ssdp33-70 handbook - pumps direct 2 u · pdf filessdp33-70 handbook ... ac wiring diagram 400...

19
SSDP33-70 Handbook Wellingborough : +44 (0)1933 677911 Fax : +44 (0)1933 677916 E-mail : [email protected] Web : www.stephill-generators.co.uk Northants NN8 6AG DO NOT OPERATE THE GENERATOR BEFORE READING THIS MANUAL AND ENGINE MANUFACTURER’S OWNER’S MANUAL AND WARNINGS. THIS STEPHILL GENERATOR HAS BEEN DESIGNED TO PROVIDE SAFE AND EFFICIENT SERVICE IF OPERATED AND MAINTAINED CORRECTLY. MANY ACCIDENTS OCCUR THROUGH FAILURE TO ADHERE TO FUNDAMENTAL SAFETY PROCEDURES.

Upload: vancong

Post on 25-Mar-2018

215 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: SSDP33-70 Handbook - Pumps Direct 2 U · PDF fileSSDP33-70 Handbook ... AC Wiring diagram 400 Volt P70 16 ... Check the rating and electrical safety of the load before connecting the

SSDP33-70 Handbook

Stephill Generators Ltd Wallis close Park Farm South Wellingborough

Tel : +44 (0)1933 677911 Fax : +44 (0)1933 677916 E-mail : [email protected] Web : www.stephill-generators.co.uk

Northants NN8 6AG

DO NOT OPERATE THE GENERATOR BEFORE READING THIS MANUAL AND ENGINE MANUFACTURER’S OWNER’S MANUAL AND WARNINGS.

THIS STEPHILL GENERATOR HAS BEEN DESIGNED TO PROVIDE SAFE AND EFFICIENT SERVICE

IF OPERATED AND MAINTAINED CORRECTLY.

MANY ACCIDENTS OCCUR THROUGH FAILURE TO ADHERE TO FUNDAMENTAL SAFETY PROCEDURES.

Page 2: SSDP33-70 Handbook - Pumps Direct 2 U · PDF fileSSDP33-70 Handbook ... AC Wiring diagram 400 Volt P70 16 ... Check the rating and electrical safety of the load before connecting the

CONTENTS Section Page 1 SPECIFICATION 1

2 GENERAL SAFETY 2

2.1 Warning signs 2 2.2 Safety hazards 2

3 POTENTIAL HAZARDS 2

3.1 Auxiliary power 2 3.2 Operating environment 2

3.3 Temperature range 2

3.4 Reference relative humidity 2

3.5 Reference barometric pressure 3 3.6 Flammable environment 3

3.7 Saline environment 3

4 SAFETY CONSIDERATIONS 3 4.1 General 3

4.2 Fuel 3

4.3 Bunded tank 3 4.4 Lubricating oil 3

4.5 Safe lifting 3

4.6 Earth connection 3

4.7 Fumes 4 4.8 Noise 4

4.9 Battery acid 4

4.10 Fire 4 4.11 Hot parts 4

5 OPERATING INSTRUCTIONS 4

5.1 Pre-Start checks 4 5.2 Emergency stop 4

5.3 Three way valve 4

5.4 Fuel lift pump priming 5

5.5 Control panel 5 5.6 Variable RCD ELR-3C 5

5.7 Hard wire terminals 6

5.8 Remote start terminals 6 5.9 Long term storage 6

6 INTELILITE MRS 15 OPERATING INSTRUCTIONS 6

6.1 Pushbuttons and LEDs 6-7 6.2 InteliLIte MRS 15 starting instructions 7 6.3 Gen-set operation states 7 6.4 Measurement screen description 8

6.5 Generator screen 8

6.6 Analogue inputs screen 8

6.7 Inputs 8 6.8 Outputs 8

6.9 Gen-Set power screen 8

6.10 Statistics 8 6.11 How to find active alarms 8

6.12 List of possible alarms 9

6.13 Re-setting Service counters 10 7 SERVICE AND MAINTENANCE 10

7.1 Engine service 10

7.2 Alternator service 10

8 SPARES 10 8.1 Perkins consumable spares 10

8.2 SSDP33-70 Spares 10

8.3 General spares 11 9 WARRANTY 12

Canopy exploded view 13

AC Wiring diagram 230 Volt P30 14 AC Wiring diagram 400 Volt P33 15

AC Wiring diagram 400 Volt P70 16

DC Wiring diagram 17

Page 3: SSDP33-70 Handbook - Pumps Direct 2 U · PDF fileSSDP33-70 Handbook ... AC Wiring diagram 400 Volt P70 16 ... Check the rating and electrical safety of the load before connecting the

1 SPECIFICATION

SSDP33 SSDP50 SSDP70

Standby Prime Standby Prime Standby Prime

kVA 33 30 50 45 67 60

kW 26.4 24 40 36 53.6 48

400V 33kVA 30kVA 50kVA 45kVA 67kVA 60kVA

230V 3 x 11kVA 3 x 10kVA 3 x 17kVA 3 x 15kVA 3 x 22kVA 3 x 20kVA

115V 3 x 3.7kVA 3 x 3.7kVA N/A N/A

Engine Perkins 1103A-33G Perkins 1103A-33TG1 Perkins 1103A-33TG2

Alternator ECO32-3S/4 ECO32-1L/4 ECO32-3L/4

SSDP33 SSDP50 SSDP70

Skid Road Trailer

Skid Road Trailer

Skid Road Trailer

Wet Weight 1490Kg 1690Kg 1670Kg 1880Kg 1700Kg 1910Kg

Length 2050mm 3800mm 2300mm 4000mm 2300mm 4000mm

Width 1000mm 1620mm 1000mm 1620mm 1000mm 1620mm

Height 1450mm 1950mm 1450mm 1950mm 1450mm 1950mm

Fuel tank Litres 280 350 350

Fuel tank working capacity

260 330 330

Hours run full load prime

36 31 24

Hours run 75% load prime

48 40 31

LWA 90 89 89

dBA @ 7M 65 64 64

Sockets

400V (RCD) 1 x 32A 1 x 32A 1 x 63A 1 x 32A 1 x 63A

230V (RCD) 3 x 32A 3 x 32A 3 x 32A

115V 3 x 32A N/A N/A

Note The P33 is a simultaneous multi phase generator and will supply all voltages up to the maximum capacity of the machine. Fuel tank working capacity P33 = 260 Litres P50/67 = 330 Litres Hours run are based on these figures.

Page 4: SSDP33-70 Handbook - Pumps Direct 2 U · PDF fileSSDP33-70 Handbook ... AC Wiring diagram 400 Volt P70 16 ... Check the rating and electrical safety of the load before connecting the

2 GENERAL SAFETY 2.1 Warning signs

Warnings shown on the machine should be observed at all times. The warning signs should be checked for legibility and any that have become damaged should be replaced. The following are shown on the generator:

2.2 Safety hazards Do not climb on the generator, as dents may cause overheating of the acoustic lining. It is important to keep the generator clean and well serviced, in particular keep all air vents / louvers clear of debris to prevent poor performance or possible overheating and permanent damage to the generator. Keep well clear of moving parts on the generator at all times. Children and pets must be kept clear of the operating area.

3 POTENTIAL HAZARDS 3.1 Auxiliary power

The electricity produced by an engine driven Generator is very similar to mains electricity and should be treated accordingly. Do not remove covers and attempt to work on the Generator while the engine is running. Check the rating and electrical safety of the load before connecting the Generator. Equipment should never be connected that in total exceeds the specified rating of the Generator. Installation of the generator as a standby or secondary power source should only be undertaken by a fully qualified electrician using the appropriate means of isolation from the mains supply. Installation must comply with all applicable laws and electrical codes.

3.2 Operating Environment

The Generator should always be operated on ground level. 3.3 Temperature Range

A temperature range between -15˚C and +45˚C are the normal limits of operation. Operating outside the range will require additional modifications.

3.4 Reference Relative Humidity

The standard reference condition for relative humidity is 30%. Above this value the rated power must be reduced.

CAUTION

HOT EXHAUST

RISK OF ELECTRIC SHOCK ALWAYS TURN OFF GENERATOR BEFORE OPENING. KEEP

CLOSED AT ALL OTHER TIMES

BEFORE STARTING.

• READ HANDBOOK AND SAFETY ADVICE

• CHECK OIL LEVEL

• DO NOT ADJUST ENGINE SPEED WITHOUT SUITABLE TEST EQUIPMENT

WARNING

Page 5: SSDP33-70 Handbook - Pumps Direct 2 U · PDF fileSSDP33-70 Handbook ... AC Wiring diagram 400 Volt P70 16 ... Check the rating and electrical safety of the load before connecting the

3.5 Reference Barometric Pressure

The standard reference condition for total barometric pressure is 1 bar. This corresponds to an altitude of approximately 100m. Above 100m the rated power must be reduced.

3.6 Flammable Environment

Stephill Generators must not be used in a flammable environment. 3.7 Saline Environment

Operation of the machine in a saline environment will require additional corrosion protection.

4 SAFETY CONSIDERATIONS 4.1 General

All Stephill Generators comply with all the current EEC directives including 89/392/EEC Machine Safety and The noise emission in the environment by equipment for use outdoors regulation 2001 (SI 2001/1701).

4.2 Fuel

Fuels and lubricants are a potential source of fire. Lubricants in particular used engine oil, are potentially carcinogenic. Direct contact should always be avoided by wearing suitable rubber gloves when handling them. Be careful not to spill fuel, clean up any spillages. Inhalation or swallowing of Diesel should be avoided. If in doubt seek medical advice. All other forms of contact are irritant and therefore should also be avoided. If skin contact is made wash with soap and water.

4.3 Bunded tank

This generator is fitted with a secondary containment system (Bunded tank). The bund will need to be inspected on a regular basis and drained accordingly. Any liquid drained from the Bund/Tank will have to be treated as Oil/Fuel contaminated waste and disposed of accordingly. Warning Although this generator is fitted with a Bunded tank it is the duty of the owner to ensure that it meets with Local/National regulations dependant on site location etc.

4.4 Lubricating Oil

New oil presents no hazard following short term exposure. Used oil should not be allowed to contact the skin. If this does occur, wash off quickly with a proprietary hand cleanser.

4.5 Safe Lifting

Where mechanical assistance is used in lifting machines, ensure the lifting eye is used, and that all components used to lift the machine are within their Safe Working Load (SWL). The integral lifting beam and associated lifting eye on the generator should be regularly checked for signs of damage or gross corrosion. All Nuts and Bolts associated with the lifting beam should be regularly checked for tightness and corrosion. Lifting equipment should not be attached directly to the Engine/Alternator except for lifting of Engine/Alternator only.

4.6 Earth connection

All Stephill products are fitted with an earth stud on the control panel this must be connected to an earthing system or spike. Any earth spike required is dependant on the local conditions of use. The size is determined by reference to current IEE regulations or to a competent electrician.

Page 6: SSDP33-70 Handbook - Pumps Direct 2 U · PDF fileSSDP33-70 Handbook ... AC Wiring diagram 400 Volt P70 16 ... Check the rating and electrical safety of the load before connecting the

4.7 Fumes

Make sure that the Generator is at least 2 metres away from any building during operation. Operate in a well ventilated unconfined area, so that fumes can be properly dispersed. Silencer outlet should be facing an open area to prevent fumes being recirculated. There is the danger of asphyxiation due to exhaust gases. Inhalation of poisonous exhaust fumes can lead to serious injury or death. The generator must not be used in a poorly ventilated or enclosed area.

4.8 Noise

Ear protection may be required depending on the combined noise level of the Generator, auxiliary load and the operator’s distance from it and the length of exposure. (Noise at Work Regulations 1989)

4.9 Battery Acid

This is corrosive and irritant by all forms of exposure. If skin contact is made wash with clean water.

4.10 Fire

Ensure that suitable fire extinguishers (AFFF or CO2) are kept within close proximity of the generator. Do not cover, enclose, or obstruct the airflow to the generator during or shortly after use, due to fire hazard or damage to the generator from overheating. Allow the generator to cool after use before storing away. Keep all inflammable objects clear of the Generator.

4.11 Hot parts

There is the danger of burns as parts of the generator will become very hot during use. No part of the engine, alternator or exhaust must be touched during or shortly after operation. Do not operate the generator unless all guards are in place. There is a risk of burns or serious mechanical injury.

5 OPERATING INSTRUCTIONS

5.1 Pre-start checks

Before starting the generator please read the engine owners manual. Check Fuel ‘Water & Oil level before attempting to start. Ensure 3 way valve is in correct position. This engine is equipped with an oil’ temperature and low water level switch and will shutdown for any of these fault conditions. Inspect the generator visually for signs of fault or damage.

5.2 Emergency stop

The generator is equipped with an emergency stop button which should only be used in an emergency and not for general stopping.

5.3 Three Way valve

This unit is equipped with a 3 Way valve (3/8” BSP fittings) which needs to be set to the correct position for the Generator to operate ‘an instruction label is located next to the fuel filler. The Engine is fitted with a lift pump for fuel delivery but this is not capable of lifting fuel above 1524mm height with a maximum length of 3048mm and minimum internal diameter of 8mm, this means you can only have the fuel tank 300mm below the level of the generator with 910mm of hose. It is therefore advisable to have the remote fuel tank at a higher level than the generator fuel tank to allow gravity feed to the lift pump. If this is not possible a remote fuel pump with a bypass valve fitted will suffice. If in any doubt please consult manufacturer.

Page 7: SSDP33-70 Handbook - Pumps Direct 2 U · PDF fileSSDP33-70 Handbook ... AC Wiring diagram 400 Volt P70 16 ... Check the rating and electrical safety of the load before connecting the

5.4 Fuel lift pump priming If engine runs out of fuel do not attempt to start until fuel bowl is full of diesel this can be achieved by pressing FUEL PUMP button until bowl is full of diesel. The engine should then self bleed and start.

5.5 Control panel

This generator is equipped with an RCD on the 400/230 Volt supply only. Before connecting plugs into generator please ensure the load is turned off. If this is not possible turn the circuit breaker to the off position. Connect the plugs into the generator. Switch on the load / Circuit breaker. This unit is also fitted with individual Circuit Breakers on each socket. Warning

Always switch load off before disconnecting plugs. To switch power off at Generator always use circuit breaker.

5.6 Variable RCD ELR-3C

The RCD and Bypass switch should only be adjusted or switched by an electrician with the appropriate test equipment. ELR-3C Earth Leakage Relay Description Its wide setting ranges allows to select the tripping current, in order that the contact voltage values are maintained below 50V as required by the CEI 64-8Standard. This is also the suitable answer for a proper selectivity,whenever there are other ELR’s or/and RCD’s downstream or upstream in the line to be protected. An outstanding characteristic of the present relays, is the permanent control of the Toroidal - ELR circuit. Its interruption brings along the immediate trip of the protection. This allows to identify the anomaly, without waiting to the periodical control, made with the Test push button. The instrument , fitted with filters at the input circuits, is practically immune to external disturbances, so as the pulse currents with dc components, complying with the requirements of VDE 0664 and project IEC 23 Standards. The ELR-3C has the possibility of an automatic or manual reset, selectable by a microswitch and to protect the settings by its sealable transparent front cover.

1)Current tripping setting potentiometer. 2) Tripping time setting potentiometer. 3) Microswitches for programming: -a In position 1 automatic reset, In position 0 manual reset -b Selection of the multiplying constant Tripping time, in position 1 K=10 in position 0 K=1 - c,d Selection of the multiplying constant of tripping current: With c d in position 0 K=0.1 With c in position 1, d in position 0 K=1 With c,d in position 1 K=10 4) Push button for Test 5) Push button for manual reset 6) Signalling green LED for Aux. Supply presence

7) Signalling red LED for relay tripped 8) Terminals for Aux. Supply 9) Output terminals for end relays 10)Connection terminals to T/T CT-1

Page 8: SSDP33-70 Handbook - Pumps Direct 2 U · PDF fileSSDP33-70 Handbook ... AC Wiring diagram 400 Volt P70 16 ... Check the rating and electrical safety of the load before connecting the

5.7 Hard wire terminals Do not attempt to work on the hard wire terminals while the set is running. The generator is fitted with hard wire terminals which are located under the Circuit breakers, the terminals are clearly marked for 400Volt. They can be accessed by either drilling the steel gland plate or passing the cables through the rubber gland plate. If cables are passed through the rubber gland plate they must be secured with cable ties to the bar inside to prevent strain on terminals. The gland plate should be re-fitted prior to running generator.

5.8 Remote start terminals

The generator is equipped with a pair of normally open contacts which will start the generator when closed.

5.9 Long term storage

For storage or long periods of inactivity, Stephill Generators recommend the following: Generators should be stored with oil filled to the correct capacity; Storage periods of 18 months and over may require special lubricants and treatments. If so please seek further advice from the engine manufacturer. Before the generator is used after long term storage, all fuels and oils should be replaced. Generator mounts, pipes and hoses should be checked to ensure that they are un-perished following extended periods of storage. The generator should be stored in a clean dry area, ideally having a reasonable constant ambient temperature, and ideally not below freezing. The battery isolator switch should be switched off.

6 INTELILITE MRS 15 OPERATING INSTRUCTIONS 6.1 Pushbuttons and LEDs

1. MODE→ : Cyclic forward selection the gen-set operation mode (OFF -> MAN -> AUT ) 2. ←MODE : Cyclic backward selection the gen-set operation mode (AUT -> MAN - OFF) 3. HORN RESET : Deactivates the HORN 4. FAULT RESET : Acknowledges faults and alarms 5. START : Start of the gen-set 6. STOP : Stop of the gen-set

Page 9: SSDP33-70 Handbook - Pumps Direct 2 U · PDF fileSSDP33-70 Handbook ... AC Wiring diagram 400 Volt P70 16 ... Check the rating and electrical safety of the load before connecting the

8. GCB ON/OFF : ^Manual open/close of the Generator circuit breaker 9. PAGE : Cyclic selection of the display mode 10. Select the screen 11. Select the screen 12. ENTER LEDs 15. GEN VOLTAGE PRESENT: GREEN LED is on, if gen. voltage is present and within limits 16. GEN-SET FAILURE: RED LED starts flashing when gen-set failure occurs. After FAULT RESET button is pressed, goes to steady light (if an alarm is still active) or is off (if no alarm is active)

6.2 InteliLIte MRS 15 starting instructions

MAN mode START. - starts the gen-set. STOP stops the gen-set. AUT mode The controller does not respond to buttons START, STOP. Engine start/stop request is given by binary input REM START/STOP. 6.3 Gen-set operation states

Init Autotest during controller power on

Not ready Genset is not ready to start

Prestart Prestart sequence in process, Prestart output is closed

Cranking Engine is cranking

Pause Pause between start attempts

Starting Starting speed is reached and the Idle timer is running

Running Genset is running at nominal speed

Loaded Genset is running at nominal speed and on load

Stop Stop

Shutdown Shut-down alarm activated

Ready Genset is ready to run

Cooling Genset is cooling before stop

Page 10: SSDP33-70 Handbook - Pumps Direct 2 U · PDF fileSSDP33-70 Handbook ... AC Wiring diagram 400 Volt P70 16 ... Check the rating and electrical safety of the load before connecting the

6.4 Measurement screen description Main measure screen

1. Operation mode of the gen-set 2. Indication of active access lock, Remote OFF or Remote TEST L and alarm ! 3. Status of the gen-set 4. Unused 5. RPM of the gen-set 6. Active power 7. Power factor 8. Timer - events counting time (e.g. prestart, cooling, etc.)

6.5 Generator screen Gen freq Gen V1-2, V2-3, V3-1 ph-ph Gen V1, V2, V3 ph-N (triple bargraph) Gen I1, I2, I3 (triple bargraph) 6.6 Analogue inputs screen Oil pressure (single bargraph) Water temperature (single bargraph) Fuel level (single bargraph) Battery voltage 6.7 Inputs

BInpIL 0 0 0 0 0 I (Running)

Rem Start / Stop 0 Coolant level 0

Emergency stop 0 High Eng Temp 0

Low Oil Press 0 Hard wire door I

6.8 Outputs

BOutIL 0 I I I 0 0 (Running)

Starter 0

Fuel solenoid I

Alarm I Air valves I Not used 0

Not used 0

6.9 Gen-set power screen Active power (total and per phase) Power factor (total and per phase) React power (total and per phase) Appar power (total and per phase) 6.10 Statistics Run hours Number of starts *Kilowatt-hours kWh (total) *Reactive power hours kVAh (total only) NextServTime

6.11 How to find active alarms Active alarm list is the last screen in the MEASUREMENT menu. Select MEASUREMENT menu. Press ↑ You will see the list of all active alarms with the number of alarms at the top-right corner Three state alarms are introduced:

Page 11: SSDP33-70 Handbook - Pumps Direct 2 U · PDF fileSSDP33-70 Handbook ... AC Wiring diagram 400 Volt P70 16 ... Check the rating and electrical safety of the load before connecting the

6.12 List of possible alarms Note WRN = Warning SD = Shutdown

Events specification Protection type Description

Oil Press Wrn WRN Oil pressure is smaller than Wrn Oil press setpoint.

Oil Press Sd SD Oil pressure is smaller than Sd Oil press setpoint.

Water Temp Wrn WRN Water temperature is greater than Wrn Water temp setpoint.

Water Temp Sd SD Water temperature is greater than Sd Water temp setpoint.

Fuel Level Wrn WRN Fuel level is smaller than Wrn Fuel Level setpoint.

Fuel Level Sd SD Fuel level is smaller than Sd Fuel Level setpoint.

Coolant level Sd SD Coolant level low

Battery voltage <, > WRN Battery voltage is out of limits given by Batt overvolt and Batt undervolt setpoints.

Battery flat SD If the controller switches off during starting sequence due to bad battery condition it doesn’t try to start again and activates this protection.

Start failed SD Gen-set start failed.

Vgen <, > SD The generator voltage is out of limits given by Gen <V and Gen >V setpoints.

Vgen unbl SD The generator voltage is unbalanced more than the value of Volt unbal setpoint.

Fgen <,> SD The generator frequency is out of limits given by Gen >f and Gen <f setpoints.

Igen unbl SD The generator current is unbalanced.

Overload SD The load is greater than the value given by Overload setpoint.

Overspeed SD The protection comes active if the speed is greater than Overspeed setpoint.

Underspeed SD During starting of the engine when the RPM reaches the value of Start RPM setpoint the starter is switched off and the speed of the engine can drop under Start RPM again. Than the Underspeed protection comes active.

Emergency Stop SD If the input Emergency stop is opened shutdown is immediately activated.

PickupFault SD Failure of magnetic pick-up sensor for speed measurement or Failure of Alternator supply to unit.

Stop fail SD Gen-set stop failed.

WrnServiceTime WRN The period for servicing is set by the NextServTime setpoint. The protection comes active if the running hours of the engine reach this value.

ChrgAlternFail WRN Failure of alternator for charging the battery.

Hard wire door Sd SD Hard wire door open.

Page 12: SSDP33-70 Handbook - Pumps Direct 2 U · PDF fileSSDP33-70 Handbook ... AC Wiring diagram 400 Volt P70 16 ... Check the rating and electrical safety of the load before connecting the

6.13 Re-setting Service counters To re-set service counters

Press Page “Password” Press Enter Enter Password Press Enter Default “0” or “1234” or Company specific code _ _ _ _ (Use up or down arrows) Press Enter Press Page Press Down arrow until “Engine protect” appears Press Enter Press Down arrow until “NextServ Time” appears Press Enter increase service time by 500 Hours by using Up arrow Press Enter Press Page Press Page Operation complete

7 SERVICE AND MAINTENANCE

IMPORTANT WARNING: After any service on the generator, ensure that all piping and electrical cables are correctly routed and secured away from hot parts. Failure to observe this warning may result in damage to the piping and cables which could result in a fire.

Do not service or work on generator whilst the engine is running. Do not service or work on the generator while wearing loose clothing.

7.1 Engine service Service the engine strictly in accordance with the instructions given in the relevant operator manual / handbook. An approved specialist must carry out any maintenance. Any spare parts required should be of genuine manufacturer’s origin. Note: failure to adhere to manufacturer’s recommended service schedules may invalidate the warranty. Please consult engine operator’s manual for full service intervals.

7.2 Alternator service Brushless alternators employed on Stephill Generators are maintenance free. Service must be carried out by competent qualified personnel strictly in accordance with the instructions given in the handbook. Any spare parts required should be of genuine manufacturer’s origin.

8 SPARES

8.1 Perkins consumable spares

Description P33 1103A-33G

P50 1103A-33TG1

P70 1103A-33TG2

Campaign Oil filter 011-0008 011-0008 011-0008

Fuel filter element 011-0009 011-0009 011-0009

Air filter element outer (Housing 2652C112) 011-0010 011-0010 011-0010

Air filter element inner (Housing 2652C112) 011-0012 011-0012 011-0012

Air filter element outer (Housing 2652C141) 011-0013 011-0013 011-0013

Air filter element inner (Housing 2652C141) 011-0014 011-0014 011-0014

Fan belt 011-0011 011-0011 011-0011

8.2 SSDP33-70 Spares

Description P33 1103A-33G P50 1103A-33TG1 P70 1103A-33TG2

Perkins Engine 011-0005 011-0006 011-0007

Meccalte ECO Alternator 018-0043 018-0072 018-0059

Reactive Silencer(1stSilencer) 016-0133 016-0175 016-0175

Absorption Silencer (With tail pipe) 016-0135 016-0176 016-0176

U Pipe 016-0136 016-0177 016-0177

Manifold flex pipe 016-0145 016-0178 016-0178

Rain cap 022-1006 016-1069 016-1069

Transit mount Qty 4 009-0153 009-0153 009-0153

Page 13: SSDP33-70 Handbook - Pumps Direct 2 U · PDF fileSSDP33-70 Handbook ... AC Wiring diagram 400 Volt P70 16 ... Check the rating and electrical safety of the load before connecting the

8.3 General spares

Part Number Description Qty

016-0148 Polycarbonate door (Does not include steel door) 1

022-0121 Exhaust bandage 3M

016-1052 Temperature sender 1

045-0034 InteliLite MRS 15 1

022-1000 Handle slam lock (Canopy door) 2

022-1001 Industrial lock chrome (Control panel door) 1

022-1003 Finger pull (Control panel door) 1

022-1007 Hinge Black 76mm (Canopy door) 4

022-0037 Housing radiator lock 1

022-0036 Insert slot 2 x 4 radiator lock 1

022-0035 Cam 28mm radiator lock 1

022-0039 Door seal 6

022-0040 Radiator flap seal 0.5

022-0042 Door hinge M5 (Control panel door) 2

016-0150 Fuel pipe brass 1/8” 278mm 1

016-1023 Breather Hose 1” 1

016-1051 Liquid level sensor (Radiator) 1

020-0246 Packard mating kit (Liquid level sensor) 1

016-1050 Emergency stop pan (Housing only) 1

020-0102 Emergency stop button 1

020-0332 Push button and mounting collar Green 1

020-0333 Push button and mounting collar Blue 1

020-0334 Auxiliary contact block N/O 3

020-0340 2 Pole change over relay 12V DC 1

020-0335 Diode and capacitor block 1

020-0195 1 Pole 30Amp relay 1

020-0339 Relay base 30Amp 1

020-0309 Fuse holder 1

020-0337 30Amp fuse 1

045-0031 150/5 Current transformer 3

020-0344 50Amp 4 Pole MCB 1

020-0345 63Amp 4 Pole RCD 30mA 1

020-0285 32Amp 3 Pole MCB 1

020-0284 32Amp 1 Pole MCB 3

022-0091 M8 Terminal stud 5

038-0101 Barrier terminal 2

038-0100 Barrier terminal end plate 1

009-0130 M10 Rubber foot (Door stop) 1

020-0311 Battery terminal cover Red 1

020-0312 Battery terminal cover Black 1

020-0243 Battery isolator switch 1

020-0229 400V 32Amp Socket 1

020-0227 230V 32Amp Socket 3

020-0226 115V 32Amp Socket 3

039-0001 DC Engine wiring loom 1

039-0002 DC Panel loom 1

Page 14: SSDP33-70 Handbook - Pumps Direct 2 U · PDF fileSSDP33-70 Handbook ... AC Wiring diagram 400 Volt P70 16 ... Check the rating and electrical safety of the load before connecting the

9 WARRANTY All equipment supplied by STEPHILL GENERATORS LTD carries a warranty of 12 months from date of despatch. During the warranty period, should the plant fail due to faulty design, materials or workmanship by STEPHILL or it’s sub-contractors, we undertake to rectify the fault. STEPHILL will accept no responsibility whatsoever for equipment that has failed due to; - Operation with incorrect fuel, lubricating oil or coolant. - Improper repair or use of parts not supplied by STEPHILL. - Lack of, or incorrect maintenance. - Fair wear and tear, misuse, negligence, accidental damage, improper storage, incorrect starting / warm-up / run-in or shutdown. No warranty claim will be considered by STEPHILL unless any defective parts are available for inspection by us, or our nominees, to determine the reason or cause of failure, and STEPHILL is given the option of repair or replacement. STEPHILL are not responsible for incidental or consequential damages, downtime, or other costs due to warrantable failure, and unauthorised alterations made to any product supplied by STEPHILL.

Page 15: SSDP33-70 Handbook - Pumps Direct 2 U · PDF fileSSDP33-70 Handbook ... AC Wiring diagram 400 Volt P70 16 ... Check the rating and electrical safety of the load before connecting the

4 23

1

5

67

8

11

12

131415 16

1718 1920

21

22

23

24 27 28

10

29 3132

34 35

37 38

40

30

41

39

25

26

36 9

33Part No Description Qty

1 16-101 SSD30 Door 22 16-102 SSD30 Base 12 16-164 SSD67 Base 13 16-103 SSD30 Roof 13 16-163 SSD67 Roof 14 16-104 SSD30 Alternator side panel 14 16-170 SSD67 Alternator side panel 15 16-107 SSD30 Alternator control panel side 15 16-169 SSD67 Alternator control panel side 16 16-108 SSD30 Control panel housing 17 16-109 SSD30 Control panel door 18 16-110 SSD30 Gland plate 19 16-111 Rubber gland retaining plate 1

10 16-115 SSD30 Engine end panel 111 16-116 SSD30 Door base 112 16-117 SSD30 Engine side panel 112 16-165 SSD67 Engine side panel 113 16-118 SSD30 Engine fuel filler side panel 113 16-166 SSD67 Engine fuel filler side panel 114 16-119 SSD30 Perkins 1103 Radiator plate 115 16-120 SSD30 Perkins radiator baffle plate 115 16-173 SSD67 Perkins radiator baffle plate 116 16-121 SSD30 U Clamp bracket 317 16-122 SSD30 Alternator channel 118 16-123 SSD30 Engine channel 119 16-126 SSD30 Battery tray 120 16-127 SSD30 Battery bracket 121 16-128 SSD30 Bund blank plate 121 16-167 SSD67 Bund blank plate 122 16-129 SSD30 Fuel tank 122 16-168 SSD67 Fuel tank 123 16-130 SSD30 Fuel tank inspection plate 124 16-132 SSD30 Radiator flap 125 16-146 SSD30 1103 Radiator plate spacer 226 16-147 SSD30 Perkins Fuel filter bracket 127 16-155 SSD30 Roof foam bracket 128 16-171 SSD30 Alternator end panel (Mark 2) 129 16-172 SSD30 Alternator air inlet duct (Mark 2) 130 16-174 SSD67 Alternator end air inlet plate 131 16-195 SSD30 Control panel rain guard 132 16-208 SSD30 Roof Baffle plate 133 16-181 SSD67 Alternator side air inlet duct 134 16-144 SSD30 Bund plate gasket 134 16-179 SSD67 Bund blank plate gasket 135 16-142 SSD30 Fuel tank gasket 136 16-138 SSD30 Rubber gland plate 137 16-124 SSD30 Lifting beam 138 16-125 SSD30 Lifting eye 139 23-205 SSDX20 Hard wire door barcket 240 16-143 SSD30 Hard wire terminal door 141 16-003 SSD30 Multivoltage control panel 1

R Golding

Date RevisionIssueTHIRDANGLE

PROJECTION

Description

Fax 01933 677916Phone 01933 677911

Drawing Number

DrawnSSDP33-70 Exploded view16-140STEPHILL GENERATORS Material

Mild steelFinishPowder coat

10/01/06 New drawingA16/11/07 P50 / 70 Information added.B

Page 16: SSDP33-70 Handbook - Pumps Direct 2 U · PDF fileSSDP33-70 Handbook ... AC Wiring diagram 400 Volt P70 16 ... Check the rating and electrical safety of the load before connecting the
Page 17: SSDP33-70 Handbook - Pumps Direct 2 U · PDF fileSSDP33-70 Handbook ... AC Wiring diagram 400 Volt P70 16 ... Check the rating and electrical safety of the load before connecting the
Page 18: SSDP33-70 Handbook - Pumps Direct 2 U · PDF fileSSDP33-70 Handbook ... AC Wiring diagram 400 Volt P70 16 ... Check the rating and electrical safety of the load before connecting the
Page 19: SSDP33-70 Handbook - Pumps Direct 2 U · PDF fileSSDP33-70 Handbook ... AC Wiring diagram 400 Volt P70 16 ... Check the rating and electrical safety of the load before connecting the