, 16" o.c., [Bldg. Use 1 - Clubhouse] 1660 13.0 0.0 0.089 0.089Window 1: Vinyl/Fiberglass Frame:Operable, Perf. Specs.: Product IDNA, SHGC 0.35, VT 0.76, [Bldg. Use 1 - Clubhouse] (b)

462 --- --- 0.350 0.750

WESTExterior Wall 2: Wood-Framed, 16" o.c., [Bldg. Use 1 - Clubhouse] 897 13.0 0.0 0.089 0.089Window 2: Vinyl/Fiberglass Frame:Operable, Perf. Specs.: Product IDNA, SHGC 0.35, VT 0.76, [Bldg. Use 1 - Clubhouse] (b)

27 --- --- 0.350 0.750

(a) Budget U-factors are used for software baseline calculations ONLY, and are not code requirements.(b) Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation.(c) Slab-On-Grade proposed and budget U-factors shown in table are F-factors.

Project Title:Data filename:

Round Rock Apartments - Building Type 4a - ClubhouseX:\16056\CALC\HVAC\Ecalcs\Clubhouse.cck

11/17/16Report date:231 ofPage

Page 16: Software Version 4.0.5.1 Envelope Compliance Certificate · Birmingham, AL 35209 205-484-2836 Designer/Contractor: Migre Engineers 1200 W SR 434 Suite 301 Longwood, FL 32750 407-636-7999

Envelope Compliance StatementCompliance Statement: The proposed envelope design represented in this document is consistent with the building plans,specifications, and other calculations submitted with this permit application. The proposed envelope systems have beendesigned to meet the 90.1 (2010) Standard requirements in COMcheck Version 4.0.5.1 and to comply with any applicablemandatory requirements listed in the Inspection Checklist.

Greg H. KlebanoffName - Title Signature Date

Envelope PASSES: Design 8% better than code

Project Title:Data filename:

Round Rock Apartments - Building Type 4a - ClubhouseX:\16056\CALC\HVAC\Ecalcs\Clubhouse.cck

11/17/16Report date:232 ofPage

11-18-16

Page 17: Software Version 4.0.5.1 Envelope Compliance Certificate · Birmingham, AL 35209 205-484-2836 Designer/Contractor: Migre Engineers 1200 W SR 434 Suite 301 Longwood, FL 32750 407-636-7999

COMcheck Software Version 4.0.5.1

Interior Lighting Compliance Certificate

Project Title:

90.1 (2010) Standard

Project Type: New Construction

Construction Site:Round Rock, TX

Owner/Agent:MN Capital Strategies2204 Lakeshore DriveSuite 450Birmingham, AL 35209205-484-2836

Designer/Contractor:Migre Engineers1200 W SR 434Suite 301Longwood, FL 32750407-636-7999

Project Information

Energy Code:

Round Rock Apartments - Building Type 4a - Clubhouse

Allowed Interior Lighting Power

AArea Category

BFloor Area

(ft2)

CAllowed

Watts / ft2

DAllowed Watts

(B X C)

1-Clubhouse (Convention Center) 5975 1.08 6453

6453Total Allowed Watts =

Proposed Interior Lighting PowerE

(C X D)D

FixtureWatt.

AFixture ID : Description / Lamp / Wattage Per Lamp / Ballast

BLamps/Fixture

C# of

Fixtures

1-Clubhouse (Convention Center)Type A: Type A: Corridor Wall Sconce: LED A Lamp 12W: 1 4 12 48Type C: Type C: Corridor Ceiling: LED Panel 19W: 1 93 12 1116Type D: Type D: 4' Striplight: LED Linear 33W: 1 3 31 93

1257Total Proposed Watts =

Interior Lighting Compliance StatementCompliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans,specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have beendesigned to meet the 90.1 (2010) Standard requirements in COMcheck Version 4.0.5.1 and to comply with any applicablemandatory requirements listed in the Inspection Checklist.

Michael L. DodaneName - Title Signature Date

Interior Lighting PASSES: Design 81% better than code

Project Title:Data filename:

Round Rock Apartments - Building Type 4a - ClubhouseX:\16056\CALC\HVAC\Ecalcs\Clubhouse.cck

11/17/16Report date:233 ofPage

11-18-16

Page 18: Software Version 4.0.5.1 Envelope Compliance Certificate · Birmingham, AL 35209 205-484-2836 Designer/Contractor: Migre Engineers 1200 W SR 434 Suite 301 Longwood, FL 32750 407-636-7999

COMcheck Software Version 4.0.5.1

Exterior Lighting Compliance Certificate

Project Title:

90.1 (2010) Standard

Project Type: New Construction

Construction Site:Round Rock, TX

Owner/Agent:MN Capital Strategies2204 Lakeshore DriveSuite 450Birmingham, AL 35209205-484-2836

Designer/Contractor:Migre Engineers1200 W SR 434Suite 301Longwood, FL 32750407-636-7999

Project Information

Energy Code:

Round Rock Apartments - Building Type 4a - Clubhouse

2 (Residentially zoned area)Exterior Lighting Zone

Allowed Exterior Lighting Power

AArea/Surface Category

BQuantity

CAllowed

Watts / Unit

DTradableWattage

EAllowed Watts

(B X C)

Entry canopy 754 ft2 0.25 Yes 188

Total Tradable Watts (a) =Total Allowed Watts =

Total Allowed Supplemental Watts (b) =

188

188

600

(a) Wattage tradeoffs are only allowed between tradable areas/surfaces.(b) A supplemental allowance equal to 600 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.

Proposed Exterior Lighting PowerE

(C X D)D

FixtureWatt.

AFixture ID : Description / Lamp / Wattage Per Lamp / Ballast

BLamps/Fixture

C# of

Fixtures

Entry canopy (754 ft2): Tradable WattageType B1: Type B1: Exterior Wall Sconce: LED A Lamp 12W: 1 3 12 36Type F: Type F: Exterior Canopy: LED A Lamp 12W: 1 13 12 156

192Total Tradable Proposed Watts =

Exterior Lighting Compliance StatementCompliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans,specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have beendesigned to meet the 90.1 (2010) Standard requirements in COMcheck Version 4.0.5.1 and to comply with any applicablemandatory requirements listed in the Inspection Checklist.

Michael L. DodaneName - Title Signature Date

Exterior Lighting PASSES: Design 76% better than code

Project Title:Data filename:

Round Rock Apartments - Building Type 4a - ClubhouseX:\16056\CALC\HVAC\Ecalcs\Clubhouse.cck

11/17/16Report date:234 ofPage

11-18-16

Page 19: Software Version 4.0.5.1 Envelope Compliance Certificate · Birmingham, AL 35209 205-484-2836 Designer/Contractor: Migre Engineers 1200 W SR 434 Suite 301 Longwood, FL 32750 407-636-7999

COMcheck Software Version 4.0.5.1

Mechanical Compliance Certificate

Project Title:

90.1 (2010) Standard

Project Type: New Construction

Location: Round Rock, TexasClimate Zone: 2a

Construction Site:Round Rock, TX

Owner/Agent:MN Capital Strategies2204 Lakeshore DriveSuite 450Birmingham, AL 35209205-484-2836

Designer/Contractor:Migre Engineers1200 W SR 434Suite 301Longwood, FL 32750407-636-7999

Project Information

Energy Code:

Round Rock Apartments - Building Type 4a - Clubhouse

Mechanical Systems List

Quantity System Type & Description

Heating: 1 each - Central Furnace, Electric, Capacity = 32000 kBtu/h No minimum efficiency requirement appliesCooling: 1 each - Split System, Capacity = 50600 kBtu/h, Air-Cooled Condenser, No Economizer, Economizer exception: LowCapacity Residential Proposed Efficiency = 16.00 EER, Required Efficiency: 9.70 EER (9.4 IPLV)Fan System: Unspecified

1 AHU/CU-1 (Single Zone):

Heating: 1 each - Central Furnace, Electric, Capacity = 32000 kBtu/h No minimum efficiency requirement appliesCooling: 1 each - Split System, Capacity = 53600 kBtu/h, Air-Cooled Condenser, No Economizer, Economizer exception: LowCapacity Residential Proposed Efficiency = 16.00 EER, Required Efficiency: 9.70 EER (9.4 IPLV)Fan System: Unspecified

1 AHU/CU-2 (Single Zone):

Heating: 1 each - Central Furnace, Electric, Capacity = 35100 kBtu/h No minimum efficiency requirement appliesCooling: 1 each - Split System, Capacity = 49800 kBtu/h, Air-Cooled Condenser, No Economizer, Economizer exception: LowCapacity Residential Proposed Efficiency = 16.00 EER, Required Efficiency: 9.70 EER (9.4 IPLV)Fan System: Unspecified

1 AHU/CU-3 (Single Zone):

Heating: 1 each - Central Furnace, Electric, Capacity = 16200 kBtu/h No minimum efficiency requirement appliesCooling: 1 each - Split System, Capacity = 22900 kBtu/h, Air-Cooled Condenser, No Economizer, Economizer exception: LowCapacity Residential Proposed Efficiency = 14.00 EER, Required Efficiency: 9.70 EER (9.4 IPLV)Fan System: Unspecified

1 AHU/CU-4 (Single Zone):

Heating: 1 each - Central Furnace, Electric, Capacity = 33500 kBtu/h No minimum efficiency requirement appliesCooling: 1 each - Split System, Capacity = 44600 kBtu/h, Air-Cooled Condenser, No Economizer, Economizer exception: LowCapacity Residential Proposed Efficiency = 14.00 EER, Required Efficiency: 9.70 EER (9.4 IPLV)Fan System: Unspecified

1 AHU/CU-5 (Single Zone):

Project Title:Data filename:

Round Rock Apartments - Building Type 4a - ClubhouseX:\16056\CALC\HVAC\Ecalcs\Clubhouse.cck

11/17/16Report date:235 ofPage

Page 20: Software Version 4.0.5.1 Envelope Compliance Certificate · Birmingham, AL 35209 205-484-2836 Designer/Contractor: Migre Engineers 1200 W SR 434 Suite 301 Longwood, FL 32750 407-636-7999

Quantity System Type & Description

Heating: 1 each - Central Furnace, Electric, Capacity = 14000 kBtu/h No minimum efficiency requirement appliesCooling: 1 each - Split System, Capacity = 20900 kBtu/h, Air-Cooled Condenser, No Economizer, Economizer exception: LowCapacity Residential Proposed Efficiency = 14.00 EER, Required Efficiency: 9.70 EER (9.4 IPLV)Fan System: Unspecified

1 AHU/CU-6 (Single Zone):

Electric Storage Water Heater, Capacity: 40 gallons Proposed Efficiency: 0.95 EF, Required Efficiency: 0.88 EF

1 Water Heater 1:

Mechanical Compliance StatementCompliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,specifications, and other calculations submitted with this permit application. The proposed mechanical systems have beendesigned to meet the 90.1 (2010) Standard requirements in COMcheck Version 4.0.5.1 and to comply with any applicablemandatory requirements listed in the Inspection Checklist.

Greg H. KlebanoffName - Title Signature Date

Project Title:Data filename:

Round Rock Apartments - Building Type 4a - ClubhouseX:\16056\CALC\HVAC\Ecalcs\Clubhouse.cck

11/17/16Report date:236 ofPage

11-18-16

Page 21: Software Version 4.0.5.1 Envelope Compliance Certificate · Birmingham, AL 35209 205-484-2836 Designer/Contractor: Migre Engineers 1200 W SR 434 Suite 301 Longwood, FL 32750 407-636-7999

COMcheck Software Version 4.0.5.1

Envelope Compliance Certificate

Project Title:

90.1 (2010) Standard

Project Type: New ConstructionVertical Glazing / Wall Area: 33%

Location: Round Rock, TexasClimate Zone: 2a

Construction Site:Round Rock, TX

Owner/Agent:MN Capital Strategies2204 Lakeshore DriveSuite 450Birmingham, AL 35209205-484-2836

Designer/Contractor:Migre Engineers1200 W SR 434Suite 301Longwood, FL 32750407-636-7999

Project Information

Energy Code:

Round Rock Apartments - Bldg Type 4b Fitness

Building Area Floor Area

1-Fitness (Exercise Center) : Residential 3038

Envelope Assemblies

Assembly CavityR-Value

Cont.R-Value

ProposedU-Factor

Budget U-Factor(a)

Gross Areaor

Perimeter

Roof 1: Attic Roof with Wood Joists, [Bldg. Use 1 - Fitness] 451 38.0 0.0 0.027 0.027Exterior Wall 1: Wood-Framed, 16" o.c., [Bldg. Use 1 - Fitness] 2045 13.0 0.0 0.089 0.089Window 1: Metal Frame, Perf. Specs.: Product ID NA, SHGC 0.35, PF0.10, [Bldg. Use 1 - Fitness] (b)

677 --- --- 0.350 0.750

Floor 1: Slab-On-Grade:Unheated, [Bldg. Use 1 - Fitness] (c) 238 --- --- 0.730 0.730

(a) Budget U-factors are used for software baseline calculations ONLY, and are not code requirements.(b) Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation.(c) Slab-On-Grade proposed and budget U-factors shown in table are F-factors.

Envelope Compliance StatementCompliance Statement: The proposed envelope design represented in this document is consistent with the building plans,specifications, and other calculations submitted with this permit application. The proposed envelope systems have beendesigned to meet the 90.1 (2010) Standard requirements in COMcheck Version 4.0.5.1 and to comply with any applicablemandatory requirements listed in the Inspection Checklist.

Greg H. KlebanoffName - Title Signature Date

Envelope PASSES: Design 0.1% better than code

Project Title:Data filename:

Round Rock Apartments - Bldg Type 4b FitnessX:\16056\CALC\HVAC\Ecalcs\Fitness.cck

11/17/16Report date:121 ofPage

11-18-16

Page 22: Software Version 4.0.5.1 Envelope Compliance Certificate · Birmingham, AL 35209 205-484-2836 Designer/Contractor: Migre Engineers 1200 W SR 434 Suite 301 Longwood, FL 32750 407-636-7999

COMcheck Software Version 4.0.5.1

Interior Lighting Compliance Certificate

Project Title:

90.1 (2010) Standard

Project Type: New Construction

Construction Site:Round Rock, TX

Owner/Agent:MN Capital Strategies2204 Lakeshore DriveSuite 450Birmingham, AL 35209205-484-2836

Designer/Contractor:Migre Engineers1200 W SR 434Suite 301Longwood, FL 32750407-636-7999

Project Information

Energy Code:

Round Rock Apartments - Bldg Type 4b Fitness

Allowed Interior Lighting Power

AArea Category

BFloor Area

(ft2)

CAllowed

Watts / ft2

DAllowed Watts

(B X C)

1-Fitness (Exercise Center) 3038 0.88 2673

2673Total Allowed Watts =

Proposed Interior Lighting PowerE

(C X D)D

FixtureWatt.

AFixture ID : Description / Lamp / Wattage Per Lamp / Ballast

BLamps/Fixture

C# of

Fixtures

1-Fitness (Exercise Center)Type A: Type A: Corridor Wall Sconce: LED A Lamp 12W: 1 2 12 24Type C: Type C: Corridor Ceiling: LED Panel 19W: 1 54 12 648

672Total Proposed Watts =

Interior Lighting Compliance StatementCompliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans,specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have beendesigned to meet the 90.1 (2010) Standard requirements in COMcheck Version 4.0.5.1 and to comply with any applicablemandatory requirements listed in the Inspection Checklist.

Michael L. DodaneName - Title Signature Date

Interior Lighting PASSES: Design 75% better than code

Project Title:Data filename:

Round Rock Apartments - Bldg Type 4b FitnessX:\16056\CALC\HVAC\Ecalcs\Fitness.cck

11/17/16Report date:122 ofPage

11-18-16

Page 23: Software Version 4.0.5.1 Envelope Compliance Certificate · Birmingham, AL 35209 205-484-2836 Designer/Contractor: Migre Engineers 1200 W SR 434 Suite 301 Longwood, FL 32750 407-636-7999

COMcheck Software Version 4.0.5.1

Exterior Lighting Compliance Certificate

Project Title:

90.1 (2010) Standard

Project Type: New Construction

Construction Site:Round Rock, TX

Owner/Agent:MN Capital Strategies2204 Lakeshore DriveSuite 450Birmingham, AL 35209205-484-2836

Designer/Contractor:Migre Engineers1200 W SR 434Suite 301Longwood, FL 32750407-636-7999

Project Information

Energy Code:

Round Rock Apartments - Bldg Type 4b Fitness

2 (Residentially zoned area)Exterior Lighting Zone

Allowed Exterior Lighting Power

AArea/Surface Category

BQuantity

CAllowed

Watts / Unit

DTradableWattage

EAllowed Watts

(B X C)

Exterior Entries (Entry canopy) 76 ft2 0.25 Yes 19

Total Tradable Watts (a) =Total Allowed Watts =

Total Allowed Supplemental Watts (b) =

19

19

600

(a) Wattage tradeoffs are only allowed between tradable areas/surfaces.(b) A supplemental allowance equal to 600 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.

Proposed Exterior Lighting PowerE

(C X D)D

FixtureWatt.

AFixture ID : Description / Lamp / Wattage Per Lamp / Ballast

BLamps/Fixture

C# of

Fixtures

Exterior Entries ( Entry canopy 76 ft2): Tradable WattageType B1: Type B1: Exterior Wall Sconce: LED A Lamp 12W: 1 2 12 24Type F: Type F: Exterior Canopy: LED A Lamp 12W: 1 2 12 24

48Total Tradable Proposed Watts =

Exterior Lighting Compliance StatementCompliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans,specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have beendesigned to meet the 90.1 (2010) Standard requirements in COMcheck Version 4.0.5.1 and to comply with any applicablemandatory requirements listed in the Inspection Checklist.

Michael L. DodaneName - Title Signature Date

Exterior Lighting PASSES: Design 92% better than code

Project Title:Data filename:

Round Rock Apartments - Bldg Type 4b FitnessX:\16056\CALC\HVAC\Ecalcs\Fitness.cck

11/17/16Report date:123 ofPage

11-18-16

Page 24: Software Version 4.0.5.1 Envelope Compliance Certificate · Birmingham, AL 35209 205-484-2836 Designer/Contractor: Migre Engineers 1200 W SR 434 Suite 301 Longwood, FL 32750 407-636-7999

COMcheck Software Version 4.0.5.1

Mechanical Compliance Certificate

Project Title:

90.1 (2010) Standard

Project Type: New Construction

Location: Round Rock, TexasClimate Zone: 2a

Construction Site:Round Rock, TX

Owner/Agent:MN Capital Strategies2204 Lakeshore DriveSuite 450Birmingham, AL 35209205-484-2836

Designer/Contractor:Migre Engineers1200 W SR 434Suite 301Longwood, FL 32750407-636-7999

Project Information

Energy Code:

Round Rock Apartments - Bldg Type 4b Fitness

Mechanical Systems List

Quantity System Type & Description

Mechanical Compliance StatementCompliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,specifications, and other calculations submitted with this permit application. The proposed mechanical systems have beendesigned to meet the 90.1 (2010) Standard requirements in COMcheck Version 4.0.5.1 and to comply with any applicablemandatory requirements listed in the Inspection Checklist.

Greg H. KlebanoffName - Title Signature Date

Project Title:Data filename:

Round Rock Apartments - Bldg Type 4b FitnessX:\16056\CALC\HVAC\Ecalcs\Fitness.cck

11/17/16Report date:124 ofPage

11-18-16

Page 25: Software Version 4.0.5.1 Envelope Compliance Certificate · Birmingham, AL 35209 205-484-2836 Designer/Contractor: Migre Engineers 1200 W SR 434 Suite 301 Longwood, FL 32750 407-636-7999

REScheck Software Version 4.6.3

Compliance Certificate

Project Round Rock Apartments - Building Type 4b Living Units

Energy Code: 2012 IECCLocation: Round Rock, TexasConstruction Type: Multi-familyProject Type: New ConstructionConditioned Floor Area: 1,894 ft2Glazing Area 19%Climate Zone: 2 (1688 HDD)Permit Date:

Construction Site:Round Rock, TX

Owner/Agent:MN Capital Strategies2204 Lakeshore DriveSuite 450Birmingham, AL 35209205-484-2836

Designer/Contractor:Migre Engineers LLC1200 W SR 434Suite 301Longwood, FL 32750407-636-7999

Permit Number:

Compliance: Passes using UA trade-off2.7% Better Than Code Maximum UA: 367 Your UA: 357

The % Better or Worse Than Code Index reflects how close to compliance the house is based on code trade-off rules.It DOES NOT provide an estimate of energy use or cost relative to a minimum-code home.

Compliance: Maximum SHGC: 0.25 Your SHGC: 0.25

Envelope Assemblies

AssemblyGross Area

orPerimeter

CavityR-Value

Cont.R-Value U-Factor UA

Ceiling 1: Flat Ceiling or Scissor Truss 2,090 30.0 0.0 0.035 73

Wall 1: Wood Frame, 16" o.c. 2,128 13.0 0.0 0.082 141

Window 1: Vinyl/Fiberglass Frame:Single Pane SHGC: 0.25

408 0.350 143

Greg H. KlebanoffName - Title Signature Date

Compliance Statement: The proposed building design described here is consistent with the building plans, specifications, and othercalculations submitted with the permit application. The proposed building has been designed to meet the 2012 IECC requirements inREScheck Version 4.6.3 and to comply with the mandatory requirements listed in the REScheck Inspection Checklist.

Project Title: Round Rock Apartments - Building Type 4b Living UnitsData filename: X:\16056\CALC\HVAC\Ecalcs\A5 Units.rck Page 1 of 1

11/17/16Report date:

11-18-16

Page 26: Software Version 4.0.5.1 Envelope Compliance Certificate · Birmingham, AL 35209 205-484-2836 Designer/Contractor: Migre Engineers 1200 W SR 434 Suite 301 Longwood, FL 32750 407-636-7999

2012 IECC EnergyEfficiency Certificate

Insulation Rating R-Value

13.00Above-Grade Wall

0.00Below-Grade Wall

0.00Floor

30.00Ceiling / Roof

_______Ductwork (unconditioned spaces):

Glass & Door Rating SHGCU-Factor

0.250.35Window

Door

Heating & Cooling Equipment Efficiency

_______Heating System:_________________________

_______Cooling System:_________________________

_______Water Heater:___________________________

Name: Date:Comments