sp60-18 rev3 cathodic protection

Upload: kmyson

Post on 06-Feb-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    1/138

    SPECIFICATION

    SP-60-18 Revision 3

    CATHODIC PROTECTION

    VALIDITY OF SPECIFICATION

    This document will be valid by directly printing the document from Sasol Intranet and

    validated by a registered Sasol Intranet user by completing the table below.

    Validity automatically expires 3 months after verification. Reinstatement of a document

    takes place by verifying pertinence and completing the next line in the table. If the

    document is found to be obsolete, it shall be destroyed or marked as such.

    It is forbidden to use obsolete or expired documents.

    Sequence

    Number

    Control

    Number

    Initials

    and

    Surname

    Signature

    Date

    of

    Verification

    Expiry

    Date

    1 2003-12-12

    2

    3

    4

    5

    6

    7

    8

    This Specification is protected by copyright and is the sole property of Sasol. The information is proprietary to Sasol and is for the sole useof the identified project or defined scope of work. Any unauthorised use, disclosure or copying or any other means of duplication orreproduction, is prohibited.Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    2/138

    SASOL SPECIFICATION SP-60-18

    CATHODIC PROTECTION

    Originator : (SIGNED)

    DG ROSS

    Reviewer : (SIGNED)

    DFM GOODWIN

    Approved by : (SIGNED)JP NELL Date : 16 MARCH 1988

    ISSUE DATE: APRIL 1988

    For interpretation of the Specification, the following person(s) can be contacted:

    GH Mller, BAR Machado, J Piorkowski, T Erasmus

    SUBSEQUENT REVISIONS

    A Revision Description sheet is included to assist in identifying the changes.

    Rev No Issue Date Proposed By Reviewed By Approved By Date

    2 Aug 2000 DG Ross BAR Machado C Thirion 5 June 2000

    3 Oct 2003 T Erasmus BAR Machado C Thirion 26 Nov 2003

    This Specification is protected by copyright and is the sole property of Sasol. The information is proprietary to Sasol and is for the sole useof the identified project or defined scope of work. Any unauthorised use, disclosure or copying or any other means of duplication orreproduction, is prohibited.Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    3/138

    Revision 3

    October 2003

    SASOL SPECIFICATION SP-60-18

    CATHODIC PROTECTION

    TECHNICAL COMMITTEE OF SPECIFICATION SP-60-18, Revision 3

    NAME DEPARTMENT AND / OR COMPANY

    BERGH, G (Gerhard) Sasol Infrachem Water Systems

    COOKE, JH (Jack) Electrical and Integrity, Natref

    ERASMUS, T (Theuns) Electrical Engineering, Sasol Technology

    HAYNES, GJ (Gerald) Sasol Technology Consultant

    HOLLER, RK (Rolf) Electrical and Integrity, Natref

    LOMBARD, ER (Sias) Electrical Engineering, Sasol Technology

    MACHADO, BAR (Tony) Electrical Engineering, Sasol Technology

    MLLER, GH (Grant) Electrical Engineering, Sasol Technology

    OOSTHUIZEN, PC (Pieter) Sasol Oil

    WILKINSON, W (William) Reliability, Sasol Synfuels

    Page i of ix

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    4/138

    Revision 3

    October 2003

    SASOL SPECIFICATION SP-60-18

    CATHODIC PROTECTION

    REVISION SHEET

    REVISION 3

    Specification SP-60-18, Revision 2 is revised in its entirety.

    Page ii of ix

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    5/138

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    6/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    Subject to SASOLs review of the report and acceptance of the conceptual design proposal, the design

    specialists scope of work should then be extended to cover:

    a. The additional site survey in order to permit the preparation of a detailed cathodic protection

    design complete with a detailed technical specification and bill of quantities. The latter shall

    permit the procurement or a Request For Quotation (RFQ) document to be issued to enable

    cathodic protection construction contractors to carry out the cathodic protection installation.

    b. The necessary liaison with the engineering contractor of the process plant, transmission or

    distribution pipeline which is to be cathodically protected, so as to ensure the inclusion of all

    cathodic protection field installation details in the final plant / pipeline engineering drawings.

    c. The site supervision, quality control and commissioning of the completed cathodic protection

    system.

    Page iv of ix

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    7/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    PAGETABLE OF CONTENTS

    PAGE

    1 GENERAL.............................................................................................................................. 1

    1.1 SCOPE ........................................................................................................................ 1

    1.2 LEGAL REQUIREMENTS........................................................................................ 2

    1.3 ABBREVIATIONS .................................................................................................... 2

    1.4 DEFINITIONS............................................................................................................ 9

    1.5 PRECEDENCE......................................................................................................... 17

    1.6 MATERIAL REQUIREMENTS .............................................................................. 17

    1.7 GUARANTEE PERIOD........................................................................................... 17

    2 REFERENCE DOCUMENTS............................................................................................ 18

    2.1 SOUTH AFRICAN NATIONAL STANDARDS (SANS) AND SOUTH

    AFRICAN BUREAU OF STANDARDS (SABS) CODES OF PRACTICE AND

    SPECIFICATIONS................................................................................................... 18

    2.2 SOUTH AFRICAN NATIONAL STANDARDS (SANS) AND SOUTHAFRICAN BUREAU OF STANDARDS / INTERNATIONAL

    ELECTROTECHNICAL COMMISSION (SABS IEC) SPECIFICATIONS.......... 21

    2.3 SOUTH AFRICAN NATIONAL STANDARDS (SANS) AND SOUTH

    AFRICAN BUREAU OF STANDARDS / INTERNATIONAL

    ORGANISATION FOR STANDARDISATION (SABS ISO) STANDARDS....... 21

    2.4 AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME)

    STANDARDS........................................................................................................... 22

    2.5 AMERICAN SOCIETY FOR THE TESTING OF MATERIALS (ASTM)............ 222.6 AMERICAN PETROLEUM INSTITUTE (API)..................................................... 23

    2.7 NATIONAL ASSOCIATION OF CORROSION ENGINEERS (NACE)

    RECOMMENDED PRACTICES............................................................................. 23

    2.8 BRITISH STANDARDS INSTITUTION (BS) SPECIFICATIONS....................... 24

    2.9 RAL DEUTSCHES INSTITUT FR GTESICHERUNG UND

    KENNZEICHNUNG RAL-FARBEN ................................................................... 25

    2.10 DEUTSCHES INSTITUT FR NORMUNG (DIN)................................................ 25

    2.11 INTERNATIONAL ELECTROTECHNICAL COMMISSION (IEC)PUBLICATIONS...................................................................................................... 25

    Page v of ix

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    8/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    PAGE2.12 INTERNATIONAL ORGANISATION FOR STANDARDISATION (ISO)

    STANDARDS........................................................................................................... 25

    2.13 SWEDISH STANDARDS INSTITUTION (SIS) STANDARDS............................ 26

    2.14 SASOL SPECIFICATIONS, DATA SHEETS AND STANDARD DRAWINGS.. 26

    3 CP SYSTEM REQUIREMENTS....................................................................................... 28

    3.1 SPECIALIST CP CONSULTANT AND CP CONTRACTOR ............................... 28

    3.2 ON SITE INVESTIGATIONS / SURVEY .............................................................. 29

    4 CATHODIC PROTECTION DETAILED DESIGN REQUIREMENTS...................... 39

    4.1 GENERAL CONSIDERATIONS ............................................................................ 39

    4.2 COATINGS AND CP............................................................................................... 39

    4.3 CHOICE OF CP SYSTEM....................................................................................... 41

    4.4 DETAILED CP DESIGN CALCULATIONS.......................................................... 42

    4.5 SPECIAL DESIGN CONSIDERATIONS ............................................................... 47

    5 CONSTRUCTION, DRAWINGS, RECORDS AND COMMISSIONING.................... 48

    5.1 CONSTRUCTION, TESTING AND INSPECTION ............................................... 495.2 COMMISSIONING, AS-BUILT DRAWINGS AND RECORDS .......................... 51

    5.3 SPARE PARTS......................................................................................................... 55

    5.4 INSTALLATION, OPERATION AND MAINTENANCE MANUALS ................ 55

    6 CP ACCEPTANCE CRITERIA ........................................................................................ 55

    6.1 ACCEPTANCE CRITERIA..................................................................................... 55

    6.2 ASSESSING THE IR FREE STRUCTURE-TO-ELECTROLYTE

    POTENTIAL............................................................................................................. 57

    7 OPERATION AND MAINTENANCE OF THE CP SYSTEM ...................................... 59

    8 CATHODIC PROTECTION MATERIALS AND THE INSTALLATION

    THEREOF............................................................................................................................ 61

    8.1 GENERAL................................................................................................................ 61

    8.2 MANUAL TAP CHANGE AND AUTOMATIC THYRISTOR CONTROLLED

    TRANSFORMER RECTIFIER UNITS ................................................................... 61

    Page vi of ix

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    9/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    PAGE9 ELECTRICAL CONSTRUCTION ................................................................................... 63

    9.1 GENERAL................................................................................................................ 63

    9.2 OUTPUT CONTROL............................................................................................... 65

    9.3 METERS AND MONITORS ................................................................................... 66

    9.4 SURGE PROTECTION............................................................................................ 67

    9.5 WIRING AND BUSBARS....................................................................................... 68

    9.6 COLOUR CODING AND LABELLING................................................................. 69

    9.7 CABLE ENDS AND TERMINALS......................................................................... 71

    9.8 EARTHING .............................................................................................................. 72

    9.9 SPARES.................................................................................................................... 72

    9.10 COMPONENT LAYOUT ........................................................................................ 73

    9.11 AUXILIARY AC SUPPLY...................................................................................... 74

    9.12 CABINET CONSTRUCTION.................................................................................. 74

    9.13 COATING................................................................................................................. 76

    9.14 INSPECTION AND TESTING ................................................................................ 76

    9.15 DOCUMENTATION................................................................................................ 78

    9.16 GUARANTEE .......................................................................................................... 78

    9.17 MANUFACTURER QUALIFICATIONS ............................................................... 78

    10 CONCRETE PLINTHS ...................................................................................................... 78

    11 CORROSION RESISTANT SILICON IRON ANODES ................................................ 79

    11.1 GENERAL CONSIDERATIONS ............................................................................ 79

    11.2 GENERAL ANODE DETAILS ............................................................................... 80

    11.3 CHEMICAL COMPOSITION.................................................................................. 82

    11.4 QUALITY CONTROL AND TESTING.................................................................. 82

    12 TYPICAL IMPRESSED CURRENT ANODE INSTALLATION DETAILS............... 83

    12.1 DEEP VERTICAL AND SHALLOW VERTICAL ANODE GROUNDBED

    SYSTEMS................................................................................................................. 83

    12.2 HORIZONTAL AND DISTRIBUTIVE ANODE GROUNDBED SYSTEMS....... 84

    12.3 MIXED METAL OXIDE (MMO) / PRECIOUS METAL OXIDE (PMO)

    ANODES .................................................................................................................. 85

    12.4 ANODE DIMENSIONS AND TITANIUM SUBSTRATE GRADES.................... 86

    Page vii of ix

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    10/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    PAGE12.5 ANODE LOADING AND OPERATING PARAMETERS..................................... 88

    12.6 ANODE CABLE CONNECTION............................................................................ 89

    12.7 CHEMICAL AND PERFORMANCE TESTING OF ANODES............................. 90

    13 IMPRESSED CURRENT CARBONACEOUS ANODE BACKFILL MATERIAL .... 91

    13.1 INTRODUCTION AND GENERAL CONSIDERATIONS.................................... 91

    13.2 CHEMICAL COMPOSITION.................................................................................. 92

    13.3 PARTICLE SIZE DISTRIBUTION (PSD) .............................................................. 92

    13.4 SHIPPING AND PACKAGING............................................................................... 93

    14 CATHODIC PROTECTION CABLING.......................................................................... 93

    14.1 INTRODUCTION .................................................................................................... 93

    14.2 GENERAL PROPERTIES OF INSULATING COMPOUNDS.............................. 94

    14.3 CABLE AND CABLE INSULATION COMPLIANCE.......................................... 95

    14.4 CP CABLE REQUIREMENTS................................................................................ 96

    14.5 CABLE INSTALLATION AND IDENTIFICATION............................................. 97

    15 EXOTHERMIC WELDING / PIN BRAZING CABLE CONNECTION DETAILS ... 9715.1 CABLE CONNECTIONS TO PIPES AND REPAIR TO COATINGS .................. 97

    15.2 SURFACE PREPARATION.................................................................................... 98

    15.3 PIN BRAZING / EXOTHERMIC WELDING......................................................... 98

    15.4 TESTING.................................................................................................................. 99

    15.5 WELD POWDER / CABLE COMBINATION........................................................ 99

    15.6 PRECAUTIONS..................................................................................................... 100

    15.7 REINSTATEMENT OF THE COATING SYSTEM ............................................. 101

    16 PERMANENT REFERENCE ELECTRODES.............................................................. 101

    16.1 GENERAL CONSIDERATIONS .......................................................................... 101

    16.2 MANUFACTURER QUALIFICATIONS ............................................................. 101

    16.3 PERMANENT REFERENCE ELECTRODE (PRE) CONSTRUCTION ............. 101

    16.4 PERMANENT REFERENCE ELECTRODE (PRE) STABILITY........................ 103

    17 CATHODIC PROTECTION TEST POINTS................................................................. 103

    17.1 INTRODUCTION .................................................................................................. 103

    17.2 LOCATION OF TEST POSTS / STATIONS ........................................................ 10417.3 TYPICAL CP TEST POSTS .................................................................................. 105

    Page viii of ix

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    11/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    PAGE18 SOLID STATE DC DECOUPLING DEVICES ............................................................. 108

    18.1 INTRODUCTION .................................................................................................. 108

    18.2 ELECTRICAL CONSTRUCTION ........................................................................ 109

    18.3 ENCLOSURE CONSTRUCTION ......................................................................... 111

    18.4 INSPECTION AND TESTING .............................................................................. 111

    18.5 DOCUMENTATION.............................................................................................. 112

    18.6 GUARANTEE ........................................................................................................ 112

    18.7 MANUFACTURER QUALIFICATIONS ............................................................. 112

    19 INSULATING FLANGE MATERIALS ......................................................................... 113

    19.1 GENERAL CONSIDERATIONS .......................................................................... 113

    19.2 MATERIAL SPECIFICATIONS ........................................................................... 113

    19.3 IDENTIFICATION / LABELS, OPERATING INSULATING FLANGE, NO

    ATTACHMENTS TO PIPEWORK PERMITTED .............................................. 115

    19.4 MONOLITHIC INSULATING JOINTS................................................................ 115

    19.5 INTERNAL PIPE LINING FOR COOLING WATER SERVICE ........................ 116

    20 HIGH POTENTIAL SACRIFICIAL MAGNESIUM ANODES (SOIL USE)............. 120

    20.1 GENERAL CONSIDERATIONS .......................................................................... 120

    20.2 MAGNESIUM ANODE CHEMICAL COMPOSITION....................................... 121

    20.3 HIGH POTENTIAL MAGNESIUM ANODE PHYSICAL PROPERTIES .......... 121

    20.4 ANODE CABLE AND CABLE CONNECTION.................................................. 122

    20.5 ELECTROCHEMICAL PROPERTIES ................................................................. 123

    20.6 TESTING AND REVIEWAL................................................................................. 123

    20.7 TYPICAL INSTALLATION DETAILS ................................................................ 123

    21 AC MITIGATION EARTH ELECTRODE.................................................................... 124

    21.1 ZINC TUBE MATERIAL SPECIFICATION........................................................ 124

    21.2 ZINC TUBE DIMENSIONS .................................................................................. 125

    21.3 ZINC TUBE CHEMICAL COMPOSITION.......................................................... 125

    21.4 HARDNESS MEASUREMENTS.......................................................................... 125

    21.5 METALLOGRAPHY............................................................................................. 126

    Page ix of ix

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    12/138

    Revision 3

    October 2003

    SASOL SPECIFICATION SP-60-18

    CATHODIC PROTECTION

    1

    1.1

    1.1.1

    a.

    b.

    c.

    d.

    e.

    1.1.2

    1.1.3

    GENERAL

    SCOPE

    This Specification defines the minimum and mandatory requirements governing the design,

    application, installation and commissioning of a Cathodic Protection (CP) system for the

    following:

    Pipelines, process, fire water, cooling water and utility piping, as well as pipes located

    inside chambers;

    Pipeline casings (cased crossings);

    On-grade storage tank bottoms and the internal surface of storage tanks;

    Well casings;

    Water boxes of heat exchangers,

    installed inside and / or outside the SASOL plant(s) battery limits.

    In the event of any detail that is not fully addressed in this specification and that is warranted

    to be carried out by the contractor, the work shall be performed in accordance with the

    relevant applicable codes and best recognised engineering practices in the CP industry. The

    contractor shall develop detailed specifications, procedures and method statements required

    to perform the CP design during the engineering phase of work and this shall be submitted to

    SASOL for review and approval prior to construction, supply and / or installation work.

    The specification covers the general requirements of the CP system. CP may be achieved

    through the use of Sacrificial Anode CP (SACP) or Impressed Current CP (ICCP).

    Page 1 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    13/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    1.1.4

    1.1.5

    1.2

    a.

    b.

    c.

    d.

    e.

    1.3

    AC interference mitigation may be achieved through the use of pipeline-earth grounding

    systems, in conjunction with solid state DC decoupling devices. It must not adversely affect

    or interfere with the CP system.

    The details and extent of the plant or structure equipment required to be cathodically

    protected, the site / locality and the meteorological data shall be both specified and supplied

    by SASOL and / or the main contractor.

    LEGAL REQUIREMENTS

    The SASOL factories are subject to the statutory requirements of the following Acts and all

    CP installations shall meet the requirements of these Acts:

    The National Environmental Management Act (NEMA) - Act 107 of 1998;

    The Occupational Health and Safety Act with Regulations - Act 85 of 1993;

    The Mine Health and Safety Act - Act 29 of 1996;

    The Minerals Act - Act 50 of 1991;

    The National Water Act - Act 36 of 1998.

    ABBREVIATIONS

    The following CP abbreviations have been used:

    A Ampere

    A / m Ampere per metre square

    AC Alternating Current

    AFC Approved For Construction

    A.hr / kg Ampere hours per kilogram (Electro-chemical Consumption Rate)

    Page 2 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    14/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    Al Aluminium

    API American Petroleum Institute

    A.y Ampere-years

    AQL Acceptable Quality Level

    ASME American Society of Mechanical Engineers

    ASTM American Society for the Testing of Materials

    Br Bromine

    BSI British Standards Institute

    C Carbon

    CD Current Drainage

    CIP Close Interval Potential

    COC Certificate of Compliance

    CP Cathodic Protection

    Cr Chromium

    Cu Copper

    CuSO4 Copper Sulphate

    Cu-Ti Copper - Titanium

    DB Distribution Board

    DC Direct Current

    DCVG Direct Current Voltage Gradient

    DIN Deutsche Institut fr Normung

    ECTFE Ethyl Carbo Tetra-Fluoro-Ethylene

    EPR Earth Potential Rise

    ETFE Ethyl Tetra-Fluoro-Ethylene

    Page 3 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    15/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    Ex Hazardous Classified Equipment

    EXW Exothermic Welding

    F Fluorine

    FBE Fusion Bonded Epoxy

    Fe Iron

    Fe-Si Silicone Iron

    FDU Forced Drainage Unit

    GC Grounding Cell

    g / ml grams per millilitre

    GIS Geographical Information System

    GPS Global Positioning System

    H2SO4 Sulphuric Acid

    HDPE High Density Polyethylene

    HMWPE High Molecular Weight Polyethylene

    HVTL High Voltage Transmission Line / High Voltage Power Line

    Hz Hertz

    ICCP Impressed Current Cathodic Protection

    ID Inner Diameter

    IEC International Electrotechnical Commission

    IJ Insulating Joint

    IF Insulating Flange

    IP Ingress Protection

    IR Ohmic Voltage Drop

    ISO International Organisation for Standardisation

    Page 4 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    16/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    IrO2 Iridium Oxide

    kg kilogram

    kg / m kilogram per cubic metre

    kPa kilopascal

    kV kilovolt

    kV / mm kilovolt per millimetre

    kW kilowatt

    LCD Liquid Crystal Display

    LMPE Low Molecular Weight Polyethylene

    m metre

    mA / m Milli-ampere per Square Metre

    Mg Magnesium

    mH Milli-henry

    m Milli-ohm

    mA Milli-ampere

    MIC Microbial Induced Corrosion

    Mil Thousandth of an Inch

    MMO Mixed Metal Oxide

    MMP Maximum Meter Point

    MMWPE Medium Molecular Weight Polyethylene

    Mn Manganese

    Mo Molybdenum

    MON Monitor

    MOV Metal Oxide Varistor

    Page 5 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    17/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    MPa Megapascal

    mV Milli-volt

    mV / C Milli-volt per Degree Celsius

    NACE National Association of Corrosion Engineers

    NDU Natural Drainage Unit

    NDT Non Destructive Testing

    NPS Nominal Pipe Size

    OD Outer Diameter

    OMM Operation and Maintenance Manual

    OWS Oily Water Sewer

    PC Printed Circuit

    PCB Polycarbonate Based

    PDF Portable Document Format

    PE Polyethylene

    pH Level of Acidity or Alkalinity

    PIV Peak Inverse Voltage

    PMO Precious Metal Oxide

    PO Purchase Order

    PPI Probable Performance Index

    PPM Parts Per Million

    PRE Permanent Reference Electrode

    PSD Particle Size Distribution

    psi Pounds Per Square Inch

    P-TP Plant Test Post

    Page 6 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    18/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    PTFE Poly-Tetra-Fluoro-Ethylene

    PVC Poly-Vinyl-Chloride

    PVDF Poly-Vinylidene Fluoride

    QCP Quality Control Plan

    Pub Publication

    RE Reference Electrode

    RFQ Request For Quotation

    RMS Root Mean Square

    RP Recommended Practice

    R-TP Recording Test Posts

    SAACE South African Association of Consulting Engineers

    SABS South African Bureau of Standards

    SACP Sacrificial Anode Cathodic Protection

    SANS South African National Standards

    SEM Scanning Electron Microscope

    Si Silicon

    SI System International

    SIS Swedish Standards Institution

    SP Specification

    SPIR Spare Parts Interchange-ability Record

    SRB Sulphate Reducing Bacteria

    SS Stainless Steel

    SS-DCD Solid State - Direct Current Decoupling Device

    STDD Standard Drawing

    Page 7 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    19/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    SWA Steel Wire Armour

    Ta Tantalum

    Ta2O5 Tantalum Oxide

    TDS Technical Data Sheet

    Ti Titanium

    TP Test Point / Test Post

    TP-R Reference Monitoring Test Post

    TRU Transformer Rectifier Unit

    V Volt

    +VE Positive Terminal

    -VE Negative Terminal

    XLPE Cross-linked Polyethylene

    Zn Zinc

    % IR Percentage Ohmic Voltage Drop

    % Percentage

    C Degrees Celsius

    F Degrees Fahrenheit

    micro

    m micro metre

    s micro second

    .m micro Ohm metre (unit of measurement for resistivity)

    Ohm

    cm Ohm Centimetre

    Page 8 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    20/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    1.4 DEFINITIONS

    ANAEROBIC Oxygen deficient environment.

    ANAEROBIC BACTERIA Also called sulphate reducing bacteria. A type of bacteria

    which corrodes steel and is present only in the absence of

    oxygen (anaerobic). When they are present, the protective

    potential must be raised to -0,95 V.

    ANODE DISTRIBUTIONCABINET

    A steel cabinet containing a bulbar to which is joined theanode cables as well as the main anode groundbed ring main

    cable(s).

    ANODIC GRADIENT Gradient arising in the soil due to the current flow through

    the soil from the anode(s).

    ANODE GROUNDBED An anode groundbed consisting of a number of impressed

    current anodes joined to a common positive rectifier cable.

    The anodes are encapsulated in coke to increase their life and

    decrease the resistance to earth. The anode groundbed is onaverage 100 m to 150 m long and a minimum of 2,5 m deep.

    APPROVAL OR

    APPROVED BY SASOL

    Written agreement or authorisation by SASOL. All requests

    for approval shall be submitted in writing and any proposed

    deviation from the specified requirements shall be fully

    explained and motivated.

    ANODE (IMPRESSED

    CURRENT)

    Any buried or submerged metal (or graphite) which is

    connected to the positive terminal of a transformer rectifier

    and serves to introduce current into the earth. CP anodes

    normally consist of a silicon iron alloy, containing 14% to

    17% silicon, and measuring 1,1 m long and 0,075 m

    diameter. Centrifugally cast tubular anodes have proven to

    be the most reliable and effective anodes at SASOL.

    Generally an anode is defined as any metal in which current

    flows from it to the electrolyte.

    Page 9 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    21/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    ANODE (SACRIFICIAL) A metal which is more electro-negative in potential than

    steel and which when buried or immersed confers protection

    to the latter when electrically connected to it. For buried

    pipelines sacrificial anodes generally consist of magnesium.

    ANODIC AND CATHODIC

    AREAS

    See Corrosion.

    BONDING CABINET A steel cabinet used to bond two or more pipelines

    electrically.

    BYPASS CURRENT The current drained from a pipeline to a railway line, when

    the latter is at very negative potential. Under such conditions,

    the transformer rectifier temporarily shuts down.

    CATHODE (IMPRESSED

    CURRENT)

    Any buried or submerged metal which is connected to the

    negative terminal of a transformer rectifier. Generally a

    cathode is defined as any metal in which current flow is

    always from the earth to the cathode.

    CATHODIC PROTECTION An active electrochemical method of corrosion protection in

    which all areas of a metallic surface are rendered cathodic.

    CLOSE POTENTIAL

    SURVEY

    A technique whereby the pipe potential is measured every

    metre along the length of the pipeline.

    COKE An electrically conducting form of carbon. It is used in

    granular form to surround each individual anode in order to

    form one long extended anode, termed the anode groundbed.

    It decreases the resistance to earth and increases the life ofthe individual anodes.

    COKE BREEZE An inferior carbonaceous backfill material generally termed

    metallurgical coke or coke breeze. It nominally contains less

    than 85% fixed carbon and high amounts of sulphur and ash.

    CONTINUITY BOND An electric cable welded to both sides of a potentially

    insulating joint, such as a coupling or flange, in order to

    ensure the electrical continuity.

    Page 10 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    22/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    CONTRACTOR /

    MANUFACTURER

    Company engaged to perform the work covered by the

    specification (successful supplier or bidder).

    CORROSION An electrochemical process resulting in metal dissolution

    and degradation. A buried or submerged metal forms anodic

    and cathodic areas on its surface with consequent flow of

    electric current between them. Corrosion occurs at the anodic

    areas.

    DATA SHEETS All necessary drawings, tabulations, sketches and relevant

    documentation which SASOL will submit with a RFQ or PO,

    to clearly indicate the technical, electrical and physical

    requirements of the equipment, together with information

    that is required to be submitted by the manufacturer.

    DC DECOUPLING

    DEVICE

    A solid state device used for two main purposes. One is to

    disconnect two metal systems, of which one is under CP and

    the other is not, while at the same time permitting continuity

    in any AC circuit, for example an earthing system connectedto a pipeline via this device. The other use is as a surge

    arrester whereby it blocks DC voltages up to several volts,

    but readily passes current at higher voltages (e.g. AC fault

    currents and lightning). Its operation does not depend on the

    moisture content of the soil, is easily inspected, tested and

    more reliable than a polarisation cell or grounding cell.

    DEEP WELL GROUND-

    BED

    One or more anodes installed vertically in a column, the top

    most anode being at a nominal depth of 15 m or more below

    the earths surface.

    DRAIN POINT That part of the pipeline connected to the negative terminal

    of the TRU.

    EARTHING The technique of using a buried electrode in order to

    decrease the voltage to earth of a particular structure.

    ELECTRODE An electrode is a solid electrical conductor which discharges,

    or picks up, current from an electrolyte.

    Page 11 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    23/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    ELECTRODE

    (REFERENCE

    ELECTRODE [HALF

    CELL])

    The voltage difference between an electrode and the

    electrolyte cannot be measured in absolute terms, but only

    with respect to a special reference electrode, whose own

    potential does not alter regardless of the solution in which it

    is immersed. A reference electrode is also referred to as a

    half cell. In CP of buried pipelines, a copper / copper

    sulphate reference electrode (Cu / CuSO4) is used.

    It consists of a copper rod in a saturated copper sulphatesolution, all housed in a suitable polymer housing and

    possesses a porous plug at the bottom to permit current to

    flow, enabling one to take potential measurements.

    ELECTROLYSIS

    (ELECTROLYTIC

    CORROSION)

    Electrolysis or electrolytic corrosion refers to the corrosion

    caused by stray electric currents flowing in the ground. 1 A

    flowing for 1 year corrodes 9 kg of steel.

    ELECTROLYTE A medium, usually liquid, in which the flow of electric

    current is by means of cations and anions. Typicalelectrolytes are water and its solutions, acids, etc., and the

    soil.

    EXOTHERMIC WELDING The universal method of welding a copper cable to a steel

    surface. The method is quick and simple and generates far

    less heat than brazing or arc welding, which would otherwise

    damage the coating and lining. Pin brazing / stud welding is

    a newer and quicker method, which generates far less heat

    than exothermic welding, but is very costly in comparison.

    FORCED DRAINAGE

    UNIT

    A transformer rectifier using the railway line as the anode is

    referred to as a forced drainage unit.

    FOREIGN SERVICE A structure lying or buried in the ground belonging to

    another owner. Typical examples are pipelines, cables,

    railway lines and electricity pylons.

    GALVANIC CORROSION A form of corrosion caused by one metal in electrical

    contact with another and at different natural potentials or

    separated in the galvanic series.

    Page 12 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    24/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    HALF CELL Another name for reference electrode. See Electrode.

    HOLIDAY A defect in the structure coating system also referred to as

    coating defects.

    HOLIDAY DETECTOR An instrument for detecting coating defects.

    HYGROSCOPIC A material that has a high affinity for water.

    INORGANIC Compounds composed of elements other than carbon. A few

    simple compounds of carbon including carbon monoxide,

    carbon dioxide, carbonates and cyanides, are generally

    considered inorganic.

    INSULATING JOINT /

    FLANGE

    A joint which is electrically insulating. An insulating flange

    normally consists of an insulating gasket, insulating bolt

    sleeves and insulating washers. An insulating joint is a

    complete joint consisting of insulating epoxies embedded in

    a spigot and socket type joint. An insulating joint nominally

    cost six to eight times more than an insulting flange.

    METAL OXIDE

    VARISTOR

    A metal oxide varistor is an electrical device used as a

    voltage arrester. It has a high resistance at low voltages and

    low resistance at high voltages.

    MONOLITHIC JOINT Immovable (flange-less) electrical insulating fitting rated to

    handle the operating pipe pressure.

    NATIVE STATE Natural state or potential of a pipeline or structure.

    NATURAL DRAINAGEUNIT

    A unidirectional bond from a pipeline to an electrifiedrailway line. It permits current flow only when the rail is at

    negative potential and consists of one or more diodes, fuses,

    surge arresters, etc. It is a passive device requiring no

    external source of power.

    NATURAL POTENTIAL Also called the corrosion potential. It is the potential of

    steel buried in the ground without receiving current from an

    external source.

    Page 13 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    25/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    OVER PROTECTION When the pipe potential is too negative, the coating may be

    damaged in the sense that it becomes detached from the steel

    pipe, also referred to as cathodic disbondment. There is no

    universal agreement as to what the maximum negative value

    should be, but the most commonly accepted value of -2,5 V

    is used, where no stray currents are present. This potential

    must exclude the IR error associated with normal potential

    measurements.

    PIPE INVERT DEPTH Depth of ground cover from surface to the bottom of the

    pipe.

    PIPE OVERT DEPTH Depth of ground cover from surface to the top of the pipe.

    PIPE POTENTIAL The voltage difference between a pipeline and a reference

    electrode inserted in the ground (also known as pipe-to-soil

    potential).

    POLARISATION The change in metal potential upon passage of current. The

    normal potential of steel in the ground is about -0,5 V and if

    current enters it via the electrolyte the potential will become

    more negative, say -1,0 V.

    Polarisation can take place slowly over weeks or months, by

    which the potential becomes even more negative and the

    current required diminishes. The latter depends on the

    coating quality.

    POLARISATION CELL A DC electrolytic varistor / decoupling device. It consists of

    two metal plates in a suitable electrolyte. The cell passes AC

    at all voltages but blocks DC below a certain voltage, but

    conducts above a certain voltage limit. By choosing different

    metals and electrolytes a number of different blocking

    voltages may be achieved. The steady state AC is generally

    limited to 0,01% of the maximum surge current. The cells

    need constant toping up and cleaning and are not as reliable

    as a solid state device.

    Page 14 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    26/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    PROTECTION LIMITS The limits in pipe potential between which a cathodically

    protected pipe should operate. The lower limit is -0,95 V for

    complete corrosion protection of the steel substrate, and the

    upper limit is -2,5 V in order to avoid coating damage. The

    value of -2,5 V is often impossible to adhere to in the

    presence of stray currents.

    PROTECTION

    POTENTIAL

    The minimum IR free pipe potential in order to achieve

    protection. It varies from metal to metal. The protectionpotential for steel ranges between -0,85 V to -0,95 V

    depending on the oxygen content of the electrolyte.

    RAIL RECORDING The potential of the rail (fluctuation) recorded over time.

    REVIEWED/REVIEWAL A formal 5-day hold period on the planning schedule while

    SASOL reviews / considers the relevant information or

    proposed deviations; all communication to be confirmed in

    writing

    SILICON IRON ANODES See Impressed Current Anode.

    SOIL AND PIPELINE

    VOLTAGE GRADIENTS

    The voltage gradients arising in the soil in the immediate

    vicinity of coating defects, as the current flows (CP or DC

    traction) to the bare steel (coating defect) through, the soil.

    SOIL RESISTIVITY The specific electrical resistance of the soil. The lower the

    resistivity, the higher the corrosivity of the soil. It is

    commonly measured on site by a technique called the

    Wenner Four method.

    STRAY CURRENTS (DC) The flow of DC electric currents in the ground which follow

    a course other than that intended. The most frequent cause of

    DC stray currents is from electrified railway lines, and of a

    fluctuating nature. Another source is that from adjacent CP

    systems.

    Page 15 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    27/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    TEST POINT Consists of a cable welded to the pipe or cleated to the

    inside of a chamber wall and connected to an insulated

    stainless steel stud protruding through the wall. It permits a

    quick and vandal resistant method of measuring the pipe

    potential. The potential measurement will however, contain

    the IR error.

    TEST POST A free standing post protruding about 0,6 m above the

    ground and containing a cable welded to the pipe andextending to the top in a suitable terminal. It permits the

    ready determination of the On pipe potential at any

    location.

    TRANSFORMER

    RECTIFIER UNIT

    An electrical apparatus which converts AC voltages to low

    DC voltages.

    UNDER- PROTECTION When the pipe is only partially protected, which is indicated

    by a potential of between -0,7 V to -0,85 V.

    VIKING JOHNSON

    COUPLING

    A flexible coupling used to mechanically join two sections

    of steel, plastic or concrete pipe materials.

    VOLTAGE SURGES Also called voltage transients. A voltage, higher than

    normal operating voltage, generally of short duration, which

    enters the transformer rectifier or natural drainage unit

    (NDU), either from the AC or DC side. It does great

    damage unless measures are taken to contain it.

    WENNER FOUR

    ELECTRODE METHOD

    A soil resistivity test method covered in ASTM G57,

    utilising four electrodes spaced equidistant to one another.

    The electrode separation distance equates to the average

    depth measured in the soil. Current is injected into the outer

    two electrodes and the potential drop is measured between

    the inner two electrodes and the resistivity is then calculated.

    Page 16 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    28/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    1.5 PRECEDENCE

    Any conflict between the technical requirements stated in the RFQ or PO and the technical

    requirements of this Specification shall be referred to SASOL for clarification. The

    precedence of purchase documents is as follows:

    a.

    b.

    c.

    d.

    1.6

    1.7

    The technical requirements specified in the RFQ or PO including terms, conditions

    and legal requirements;

    Data sheets;

    This Specification;

    Documents referenced in this Specification.

    MATERIAL REQUIREMENTS

    The material requirements shall detail all of the necessary drawings, tabulations, sketches,

    technical data, materials specification and relevant documentation which will be issued with

    a RFQ and / or PO.

    The latter shall clearly indicate the technical, electrical, metallurgical and physical

    requirements of any equipment, together with the information that is required to be

    submitted by the manufacturer.

    GUARANTEE PERIOD

    The contractor shall guarantee the CP system for a 36 month period, which shall commence

    from the date of commissioning.

    Page 17 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    29/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    2 REFERENCE DOCUMENTS

    Where reference is made to a code, specification or standard, the reference shall be taken to

    mean the latest edition of the code, specification or standard, including addenda,

    supplements and revisions thereto.

    2.1 SOUTH AFRICAN NATIONAL STANDARDS (SANS) AND SOUTH AFRICAN

    BUREAU OF STANDARDS (SABS) CODES OF PRACTICE AND SPECIFICATIONS

    SANS 10086-1 / SABS 086 The installation, inspection and maintenance of

    equipment used in explosive atmospheres Part 1:

    Installations including surface installations on mines

    SANS 10089-2 / SABS 089-2 The petroleum industry Part 2: Electrical

    installations in the distribution and marketing sector

    SANS 10108 / SABS 0108 The classification of hazardous locations and the

    selection of apparatus for use in such locations

    SANS 10121 / SABS 0121 Cathodic protection of buried and submerged

    structures

    SANS 10142-1 / SABS 0142-1 The wiring of premises Part 1: Low-voltage

    installations

    SANS 10199 / SABS 0199 The design and installation of an earth electrode

    specifications

    SANS 122 / SABS 122 Pressure-sensitive adhesive tapes for electrical

    purposes (Metric units)

    SANS 1700-7 /SABS 1700-7 Fasteners Part 7: External drive hexagon bolts and

    screws Section 1 - 10: Hexagon head bolts - Product

    grades A and B

    Page 18 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    30/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    SANS 1700-14 / SABS 1700-14 Hexagon nuts Section 1: Style 1 - Product grades A

    and B

    SANS 1700-7-2 / SABS 1700-7-2 Fasteners Part 7: External drive hexagon bolts and

    screws Section 2: Hexagon head bolts - Product

    grade B - Reduced shank (shank diameter

    approximately equal to pitch diameter)

    SANS 1700-7-3 / SABS 1700-7-3 Fasteners Part 7: External drive hexagon bolts and

    screws Section 3: Hexagon head bolts - Product

    grade C

    SANS 1700-7-4 / SABS 1700-7-4 Fasteners Part 7: External drive hexagon bolts and

    screws Section 4: Hexagon head screws - Product

    grades A and B

    SANS 1700-7-5 / SABS 1700-7-5 Fasteners Part 7: External drive hexagon bolts andscrews Section 5: Hexagon head screws - Product

    grade C

    SANS 1700-14-1 / SABS 1700-14-1 Fasteners Part 14: Hexagon nuts Section 1: Style 1 -

    Product grades A and B

    SANS 1700-14-2 / SABS 1700-14-2 Fasteners Part 14: Hexagon nuts Section 2: Style 2 -

    Product grades A and B

    SANS 1700-14-3 / SABS 1700-14-3 Fasteners Part 14: Hexagon nuts Section 3: Product

    grade C

    SANS 1700-14-4 / SABS 1700-14-4 Fasteners Part 14: Hexagon nuts Section 4: Hexagon

    thin nuts (chamfered) - Product grades A and B

    Page 19 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    31/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    SANS 32 / SABS EN 10240 Internal and / or external protective coatings for steel

    tubes - Specification for hot dip galvanized coatings

    applied in automatic plants

    SANS 1411-1 / SABS 1411-1 Materials of insulated electric cables and flexible

    cords Part 1: Conductors

    SANS 1411-2 / SABS 1411-2 Materials of insulated electric cables and flexible

    cords Part 2: Poly-Vinyl-Chloride (PVC)

    SANS 1411-3 / SABS 1411-3 Materials of insulated electric cables and flexible

    cords Part 3: Elastomers

    SANS 1411-4 / SABS 1411-4 Materials of insulated electric cables and flexible

    cords Part 4: Cross-linked Polyethylene (XLPE)

    SANS 1411-5 / SABS 1411-5 Materials of insulated electric cables and flexible

    cords Part 5: Halogen-free, flame-retardant materials

    SANS 1411-6 / SABS 1411-6 Materials of insulated electric cables and flexible

    cords Part 6: Armour

    SANS 1507-1 / SABS 1507-1 Electric cables with extruded solid dielectric

    insulation for fixed installations (300 / 500 V to

    1900 / 3300 V) Part 1: General

    SANS 1507-2 / SABS 1507-2 Electric cables with extruded solid dielectric

    insulation for fixed installations (300 / 500 V to 1900

    / 3300 V) Part 2: Wiring cables

    SANS 1507-3 / SABS 1507-3 Electric cables with extruded solid dielectric

    insulation for fixed installations (300 / 500 V to 1900

    / 3300 V) Part 3: PVC distribution cables

    Page 20 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    32/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    SANS 1507-4 / SABS 1507-4 Electric cables with extruded solid dielectric

    insulation for fixed installations (300 / 500 V to

    1900 / 3300 V) Part 4: XLPE distribution cables

    SANS 1507-5 / SABS 1507-5 Electric cables with extruded solid dielectric

    insulation for fixed installations (300 / 500 V to

    1900 / 3300 V) Part 5: Halogen-free distribution

    cables

    SANS 1507-6 / SABS 1507-6 Electric cables with extruded solid dielectric

    insulation for fixed installations (300 / 500 V to 1900

    / 3300 V) Part 6: Service cables

    SANS 555 / SABS 555 Unused and reclaimed mineral insulating oils for

    transformers and switchgear

    SANS 1149 / SABS 1149 Flat and taper steel washers

    2.2

    2.3

    SOUTH AFRICAN NATIONAL STANDARDS (SANS) AND SOUTH AFRICAN

    BUREAU OF STANDARDS / INTERNATIONAL ELECTROTECHNICAL

    COMMISSION (SABS IEC) SPECIFICATIONS

    SANS 60079-10 / SABS IEC 60079-10 Electrical apparatus for explosive gas

    atmospheres Part 10: Classification of

    hazardous areas

    SOUTH AFRICAN NATIONAL STANDARDS (SANS) AND SOUTH AFRICAN

    BUREAU OF STANDARDS / INTERNATIONAL ORGANISATION FOR

    STANDARDISATION (SABS ISO) STANDARDS

    SANS 121 / SABS ISO 1461 Hot dip galvanized coatings on fabricated iron and steel

    articles - Specifications and test methods

    Page 21 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    33/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    2.4 AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME) STANDARDS

    ASME B31.4 Liquid transportation systems for hydrocarbons, liquid petroleum gas,

    anhydrous ammonia and alcohols

    ASME B31.8 Gas transmission and distribution systems

    2.5

    AMERICAN SOCIETY FOR THE TESTING OF MATERIALS (ASTM)

    ASTM A325 Standard specification for structural bolts, steel and heat treated, 120 /

    105 psi minimum tensile strength

    ASTM A694 Standard specification for carbon and alloy steel forgings for pipe

    flanges, fittings, valves and parts for high-pressure transmission

    service

    ASTM B265 Standard specification for titanium and titanium alloy strip, sheet andplate

    ASTM B338 Standard specification for seamless and welded titanium and titanium

    alloy tubes for condensers and heat exchangers

    ASTM A518 Specification for corrosion resistant high silicon iron castings

    ASTM B571 Standard practice for qualitative adhesion testing of metallic coatings

    ASTM D149 Standard test method for dielectric breakdown voltage

    ASTM D229 Standard test method for rigid sheet and plate material used for

    electrical insulation

    ASTM D293 Standard test method for sieve analysis of coke

    ASTM D709 Standard test method for laminated thermosetting materials

    ASTM D732 Standard test method for shear strength of plastics by punch tool

    ASTM D785 Standard test method for Rockwell hardness of plastics and electrical

    insulating materials

    Page 22 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    34/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    ASTM D1248 Polyethylene plastic moulding and extrusion materials

    ASTM D2000 Standard classification system for rubber products

    ASTM D3222 Standard specification for unmodified Poly-Vinylidene Fluoride

    (PVDF) moulding extrusion and coating material

    ASTM E186 Standard reference radiographs for heavy walled (51 to 114 mm) steel

    castings

    ASTM G57 Method for field measurement of soil resistivity using the Wenner

    Four Electrode method

    2.6

    2.7

    AMERICAN PETROLEUM INSTITUTE (API)

    API Std 620 Design and Construction of Large, Welded Low-Pressure Storage

    Tanks

    API Std 650 Welded Steel Tanks for Oil Storage

    API RP651 Cathodic Protection of Aboveground Petroleum Storage Tanks

    API RP1632 Cathodic Protection of Underground Petroleum Storage Tanks and

    Piping Systems

    API RP2003 Protection against Ignitions Arising out of Static, Lightning and Stray

    Currents

    NATIONAL ASSOCIATION OF CORROSION ENGINEERS (NACE) RECOMMENDED

    PRACTICES

    NACE RP0169 Control of external corrosion on under ground or submerged, metallic

    piping systems

    NACE RP0177 Mitigation of alternating current and lightning effects on metallic

    structures and corrosion control systems

    Page 23 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    35/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    NACE RP0186 Application of cathodic protection for well casings

    NACE RP0193 External cathodic protection of on-grade carbon steel storage tank

    bottoms

    NACE RP0285 Corrosion control of under ground storage tank systems by cathodic

    protection

    NACE RP0286 Electrical isolation of cathodically protected pipelines

    NACE RP0388 Impressed current cathodic protection of internal submerged surfaces

    of steel water storage tanks

    NACE RP0572 Design, installation, operation and maintenance of impressed current

    deep groundbeds

    NACE RP0575 Recommended practice for design, installation, operation and

    maintenance of internal cathodic protection system in oil treating

    vessels

    NACE Pub10A190 Measurement techniques related to criteria for cathodic protection of

    underground or submerged steel piping systems

    2.8

    BRITISH STANDARDS INSTITUTION (BS) SPECIFICATIONS

    BS 171 Specification for power transformers

    BS 1016 Method for analysing and testing of coal and coke

    BS 1591 Specification for corrosion resisting high silicon iron castings

    BS 1872 Specification of electroplated coatings on tin

    BS 6001 (ISO 2859-1) Sampling procedures for inspection by attributes

    Part 1: Specification for sampling plans indexed by acceptable quality

    levels (AQL) for lot-by-lot inspection

    Page 24 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    36/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    BS 7361 Cathodic Protection

    Part 1: Code of practice for land and marine applications

    2.9

    2.10

    2.11

    2.12

    RAL DEUTSCHES INSTITUT FR GTESICHERUNG UND KENNZEICHNUNG

    RAL-FARBEN

    RAL Specification for Colours for Identification, Coding and Special Purposes

    DEUTSCHES INSTITUT FR NORMUNG (DIN)

    DIN 30676 Design and application of cathodic protection of external surfaces

    DIN 50918 Corrosion of metals, electrochemical corrosion tests

    DIN 50925 Verification of the effectiveness of the cathodic protection of buried

    structures

    DIN 50929 Probability of corrosion of metallic materials when subject to corrosion from

    the outside

    INTERNATIONAL ELECTROTECHNICAL COMMISSION (IEC) PUBLICATIONS

    IEC 60038 Standard voltages

    IEC 60144 Degree of protection of enclosures for low voltage switchgear and control

    gear

    INTERNATIONAL ORGANISATION FOR STANDARDISATION (ISO) STANDARDS

    ISO 2325 Method for analysing and testing of coal and coke

    Page 25 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    37/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    ISO 2859-1 Sampling procedures for inspection by attributes

    Part 1: Specification for sampling plans indexed by Acceptable

    Quality Levels (AQL) For Lot-by-Lot inspection

    ISO 8501-1 Preparation of steel substrates before application of paints and

    related products

    Part 1 to 3 and supplement 1994

    ISO 13 623: 2000E CP monitoring plan

    2.13

    2.14

    2.14.1

    SWEDISH STANDARDS INSTITUTION (SIS) STANDARDS

    SIS 05 59 00 Pictorial visual standards for surface preparation for the painting of steel

    surfaces

    SASOL SPECIFICATIONS, DATA SHEETS AND STANDARD DRAWINGS

    Specifications

    SP-40-3 Spare parts requirements

    SP-50-6 Coating and wrapping of under ground steel pipe

    SP-50-7 Design of under ground gravity sewers

    SP-60-1 General electrical specification

    SP-60-4 Low voltage switchgear and motor control centres

    SP-60-10 Power and control cables rated 600 / 1000 V

    SP-60-35 Earthing systems

    Page 26 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    38/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    SP-60-37 Classification of hazardous locations and the selection of apparatus for use in

    such locations

    SP-60-47 Requirements for electrical engineering documentation

    SP-90-32 Minimum requirements for SASOL engineering drawings

    SP-90-37 End of job documentation deliverables

    2.14.2

    2.14.3

    Data Sheets

    E979 Spare Parts and Interchange-ability Record (SPIR)

    Standard Drawings

    STDD-6005CA Electrical CP general assembly G-026 to G-028

    STDD-6005CB Electrical CP general assembly G-030

    STDD-6005CD Electrical CP connection assembly G-034 to G-036

    STDD-6005CN Electrical CP manual output transformer rectifier

    STDD-6005CP Electrical CP details of thermit weld

    STDD-6005CQ Electrical CP insulating flange

    STDD-6005CR Electrical CP junction box test point

    STDD-6005CS Electrical CP cabling at tanks located in tank farms

    STDD-6005CT Electrical CP schematic diagram of variable voltage DC decoupler

    STDD-6005CU Electrical CP encapsulating of anode head

    STDD-6005CV Electrical CP electronic controller

    Page 27 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    39/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    STDD-6005CW Electrical CP data logger post

    STDD-6005CX Electrical CP potential test point details

    STDD-6005CY Electrical CP insulating joint details

    STDD-6005CZ Electrical CP high potential magnesium and cable connection details

    3

    3.1

    3.1.1

    3.1.2

    3.1.3

    CP SYSTEM REQUIREMENTS

    SPECIALIST CP CONSULTANT AND CP CONTRACTOR

    SASOL and / or the main contractor shall appoint a specialist sub-consultant in order to carry

    out a detailed site survey, to permit the drafting of both a conceptual and detailed CP design,

    should they be warranted. The detailed design shall only be carried out upon the reviewal of

    the conceptual design by SASOL.

    The design of the CP system shall be carried out by a SASOL approved consultant. The CP

    consultant shall be completely independent as defined by the Southern African Association

    of Consulting Engineers (SAACE). The main contractor shall assist the CP consultant with

    drawings to permit the AFC drawings to be issued. The CP consultant shall prepare and

    submit to the main contractor / SASOL a detailed list of all materials and equipment required

    permitting the relevant RFQ document to be formulated.

    The CP construction contractor shall install the CP field installation elements, concurrently

    with the construction of the associated process plant and / or pipeline. The CP consultant

    shall provide field engineering support and site supervision necessary to ensure the integrity

    of the as-built CP installation. The CP consultant shall prepare a quality control plan for the

    progressive checkout and acceptance of the CP installation and assist the main contractor in

    its implementation.

    Page 28 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    40/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    3.1.4 The CP consultant shall assist in the checkout, testing and commissioning of the installation

    and the marking-up of AFC drawings to reflect the as-built status. He shall also submit a

    final commissioning report in accordance with the requirements stipulated below.

    3.2

    3.2.1

    a.

    i)

    ii)

    iii)

    iv)

    ON SITE INVESTIGATIONS / SURVEY

    The following surveys shall be carried out by the CP consultant prior to commencing with

    the design:

    Soil Corrosivity Survey

    Distribution / transmission pipelines

    Soil resistivity measurements shall be conducted nominally every 250 m along

    the pipeline route in accordance with the Wenner Four Electrode Method, as

    stipulated in ASTM G57 at pipe invert depth. Where corrosive areas are

    encountered or at locations where temporary CP will be required or where it isto be anticipated, measurements will be conducted every 50 m or as required.

    Alternatively, an electromagnetic soil conductivity meter may be used, on long

    remote pipelines. Measurements shall be carried out every 50 m at pipe invert

    and overt depth.

    Soil samples shall be taken at pipe invert depth or proposed burial depth along

    the pipeline route nominally every 1000 m. The samples shall be analysed and

    assessed in accordance with DIN 90529 Part 1 to 3, in order to determine thePPI of the proposed or existing buried steel pipe.

    The presence and probable magnitude of SRB shall be assessed every 1000 m

    and / or at corrosive locations where the soil resistivity is less than 30 m.

    Page 29 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    41/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    b. Petrochemical plants

    i)

    ii)

    iii)

    iv)

    v)

    3.2.2

    a.

    i)

    ii)

    Soil resistivity measurements shall be conducted accordance with the Wenner

    Four Electrode Method, as stipulated in ASTM G57. The measurements shall be

    carried out in a 50 m x 50 m grid section at a depth of 0,5 m, 1,5 m, 2,5 m and

    3,5 m per grid section.

    Soil samples shall be taken at pipe invert depth or proposed burial depth across

    the site in accordance with BS 6001: Part1. The samples shall be analysed and

    assessed in accordance with DIN 90529 Part 1 to 3, in order to determine the

    PPI of the proposed or existing buried steel pipe.

    The presence and probable magnitude of SRB shall be assessed per 50 m x

    50 m grid section, but only where the soil resistivity is less than 30 m.

    Where on-grade carbon steel storage tank bottoms are encountered, all of the

    items described in Section 3, of NACE RP0193, shall be evaluated in full for

    both new and existing tanks, in order to determine whether or not CP will be

    required.

    Redox measurements will not be carried out, as they are difficult to perform and

    assess under normal site conditions.

    Stray Current Survey

    Distribution / transmission pipelines

    The presence and magnitude of DC traction stray currents shall be assessedprior to installation of the pipeline and / or after installation of any transmission

    pipeline. In the absence of a pipeline, rail recordings and pipe to soil and

    pipeline voltage gradient recordings shall be conducted at the foreign service(s).

    This, however, shall only be conducted upon approval from the foreign

    service(s) owner.

    On long transmission pipelines, the possible presence and magnitude of telluric

    (magnetic interference effects from solar storms and flares) effects, shall also be

    determined.

    Page 30 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    42/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    iii) All foreign service(s) shall be identified, as well as foreign CP system(s) which

    may influence (positively and / or negatively) the SASOL system. Where

    possible, the GPS co-ordinates shall be obtained and the data entered into the

    existing SASOL GIS. Operating data shall be obtained from the railway

    authority, including the polarity, operating voltage and power of the overhead

    catenary.

    iv)

    b.

    i)

    ii)

    iii)

    Where transmission pipelines are located in close proximity of HVTL, where

    resistive and / or capacitive and / or inductive coupling may occur, tests shall be

    conducted in order to determine the extent of the interference. All of the

    relevant data pertaining to the supply authority shall be obtained, as well as the

    soil resistivity at a depth in the vicinity of the HVTL towers representative of

    pipe invert and overt depths along the affected pipeline route. All data relating

    to the power line transpositions shall be obtained, as well as the distance

    between the pipeline and HVTL, including angles of convergence, divergence

    and all earthing (earth mat or point) details.

    Petrochemical plants

    Tests shall be conducted to determine whether the adjacent CP systems will

    introduce any form of stray current into the new plant.

    The tests shall include but not be limited to obtaining natural potentials with all

    of the CP system(s) de-energised. Measurements shall also be obtained with the

    neighbouring CP systems re-energised one-by-one. The neighbouring TRU(s)

    shall also be pulsed at a 1,1 Hz frequency and the pipe potential signal (On -

    Off) influence be recorded, mapped and modelled.

    Once the above surveys have been carried out, definitive recommendations can

    be made as to whether CP is required or not. A conceptual CP design report

    shall be issued to SASOL for reviewal, should CP deemed to be required. As

    soon as the conceptual CP design has been reviewed by SASOL, the following

    additional tests shall be carried out.

    Page 31 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    43/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    3.2.3

    a.

    i)

    ii)

    iii)

    iv)

    v)

    vi)

    Anode Groundbed Survey

    General considerations

    When designing and / or selecting to use ICCP, consideration must be given to the

    proper use and selection of the anode groundbed(s).

    The groundbed location shall be determined early in the design process because its

    location may affect the choice of which groundbed type may be best suited to a

    particular application. The following factors should be considered when choosing a

    groundbed location:

    Soil resistivity and moisture content;

    Interference with other structures;

    Electrical shielding by structures;

    Availability of power supply and site accessibility;

    Vandalism or other damage (e.g. operational damage);

    Purpose of the groundbed and availability of Right-of-Way or servitudes.

    Horizontal (conventional) anode groundbeds are normally used to distribute the

    protective current over a broad area of the structure requiring protection. These are

    frequently called remote groundbeds because the structure is outside the anodic

    gradient of the groundbed caused by the discharge of current from the anodes to the

    surrounding soil. They may be continuous or discrete in construction as detailed in

    Figure 1 and 2.

    FIGURE 1 SHALLOW CONTINUOUS HORIZONTAL ANODE GROUNDBED

    Page 32 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    44/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    FIGURE 2 SHALLOW DISCRETE HORIZONTAL ANODE GROUNDBED

    b.

    i)

    ii)

    iii)

    Anode Groundbeds

    Distributed Anode Groundbeds (2,5 m to 15 m deep) are used to reduce the

    potential for interference effects on neighbouring structures. They are also used

    to protect sections of bare or poorly coated structure. They are extensively used

    in congested areas where electrical shielding may or will occur, if other types of

    groundbeds are considered.

    Deep Vertical Anode Groundbeds (30 m deep) are remote to the structure by

    virtue of the vertical distance between the anode and structure. Deep anode

    groundbeds therefore achieve results similar to remote horizontal (surface)

    groundbeds. A deep anode groundbed is an appealing choice when space is not

    available for a horizontal groundbed or when the surface soil has a high

    resistivity and the deeper strata exhibit low resistivity. They should however,

    not be used where electrical shielding can occur in congested plant areas.

    Shallow Vertical Anode Groundbeds (15 m but 30 m deep) are commonly

    used where space is limited and shielding might occur, as well as to mitigate

    costs associated with a distributive anode groundbed system as shown in

    Figure 3.

    Page 33 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    45/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    FIGURE 3: DISTRIBUTIVE, DEEP AND SHALLOW VERTICAL ANODE BED

    ARRANGEMENT

    c.

    i)

    ii)

    Distribution / transmission pipelines

    Preference shall be given to remote horizontal continuous or discrete anode

    groundbed systems. Where servitude and / or Right-of-Way problems exist,

    deep vertical anode groundbed systems shall be employed.

    Where horizontal anode beds are to be installed, the soil resistivity shall be

    measured at 20 m intervals along the entire length of the active anode bed

    length at the proposed anode installation depth.

    Page 34 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    46/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    iii) Soil resistivity measurements shall also be conducted at two, three, four and

    five times the equivalent depth of the proposed anodes, at the beginning, half

    way to the centre, centre, halfway between the centre and end and end of the

    proposed anode bed, using the Wenner Four Electrode Method, as per

    ASTM G57.

    iv)

    v)

    vi)

    d.

    i)

    ii)

    iii)

    The minimum distance between the pipeline and anode bed shall be two and

    half times the length of the anode bed.

    Where deep vertical anode groundbeds are required, the soil resistivity shall be

    measured at a depth of 2 m, 4 m, 8 m, 16 m, 32 m, etc., until the final depth of

    the proposed deep vertical anode groundbed is attained, using the Wenner Four

    Electrode Method, as per ASTM G57. The values will be rechecked upon

    drilling of the bore hole.

    The minimum burial depth of the vertical anode bed (i.e. excluding the active

    length) shall be determined according to the resistivity data obtained from the

    bore hole, but shall nominally be two and a half times the active length of thebed.

    Petrochemical plants

    In uncongested areas, deep vertical anode groundbeds shall be the preferred

    choice of anode groundbed systems.

    In congested areas where electrical shielding can occur, only shallow vertical

    and / or distributive anode groundbed systems shall be employed.

    In both instances, the soil resistivity shall be measured at the active anode depth

    of the proposed shallow vertical / distributive anode groundbed, using the

    Wenner Four Electrode Method, as per ASTM G57. The values will be

    rechecked upon the drilling of a test hole.

    Page 35 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    47/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    3.2.4 Current Drainage (CD) Survey

    a.

    b.

    c.

    d.

    e.

    f.

    g.

    A CD test is conducted in order to calculate the total current required to confer

    complete protection to the structure / pipeline. This is of utmost importance as the

    current requirements determine the rating and number of TRUs required and the size

    and rating of the anode groundbed(s). The current required is also used in order to

    determine both the number and distribution (in conjunction with the soil resistivity

    data) of the sacrificial anodes required.

    This survey cannot generally be carried out on new structures / pipelines or during the

    construction of a new process plant or during construction of new on-grade steel

    storage tank(s), as construction schedules generally preclude such testing.

    On existing pipelines and / or tanks the CD survey must be carried out.

    During a CD survey, one essentially sets up a temporary CP system and injects a

    known current into the structure(s) requiring protection via a suitable anode

    groundbed. The latter may be a convenient fence or steel rods driven into the groundand the former may be a portable DC power source such as a car battery, AC

    generator connected to a rectifier bridge, etc.

    The pipe potential is measured along the pipeline / structure before (natural potential),

    and after injection of current (On potential). The current is adjusted until adequate

    protection is achieved over a meaningful length of pipe or meaningful area of the

    structure requiring protection.

    It must also be appreciated that the On potentials of the structure / pipeline will also

    vary as a result of temperature variations and due to the fact that the On potentials

    also contain a voltage drop as a result of the current flowing through the soil /

    electrolyte.

    From the magnitude of current required and the length of pipe and / or surface area of

    the structure protected and taking into consideration the abovementioned variations,

    one may proceed towards preparing a CP design based on the current requirements.

    Page 36 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    48/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    3.2.5

    a.

    b.

    c.

    Electrical Continuity Survey

    This survey is generally conducted on old pipelines where the method of construction

    may not be fully documented and on newly constructed OWS lines. The survey entails

    measuring the voltage drop along the pipeline(s), with CP current flowing.

    A break in electrical continuity is indicated by a voltage drop and complete electrical

    continuity is indicated by a direct short measured between the two points with

    current flowing in the pipeline as shown in Figure 4a and 4b.

    This survey is obligatory, as any break in electrical continuity will result in corrosion

    occurring downstream of the break.

    FIGURE 4a and 4b: CONTINUITY BONDED CHAMBER / FLEXIBLE COUPLING

    FIGURE 4a:

    Page 37 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    49/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    FIGURE 4b:

    3.2.6

    a.

    b.

    c.

    d.

    Other CP Requirements

    All other aspects pertinent to the installation of a CP system shall be addressed. Theseinclude, but are not limited to the following:

    Location of a suitable power source (public, plant and / or remote);

    Location of river, rail and / or road crossing where casing will be required;

    Location of test stations / points for CP, AC mitigation, foreign crossings, Insulating

    Flanges (IF) or Insulating Joints (IJ);

    Location of in-line valves, chambers, block valves, etc., etc., etc.

    Once all of the above surveys have been carried out, a detailed CP design report will be

    submitted to SASOL for reviewal.

    Page 38 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    50/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    4 CATHODIC PROTECTION DETAILED DESIGN REQUIREMENTS

    4.1

    4.2

    4.2.1

    4.2.2

    4.2.3

    GENERAL CONSIDERATIONS

    CP is perhaps the most important of all approaches to corrosion control. By means of an

    externally applied electric current, corrosion may be reduced to virtually zero and the metal

    surface may be exposed to a corrosive environment without any deterioration for an almost

    indefinite period of time. CP is also one of the most economically viable methods available

    in abating the corrosion process of submerged metallic structures.

    COATINGS AND CP

    Coatings (e.g. tape wrap systems, bitumen fibreglass, Fusion Bonded Epoxy (FBE), etc.)

    applied to metal surfaces can be extremely effective in containing the corrosion of the steel

    substrate in many environments.

    However, no freshly applied coating is entirely free from defects and there will always be

    small areas of steel which are exposed directly to the corrosive environment. It is possible to

    reduce, but not eliminate these defects, by paying attention to workmanship. In practice it

    becomes increasingly expensive to achieve fewer and fewer defects due to the need for high

    quality inspection, detection and the repair of individual defects.

    The coating provides the initial barrier against the corrosive environment and CP provides

    protection at the coating defects. This apparently ideally complementary behaviour occurs as

    a result of the low resistance path offered by the defects, as opposed to the high resistance

    path offered by the coating.

    A coating will deteriorate both chemically and mechanically during its lifetime. These results

    in an increase in both the number of defects and the current required in order to protect the

    newly exposed steel surface areas (defects).

    Page 39 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    51/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    The defects will once again provide a low path of resistance and the CP current will flow to

    it and provide protection, providing that it is of sufficient magnitude. This naturally implies

    that the CP system must be designed such that it has sufficient reserve in order to provide the

    necessary additional current.

    4.2.4

    4.2.5

    In general, the choice of the coating system falls outside the scope of the CP Consultant.

    However, the coating system must be compatible with the choice of CP utilised to protect the

    structure.

    Specification SP-50-6 must be complied with in full and any deviations must be reviewed by

    SASOL prior to carrying out the work.

    As a guideline, the protective coating system efficiencies should comply with the following:

    COATING SYSTEM EFFICIENCY (%)

    Three Layer FBE / Polypropylene > 98,5

    FBE > 97,5

    Polyethylene Tapes > 96

    Cold Applied Mastics or Enamels > 95

    Internal Pipe and Tank Linings > 94,5

    Bitumen Fibre Glass Coatings > 92

    External Epoxy Paint Coatings > 90

    No Coating System 0

    4.2.6

    The pipeline shall be backfilled in accordance with ASME B31.4 / 8. This implies a selected

    pipeline backfill material (size less than 9 mm) free from sharp objects, rocks, stones or any

    other material which may damage the coating system. Pipelines located in the same trench

    should nominally be separated by at least one and a half times the diameter of the largest

    pipe, in order to prevent shielding.

    Page 40 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    52/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    4.2.7 Where concrete encasement of the pipe is required, such as at river crossings, the reinforcing

    steel shall be electrically isolated from the steel pipe. The pipeline shall be wrapped as per

    Specification SP-50-6 prior to being concrete encased.

    4.2.8

    4.2.9

    4.2.10

    4.3

    4.3.1

    4.3.2

    All buried pipelines when entering, passing through or leaving a chamber, reservoir, or any

    concrete structure shall ensure a minimum clearance of 50 mm from the steel reinforcing and

    the pipe or pipe puddle flange and shall be completely wrapped / coated as per Specification

    SP-50-6 in the concrete covered section.

    Pipeline sections which will be located inside chambers that may become flooded from time

    to time or which will be continuously flooded, shall be wrapped / coated as per Specification

    SP-50-6. Sacrificial magnesium anodes shall be employed to protect the pipeline or pipe

    section in these chambers.

    A DCVG survey shall be conducted on all transmission and distribution lines afterconstruction, in order to assess the condition of the coating subsequent to construction. The

    pipeline construction contractor shall be responsible for the repair of all major defects

    identified during the DCVG survey. Some 10 % of the defects will be exposed in order to

    delineate defects and compare them to the DCVG % IR values prior to prioritising defects

    for repair.

    CHOICE OF CP SYSTEM

    CP may be achieved by means of ICCP or SACP. The choice of which system to use shall be

    based on both technical and economic factors.

    ICCP utilises a TRU, which is supplied by a 230 V, 400 V or 525 V AC supply and produces

    a low voltage direct current. The negative terminal of the TRU is connected to the structure

    (tank / pipe), which becomes the cathode, and the positive terminal to an anode or a series of

    anodes buried in the ground. This set-up is generally termed an anode groundbed.

    Page 41 of 127

    Copyright 2003. Sasol. All rights reserved.

  • 7/21/2019 SP60-18 Rev3 Cathodic Protection

    53/138

    SP-60-18

    Revision 3

    October 2003

    CATHODIC PROTECTION

    Current flows from the anode to the cathode through the electrolyte (soil or ground), and

    provided it is of an adequate magnitude, protection will be attained.

    4.3.3

    4.3.4

    4.4

    4.4.1

    a.

    b.

    c.

    d.

    e.

    f.

    g.

    h.

    i.

    A SACP system does not need an external source of power. It exploits the difference in

    potential of various metals in the galvanic series and generates its own voltage, much like a

    battery. For example, magnesium possess a natural potential of -1700 mV and steel a natural

    potential of -500 mV with regard to a saturated copper / copper sulphate reference electrode.

    Therefore, the two combined will produce a driving voltage of approximately 1200 mV.

    If the structure is subject to moderate to sever