split water-cooled condensing unit minisplit air conditioners · mcx mcd---db/aa mcd---db w/plenum...

4
Minisplit Air Conditioners Split Water-Cooled Condensing Unit 7,000-60,000 Btu/h WTK Series 50 Hz Split Water-Cooled Condensing Unit

Upload: others

Post on 14-May-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Split Water-Cooled Condensing Unit Minisplit Air Conditioners · MCX MCD---DB/AA MCD---DB W/Plenum Literature Order Number: MS-SLB024-EN Date: Jun 2009 Supersedes: Dec 2008 Stocking

Minisplit Air Conditioners

Split Water-CooledCondensing Unit7,000-60,000 Btu/hWTK Series 50 Hz

Split Water-CooledCondensing Unit

Page 2: Split Water-Cooled Condensing Unit Minisplit Air Conditioners · MCX MCD---DB/AA MCD---DB W/Plenum Literature Order Number: MS-SLB024-EN Date: Jun 2009 Supersedes: Dec 2008 Stocking

MS-SLB024-EN2

MCD

MCD

MCX

Cooling Tower

WTK

WTK

WTK

Improved Cash Management• Factory packaging and testing

reduce field labor and installationrisk and improve system reliability.

• Phased equipment start-up matchesbuilding lease-up.

• Short construction cycles maximizecash flow.

• Requires less sophisticatedmaintenance than built-up systems.

Tenant Satisfaction• Enjoy the benefits of individual

tenant metering since buildings canoften be occupied on a one tenantper unit basis.

• After-hour operational cost savingsare tremendous since units can bedeactivated when not required.

• Complete HVAC system on eacharea minimized tenantinconvenience during routinemaintenance.

Low First Cost• Factory packaged controls reduce

field labor, installation time, andcosts.

• Minimize need and cost for firedampers and air shafts.

• Large equipment rooms andpenthouses are not needed.

• Condenser water is available oneach floor for tenant computersystems.

Economical Operation• Area-by-area system results in

energy saving since only airconditioners on areas requiringcooling are needed.

• Especially economical after normalbuilding occupancy hours.

• Annual system energy consumptioncomparable to central chilled watersystem but with significant energyconsumption reduction duringpartial occupancy and after-hours.

Human Comfort Solutions

A New Standard For TheIndustryTrane sets new standards for• Serviceability• Installability• Reliability• Flexibility of application in their

commercial air conditioningproducts.

These products enhance Trane’sreputation for quality in airconditioning equipments.

Quality ControlAll of Trane products have inspectedin assembly line. After completion, thecondensing unit has been evacuated,leak tested and holding charged withrefrigerant to protect rust and dirt.This is to assure that every parts willwork in the right condition and at thehighest efficiency.

Figure 1- System Diagram of WTK

Space Saving• Compact in size.• Unit can be installed in a very limited

space.

Table 1- General Data

Unit Model WTK507 WTK509 WTK512 WTK518 WTK524 WTK530 WTK536 WTK048 WTK060Nominal Capacity Btu/h 7,000 9,000 12,000 18,000 24,000 30,000 36,000 48,000 60,000Power supply V/ph/Hz 220-240/1/50 380-415/3/50Compressor Data Type Rotary Scroll

No. Used 1 1 1 1 1 1 1 1 1Compressor Speed rpm 2,840 2,840 2,820 2,840 2,850 2,850 2,850 2,900 2,900V/ph/Hz 220-240/1/50 380-415/3/50

RLA/LRA A 3.5/17.0 4.2/21.0 5.3/29.0 8.5/43.0 10.0/56.0 14.2/85.0 15.8/79.0 10.0/59.0 10.0/74.0Condenser Data Type Tube in tube

Water Inlet/Outlet Size in 3/4 3/4 3/4 3/4 3/4 3/4 3/4 7/8 7/8Outer Tube Diameter in 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8Inner Tube Diameter in 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4Water Coil Operating Pressure psig 200 200 200 200 200 200 200 200 200

Refrigerant Type R-22Dimension (HxWxD) mm 400 x 400 x 400 520 x 400 x 500Weight kg 29 29 27 32 43 52 53 63 65

Note: 1.) WTK507 and WTK509 are designed for export market only.2.) Please see Table 3 for the different liquid line and suction line size of WTK512, WTK518, WTK048, and WTK060 between Thailand and export.3.) Condenser water pipe size is designed upon condenser water flow rate and may not be the same size as Condenser Water Inlet/Outlet size.

Page 3: Split Water-Cooled Condensing Unit Minisplit Air Conditioners · MCX MCD---DB/AA MCD---DB W/Plenum Literature Order Number: MS-SLB024-EN Date: Jun 2009 Supersedes: Dec 2008 Stocking

3MS-SLB024-EN

Figure 2- Dimensional Data

Performance Data

Notes: 1. At ARI system rating conditions of 80OF-DB/67OF-WB indoor.2. Condensing water temperature inlet/outlet = 90/100OF.3. Nominal cfm at high speed fan.4. MCX—GB, MCD048, and MCD060 are for both Thailand and export market.

* means MCD used for Thailand market only.

Table 2- System Performance Matrix

WTK507-518 WTK524-060

Table 3- Dimensional Data

Export Market Thailand MarketModel Liquid Line Suction Line Liquid Line Suction Line

(in) (in) (in) (in)WTK507-509 1/4 3/8 1/4 3/8WTK512-518 1/4 1/2 3/8 5/8WTK524-530 3/8 5/8 3/8 5/8

WTK536 3/8 3/4 3/8 3/4WTK048-060 3/8 1 1/8 1/2 7/8

MCX512GB 627 1,074 234 29WTK512 MCD012AA* 400 12,000 3.3 0.5 230 946 445 20

MCD512DB 258 946 494 20

MCX518GB 627 1,074 234 30WTK518 MCD018AA* 600 18,000 5.0 1.4 260 946 445 23

MCD518DB 258 946 494 22

MCX524GB 627 1,324 234 34WTK524 MCD024AA* 800 24,000 6.6 2.2 260 1,098 445 26

MCD524DB 258 946 531 24

MCX530GB 627 1,574 234 46WTK530 MCD030DB*/EB* 1,000 30,000 8.3 4.3 300 1,098 625 36

MCD530DB 258 1,098 531 26

MCX536GB 627 1,574 234 47WTK536 MCD036DB*/EB* 1,200 36,000 9.9 7.0 300 1,251 625 40

MCD536DB 258 1,251 531 29

MCX048GB 627 1,824 234 59WTK048 1,600 48,000 13.2 10.9

MCD048DB 408 1,098 759 49

MCX060GB 627 2,074 234 70WTK060 2,000 60,000 16.5 16.0

MCD060DB 408 1,251 759 55

Cond. Air Supply Cooling Cond. Pressure Fan Coil UnitUnit Handler Air Cap. Water Drop Dimension - (mm) Weight (Kg)

Model Model cfm Btu/h GPM Ft of water Height Width Depth

50.8

WATER OUTLET

WATER OUTLET

WATER INLET

WATER INLET

LIQUID LINE

LIQUID LINE

SUCTION LINE

SUCTION LINE

Ø3/4 FPT DRAIN PIPEØ3/4 FPT DRAIN PIPE

POWER SUPPLYØ3/4 In.

179

109

49

179

43

51.1

POWER SUPPLYØ5/8 In.

50.8

43 53.5

302.

2

477.

6

432.

6

412.

6 477.

6

200.

4

232.

2 293.

2 358.

2

69

400

400

400

520

500

400

Page 4: Split Water-Cooled Condensing Unit Minisplit Air Conditioners · MCX MCD---DB/AA MCD---DB W/Plenum Literature Order Number: MS-SLB024-EN Date: Jun 2009 Supersedes: Dec 2008 Stocking

Fan Coil Section

Convertible Air HandlerMCX SeriesThe MCX-GB series is the compactdesign with 3-convenienceinstallation-floor, low wall, and ceilingtypes. Fashionable adjustabledischarge grille and decorative returnair grilles are modern and elegantoutlook. Unit panels are internallyacoustically insulated with closed cellelastomeric insulator for quiet opera-tion and healthy indoor air quality.

Ceiling Air HandlerModel MCD-AA and MCD-EB airhandler are designed for horizontalconcealed ceiling applications,commonly used within the closets ofhotels, motels and apartment.Standard features include tripleprotection drain pan (galvanized steel,polystyrene foam, and plastic)providing maximum insulation andwater integrity. Servicing is madesimple because the motor-blowersection is completely removable fromthe coil section.

Ducted Air HandlerModel MCD-DB is the high staticversion of the model MCD-AA andMCD-EB unit. It utilizes the largerdiameter fans operating at low RPM toachieve the increased static pressurerequirements needed for limiteddistribution ducts. The standard unithas a 1-inch supply air duct collar tofacilitate field connection of the supplyductwork.

Mechanical Specifications

Condensing SectionThe Trane Split water-Cooledcondensing units are designed forcommercial and industrial applications.Trane split water-cooled condensingunit can be matched with a variety ofair handlers in either convertible,ceiling, or ducted air handlers. Theseunits may be arranged to meet almostany space to make them suitable forevery application.

CabinetUnit panels are fabricated ofheavy-gauge steel and finished witha polyester powder painting andweather-resistant baked enamel finish.Unit surface has been tested 500 hoursin salt spray test. Condenser waterinlet/outlet and electrical wiring holesare provided. Base drain is a 3/4 -inchfemale connection.

High Efficiency CompressorSpecial low-friction valve ports andrubbing surfaces allow same capacityfor less electrical power input-higherEER. Compressor is externallymounted on isolators to isolate theoperating sound for quiet operation.

Refrigerant CircuitRefrigerant piping for condensing unithas been designed and installed toabsorb vibration. Packed valves makethe quicker and easier installation ofrefrigerant lines. Easy for refrigerantcharging with charging port.

Water-Cooled CondenserTube in tube condenser is constructedwith copper tubing. Water copper pipeconnections are provided forcondenser water inlet and outlet.

Options• Hi-Low pressure cut off

(from WTK507 to WTK536)• 3 minute time delay

(for use with MCD)

MCX

MCD---DB/AA

MCD---DB W/Plenum

Literature Order Number: MS-SLB024-EN

Date: Jun 2009

Supersedes: Dec 2008

Stocking Location: Bangkok, Thailand

Trane has a policy of continuous product and product data improvement and reserves the right to changedesign and specifications without notice.

Tranewww.trane.com

For more information, contact your localdistrict office