MSY-GE09NA MUY-GE09NA 9,000 7,380 NA 208-230/1 12 15 21 40' 65' 3/8 1/4
MSY-GE12NA MUY-GE12NA 12,000 8,880 NA 208-230/1 12 15 20.5 40' 65' 3/8 1/4
MSY-GE15NA MUY-GE15NA 14,000 11,200 NA 208-230/1 12 15 21 40' 65' 1/2 1/4
MSY-GE18NA MUY-GE18NA 17,200 12,212 NA 208-230/1 14 15 19.2 50' 100' 1/2 1/4
MSY-GE24NA MUY-GE24NA 22,500 16,875 NA 208-230/1 17 20 19 50' 100' 5/8 3/8
MSY-D30NA MUY-D30NA 30,700 19,648 NA 208-230/1 21 25 16 50' 100' 5/8 3/8
MSY-D36NA MUY-D36NA 34,600 21,452 NA 208-230/1 21 25 15.1 50' 100' 5/8 3/8
MSZ-GE09NA MUZ-GE09NA 9,000 7,380 6,600 208-230/1 12 15 21 40' 65' 3/8 1/4
MSZ-GE12NA MUZ-GE12NA 12,000 8,880 8,800 208-230/1 12 15 20.5 40' 65' 3/8 1/4
MSZ-GE15NA MUZ-GE15NA 14,000 11,200 11,300 208-230/1 12 15 21 40' 65' 1/2 1/4
MSZ-GE18NA MUZ-GE18NA 17,200 12,212 13,400 208-230/1 14 15 19.2 50' 100' 1/2 1/4
MSZ-GE24NA MUZ-GE24NA 22,500 16,875 16,000 208-230/1 17 20 17.5 50' 100' 5/8 3/8
MSZ-D30NA MUZ-D30NA 30,700 19,648 19,500 208-230/1 21 25 14.5 50' 100' 5/8 3/8
MSZ-D36NA MUZ-D36NA 33,200 20,584 21,800 208-230/1 21 25 14.5 50' 100' 5/8 3/8
PKA-A12HA PUY-A12NHA 12,000 9,720 NA 208-230/1 13 15 15.2 100' 100' 1/2 1/4
PKA-A18HA PUY-A18NHA 18,000 12,240 NA 208-230/1 13 20 15.3 100' 100' 1/2 1/4
PKA-A24KA PUY-A24NHA 24,000 18,480 NA 208-230/1 18 30 17 100' 165' 5/8 3/8
PKA-A30KA PUY-A30NHA 30,000 21,000 NA 208-230/1 25 40 15.5 100' 165' 5/8 3/8
PKA-A36KA PUY-A36NHA 34,200 23,940 NA 208-230/1 25 40 14 100' 165' 5/8 3/8
PKA-A18HA PUZ-A18NHA 18,000 12,240 13,000 208-230/1 13 20 15.3 100' 100' 1/2 1/4
PKA-A24KA PUZ-A24NHA 24,000 18,480 18,000 208-230/1 18 30 17 100' 165' 5/8 3/8
PKA-A30KA PUZ-A30NHA 30,000 21,000 23,000 208-230/1 25 40 15.5 100' 165' 5/8 3/8
PKA-A36KA PUZ-A36NHA 34,200 23,940 25,000 208-230/1 25 40 14 100' 165' 5/8 3/8
1. The P-Series can cool down to 0 deg F outdoor ambient and the M-Series can only go to 14 deg F.
2. The P-Series has longer line lengths than the M-Series for similar tonnages.
3. The P-Series has larger models for some indoor styles than the M-Series.
Condensate
Electrical
Notes
The M-Series can cool down to 14 deg F outdoor ambient. There is no low ambient kit for the M-Series. The P-Series can cool down to 0 deg F outdoor ambient with the Wind Baffle low ambient kit.
The Wall Mounted models do not come with an integral condensate pump. Any condensate pump with a float switch can be wired to stop operation when the condensate overflows.
The Mitsubishi mini-splits require a single point power connection at the outdoor unit. Three wires are then ran from the outdoor unit to the indoor unit carrying line voltage.
ODB 95, EAT 80/67
M-Series Wall Mounted Heat Pump
Indoor Unit
P-Series Wall Mounted Cooling-Only
Outdoor Unit Voltage SEER
Refrigerant Pipe
Mitsubishi Mini-Split Single Zone Systems
M-Series Wall Mounted Cooling Only
MCA
(Outdoor
Unit)
MOCP
(Outdoor
Unit)
Cooling Capacity
Wall Mounted
Systems
P-Series Wall Mounted Heat Pump
M-Series or P-Series?
Low Ambient
Cooling
Heating Capacity
ODB 17, EAT 70
Total Sensible Total Max Height Max LengthGas Side OD
(in)
Liquid Side
OD (in)
SLZ-KA09NA SUZ-KA09NA 8,400 6,720 6,200 208-230/1 12 15 15 40' 65' 3/8 1/4
SLZ-KA12NA SUZ-KA12NA 11,100 8,436 8,300 208-230/1 12 15 15.4 40' 65' 3/8 1/4
SLZ-KA15NA SUZ-KA15NA 15,000 12,000 10,200 208-230/1 12 15 16 40' 65' 1/2 1/4
PLA-A12BA PUY-A12NHA 12,000 10,080 NA 208-230/1 13 15 13.5 100' 100' 1/2 1/4
PLA-A18BA PUY-A18NHA 18,000 14,580 NA 208-230/1 13 20 14.2 100' 100' 1/2 1/4
PLA-A24BA PUY-A24NHA 24,000 18,240 NA 208-230/1 18 30 13.6 100' 165' 5/8 3/8
PLA-A30BA PUY-A30NHA 30,000 21,900 NA 208-230/1 25 40 13.6 100' 165' 5/8 3/8
PLA-A36BA PUY-A36NHA 35,000 25,900 NA 208-230/1 25 40 14.2 100' 165' 5/8 3/8
PLA-A42BA PUY-A42NHA 42,000 29,820 NA 208-230/1 26 40 14.4 100' 165' 5/8 3/8
PLA-A18BA PUZ-A18NHA 18,000 14,580 13,000 208-230/1 13 20 14.2 100' 100' 1/2 1/4
PLA-A24BA PUZ-A24NHA 24,000 18,240 16,000 208-230/1 18 30 13.6 100' 165' 5/8 3/8
PLA-A30BA PUZ-A30NHA 30,000 21,900 23,000 208-230/1 25 40 13.6 100' 165' 5/8 3/8
PLA-A36BA PUZ-A36NHA 35,000 25,900 25,000 208-230/1 25 40 14.2 100' 165' 5/8 3/8
PLA-A42BA PUY-A42NHA 42,000 29,820 30,000 208-230/1 26 40 14.4 100' 165' 5/8 3/8
1. The P-Series can cool down to 0 deg F outdoor ambient and the M-Series can only go to 14 deg F.
2. The P-Series has longer line lengths than the M-Series for similar tonnages.
3. The P-Series has larger models for some indoor styles than the M-Series.
Access
Electrical
Mitsubishi Mini-Split Single Zone Systems
Ceiling Cassette
Systems
Indoor Unit Outdoor Unit
Cooling Capacity
Voltage
MCA
(Outdoor
Unit)
MOCP
(Outdoor
Unit)
SEER
Refrigerant Pipe
Low Ambient
Cooling
The M-Series can cool down to 14 deg F outdoor ambient. There is no low ambient kit for the M-Series. The P-Series can cool down to 0 deg F outdoor ambient with the Wind Baffle
low ambient kit.
ODB 95, EAT 80/67
M-Series 2' X 2' Ceiling Cassette Heat Pump
P-Series 3' X 3' Ceiling Cassette Cooling-Only
The Mitsubishi mini-splits require a single point power connection at the outdoor unit. Three wires are then ran from the outdoor unit to the indoor unit carrying line voltage.
An 18" x 18" access panel is required for the SLZ models when installed in a hard lid ceiling
P-Series 3' X 3' Ceiling Cassette Heat Pump
M-Series or P-Series?
The M and P Series Ceiling Cassettes come with an integral condensate pump. The condensate pump includes a float switch that turns off the indoor unit and produces an error
code when the condensate overflows. The M-Series SLZ cassette has a lift of 19 11/16" from the ceiling up and the P-Series PLA cassette has a lift of 33 7/16" from the ceiling up.Condensate
Notes
Heating Capacity
ODB 17, EAT 70
Total Sensible Total Low-Med-Hi (In. W.G.) Max Height Max LengthGas Side
OD (in)
Liquid
Side OD
(in)
SEZ-KD09NA SUZ-KA09NA 8,100 6,480 6,700 208-230/1 12 15 15 194-247-317 0.2 40' 65' 3/8 1/4
SEZ-KD12NA SUZ-KA12NA 11,500 8,740 9,000 208-230/1 12 15 16 247-317-388 0.2 40' 65' 3/8 1/4
SEZ-KD15NA SUZ-KA15NA 14,100 11,280 11,900 208-230/1 12 15 15.5 353-441-529 0.2 40' 65' 1/2 1/4
SEZ-KD18NA SUZ-KA18NA 17,200 13,588 13,100 208-230/1 14 15 17.5 423-529-635 0.2 50' 100' 1/2 1/4
PEA-A12AA PUY-A12NHA 12,000 9,240 NA 208-230/1 13 15 13.8 247-317-388 0.2 100' 100' 1/2 1/4
PEA-A18AA PUY-A18NHA 18,000 14,400 NA 208-230/1 13 20 14.3 423-529-635 0.2 100' 100' 1/2 1/4
PEAD-A24AA PUY-A24NHA 24,000 16,320 NA 208-230/1 18 30 16 512-636-742 0.6 100' 165' 5/8 3/8
PEAD-A30AA PUY-A30NHA 30,000 20,400 NA 208-230/1 25 40 15.5 618-742-883 0.6 100' 165' 5/8 3/8
PEAD-A36AA PUY-A36NHA 35,000 26,250 NA 208-230/1 25 40 15 847-1024-1201 0.6 100' 165' 5/8 3/8
PEAD-A42AA PUY-A42NHA 42,000 31,920 NA 208-230/1 26 40 13.8 1024-1254-1483 0.6 100' 165' 5/8 3/8
PEA-A18AA PUZ-A18NHA 18,000 14,400 13,000 208-230/1 13 20 14.3 423-529-635 0.2 100' 100' 1/2 1/4
PEAD-A24AA PUZ-A24NHA 24,000 16,320 18,000 208-230/1 18 30 16 512-636-742 0.6 100' 165' 5/8 3/8
PEAD-A30AA PUZ-A30NHA 30,000 20,400 23,000 208-230/1 25 40 15.5 618-742-883 0.6 100' 165' 5/8 3/8
PEAD-A36AA PUZ-A36NHA 35,000 26,250 25,000 208-230/1 25 40 15 847-1024-1201 0.6 100' 165' 5/8 3/8
PEAD-A42AA PUY-A42NHA 42,000 31,920 30,000 208-230/1 26 40 13.8 1024-1254-1483 0.6 100' 165' 5/8 3/8
1. The P-Series can cool down to 0 deg F outdoor ambient and the M-Series can only go to 14 deg F.
2. The P-Series has longer line lengths than the M-Series for similar tonnages.
3. The P-Series has larger models for some indoor styles than the M-Series.
Access
Electrical The Mitsubishi mini-splits require a single point power connection at the outdoor unit. Three wires are then ran from the outdoor unit to the indoor unit carrying line voltage.
Airflow (CFM) Max. ESP
Mitsubishi Mini-Split Single Zone Systems
Ducted Systems
Indoor Unit Outdoor Unit
Cooling Capacity
Voltage
MCA
(Outdoor
Unit)
MOCP
(Outdoor
Unit)
SEER
Refrigerant Pipe
All Ducted models come with an integral condensate pump. The condensate pump includes a float switch that turns off the indoor unit and produces an error code when the condensate
overflows. The M-Series SEZ Ducted models have a lift of 21 11/16" from the bottom of the unit up and the P-Series PEA Ducted models have a lift of 21 11/16" for 1-1.5 ton units and
27 9/16" for 2-3.5 ton units from the bottom of the unit up.
ODB 95, EAT 80/67
M-Series Ducted Heat Pump
M-Series or P-Series?
P-Series Ducted Cooling-Only
P-Series Ducted Heat Pump
Notes
Low Ambient
Cooling
The M-Series can cool down to 14 deg F outdoor ambient. There is no low ambient kit for the M-Series. The P-Series can cool down to 0 deg F outdoor ambient with the Wind Baffle
low ambient kit.
An 18" x 18" access panel is required for all ducted models when installed in a hard lid ceiling. The access panel should be placed 6" from the left-hand side when looking through the
return of the unit.
Condensate
Heating Capacity
ODB 17, EAT 70
Total Sensible Total Max Height Max LengthGas Side
OD (in)
Liquid Side
OD (in)
PCA-A24KA PUY-A24NHA 24,000 17,520 NA 208-230/1 18 30 16.8 100' 165' 5/8 3/8
PCA-A30KA PUY-A30NHA 30,000 20,700 NA 208-230/1 25 40 14.5 100' 165' 5/8 3/8
PCA-A36KA PUY-A36NHA 35,000 25,550 NA 208-230/1 25 40 14.4 100' 165' 5/8 3/8
PCA-A42KA PUY-A42NHA 42,000 28,980 NA 208-230/1 26 40 15.8 100' 165' 5/8 3/8
PCA-A24KA PUZ-A24NHA 24,000 17,520 18,000 208-230/1 18 30 16.8 100' 165' 5/8 3/8
PCA-A30KA PUZ-A30NHA 30,000 20,700 23,000 208-230/1 25 40 14.5 100' 165 5/8 3/8
PCA-A36KA PUZ-A36NHA 35,000 25,550 25,000 208-230/1 25 40 14.4 100' 165 5/8 3/8
PCA-A42KA PUZ-A42NHA 42,000 28,980 30,000 208-230/1 26 40 15.8 100' 165 5/8 3/8
Electrical
Refrigerant Pipe
The Mitsubishi mini-splits require a single point power connection at the outdoor unit. Three wires are then ran from the outdoor unit to the indoor unit carrying line voltage.
ODB 95, EAT 80/67
P-Series Ceiling Suspended Cooling-Only
P-Series Ceiling Suspended Heat Pump
Mitsubishi Mini-Split Single Zone Systems
Ceiling Suspended
Systems
Indoor Unit Outdoor Unit
Cooling Capacity
Voltage
MCA
(Outdoor
Unit)
MOCP
(Outdoor
Unit)
SEER
Notes
Low Ambient
CoolingThe P-Series can cool down to 0 deg F outdoor ambient with the Wind Baffle low ambient kit.
CondensateThe Ceiling Cassette models do not come with a condensate pump. An optional integral condensate pump is available, model PAC-SH84DM-E. The pump has a lift of 23 9/16"
from the top of the unit up.
Max Heating
Capacity @ ODB 5
Total Sensible Total Max Height Max LengthGas Side OD
(in)
Liquid Side OD
(in)
MSZ-FE09NA MUZ-FE09NA 9,000 6,840 10,900 208-230/1 12 15 26 40' 65' 3/8 1/4
MSZ-FE12NA MUZ-FE12NA 12,000 8,760 12,500 208-230/1 12 15 23 40' 65' 3/8 1/4
MSZ-FE18NA MUZ-FE18NA 18,000 15,120 21,600 208-230/1 17.1 20 20.2 50' 100' 5/8 3/8
PKA-A30KA PUZ-HA30NHA2 30,000 21,000 32,000 208-230/1 28 40 16.5 100' 245 5/8 3/8
PKA-A36KA PUZ-HA36NHA2 33,500 23,785 38,000 208-230/1 28 40 16.2 100' 245 5/8 3/8
PLA-A30KA PUZ-HA30NHA2 30,000 21,900 32,000 208-230/1 28 40 16.5 100' 245 5/8 3/8
PLA-A36KA PUZ-HA36NHA2 34,000 24,140 38,000 208-230/1 28 40 16.2 100' 245 5/8 3/8
PEAD-A30KA PUZ-HA30NHA2 30,000 20,100 32,000 208-230/1 28 40 16.5 100' 245 5/8 3/8
PEAD-A36KA PUZ-HA36NHA2 34,000 25,840 38,000 208-230/1 28 40 16.2 100' 245 5/8 3/8
PCA-A30KA PUZ-HA30NHA2 30,000 20,700 32,000 208-230/1 28 40 16.5 100' 245 5/8 3/8
PCA-A36KA PUZ-HA36NHA2 34,000 24,820 38,000 208-230/1 28 40 16.2 100' 245 5/8 3/8
1. Hyper Heat units are rated to operate in heating down to -13° F. They can operate down to -18° F and will auto restart when temperatures rise above -13° F.
2. Standard units are rated to operate in heating down to -5°.
3. Hyper Heat units cost around 15% more for M-Series and 30% more for P-Series, but they can eliminate the need for backup heat.
P-Series Ducted Heat Pump
P-Series Ceiling Suspended Heat Pump
ODB 95, EAT 80/67
M-Series Wall Mounted Heat Pump
P-Series Wall Mounted Heat Pump
P-Series Ceiling Mounted Heat Pump
Hyper Heat or Standard?
Mitsubishi Mini-Split Single Zone Systems
h2i Hyper Heat
Inverter Units
Indoor Unit Outdoor Unit
Cooling Capacity
Voltage
MCA
(Outdoor
Unit)
MOCP
(Outdoor
Unit)
SEER
Refrigerant Pipe
Cost
User Control
User Monitor
Dual Set Point
7-Day Programmable
Temperature Sensor Built In
Back-Lit
Required Accessory for MSZ/MSY
Required Accessory for PKA
Permit/Prohibit Functions
Error Indication
Model
Default Controller
Mounted
Installation Method
User Functions
No
No
None
PAR-SA9CA-E Receiver
PAR-FA32MA-E Receiver
PAR-SA9FA-E Receiver
On/Off, Set Temp., Operation Mode, and Filter Sign
None
MSZ / MSY
Handheld
N/A
On/Off, Mode, Fan Speed, Air Flow Direction, Set Temp.
No
No
None
None
MAC-397IF-E Contact Interface
PAC-SF40RM-E Contact Interface
Not Applicable
MAC-399IF-E M-Net Interface
PAC-SF81MA-E
BACnet and LonWorks
PAR-FA32MA-E Receiver
Error/OK Status
PAR-21MAA
-
Wall Mounted
Wired
On/Off, Mode, Fan Speed, Air Flow Direction, Set Temp.
No
Controls
PAR-FL32MA-E MHK1
PKA / PLA / SLZ / PEA / SUZ
Wall Mounted
Wireless
None
None
None
PAR-FA32MA-E Receiver
PAR-SL93B
Required Accessory for SLZ
Required Accessory for PLA
Required Accessory for PEA
Required Accessory for PCA
LonWorks Interface
BAC-HD150
LMAP03UNot Applicable
Installation MethodRequired for MSZ / MSY / SLZ /
SEZRequired for PKA / PLA / PEA /
PCABACnet Interface
Through relays provided by others
Mitsubishi Mini-Split Single Zone Systems
Yes
Yes
No
MAC-397IF-E Contact Interface
On/Off, Mode, Fan Speed, Air Flow Direction, Set Temp.
Yes
Yes
Yes
Room Temp., Error Code, On/Off, Set Temp., Mode, Fan Speed, Air Flow Direction
Through City Multi M-Net and BMS Interface
Compatible BMS Integration Any BMS System that accepts relay inputs
Displays Error Code Displays Error Code
Required Accessory for SEZ
None
None
NoneNone
None
None
None
Local Controllers
BMS Integration
On/Off, Set Temp., and Operation Mode On/Off, Set Temp., Operation Mode, and Filter Sign
Yes
None
Partial Integration
Less Expensive
On/Off
Full Integration
More Expensive
On/Off, Set Temp., Mode, Fan Speed, Air Flow Direction
Contacts
Joe Higham
Norman S. Wright Co.
Sales Engineer
505-345-8811