20mm layer of NOFIRNOsealant. 60mm RISENOFIRNO Multi sleeves
• Certi�ed Pressure Resistance – 4 bar
Step 1
Adding new cables is a simple process. Cut awaythe sealant layer using a plastic knife or hollow punch. Take care not to damage existing cables.A hole slightly larger thanthe new cable should be made.
Step 2 Step 3
Pull the new cable through one of the empty �ller sleeves. Use an approved degreaser to ensure the cable sheath is clean and free from dirt, dust or oil to ensure the sealant will bond to the cable.
Step 4
Re�ll the opening cut in the sealant layer with suf�cient sealant. A slight over�ll is required.
Adding a cable.
Standard RISE RAPID Duct Seal kits – order table.
NOTE: RISE can be used to suit ANY size opening. If the above standard selection does not suit your requirements please contact us.
TOOLS REQUIRED
RISE FINISHING KITS AVAILABLE
• High ratio sealant gun• Disposable nitrile gloves• Approved cloths• Long nose pliers
• Water spray• Wooden 20mm depth gauge• Wire brush• Approved degreaser• Sleeve cutting tool
REQUIREMENT SIZE ORDER CODEGASTIGHT/WATERTIGHT
125MM DUCT
RISEDUCT125-RGASTIGHT/WATERTIGHT
160MM DUCT
RISEDUCT160-RGASTIGHT/WATERTIGHT
200MM DUCT
RISEDUCT200-RGASTIGHT/WATERTIGHT
225MM DUCT
RISEDUCT225-RGASTIGHT/WATERTIGHT
250MM DUCT
RISEDUCT250-RGASTIGHT/WATERTIGHT
300MM DUCT
RISEDUCT300-R
RISE Finishing Kit (includes water spray, cloths, nitrile gloves, wooden gauge, long nozzels & angles)
RISE Full Installation Kit (includes all tools)
RAPID
Simple and effective
The RISE RAPID Duct seal has been developed with speed of installation in mind, but without compromising on the high levels of reliability and safety synonymous with our range of RISE Duct sealing systems.
The innovative multi sleeves are supplied bonded in strips of ten, making installation even quicker than with our traditional RISE Duct Seals. Bonded sleeves can be easily torn off if neccessary and with our cutting tool, sleeves can be quickly slit to �t around cables.
Gas and water tight
The elasticity and high bonding strength of NOFIRNO sealant offers a �exible seal, which resists movement, shock and vibration, as well as high pressure. The RISE NOFIRNO multi sleeves ensure cable separation and are used to pack the free space and provide a backing for the application of the sealant. The completed duct seal will prevent the migration of dangerous gases and provide �ood protection and has been independently tested to prove no deteriation in performance for more than 50 years.
RISE NOFIRNO Multi sleeve
cable
cable
20mm 60mm
NOFIRNO sealant 20mm thick
For further information contact 01670 739 970 or visit www.csdsealingsystems.co.uk
GASTIGHT/WATERTIGHTGASTIGHT/WATERTIGHT
1 KIT = 100MM DUCT2 KITS = 150MM DUCT
150MM DUCT
RISEDUCT-R
RISEDUCT150-R
300MM DUCT RISEDUCT300-R
Finish the sealant layer in the usual way. Using a damp cloth pat downthe NOFIRNO sealant, ensure the sealant makes good contact with the cable and the existing sealant layer. Finally, smooth the surface by hand.
Installation instructionsThe RISE RAPID Multi Cable and Pipe Transit Sealing System provides an effective and simple solution to all gas and water tight duct sealing requirements. It consists of only two components: NOFIRNO sealant, a silicone based fire resistant, water repellent sealant and rubber multi sleeves. These joined sleeves make the system even quicker and easier to install than the standard RISE Duct Seal.
Step 1
Ensure the duct openingis clear, removing any debris which may interfere with the installation of the RISE Duct Seal. The duct should also be dry.
Step 2
Using an approved degreasing cleaner, thoroughly clean the inside 20mm edge of the transit. All dirt, dust, rust or oil residues must be removed to ensure a good bond of the NOFIRNO sealant to the ducting.
Step 3
Using the sleeve cutting tool, slit a quantity of the No�rno sleeves, about equal to the quantity of cables in the duct.
Step 4
Place a split sleeve around each of the cables in the duct and then push the multi sleeves into the duct.For larger or single cables,this is not necassary. Simply ensure the multi sleeves provide separation between cables and between the duct and cables.
Step 5
Fill the remaining free space with spare NOFIRNO multi sleeves.
Step 6
Smaller gaps should be �lled with smaller sized 18/12 NOFIRNO �ller sleeves. Filler sleeves can be easily separated in to smaller quantities. It is important to ensure �ller sleeves are tightly packedinto the transit to create a solid base for the application of the sealant.
Step 7
Push all of the �ller sleeves into the duct.
Step 8
Leave 20mm free space at the front of the duct for the application of the NOFIRNO sealant layer.
Step 9
Adjustments can be made to the �ller sleeves using a pair of long nosed pliers. Allowing the correct 20mm depth will ensure a suitable layer of sealant is applied and a good seal is maintained.
Step 10
Attach the nozzle to the NOFIRNO sealant cartridge and snip the nozzle at an angle, this will help installation. For awkward applications longer nozzles and angled applicators are available.
Step 11
Using a specialist high ratio caulking gun, apply the NOFIRNO sealant to the most awkward places, (around cables). Apply sealant against sleeves, allowing to �ll out to the required 20mm depth; a slight over�ll is needed.
Step 12
Using the water spray dampen a cloth, this is done to stop the sealant from sticking to the cloth whilst working with it. When working with the NOFIRNO sealant we recommend the use of disposable nitrile gloves.
Step 13
Using a dabbing motion, pat down the NOFIRNO sealant, ensuring the sealant makes good contact with both cable and the duct wall. The sealant should stand just proud of the duct; allowing any water to run off the surface without pooling.
Step 14
Use the water spray to wet your gloves, this will ensure the sealant does not stick to the gloves.
Step 15
The surface of the NOFIRNO sealant should then be �nished off by hand. Ensuring a good smooth �nish is obtained.
Step 16
Take a �nal check with a torch to ensure suf�cient sealant has been applied and the transit is properly sealed. If there are any areas that do not seem suf�ciently sealed add more NOFIRNO sealant in this area and smooth off in the usual way.
Step 17See overleaf for
‘Adding or replacing a cable’
The completed RISE RAPID Duct Seal will provide a 4 bar (58 psi) water tight and 1.0 bar (15 psi) gas tight rated seal. The RISE NOFIRNO system is proven to provide maintenance free protection for a period in excess of 50 years.
Step 1
Adding new cables is a simple process. Cut awaythe sealant layer using a plastic knife or hollow punch. Take care not to damage existing cables.A hole slightly larger thanthe new cable should be made.
Step 2 Step 3
Pull the new cable through one of the empty �ller sleeves. Use an approved degreaser to ensure the cable sheath is clean and free from dirt, dust or oil to ensure the sealant will bond to the cable.
Step 4
Re�ll the opening cut in the sealant layer with suf�cient sealant. A slight over�ll is required.
Adding a cable.
Standard RISE RAPID Duct Seal kits – order table.
NOTE: RISE can be used to suit ANY size opening. If the above standard selection does not suit your requirements please contact us.
TOOLS REQUIRED
RISE FINISHING KITS AVAILABLE
• High ratio sealant gun• Disposable nitrile gloves• Approved cloths• Long nose pliers
• Water spray• Wooden 20mm depth gauge• Wire brush• Approved degreaser• Sleeve cutting tool
REQUIREMENT SIZE ORDER CODEGASTIGHT/WATERTIGHT
125MM DUCT
RISEDUCT125-RGASTIGHT/WATERTIGHT
160MM DUCT
RISEDUCT160-RGASTIGHT/WATERTIGHT
200MM DUCT
RISEDUCT200-RGASTIGHT/WATERTIGHT
225MM DUCT
RISEDUCT225-RGASTIGHT/WATERTIGHT
250MM DUCT
RISEDUCT250-RGASTIGHT/WATERTIGHT
RISE Finishing Kit (includes water spray, cloths, nitrile gloves, wooden gauge, long nozzels & angles)
RISE Full Installation Kit (includes all tools)
For further information contact 01670 739 970 or visit www.csdsealingsystems.co.uk
GASTIGHT/WATERTIGHTGASTIGHT/WATERTIGHT
1 KIT = 100MM DUCT2 KITS = 150MM DUCT
150MM DUCT
RISEDUCT-R
RISEDUCT150-R
300MM DUCT RISEDUCT300-R
Finish the sealant layer in the usual way. Using a damp cloth pat downthe NOFIRNO sealant, ensure the sealant makes good contact with the cable and the existing sealant layer. Finally, smooth the surface by hand.