solid dielectric switchgear catalog - siemens méxico
TRANSCRIPT
Company profileSince 1905, G&W Electric has helped energize the world with innovative power system solutions. With the introduction of the first disconnecting cable terminating device, G&W began to build a reputation for engineering custom solutions to meet the needs of system designers. Solutions which today have extended far beyond cable accessory products and into the latest in load and fault interrupting switchgear, reclosers, system protection equipment and distribution automation.
HeadquartersG&W headquarters is located in Bolingbrook, IL, USA, a suburb of Chicago. G&W also has manufacturing facilities or sales offices in China, Mexico, Canada, India, Singapore and Brazil. G&W covers the globe with product installations and sales representation in over 100 countries and all seven continents.
p G&W headquarters in Bolingbrook, IL USA
G & W E L E C T R I C P A G E 2
G&W Manufacturing Facility
G&W Sales Office
G&W Electric Facilities:
G&W Electric Co. Headquarters (Bolingbrook, IL, USA)
G&W China (Shanghai)
G&W Canada (Mississauga, Ontario)
G&W Mexico (San Luis Potosí)
G&W do Brasil (Salvador)
G&W sales office (Dubai)
G&W sales office (Delhi, India)
G&W sales office (Singapore)
Manufacturer’s Brass and Aluminum Foundry (Blue Island, IL, USA)
Transmission and Distribution Cable Accessories
Solid Dielectric Underground Distribution Switchgear
SF6 Underground Distribution Switchgear
Single and Three Phase Solid Dielectric Reclosers
System Protection Equipment
System Automation and Smart Grid Solutions
g&w Product overview
over 110 YearS Serving our marketS
G & W E L E C T R I C P A G E 3
G & W E L E C T R I C P A G E 4
Table of Contents
Technology
Solid Dielectric Insulation......................................................................................................... 5
Trident with SafeVu................................................................................................................. 5
Multi-way Trident Solid Dielectric Switch Overview................................................................... 8
Multi-way Three Phase Front Access
Three Phase Load Break and Three Phase Tripping (PLS-FA)...................................................10
Three Phase Load Break Ways and Fault Interrupter Ways with Single Phase Tripping (PLT-FA)..........12
Multi-way Three Phase Front/Back Access
Three Phase Load Break and Three Phase Tripping (PLS-FB)...................................................14
Three Phase Load Break and Single Phase Tripping (PLT-FB)...................................................15
Two-way Trident Solid Dielectric Switch Overview....................................................................16
Two-way Three Phase Front Access...........................................................................................18
Two-way Three Phase Front/Back Access..................................................................................19
Components for Three Phase Switches.....................................................................................20
Overcurrent Protection Options..................................................................................................21
Single Phase
Single Phase Load Break and Fault Interrupting........................................................................22
G & W E L E C T R I C P A G E 5
Technology
WHat is solid dieleCtriC insulation?G&W’s solid dielectric insulation is a field proven epoxy which is used to insulate the high voltage connections of a vacuum switch. The load break and fault interrupting vacuum bottle and bushing conductors are fully over mold-ed creating a single phase module. Each module is then coated with a semi-conductive paint creating a continuous grounding surface for a truly dead front design. For three phase switches, three modules are combined together to create one way of the switch.
Each module can also include an integral current trans-former fully protected by the solid dielectric epoxy. This ensures that the transformer is impervious to environmen-tal conditions and insulated from extreme temperatures.
G&W’s molding expertise allows for various options includ-ing 200A bushing wells or 600A apparatus bushings. The rugged epoxy surface minimizes the force required for re-moving elbow connections compared to rubber-to-rubber junctions. Different module orientations are available which permit cable entry from the front, back, or bottom of the unit.
The solid dielectric insulations and vacuum bottle combi-nation make the Trident switchgear suitable for wet and corrosive environments, vertical or horizontal mounting and use in any altitude.
Trident switches are available with the SafeVu™ option. These switches include an innovative visible break feature built into the switch, which eliminates the need to remove elbows or use externally mounted components to provide a visible open. The SafeVu operating handle is operable via hook stick or rope rigging, making it ideal for subsurface applications where space or safety practices prevent the operator from entering the vault to create a visible break.
desCriptionThe visible break is achieved with a blade type switch incorporated within the solid dielectric module. The blade is in series with the vacuum interrupter and provides a clear visible open. The blade is easily visible through a viewing window molded as an integral part of each module.
p Internal components are shown outside the module as reference.
p Close up of integrated visible break in the open position
Drive rod
Vacuum bottle
Encapsulated current transformer
when You need viSible break... trident with Safevu™
G & W E L E C T R I C P A G E 6
front acceSS
front aCCess
Front Access Trident Switches provide a solution for environments where space or aesthetics are critical factors:• Single Side Entry – There are only doors on one side of the pad mount enclosure which means
the enclosure can be placed close to a structure• Easy Access – All components, connections, and operators are located within one compartment• Flexible Configurations – Switches can range from a two way (in and out) to 6 way and can in-
clude inverted designs (bushings towards the top) or bus-tie options.
Multi-way Trident Solid Dielectric Switches
G & W E L E C T R I C P A G E 7
Multi-way Trident Solid Dielectric Switches
front/back acceSS
front/BaCk aCCess
Front/Back Access Trident Switches provide a compact foot print in a traditional switch design:• Two Side Entry – With two entry points, one side of the switch can be designated Line (Source)
and the other Load to simplify operations• Compact Foot print – The Front/Back switches can be designed to fit on existing or pre-manufac-
tured pads to simplify installation
G & W E L E C T R I C P A G E 8
p Trident PLS Switch Series p Trident PLT Switch Series
Trident solid dielectric insulated switches provide the total life cycle cost and operational benefits of fuseless, electronically controlled, resettable overcurrent protection, with the safety and maintenance benefits of an environmentally friendly dead-front design.
The Trident utilizes G&W’s time proven, submersible epoxy insulation to fully encapsulate load and fault interrupting vacuum interrupters. This solid dielectric insulation eliminates the degradation of dielectric integrity commonly associated with oil and air insulated switchgear.
pls sWitCH seriesThe Trident PLS Series is available in two through six way configurations, in any combination of three phase load break switch ways and three phase fault interrupter ways. The fault interrupter utilizes a trip-free mechanism, which provides interruption independent of the operating handle when closing into a fault. Viewing windows provide visible indication of the contact position.
plt sWitCH seriesThe Trident PLT Series is available in two through six way configurations, in any combination of three phase load break switch ways and single phase fault interrupter ways. Each fault interrupting mechanism incorporates a trip-free design which permits interruption independent of the operating handle if closing into a fault. Each phase of the fault interrupting mechanism can be independently tripped and reset, providing the ability to maintain energization of the other phases in the case of a single phase fault. Viewing windows permit visible indication of the contact position of all phases.
appliCationsTrident load and fault interrupting combination switches provide a direct replacement for power fused air and vacuum-in-oil switchgear. Some ideal applications include:
Transformer and Motor Protection — The three phase trip feature and high continuous current make the PLS switches ideal for protecting three phase motors and trans-former loads.
Loop Switching — Standard 600A loop switching is accomplished using field proven vacuum switching and solid dielectric insulation. Switching through 630A provides up to 12.5kA symmetric fault protection using resettable, electronically controlled vacuum interrupters. The vacuum interrupters also function as load break switches.
Residential and Fuse Replacement — The single phase trip feature of the PLT switches makes them ideal for pro-tecting single phase motors and transformer loads.
Access Options — Trident switches are available in a Front Access design, with operating handles and bushings on the same side of the switch, and a Front/Back Access design, with operating handles and bushings on both sides of the switch.
additional featuresVisible Break — The load break and three phase fault interrupter ways are available with G&W’s SafeVu feature, which provides an integrated visible break disconnect switch in series with the vacuum interrupter. This eliminates the need to remove elbows or use externally mounted link-age systems to provide a visible open. Switches equipped with the SafeVu feature incorporate redundant mechanical interlocks to ensure the load break switch is open prior to the operation of the visible break switch.
testingTrident switches are designed and tested to applicable stan-dards including IEEE C37.74 (IEEE C37.71 and C37.72), IEEE 386, IEC 60265, IEEE 592, and IEEE C57.12.28. All fault interrupter devices have passed IEEE C37.60. Trident switches are RUS accepted.
Fully encapsulated current transformers provide power and sensing for G&W’s Vacuum Interrupter controls. The con-trols emulate the most common time current curves (TCC) for power fuses, mechanical relays, and fuse links. Control options include Ground Fault (Phase Imbalance), Time De-lays, and Inrush Restraint (Cold Load Pickup).
Multi-way Trident Solid Dielectric Switches
G & W E L E C T R I C P A G E 9
features and Benefits
Features Benefits
Epoxy Insulation (No oil or SF6, and true dead-front design)
No maintenance or monitoring system necessary, lowest total life cycle costs
Dead-front design provides increased operator safety by eliminating all exposed live parts
Epoxy is inert, environmentally friendly, with no EPA usage restrictions
Resettable Vacuum Interrupter Mechanism No fuses or fuse links to stock and replace
Integral self-powered overcurrent protection available Integrated solution with fully encapsulated current transformers and no external power source or PT required
Load Break Ratings
Voltage Class 15kV 1,2 25kV 2 35kV 3
Max System Voltage 15.5kV 27kV 38kV
BIL Impulse 110kV 4 125kV 150kV
Continuous Current 630A 630A 630A
Load Break Current 630A 630A 630A
AC Withstand, 1 minute 35kV 60kV 70kVAC Withstand,
Production, 1 minute 34kV 40kV 50kV
DC Withstand, 15 minutes 53kV 78kV 103kV
Momentary Current, RMS, asym 20kA 20kA 20kA
Fault-Close 3-times, asym 20kA 20kA 20kA
1 Second Current, sym 12.5kA 12.5kA 12.5kALoad Break Switch
Mechanical Operations 2,000 2,000 2,000
Fault Interrupting Ratings
Voltage Class 15kV 1,2 25kV 2 35kV 3
Max System Voltage 15.5kV 27kV 38kV
BIL Impulse 110kV 4 125kV 150kV
Continuous Current 630A 630A 630A
AC Withstand, 1 minute 35kV 60kV 70kVAC Withstand,
Production, 1 minute 34kV 40kV 50kV
DC Withstand, 15 minutes 53kV 78kV 103kV
Fault Interrupting Current, sym 12.5kA 12.5kA 12.5kA
Vacuum Interrupter Mechanical Operations 2,000 2,000 2,000
ratingsThe switch is designed, tested and built per IEEE C37.74 for load break switching, IEEE C37.60 for fault interrupting, IEEE 386 for bushing specification, and IEC 60529 for environmental protection rating. Certified test reports are available.
Percent of Maximum
Interrupting Rating
Approximate Interrupting
Current, Amps
Number of Fault
Interruptions
15-20%45-55%
90-100%
2,0006,000
12,500
445616
Total number of Fault Interruptions: 116
IEEE C37.60 Fault Interrupting Duty
(1) Integrated visible break available on 15kV load break and three phase fault interrupters. (PLS-FA and PLS-FB
configurations.)(2) 15kV and 25kV class available for single phase fault
interrupters (PLT-FA and PLT-FB configurations) (3) 35kV class available for PLS-FB configurations. (4) BIL impulse rating is 95kV when using integrated visible
break feature.
Multi-way Trident Solid Dielectric Switches
G & W E L E C T R I C P A G E 1 0
Depth= 42in (1067mm) 45in (1143mm) with SafeVu options with standard 24” cable compartment
Height = 59 in (1494 mm) with standard 24” Bushing height.
Dimensions are approximate. Do not use for construction.
pls-fa sWitCH seriesModel One-line
DiagramVoltage
(kv) Catalog NumberApproximate
WidthInches (mm)
Weightlbs (kg)
615
PLS32-376-12-6FA 80 (2040) 2300 (1100)
PLS32-376-12-6FAVU* 103 (2620) 2500 (1200)
25 PLS32-386-12-6FA 80 (2040) 2300 (1100)
715
PLS31-376-12-7FA 80 (2040) 2300 (1100)
PLS31-376-12-7FAVU* 103 (2620) 2500 (1200)
25 PLS31-386-12-7FA 80 (2040) 2300 (1100)
915
PLS42-376-12-9FA 106 (2700) 2400 (1100)
PLS42-376-12-9FAVU* 132 (3360) 2800 (1300)
25 PLS42-386-12-9FA 106 (2700) 2400 (1100)
1015
PL44-376-20-10FA 106 (2700) 2400 (1100)
PL44-376-20-10FAVU* 132 (3360) 2800 (1300)
25 PL44-386-20-10FA 106 (2700) 2400 (1100)
1115
PLS43-376-12-11FA 106 (2700) 2400 (1100)
PLS43-376-12-11FAVU* 132 (3360) 2800 (1300)
25 PLS43-386-12-11FA 106 (2700) 2400 (1100)
1215
PLS41-376-12-12FA 106 (2700) 2400 (1100)
PLS41-376-12-12FAVU* 132 (3360) 2800 (1300)
25 PLS41-386-12-12FA 106 (2700) 2400 (1100)
1315
PL33-376-20-13FA 80 (2040) 2300 (1100)
PL33-376-20-13FAVU* 103 (2620) 2500 (1200)
25 PL33-386-20-13FA 80 (2040) 2300 (1100)
4015
PS40-376-12-40FA 106 (2700) 2400 (1100)
PS40-376-12-40FAVU* 132 (3360) 2800 (1300)
25 PS40-386-12-40FA 106 (2700) 2400 (1100)
5015
PS50-376-12-50FA 130 (3310) 2600 (1200)
PS50-376-12-50FAVU* 162 (4120) 3000 (1400)
25 PS50-386-12-50FA 130 (3310) 2600 (1200)
5115
PLS51-376-12-51FA 130 (3310) 2600 (1200)
PLS51-376-12-51FAVU* 162 (4120) 3000 (1400)
25 PLS51-386-12-51FA 130 (3310) 2600 (1200)
5215
PLS52-376-12-52FA 130 (3310) 2600 (1200)
PLS52-376-12-52FAVU* 162 (4120) 3000 (1400)
25 PLS52-386-12-52FA 130 (3310) 2600 (1200)
*VU indicates the switch includes the SafeVu integrated visible break.
Front Access
Visit gwelec.com/specs.html for electronic versions of guide specifications.
Thisd
rawing
and t
he in
forma
tion t
he
G&W ELECTRIC Co.
* ALL PRIMARY DIMENSIONS ARE IN INCHES. ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
10.86[276]
2.19[56]
84.0[2135]
ADJUSTABLEENCLOSURE
MOUNTING
37.8[960]
ADJUSTABLEENCLOSURE
MOUNTING44.00
[1118]
94.38[2397]
8.27[210]
22.00[559]
4.00[102]
3.00[76]
92.13[2340]
101.59[2580]
ENCLOSUREMOUNTING
2.19[56]TYP.
50.38[1280]
SWITCH ELECTRICAL INFORMATIONSEE NOTES FOR LIMITATIONS
ALL WAYSMAXIMUM DESIGN VOLTAGE 15.5 KVIMPULSE LEVEL 1 BIL 110 KVAC 1 MIN. WITHSTAND 34 KVDC 15 MIN. WITHSTAND 53 KVCURRENT CONTINUOUS 630 AMPCURRENT INTERRUPTING 630 AMPMOMENTARY CURRENT RMS ASYM. 20 KAMAKING CURRENT RMS ASYM. 20 KA1 SEC. RATING RMS SYM. 12.5 KA
THREE LINE DIAGRAM
SWITCH WEIGHT 2200 LBS/ 1000 KG
3D M
ODEL
MC
ERRO
RS 0
DRAW
ING
MC
ERRO
RS 0
3D M
ODEL
LAST
CHE
CKED
Wed
Nov 0
9 201
1 18:2
5:06 G
MT-0
600
3_PH
ASE_
TRID
_S_S
IDE_
HAND
LE_C
UST
DRAW
ING
LAST
CHE
CKED
Wed
Nov
09 20
11 20
:14:59
GM
T-060
0 STA
NDAR
DSH
EET 1
of 2
1 of 2SHEET:SCALE:DATE:APPR BY:
REVDRAWING NO.
D97LL FF00 L00Nov-09-11DATE:N.A.DRAWN BY:
PA13-SL1SL1S21S21CAT. NO.:
FOUR WAY SOLID DIELECTRIC SWITCH
PA13-SL1SL1S21S21
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
NOTES:
1. ALL SWITCHED WAYS EQUIPPED WITH INTERNAL SPRING OPERATOR AND EXTERNAL PROVISIONS FOR PADLOCKING IN ALL POSITIONS
2. UNFINISHED 304 STAINLESS STEEL MOUNTING PLATE WITH BOLTED STAINLESS MECHANISM COVER FINISHED ASA 70 LIGHT GRAY.
3. SWITCH ELECTRICAL RATINGS MAY BE REDUCED BY THE CHOICE OF ENTRANCES.
4. GALVANIZED STEEL ENCLOSURE FINISHED MUNSELL 7GY3.29/1.5 PADMOUNT GREEN.
5. ENCLOSURE IS DESIGNED PER APPLICABLE SECTIONS OF ANSI/IEEE C37.72 AND ANSI C57.12.28. DRAWING IS TYPICAL AND SHOWS OVERALL DIMENSIONS ONLY. CONSTRUCTION DETAILS MAY VARY FROM THOSE DEPICTED.
6. SWITCH IS EQUIPPED WITH NEMA 4X TYPE 2, 15-300 AMP ELECTRONIC CONTROLS ON WAYS 3 & 4.
7. 200 AMP RATED DEEPWELL BUSHINGS WILL REDUCE THE ELECTRICAL RATINGS TO 200 AMP CONTINUOUS AND 15 KA ASYM. FOR 10 CYCLES.
8. SWITCH IS EQUIPPED WITH 2 FORM C AUXILIARY CONTACTS ON ALL WAYS. BOTH FORM C CONTACTS FROM ALL 4 WAYS ARE TERMINATED INTO THE NEMA 4X JUNCTION BOX FOR CUSTOMER USE.
TYPE 2 15-300A
TYPE 2 15-300A
SEE ENCLOSUREMOUNTINGDETAIL "A"
SHOWING OVERALL DIMENSIONSAND MAXIMUM DIMENSIONS
WHEN ENCLOSURE DOORS ARE OPEN
PLAN VIEW
SHOWING ELECTRONIC CABLE OUTPUT
CABLE TRAININGOUTLINE
ALL DOORS EQUIPPEDWITH PENTA HEADBOLT AND THREEPOINT LATCHING
BOTTOM VIEWELECTRONICCABLE OUTPUTWAYS 3 & 4(CABLE CUTTO LENGTH)
ENTRANCESWAY
1
2
3
4
15.5KV 630AMP 110KV BIL APPARATUS BUSHING **
15.5KV 200AMP 110KV BIL DEEPWELL BUSHING **
15.5KV 200AMP 110KV BIL DEEPWELL BUSHING **
** ELBOWS AND INSERTS PROVIDED BY OTHERS AND MAY HAVE REDUCED ELECTRICAL RATINGS.
15.5KV 630AMP 110KV BIL APPARATUS BUSHING **
CONCRETEPAD
.25" STAINLESS STEELANCHOR BRACKETWITH .875" X 1.125" OVALSUPPLIED BY G&W
.625" DIA.HARDWARE(4)-SUPPLIEDBY USER
2.1956MMTYP.
1.50
38M
MM
IN.
ENCLOSURE
ENCLOSUREMOUNTINGDETAIL "A"
DATE G&W NO.
CUSTOMER
ORDER NO.
FOR RECORD
FOR APPROVAL-NO MORE WORK TO BE DONE UNTIL APPROVAL IS RECEIVED
PRINT IDENTIFICATION
ITEM NO.
ELECTRONICS
WAY1: WAY2:
WAY4:WAY3:
Thisd
rawing
and t
he in
forma
tion t
he
G&W ELECTRIC Co.
* ALL PRIMARY DIMENSIONS ARE IN INCHES. ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
10.86[276]
2.19[56]
84.0[2135]
ADJUSTABLEENCLOSURE
MOUNTING
37.8[960]
ADJUSTABLEENCLOSURE
MOUNTING44.00
[1118]
94.38[2397]
8.27[210]
22.00[559]
4.00[102]
3.00[76]
92.13[2340]
101.59[2580]
ENCLOSUREMOUNTING
2.19[56]TYP.
50.38[1280]
SWITCH ELECTRICAL INFORMATIONSEE NOTES FOR LIMITATIONS
ALL WAYSMAXIMUM DESIGN VOLTAGE 15.5 KVIMPULSE LEVEL 1 BIL 110 KVAC 1 MIN. WITHSTAND 34 KVDC 15 MIN. WITHSTAND 53 KVCURRENT CONTINUOUS 630 AMPCURRENT INTERRUPTING 630 AMPMOMENTARY CURRENT RMS ASYM. 20 KAMAKING CURRENT RMS ASYM. 20 KA1 SEC. RATING RMS SYM. 12.5 KA
THREE LINE DIAGRAM
SWITCH WEIGHT 2200 LBS/ 1000 KG
3D M
ODEL
MC
ERRO
RS 0
DRAW
ING
MC
ERRO
RS 0
3D M
ODEL
LAST
CHE
CKED
Wed
Nov 0
9 201
1 18:2
5:06 G
MT-0
600
3_PH
ASE_
TRID
_S_S
IDE_
HAND
LE_C
UST
DRAW
ING
LAST
CHE
CKED
Wed
Nov
09 20
11 20
:14:59
GM
T-060
0 STA
NDAR
DSH
EET 1
of 2
1 of 2SHEET:SCALE:DATE:APPR BY:
REVDRAWING NO.
D97LL FF00 L00Nov-09-11DATE:N.A.DRAWN BY:
PA13-SL1SL1S21S21CAT. NO.:
FOUR WAY SOLID DIELECTRIC SWITCH
PA13-SL1SL1S21S21
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
NOTES:
1. ALL SWITCHED WAYS EQUIPPED WITH INTERNAL SPRING OPERATOR AND EXTERNAL PROVISIONS FOR PADLOCKING IN ALL POSITIONS
2. UNFINISHED 304 STAINLESS STEEL MOUNTING PLATE WITH BOLTED STAINLESS MECHANISM COVER FINISHED ASA 70 LIGHT GRAY.
3. SWITCH ELECTRICAL RATINGS MAY BE REDUCED BY THE CHOICE OF ENTRANCES.
4. GALVANIZED STEEL ENCLOSURE FINISHED MUNSELL 7GY3.29/1.5 PADMOUNT GREEN.
5. ENCLOSURE IS DESIGNED PER APPLICABLE SECTIONS OF ANSI/IEEE C37.72 AND ANSI C57.12.28. DRAWING IS TYPICAL AND SHOWS OVERALL DIMENSIONS ONLY. CONSTRUCTION DETAILS MAY VARY FROM THOSE DEPICTED.
6. SWITCH IS EQUIPPED WITH NEMA 4X TYPE 2, 15-300 AMP ELECTRONIC CONTROLS ON WAYS 3 & 4.
7. 200 AMP RATED DEEPWELL BUSHINGS WILL REDUCE THE ELECTRICAL RATINGS TO 200 AMP CONTINUOUS AND 15 KA ASYM. FOR 10 CYCLES.
8. SWITCH IS EQUIPPED WITH 2 FORM C AUXILIARY CONTACTS ON ALL WAYS. BOTH FORM C CONTACTS FROM ALL 4 WAYS ARE TERMINATED INTO THE NEMA 4X JUNCTION BOX FOR CUSTOMER USE.
TYPE 2 15-300A
TYPE 2 15-300A
SEE ENCLOSUREMOUNTINGDETAIL "A"
SHOWING OVERALL DIMENSIONSAND MAXIMUM DIMENSIONS
WHEN ENCLOSURE DOORS ARE OPEN
PLAN VIEW
SHOWING ELECTRONIC CABLE OUTPUT
CABLE TRAININGOUTLINE
ALL DOORS EQUIPPEDWITH PENTA HEADBOLT AND THREEPOINT LATCHING
BOTTOM VIEWELECTRONICCABLE OUTPUTWAYS 3 & 4(CABLE CUTTO LENGTH)
ENTRANCESWAY
1
2
3
4
15.5KV 630AMP 110KV BIL APPARATUS BUSHING **
15.5KV 200AMP 110KV BIL DEEPWELL BUSHING **
15.5KV 200AMP 110KV BIL DEEPWELL BUSHING **
** ELBOWS AND INSERTS PROVIDED BY OTHERS AND MAY HAVE REDUCED ELECTRICAL RATINGS.
15.5KV 630AMP 110KV BIL APPARATUS BUSHING **
CONCRETEPAD
.25" STAINLESS STEELANCHOR BRACKETWITH .875" X 1.125" OVALSUPPLIED BY G&W
.625" DIA.HARDWARE(4)-SUPPLIEDBY USER
2.1956MMTYP.
1.50
38M
MM
IN.
ENCLOSURE
ENCLOSUREMOUNTINGDETAIL "A"
DATE G&W NO.
CUSTOMER
ORDER NO.
FOR RECORD
FOR APPROVAL-NO MORE WORK TO BE DONE UNTIL APPROVAL IS RECEIVED
PRINT IDENTIFICATION
ITEM NO.
ELECTRONICS
WAY1: WAY2:
WAY4:WAY3:
SIDE
FRONT
WIDTH
DEPTH44”
(1118mm)
HEIGHT59”
(1494mm)
G & W E L E C T R I C P A G E 1 1
Depth= 42in (1067mm) 45in (1143mm) with SafeVu options with standard 24” cable compartment
Height = 59 in (1494 mm) with standard 24” Bushing height.
Dimensions are approximate. Do not use for construction.
pls-fa sWitCH series
*VU indicates the switch includes the SafeVu integrated visible break.
Model One-line Diagram
Voltage (kv) Catalog Number
ApproximateWidth
Inches (mm)Weightlbs (kg)
5315
PLS53-376-12-53FA 130 (3310) 2600 (1200)
PLS53-376-12-53FAVU* 162 (4120) 3000 (1400)
25 PLS53-386-12-53FA 130 (3310) 2600 (1200)
5415
PLS54-376-12-54FA 130 (3310) 2600 (1200)
PLS54-376-12-54FAVU* 162 (4120) 3000 (1400)
25 PLS54-386-12-54FA 130 (3310) 2600 (1200)
5515
PL55-376-20-55FA 130 (3310) 2600 (1200)
PL55-376-20-55FAVU* 162 (4120) 3000 (1400)
25 PL55-386-20-55FA 130 (3310) 2600 (1200)
6015
PS60-376-12-60FA 155 (3940) 2800 (1300)
PS60-376-12-60FAVU* 197 (5010) 3300 (1500)
25 PS60-386-12-60FA 155 (3940) 2800 (1300)
6115
PLS61-376-12-61FA 155 (3940) 2800 (1300)
PLS61-376-12-61FAVU* 197 (5010) 3300 (1500)
25 PLS61-386-12-61FA 155 (3940) 2800 (1300)
6215
PLS62-376-12-62FA 155 (3940) 2800 (1300)
PLS62-376-12-62FAVU* 197 (5010) 3300 (1500)
25 PLS62-386-12-62FA 155 (3940) 2800 (1300)
6315
PLS63-376-12-63FA 155 (3940) 2800 (1300)
PLS63-376-12-63FAVU* 197 (5010) 3300 (1500)
25 PLS63-386-12-63FA 155 (3940) 2800 (1300)
6415
PLS64-376-12-64FA 155 (3940) 2800 (1300)
PLS64-376-12-64FAVU* 197 (5010) 3300 (1500)
25 PLS64-386-12-64FA 155 (3940) 2800 (1300)
6515
PLS65-376-12-65FA 155 (3940) 2800 (1300)
PLS65-376-12-65FAVU* 197 (5010) 3300 (1500)
25 PLS65-386-12-65FA 155 (3940) 2800 (1300)
6615
PL66-376-20-66FA 155 (3940) 2800 (1300)
PL66-376-20-66FAVU* 197 (5010) 3300 (1500)
25 PL66-386-20-66FA 155 (3940) 2800 (1300)
Front Access
Visit gwelec.com/specs.html for electronic versions of guide specifications.
DEPTH44”
(1118mm)
Thisd
rawing
and t
he in
forma
tion t
he
G&W ELECTRIC Co.
* ALL PRIMARY DIMENSIONS ARE IN INCHES. ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
10.86[276]
2.19[56]
84.0[2135]
ADJUSTABLEENCLOSURE
MOUNTING
37.8[960]
ADJUSTABLEENCLOSURE
MOUNTING44.00
[1118]
94.38[2397]
8.27[210]
22.00[559]
4.00[102]
3.00[76]
92.13[2340]
101.59[2580]
ENCLOSUREMOUNTING
2.19[56]TYP.
50.38[1280]
SWITCH ELECTRICAL INFORMATIONSEE NOTES FOR LIMITATIONS
ALL WAYSMAXIMUM DESIGN VOLTAGE 15.5 KVIMPULSE LEVEL 1 BIL 110 KVAC 1 MIN. WITHSTAND 34 KVDC 15 MIN. WITHSTAND 53 KVCURRENT CONTINUOUS 630 AMPCURRENT INTERRUPTING 630 AMPMOMENTARY CURRENT RMS ASYM. 20 KAMAKING CURRENT RMS ASYM. 20 KA1 SEC. RATING RMS SYM. 12.5 KA
THREE LINE DIAGRAM
SWITCH WEIGHT 2200 LBS/ 1000 KG
3D M
ODEL
MC
ERRO
RS 0
DRAW
ING
MC
ERRO
RS 0
3D M
ODEL
LAST
CHE
CKED
Wed
Nov 0
9 201
1 18:2
5:06 G
MT-0
600
3_PH
ASE_
TRID
_S_S
IDE_
HAND
LE_C
UST
DRAW
ING
LAST
CHE
CKED
Wed
Nov
09 20
11 20
:14:59
GM
T-060
0 STA
NDAR
DSH
EET 1
of 2
1 of 2SHEET:SCALE:DATE:APPR BY:
REVDRAWING NO.
D97LL FF00 L00Nov-09-11DATE:N.A.DRAWN BY:
PA13-SL1SL1S21S21CAT. NO.:
FOUR WAY SOLID DIELECTRIC SWITCH
PA13-SL1SL1S21S21
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
NOTES:
1. ALL SWITCHED WAYS EQUIPPED WITH INTERNAL SPRING OPERATOR AND EXTERNAL PROVISIONS FOR PADLOCKING IN ALL POSITIONS
2. UNFINISHED 304 STAINLESS STEEL MOUNTING PLATE WITH BOLTED STAINLESS MECHANISM COVER FINISHED ASA 70 LIGHT GRAY.
3. SWITCH ELECTRICAL RATINGS MAY BE REDUCED BY THE CHOICE OF ENTRANCES.
4. GALVANIZED STEEL ENCLOSURE FINISHED MUNSELL 7GY3.29/1.5 PADMOUNT GREEN.
5. ENCLOSURE IS DESIGNED PER APPLICABLE SECTIONS OF ANSI/IEEE C37.72 AND ANSI C57.12.28. DRAWING IS TYPICAL AND SHOWS OVERALL DIMENSIONS ONLY. CONSTRUCTION DETAILS MAY VARY FROM THOSE DEPICTED.
6. SWITCH IS EQUIPPED WITH NEMA 4X TYPE 2, 15-300 AMP ELECTRONIC CONTROLS ON WAYS 3 & 4.
7. 200 AMP RATED DEEPWELL BUSHINGS WILL REDUCE THE ELECTRICAL RATINGS TO 200 AMP CONTINUOUS AND 15 KA ASYM. FOR 10 CYCLES.
8. SWITCH IS EQUIPPED WITH 2 FORM C AUXILIARY CONTACTS ON ALL WAYS. BOTH FORM C CONTACTS FROM ALL 4 WAYS ARE TERMINATED INTO THE NEMA 4X JUNCTION BOX FOR CUSTOMER USE.
TYPE 2 15-300A
TYPE 2 15-300A
SEE ENCLOSUREMOUNTINGDETAIL "A"
SHOWING OVERALL DIMENSIONSAND MAXIMUM DIMENSIONS
WHEN ENCLOSURE DOORS ARE OPEN
PLAN VIEW
SHOWING ELECTRONIC CABLE OUTPUT
CABLE TRAININGOUTLINE
ALL DOORS EQUIPPEDWITH PENTA HEADBOLT AND THREEPOINT LATCHING
BOTTOM VIEWELECTRONICCABLE OUTPUTWAYS 3 & 4(CABLE CUTTO LENGTH)
ENTRANCESWAY
1
2
3
4
15.5KV 630AMP 110KV BIL APPARATUS BUSHING **
15.5KV 200AMP 110KV BIL DEEPWELL BUSHING **
15.5KV 200AMP 110KV BIL DEEPWELL BUSHING **
** ELBOWS AND INSERTS PROVIDED BY OTHERS AND MAY HAVE REDUCED ELECTRICAL RATINGS.
15.5KV 630AMP 110KV BIL APPARATUS BUSHING **
CONCRETEPAD
.25" STAINLESS STEELANCHOR BRACKETWITH .875" X 1.125" OVALSUPPLIED BY G&W
.625" DIA.HARDWARE(4)-SUPPLIEDBY USER
2.1956MMTYP.
1.50
38M
MM
IN.
ENCLOSURE
ENCLOSUREMOUNTINGDETAIL "A"
DATE G&W NO.
CUSTOMER
ORDER NO.
FOR RECORD
FOR APPROVAL-NO MORE WORK TO BE DONE UNTIL APPROVAL IS RECEIVED
PRINT IDENTIFICATION
ITEM NO.
ELECTRONICS
WAY1: WAY2:
WAY4:WAY3:
Thisd
rawing
and t
he in
forma
tion t
he
G&W ELECTRIC Co.
* ALL PRIMARY DIMENSIONS ARE IN INCHES. ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
10.86[276]
2.19[56]
84.0[2135]
ADJUSTABLEENCLOSURE
MOUNTING
37.8[960]
ADJUSTABLEENCLOSURE
MOUNTING44.00
[1118]
94.38[2397]
8.27[210]
22.00[559]
4.00[102]
3.00[76]
92.13[2340]
101.59[2580]
ENCLOSUREMOUNTING
2.19[56]TYP.
50.38[1280]
SWITCH ELECTRICAL INFORMATIONSEE NOTES FOR LIMITATIONS
ALL WAYSMAXIMUM DESIGN VOLTAGE 15.5 KVIMPULSE LEVEL 1 BIL 110 KVAC 1 MIN. WITHSTAND 34 KVDC 15 MIN. WITHSTAND 53 KVCURRENT CONTINUOUS 630 AMPCURRENT INTERRUPTING 630 AMPMOMENTARY CURRENT RMS ASYM. 20 KAMAKING CURRENT RMS ASYM. 20 KA1 SEC. RATING RMS SYM. 12.5 KA
THREE LINE DIAGRAM
SWITCH WEIGHT 2200 LBS/ 1000 KG
3D M
ODEL
MC
ERRO
RS 0
DRAW
ING
MC
ERRO
RS 0
3D M
ODEL
LAST
CHE
CKED
Wed
Nov 0
9 201
1 18:2
5:06 G
MT-0
600
3_PH
ASE_
TRID
_S_S
IDE_
HAND
LE_C
UST
DRAW
ING
LAST
CHE
CKED
Wed
Nov
09 20
11 20
:14:59
GM
T-060
0 STA
NDAR
DSH
EET 1
of 2
1 of 2SHEET:SCALE:DATE:APPR BY:
REVDRAWING NO.
D97LL FF00 L00Nov-09-11DATE:N.A.DRAWN BY:
PA13-SL1SL1S21S21CAT. NO.:
FOUR WAY SOLID DIELECTRIC SWITCH
PA13-SL1SL1S21S21
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
NOTES:
1. ALL SWITCHED WAYS EQUIPPED WITH INTERNAL SPRING OPERATOR AND EXTERNAL PROVISIONS FOR PADLOCKING IN ALL POSITIONS
2. UNFINISHED 304 STAINLESS STEEL MOUNTING PLATE WITH BOLTED STAINLESS MECHANISM COVER FINISHED ASA 70 LIGHT GRAY.
3. SWITCH ELECTRICAL RATINGS MAY BE REDUCED BY THE CHOICE OF ENTRANCES.
4. GALVANIZED STEEL ENCLOSURE FINISHED MUNSELL 7GY3.29/1.5 PADMOUNT GREEN.
5. ENCLOSURE IS DESIGNED PER APPLICABLE SECTIONS OF ANSI/IEEE C37.72 AND ANSI C57.12.28. DRAWING IS TYPICAL AND SHOWS OVERALL DIMENSIONS ONLY. CONSTRUCTION DETAILS MAY VARY FROM THOSE DEPICTED.
6. SWITCH IS EQUIPPED WITH NEMA 4X TYPE 2, 15-300 AMP ELECTRONIC CONTROLS ON WAYS 3 & 4.
7. 200 AMP RATED DEEPWELL BUSHINGS WILL REDUCE THE ELECTRICAL RATINGS TO 200 AMP CONTINUOUS AND 15 KA ASYM. FOR 10 CYCLES.
8. SWITCH IS EQUIPPED WITH 2 FORM C AUXILIARY CONTACTS ON ALL WAYS. BOTH FORM C CONTACTS FROM ALL 4 WAYS ARE TERMINATED INTO THE NEMA 4X JUNCTION BOX FOR CUSTOMER USE.
TYPE 2 15-300A
TYPE 2 15-300A
SEE ENCLOSUREMOUNTINGDETAIL "A"
SHOWING OVERALL DIMENSIONSAND MAXIMUM DIMENSIONS
WHEN ENCLOSURE DOORS ARE OPEN
PLAN VIEW
SHOWING ELECTRONIC CABLE OUTPUT
CABLE TRAININGOUTLINE
ALL DOORS EQUIPPEDWITH PENTA HEADBOLT AND THREEPOINT LATCHING
BOTTOM VIEWELECTRONICCABLE OUTPUTWAYS 3 & 4(CABLE CUTTO LENGTH)
ENTRANCESWAY
1
2
3
4
15.5KV 630AMP 110KV BIL APPARATUS BUSHING **
15.5KV 200AMP 110KV BIL DEEPWELL BUSHING **
15.5KV 200AMP 110KV BIL DEEPWELL BUSHING **
** ELBOWS AND INSERTS PROVIDED BY OTHERS AND MAY HAVE REDUCED ELECTRICAL RATINGS.
15.5KV 630AMP 110KV BIL APPARATUS BUSHING **
CONCRETEPAD
.25" STAINLESS STEELANCHOR BRACKETWITH .875" X 1.125" OVALSUPPLIED BY G&W
.625" DIA.HARDWARE(4)-SUPPLIEDBY USER
2.1956MMTYP.
1.50
38M
MM
IN.
ENCLOSURE
ENCLOSUREMOUNTINGDETAIL "A"
DATE G&W NO.
CUSTOMER
ORDER NO.
FOR RECORD
FOR APPROVAL-NO MORE WORK TO BE DONE UNTIL APPROVAL IS RECEIVED
PRINT IDENTIFICATION
ITEM NO.
ELECTRONICS
WAY1: WAY2:
WAY4:WAY3:
SIDE
FRONT
WIDTH
HEIGHT59”
(1494mm)
G & W E L E C T R I C P A G E 1 2
Model One-line Diagram
Voltage (kv) Catalog Number
ApproximateWidth
Inches (mm)Weightlbs (kg)
615
PLT32-376-12-6FA 80 (2040) 2400 (1100)
PLT32-376-12-6FAVU* 103 (2620) 2600 (1200)
25 PLT32-386-12-6FA 80 (2040) 2400 (1100)
715
PLT31-376-12-7FA 80 (2040) 2500 (1200)
PLT31-376-12-7FAVU* 103 (2620) 2600 (1200)
25 PLT31-386-12-7FA 80 (2040) 2500 (1200)
915
PLT42-376-12-9FA 106 (2700) 2700 (1300)
PLT42-376-12-9FAVU* 132 (3360) 2800 (1300)
25 PLT42-386-12-9FA 106 (2700) 2700 (1300)
1115
PLT43-376-12-11FA 106 (2700) 2500 (1200)
PLT43-376-12-11FAVU* 132 (3360) 2800 (1300)
25 PLT43-386-12-11FA 106 (2700) 2500 (1200)
1215
PLT41-376-12-12FA 106 (2700) 2800 (1300)
PLT41-376-12-12FAVU* 132 (3360) 2900 (1400)
25 PLT41-386-12-12FA 106 (2700) 2800 (1300)
4015
PT40-376-12-40FA 106 (2700) 2300 (1100)
PT40-376-12-40FAVU* 132 (3360) 2200 (1000)
25 PT40-386-12-40FA 106 (2700) 2300 (1100)
5015 PT50-376-12-50FA 130 (3310) 3200 (1500)
25 PT50-386-12-50FA 130 (3310) 3200 (1500)
5115
PLT51-376-12-51FA 130 (3310) 3000 (1400)
PLT51-376-12-51FAVU* 162 (4120) 3100 (1400)
25 PLT51-386-12-51FA 130 (3310) 3000 (1400)
5215
PLT52-376-12-52FA 130 (3310) 3000 (1400)
PLT52-376-12-52FAVU* 162 (4120) 3100 (1400)
25 PLT52-386-12-52FA 130 (3310) 3000 (1400)
5315
PLT53-376-12-53FA 130 (3310) 3000 (1400)
PLT53-376-12-53FAVU* 162 (4120) 3000 (1400)
25 PLT53-386-12-53FA 130 (3310) 3000 (1400)
Depth= 42in (1067mm) 45in (1143mm) with SafeVu options with standard 24” cable compartment
Height = 59 in (1494 mm) with 24” Bushing height.
*VU indicates the switch includes the SafeVu integrated visible break.
Dimensions are approximate. Do not use for construction.
plt-fa sWitCH series
Front Access
Visit gwelec.com/specs.html for electronic versions of guide specifications.
Thisd
rawing
and t
he in
forma
tion t
hereo
n are
and r
emain
the
prop
erty
of G
&Wan
d are
not t
o bec
opied
, repr
oduc
ed o
r dicl
osed
to ot
hers
with
out t
heex
pres
sed w
ritten
cons
ento
f G&W
.
G&W ELECTRIC Co.
* ALL PRIMARY DIMENSIONS ARE IN INCHES. ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
SWITCH ELECTRICAL INFORMATIONSEE NOTES FOR LIMITATIONS
WAY 1 WAYS 2 & 3MAXIMUM DESIGN VOLTAGE 15.5 KV 15.5 KVIMPULSE LEVEL 1 BIL 110 KV 110 KVAC 1 MIN. WITHSTAND 34 KV 34 KVDC 15 MIN. WITHSTAND 53 KV 53 KVCURRENT CONTINUOUS 630 AMP 630 AMPCURRENT INTERRUPTING 630 AMP 16 KAMOMENTARY CURRENT RMS ASYM. 20 KAMAKING CURRENT RMS ASYM. 25.6 KA1 SEC. RATING RMS SYM. 12.5 KA
SWITCH WEIGHT 2200 LBS/ 998 KG
D97
LF F
000
R00
DWG.
NO.
:3D
MOD
EL M
C ER
RORS
0DR
AWIN
G M
C ER
RORS
03D
MOD
EL LA
ST C
HECK
ED Fr
i Sep
26 20
14 15
:43:14
GM
T-060
0 ST
ANDA
RDDR
AWIN
G LA
ST C
HECK
ED F
ri Se
p 26
2014
15:44
:31 G
MT-0
600 S
TAND
ARD
SHEE
T 1 of
2
1 of 2SHEET:SCALE:DATE:APPR BY:
REVDRAWING NO.
D97LF F000 R009-26-14DATE:NMDDRAWN BY:
PA13-SL1T11T11CAT. NO.:
THREE WAY SOLID DIELECTRIC SWITCHPAD 0649A
PA13-SL1T11T11
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
REVISIONS
DATE
DRAWING REVIEW TEAM
PLAN VIEWSHOWING OVERALL DIMENSIONS AND MAXIMUM
DIMENSIONS WHEN ENCLOSURE DOORS ARE OPEN
BOTTOM VIEW (WAYS 2 & 3)SHOWING CABLE FEEDTHRU
BOTTOM VIEW (WAY 1)SHOWING CABLE FEEDTHRU
ENTRANCESWAY
1
2
3
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
15.5KV 110KV BIL 200A BUSHING WELL PER IEEE 386 FIGURE 3
15.5KV 110KV BIL 200A BUSHING WELL PER IEEE 386 FIGURE 3
CONCRETEPAD
.25" STAINLESS STEELANCHOR BRACKETWITH .875" X 1.125"SLOTTED HOLESUPPLIED BY G&W
.625" DIA.HARDWARE(4)-SUPPLIEDBY USER
2.1956MMTYP.
1.50
38M
MM
IN.
ENCLOSURE
ENCLOSUREMOUNTINGDETAIL "A"
DATE G&W NO.
CUSTOMER
ORDER NO.
FOR RECORD
FOR APPROVAL-NO MORE WORK TO BE DONE UNTIL APPROVAL IS RECEIVED
PRINT IDENTIFICATION
ITEM NO.
Thisd
rawing
and t
he in
forma
tion t
hereo
n are
and r
emain
the
prop
erty
of G
&Wan
d are
not t
o bec
opied
, repr
oduc
ed o
r dicl
osed
to ot
hers
with
out t
heex
pres
sed w
ritten
cons
ento
f G&W
.
G&W ELECTRIC Co.
* ALL PRIMARY DIMENSIONS ARE IN INCHES. ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
SWITCH ELECTRICAL INFORMATIONSEE NOTES FOR LIMITATIONS
WAY 1 WAYS 2 & 3MAXIMUM DESIGN VOLTAGE 15.5 KV 15.5 KVIMPULSE LEVEL 1 BIL 110 KV 110 KVAC 1 MIN. WITHSTAND 34 KV 34 KVDC 15 MIN. WITHSTAND 53 KV 53 KVCURRENT CONTINUOUS 630 AMP 630 AMPCURRENT INTERRUPTING 630 AMP 16 KAMOMENTARY CURRENT RMS ASYM. 20 KAMAKING CURRENT RMS ASYM. 25.6 KA1 SEC. RATING RMS SYM. 12.5 KA
SWITCH WEIGHT 2200 LBS/ 998 KG
D97
LF F
000
R00
DWG.
NO.
:3D
MOD
EL M
C ER
RORS
0DR
AWIN
G M
C ER
RORS
03D
MOD
EL LA
ST C
HECK
ED Fr
i Sep
26 20
14 15
:43:14
GM
T-060
0 ST
ANDA
RDDR
AWIN
G LA
ST C
HECK
ED F
ri Se
p 26
2014
15:44
:31 G
MT-0
600 S
TAND
ARD
SHEE
T 1 of
2
1 of 2SHEET:SCALE:DATE:APPR BY:
REVDRAWING NO.
D97LF F000 R009-26-14DATE:NMDDRAWN BY:
PA13-SL1T11T11CAT. NO.:
THREE WAY SOLID DIELECTRIC SWITCHPAD 0649A
PA13-SL1T11T11
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
REVISIONS
DATE
DRAWING REVIEW TEAM
PLAN VIEWSHOWING OVERALL DIMENSIONS AND MAXIMUM
DIMENSIONS WHEN ENCLOSURE DOORS ARE OPEN
BOTTOM VIEW (WAYS 2 & 3)SHOWING CABLE FEEDTHRU
BOTTOM VIEW (WAY 1)SHOWING CABLE FEEDTHRU
ENTRANCESWAY
1
2
3
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
15.5KV 110KV BIL 200A BUSHING WELL PER IEEE 386 FIGURE 3
15.5KV 110KV BIL 200A BUSHING WELL PER IEEE 386 FIGURE 3
CONCRETEPAD
.25" STAINLESS STEELANCHOR BRACKETWITH .875" X 1.125"SLOTTED HOLESUPPLIED BY G&W
.625" DIA.HARDWARE(4)-SUPPLIEDBY USER
2.1956MMTYP.
1.50
38M
MM
IN.
ENCLOSURE
ENCLOSUREMOUNTINGDETAIL "A"
DATE G&W NO.
CUSTOMER
ORDER NO.
FOR RECORD
FOR APPROVAL-NO MORE WORK TO BE DONE UNTIL APPROVAL IS RECEIVED
PRINT IDENTIFICATION
ITEM NO.
SIDE
FRONT
WIDTH
HEIGHT59”
(1494mm)
DEPTH44”
(1118mm)
G & W E L E C T R I C P A G E 1 3
Model One-line Diagram
Voltage (kv) Catalog Number
ApproximateWidth
Inches (mm)Weightlbs (kg)
5415
PLT54-376-12-54FA 130 (3310) 3000 (1400)
PLT54-376-12-54FAVU* 162 (4120) 3000 (1400)
25 PLT54-386-12-54FA 130 (3310) 3000 (1400)
6015 PT60-376-12-60FA 155 (3940) 3400 (1600)
25 PT60-386-12-60FA 155 (3940) 3400 (1600)
6115
PLT61-376-12-61FA 155 (3940) 3300 (1500)
PLT61-376-12-61FAVU* 197 (5010) 3400 (1600)
25 PLT61-386-12-61FA 155 (3940) 3300 (1500)
6215
PLT62-376-12-62FA 155 (3940) 3200 (1500)
PLT62-376-12-62FAVU* 197 (5010) 3400 (1600)
25 PLT62-386-12-62FA 155 (3940) 3200 (1500)
6315
PLT63-376-12-63FA 155 (3940) 3100 (1400)
PLT63-376-12-63FAVU* 197 (5010) 3400 (1600)
25 PLT63-386-12-63FA 155 (3940) 3100 (1400)
6415
PLT64-376-12-64FA 155 (3940) 3000 (1400)
PLT64-376-12-64FAVU* 197 (5010) 3300 (1500)
25 PLT64-386-12-64FA 155 (3940) 3000 (1400)
6515
PLT65-376-12-65FA 155 (3940) 2900 (1300)
PLT65-376-12-65FAVU* 197 (5010) 3300 (1500)
25 PLT65-386-12-65FA 155 (3940) 2900 (1300)Depth= 42in (1067mm) 45in (1143mm) with SafeVu options with standard 24” cable compartment
Height = 59 in (1494 mm) with 24” Bushing height.
Dimensions are approximate. Do not use for construction.
plt-fa sWitCH series
*VU indicates the switch includes the SafeVu integrated visible break.
Front Access
Visit gwelec.com/specs.html for electronic versions of guide specifications.
Thisd
rawing
and t
he in
forma
tion t
hereo
n are
and r
emain
the
prop
erty
of G
&Wan
d are
not t
o bec
opied
, repr
oduc
ed o
r dicl
osed
to ot
hers
with
out t
heex
pres
sed w
ritten
cons
ento
f G&W
.
G&W ELECTRIC Co.
* ALL PRIMARY DIMENSIONS ARE IN INCHES. ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
SWITCH ELECTRICAL INFORMATIONSEE NOTES FOR LIMITATIONS
WAY 1 WAYS 2 & 3MAXIMUM DESIGN VOLTAGE 15.5 KV 15.5 KVIMPULSE LEVEL 1 BIL 110 KV 110 KVAC 1 MIN. WITHSTAND 34 KV 34 KVDC 15 MIN. WITHSTAND 53 KV 53 KVCURRENT CONTINUOUS 630 AMP 630 AMPCURRENT INTERRUPTING 630 AMP 16 KAMOMENTARY CURRENT RMS ASYM. 20 KAMAKING CURRENT RMS ASYM. 25.6 KA1 SEC. RATING RMS SYM. 12.5 KA
SWITCH WEIGHT 2200 LBS/ 998 KG
D97
LF F
000
R00
DWG.
NO.
:3D
MOD
EL M
C ER
RORS
0DR
AWIN
G M
C ER
RORS
03D
MOD
EL LA
ST C
HECK
ED Fr
i Sep
26 20
14 15
:43:14
GM
T-060
0 ST
ANDA
RDDR
AWIN
G LA
ST C
HECK
ED F
ri Se
p 26
2014
15:44
:31 G
MT-0
600 S
TAND
ARD
SHEE
T 1 of
2
1 of 2SHEET:SCALE:DATE:APPR BY:
REVDRAWING NO.
D97LF F000 R009-26-14DATE:NMDDRAWN BY:
PA13-SL1T11T11CAT. NO.:
THREE WAY SOLID DIELECTRIC SWITCHPAD 0649A
PA13-SL1T11T11
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
REVISIONS
DATE
DRAWING REVIEW TEAM
PLAN VIEWSHOWING OVERALL DIMENSIONS AND MAXIMUM
DIMENSIONS WHEN ENCLOSURE DOORS ARE OPEN
BOTTOM VIEW (WAYS 2 & 3)SHOWING CABLE FEEDTHRU
BOTTOM VIEW (WAY 1)SHOWING CABLE FEEDTHRU
ENTRANCESWAY
1
2
3
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
15.5KV 110KV BIL 200A BUSHING WELL PER IEEE 386 FIGURE 3
15.5KV 110KV BIL 200A BUSHING WELL PER IEEE 386 FIGURE 3
CONCRETEPAD
.25" STAINLESS STEELANCHOR BRACKETWITH .875" X 1.125"SLOTTED HOLESUPPLIED BY G&W
.625" DIA.HARDWARE(4)-SUPPLIEDBY USER
2.1956MMTYP.
1.50
38M
MM
IN.
ENCLOSURE
ENCLOSUREMOUNTINGDETAIL "A"
DATE G&W NO.
CUSTOMER
ORDER NO.
FOR RECORD
FOR APPROVAL-NO MORE WORK TO BE DONE UNTIL APPROVAL IS RECEIVED
PRINT IDENTIFICATION
ITEM NO.
Thisd
rawing
and t
he in
forma
tion t
hereo
n are
and r
emain
the
prop
erty
of G
&Wan
d are
not t
o bec
opied
, repr
oduc
ed o
r dicl
osed
to ot
hers
with
out t
heex
pres
sed w
ritten
cons
ento
f G&W
.
G&W ELECTRIC Co.
* ALL PRIMARY DIMENSIONS ARE IN INCHES. ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
SWITCH ELECTRICAL INFORMATIONSEE NOTES FOR LIMITATIONS
WAY 1 WAYS 2 & 3MAXIMUM DESIGN VOLTAGE 15.5 KV 15.5 KVIMPULSE LEVEL 1 BIL 110 KV 110 KVAC 1 MIN. WITHSTAND 34 KV 34 KVDC 15 MIN. WITHSTAND 53 KV 53 KVCURRENT CONTINUOUS 630 AMP 630 AMPCURRENT INTERRUPTING 630 AMP 16 KAMOMENTARY CURRENT RMS ASYM. 20 KAMAKING CURRENT RMS ASYM. 25.6 KA1 SEC. RATING RMS SYM. 12.5 KA
SWITCH WEIGHT 2200 LBS/ 998 KG
D97
LF F
000
R00
DWG.
NO.
:3D
MOD
EL M
C ER
RORS
0DR
AWIN
G M
C ER
RORS
03D
MOD
EL LA
ST C
HECK
ED Fr
i Sep
26 20
14 15
:43:14
GM
T-060
0 ST
ANDA
RDDR
AWIN
G LA
ST C
HECK
ED F
ri Se
p 26
2014
15:44
:31 G
MT-0
600 S
TAND
ARD
SHEE
T 1 of
2
1 of 2SHEET:SCALE:DATE:APPR BY:
REVDRAWING NO.
D97LF F000 R009-26-14DATE:NMDDRAWN BY:
PA13-SL1T11T11CAT. NO.:
THREE WAY SOLID DIELECTRIC SWITCHPAD 0649A
PA13-SL1T11T11
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
REVISIONS
DATE
DRAWING REVIEW TEAM
PLAN VIEWSHOWING OVERALL DIMENSIONS AND MAXIMUM
DIMENSIONS WHEN ENCLOSURE DOORS ARE OPEN
BOTTOM VIEW (WAYS 2 & 3)SHOWING CABLE FEEDTHRU
BOTTOM VIEW (WAY 1)SHOWING CABLE FEEDTHRU
ENTRANCESWAY
1
2
3
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
15.5KV 110KV BIL 200A BUSHING WELL PER IEEE 386 FIGURE 3
15.5KV 110KV BIL 200A BUSHING WELL PER IEEE 386 FIGURE 3
CONCRETEPAD
.25" STAINLESS STEELANCHOR BRACKETWITH .875" X 1.125"SLOTTED HOLESUPPLIED BY G&W
.625" DIA.HARDWARE(4)-SUPPLIEDBY USER
2.1956MMTYP.
1.50
38M
MM
IN.
ENCLOSURE
ENCLOSUREMOUNTINGDETAIL "A"
DATE G&W NO.
CUSTOMER
ORDER NO.
FOR RECORD
FOR APPROVAL-NO MORE WORK TO BE DONE UNTIL APPROVAL IS RECEIVED
PRINT IDENTIFICATION
ITEM NO.
SIDE
FRONT
WIDTH
HEIGHT59”
(1494mm)
DEPTH44”
(1118mm)
G & W E L E C T R I C P A G E 1 4
Model One-line Diagram
Voltage (kv) Catalog Number
ApproximateDepth
Inches (mm)Weightlbs (kg)
615
PLS32-376-12-6FB 77 (1960) 1500 (700)PLS32-376-12-6FBVU* 92 (2340) 1900 (900)
25 PLS32-386-12-6FB 77 (1960) 1700 (800)35 PLS32-396-12-6FB 77 (1960) 1700 (800)
715
PLS31-376-12-7FB 77 (1960) 1700 (800)PLS31-376-12-7FBVU* 92 (2340) 1900 (900)
25 PLS31-386-12-7FB 77 (1960) 1700 (800)35 PLS31-396-12-7FB 77 (1960) 1700 (800)
915
PLS42-376-12-9FB 77 (1960) 1800 (900)PLS42-376-12-9FBVU* 92 (2340) 2200 (1000)
25 PLS42-386-12-9FB 77 (1960) 1800 (900)35 PLS42-396-12-9FB 77 (1960) 1800 (900)
1015
PL44-376-20-10FB 77 (1960) 1800 (900)PL44-376-20-10FBVU* 92 (2340) 2200 (1000)
25 PL44-386-20-10FB 77 (1960) 1800 (900)35 PL44-396-20-10FB 77 (1960) 1800 (900)
1115
PLS43-376-12-11FB 77 (1960) 1800 (900)PLS43-376-12-11FBVU* 92 (2340) 2200 (1000)
25 PLS43-386-12-11FB 77 (1960) 1800 (900)35 PLS43-396-12-11FB 77 (1960) 1800 (900)
1215
PLS41-376-12-12FB 77 (1960) 1800 (900)PLS41-376-12-12FBVU* 92 (2340) 2200 (1000)
25 PLS41-386-12-12FB 77 (1960) 1800 (900)35 PLS41-396-12-12FB 77 (1960) 1800 (900)
1315
PL33-376-20-13FB 77 (1960) 1700 (800)PL33-376-20-13FBVU* 92 (2340) 1900 (900)
25 PL33-386-20-13FB 77 (1960) 1700 (800)35 PL33-396-20-13FB 77 (1960) 1700 (800)
4015
PS40-376-12-40FB 77 (1960) 1800 (900)PS40-376-12-40FBVU* 92 (2340) 2200 (1000)
25 PS40-386-12-40FB 77 (1960) 1800 (900)35 PS40-396-12-40FB 77 (1960) 1800 (900)
Width= 72 in (1810 mm)
Height = 59 in (1494 mm) with standard 24” Bushing height.
Depth includes 24” cable compartments
*VU indicates the switch includes the SafeVu integrated visible break.
Dimensions are approximate. Do not use for construction.
pls-fB sWitCH series
Front/Back Access
Visit gwelec.com/specs.html for electronic versions of guide specifications.
Thisd
rawing
and t
he in
forma
tion t
hereo
n are
and r
emain
the
prop
erty
of G
&Wan
d are
not t
o bec
opied
, repr
oduc
ed o
r dicl
osed
to ot
hers
with
out t
heex
pres
sed w
ritten
cons
ento
f G&W
.
G&W ELECTRIC Co.
* ALL PRIMARY DIMENSIONS ARE IN INCHES. ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
SWITCH ELECTRICAL INFORMATIONSEE NOTES FOR LIMITATIONS
WAYS 1 & 2 WAYS 3 & 4
MAXIMUM DESIGN VOLTAGE 15.5 KV 15.5 KVIMPULSE LEVEL (BIL) 110 KV 110 KVAC 1 MIN. WITHSTAND 34 KV 34 KVDC 15 MIN. WITHSTAND 53 KV 53 KVCURRENT CONTINUOUS 630 AMP 630 AMPCURRENT INTERRUPTING 630 AMP 12.5 KAMOMENTARY CURRENT RMS ASYM. 20 KAMAKING CURRENT RMS ASYM. 20 KA1 SEC. RATING RMS SYM. 12.5 KV
SWITCH WEIGHT 2000 LBS / 909 KG
D98
LL F
F00
BE0
DWG.
NO.
:3D
MOD
EL M
C ER
RORS
1DR
AWIN
G M
C ER
RORS
23D
MOD
EL LA
STCH
ECKE
DW
ed O
ct 15
2014
20:01
:42 G
MT-0
600
3_PH
ASE_
TRID
_S_S
IDE_
HAND
LE_C
UST
DRAW
ING
LAST
CHE
CKED
Thu
Oct
1620
14 01
:23:28
GM
T-060
0 STA
NDAR
DSH
EET 1
of 1
1 of 1SHEET:SCALE:Oct-16-14DATE:JQAPPR BY:
REVDRAWING NO.
D98LL FF00 BE0Oct-16-14DATE:SHDRAWN BY:
BA13-SL0SL0S10S10CAT. NO.:
FOUR WAY FRONT/ BACK PADMOUNTSOLID DIELECTRIC SWITCH
BA13-SL0SL0S10S10
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
REVISIONS
DATECHANGEREV.
DRAWING REVIEW TEAM
RDSHJQ
BOTTOM VIEW SHOWINGFEEDTHRU LOCATIONS
(WAYS 3 & 4)
NOTES:
1. ALL WAYS ARE EQUIPPED WITH INTERNAL SPRING OPERATORS AND EXTERNAL PROVISIONS FOR PADLOCKING IN ALL POSITIONS.
2. UNFINISHED 304/304L STAINLESS STEEL MOUNTING PLATE WITH BOLTED 304/304L STAINLESS MECHANISM COVER PAINTED ASA 70 LIGHT GRAY. GALVANIZED STEEL ENCLOSURE FINISHED MUNSELL 7GY3.29/1.5 PADMOUNT GREEN.
3. ENCLOSURE IS DESIGNED PER APPLICABLE SECTIONS OF ANSI/IEEE C37.74 & C57.12.28. ENCLOSURE IS TYPICAL AND SHOWS THE OVERALL DIMENSIONS ONLY. CONSTRUCTION DETAILS MAY VARY FROM THOSE DEPICTED. ENCLOSURE DOOR IS EQUIPPED WITH THREE POINT LATCH WITH PENTA HEAD BOLT AND PROVISION FOR PADLOCK.
4. SWITCH IS EQUIPPED WITH INTERNAL 1000:1 CURRENT TRANSFORMERS ON WAYS 3 & 4. WAYS 3 & 4 EACH INCLUDE A TYPE 1 VACUUM INTERRUPTER CONTROL FOR OVERCURRENT PROTECTION. CUSTOMER IS RESPONSIBLE FOR ENTERING PROTECTION SETTINGS INTO THE CONTROL BEFORE ENERGIZING.
5. WHEN ELBOWS, INSERTS, AND ANY OTHER ACCESSORIES ARE CONNECTED TO THE SWITCH,THE RATINGS OF EACH CONNECTED ASSEMBLY WILL BE THAT OF THE LOWEST RATED
COMPONENT OF THE ASSEMBLY.
6. MOUNTING INFORMATION: THE FRAME OF THE SWITCH MUST BE ANCHORED TO THE PAD.THE FRAME IS EQUIPPED WITH 4 SLOTTED ANCHORING HOLES, EACH MEASURING
9/16" X 1". THE LOCATIONS OF THESE HOLES, REFERRED TO AS "FRAME MOUNTING" ARE SHOWN IN THE FRONT VIEW AND RIGHT VIEW. THE PAD MOUNT ENCLOSURE SHOULD BE SECURED TO THE PAD TO PROVIDE IT WITH ADDITIONAL STABILITY. EACH PAD MOUNT ENCLOSURE IS SHIPPED WITH 4 SECURING BRACKETS THAT ARE TO BE USED FOR THIS PURPOSE. THE SECURING BRACKETS CAN BE INSTALLED ANYWHERE ALONG THE INNER EDGE OF THE ENCLOSURE. SEE ENCLOSURE MOUNTING DETAIL "A" AND THE PLAN VIEW FOR MORE DETAILS ABOUT SECURING THE PAD MOUNT ENCLOSURE TO THE PAD.
PLAN VIEW SHOWING OVERALLDIMENSIONS AND MAXIMUM
DIMENSIONS WHEN ENCLOSUREDOORS ARE OPEN
BACK
FRONT
DATE G&W NO.
CUSTOMER
ORDER NO.
FOR RECORD
FOR APPROVAL-NO MORE WORK TO BE DONE UNTIL APPROVAL IS RECEIVED
PRINT IDENTIFICATION
ITEM NO.
ENTRANCESWAY
1
2
3
4
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
Thisd
rawing
and t
he in
forma
tion t
hereo
n are
and r
emain
the
prop
erty
of G
&Wan
d are
not t
o bec
opied
, repr
oduc
ed o
r dicl
osed
to ot
hers
with
out t
heex
pres
sed w
ritten
cons
ento
f G&W
.
G&W ELECTRIC Co.
* ALL PRIMARY DIMENSIONS ARE IN INCHES. ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
SWITCH ELECTRICAL INFORMATIONSEE NOTES FOR LIMITATIONS
WAYS 1 & 2 WAYS 3 & 4
MAXIMUM DESIGN VOLTAGE 15.5 KV 15.5 KVIMPULSE LEVEL (BIL) 110 KV 110 KVAC 1 MIN. WITHSTAND 34 KV 34 KVDC 15 MIN. WITHSTAND 53 KV 53 KVCURRENT CONTINUOUS 630 AMP 630 AMPCURRENT INTERRUPTING 630 AMP 12.5 KAMOMENTARY CURRENT RMS ASYM. 20 KAMAKING CURRENT RMS ASYM. 20 KA1 SEC. RATING RMS SYM. 12.5 KV
SWITCH WEIGHT 2000 LBS / 909 KG
D98
LL F
F00
BE0
DWG.
NO.
:3D
MOD
EL M
C ER
RORS
1DR
AWIN
G M
C ER
RORS
23D
MOD
EL LA
STCH
ECKE
DW
ed O
ct 15
2014
20:01
:42 G
MT-0
600
3_PH
ASE_
TRID
_S_S
IDE_
HAND
LE_C
UST
DRAW
ING
LAST
CHE
CKED
Thu
Oct
1620
14 01
:23:28
GM
T-060
0 STA
NDAR
DSH
EET 1
of 1
1 of 1SHEET:SCALE:Oct-16-14DATE:JQAPPR BY:
REVDRAWING NO.
D98LL FF00 BE0Oct-16-14DATE:SHDRAWN BY:
BA13-SL0SL0S10S10CAT. NO.:
FOUR WAY FRONT/ BACK PADMOUNTSOLID DIELECTRIC SWITCH
BA13-SL0SL0S10S10
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
REVISIONS
DATECHANGEREV.
DRAWING REVIEW TEAM
RDSHJQ
BOTTOM VIEW SHOWINGFEEDTHRU LOCATIONS
(WAYS 3 & 4)
NOTES:
1. ALL WAYS ARE EQUIPPED WITH INTERNAL SPRING OPERATORS AND EXTERNAL PROVISIONS FOR PADLOCKING IN ALL POSITIONS.
2. UNFINISHED 304/304L STAINLESS STEEL MOUNTING PLATE WITH BOLTED 304/304L STAINLESS MECHANISM COVER PAINTED ASA 70 LIGHT GRAY. GALVANIZED STEEL ENCLOSURE FINISHED MUNSELL 7GY3.29/1.5 PADMOUNT GREEN.
3. ENCLOSURE IS DESIGNED PER APPLICABLE SECTIONS OF ANSI/IEEE C37.74 & C57.12.28. ENCLOSURE IS TYPICAL AND SHOWS THE OVERALL DIMENSIONS ONLY. CONSTRUCTION DETAILS MAY VARY FROM THOSE DEPICTED. ENCLOSURE DOOR IS EQUIPPED WITH THREE POINT LATCH WITH PENTA HEAD BOLT AND PROVISION FOR PADLOCK.
4. SWITCH IS EQUIPPED WITH INTERNAL 1000:1 CURRENT TRANSFORMERS ON WAYS 3 & 4. WAYS 3 & 4 EACH INCLUDE A TYPE 1 VACUUM INTERRUPTER CONTROL FOR OVERCURRENT PROTECTION. CUSTOMER IS RESPONSIBLE FOR ENTERING PROTECTION SETTINGS INTO THE CONTROL BEFORE ENERGIZING.
5. WHEN ELBOWS, INSERTS, AND ANY OTHER ACCESSORIES ARE CONNECTED TO THE SWITCH,THE RATINGS OF EACH CONNECTED ASSEMBLY WILL BE THAT OF THE LOWEST RATED
COMPONENT OF THE ASSEMBLY.
6. MOUNTING INFORMATION: THE FRAME OF THE SWITCH MUST BE ANCHORED TO THE PAD.THE FRAME IS EQUIPPED WITH 4 SLOTTED ANCHORING HOLES, EACH MEASURING
9/16" X 1". THE LOCATIONS OF THESE HOLES, REFERRED TO AS "FRAME MOUNTING" ARE SHOWN IN THE FRONT VIEW AND RIGHT VIEW. THE PAD MOUNT ENCLOSURE SHOULD BE SECURED TO THE PAD TO PROVIDE IT WITH ADDITIONAL STABILITY. EACH PAD MOUNT ENCLOSURE IS SHIPPED WITH 4 SECURING BRACKETS THAT ARE TO BE USED FOR THIS PURPOSE. THE SECURING BRACKETS CAN BE INSTALLED ANYWHERE ALONG THE INNER EDGE OF THE ENCLOSURE. SEE ENCLOSURE MOUNTING DETAIL "A" AND THE PLAN VIEW FOR MORE DETAILS ABOUT SECURING THE PAD MOUNT ENCLOSURE TO THE PAD.
PLAN VIEW SHOWING OVERALLDIMENSIONS AND MAXIMUM
DIMENSIONS WHEN ENCLOSUREDOORS ARE OPEN
BACK
FRONT
DATE G&W NO.
CUSTOMER
ORDER NO.
FOR RECORD
FOR APPROVAL-NO MORE WORK TO BE DONE UNTIL APPROVAL IS RECEIVED
PRINT IDENTIFICATION
ITEM NO.
ENTRANCESWAY
1
2
3
4
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
Thisd
rawing
and t
he in
forma
tion t
hereo
n are
and r
emain
the
prop
erty
of G
&Wan
d are
not t
o bec
opied
, repr
oduc
ed o
r dicl
osed
to ot
hers
with
out t
heex
pres
sed w
ritten
cons
ento
f G&W
.
G&W ELECTRIC Co.
* ALL PRIMARY DIMENSIONS ARE IN INCHES. ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
SWITCH ELECTRICAL INFORMATIONSEE NOTES FOR LIMITATIONS
WAYS 1 & 2 WAYS 3 & 4
MAXIMUM DESIGN VOLTAGE 15.5 KV 15.5 KVIMPULSE LEVEL (BIL) 110 KV 110 KVAC 1 MIN. WITHSTAND 34 KV 34 KVDC 15 MIN. WITHSTAND 53 KV 53 KVCURRENT CONTINUOUS 630 AMP 630 AMPCURRENT INTERRUPTING 630 AMP 12.5 KAMOMENTARY CURRENT RMS ASYM. 20 KAMAKING CURRENT RMS ASYM. 20 KA1 SEC. RATING RMS SYM. 12.5 KV
SWITCH WEIGHT 2000 LBS / 909 KG
D98
LL F
F00
BE0
DWG.
NO.
:3D
MOD
EL M
C ER
RORS
1DR
AWIN
G M
C ER
RORS
23D
MOD
EL LA
STCH
ECKE
DW
ed O
ct 15
2014
20:01
:42 G
MT-0
600
3_PH
ASE_
TRID
_S_S
IDE_
HAND
LE_C
UST
DRAW
ING
LAST
CHE
CKED
Thu
Oct
1620
14 01
:23:28
GM
T-060
0 STA
NDAR
DSH
EET 1
of 1
1 of 1SHEET:SCALE:Oct-16-14DATE:JQAPPR BY:
REVDRAWING NO.
D98LL FF00 BE0Oct-16-14DATE:SHDRAWN BY:
BA13-SL0SL0S10S10CAT. NO.:
FOUR WAY FRONT/ BACK PADMOUNTSOLID DIELECTRIC SWITCH
BA13-SL0SL0S10S10
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
REVISIONS
DATECHANGEREV.
DRAWING REVIEW TEAM
RDSHJQ
BOTTOM VIEW SHOWINGFEEDTHRU LOCATIONS
(WAYS 3 & 4)
NOTES:
1. ALL WAYS ARE EQUIPPED WITH INTERNAL SPRING OPERATORS AND EXTERNAL PROVISIONS FOR PADLOCKING IN ALL POSITIONS.
2. UNFINISHED 304/304L STAINLESS STEEL MOUNTING PLATE WITH BOLTED 304/304L STAINLESS MECHANISM COVER PAINTED ASA 70 LIGHT GRAY. GALVANIZED STEEL ENCLOSURE FINISHED MUNSELL 7GY3.29/1.5 PADMOUNT GREEN.
3. ENCLOSURE IS DESIGNED PER APPLICABLE SECTIONS OF ANSI/IEEE C37.74 & C57.12.28. ENCLOSURE IS TYPICAL AND SHOWS THE OVERALL DIMENSIONS ONLY. CONSTRUCTION DETAILS MAY VARY FROM THOSE DEPICTED. ENCLOSURE DOOR IS EQUIPPED WITH THREE POINT LATCH WITH PENTA HEAD BOLT AND PROVISION FOR PADLOCK.
4. SWITCH IS EQUIPPED WITH INTERNAL 1000:1 CURRENT TRANSFORMERS ON WAYS 3 & 4. WAYS 3 & 4 EACH INCLUDE A TYPE 1 VACUUM INTERRUPTER CONTROL FOR OVERCURRENT PROTECTION. CUSTOMER IS RESPONSIBLE FOR ENTERING PROTECTION SETTINGS INTO THE CONTROL BEFORE ENERGIZING.
5. WHEN ELBOWS, INSERTS, AND ANY OTHER ACCESSORIES ARE CONNECTED TO THE SWITCH,THE RATINGS OF EACH CONNECTED ASSEMBLY WILL BE THAT OF THE LOWEST RATED
COMPONENT OF THE ASSEMBLY.
6. MOUNTING INFORMATION: THE FRAME OF THE SWITCH MUST BE ANCHORED TO THE PAD.THE FRAME IS EQUIPPED WITH 4 SLOTTED ANCHORING HOLES, EACH MEASURING
9/16" X 1". THE LOCATIONS OF THESE HOLES, REFERRED TO AS "FRAME MOUNTING" ARE SHOWN IN THE FRONT VIEW AND RIGHT VIEW. THE PAD MOUNT ENCLOSURE SHOULD BE SECURED TO THE PAD TO PROVIDE IT WITH ADDITIONAL STABILITY. EACH PAD MOUNT ENCLOSURE IS SHIPPED WITH 4 SECURING BRACKETS THAT ARE TO BE USED FOR THIS PURPOSE. THE SECURING BRACKETS CAN BE INSTALLED ANYWHERE ALONG THE INNER EDGE OF THE ENCLOSURE. SEE ENCLOSURE MOUNTING DETAIL "A" AND THE PLAN VIEW FOR MORE DETAILS ABOUT SECURING THE PAD MOUNT ENCLOSURE TO THE PAD.
PLAN VIEW SHOWING OVERALLDIMENSIONS AND MAXIMUM
DIMENSIONS WHEN ENCLOSUREDOORS ARE OPEN
BACK
FRONT
DATE G&W NO.
CUSTOMER
ORDER NO.
FOR RECORD
FOR APPROVAL-NO MORE WORK TO BE DONE UNTIL APPROVAL IS RECEIVED
PRINT IDENTIFICATION
ITEM NO.
ENTRANCESWAY
1
2
3
4
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
SIDE
FRONT
BACK
WIDTH72”
(1810mm)
DEPTH
HEIGHT59”
(1494mm)
G & W E L E C T R I C P A G E 1 5
Model One-line Diagram
Voltage (kv) Catalog Number
ApproximateDepth
Inches (mm)Weightlbs (kg)
615
PLT32-376-12-6FB 77 (1960) 1700 (800)
PLT32-376-12-6FBVU* 92 (2340) 1900 (900)
25 PLT32-386-12-6FB 77 (1960) 2000 (900)
715
PLT31-376-12-7FB 77 (1960) 2000 (900)
PLT31-376-12-7FBVU* 92 (2340) 1900 (900)
25 PLT31-386-12-7FB 77 (1960) 2000 (900)
915
PLT42-376-12-9FB 77 (1960) 2300 (1100)
PLT42-376-12-9FBVU* 92 (2340) 2200 (1000)
25 PLT42-386-12-9FB 77 (1960) 2300 (1100)
1015
PL44-376-20-10FB 77 (1960) 2300 (1100)
PL44-376-20-10FBVU* 92 (2340) 2200 (1000)
25 PL44-386-20-10FB 77 (1960) 2300 (1100)
1115
PLT43-376-12-11FB 77 (1960) 2300 (1100)
PLT43-376-12-11FBVU* 92 (2340) 2200 (1000)
25 PLT43-386-12-11FB 77 (1960) 2300 (1100)
1215
PLT41-376-12-12FB 77 (1960) 2300 (1100)
PLT41-376-12-12FBVU* 92 (2340) 2200 (1000)
25 PLT41-386-12-12FB 77 (1960) 2300 (1100)
1315
PL33-376-20-13FB 77 (1956) 2000 (900)
PL33-376-20-13FBVU* 92 (2340) 1900 (900)
25 PL33-386-20-13FB 77 (1960) 2000 (900)
4015
PT40-376-12-40FB 77 (1960) 2300 (1100)
PT40-376-12-40FBVU* 92 (2340) 2200 (1000)
25 PT40-386-12-40FB 77 (1960) 2300 (1100)
Width= 72 in (1810 mm)
Height = 59 in (1494 mm) with standard 24” Bushing height.
Depth includes 24” cable compartments
*VU indicates the switch includes the SafeVu integrated visible break.
Dimensions are approximate. Do not use for construction.
plt-fB sWitCH series
Visit gwelec.com/specs.html for electronic versions of guide specifications.
Front/Back Access
WIDTH72”
(1810mm)
SIDE
FRONT
BACK
DEPTH
HEIGHT59”
(1494mm)
G & W E L E C T R I C P A G E 1 6
front acceSS
front aCCess
Front Access Trident Switches provide a solution for environments where space or aesthetics are critical factors:• Single Side Entry – There are only doors on one side of the pad mount enclosure which means
the enclosure can be placed close to a structure• Easy Access – All components, connections, and operators are located within one compartment• Flexible Configurations – Switches can range from a two way (in and out) to 6 way and can in-
clude inverted designs (bushings towards the top) or bus-tie options.
Two-way Trident Solid Dielectric Switches
G & W E L E C T R I C P A G E 1 7
front/back acceSS
front/BaCk aCCess
Front/Back Access Trident Switches provide a compact foot print in a traditional switch design:• Two Side Entry – With two entry points, one side of the switch can be designated Line (Source)
and the other Load to simplify operations• Compact Foot print – The Front/Back switches can be designed to fit on existing or pre-manufac-
tured pads to simplify installation
Two-way Trident Solid Dielectric Switches
G & W E L E C T R I C P A G E 1 8
Trident solid dielectric insulated switches provide the total life cycle cost and operational benefits of fuseless, electronically controlled, resettable overcurrent protection, with the safety and maintenance benefits of an environmentally friendly dead-front design.
The Trident utilizes G&W’s time proven, submersible epoxy insulation to fully encapsulate load and fault interrupting vacuum interrupters. This solid dielectric insulation eliminates the degradation of dielectric integrity commonly associated with oil and air insulated switchgear.
ConfigurationsThe two way Trident is available as a loadbreak switch or a fault interrupter. The fault interrupter utilizes a trip-free mechanism, which provides interruption independent of the operating handle when closing into a fault. Viewing windows provide visible indication of the contact position.
appliCationsTrident load and fault interrupting switches provide a direct replacement for power fused air and vacuum-in-oil switchgear. Some ideal applications include:
Transformer and Motor Protection — The three phase trip feature and high continuous current make the two way Trident fault interrupters switches ideal for protect-ing three phase motors and transformer loads.
Access Options — Trident switches are available in a Front Access design, with operating handles and bush-ings on the same side of the switch, and a low profile Front/Back Access design, with bushings on both sides of the switch.
additional featuresVisible Break — The Front Access two way Trident is available with G&W’s SafeVu feature, which provides an integrated visible break disconnect switch in series with the vacuum interrupter. This eliminates the need to
remove elbows or use externally mounted linkage sys-tems to provide a visible open. Switches equipped with the SafeVu feature incorporate redundant mechanical interlocks to ensure the load break switch is open prior to the operation of the visible break switch.
testingTrident switches are designed and tested to applicable standards including IEEE C37.74 (IEEE C37.71 and C37.72), IEEE 386, IEC 60265, IEEE 592, and IEEE C57.12.28. All fault interrupter devices have passed IEEE C37.60. Trident switches are RUS accepted.
Fully encapsulated current transformers provide power and sensing for G&W’s Vacuum Interrupter controls. The controls emulate the most common time current curves (TCC) for power fuses, mechanical relays, and fuse links. Control options include Ground Fault (Phase Imbalance), Time Delays, and Inrush Restraint (Cold Load Pickup).
p Low Profile Front/Back Access Design
Two-way Trident Solid Dielectric Switches
G & W E L E C T R I C P A G E 1 9
features and Benefits
Features Benefits
Epoxy Insulation (No oil or SF6, and true dead-front design)
No maintenance or monitoring system necessary, lowest total life cycle costs
Dead-front design provides increased operator safety by eliminating all exposed live parts
Epoxy is inert, environmentally friendly, with no EPA usage restrictions
Resettable Vacuum Interrupter Mechanism No fuses or fuse links to stock and replace
Integral self-powered overcurrent protection available Integrated solution with fully encapsulated current transformers and no external power source or PT required
Load Break Ratings
Voltage Class 15kV 1 25kV 35kV
Max System Voltage 15.5kV 27kV 38kV
BIL Impulse 110kV 2 125kV 150kV
Continuous Current 630A 630A 630A
Load Break Current 630A 630A 630A
AC Withstand, 1 minute 35kV 60kV 70kVAC Withstand,
Production, 1 minute 34kV 40kV 50kV
DC Withstand, 15 minutes 53kV 78kV 103kV
Momentary Current, RMS, asym 20kA 20kA 20kA
Fault-Close 3-times, asym 20kA 20kA 20kA
1 Second Current, sym 12.5kA 12.5kA 12.5kALoad Break Switch
Mechanical Operations 2,000 2,000 2,000
Fault Interrupting Ratings
Voltage Class 15kV 1 25kV 35kV
Max System Voltage 15.5kV 27kV 38kV
BIL Impulse 110kV 2 125kV 150kV
Continuous Current 630A 630A 630A
AC Withstand, 1 minute 35kV 60kV 70kVAC Withstand,
Production, 1 minute 34kV 40kV 50kV
DC Withstand, 15 minutes 53kV 78kV 103kV
Fault Interrupting Current, sym 12.5kA 12.5kA 12.5kA
Vacuum Interrupter Mechanical Operations 2,000 2,000 2,000
Percent of Maximum
Interrupting Rating
Approximate Interrupting
Current, Amps
Number of Fault
Interruptions
15-20%45-55%
90-100%
2,0006,000
12,500
445616
Total number of Fault Interruptions: 116
IEEE C37.60 Fault Interrupting Duty
(1) Integrated visible break available on 15kV load break and three phase fault interrupters.
(2) BIL impulse rating is 95kV when using integrated visible break feature.
ratingsThe switch is designed, tested and built per IEEE C37.74 for load break switching, IEEE C37.60 for fault interrupting, IEEE 386 for bushing specification, and IEC 60529 for environmental protection rating. Certified test reports are available.
Two-way Trident Solid Dielectric Switches
G & W E L E C T R I C P A G E 2 0
Model One-line Diagram
Voltage (kv) Catalog Number
3
15 PL21-376-20-3FA
25 PL21-386-20-3FA
35 PL21-396-20-3FA
4
15 PS20-376-12-4FA
25 PS20-386-12-4FA
35 PS20-396-12-4FA
front aCCess sWitCH series
front aCCess WitH safeVu sWitCH series
This d
rawing
and t
he in
forma
tion t
hereo
n are
and r
emain
the
prop
erty
of G
&W an
d are
not t
o be c
opied
, repr
oduc
ed o
r dicl
osed
to ot
hers
with
out t
he
expr
esse
d writ
ten co
nsen
t of G
&W.
G&W ELECTRIC Co.
* ALL PRIMARY DIMENSIONS ARE IN INCHES. ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
26.00[660]
26.63[676]
ENCLOSUREMOUNTING
25.00[635]
3.00[76]
ADJUSTABLEENCLOSURE
MOUNTINGUP TO21.75[552]
31.00[787]
53.75[1365]
D97
00 2
FCR
HR0
DWG.
NO.
:3D
MOD
EL M
C ER
RORS
0DR
AWIN
G M
C ER
RORS
13D
MOD
EL LA
ST C
HECK
ED Tu
e Apr
15 20
14 14
:02:42
GM
T-060
0 3_
PHAS
E_TR
ID_S
_SID
E_HA
NDLE
_CUS
TDR
AWIN
G LA
ST C
HECK
ED T
ue A
pr 22
2014
11:21
:08 G
MT-0
600 S
TAND
ARD
SHE
ET 1
OF 1
1 of 1SHEET:SCALE:Apr-15-14 DATE:RYLAPPR BY:
REV
ADRAWING NO.
D9700 2FCR HR0Apr-15-14DATE:IMNDRAWN BY:
PA13-S206CAT. NO.:
THREE PHASESOLID DIELECTRIC SWITCH
PA13-S206
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
REVISIONS
DATECHANGEREV.
6-5-14 204309 CL A
DRAWING REVIEW TEAM
SWITCH ELECTRICAL INFORMATION
MAXIMUM DESIGN VOLTAGEIMPULSE LEVEL ( BIL )AC 1 MIN. WITHSTANDDC 15 MIN. WITHSTANDCURRENT CONTINUOUSCURRENT INTERRUPTING SYM.
SWITCH WEIGHT 550 LBS / 250 KG
SEE NOTES FOR LIMITATIONS
KVKVKVKVAMPKA
15.5110345363012.5
THREE LINE DIAGRAM
PLAN VIEW SHOWING MAXIMUMDIMENSIONS WHEN ENCLOSURE
DOOR IS OPEN
BOTTOM VIEWSHOWING FEEDTHRU LOCATION
(MOUNTING PLATE NOTSHOWN FOR CLARITY)
DATE G&W NO.
CUSTOMER
ORDER NO.
FOR RECORD
FOR APPROVAL-NO MORE WORK TO BE DONE UNTIL APPROVAL IS RECEIVED
PRINT IDENTIFICATION
ITEM NO.
ENTRANCESWAY
1
2
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
CONCRETEPAD
.25" STAINLESS STEELANCHOR BRACKETWITH .875" X 1.125"SLOTTED HOLESUPPLIED BY G&W
.625" DIA.HARDWARE(4)-SUPPLIEDBY USER
2.1956MMTYP.
1.50
38M
MM
IN.
ENCLOSURE
ENCLOSUREMOUNTINGDETAIL "A"
This d
rawing
and t
he in
forma
tion t
hereo
n are
and r
emain
the
prop
erty
of G
&W an
d are
not t
o be c
opied
, repr
oduc
ed o
r dicl
osed
to ot
hers
with
out t
he
expr
esse
d writ
ten co
nsen
t of G
&W.
G&W ELECTRIC Co.
* ALL PRIMARY DIMENSIONS ARE IN INCHES. ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
26.00[660]
26.63[676]
ENCLOSUREMOUNTING
25.00[635]
3.00[76]
ADJUSTABLEENCLOSURE
MOUNTINGUP TO21.75[552]
31.00[787]
53.75[1365]
D97
00 2
FCR
HR0
DWG.
NO.
:3D
MOD
EL M
C ER
RORS
0DR
AWIN
G M
C ER
RORS
13D
MOD
EL LA
ST C
HECK
ED Tu
e Apr
15 20
14 14
:02:42
GM
T-060
0 3_
PHAS
E_TR
ID_S
_SID
E_HA
NDLE
_CUS
TDR
AWIN
G LA
ST C
HECK
ED T
ue A
pr 22
2014
11:21
:08 G
MT-0
600 S
TAND
ARD
SHE
ET 1
OF 1
1 of 1SHEET:SCALE:Apr-15-14 DATE:RYLAPPR BY:
REV
ADRAWING NO.
D9700 2FCR HR0Apr-15-14DATE:IMNDRAWN BY:
PA13-S206CAT. NO.:
THREE PHASESOLID DIELECTRIC SWITCH
PA13-S206
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
REVISIONS
DATECHANGEREV.
6-5-14 204309 CL A
DRAWING REVIEW TEAM
SWITCH ELECTRICAL INFORMATION
MAXIMUM DESIGN VOLTAGEIMPULSE LEVEL ( BIL )AC 1 MIN. WITHSTANDDC 15 MIN. WITHSTANDCURRENT CONTINUOUSCURRENT INTERRUPTING SYM.
SWITCH WEIGHT 550 LBS / 250 KG
SEE NOTES FOR LIMITATIONS
KVKVKVKVAMPKA
15.5110345363012.5
THREE LINE DIAGRAM
PLAN VIEW SHOWING MAXIMUMDIMENSIONS WHEN ENCLOSURE
DOOR IS OPEN
BOTTOM VIEWSHOWING FEEDTHRU LOCATION
(MOUNTING PLATE NOTSHOWN FOR CLARITY)
DATE G&W NO.
CUSTOMER
ORDER NO.
FOR RECORD
FOR APPROVAL-NO MORE WORK TO BE DONE UNTIL APPROVAL IS RECEIVED
PRINT IDENTIFICATION
ITEM NO.
ENTRANCESWAY
1
2
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
CONCRETEPAD
.25" STAINLESS STEELANCHOR BRACKETWITH .875" X 1.125"SLOTTED HOLESUPPLIED BY G&W
.625" DIA.HARDWARE(4)-SUPPLIEDBY USER
2.1956MMTYP.
1.50
38M
MM
IN.
ENCLOSURE
ENCLOSUREMOUNTINGDETAIL "A"
This d
rawing
and t
he in
forma
tion t
hereo
n are
and r
emain
the
prop
erty
of G
&W an
d are
not t
o be c
opied
, repr
oduc
ed o
r dicl
osed
to ot
hers
with
out t
he
expr
esse
d writ
ten co
nsen
t of G
&W.
G&W ELECTRIC Co.
* ALL PRIMARY DIMENSIONS ARE IN INCHES. ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
3.00[76]TYP.
82.00[2083]
34.63[879]
ENCLOSUREMOUNTING
34.00[864]
2.19[56]TYP.
33.00[838]
39.00[991]
61.26[1556]
3.81[97]
D97
00 8
LCR
B00
DWG.
NO.
:3D
MOD
EL M
C ER
RORS
0DR
AWIN
G M
C ER
RORS
03D
MOD
EL LA
ST C
HECK
ED Th
u Feb
13 20
14 18
:58:16
GM
T-060
0 ST
ANDA
RDDR
AWIN
G LA
ST C
HECK
ED T
hu Fe
b 13
2014
02:21
:51 G
MT-0
600 S
TAND
ARD
SHEE
T 1 of
1
1 of 1SHEET:SCALE:9-28-13 DATE:RYLAPPR BY:
REV
CDRAWING NO.
D9700 8LCR B009-28-13DATE:WMJDRAWN BY:
PA13-SVL06CAT. NO.:
PADMOUNT TRIDENT WITH SAFEVUWITH 600A BUSHINGS
PA13-SVL06
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
REVISIONS
DATECHANGEREV.
1-15-14187586 BSNA2-13-14189834 JXUB3-20-14195152 SHC
DRAWING REVIEW TEAM
VXSHJQ
SWITCH ELECTRICAL INFORMATION
MAXIMUM DESIGN VOLTAGEIMPULSE LEVEL ( BIL )AC 1 MIN. WITHSTANDDC 15 MIN. WITHSTANDCURRENT CONTINUOUSCURRENT INTERRUPTING SYM.MOMENTARY CURRENT RMS ASYM.MAKING CURRENT RMS ASYM.1 SEC. RATING RMS SYM.
SWITCH WEIGHT 750 LBS / 340 KG
SEE NOTES FOR LIMITATIONS
THREE LINE DIAGRAM
15.5953453630630202012.5
KVKVKVKVAMPAMPKAKAKA
SHOWING MAXIMUM DIMENSIONSWHEN ENCLOSURE DOOR IS OPEN
TRIDENT BOTTOM VIEW
PLAN VIEW
DATE G&W NO.
CUSTOMER
ORDER NO.
FOR RECORD
FOR APPROVAL-NO MORE WORK TO BE DONE UNTIL APPROVAL IS RECEIVED
PRINT IDENTIFICATION
ITEM NO.
ENTRANCESWAY
1
2
15.5KV 95KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
15.5KV 95KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
This d
rawing
and t
he in
forma
tion t
hereo
n are
and r
emain
the
prop
erty
of G
&W an
d are
not t
o be c
opied
, repr
oduc
ed o
r dicl
osed
to ot
hers
with
out t
he
expr
esse
d writ
ten co
nsen
t of G
&W.
G&W ELECTRIC Co.
* ALL PRIMARY DIMENSIONS ARE IN INCHES. ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
3.00[76]TYP.
82.00[2083]
34.63[879]
ENCLOSUREMOUNTING
34.00[864]
2.19[56]TYP.
33.00[838]
39.00[991]
61.26[1556]
3.81[97]
D97
00 8
LCR
B00
DWG.
NO.
:3D
MOD
EL M
C ER
RORS
0DR
AWIN
G M
C ER
RORS
03D
MOD
EL LA
ST C
HECK
ED Th
u Feb
13 20
14 18
:58:16
GM
T-060
0 ST
ANDA
RDDR
AWIN
G LA
ST C
HECK
ED T
hu Fe
b 13
2014
02:21
:51 G
MT-0
600 S
TAND
ARD
SHEE
T 1 of
1
1 of 1SHEET:SCALE:9-28-13 DATE:RYLAPPR BY:
REV
CDRAWING NO.
D9700 8LCR B009-28-13DATE:WMJDRAWN BY:
PA13-SVL06CAT. NO.:
PADMOUNT TRIDENT WITH SAFEVUWITH 600A BUSHINGS
PA13-SVL06
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
REVISIONS
DATECHANGEREV.
1-15-14187586 BSNA2-13-14189834 JXUB3-20-14195152 SHC
DRAWING REVIEW TEAM
VXSHJQ
SWITCH ELECTRICAL INFORMATION
MAXIMUM DESIGN VOLTAGEIMPULSE LEVEL ( BIL )AC 1 MIN. WITHSTANDDC 15 MIN. WITHSTANDCURRENT CONTINUOUSCURRENT INTERRUPTING SYM.MOMENTARY CURRENT RMS ASYM.MAKING CURRENT RMS ASYM.1 SEC. RATING RMS SYM.
SWITCH WEIGHT 750 LBS / 340 KG
SEE NOTES FOR LIMITATIONS
THREE LINE DIAGRAM
15.5953453630630202012.5
KVKVKVKVAMPAMPKAKAKA
SHOWING MAXIMUM DIMENSIONSWHEN ENCLOSURE DOOR IS OPEN
TRIDENT BOTTOM VIEW
PLAN VIEW
DATE G&W NO.
CUSTOMER
ORDER NO.
FOR RECORD
FOR APPROVAL-NO MORE WORK TO BE DONE UNTIL APPROVAL IS RECEIVED
PRINT IDENTIFICATION
ITEM NO.
ENTRANCESWAY
1
2
15.5KV 95KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
15.5KV 95KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
SIDE
SIDE
HEIGHT58”
(1458mm)
FRONT
FRONT
DEPTH36”
(705mm)
WIDTH39”
(991mm)
DEPTH48”
(1219mm)
HEIGHT59”
(1499mm)
Depth includes 24” cable compartment
Dimensions are approximate. Do not use for construction.
WIDTH31”
(787mm)
Two-way Trident Solid Dielectric Switches
Model One-line Diagram
Voltage (kv) Catalog Number
3
15
PL21-376-20-3FAVU
4 PS20-376-12-4FAVU
G & W E L E C T R I C P A G E 2 1
Model One-line Diagram
Voltage (kv) Catalog Number
3
15 PL21-376-20-3FB
25 PL21-386-20-3FB
35 PL21-396-20-3FB
4
15 PS20-376-12-4FB
25 PS20-386-12-4FB
35 PS20-396-12-4FB
front/BaCk sWitCH series
This
draw
ing an
d the
infor
matio
n the
reon a
re an
d rem
ain th
e pr
oper
ty of
G&W
and a
re no
t to b
e cop
ied, re
prod
uce
d or d
iclos
ed to
othe
rs wi
thou
t the
ex
pres
sed w
ritten
cons
ent o
f G&W
.
G&W ELECTRIC Co.
* ALL PRIMARY DIMENSIONS ARE IN INCHES. ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
72.66[1846]
106.87[2715]
39.21[996]
11.00[279]
27.00[686]
TYP.
ADJUSTABLEENCLOSURE
MOUNTINGUP TO32.46[824]
3.00[76]TYP.
6.08[155]TYP.
3.00[76]TYP.
34.83[885]
ENCLOSUREMOUNTING
2.19[56]TYP.
8.00[203]
34.21[869]
TYP.
D97
00 2
LCR
AZ0
DWG.
NO.
:3D
MOD
EL M
C ER
RORS
1DR
AWIN
G M
C ER
RORS
13D
MOD
EL LA
ST C
HECK
ED W
ed D
ec 24
2014
01:39
:25 G
MT-
0600
CUS
TOM
ERDR
AWIN
G LA
ST C
HECK
ED W
ed D
ec 24
2014
01:40
:52 G
MT-
0600
STAN
DARD
SHEE
T 1 o
f 1
1 of 1SHEET:SCALE:Dec-24-14DATE:JQAPPR BY:
REVDRAWING NO.
D9700 2LCR AZ0Dec-24-14DATE:SHDRAWN BY:
BA13-SL06CAT. NO.:
THREE PHASE SOLID DIELECTRIC SWITCH
BA13-SL06
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
SWITCH ELECTRICAL INFORMATION
MAXIMUM DESIGN VOLTAGEIMPULSE LEVEL ( BIL )AC 1 MIN. WITHSTANDDC 15 MIN. WITHSTANDCURRENT CONTINUOUSCURRENT INTERRUPTING SYM.MOMENTARY CURRENT RMS ASYM.MAKING CURRENT RMS ASYM.1 SEC. RATING RMS SYM.
SWITCH WEIGHT 600 LBS / 273 KG
SEE NOTES FOR LIMITATIONS
KVKVKVKVAMPAMPKAKAKA
15.51103453630630202012.5
THREE LINE DIAGRAM
PLAN VIEW
NOTES:
1. SWITCHED WAY EQUIPPED WITH INTERNAL SPRING OPERATOR AND EXTERNAL PROVISIONS FOR PADLOCKING IN ALL POSITIONS.
2. UNFINISHED 304/304L STAINLESS STEEL MOUNTING PLATE WITH BOLTED 304/304L STAINLESS MECHANISM COVER PAINTED ASA 70 LIGHT GRAY. 304 STAINLESS STEEL ENCLOSURE FINISHED PADMOUNT GREEN MUNSELL 7GY3.29/1.5.
3. ENCLOSURE IS DESIGNED PER APPLICABLE SECTIONS OF ANSI/IEEE C37.74 & C57.12.29. ENCLOSURE IS TYPICAL AND SHOWS THE OVERALL DIMENSIONS ONLY, CONSTRUCTION DETAILS MAY VARY FROM THOSE DEPICTED. ENCLOSURE DOOR IS EQUIPPED WITH THREE POINT LATCH WITH PENTA HEAD BOLT AND PROVISION FOR PADLOCK.
4. WHEN ELBOWS, INSERTS, AND ANY OTHER ACCESSORIES ARE CONNECTED TO THE SWITCH, THE RATINGS OF EACH CONNECTED ASSEMBLY WILL BE THAT OFTHE LOWEST RATED COMPONENT OF THE ASSEMBLY
5. MOUNTING INFORMATION: THE FRAME OF THE SWITCH MUST BE ANCHORED TO THE PAD.THE FRAME IS EQUIPPED WITH 4 SLOTTED ANCHORING HOLES, EACH MEASURING
9/16" X 1". THE LOCATIONS OF THESE HOLES, REFERRED TO AS "FRAME MOUNTING" ARE SHOWN IN THE BACK VIEW AND LEFT VIEW. THE PAD MOUNT ENCLOSURE SHOULD BE SECURED TO THE PAD TO PROVIDE IT WITH ADDITIONAL STABILITY. EACH PAD MOUNT ENCLOSURE IS SHIPPED WITH 4 SECURING BRACKETS THAT ARE TO BE USED FOR THIS PURPOSE. THE SECURING BRACKETS CAN BE INSTALLED ANYWHERE ALONG THE INNER EDGE OF THE ENCLOSURE. SEE ENCLOSURE MOUNTING DETAIL "A" AND THE PLAN VIEW FOR MORE DETAILS ABOUT SECURING THE PAD MOUNT ENCLOSURE
TO THE PAD.
SHOWING OVERALL DIMENSIONSAND MAXIMUM DIMENSIONS
WHEN ENCLOSURE DOORS ARE OPEN.
FRONT
BACK
CABLETRAININGOUTLINES
ENTRANCESWAY
1
2
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
CONCRETEPAD
.25" STAINLESS STEELANCHOR BRACKETWITH .875" X 1.125"SLOTTED HOLESUPPLIED BY G&W
.625" DIA.HARDWARE(4)-SUPPLIEDBY USER
2.1956MMTYP.
1.50
38M
MM
IN.
ENCLOSURE
ENCLOSUREMOUNTINGDETAIL "A"
DATE G&W NO.
CUSTOMER
ORDER NO.
FOR RECORD
FOR APPROVAL-NO MORE WORK TO BE DONE UNTIL APPROVAL IS RECEIVED
PRINT IDENTIFICATION
ITEM NO.
This
draw
ing an
d the
infor
matio
n the
reon a
re an
d rem
ain th
e pr
oper
ty of
G&W
and a
re no
t to b
e cop
ied, re
prod
uce
d or d
iclos
ed to
othe
rs wi
thou
t the
ex
pres
sed w
ritten
cons
ent o
f G&W
.
G&W ELECTRIC Co.
* ALL PRIMARY DIMENSIONS ARE IN INCHES. ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
72.66[1846]
106.87[2715]
39.21[996]
11.00[279]
27.00[686]
TYP.
ADJUSTABLEENCLOSURE
MOUNTINGUP TO32.46[824]
3.00[76]TYP.
6.08[155]TYP.
3.00[76]TYP.
34.83[885]
ENCLOSUREMOUNTING
2.19[56]TYP.
8.00[203]
34.21[869]
TYP.
D97
00 2
LCR
AZ0
DWG.
NO.
:3D
MOD
EL M
C ER
RORS
1DR
AWIN
G M
C ER
RORS
13D
MOD
EL LA
ST C
HECK
ED W
ed D
ec 24
2014
01:39
:25 G
MT-
0600
CUS
TOM
ERDR
AWIN
G LA
ST C
HECK
ED W
ed D
ec 24
2014
01:40
:52 G
MT-
0600
STAN
DARD
SHEE
T 1 o
f 1
1 of 1SHEET:SCALE:Dec-24-14DATE:JQAPPR BY:
REVDRAWING NO.
D9700 2LCR AZ0Dec-24-14DATE:SHDRAWN BY:
BA13-SL06CAT. NO.:
THREE PHASE SOLID DIELECTRIC SWITCH
BA13-SL06
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
SWITCH ELECTRICAL INFORMATION
MAXIMUM DESIGN VOLTAGEIMPULSE LEVEL ( BIL )AC 1 MIN. WITHSTANDDC 15 MIN. WITHSTANDCURRENT CONTINUOUSCURRENT INTERRUPTING SYM.MOMENTARY CURRENT RMS ASYM.MAKING CURRENT RMS ASYM.1 SEC. RATING RMS SYM.
SWITCH WEIGHT 600 LBS / 273 KG
SEE NOTES FOR LIMITATIONS
KVKVKVKVAMPAMPKAKAKA
15.51103453630630202012.5
THREE LINE DIAGRAM
PLAN VIEW
NOTES:
1. SWITCHED WAY EQUIPPED WITH INTERNAL SPRING OPERATOR AND EXTERNAL PROVISIONS FOR PADLOCKING IN ALL POSITIONS.
2. UNFINISHED 304/304L STAINLESS STEEL MOUNTING PLATE WITH BOLTED 304/304L STAINLESS MECHANISM COVER PAINTED ASA 70 LIGHT GRAY. 304 STAINLESS STEEL ENCLOSURE FINISHED PADMOUNT GREEN MUNSELL 7GY3.29/1.5.
3. ENCLOSURE IS DESIGNED PER APPLICABLE SECTIONS OF ANSI/IEEE C37.74 & C57.12.29. ENCLOSURE IS TYPICAL AND SHOWS THE OVERALL DIMENSIONS ONLY, CONSTRUCTION DETAILS MAY VARY FROM THOSE DEPICTED. ENCLOSURE DOOR IS EQUIPPED WITH THREE POINT LATCH WITH PENTA HEAD BOLT AND PROVISION FOR PADLOCK.
4. WHEN ELBOWS, INSERTS, AND ANY OTHER ACCESSORIES ARE CONNECTED TO THE SWITCH, THE RATINGS OF EACH CONNECTED ASSEMBLY WILL BE THAT OFTHE LOWEST RATED COMPONENT OF THE ASSEMBLY
5. MOUNTING INFORMATION: THE FRAME OF THE SWITCH MUST BE ANCHORED TO THE PAD.THE FRAME IS EQUIPPED WITH 4 SLOTTED ANCHORING HOLES, EACH MEASURING
9/16" X 1". THE LOCATIONS OF THESE HOLES, REFERRED TO AS "FRAME MOUNTING" ARE SHOWN IN THE BACK VIEW AND LEFT VIEW. THE PAD MOUNT ENCLOSURE SHOULD BE SECURED TO THE PAD TO PROVIDE IT WITH ADDITIONAL STABILITY. EACH PAD MOUNT ENCLOSURE IS SHIPPED WITH 4 SECURING BRACKETS THAT ARE TO BE USED FOR THIS PURPOSE. THE SECURING BRACKETS CAN BE INSTALLED ANYWHERE ALONG THE INNER EDGE OF THE ENCLOSURE. SEE ENCLOSURE MOUNTING DETAIL "A" AND THE PLAN VIEW FOR MORE DETAILS ABOUT SECURING THE PAD MOUNT ENCLOSURE
TO THE PAD.
SHOWING OVERALL DIMENSIONSAND MAXIMUM DIMENSIONS
WHEN ENCLOSURE DOORS ARE OPEN.
FRONT
BACK
CABLETRAININGOUTLINES
ENTRANCESWAY
1
2
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
CONCRETEPAD
.25" STAINLESS STEELANCHOR BRACKETWITH .875" X 1.125"SLOTTED HOLESUPPLIED BY G&W
.625" DIA.HARDWARE(4)-SUPPLIEDBY USER
2.1956MMTYP.
1.50
38M
MM
IN.
ENCLOSURE
ENCLOSUREMOUNTINGDETAIL "A"
DATE G&W NO.
CUSTOMER
ORDER NO.
FOR RECORD
FOR APPROVAL-NO MORE WORK TO BE DONE UNTIL APPROVAL IS RECEIVED
PRINT IDENTIFICATION
ITEM NO.
This
draw
ing an
d the
infor
matio
n the
reon a
re an
d rem
ain th
e pr
oper
ty of
G&W
and a
re no
t to b
e cop
ied, re
prod
uce
d or d
iclos
ed to
othe
rs wi
thou
t the
ex
pres
sed w
ritten
cons
ent o
f G&W
.
G&W ELECTRIC Co.
* ALL PRIMARY DIMENSIONS ARE IN INCHES. ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
72.66[1846]
106.87[2715]
39.21[996]
11.00[279]
27.00[686]
TYP.
ADJUSTABLEENCLOSURE
MOUNTINGUP TO32.46[824]
3.00[76]TYP.
6.08[155]TYP.
3.00[76]TYP.
34.83[885]
ENCLOSUREMOUNTING
2.19[56]TYP.
8.00[203]
34.21[869]
TYP.
D97
00 2
LCR
AZ0
DWG.
NO.
:3D
MOD
EL M
C ER
RORS
1DR
AWIN
G M
C ER
RORS
13D
MOD
EL LA
ST C
HECK
ED W
ed D
ec 24
2014
01:39
:25 G
MT-
0600
CUS
TOM
ERDR
AWIN
G LA
ST C
HECK
ED W
ed D
ec 24
2014
01:40
:52 G
MT-
0600
STAN
DARD
SHEE
T 1 o
f 1
1 of 1SHEET:SCALE:Dec-24-14DATE:JQAPPR BY:
REVDRAWING NO.
D9700 2LCR AZ0Dec-24-14DATE:SHDRAWN BY:
BA13-SL06CAT. NO.:
THREE PHASE SOLID DIELECTRIC SWITCH
BA13-SL06
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
SWITCH ELECTRICAL INFORMATION
MAXIMUM DESIGN VOLTAGEIMPULSE LEVEL ( BIL )AC 1 MIN. WITHSTANDDC 15 MIN. WITHSTANDCURRENT CONTINUOUSCURRENT INTERRUPTING SYM.MOMENTARY CURRENT RMS ASYM.MAKING CURRENT RMS ASYM.1 SEC. RATING RMS SYM.
SWITCH WEIGHT 600 LBS / 273 KG
SEE NOTES FOR LIMITATIONS
KVKVKVKVAMPAMPKAKAKA
15.51103453630630202012.5
THREE LINE DIAGRAM
PLAN VIEW
NOTES:
1. SWITCHED WAY EQUIPPED WITH INTERNAL SPRING OPERATOR AND EXTERNAL PROVISIONS FOR PADLOCKING IN ALL POSITIONS.
2. UNFINISHED 304/304L STAINLESS STEEL MOUNTING PLATE WITH BOLTED 304/304L STAINLESS MECHANISM COVER PAINTED ASA 70 LIGHT GRAY. 304 STAINLESS STEEL ENCLOSURE FINISHED PADMOUNT GREEN MUNSELL 7GY3.29/1.5.
3. ENCLOSURE IS DESIGNED PER APPLICABLE SECTIONS OF ANSI/IEEE C37.74 & C57.12.29. ENCLOSURE IS TYPICAL AND SHOWS THE OVERALL DIMENSIONS ONLY, CONSTRUCTION DETAILS MAY VARY FROM THOSE DEPICTED. ENCLOSURE DOOR IS EQUIPPED WITH THREE POINT LATCH WITH PENTA HEAD BOLT AND PROVISION FOR PADLOCK.
4. WHEN ELBOWS, INSERTS, AND ANY OTHER ACCESSORIES ARE CONNECTED TO THE SWITCH, THE RATINGS OF EACH CONNECTED ASSEMBLY WILL BE THAT OFTHE LOWEST RATED COMPONENT OF THE ASSEMBLY
5. MOUNTING INFORMATION: THE FRAME OF THE SWITCH MUST BE ANCHORED TO THE PAD.THE FRAME IS EQUIPPED WITH 4 SLOTTED ANCHORING HOLES, EACH MEASURING
9/16" X 1". THE LOCATIONS OF THESE HOLES, REFERRED TO AS "FRAME MOUNTING" ARE SHOWN IN THE BACK VIEW AND LEFT VIEW. THE PAD MOUNT ENCLOSURE SHOULD BE SECURED TO THE PAD TO PROVIDE IT WITH ADDITIONAL STABILITY. EACH PAD MOUNT ENCLOSURE IS SHIPPED WITH 4 SECURING BRACKETS THAT ARE TO BE USED FOR THIS PURPOSE. THE SECURING BRACKETS CAN BE INSTALLED ANYWHERE ALONG THE INNER EDGE OF THE ENCLOSURE. SEE ENCLOSURE MOUNTING DETAIL "A" AND THE PLAN VIEW FOR MORE DETAILS ABOUT SECURING THE PAD MOUNT ENCLOSURE
TO THE PAD.
SHOWING OVERALL DIMENSIONSAND MAXIMUM DIMENSIONS
WHEN ENCLOSURE DOORS ARE OPEN.
FRONT
BACK
CABLETRAININGOUTLINES
ENTRANCESWAY
1
2
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
15.5KV 110KV BIL 600A DEADBREAK APPARATUS BUSHING PER IEEE 386 FIGURE 11
CONCRETEPAD
.25" STAINLESS STEELANCHOR BRACKETWITH .875" X 1.125"SLOTTED HOLESUPPLIED BY G&W
.625" DIA.HARDWARE(4)-SUPPLIEDBY USER
2.1956MMTYP.
1.50
38M
MM
IN.
ENCLOSURE
ENCLOSUREMOUNTINGDETAIL "A"
DATE G&W NO.
CUSTOMER
ORDER NO.
FOR RECORD
FOR APPROVAL-NO MORE WORK TO BE DONE UNTIL APPROVAL IS RECEIVED
PRINT IDENTIFICATION
ITEM NO.
BACK
SIDE
FRONT
HEIGHT42”
(1067mm)
Depth includes 16” cable compartments
Dimensions are approximate. Do not use for construction.
WIDTH40”
(1016mm)
DEPTH41”
(1042mm)
Two-way Trident Solid Dielectric Switches
G & W E L E C T R I C P A G E 2 2
Components for Three Phase Switches
oVerCurrent proteCtionFault interrupters are equipped with an encapsulated 500:1 or 1000:1 current transformer and a G&W self powered Vacuum Interrupter Control. Alternately, a wide variety of protective relay packages are available, includ-ing relays from SEL and other leading relay suppliers.
external Cts and external pts Metering or relaying accuracy current and potential transformers are available for use with protective relay packages.
operating HandleG&W will select the appropriate handle based on the application. Handles are operable via hook stick or rope rigging.
key interloCksKey interlocks may be used to ensure safe coordination of equip-ment. All Trident ways can be equipped with provisions for key interlocks. Key interlocks can be pro-vided, and factory installed if required.
auxiliary ContaCtsAuxiliary contacts are mounted internal to the mechanism housing to provide remote indication of switch contact position. One normally open and one normally closed Form C contact is provided. A junction box is available with terminal strip connections for up to four auxiliary contacts.
motor aCtuatorAutomation begins with the addition of motor actuators to a manual switch. These actuators can be factory installed for new equipment or retrofitted to switchgear installed in the field. (Refer to the Motor Operator catalog, MO11, for motor control options.)
p Example of integrated external transformer
p Side mounted motor actuator
p Key interlock
G & W E L E C T R I C P A G E 2 3
Overcurrent Protection Options
* Optional clear lid enclosure available (shown above on Type 2)
Type Trip Selection
Enclosure Rating
User Interface
Settings Available Notes
Type 1.0 Single or Three Phase NEMA 4X* Knobs Phase Only
Type 2.0 Three Phase NEMA 4X* Knobs Phase and Ground
Type 3.1 Single or Three Phase NEMA 4X*
Via computer us-
ing a program-ming port, or manually via the pushbut-tons on the front panel
Phase and Ground
Available as EZset or Plus
Type 4.1 NEMA 4X
Single or Three Phase NEMA 4X
Computer using a
Programming Port
Phase and Ground
Available as EZset or Plus
Type 4.1 IP68
Single or Three Phase
IP68 (submerged in 20’ of water for
20 days)
Computer using a
Programming Port
Phase and Ground
Available as EZset or Plus
Type 7.1 Single or Three Phase
IP68 (located within the mechanism
housing)
Computer using a
Programming Port
Phase and Ground
Available as EZset or Plus
G & W E L E C T R I C P A G E 2 4
Single Phase
Trident solid dielectric insulated switches provide the total life cycle cost and operational benefits of fuseless, electronically controlled, resettable overcurrent protection, with the safety and maintenance benefits of an environmentally friendly dead-front design.
The Trident utilizes G&W’s time proven, submersible epoxy insulation to fully encapsulate load and fault interrupting vacuum interrupters. This solid dielectric insulation eliminates the degradation of dielectric integrity commonly associated with oil insulated switchgear.
single pHaseTrident single phase, spring-assisted switchgear is avail-able for load break or fault interrupting switching. The compact units are ideal for switching residential loops and for oil fuse cutout replacements. Fault protection can be provided using vacuum interrupters with inte-gral current transformers and a variety of overcurrent controls.
The Single Phase Trident is available in a Front Access design, with operating handles and bushings on the same side of the switch, The switch can be mounted vertically (as shown on the right) or horizontally (as shown on page 19) to best meet the requirements of the application.
testingTrident switches are designed and tested to applicable stan-dards including IEEE C37.74 (IEEE C37.71 and C37.72), IEEE 386, IEC 60265, IEEE 592, and IEEE C57.12.28. All fault interrupter devices have passed IEEE C37.60. Trident switches are RUS accepted.
Fully encapsulated current transformers provide power and sensing for G&W’s solid state electronic controls. The con-trols emulate the most common time current curves (TCC) for power fuses, mechanical relays, and fuse links.
features and Benefits
Features Benefits
Epoxy Insulation (No oil or SF6, and true dead-front design)
No maintenance or monitoring system, lowest total life cycle costs
Dead-front design provides increased operator safety by eliminating all exposed live parts
Epoxy is inert, environmentally friendly, with no EPA usage restrictions
Resettable Vacuum Interrupter Mechanism No fuses or fuse links to stock and replace
Integral self-powered overcurrent protection available Integrated solution with fully encapsulated current transformers and no external power source or PT required
p Single phase Trident switch
G & W E L E C T R I C P A G E 2 5
Single Phase
Catalog numBering
ratings
Model One-line Diagram
Voltage (kv) Catalog Number
315 PL21-176-20-3FA
25 PL21-186-20-3FA
415 PS20-176-12-4FA
25 PS20-186-12-4FA
SIDE
FRONT
Load Break & Fault Interrupting Ratings
Voltage Class 15kV 25kV
Max System Voltage 15.5kV 27kV
BIL Impulse 110kV 125kV
Continuous Current 630A 630A
Load Break Current 630A 630A
AC Withstand, 1 minute 35kV 60kVAC Withstand, Production,
1 minute 34kV 40kV
DC Withstand, 15 minutes 53kV 78kV
Momentary Current, RMS, asym 20kA 20kA
Fault-Close 3-times, asym 20kA 20kA
Fault Interrupting Current, asym 12.5kA 12.5kA
1 Second Current, sym 12.5kA 12.5kALoad Break Switch
Mechanical Operations 2,000 2,000
Approximate Weight = 150 lbs. (68 kg)
Dimensions are approximate. Do not use for construction.
24”(610mm)
38”(965mm)
31”(787mm)
30”(762mm)