We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

Operat ing Manual

UK

WT 4

WT 5

WT 6

WT 7

WT 8

WT 9

WT 10

WT 11

SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

WT 1

WT 2

WT 3

Page 2: SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

2We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

please read firstThis operating manual provides important information on the handling of the unit. It is an integral part of the product and must be stored so that it is accessible in the immediate vicinity of the unit. It must remain available throughout the entire service life of the unit. It must be handed over to subsequent owners or users of the unit.

Read the operating manual before working on or operating the unit. This applies in particular to the chapter on safety. Always follow all instructions completely and without restrictions.

It is possible that this operating manual may contain instructions that seem incomprehensible or unclear. In the event of any questions or if any details are unclear, contact the factory customer service department or the manufacturer's local partner.

Since this operating manual was written for several different models of the unit, always comply with the parameters for the respective model.

This operating manual is intended only for persons assigned to work on or operate the unit. Treat all constituent parts confidentially. The information contained herein is protected by copyright. No part of this manual may be reproduced, transmitted, copied, stored in electronic data systems or translated into another language, either wholly or in part, without the express written permission of the manufacturer.

SymbolsThe following symbols are used in the operating manual. They have the following meaning:

Information for operators.

Information or instructions for qualified technicians.

Danger! Indicates a direct impending danger

resulting in severe injuries or death.

WarnIng! Indicates a potentially dangerous situation

that could result in serious injuries or death.

CautIon! Indicates a potentially dangerous situation

that could result in medium or slight injuries.

Important Indicates a potentially dangerous situation, which

could result in property damage.

notICe Emphasised information.

Reference to other sections of the operating manual.

Reference to other documents of the manufacturer.

Page 3: SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

3We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

contents

INfoRmATIoN foR USERS ANd qUAlIfIEd pERSoNNEl

plEASE REAd fIRST ..................................................................2

SymbolS .....................................................................................2

INfoRmATIoN foR USERS ANd qUAlIfIEd pERSoNNEl

INTENdEd USE ..........................................................................4

opERATINg pRINcIplE of plATE hEAT ExchANgERS 4

REqUIREmENTS oN ThE hEAT SoURcE SIdE ................4Water temperature / water quantity ...........................4Water quality ....................................................................4Evaluation of the water analysis ....................................5

dISclAImER................................................................................5

SAfETy .........................................................................................6

WARRANTy / gUARANTEE ...................................................6

dISpoSAl ....................................................................................6

INSTRUcTIoNS foR qUAlIfIEd TEchNIcIANS

ScopE of dElIvERy ..................................................7

INSTAllATIoN ANd ASSEmbly ...........................................7Transport to the installation location and installation ...7

WT 1 – WT 3 ...................................................................7WT 4 – WT 11 .................................................................8

connection to the pipe system ........................................10WT 1 – WT 3 .................................................................10WT 4 – WT 11 ............................................................... 11

clEANINg ................................................................................ 11

TEchNIcAl dATA ANd dImENSIoNAl dRAWINgSWT 1 – 2 ..............................................................................12WT 3 .....................................................................................13WT 4 .....................................................................................14WT 5 .....................................................................................15WT 6 .....................................................................................16WT 7 ..................................................................................... 17WT 8 .....................................................................................18WT 9 .....................................................................................19WT 10 ...................................................................................20WT 11 ...................................................................................21

pRESSURE loSS cURvESheat source volume flow WT 1 – WT 3 ........................22brine volume flow (25% brine) WT 1 – WT 3...............23heat source volume flow WT 4 – WT 7 ........................24brine volume flow (25% brine) WT 4 – WT 7...............25heat source volume flow WT 8 – WT 11 ......................26brine volume flow (25% brine) WT 8 – WT 11 .............27

ovERvIEW of floW REqUIREmENTS WT 1 – WT 3 ..28

ovERvIEW of floW REqUIREmENTS WT 4 – WT 11 29

Page 4: SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

4We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

intended useThe plate heat exchanger may be used only for the intended purpose.

This means:

- for passive cooling with groundwater heat source in conjunction with brine/water heat pumps.

Operating principle of plate heat exchangers

profiled plates strung together with flow openings form a stack of flow gaps (flow passages) in the plate heat exchanger. These are flowed through from both sides by the flow media involved in the heat exchange.

requirements on the heat source side

Water temperature / Water quantity

The water in the extraction well of the heat source sys-tem must have a minimum temperature of 7 °c all year round and may not exceed a temperature of 25°c. de-pending on the heat output required or its cooling ca-pacity as a relevant variable for dimensioning the heat source, a minimum water rate is required, which must be provided by the heat source as a continuous output. before installing the water/water heat pump, a pump test should/must be carried out for at least 12 hours with verification of a quasi-constantly lowered water table (persistence) to provide information about the quanti-ty of water available. for efficient operation of the wells, during the initial start-up the nominal volume flow must be adjusted on the heat source side. Any appropriate components, which enable balancing, are to be installed in the pipe network here. The material of the compo-nents used must be chosen according to the water qual-ity. The necessary volume flow (heat source water rate) must satisfy the heat pump’s requirements.

“Technical data/scope of delivery” overview in the operating manual of your heat pump.

Water quality

In germany the well must be designed and built to dIN 4021 and vdI 4640 (in other countries according to the corresponding regulations). Wells may only be drilled and built by drilling companies with a permit in ac-cordance with dvgW W120. The water quality of the heat source is defined as normal groundwater. Ensure that the suction and return pipe always extends below the water level by sufficient depth, to ensure that oxy-gen is not added to the water (risk of iron oxide depo-sits). please discuss the problem of iron oxide deposits with your well builder. during the planning the quality of the groundwater should be checked in advance as well as possible (e.g. by asking the competent water autho-rity or searching for data on existing adjacent wells) and subsequently verified by water analysis in the built pro-duction well. The following table helps to assess the wa-ter quality.

Page 5: SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

5We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

Important A water analysis and pump test must be carried

out before installing the water/water heat pump. please send the results of the analysis and test

directly to the manufacturer for checking and coordination.

notICe: Water analyses are prepared by wa-

ter test laboratories. Initial informa-tion about possible use of groundwater is available from your local water management authority. A pump test provides information as to whether a sufficient quantity / rate of water is available to cover the requirements for the hea-ting output of your unit. The minimum ground-water volume flow must at least be available as a continuous output.

“Technical data/Scope of delivery” overview, “heat source volume flow” section in the operating manual of your heat pump

evaluation of the Water analysis

Water constituents - minimum requirement. The water should be analysed in advance for the test values listed below (table). An important criterion for taking water samples is the dvgW Standard, Technical Notices, leaf-let W 112 and use of the Technical Regulations listed in it (dIN, EN and ISo standards).

Water constituents minimum requirementpH value > 6,8Iron content < 0,2 mg / lManganese content < 0,1 mg / lChloride content < 300 mg / lFree chlorine content < 3 mg / lTurbidity none

Technical freedom from sand < 0.1 mg / l sand per 10 l pumped water

Important If a value does not conform to the limit value li-

sted in the table, heat exchangers may not be used. Use of the unit with surface water, waste-water, industrial wastewater or mixtures of wa-ter and alkali solutions, acids or chlorine is not allowed.

DisclaimerThe manufacturer is not liable for losses resulting from any use of the unit which is not its intended use.

The manufacturer's liability also lapses:

• if work is carried out on the unit and its components contrary to the instructions in this operating manual.

•if work is improperly carried out on the unit and its components.

• if work is carried out on the unit which is not described in this operating manual, and this work has not been explicitly approved by the manufacturer in writing.

• if the unit or components in the unit have been altered, modified or removed without the explicit written consent of the manufacturer.

Page 6: SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

6We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

SafetyThe unit is safe to operate for its intended use. The construction and design of the unit conform to current state of the art standards, all relevant dIN/vdE regulations and all relevant safety regulations.

Every person who performs work on the unit must have read and understood the operating manual prior to starting any work. This also applies if the respective person has already worked with such a unit or a similar unit or has been trained by the manufacturer.

WarnIng! only qualified technicians (trained heating,

cooling, refrigerant and electrical techni-cians) may perform work on the unit and its components.

CautIon! Wear safety gloves.

the thin heat exchanger plates have sharp edges. there is also a risk of injuries due to burr, threads or similar parts of the plate heat exchanger.

CautIon! upright heat exchangers which are not

anchored can tip over.

always secure plate heat exchangers against tipping over and fasten them to the ground.

CautIon! Before opening the plate heat exchanger,

ensure that it is depressurised and empty.

CautIon! Before opening the plate heat exchanger,

ensure that the heat exchanger plates cannot detach themselves from the guide and tip over.

customer servicefor technical information please contact a qualified technician or the manufacturer's local partner.

“customer service” overview in the heat pump operating manual.

Warranty / guaranteefor warranty and guarantee conditions, please refer to the purchase documents.

notICe please contact your dealer about all matters

concerning warranties and guarantees.

DisposalWhen decommissioning the unit, always comply with applicable laws, directives and standards concerning recovery, recycling and disposal.

Page 7: SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

7We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

Scope of delivery WT 1 – WT 3:

Nickel soldered plate heat exchangers

WT 4 – WT 11:

bolted plate heat exchangers

complete the following first:

Inspect the delivery for outwardly visible signs of damage…

check to make sure that the delivery is complete. Any defects or incorrect deliveries must be claimed

immediately.

installation and assemblyThe following applies to all work to be done:

notICe Always comply with the applicable local accident

prevention regulations, statutory regulations, ordinances, guidelines and directives.

Important Ensure that the installation site is sufficiently

large and the ground or floor is flat and is able to support the load.

“Technical data, weight” overview

transport to the installation location and installation

Wt 1 – Wt 3

To avoid damage during transport, you should transport the plate heat exchanger (secured on the wooden pallet) to its final installation location using a lifting truck.

If it is not possible to transport the unit to the final installation location using a lifting truck, you can also transport the unit using a hand truck.

CautIon! Wear safety gloves.

dispose of the transport and packaging materials properly and under ecological aspects.

notICe Install the heat exchanger so that there is suffici-

ent space to carry out maintenance work on the unit. choose the installation location so that it is possible to vent and drain the heat exchanger.

Page 8: SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

8We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

A vertical installed position of the heat exchanger is the most effective for heating systems. All other installation positions can cause output losses.

vertical installed position

CautIon. Never install the heat exchanger with the con-

nections facing downwards.

fix the heat exchanger onto a wall-mounting bracket. A holder on the connections is not sufficiently strong.

Wt 4 – Wt 11

To avoid damage during transport, you should transport the plate heat exchanger (secured on the wooden pallet) to its final installation location using a lifting truck.

CautIon! Wear safety gloves.

CautIon! only transport the plate heat exchanger with

the lift truck if it is on the wooden pallet and is securely anchored onto the pallet. Never po-sition the lift truck directly under the stack of plates to lift the plate heat exchanger.

WarnIng! Several people are required to transport

the unit. Do not underestimate the weight of the plate heat exchanger.

“Technical data, weight” overview

Important Never lift the plate heat exchanger by the clam-

ping bolts or at the connections.

Page 9: SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

9We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

WarnIng! ensure that the lifting tools are

adequately dimensioned and are designed for the weight of the plate heat exchanger. ensure that the lifting tools cannot become detached or slip off. ensure that no swinging movements develop during lifting.

proceed as follows:

Remove the transport straps from the plate heat exchanger and from the wooden pallet…

place a sling around the bottom and top clamping nuts on each side of the plate heat exchanger…

Important only use slings. Never use chains or steel ropes

or cables.

If the bottom clamping nuts are not accessible for positioning the round slings, use an additional sling to slightly tilt the plate heat exchanger first. Always position this additional sling between the two clamping nuts…

Then lift the plate heat exchanger slightly and place a sling around the now accessible bottom clamping nuts. Then around the top clamping nuts too…

CautIon! ensure that the slings are securely in

place.

ensure that the connection sockets are not exposed to any tensile loads and do not support any loads.

Slowly lift the plate heat exchanger from the pallet above its centre of gravity. At the same time, check that the slings are correctly positioned and ensure that the sling remains tightly slung around the top and bottom clamping nuts during lifting and cannot slip…

Page 10: SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

10We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

WarnIng! never step under suspended loads.

Slowly lower the plate heat exchanger onto the edge of the fixed plate or onto its feet…

Align the plate heat exchanger and place it in its final position in the installation location…

notICe Install the heat exchanger so that there is suffi-

cient space to carry out connection and mainte-nance work on the unit.

choose the installation location so that it is pos-sible to vent and drain the heat exchanger.

Remove the slings and other transport equipment from the plate heat exchanger…

WarnIng! plate heat exchangers can tilt over with

relatively little effort.

Securely anchor the plate heat exchanger into the ground where it is installed.

dispose of the transport and packaging materials properly and under ecological aspects.

connection to the pipe system

dirt and deposits which get into the heat exchanger from the pipe network can cause corrosion in the heat exchanger (and in some applications can cause the heat exchanger to freeze up).

Therefore, thoroughly rinse the pipes before connecting the heat exchanger to the pipe system.

Install dirt filters at the connections of the heat exchanger to prevent dirt from getting into the heat exchanger.

lay the pipes so that vibrations, stresses and impacts or pulsations do not impinge on the heat exchanger.

connect the pipes to the heat exchanger at the threaded connections on the heat exchanger.

notICe connect the heat exchanger to the pipe system

so that the primary and secondary medium flow through the heat exchanger in opposite direc-tions.

Wt 1 – Wt 3

1 Inlet2 outlet

3 Inlet4 outlet

5 coloured dot for marking the primary or secondary side

notICe If there is a red dot on your heat exchanger, it

marks the primary side. If there is a blue dot on your heat exchanger, it

marks the secondary side.

Page 11: SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

11We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

Wt 4 – Wt 11

please refer to the dimensioned drawings of your heat exchanger to find out the position of the inlets and outlets on the primary and secondary side.

dimensional drawing for the respective heat exchanger type.

cleaningIf, due to the water quality (for example, high hardness or heavy soiling) a deposit is expected to form, clean the exchanger at regular intervals by rinsing it.

Use a suitable cleaning solution and rinse the heat exchanger in the direction opposite to the normal direction of flow.

Important If you use chemicals to clean the heat exchanger,

ensure that it is not incompatible with stainless steel, copper or nickel, as incompatible chemi-cals irreparably damage the heat exchanger.

Page 12: SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

12We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

WT 1 – 2 Dimensional drawings

WT 1 WT 2S = 20 20

Plate material: Stainless steel 1.4404 Stainless steel 1.4404

nickel soldered nickel solderedConnections G 5/4” AG G 5/4” AG

Operating temperature: ± 195 °C ± 195 °C

Operating pressure: 16 bar 16 bar

Number of plates: 40 60

Empty weight: 11.6 16.4Heat exchanger area: 2.24 m² 3.42 m²

Page 13: SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

13We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

Dimensional drawings WT 3

WT 3S = 20

Plate material: Stainless steel 1.4404

nickel solderedConnections G 5/4” AG

Operating temperature: ± 195 °C

Operating pressure: 16 bar

Number of plates: 50

Empty weight: 36.6Heat exchanger area: 6.48 m²

Page 14: SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

Angebot 1074800215 Rev. 0 Kunde: Alpha-Inno Tec GmbH

Seite 4

Maßblatt Plattenwärmetauscher

Kunde: Alpha-Inno Tec GmbH Angebot.: 1074800215 Positions-Nr.: 10 Alternative-Nr.: 0 Kundenposition: 15025401 WT4 Ihre Artikel-Nr. 604165 (47 kW)

Typ: NT50M CDH-10 Abmessungen der Zeichnung in [mm] 0050-250-Layout1.tif

n: 419 mm s1: 15,00 mm a-max Gestell: 195 mm Leergewicht: 100 kg k: 420 mm s2: 15,00 mm a-max aktuell: 93 mm max. Gesamtgewicht: 112 kg l: 400 mm

Pos Größe Typ Medium Ein Aus Zusatz m-Maß1F DN50 Nippel DIN 2999 1.4571 DN50 0,058 Wasser x - - 43 mm 2F DN50 Nippel DIN 2999 1.4571 DN50 0,058 Ethylenglykol 25,0 - x - 43 mm 3F DN50 Nippel DIN 2999 1.4571 DN50 0,058 Ethylenglykol 25,0 x - - 43 mm 4F DN50 Nippel DIN 2999 1.4571 DN50 0,058 Wasser - x - 43 mm

Nippel DIN2999 1.4571 1F;2F;3F;4F

Technische Änderungen vorbehalten. Farbschichtdicke bei lackierten Gestellen gemäß DIN EN ISO 12944-5, Gestellplattenoberflächengüte gemäß DIN EN 10029. Die konstruktiven Angaben gelten für die von der GEA Ecoflex GmbH/Sarstedt hergestellten PWT.

14We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

WT 4 Dimensional drawings

n: 419 mm s1: 15,00 mm dimension a max.: 195 mm Empty weight: 100 kgk: 420 mm s2: 15,00 mm dimension a currently: 93 mm max. total weight: 112 kgl: 400 mm

Item DN Type Medium Inlet Outlet dimension m1F 50 Nippel DIN 2999 1.4571 DN50 0,058 Water X – 43 mm2F 50 Nippel DIN 2999 1.4571 DN50 0,058 Ethylene glycol 25.0 – X 43 mm3F 50 Nippel DIN 2999 1.4571 DN50 0,058 Ethylene glycol 25.0 X – 43 mm4F 50 Nippel DIN 2999 1.4571 DN50 0,058 Water – X 43 mm

Page 15: SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

Angebot 1074800215 Rev. 0 Kunde: Alpha-Inno Tec GmbH

Seite 6

Maßblatt Plattenwärmetauscher

Kunde: Alpha-Inno Tec GmbH Angebot.: 1074800215 Positions-Nr.: 20 Alternative-Nr.: 0 Kundenposition: 15025501 WT 5 Ihre Artikel-Nr. 604166 (61 kW)

Typ: NT50M CDH-10 Abmessungen der Zeichnung in [mm] 0050-250-Layout1.tif

n: 419 mm s1: 15,00 mm a-max Gestell: 195 mm Leergewicht: 106 kg k: 420 mm s2: 15,00 mm a-max aktuell: 119 mm max. Gesamtgewicht: 122 kg l: 400 mm

Pos Größe Typ Medium Ein Aus Zusatz m-Maß1F DN50 Nippel DIN 2999 1.4571 DN50 0,058 Wasser x - - 43 mm 2F DN50 Nippel DIN 2999 1.4571 DN50 0,058 Ethylenglykol 25,0 - x - 43 mm 3F DN50 Nippel DIN 2999 1.4571 DN50 0,058 Ethylenglykol 25,0 x - - 43 mm 4F DN50 Nippel DIN 2999 1.4571 DN50 0,058 Wasser - x - 43 mm

Nippel DIN2999 1.4571 1F;2F;3F;4F

Technische Änderungen vorbehalten. Farbschichtdicke bei lackierten Gestellen gemäß DIN EN ISO 12944-5, Gestellplattenoberflächengüte gemäß DIN EN 10029. Die konstruktiven Angaben gelten für die von der GEA Ecoflex GmbH/Sarstedt hergestellten PWT.

15We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

Dimensional drawings WT 5

n: 419 mm s1: 15,00 mm dimension a max.: 195 mm Empty weight: 106 kgk: 420 mm s2: 15,00 mm dimension a currently: 119 mm max. total weight: 122 kgl: 400 mm

Item DN Type Medium Inlet Outlet dimension m1F 50 Nippel DIN 2999 1.4571 DN50 0,058 Water X – 43 mm2F 50 Nippel DIN 2999 1.4571 DN50 0,058 Ethylene glycol 25.0 – X 43 mm3F 50 Nippel DIN 2999 1.4571 DN50 0,058 Ethylene glycol 25.0 X – 43 mm4F 50 Nippel DIN 2999 1.4571 DN50 0,058 Water – X 43 mm

Page 16: SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

Angebot 1074800215 Rev. 0 Kunde: Alpha-Inno Tec GmbH

Seite 8

Maßblatt Plattenwärmetauscher

Kunde: Alpha-Inno Tec GmbH Angebot.: 1074800215 Positions-Nr.: 30 Alternative-Nr.: 0 Kundenposition: 15025601 WT 6 Ihre Artikel-Nr. 604167 (76 kW)

Typ: NT50M CDH-10 Abmessungen der Zeichnung in [mm] 0050-250-Layout1.tif

n: 419 mm s1: 15,00 mm a-max Gestell: 195 mm Leergewicht: 118 kg k: 420 mm s2: 15,00 mm a-max aktuell: 153 mm max. Gesamtgewicht: 138 kg l: 400 mm

Pos Größe Typ Medium Ein Aus Zusatz m-Maß1F DN50 Nippel DIN 2999 1.4571 DN50 0,058 Wasser x - - 43 mm 2F DN50 Nippel DIN 2999 1.4571 DN50 0,058 Ethylenglykol 25,0 - x - 43 mm 3F DN50 Nippel DIN 2999 1.4571 DN50 0,058 Ethylenglykol 25,0 x - - 43 mm 4F DN50 Nippel DIN 2999 1.4571 DN50 0,058 Wasser - x - 43 mm

Nippel DIN2999 1.4571 1F;2F;3F;4F

Technische Änderungen vorbehalten. Farbschichtdicke bei lackierten Gestellen gemäß DIN EN ISO 12944-5, Gestellplattenoberflächengüte gemäß DIN EN 10029. Die konstruktiven Angaben gelten für die von der GEA Ecoflex GmbH/Sarstedt hergestellten PWT.

16We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

WT 6 Dimensional drawings

n: 419 mm s1: 15,00 mm dimension a max.: 195 mm Empty weight: 118 kgk: 420 mm s2: 15,00 mm dimension a currently: 153 mm max. total weight: 138 kgl: 400 mm

Item DN Type Medium Inlet Outlet dimension m1F 50 Nippel DIN 2999 1.4571 DN50 0,058 Water X – 43 mm2F 50 Nippel DIN 2999 1.4571 DN50 0,058 Ethylene glycol 25.0 – X 43 mm3F 50 Nippel DIN 2999 1.4571 DN50 0,058 Ethylene glycol 25.0 X – 43 mm4F 50 Nippel DIN 2999 1.4571 DN50 0,058 Water – X 43 mm

Page 17: SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

Angebot 1074800215 Rev. 0 Kunde: Alpha-Inno Tec GmbH

Seite 10

Maßblatt Plattenwärmetauscher

Kunde: Alpha-Inno Tec GmbH Angebot.: 1074800215 Positions-Nr.: 40 Alternative-Nr.: 0 Kundenposition: 15025701 WT 7 Ihre Artikel-Nr. 604168 (93 kW)

Typ: NT50X CDH-10 Abmessungen der Zeichnung in [mm] 0050-270-Layout1.tif

n: 419 mm s1: 15,00 mm a-max Gestell: 195 mm Leergewicht: 166 kg k: 420 mm s2: 15,00 mm a-max aktuell: 169 mm max. Gesamtgewicht: 199 kg l: 400 mm

Pos Größe Typ Medium Ein Aus Zusatz m-Maß1F DN50 Nippel DIN 2999 1.4571 DN50 0,058 Wasser x - - 43 mm 2F DN50 Nippel DIN 2999 1.4571 DN50 0,058 Ethylenglykol 25,0 - x - 43 mm 3F DN50 Nippel DIN 2999 1.4571 DN50 0,058 Ethylenglykol 25,0 x - - 43 mm 4F DN50 Nippel DIN 2999 1.4571 DN50 0,058 Wasser - x - 43 mm

Nippel DIN2999 1.4571 1F;2F;3F;4F

Technische Änderungen vorbehalten. Farbschichtdicke bei lackierten Gestellen gemäß DIN EN ISO 12944-5, Gestellplattenoberflächengüte gemäß DIN EN 10029. Die konstruktiven Angaben gelten für die von der GEA Ecoflex GmbH/Sarstedt hergestellten PWT.

17We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

Dimensional drawings WT 7

n: 419 mm s1: 15,00 mm dimension a max.: 195 mm Empty weight: 166 kgk: 420 mm s2: 15,00 mm dimension a currently: 169 mm max. total weight: 199 kgl: 400 mm

Item DN Type Medium Inlet Outlet dimension m1F 50 Nippel DIN 2999 1.4571 DN50 0,058 Water X – 43 mm2F 50 Nippel DIN 2999 1.4571 DN50 0,058 Ethylene glycol 25.0 – X 43 mm3F 50 Nippel DIN 2999 1.4571 DN50 0,058 Ethylene glycol 25.0 X – 43 mm4F 50 Nippel DIN 2999 1.4571 DN50 0,058 Water – X 43 mm

Page 18: SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

Angebot 1074800215 Rev. 0 Kunde: Alpha-Inno Tec GmbH

Seite 12

Maßblatt Plattenwärmetauscher

Kunde: Alpha-Inno Tec GmbH Angebot.: 1074800215 Positions-Nr.: 50 Alternative-Nr.: 0 Kundenposition: 15025801 WT 8 Ihre Artikel-Nr. 604169 (124 kW)

Typ: NT100T CDH-10 Abmessungen der Zeichnung in [mm] 0100-232-Layout1.tif

n: 850 mm s1: 30,00 mm a-max Gestell: 274 mm Leergewicht: 352 kg k: 960 mm s2: 30,00 mm a-max aktuell: 154 mm max. Gesamtgewicht: 391 kg l: 800 mm

Pos Größe Typ Medium Ein Aus Zusatz m-Maß1F DN100 Gummi-Formteil DIN 2633 NBR Wasser x - - 4 mm 2F DN100 Gummi-Formteil DIN 2633 NBR Ethylenglykol 25,0 - x - 4 mm 3F DN100 Gummi-Formteil DIN 2633 NBR Ethylenglykol 25,0 x - - 4 mm 4F DN100 Gummi-Formteil DIN 2633 NBR Wasser - x - 4 mm

Gummi-Formteil DIN2633 NBR PN16 1F;2F;3F;4F

Technische Änderungen vorbehalten. Farbschichtdicke bei lackierten Gestellen gemäß DIN EN ISO 12944-5, Gestellplattenoberflächengüte gemäß DIN EN 10029. Die konstruktiven Angaben gelten für die von der GEA Ecoflex GmbH/Sarstedt hergestellten PWT.

18We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

WT 8 Dimensional drawings

n: 850 mm s1: 30,00 mm dimension a max.: 274 mm Empty weight: 352 kgk: 960 mm s2: 30,00 mm dimension a currently: 154 mm max. total weight: 391 kgl: 800 mm

Item DN Type Medium Inlet Outlet dimension m1F 100 Rubber moulded part DIN 2633 NBR DN100 0,034 Water X – 4 mm2F 100 Rubber moulded part DIN 2633 NBR DN100 0,034 Ethylene glycol 25.0 – X 4 mm3F 100 Rubber moulded part DIN 2633 NBR DN100 0,034 Ethylene glycol 25.0 X – 4 mm4F 100 Rubber moulded part DIN 2633 NBR DN100 0,034 Water – X 4 mm

Page 19: SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

Angebot 1074800215 Rev. 0 Kunde: Alpha-Inno Tec GmbH

Seite 14

Maßblatt Plattenwärmetauscher

Kunde: Alpha-Inno Tec GmbH Angebot.: 1074800215 Positions-Nr.: 60 Alternative-Nr.: 0 Kundenposition: 15025901 WT 9 Ihre Artikel-Nr. 604170 (181 kW)

Typ: NT100T CDH-10 Abmessungen der Zeichnung in [mm] 0100-232-Layout1.tif

n: 850 mm s1: 30,00 mm a-max Gestell: 274 mm Leergewicht: 367 kg k: 960 mm s2: 30,00 mm a-max aktuell: 194 mm max. Gesamtgewicht: 416 kg l: 800 mm

Pos Größe Typ Medium Ein Aus Zusatz m-Maß1F DN100 Gummi-Formteil DIN 2633 NBR Wasser x - - 4 mm 2F DN100 Gummi-Formteil DIN 2633 NBR Ethylenglykol 25,0 - x - 4 mm 3F DN100 Gummi-Formteil DIN 2633 NBR Ethylenglykol 25,0 x - - 4 mm 4F DN100 Gummi-Formteil DIN 2633 NBR Wasser - x - 4 mm

Gummi-Formteil DIN2633 NBR PN16 1F;2F;3F;4F

Technische Änderungen vorbehalten. Farbschichtdicke bei lackierten Gestellen gemäß DIN EN ISO 12944-5, Gestellplattenoberflächengüte gemäß DIN EN 10029. Die konstruktiven Angaben gelten für die von der GEA Ecoflex GmbH/Sarstedt hergestellten PWT.

19We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

Dimensional drawings WT 9

n: 850 mm s1: 30,00 mm dimension a max.: 274 mm Empty weight: 367 kgk: 960 mm s2: 30,00 mm dimension a currently: 194 mm max. total weight: 416 kgl: 800 mm

Item DN Type Medium Inlet Outlet dimension m1F 100 Rubber moulded part DIN 2633 NBR DN100 0,034 Water X – 4 mm2F 100 Rubber moulded part DIN 2633 NBR DN100 0,034 Ethylene glycol 25.0 – X 4 mm3F 100 Rubber moulded part DIN 2633 NBR DN100 0,034 Ethylene glycol 25.0 X – 4 mm4F 100 Rubber moulded part DIN 2633 NBR DN100 0,034 Water – X 4 mm

Page 20: SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

Angebot 1074800215 Rev. 0 Kunde: Alpha-Inno Tec GmbH

Seite 16

Maßblatt Plattenwärmetauscher

Kunde: Alpha-Inno Tec GmbH Angebot.: 1074800215 Positions-Nr.: 70 Alternative-Nr.: 0 Kundenposition: 15028201 WT 10 Ihre Artikel-Nr. 604729 (280 kW)

Typ: NT100M CDH-10 Abmessungen der Zeichnung in [mm] 0100-235-Layout1.tif

n: 1130 mm s1: 30,00 mm a-max Gestell: 414 mm Leergewicht: 605 kg k: 1240 mm s2: 30,00 mm a-max aktuell: 338 mm max. Gesamtgewicht: 740 kg l: 1080 mm

Pos Größe Typ Medium Ein Aus Zusatz m-Maß1F DN100 Gummi-Formteil DIN 2633 NBR Wasser x - - 4 mm 2F DN100 Gummi-Formteil DIN 2633 NBR Ethylenglykol 25,0 - x - 4 mm 3F DN100 Gummi-Formteil DIN 2633 NBR Ethylenglykol 25,0 x - - 4 mm 4F DN100 Gummi-Formteil DIN 2633 NBR Wasser - x - 4 mm

Gummi-Formteil DIN2633 NBR PN16 1F;2F;3F;4F

Technische Änderungen vorbehalten. Farbschichtdicke bei lackierten Gestellen gemäß DIN EN ISO 12944-5, Gestellplattenoberflächengüte gemäß DIN EN 10029. Die konstruktiven Angaben gelten für die von der GEA Ecoflex GmbH/Sarstedt hergestellten PWT.

20We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

WT 10 Dimensional drawings

n: 1130 mm s1: 30,00 mm dimension a max.: 414 mm Empty weight: 605 kgk: 1240 mm s2: 30,00 mm dimension a currently: 338 mm max. total weight: 740 kgl: 1080 mm

Item DN Type Medium Inlet Outlet dimension m1F 100 Rubber moulded part DIN 2633 NBR DN100 0,034 Water X – 4 mm2F 100 Rubber moulded part DIN 2633 NBR DN100 0,034 Ethylene glycol 25.0 – X 4 mm3F 100 Rubber moulded part DIN 2633 NBR DN100 0,034 Ethylene glycol 25.0 X – 4 mm4F 100 Rubber moulded part DIN 2633 NBR DN100 0,034 Water – X 4 mm

Page 21: SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

Angebot 1074800215 Rev. 0 Kunde: Alpha-Inno Tec GmbH

Seite 18

Maßblatt Plattenwärmetauscher

Kunde: Alpha-Inno Tec GmbH Angebot.: 1074800215 Positions-Nr.: 80 Alternative-Nr.: 0 Kundenposition:

Typ: NT100M CDH-10 Abmessungen der Zeichnung in [mm] 0100-235-Layout1.tif

n: 1130 mm s1: 30,00 mm a-max Gestell: 414 mm Leergewicht: 635 kg k: 1240 mm s2: 30,00 mm a-max aktuell: 392 mm max. Gesamtgewicht: 791 kg l: 1080 mm

Pos Größe Typ Medium Ein Aus Zusatz m-Maß1F DN100 Gummi-Formteil DIN 2633 NBR Wasser x - - 4 mm 2F DN100 Gummi-Formteil DIN 2633 NBR Ethylenglykol 25,0 - x - 4 mm 3F DN100 Gummi-Formteil DIN 2633 NBR Ethylenglykol 25,0 x - - 4 mm 4F DN100 Gummi-Formteil DIN 2633 NBR Wasser - x - 4 mm

Gummi-Formteil DIN2633 NBR PN16 1F;2F;3F;4F

Technische Änderungen vorbehalten. Farbschichtdicke bei lackierten Gestellen gemäß DIN EN ISO 12944-5, Gestellplattenoberflächengüte gemäß DIN EN 10029. Die konstruktiven Angaben gelten für die von der GEA Ecoflex GmbH/Sarstedt hergestellten PWT.

21We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

Dimensional drawings WT 11

n: 1130 mm s1: 30,00 mm dimension a max.: 414 mm Empty weight: 635 kgk: 1240 mm s2: 30,00 mm dimension a currently: 392 mm max. total weight: 791 kgl: 1080 mm

Item DN Type Medium Inlet Outlet dimension m1F 100 Rubber moulded part DIN 2633 NBR DN100 0,034 Water X – 4 mm2F 100 Rubber moulded part DIN 2633 NBR DN100 0,034 Ethylene glycol 25.0 – X 4 mm3F 100 Rubber moulded part DIN 2633 NBR DN100 0,034 Ethylene glycol 25.0 X – 4 mm4F 100 Rubber moulded part DIN 2633 NBR DN100 0,034 Water – X 4 mm

Page 22: SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

Bezeichnung: DruckverlusteSeite: 1/2 WT 1-3Zeichnungsnummer:

Datei:

- / PEP004-2007 / Neumann / 21.08.07

Änd./ ÄM / Ersteller / Datum

812163812163 Druckverluste WT 1-3.xls

0,00

0,05

0,10

0,15

0,20

0,25

0,30

0 1 2 3 4 5 6 7 8 9 10

Wärmequellenvolumenstrom primär (m3/h)

WT1 WT2 WT3

Druckverlust (bar)

heat exchanger pressure loss (bar)

heat source volume flow, primary (m3/h)

22We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

heat source volume flow WT 1 – WT 3 pressure loss curves

Page 23: SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

Bezeichnung: DruckverlusteSeite: 2/2 WT 1-3Zeichnungsnummer:

Datei:

Änd./ ÄM / Ersteller / Datum

- / PEP004-2007 / Neumann / 21.08.07

812163 Druckverluste WT 1-3.xls812163

0,00

0,05

0,10

0,15

0,20

0,25

0,30

0 1 2 3 4 5 6 7 8 9 10

Solevolumenstrom sekundär (m3/h)

WT1 WT2 WT3

Druckverlust (bar)

heat exchanger pressure loss (bar)

heat source volume flow, secondary (m3/h)

23We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

pressure loss curves brine volume flow (25% brine) WT 1 – WT 3

Page 24: SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

Bezeichnung: DruckverlusteSeite: 1/4 Zwischentauscher SWPZeichnungsnummer: Datei:

812162 - / PEP004-2007 / Neumann / 17.08.07

Änd./ ÄM / Ersteller / Datum

812162 - Druckverluste WT 4-11

0,00

0,05

0,10

0,15

0,20

0,25

0,30

0,35

0,40

0 5 10 15 20 25 30 35 40 45

Wärmequellenvolumenstrom primär (m3/h)

WT4 WT5 WT6 WT7

Druckverlust (bar)

heat exchanger pressure loss (bar)

heat source volume flow, primary (m3/h)

24We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

heat source volume flow WT 4 – WT 7 pressure loss curves

Page 25: SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

Bezeichnung: DruckverlusteSeite: 2/4 Zwischentauscher SWPZeichnungsnummer: Datei: 812162 - Druckverluste WT 4-11

812162

Änd./ ÄM / Ersteller / Datum - / PEP004-2007 / Neumann / 17.08.07

0,00

0,05

0,10

0,15

0,20

0,25

0,30

0,35

0,40

0 5 10 15 20 25 30 35 40

Solevolumenstrom sekundär (m3/h)

WT4 WT5 WT6 WT7

Druckverlust (bar)

heat exchanger pressure loss (bar)

heat source volume flow, secondary (m3/h)

25We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

pressure loss curves brine volume flow (25% brine) WT 4 – WT 7

Page 26: SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

Bezeichnung: DruckverlusteSeite: 3/4 Zwischentauscher SWPZeichnungsnummer: Datei:

Änd./ ÄM / Ersteller / Datum

- / PEP004-2007 / Neumann / 17.08.07

812162812162 - Druckverluste WT 4-11

0,00

0,05

0,10

0,15

0,20

0,25

0,30

0,35

0,40

0 10 20 30 40 50 60 70 80 90 100 110 120

Wärmequellenvolumenstrom primär (m3/h)

WT8 WT9 WT10 WT11

Druckverlust (bar)

heat exchanger pressure loss (bar)

heat source volume flow, primary (m3/h)

26We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

heat source volume flow WT 8 – WT 11 pressure loss curves

Page 27: SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

Bezeichnung: DruckverlusteSeite: 4/4 Zwischentauscher SWPZeichnungsnummer: Datei:

Änd./ ÄM / Ersteller / Datum

- / PEP004-2007 / Neumann / 17.08.07

812162812162 - Druckverluste WT 4-11

0,00

0,05

0,10

0,15

0,20

0,25

0,30

0,35

0,40

0 10 20 30 40 50 60 70 80 90 100 110 120

Solevolumenstrom sekundär (m3/h)

WT8 WT9 WT10 WT11

Druckverlust (bar)

heat exchanger pressure loss (bar)

heat source volume flow, secondary (m3/h)

27We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

pressure loss curves brine volume flow (25% brine) WT 8 – WT 11

Page 28: SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

28We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

Exchanger (Item No.)

Design output (kW) minimum volume flows (l/h)

primary (water)

7 °C inlet

secondary (monoethylene glycol)

1 °C inlet

WT 1 (150 251)

Heat pumps:7.5 2200 1400

9 2600 170010 2900 1900

12 3400 2300

Heat stations:7.5 2200 1400

10 2900 1900

WT 2 (150 252)

Heat pumps:14.5 4200 2700

16 4600 300019 5400 3600

Heat stations:12 4100 2000

WT 3 (150 253)Heat pumps:

27 7700 4900

34 9700 6400

Overview of flow requirements WT 1 – WT 3

Exchanger (Item No.)

Design output (kW)

Pressure loss Exchanger

primary (water)

necessary BOSPUP

max. pressure loss for piping of secondary

volume flow

WT 1 (150 251)

Heat pumps:7.5 0.08 bar Standard 0.35 bar

9 0.11 bar Standard 0.26 bar10 0.13 bar Standard 0.43 bar

12 0.18 bar Standard 0.14 barHeat stations:

7.5 0.08 bar Standard 0.25 bar

10 0.13 bar Standard 0.13 bar

WT 2 (150 252)

Heat pumps:14.5 0.13 bar Standard 0.23 bar

16 0.16 bar Standard 0.19 bar19 0.22 bar TOP-S 30/10 0.4 bar

Heat stations:12 0.13 bar Standard 0.16 bar

WT 3 (150 253)Heat pumps:

27 0.12 bar Standard 0.32 bar34 0.18 bar Standard 0.17 bar

Page 29: SpliT heaT exchangerS fOr WaTer / brine SySTeM SeparaTiOn

29We reserve the right to modify technical specif ications without prior notice.83018400aUK – translation of the operating manual

Exchanger (Item No.)

Design output (kW) minimum volume flows (l/h)

primary (water)

7 °C inlet

secondary (monoethylene glycol)

1 °C inlet

WT 4 (150 254)

31 8900 760038 10900 9800

50 14200 1470047 13500 14200

WT 5 (150 255)57 16300 1560061 17500 18400

WT 6 (150 256)76 21700 2290078 22300 21400

95 27200 28700

WT 7 (150 257)93 26600 28000

112 32000 33800

WT 8 (150 258)124 35400 33000

142 40600 42800WT 9 (150 259) 180 51700 54600WT 10 (150 282) 280 80000 63300WT 11 (150 283) 360 102830 81400

Overview of flow requirements WT 4 – WT 11