sp3263
DESCRIPTION
sPTRANSCRIPT
![Page 1: SP3263](https://reader031.vdocument.in/reader031/viewer/2022012404/577c790f1a28abe054914341/html5/thumbnails/1.jpg)
INSTALLATION INSTRUCTIONS FORSP32 / SP32 - EIT / SP32 - NS
SP63 / SP63 - EIT / SP63 - ES / SP63 - D
1. CARTON DETAILSThe unit is supplied in a carton. On receipt, please checkfor the following items :
a. Basic unit (3 poles) and a neutral pole.b. Front drive kitc. 4 nos. M3.5 x 16 mounting screws along with washers
and nuts in a polythene bag.d. 3 nos. M4 x 22 self tapping screws and template for door drilling in a polythene bag.e. For SP63-D, 4 nos. phase barriers are also supplied.
2. UNIT MOUNTINGMark the centre of operating shaft on the panel door basedon the hinge distance given in fig.1.
Paste the template (from outside the door) after aligningthe centre mark with the mark made in previous step.
Drill the holes on panel and panel door as in fig.1.
Mount the unit on the panel with 4 nos. M3.5 x 16 screws(supplied with the unit). Initially do not tighten the screwsfully. Check the alignment of the centre of the operatingshaft with the centre of Ø50 hole made on panel door forfixing the front drive. After making sure of the alignment,tighten the screws fully. Now, the appropriate fuse linkscan be mounted (ref. table 2)
For Din-rail mounting pull the din-rail clips (R & B poles)out, insert the unit onto 35 mm wide Dinrail & push theclips back.
In the case of SP32-NS & SP63-ES, remove the fuse coverand fuse holders ; locate the fuses in the fuse holders;insert the fuse holders along with fuses into the clips andfinally replace the cover. This is not applicable for somespecial SP32-NS / SP63-ES Switches which are not providedwith fuse holders.
For SP63-D click the phase barriers ( 4 Nos.) in the spaceprovided between the poles.
For ordering details of fuse links, refer table 2.
Always use GE POWER CONTROLS make fuse links only.
Fig. 4
SDF / SD DETAILS
All dimensions are in mm
GE POWER CONTROLS INDIA PRIVATE LTD.GE POWER CONTROLS INDIA PRIVATE LTD.GE POWER CONTROLS INDIA PRIVATE LTD.GE POWER CONTROLS INDIA PRIVATE LTD.GE POWER CONTROLS INDIA PRIVATE LTD.
Catalogue No. : SDG0300637 issue D
ADD-ON ACCESSORY KIT ORDERING DETAILS
TABLE - 1
TABLE - 2
FUSE ORDERING DETAILS :
Amp NS EIT ES DIN0002 SFA9311002 SFA8120002 SFA81210024 SFA9311004 SFA8120004 SFA81210046 SFA9311006 SFA8120006 SFA8121006 SFD8500006
10 SFA9311010 SFA8120010 SFA8121010 SFD850001016 SFA9311016 SFA8120016 SFA8121016 SFD850001620 SFA9311020 SFA8120020 SFA8121020 SFD850002025 SFA9311025 SFA8120025 SFA8121025 SFD850002532 SFA9311032 SFA8120032 SFA8121032 SFD850003236 SFA8120036 SFA8121036 SFD850003650 SFA8120050 SFA8121050 SFD850005063 SFA8120063 SFA8121063 SFD8500063
TABLE - 3
![Page 2: SP3263](https://reader031.vdocument.in/reader031/viewer/2022012404/577c790f1a28abe054914341/html5/thumbnails/2.jpg)
PANEL DRILLING DETAILS(View as seen from front of the door)
3. FRONT DRIVE MOUNTING
a. Insert front drive along with gasket (both supplied with theunit) in the Ø50 cut-out made on the panel door ( fig. 3).
b. Drive the three self tapping screws (supplied with the unit)from inside the panel door
c. See that handle is in "OFF" position
Note : Do not operate the Front drive before mounting.
Fig. 3
4. INSTRUCTIONS FOR USEa. Use max. 25 sq. mm. direct flexible cable Cu/Al for main
and neutral connections.
b. Operate the handle in the direction shown in fig.3 forswitching ON and OFF.
c. The door interlock ensures that the door cannot beopened when the SDF or SD unit is in ON position.
d. However, with door interlock defeat facility (available af-ter knocking out a window on the side of front drive), anauthorised person can defeat the door interlock by push-ing the interlock defeat actuator up with a screw driver.This interlock has an auto-reset feature so that it neednot be re-defeated while closing the door later.
e. For padlocking the switch in OFF position, the padlockplate that projects out of the Handle is pulled down andupto 3 padlocks of max 6 mm shackle dia can be used.
f. Always use fuse cover for SP32-EIT / SP32-NS / SP63-EIT and SP63-ES .
g. Do not use wire fuse.
fig. 1
CABLE DETAILS
Fig. 2
TIGHTENING TORQUE M 4 N-M
PEELED CABLE LENGTH D 11.2mm max
CABLE CROSS SECTION S 25 Sq. mm max
Shaft comingfrom switch
22B Pole
l Use Screw M5 X 34 for EIT / ES / NS.l Use Screw M5 X 25 for DIN.
5. INSTRUCTIONS FOR ADD-ONACCESSORY KITS
a) SWITCHED NEUTRAL
Remove Isolable Neutral. InsertNeutral Shaft along with circlipwhich is supplied with the unitinto B pole Align Switchedneutral with B Pole, drive two M5x 20 screws onto it.
b) AUXILIARY KIT + solid n
Remove Isolable Neutral. AlignAuxiliary kit with B pole. AlignIsolable Neutral as in Figureand Fasten. Use Screws as perthe Note below.
c) SWITCHED NEUTRAL + AUXILIARY KIT
Insert Neutral Shaft alongwith circlip which is suppliedwith switched neutral into Bpole (as shown in a)
Align & insert Switchedneutral into the shaft
Align & insert Auxiliary shaftonto Switched neutral
Drive two M5 x 40 screwsthrough Auxiliary andSwitched neutral
SWITCHEDNEUTRAL