LINDA LINGLE GOVERNOR OF HAWAII STATE OF HAWAII DEPARTMENT OF LAND AND NATURAL RESOURCES COMMISSION ON WATER RESOURCE MANAGEMENT P.O. BOX 621 HONOLULU. HAWAII 96809 March 30, 2004 Mr. Edward T. Tschupp Manager and Chief Engineer County of Kauai Department of Water P.O. Box 1706 Lihue, HI 96766 Dear Mr. Tschupp: Well Completion Report for Well No. 0023-02 PETER T. YOUNG CHAIRPERSON MEREDITH J. CHING CLAYTON W. DELA CRUZ JAMES A. FRAZIER CHIYOME L. FUKINO. M.D. STEPHANIE A. WHALEN ERNEST y.w. LAU OEPUTY DIRECTOR 0023-02.wcr2 Thank you for submitting the pump curves for the permanent pump that wa!? installed in Pukaki Well (Well No. 0023-02). We received the documents on March 25, 2004r'and acknowledge that the Well Completion Report Part II is now complete. If you have any questions, please contact Lenore Y. Nakama of the Commission staff at 587-0218 or toll-free at 274-3141 (Kauai), extension 70218. LYN:ss c: Beylik Drilling, Inc. Sincerely, -/,,, ERNEST Y.W. LAU Deputy Director /

Upload: hoangcong

Post on 10-Jul-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

LINDA LINGLE GOVERNOR OF HAWAII

STATE OF HAWAII DEPARTMENT OF LAND AND NATURAL RESOURCES

COMMISSION ON WATER RESOURCE MANAGEMENT P.O. BOX 621

HONOLULU. HAWAII 96809

March 30, 2004

Mr. Edward T. Tschupp Manager and Chief Engineer County of Kauai Department of Water P.O. Box 1706 Lihue, HI 96766

Dear Mr. Tschupp:

Well Completion Report for Well No. 0023-02

PETER T. YOUNG CHAIRPERSON

MEREDITH J. CHING CLAYTON W. DELA CRUZ

JAMES A. FRAZIER CHIYOME L. FUKINO. M.D. STEPHANIE A. WHALEN

ERNEST y.w. LAU OEPUTY DIRECTOR

0023-02.wcr2

Thank you for submitting the pump curves for the permanent pump that wa!? installed in Pukaki Well (Well No. 0023-02). We received the documents on March 25, 2004r'and acknowledge that the Well Completion Report Part II is now complete.

If you have any questions, please contact Lenore Y. Nakama of the Commission staff at 587-0218 or toll-free at 274-3141 (Kauai), extension 70218.

LYN:ss

c: Beylik Drilling, Inc.

Sincerely,

W'~M -/,,, ERNEST Y.W. LAU Deputy Director

/

03/25/04 14 :36 FAX 808 245 5813 DEPT OF WATER ~010

nIT INDUSTRIF '. GOULDS PUMPS - TURBINE Or-~ J'ION ! PERFORMANce TEST RESULTS

CUSTOMS~ ROSCO MOSS 1, .. DO'!... '? - 02. Yu 'LA. ~ \

CUST PIO: 01~156 iTEM: P\JAAKI WELL

~NUM! I 1 liP. OR! 1.00

PUMP TYPe. I OW( VlSC.S$U: 32.

PUMPMCDlL: I mAfiC I

WATER T!MP (P); 7' STAGES: I 1& wmESSED: Y

IMP. MAl\.: 1101 MOTOR 51"': 011207er100R-Ol

1ST IMP. DIA: 6 • .0 151lMP. QlY;

2ND IMP. CIA; 0.00 2ND IMP. Q1Y: 0

CUSTRPM: 1770 ll\Q METEIt: 2

CUSTNP: 30 'TRTEDJY: M.rt< NlI'Ioa . . .. --"-.-

READINGS DURING TEST Potm 1 Z , .(

PSi 2T.U 255.' 211.5 154 ... gl$c;;H. FT. 632.71 613.77 GOt.aT .51Ut EUV. FT. !too 5.00 ~.oo S.CO

VEL FT. 0.00 0.01 0.04 0.C8 ftf1; FRIC. 0.00 0.00 0.00 0.00

PUMPHP 12." 13.79 16.33 151.7:1

1NPUTt(:N 10.so \'.10 13..90 111.50

AMPeR£S 1G.9O 18.10 2D.AO 23.00

\llSl\AnoN

TEST DATA RECORDED AT TEST RPM IU'M ,1S3 1793 '111' 17" GJDM 0 30 61 91

TDt-H:E.ET 637.7 .., ... 6OD.1 592..1

PUMPHP 12.~ 13.' 1U 18.1

PUMPEFF 0.0 ~,4 51:1. &t.0

TEST DATA CONvaRTEO TO CUSTOt.'lER RPM JUItIl 1770 1770 1770 1770 GPM 0 30 w 80

TOtt.f'&T 821.5 8O!.O St4.9 5&0.2 PUMP" 11.8 13.3 15.' 1'.' PUMPEFF 0.0. a... 57.2 89.0

, • I .,. I ,.., .,.."

5

241.0

656.71 5.00

0.14' 0.00

21.4' 18.40

25.30

'786 121

561.9

11.4

BO.2

1770 1%0

5S1.6 20.& 110.2

BOWL-TOH;

P\JIIIP'rDH:

REQGPM:

MAXGf'M: E'fIICIINCY%;

TESTRPD4: TEST MOTOR:

TESTJ.JM;:

CURVE RPM:;

i

205.2 .476.32

5.00 0.23

0.00 2 •• 08

~.20

27.m

,,,eT 151

461.6 l4.1

76.4

1770 1150

472.<4

23.4 7 •• 4

-

459282 12/16102

550.0

lUI

120

180 78J)

1775 3OHf'

4

1770

7

'''.8 340.159

5.00

0.33 0.01

25.07

20.80 28.60

1.00

t787

1a~

3e6.0 15.1 70.1

1770 180

378.7

14.4 70.7

£MJWJ...... 5I2IMI1

--__ ~·~tb_·~--. .. ~· __ - ______ -~ __ -~. ________ ~ ___ , - .. - - - .. C' t *+ ""'....-...-~-..... ...,..~ .................... - ................ • ........ ____ ... wOt'~ ...... ,lf'_ •. __ .~~"'. ___ •

C') .-t Q() It)

It)

~ C\I

Q()

0 Q()

~ co C')

" ~ .-t

~ 0 "-It)

C\I "-C'? 0 ,.

",BN.F007 .Rev 1 SflOO2 .

800

720

640

560 t

t!:,. ~ 48.0 r 0

0:: ~. 400 [3a

0:: 320

240

160

80 7 .-.--------- ---- -·0-o

TDH

-' V

~

I~

~ ~

17

I" ., ,. ~

" ~

20 40

so: 459282 Mode!: 7WAHCl18

,ITT - Goulds Pumps Turbine Operatio~s

Err

l.ooo" -.", II"'" -

J l.ooo" Design -....

~ 1""01. .JI

100

90

t.,;". ,80 ..... -

"- 0' -!-o.. 70

~

~

""'" . 60 ..,

HP • I I

,1 - - --60 80 100 120

Flow-GPM

1""0.. ..... 50

..... i'oo..

40

30

20

10

-- -, 0--140 160 180 200

lmp Dia: 5.40 in ~} Speed: 1770RPM t~

c: _'T" - C

-~ ... ~ c c

'" -c . .j

" ~

~ ,

~ CD . .... ~ ~

0'" ~i!tI.o ifp.':Ci

03/25/04 14:32 FAX 808 245 5813

Fax To: Lenore Y. Nakama

Company: COWRM

Fax: 587-0219

Phone: 587-0218

Pages: 11

o Urgent IZJ For Review

DEPT OF WATER

4398 Pua Loke Street, P. O. Box 1706 Lihue, Kauai, Hawaii 96766

Phone: 808-245-5400 Fax: 808-245-5813 e-mail: [email protected]

From: Michael K. Hinazumi

Phone: (808) 245-5413

Email: [email protected]

Date: March 25, 2004

Re: Pump Curves

o Please Comment 0 Please Reply

t8l Originals will be mailed 0 Originals will not be mailed

X Comments

Please see the attached sheets for Puhi Wells SA & 5B Well Completion Report Part n Pump Curves and the Pukaki Well Pwnp Curve.

If you have any questions, please give me a call.

Thanks, \1 O~~

141 001

LINDA LINGLE GOVERNOR OF HAWAII

STATE OF HAWAII DEPARTMENT OF LAND AND NATURAL RESOURCES

COMMISSION ON WATER RESOURCE MANAGEMENT P.O. BOX 621

HONOLULU, HAWAII 96809

March 22, 2004

Mr. Edward T. Tschupp Manager and Chief Engineer County of Kauai Department of Water P.O. Box 1706 Lihue, HI 96766

Dear Mr. Tschupp:

Well Completion Report for Well No. 0023-02

PETER T. YOUNG CHAIRPERSON

MEREDITH J. CHING CLAYTON W. DELA CRUZ

JAMES A FRAZIER CHIYOME L FUKINO, M.D. STEPHANIE A. WHALEN

ERNEST YW. LAU DEPUTY DIRECTOR

0023-02.wcr

We have received your Well Completion Report Part II for the Pukaki Well (Well No. 0023-02). 7However, matters which must be addressed before we accept your report as complete are as follows:

1. Please submit the pump curves for the permanent pump installed in the well.

If you have any questions, please contact Lenore Y. Nakama of the Commission staff at 587-0218 or toll-free at 274-3141 (Kauai), extension 70218.

LYN:ss

c: Beylik Drilling, Inc.

Sincerely,

Wfr'tH ~ ERNEST Y.W. LAU

Deputy Director

/ /

State of Hawaii COMMISSION ON WATER RESOURCE MANAGEMENT Department of Land and Natural Resources

WELL COMPLETION REPORT - PART II Installation

"-. -"

Instructions: Please print in ink or type and send completed report (with attachments. if applicable) to the Commission on Water Resource Management. P.O. Box 621, Honolulu, Hawaii 96809. The Commission may not accept incomplete reports. This form shall be submitted within 60 days of the completion of work. For assistance. please consult the Hawaii WeH Construction and Pump Installation Standards or call the Regulation Branch at 587-0225. For updates to this form or additional information. please visit our website at http://www.hawaii.goll/dlnr/cwrm/

.,', -- • ' •• j '. ~. ,

Well Name: Pukaki Well 19 1. State Well No.: -,-0-,-02-'.3_-0_2 __ _ Island: Kaua'j -------2. Address: Uhue Basin -------------------------- Tax Map Key: 3-8-2:2 ---------------------3. Pump Installation Company: Beylik Drilling, Inc. ----------------------------------------------4. Date Pump Installed: 5/27/03

--m~-n~W7d~ay~/y-e-ar---------------

5. PERMANENT PUMP INFORMATION (Attach pump specifications and rating curve)

Pump Type, Make, Serial No.: Une Shaft, 7WAHC (18 Stage) Goulds,

Rated Capacity: 120 gpm at head of: 550 ft ----------------- . M t T H P V It US TEFC, 30 HP, 3 Phase 460 v, 1800 RPM o or ype, .. , 0 age, rpm:

Type of flow meter:

Pump type (check one):

61'l Deep Well Turbine o Rotary o Propeller

o Submersible o Rotary-Displacement o Reciprocating

o Centrifugal

6. Method of flow measurement:

o Flowmeter

o Rotary-Gear

Manufacturer

o Impulse

Make Size ------- ---------o Weir 0 Open Pipe 0 Orifice'

'attach schematic

7. Fill in the as-built section on the other side of this sheet.

Ci!"'""Other'. explain below

8. Attach photograph of well and concrete pad clearly showing benchmark on concrete pad.

9. Other remarks/comments:

;..fe. ...... r" /""",,' ~/,...v /"'6~ '<xl";

. Beylik Drilling, Inc. . AC 21896 Pump Installation Contractor (pnnt) _______________ C-57/C-57a!A Llc. No.

Signature ~~~_________________ Date ~/2/0~ _______________ _

Dwight Ho, Division Manager

Permittee (print)

Signature

WCR2 Form 1214/01 Page 1 of 2

/ .

/

- ......................... __ ._------------

9. AS·BUlL T PUMP SECTION (Please attach as-built if different from diagram provided below)

Bench mark elevation surveyed to nearest 0.01 ft. = f-;

3'!~~i..ft. mean sea level

*

*

Elevation of top of chase tube _~ __ ft. mean sea level

I Pump intake depth = -=-~.6~_ ft. (referenced to bench mark)

Chase tube depth = _.:.~O.4~_ ft. (referenced to bench mark)

If airline installed, b?!to/.' of airline elevation = _N/4 __ ft. mean sea level

WCR2 Form 1214101 Page 2 of 2

/ /

".... .,... DEPARTMENT OF WATER

COUNTY OF KAUAI 4398 PUA LOKE STREET

P. O. BOX 1706 LIHUE, KAUAI, HAWAII 96766

PHONE: 808-245-5400 FAX: 808-245-5813

DATE:

TO:

March 9, 2004

Ms. Lenore Nakama Commission on Water Resource Management Department of Land and Natural Resources State of Hawaii P.O. Box 621 Honolulu, HI 96809

~

'WI

LETTER OF TRANSMITTAL

'e!':." "":11.'i~ ,. " ,., " ,'f:' "0 " .... ", • I J - I I,. "I ~'\ ! ~ . ~! I .•

HOSINOt j·,96!..;t:'·:: RE: Lihue-Hanamaulu Water Development

Project, Phase III, Pukaki Well.

We are sending you l attached: _ under separate cover via: _ the following items:

COPIES DESCRIPTION 1 Well Completion Report for Pukaki Well, Well No. 0023-02.

These are transmitted as checked below:

1 For approval signature '---------'

1 For review and comment '---------'

L--_--'I For your Information

1.....-_--'1 Other (see comments below)

REMARKS:

1.....-_...11 Approved as submitted

X 1 As requested

1.....-_-11 Returned for corrections

L--_--'I Return revision with DOW red-lined set

If there are any questions, please call Keith Fujimoto at 245-5449.

Ms. Lynn Malinger, wi enclosure COPIES TO: Mr. Dan Lum wi enclosure

C:\templates\transltr.dot

SIGNED:_~~~~~~ _____________ __ anager & Chief Engineer

I .,.....

0-

1 = ...r I.C>

= C>

=

AIR VENT,. SEE @ --------, 1/4" THICK NEOPRENE GASKET------.

GALVANIZED STEEL BASE PLATE BY----, PUMP MANUFACTURER. SUBMIT SHOP DRAWINGS.

,..----- PROVIDE TWO MONITORING TUBES. TERMINATE ONE MONITOR TUBE FOR WATER COMMISSION WITH A CAP AND ALLOW FOR EASY ACCESS. USE ONE MONITOR TUBE FOR WELL LEVEL TRANSDUCER, SEE~ AND ~

~ ~ -- TO PUMP DISCHARGE PIPING GALVANIZED STEEL SOLE PLATE BY

PUMP MANUFACTURER. OPENING IN PLATE SHALL fiT OVER WELL CASING. LEVEL SOLE PLATE AND GROUT UNDER PLATE. SUBMIT SHOP DRAWINGS.

NEW STEEL PIPE, MIN. 0.365" THK. t LENGTH TO SUIT FIELD CONDITIONS. DIAMETER TO SUIT PUMP AND TO CLEAR MONITORING TUBES. SUBMIT SHOP DRAWINGS.

STRAP DRAIN I

2" THICK NON-SHRINK GROUT-~

CON RETE UM P 0 . .

TOP ElEV.=34-6.5 (Pukaki) SEE STRUCTURAL 'SHEET

CUT AND REMOVE MIN. TOP 8tl

PORTION OF CASING AND WELD NEW STEEL REDUCER SECTION ASSEMBLY TO EXISTING CASING.

1/2" RADIUS TOOLED EDGE---"'I. \ (lYPICAl FOR ALL EXPOSED EDGES) \---l---J' --_ .. , ..... --1.,. ,­

r1/2" THICKx 1" DEEP I ELASTOMERIC JOtNT SEALER

F1NISH PAVT.

j , l

i i :'< 1/2" THICK PREMOlDED -+ I~-EXPANSION JOINT FILLER

DEMOLISH AND /. 1. ~ TO W/lN 1" OF TOP OF SLAB

~

EXISTING 5' SQ.x4" THK. ~~~ i ,. )} ~':< REINFORCED CONC. BASE <'_~_~,~_~'_ .. _~ __ .... ____ . __ . __ , r-liHIB'. 8R81!H46 :eB~ ~M: 661&)

r=rr -------------t--.. ··~?--'·'-((··· '""'-1"-" .. ··ir ... --"'<-----r-- l - t _ _ :;; 4!S± (p:i~:t<;). , I / If I /I , I

. l._ .... II • II ,-_J \I I II

" , ~~ i II EXISTING GROUT SEAL TO BE PROTECTED

()

(J

Mar· l.. LUU4 4:11PM

Z -\ (.) ~ ~

~ m

() z U\ G (\ ~ 0 ~

:r.

THIS WORK WAS PREPARED BY ME OR UNDER MY SUPERVISION

Si9noture ESAKI SURVEYING &: MAPPING. INC.

No.0540 p. I

Ne~.~ell

5' X 5' c.onc.rete Slab

~ 4.

~ 4.

4.

1\ .. e. ~

C> @" 4.

~

Ie> ~

4. ();, ().

4- /:).

~ 4.

Benc.h Mark Elevation = 946.54 Southeast C.orner c,onc.rete Pad

c:. ~

~ c:.

c:.

NE~ PUKAKI ~ELL September" 2, 2003

02-7B.dw(,3 ESAKI 5URYEYIN5 4 MAPPING, INC. B.5" X II" 1.0 Sq, Ft. Civil Engineers - Land Surveyors - Planners

"Fujimoto, Keith" <[email protected]>

02/09/2004 01 :39 PM

"'[email protected]'" To

<[email protected]> cc

bcc

Subject Hanamaulu - Pukaki expiring permits

Thanks, Lenore. I haven't found anything and believe you're correct. I'll request it from the contractor ASAP ...

keith

-----Original Message-----From: [email protected] [mailto:[email protected]] Sent: Monday, February 09, 2004 1:41 PM To: Fujimoto, Keith Subject: Re: Hanamaulu - Pukaki expiring permits

Hi Keith,

I rechecked our files. Last thing we have on record is our 5/15/03 letter extending the pump permit for another 6 months (to 1/20/04). If you did already send, can you please resend the Well Completion Report Part 2, because it must have gotten lost somewhere in our office. thanks, lenore

"Fujimoto, Keith" <KFujimoto@kauaiw ater.org>

02/09/2004 01:20 PM

"'[email protected]'" <[email protected]>

To

cc

Subject Hanamaulu - Pukaki expiring permits

Thanks for the reminders, Lenore. I thought I sent Pukaki Well, however let me check the files ...

-----Original Message-----From: [email protected] [mailto:[email protected]] Sent: Friday, February 06, 2004 10:19 AM To: [email protected] [email protected]

Subject: expiring permits

Hi Keith & Michael,

Just following up on some Pump Installation Permits that have expired:

Pukaki Well (0023-02) - expired on 1/20/04 Puhi 5A (5824-08) - expired on 12/31/03 Puhi 58 (5824-09) - expired on 12/31/03

Was the installation work completed?

Aloha, Lenore

LINDA LINGLE GOVERNOR OF HAWAII

STATE OF HAWAII DEPARTMENT OF LAND AND NATURAL RESOURCES

COMMISSION ON WATER RESOURCE MANAGEMENT P.O. BOX 621

Mr. Edward T. Tschupp Manager & Chief Engineer County of Kauai Department of Water P.O. Box 1706 Lihue, HI 96766

Dear Mr. Tschupp:

HONOLULU, HAWAII 96809

May 15,2003

Request for Extension Pump Installation Permit for Well No. 0023-02

PETER T. YOUNG CHAIRPERSON

MEREDITH J. CHING CLAYTON W. DELA CRUZ CHIYOME L. FUKINO, M.D.

BRIAN C. NISHIDA HERBERT M. RICHARDS, JR

ERNEST YW. LAU OEPUTY DIRECTOR

Ref:0023-02.let2

We have received your May 7, 2003 letter, requesting an extension ofthe above­referenced permit for an additional six months. Your letter indicates that the pump is ready to be installed, but is awaiting the arrival of a critical part, which is expected soon.

Your request to extend the permit expiration date is hereby approved. The new expiration date is January 20, 2004/Thank you for your attention to the terms and conditions of your permit.

Sincerely,

~M~ ERNEST Y.Wq-;~· Deputy Director

LN:ss

/

, .... : \.f

RECE1\/rr;

03 MAY 12 A9: ~Z

May 7, 2003

Ms. Lenore Nakama Commission on Water Resource Management P.O. Box 621 Honolulu, HI 96809

Dear Ms. Nakama: I'

o Water has no substitute ••.••.. Conserve it

Subject: Pump Installation Permit 'for Pukaki Well (Well #0023-02), Hanamaulu, Kauai

We would like to request an extension to submit the final pump installation report for this project. The pump is ready to be installed; however, a critical part is missing and should be arriving shortly. We, therefqre, request a six months' extension to the pump installation permit or until December 2003. Your favorable reply will be greatly appreciated. '

Ifthere are any questions, please call Keith Fujimoto at 245-5449.

, Sincerely,

Edward W. Tschupp Manager & Chief Engineer

Kf:emi

c: Fukunaga & Associates R Electric, Inc.

4398 Pua Loke St., P,O. Box 1706, Lihue, HI 96766 Phone: 808-245-5400

Engineeri~g and Fiscal Fax: 808-245-5813, Operations Fax: 808-245-5402, Administration Fax: 808-246-8628

c o

,.,....,. ~MP INSTALLATION PERMIT

Pukaki Well, Well No. 0023-02

In accordance with Department of Land and Natural Resources, Commission on Water Resource Management's Administrative Rules, Section 13-168, entitled 'Water Use, Wells, and Stream Diversion Works", this document permits the pump installation for Pukaki Well (Well No. 0023-02) at Lihue Basin, Kauai,TMK 3-8-2:2, subjeJi\\..to the Hawaii Well Construction & Pump Installation Standards (1/23/97) which include but are not limited to the following ~£.I'dititJlnr.,

/"-ilfT 3 P 2 . 1. The Chairperson to the Commission on Water Resource Management (Commission), P.O. Box 621, Honolulu, HI 96809, shall be' I 0

notified, in writing, at least two (2) weeks before any wor~ covered by this permit commences and staff shalVqealiowed to inspect installation activities in accordance With § 13-168-15, HawaII Administrative Ru les. ;:, ' _

2.

3,

4,

5.

6.

7.

8.

9.

10.

11.

The pump installation permit shall be for installation of a 700 gpm capacity, or less, pump in the well. \"'L<'-,; I ;' , ,', ",' , -, ii/.{L/lj

The permittee shall provide and maintain an approved meter or other appropriate means for measuring and reporting withdrawals a~ water levels, and appropriate devices or means for measuring chlOrides and temperature. These data shall be measured monthly and reported to the Commission on a monthly basis, on forms prOVided by the Chairperson (attached).

The proposed use shall not adversely, affect existing or future, legal uses of water in the area. including any surface water or established instream flow standards. ThiS permit or the authOrization to pump water from a well shall not constitute a determination of correlative water rights. The permittee is notified and by this proviSion understands that the quantity of water taken from the well could be reduced by the Commission in the future. This permit is not a commitment that the pump capacity permitted here or even some lesser amount is guaianteed in the future.

The permittee shall complete and submit as-buUt drawings a"d Part II - (Permanent) Pump :nstaliation Report of the vVdl Completion Report (attached) to the Chairperson Within Sixty (60) days after complellon of work,

The permittee shall comply with all applicable laws, rules, and ordinances, and non-compliance may be grounds for revocation of this

permit.

The pump installation permit application is incorporated into this permit by reference and is subject to the Hawaii Well Construction & Pump Installation Standards (1/23/97). If the HWCPIS are not followed and as a consequence water is wasted or contaminated, a lien on the property may result.

The permit may be revoked if work is not started within six (6) months after the date of approval or if work is suspended or abandoned for six (6) months, unless otherwise specified. The work proposed in the pump installation permit application shall be completed within two (2) years from the date of permit approval, unless otherwise specified. The permit may be extended by the Chairperson upon a showing of good cause and good-faith performance. A request to extend the permit shall be submitted to the Chairperson no later than three (3) months prior to the date the permit expires. If the commencement date is not met, the Commission may revoke the permit after giving the permittee notice of the proposed action and an opportunity to be heard,

If the well is not to be used it must be properly capped, If the well is to be abandoned then the permittee must apply for a well abandonment permit in accordance with §13-168-12(f) prior to any well sealing or plugging work,

The permittee, its successors, and assigns shall indemnify, defend, and hold the State of Hawaii harmless from and against any loss, liability, claim, or demand for property damage, personal InJUry, or death anslng out of any act or omission of the applicant, assigns, officers, employees, contractors, and agents under thiS permit or relating to or connected with the granting of this permit.

Special conditions in the attached cover transmittal letter are incorporated herein by reference.

Date of Approval: March 31, 1999 Expiration Date: March 31, 2001 h (;;,.11;, rif/Cil

f TIMOTHY E. J NS, Chairperson Commission on Water Resource Management

I have read the conditions and terms of this permit and understand them. I accept and agree ;.0 meet these cond:tions as a prerequisite and underlying condition of my ability t<:> proceed and ~n~erstand that I do not hold a valid permit until I and the pump installer have signed, dated, and returned the permit to the Commission. I also understand that non-compliance with any permit

:o::::~:y~::~:::: 10~1000 po< d.y ".~ng I'om ~o po=;' d.'o 01 'PP':~:e. ~ Printed Name:

Installers Signature:

Printed Name:

E:D~ "f~ Firm or Title: pswry ~ t J2ef[PE ~

AV/lt;.., C-57, C-57a, or A License #: AG vee;, Date: Zl /tf4R.Cf./

Firm or Title: IflMJAGrtl. - 6l'Vl;1 k 7/ii/uING: I Ale . . tNN411 7J/l/()'O;/j

Please sign both copies of this permit, return one to the ChaIrperson, and retam the other for your records. -

Attachments c: USGS

Department of Health! Safe Drinking Water & Wastewater Branch Lihue Plantation Co.

BENJAMIN J. CAYETANO GOVERNOR OF HAWAH

STATE OF HAWAII DEPARTMENT OF LAND AND NATURAL RESOURCES

COMMISSION ON WATER RESOURCE MANAGEMENT P.O. BOX 621

HONOLULU, HAWAII 96809

Mr. Ernest Y.W. Lau Manager and Chief Engineer County of Kauai

DEC 13 2001

Department of Water P.O. Box 1706 Lihue, HI 96766-5706

Dear Mr. Lau:

Request for Extension Pump Installation Permit for Well No. 0023-02

GILBERT S. COLOMA-AGARAN CHAIRPERSON

BRUCE S. ANDERSON ROBERT G. GIRALD BRIAN C. NISHIDA DAVID A. NOBRIGA

HERBERT M. RICHARDS, JR.

LlNNEL T. NISHIOKA DEPVTY DIRECTOR

We have received your November 14, 2001 letter, requesting a second extension ofthe . above-referenced permit. Our records show that this permit was conditionally extended to July / 20, 2003, provided that a fully validated permit is returned to our office by December 20,2001. You are now anticipating returning a fully validated permit to us by April, 2002.

Your request to extend the deadline to submit a fully validated permit is hereby approved. Please submit a fully validated permit to our office no later than April 30, 2002. The current expiration date, July 20, 2003, remains unchanged. Ifwe do not receive a fully validated permit by April 30, 2002, the permit will be cancelled as of April 30, 2002. No further extensions of this permit will be granted.

If you have any questions, please contact Lenore Nakama at 587-0218 or toll-free at 274-3141, extension 70218.

LN:ss

LINNEL T. NISHIOKA Deputy Director

I , 1

1

November 14,2001

Ms. Lenore ,Nakama Commission on Water, Resource Management P.O. Box 621 Honolulu, HI 96809

Dear Ms. Nakama:

o Water has no substitute •.•.•.• Conserve it

Subject: Job No. 96-1 - Pump Installation Permit for Pukaki Well (Well No. 0023-02), Hanamaulu, Kauai

We would like to r~quest an extension to file the Pump Installation Permit as requested by your communication dated July 10,2001 (Ref:0023-02.let) for this project."

We are currently soliciting bidders fo~ the pump installation, with bid opening scheduled for November 29,2001. Allowing for some time to execut.e the contract, and forthe contractor to mobilize, we expect to have the fully executed permit to your office by April 2002. Your favorable reply will be greatly appreciated.

Ifthere are any questions, please call Keith Fujimoto at 245-5449. '\

(ll;:n:~t Y. W. La~ tar, Manager and Chief Engineer

KF:emi

./

c: Water Resource Associates Fukunaga & Associates

4398 Pua Lake St., P.O. Box ,1706, Lihue, HI 96766 PhO/1e: 808-245-5400

Engineering and Fiscal Fax: 808-245-58 I 3, Operations Fax: 808-245-5402, Administration Fax: 808-246-8628

c

BENJAMIN J. CAYETANO GOVERNOR OF HAWAII

Ref:0023-02.let

-

STATE OF HAWAII DEPARTMENT OF LAND AND NATURAL RESOURCES

COMMISSION ON WATER RESOURCE MANAGEMENT P.O. BOX 621

HONOLULU. HAWAII 96809

Mr. Ernest Y.W. Lau Manager and Chief Engineer County of Kauai Department of Water P.O. Box 1706 Lihue, HI 96766-5706

Dear Mr. Lau:

Request for Extension Pump Installation Permit for Well No. 0023-02

GILBERT S. COLOMA·AGARAN CHAIRPERSON

BRUCE S. ANDERSON ROBERT G. GIRALD BRIAN C. NISHIDA DAVID A. NOBRIGA

HERBERT M. RICHARDS. JR.

LlNNEL T. NISHIOKA DEPUTY DIRECTOR

Co. w~

Phone # 1 - 0 2..{ ~

Fax #

We have received your June 20, 2001 letter, requesting an extension of the above­referenced permit. Our records show that this permit expired on March 31,2001.

Condition 8 of your permit states that a request to extend the permit must be made no later than three (3) months prior to the permit expiration date. Your request is therefore untimely. However, we find that the following extenuating circumstances apply: 1) government agencies are currently not assessed filing fees for permit processing; 2) we do not feel that any new information will be gained by the submittal of a new application requiring another Department of Health review, as the permit expired less than 3 months ago; and 3) your letter establishes August, 2001 as a tentative timeframe for the start of work. Based on the foregoing, we are agreeing to extend the permit at this late date. (For your information, we are in the process of revising the statutes to allow us to charge government agencies a permit filing fee. Should this statutory change be approved, the Commission will revert to strict enforcement of the terms outlined in Condition 8.)

By this letter, your permit is conditionally EjXtended. We will extend the permit to two (2) years from the date of your letter, June 20, 2003, provided that a fully validated permit is returned to us within the next six (6) months. If we do not receive a fully validated permit by December 20, 2001, the permit will be cancelled as of December 20, 2001. Any permanent pump installation work that proceeds without a valid permit may be subject to fines of up to $1000 per day.

If you have any questions, please contact Lenore Nakama at 587-0218 or toll-free at 274-3141, extension 70218.

LN:ky

Sincerely, A-" n '-Q /~. A . \ ""i.//

O)xV~!J . u I/~~ LlN~EL T. NISHIOKA Deputy Director

/

DQ»ARTMENT OF WAT~ county of Kauai

"Water has no Substitute - Conserve It!"

June 20, 2001

Ms. Lenore Nakama Commission on Water Resource Management P. O. Box 621 Honolulu, HI 96809

Dear Ms. Nakama:

Subject: Job No. 96-1, Pump Installation Permit for Pukaki Well (Well No. 0023-02), Hanamaulu, Kauai.

We would like to request for an extension to the Pump Installation Permit approved by your office on March 31, 1999. We are finalizing the construction plans and hope to bid the project in early August, 2001. Your favorable reply will be greatly appreciated.

If there are any questions, please contact Keith Fujimoto of my staff at 245-5449.

fj:~ ~/IEmest Y. W. Lau '-('f

Manager and Chief Engineer

cc: Water Resource Associates Fukunaga & Associates

KF:ri

- 4398 Pua Loke Street, Lihue, Kauai, Hawaii or P. O. Box 1706, Lihue, HI 96766-5706-Phone No. (808) 245-5400 - Administration FAX No. (808) 246-8628 - Engineering/FiscallShop FAX No. (808) 245-5813

BENJAMIN J CAYETANO QOW:1tNOA 01 HAW ...

c

STATE OF HAWAII DEPARTMENT OF lAND AND NA ruRAl RESOURCES

COMMISSION ON WATER RESOURCE MANAGEMENT PO BOX621

HONOllA.U. HAWAII 96809

APR - 5 LIDl

Mr. Ernest Y.W. Lau Manager and Chief Engineer County of Kauai Department of Water P.O. Box 1706 Lihue, HI 96766

r. .. t~ IA\L'

Dear M:t;l'tau:

TM)THY E JOHNS --BRUCE SANDERSON

ROeERT G. GIRAlD BRIAN C NISHIDA OAVID A. NOBRIGA

HERBERT M RICHARDS. JR

LlNNEl T NISHIOKA O(I'\fT't'OIMCT(MI:

A review of our records show that we have not yet received signed permits for well construction/pump installations for the following wells:

Pennit Tme Well No. Well Name

Well Construction 1125-03 Kilauea 3 / Pump Installation 0023-02 Pukaki / Pump Installation 5824-09 Puhi 5B / Pump Installation 0622-02 Kapaa Homesteads 2 /

Please return a fully signed copy of the permit to us and keep the second copy for your record. Any work shall not commence until all required signatures are obtained and submitted to the Commission on Water Resource Management.

If you have any questions, please contact Lenore Nakama at 587-0218 or toll-free at 274-3141, extension 70218.

LN:ss

Sincerely,

JT8J.J~ LINNEL T. NISHIOKA Deputy Director

/

BENJAMIN J. CAYETANO GOVERNOR OF HAWAII

STATE OF HAWAII '\" 1)'8 DEPARTMENT ~'9t&Mr~O p ,,-: "

P.O. BOX 3378

HONOLULU, HAWAII 96801 ., .~' ."" itR ,_ , ,', ''''<''<'~''''I'i! \ ""1 'W 1\, I

'COP\i\;\~C;'J ~'\; "l{ I, i3E~EN' July 27, ~§ll:,\ t 1 ,r" /,

Ms. Lynn Katahara Fukunaga and Associates, Inc. 1388 Kapiolani Blvd., 200 Floor Honolulu, Hawaii 96814

Dear Ms. Katahara:

SUBJECT: INTER-AGENCIES REVIEW COMMENTS ON ENGINEERING REPORT FOR PUKAKI WELL AND HANAMAULU WELL NO. 3 STATE WELL NOS. 2,aIID;':J.2,;, AND 2-0124-02

BRUCE S. ANDERSON, Ph.D., M.P.H. DIRECTOR OF HEAlTH

In reply. please refer to: EMD/SDWB

The subject engineering report was forwarded to various agencies for review. The 30-day comment period ended on July 5, 1999. Enclosed is a copy of the comments received from the Commission on Water Resource Management (CWRM).

Please reply directly to CWRM in a timely manner. Copy of your comments must also be provided to the Safe Drinking Water Branch. If the Kauai Department of Water Supply has decided to deepen the Hanamaulu Well No.3, the subject engineering report will need to be revised accordingly and additional water analyses may be required to ensure that watef~ality has not be compromised. If you should have any questions, please contact Ms. Queenie Komori of the Safe Drinking Water Branch, Engineering Section, at 586-4258.

Sincerely,

a (;;aw IeJIha WILLIAM WONG, ~E., Chief Safe Drinking Water Branch Environmental Management Division

QK:gm

c: Mr. Ernest Lau (with enclosure) Kauai Department of Water Supply

Commission on Water Resource Management (without enclosure)

BENJAMIN J CAYETANO GOVERNOR OF HAWAJI

REF:CWRM-SS

Mr, Ernest Lau Manager and Chief Engineer Kauai Department of Water P,O, Box 1706 Lihue, Hawaii 96766-5706

Dear Mr, Lau:

-,

STATE OF HAWAII DEPARTMENT OF LAND AND NATURAL RESOURCES

COMMISSION ON WATER RESOURCE MANAGEMENT P.O, BOX 621

HONOLULU, HAWAII 96809

APR - 6 1999

Pump Installation Permit Pukaki Well (Well No, 0023-02)

TIMOTHY E JOHNS

BRUCE SANDERSON RICHARD H COX

ROBERT G GIRALD DAVID A N08RIGA

HERBERT M RICHARDS, JR

EOWIN T SAKODA Acting Deputy DIrector

Enclosed are two (2) originals of your approved Pump Installation Permit for the captioned welles) that authorize permanent pump installation work for your welles), As part of the Chairperson's approval, the following special conditions were added and are part of your permit under Permit Condition 11:

Special Conditions

1. Kauai Department of Water may submit monthly reports of water use, water levels, chlorides, and temperature on their own forms, provided that the information is submitted in a format that is acceptable to the Commission staff,

The permittee is responsible for all conditions of the permit. This includes f'~suring that the pump installation contractor, or other party who installs the pump, submits a completed Part II of the Well Completion Report form (enclosed) within sixty (60) days after the pump installation work is completed. Be advised that you may be subject to fines of up to $1000 per day for any violations of your permit conditions starting from the permit approval date.

To validate your pump installation permit, please sign and have the contractor sign both permit originals and return one for our files. A copy of the Well Completion Report (Part II) and a copy of your water use report form are enclosed for your use,

IMPORTANT - Unless specifically exempted, pump installation may not proceed without a validated permit returned to the Commission. Except for the monthly water use report form, please provide copies of all the information in this packet to your pump installation contractor.

70218.

Finally, this letter is notice that we have accepted your Well Completion Report - Part I as complete,

If you have any questions, please call the Commission staff at 587-0218 or toll-free at 274-3141, extension

Aloha,

(/uJ/~~ 1jCvi~.L TIMOTHY E, JOHNS Chairperson

Enclosure

/

c .~

PUMP INSTALLATION PERMIl"..., PukakiWell, Well No. 0023-02

In accordance with Department of Land and Natural Resources, Commission on Water Resource Management's Administrative Rules, Section 13-168, entitled 'Water Use, Wells, and Stream Diversion Works·, this document permits the pump installation for Pukaki Well (Well No. 0023-02) at Lihue Basin, Kauai,TMK 3-8-2:2. subject to the Hawaii Well Construction & Pump Installation Standards (1123/97) which include but are not limited to the following conditions:

1. The Chairperson to the Commission on Water Resource Management (Commission), P.O. Box 621, Honolulu, HI 96809, shall be notified, in writing, at least two (2) weeks before any work covered by this permit commences and staff shall be allowed to inspect installation activities in accordance with §13-168-15, Hawaii Administrative Rules.

2. The pump installation permit shall be for installation of a Jflfi gprii ~pacity, or less, pump in the well.

3. The permittee shall provide and maintain an approved meter or other appropriate means for measuring and reporting withdrawals and water levels, and appropriate devices or means for measuring chlorides and temperature. These data shall be measured monthly and reported to the Commission on a monthly basis, on forms provided by the Chairperson (attached).

4. The proposed use shall not adversely affect existing or future legal uses of water in the area, including any surface water or established instream flow standards. This permit or the authorization to pump water from a well shall not constitute a determination of correlative water rights. The permittee is notified and by this provision understands that the quantity of water taken from the well could be reduced by the Commission in the Mure. This permit is not a commitment that the pump capacity permitted here or even some lesser amount is guaranteed in the future.

5. The permittee shall complete and submit as-built drawings and Part II - (Permanent) Pump Installation Report of the Well Completion Report (attached) to the Chairperson within sixty (60) days after completion of work.

6. The permittee shall comply with all applicable laws, rules, and ordinances, and non-compliance may be grounds for revocation of this permit.

7. The pump installation permit application is incorporated into this permit by reference and is subject to the Hawaii Well Construction & Pump Installation Standards (1123/97). If the HWCPIS are not followed and as a consequence water is wasted or contaminated, a lien on the property may result.

8. The permit may be revoked if work is not started within six (6) months after the date of approval or if work is suspended or abandoned for six (6) months, unless otherwise specified. The work proposed in the pump installation permit application shall be completed within two (2) years from the date of permit approval, unless otherwise specified. The permit may be extended by the Chairperson upon a showing of good cause and good-faith performance. A request to extend the permit shall be submitted to the Chairperson no later tlian three (3) months prior to the date the permit expires. If the commencement date is not met, the Commission may revoke the permit after giving the permittee notice of the proposed action and an opportunity to be heard.

9. If the well is not to be used it must be properly capped. If the well is to be abandoned then the permittee must apply for a well abandonment permit in accordance with §13-168-12(f) prior to any well sealing or plugging work.

10. The permittee, its successors, and assigns shall indemnify. defend, and hold the State of Hawaii harmless from and against any loss, liability, claim, or demand for property damage. personal injury, or death arising out of any act or omission of the applicant, assigns, officers, employees, contractors, and agents under this permit or relating to or connected with the granting of this permit.

11. Special conditions in the attached cover transmittal letter are incorporated herein by reference.

Date of Approval: March 31, 1999 Expiration Date: March 31, 2001

(.,...: TIMOTHY E. kt>HNS, Chairperson r Commission on Water Resource Management

I have read the conditions and terms of this permit and understand them. I accept and agree to meet these conditions as a prerequisite and underlying condition of my ability to proceed and understand that I do not hold a valid permit until I and the pump installer have signed, dated, and returned the permit to the Commission. I also understand that non-compliance with any permit condition may be grounds for revocation and fines of up to $1000 per day starting from the permit date of approval.

Permittee's Signature: Oate: ____ _

Printed Name: Firm or Title: ________________ _

Installer's Signature: C-57, C-57a, or A License #: Oate: ___ _

Printed Name: Firm or Title: _______________ _

Please sign both copies of this permit, return one to the Chairperson, and retain the other for your records.

Attachments c: USGS

Department of Health! Safe Drinking Water & Wastewater Branch Uhue Plantation Co.

/

I WCR 1 Check for Well No. 0023-02 (survey to regulation memo)

1. Pump Tests Check Glenn Bauer .L (initial) , Yes No If no. describe deficiency

Step-Drawdown Test: acceptable followed wePI Stds analysis attached proposed pump cap o.k.

Aquifer Pump Test: acceptable followed wePI Stds T & S analysis attached

Well Interference: estimated Steady-State drawdown at 1-mile radius is _____ ft.

analysis attached

Stream Surface Water Impacted:

o

o

o o o o

o o o

o ~ If yes, identify most probable stream

2. Construction Check Mitch Ohye \ ... / (initial)

data complete followed wePI Stds wellphys.dbf updated welaplic.dbf updated

Yes No

o o o o

\/

If no. describe deficiency

\1

03/22/99

CWRM DLNR c 1151 Punchbowl Street

Honolulu, Hawaii 96813

Pumping Test No. Long-Term Test

Well No. 0023-02

Discharge 130.00 U.S.gal/min

Pumping test analysis Distance-Time-Drawdown-method· after COOPER & JACOB Confined aquifer Evaluated by: Glenn Bauer

Test conducted on: July 20-30, 1998

tlr2 [d/ft2] 1 0-6 1 0-5 1 0-4

0.00 ~-------~II---~~I-o--o~:--~:~:~:~:-~II~------~:~---~II---~II--~II ~:~:~:-:~

1.00

2.00

3.00

4.00

5.00

6.00

7.00

8.00

9.00

10.00

I I

I I

I

I

o Pukaki Res. Well Obs

II '\.~ I I I I I ~ I I I I I

I I

I I

1'1 I I I I

I "I\. I I I I I I '\.~ 10 I I

I I I '\!.. I I

I I I 1,\ ~ I I I I:~

I I I I I)'\. I I I I I I ~ I

I I I I I I '\. I

I I I I I I '\. I

I I

I

~: : I I I I I I

I I

I I

I I I

I I I

I I I I I

I I I I I

~:

Transmissivity [ft2/d]: 4.99 x 102

I I I I I I I I I I I I

I I I I I I

I I I I I I I I I I I I I I I I I I

I I I I I I

I I I I I I

I I I I I I I I I I I I

I I I I I I

I I I I I I

I I I I I I I I I I I I

I I I I I I

I I I I I I

I I I I I I

I I I I I I

• CWRM "...., Pumping test analysis j~ Date: 29.03.199~ Page 2

DLNR ~ Distance- ".;a"vu .... Project: Pukaki Well, Kauai

1151 Punchbowl Street atter COOPER & JACOB Honolulu, Hawaii 96813 Confined aquifer Evaluated by: Glenn Bauer

Pumping Test No. Long-Term Test Test conducted on: July 20-30, 1998

Well No. 0023-02 Pukaki Res. Well Obs. 0023-01

Discharge 130.00 U.S.gal/min Distance from the pumping well 321.00 tt

Static water level: 156.90 tt below datum

Pumping test duration Water level Drawdown

[d] [ttl [ttl 1 20833 156.40 -0.50 2 7~nnr 156.81 -0.09 3 U.2910f 157.17 U.2f 4 0.33333 157.46 0.56 5 0.37500 157.80 0.90 0 0.41667 158.35 1.45 7 4 "H";{";{ 159.03 2.13 8 0.50000 159.85 2.95 9 0.54167 159.90 3.00

10 0.58333 1t19.98 3.U8 11 0.66667 159.91 3.01 12 0.75000 160.05 3.15 13 0.87500 161.90 5.00 14 1.00000 102.25 5.35 15 1.16667 162.81 5.91 16 1.33333 163.20 6.30 17 1.58333 164.45 7.55 18 2.08333 10tl.UU 8.1U 19 2.58333 165.65 8.75

~~ T r- /~A,4' tJ~ OD2-3·o-z., I C~·

~S f~-~ .eI-&;; /-i II/Iffl

~ 7/ ~ ~ AL,( Z,~/1'1'

IVO 77. t/v

/J7>

A-T :;' ~ () ..f " Q 1..-

fo f'~ f.- a. ~ b

/ 0'0 (J..} -t / 0) ~ { .lJ - t 1, r D ~ l:>

/JO {4J -+ l..l"rth (. J) - /D,s. 03 s D

til j • 'IVY' .6 :s • QO, 70V

IS

sea e :: / /tnrf:j

-/ :;

Ote of Hawaii ~ COMMISSION ON WATER RESOU~CE MANAGEMENT' Department of Land and Natural Resources

~ .. , /

(Check Appropriate Box)

WELL COMPLETION REPO~:r;,,' ,: I ~ h 9 :4~5~7 WCR Form

o Well Construction 0 (Permanent) Pump Installation Instructions: Please print or type and submit completed report within 30 days after well completion to the Commission on Water Resource Management, P.O. Box 621, Honolulu, Hawaii 96809. An as-built drawing of the well and chemical 8nalysis should also be submitted Fe! Jssistance call the Commission ReQulation Branch at 587-0225, or 1-800-468··~64,+ Ex7ension .70225. " . --------- ---, 1. State Well No.: 0023=02 Well Name: .... P-'u'-!,;k,..a"uk .... i _____ _ Island;-,K..>..:a"-,u",,,a~i ____ _ 2. Location/Address: --!L::,!i.!.,!h",.u""e ..... B""a""s""i"'-'n:.....-______________ _ Tax Map Key:-=3,-,-8~-=2::..::2 __ _

II PART I,' ..... . .' ..... i<'WELLCONSTRUCTIONREPC>RT<'

3. Drilling Company: -T.ktN4J.2tN O,£}UliY( ~)8[C' 6',pI5~ //"< 4. Name of driller who performed work: (':; l-er /M/0"u r f?.

5. Type of rig/construction: 'J?c,;r-,<1p··z /1,*" 5;'6'«1 ?)c: . ...., ...... -., f:i..::>z-c /.!;·,(/A!~:' 6. Date(s) Well Construction and pu~p tests (if any) completed: 7/ ..... .:.;,~/?8' 7. GROUND ELEVATION (referenced to mean sea level, msl): ft.' II "'.'

Well Bench Mark (description/location): Elevation(msl): __ _

8. DRILLER'S LOG: Please attach geologic log (if available or if required by permit)

Depths (ft.) Rock Description, Water Level, Dates, etc. Depths (ft,) Rock Description, Water Level, Dates, etc.

8R<'CW-"'" P~t9LrlCf?C/.J /Y1r.Ff( I~"""",,,;...to~ .?fED OIR! ~to C;;q' ~ to 28" /£':::0 ,\.-, /;:lcpzv.-' 0Jirt ~ to ~ /CeQ /'-1" !_/"""o"-____ _

(If more space is needed, continue on back.)

9. Total depth of well below ground: 810 ' ft. 10. Hole size: 2.6 inch dia. from S'-'I;£Bu; ft, to ._4-,-",::"","; ___ ft below ground

i! 2. inch dia. from 4.3 ft. to 8; 0 ft, below ground ______ inch dia. from _. ______ ft. to ______ ft. below ground

11, Casing installed:_~i...:.2.:::.. __ in. 1.0. x 3/8 in. wall solid section to ,49 ~ ft, below ground ____ in. 1.0, x ____ in. wall perforated section to ____ ft. below gr'ollnd

Casing Material/Slot Size: ____________ _

12. Annulus: Grouted from 5 .. ') R F t! " Z ft. below ground to _~l'-'.L(.L' _.<J<--_ ft. below ground Gravel packed from ______ ft. below ground to ft, below ground

13. Initial water level: 9;.,83 ft. below ground. 14. I nitial chloride: .I -;eP',· ppm 15. Initial temperature: OF 16. PUMPING TESTS: Reference Point (R.P.) used:

(1) Step-Drawdown Test Date 7/lJ/:.:!,q Start water level / 11.5 c ft. below R.P.

Date and time of measurement: 7/1 /~r,:.,~ / Z': , I I

Date and time of sampling: _______ _ Date and time of measurement:

G p,,", )0.1..' j.E:v[ c, which elevation is ft (2) Long-term Aquifer Test Date ~;;,: [,://;~

Start water level ::~/,!(i-'i ft. below R.P End water level .3 Ie, 88 ft. below R.P End water level ,-.; :'./ ' i? ft. below RP

No 17, Aquifer Pump Test Procedures data & graphs (1/9/96 LTAT Form) attached? _ Yes 18. A,s-built drawings attached attached? _ Yes _ No 19. Other remarks/comments: (On back of this form)

Well Drilling Contractor (print) &'Ul/d?<y t}ek,//J'

Signature t;7L/~~;;W

Surveyor (print)

Signature

Applicant (print)

Signature

Ronald Casuga

See attached

C-57 Lie. No. __ ~-J.-:""'>'--'--''--___ _

Date _~~--""~I-~-'--__ _

Lic.No. 4332

Date February 26, 1999

Date

":

3./'20J'9(' IN':; R ,-Cfl11 1"". ~ rr============~-!!'!f::=================================--=o--.y

PART II. (PERMANENT) PUMP INSTALLATION REPORT

20. Pump Installation Company: ________________ _ 21. Name of person performing work: ______________ _ 22. Date Pump Installation Completed: _____________ _

23. PUMP INSTALLATION: Pump. Type, Make, Serial No.: _____________ _ Capacity: ____ gpm Motor type, H.P., Voltage, rpm: __________________________ 1

Depth of Pump Intake Setting ft. below _____ " which elevation is _______ ft

Depth to bottom of airline ft. below , which elevation is ttl Pumping Head is ft. Type of flow meter: which measures in ____ _

24. As-built drawings attached attached? _ Yes No I 25. Other remarks/comments: (See be/ow)

Pump Installation Contractor (print) ___________ C-57 Lic. No. ______________ .

Signature Date _____________ _

Applicant (print)

Signature

8.(cont'd) DRILLER'S LOG (cont'd):

Water Level Dates (ft.) h"O to 54() ~t038S-3Bs- to~ "'fOS to4fL2 ~~toZ!f?-.

to to to to to to to to to to to to to to to

Depth (ft.) Rock Description, Remarks,

w Fe A-"'- ;U9 Ey

Date ________________ _

Water Level Dates (ft.)

to to to to to to to to to to to to to to

Depth (ft.) Rock Description, Remarks,

19.& 25. Remarks: ________________________________ _

QELL CONSTRUCTION PERMIT C) Pukaki Well, Well No. 0023-02

In accordance with Department of Land and Natural Resources, Commission on Water Resource Management's Administrative Rules, Section 13-168, entitled 'Water Use, Wells, and Stream Diversion Works", this document permits the construction and testing of Pukaki Well (Well No. 0023-(2) at Lihue Basin, Kauai, TMK 3-8-2:2, subject to the Hawaii Well Construction & Pumo Installation Standards (1/23/97) which include but are not limited to the following conditions:

1. The Chairperson of the Commission on Water Resource Management (Commission). P.O. Box 621, Honolulu, HI 96809, shall be notified, in writing, at least two (2) weeks before any work authorized by this permit commences.

2. The well construction permit shall be for construction and testing of the well only. A minimum one-inch diameter monitor tube shall be permanently installed, in a manner acceptable to the Chairperson, to accurately record water levels. The permittee shall coordinate with the Chairperson and conduct a pumping test in accordance with the Standards (a pump testing worksheet is attached). The permittee shall submit to the Chairperson the test results as a basis for supporting an application to install a permanent pump ana withdraw water for use. No permanent pump may be installed until a pump installation permit is approved and issued by the Chairperson.

3. In basal ground water, the depth of the well may not exceed one-fourth (1!4) of the theoretical thickness (41 times initial head) of the basal ground water unless otherwise authorized by the Chairperson.

4. The permittee shall incorporate mitigation measures to prevent construction debris from entering the aquatic environment, to schedule work to avoid periods of high rainfall, and to revegetate any cleared areas as soon as possible.

5. In the event that subsurface cultural remains such as artifacts, burials or concentrations of shells or charcoal are encountered during construction, the permittee shall stop work and contact the Department's Historic Preservation Division (587-0045) immediately.

6. The proposed well construction shall not adversely affect existing or future legal uses of water in the area, including any surface water or established instream flow standards. This permit or the authorization to construct the well shall not constitute a determination of correlative water rights.

7. The following shall be submitted to the Chairperson within sixty (60) days after completion of work: a. Well completion report, (attached - Part I, Welf Construction Report). b. Elevation (referenced to mean sea level, msl) survey by a Hawaii-licensed surveyor. c. As-built sectional drawing of the well. d. Plot plan and map showing the exact location of the well. e. Complete pumping test records, including time, pumping rate, drawdown, chloride content, al"'d other data.

8. The permittee shall comply with all applicable laws, rules, and ordinances, and non-compliance may be grounds for revocation of this permit. I

9. The well construction permit application is incorporated into this permit by reference and is subject to the Hawaii Well Construction & Pump Installation Standards (1123!97).

10. The permit may be revoked if work is not started within six (6) months after the date of approval or if work is suspenped or abandoned for six (6) months, unless otherwise specified. The work proposed in the well construction permit application shall be completed within two (2) years from the date of permit approval, unless otherwise specified. The permit may be extended by the Chairperson upon a showing of good cause and good-faith performance. A request to extend the permit shall be submitted to the Chairperson no later than 'three (3) months prior to the date the permit expires. If the commencement date is not met, the Commission may revoke the permit after giving the permittee notice of the proposed action and an opportunity to be heard.

11. If the well is not to be used it must be properly capped. If the well is to be abandoned then the permittee must apply fora well abandonment permit in accordance with §13-168-12(f) prior to any well sealing or plugging work.

12. Special conditions in the attached cover transmittal letter are incorporated herein by reference.

Date of Approval: July 21, 1997 Expiration Date: July 21, 1997 i

~ hl~RAEL D. WILSON, Chairperson Commission on Water Resource Management

I have read the conditions and terms of this permit and understand them. I accept and agree to meet these conditions as a prerequisite and underlying condition of my ability to proceed. I also understand that non-compliance with any permit condition may be grounds for revocation nd fines of up to $1000 per day.

Permittee's Signature7=:::::g:~;S~1..J.~;;~:£ ______ _ Date: ____ _

Printed Name: w. Firm or Title:Manager & Olief Engineer

Drille~s Signature: c~ ~/ license #:C ~3: Date: r Printed Name: e Me AfveLL.c/Z Firm or Title: 6 '6'4'UJ JU/~

, <:"jPct:./ A ~ 1~7~ /~ C. Please sign both copies of this permit, return one to the Chairperson, and retain the other for your records.

Attachment c: USGS .

Department of Health! Safe Drinking Water, Wastewater, and Clean Water Branches Robert Vorfe/d, Lihue Plantation Co.

BENJAMIN J. CAYETANO GOVERNOR OF HAWAII

MICHAEL D. WILSON CHAIRPERSON

Q 7 II II ? 4 p Z: 0 S ROBERT G. GIRALD DAVID A. NOBRIGA

LAWRENCE H. MilKE

STATE OF HAWAII-": uV'" ... RICHARD H. COX

HERBERT M. RICHARDS. JR.

REF:CWRM-SS DEPARTMENT OF LAND AND NATURAL RESOURCES

COMMISSION ON WATER RESOURCE MANAGEMENT. RAE M. LOUI. P.E.

Mr. Ernest Lau Kauai Department of Water P.O. Box 1706 Lihue, Hawaii 96766-5706

Dear Mr. Lau:

P. O. BOX 621 HONOLULU. HAWAII 96809

JUL 23 1997

Well Construction Permit Pukaki (Well No. 0023-02)

Enclosed are two (2) copies of your approved Well Construction Permit for the captioned well(s) which authorizes well construction activities but excludes installation work for your permanent pump. As part of the Chairperson's approval, the following special conditions were added and are part of your permit under Permit Condition 12:

Special Conditions

1. The well shall be cased with new steel casing conforming to one of the manufacturing standards listed in Hawaii Well Construction and Pump Installation Standards (January, 1997) and in the standards of AWWA publication ANSIIAWWA A100-90, as may be amended. The physical properties of the steel shall conform to ASTM A-242, ASTM A53, Type E or S, Grade B, or approved equal. The well casing shall be manufactured in accordance with applicable sections of ASTM A139, as may be amended.

This permit does not authorize work for your permanent pump installation. Approval and issuance of your pump installation permit is contingent upon completed application and information provided to and accepted by Commission staff as required in the Well Construction & Pump Installation Standards (1123/97) and any special conditions performed under this permit. Please note that special conditions may simply highlight application deviations from the Standards.

The well owner is responsible for all conditions of the permit. This includes ensuring that the well construction contractor, or other party who constructs the well(s), submits a completed Part I of the Well Completion Report form (enclosed) within sixty (60) days after the well construction work is completed. Be advised that you may be subject to fIDes of up to $1000 per day for any violations of your permit conditions. -

To validate your permit, please sign and have the contractor sign both permit originals and return one for our files. Also, copies of the aquifer pump test worksheet and the well completion report form are enclosed for your use. Please provide all the information in this packet to your well drilling contractor.

OEPUTY

Also attached for your information is a copy of the Department of Health's review comments.

If you have any questions, please call the Commission staff at 587-0218 or toll-free at 274-3141, extension 70218. Lc""""(..

Enclosures

Aloha,

-J-.rv ICHAEL D. WILSON () , - Chairperson

eG-TERM AQUIFER TEST OAt A _,

Pumped Well No. Observation well no. __ """ __ -:-~ ___ _ Pumped Well Name Distance between Obs.& Pumped Well ft. Target Q gpm Reference pt. for depth to water ft. msl

Static Water Level @ start of test ft. msl Water level measurements by: 0 steel tape 0 pressure transducer 0 airline

START TEST Date: _____ Hour of day: ___ _

Flow Meter Reading Start gals Suggested Actual Depth Drawdown Data in this table is for: 1

elapsed elapsed to • Pumping Temp. o Pumped Well time time water (unadjusted rate _oF o Observation WeU

t e (nearest to nearest Q EC cr 0( Remarks

(min) (min) 0.01 ft) .' 0.01 ft) (gpm) (j,Lmhos) (fTl9/1) - °c

0 0 //&75 0.00 Start test

1 i I 05 2. i4,77 qa.07 .- -"-

1.5 i .S5 21'1-, {l qq~~8 ISh 2

2.5 2,5~- 2 J;)~ '1 cf 9.~ ''1 v,(j-

3 3.SS- 2/0:(-::0' q(14j~

4 4,20 2/6.4'1 91.72 5 4,::;-() Zi 7,01 /00,34 6 0. 0 5 2i8Z9 fO/, 54 7 7,/0 211,17 102,42 8 8,iO P~~()~{).8 IOJ •. i] f c.:- (J '

) ( . 10 10140 ?2i,44 IC9-,G9 15 'S'/+D 22{~,14 107..31 IS.] ~,

.--

20 COIIO 22~ S4 f Og,Sq 25 25.i{) 2281R /12.i3 -30 3 0 .. Z() ?,V. Ii-, //<)-.. 4) , -'-. / '::;\..)

40 31.50 Z.3~.P~ I ZrJ .. J] 50 S·O.ZO 2(/- /, R4- . -,.- r,q /<. c:.., .U 60 s'1,5() 242.48 (25,73 70 69. 50 2<13,SJ / CYr~ 7h 80 Qr, ~

l u:; (.() ~11. " c: /(, 127..,5) 141'// 90 '1,' . (! ~ A(" .-

C:-I .. Ai -j j<--8~.lP 14c).,-i 100 /CJ {; ~/1 r; 63 /eJ1,,_aS ( __ ;t~/. '

--150 /5"0 26 c: 13 /28,,3f3 - r..),

.. ~ 200 'ZOO 24Sill: 128,£'7 250 250 216 .. 2/ 121,.% I

i . Suggested Actual I Depth ~raWdown T T

I ......... Data in this table is for: !

I elapsed elapsed to 4- I Pumping I ~mp. o PumpedWeU I time time water. I (unadjusted rate _oF o Observation Well t t (nearest to nearest Q EC cr or

Remarks (min) (min) 0.01 ft) 0.01 ft) (gpm) Uu"nhos) (mgII) °C

300 300 24R.OO 1_1J.2S 145,/ 400 3g0 2.5 J. 33 134..,,58 i42.Q · 500 480 257;71 140,q/~ 142;S · 600 bOO 27/S4 i 54. '/'1 i4tn 2 700 720 27BQz /62,08 145..4 800 840 2..7~H2 /(;(, i7 14~.4 900 q(JO G 78 ,t{) Ibl ,G.~ 14.1.2

1000 1020 ZZZA2 IbS)~7 ILf4/7 · 1500 1500 Zf1H'£{l /8l.8S 141. q · 2000 1'1 ~D 3 JBAt, 20/ 'j I 14 r' ." ),C 2500 2r.:-:» j(~( ... It,O.og 243 y~ . .:u J4L/;q 3000 3000 .:Y;(, I (}') Z4Q"fS ;35, 1 It' r:?"L: I/'~: i:

-i- •. ~n.(} --

4000 40?J) 34'1.bl 2 7 '"" 0" .- (' i-('A) T E .~ ..., . " ....... -

~( .c. r ":)c); C--, . t I "::1 .... ) f."7

5000 5C20 330,i0 z i 3,35 I JUll · 6000 Goco jl)jQ') 235.3~ I:(C 2 - J 10.J ,.1 ("; :.J

7000 7Cl.C 321, ,), Zi3.02 1 G if. S- · 8000 8C20 323/rJ '"" I ~ (Jj c:. (...,,' I 21. . .,

) c L 9000 9 (juO 3ZGJ.~i 26qA~ 130/.(,

10000 fOC-cO 3Z(;.1<:::' ZI(', ,7 I -, -, f""o: , z. l_J Y ,,) Max possible duration,

321, I) 264,'tZ j 2.'1,4-water level or quality did not

/4400 { 44--()O stabilize for any 24 period

Use same 0 Begin recovery data ending next page drawdown Flow meter reading at figure as end of pumped period: start for gals recovery

,"suggested\' -Actual Depth ~ ~ecoveiY~I~' -.

\

--~-1 ~_"_C~

elapsed elapsed to # Pumping time time water (unadjusted rate

t t (nearest to nearest a EC cr (min) (min) 0.01 It) 0.01 It) (gpm) ~hos) (mgII)

0 0 32 /. \l 0

1 280 /'3.25 0 " 1.5 2b6 /49.zs 0

2 2.~4 147,25 0

2.5 26Z 145.25 0

3 259 142.25 0

4 2.s'A- 1.37.25 0

5 2SD 133.25 0

6 245 128.25 0

7 240 /Z.3.Z$ 0

8 236 11'1,25 0

10 Z:Z7 Ilo.2S 0

15 208 91.25 0

20 , 1-' I ~) 7b"ZS 0

25 J 8 I ~q...2S 0

·30 IrS 58.2.5 0

40 t' 5 48,zS 0

50 /SA 41.25 0

60 154 371cS 0

70 V51 34#c5 0

80 14_9 3Z,25 0

90 140 31.25 0

100 147. I 30,,35 0

150 144~2.., 27,'15 0

200 142.Z1 ZS.S4 0

250 / .:./0.80 241tJS 0

END TEST Date: 713/ /98 / I

Hour of day: 15=0 0

ADDITIONAL REMARKS:

.-

Yemp. Data in this table is for:

o ~umpedWell _"F o Observation Well

or Remarks _oC

Start recovery · · ·

· · · · · · ·

· · ·

·

· ·

·

o 80% recovery achieved o 80% reC(lvery not achieved

Person in charge of pump test (print): C kE /Y!i.JE/:'I.t-;:e

Signature: ;:c ~2 The signature above indicates that the data reported ~iS accurate and tFue to the best of the person's knowledge who operated this aquifer test

CWRM L T AT Form 1/9196

o

- -~ ~ -.' OD 0 0 .' ;).) ""0 " () "0 " .. r..i~ °0

0 0

0

00

~

°0 0

<>0

0 0 cl ()

.0 0 0

~ "S I ~ I

'5'

8 If)'

0t; 0 00

o <;,

0° Ob

0

0""

0" °0 ()' 0

()<l 0

POO 0

~ ~

o •• b ••

O. • ~.;;

~2 Co:

C'R~'H

tt,our

7£rd'

So ?? 1/ fV ~~

PUklfKI

Bench Mark Elevation = 345.88 Northeast Corner Box Cut

<1

4 ,4 t:1

'<1

.d

<1

4 6

<1

4 ' '.d Ll

'6 <1

,<1

NeN Hell 5' x 5' Concrete Slab

.d 6

<1

' '.d: <1

THIS HORK}'IIAS PREPARE!? BY HE OR VNOER HY DIRE(; T SUPERVISION NEH PUKAKI HELL

Professional Land Certificate No. 433

February 26, /qqq

KODANI AND ASSOCIA TES, INC. 8.5 H X 11"=1.0 Sq. Ft.

/

PUKAKI WELL - STEP TEST Date Conducted: July 11, 1998

Depth to Drawdown Depth to Drawdown Time Flow Water (feet) Time Flow Water (feet)

(gpm) (feet) (gpm) (feet)

7: 30 111. 50 10:16:20 100 172.86 61.36 7:50 111.08 -.42 10:17:40 7:57:50 100 137.79 26.29 10:25 7:59:20 100 137.79 26.29 10:23:10 120 172.63 61.13 8:00 100 137.42 25.92 10:24 120 8:00:30 100 125.83 14.33 10:27:35 120 176.78 65.28 8:01:20 100 120.38 8.88 10:28:20 120 177.94 66.44 8:02:40 100 10:29 120 178.64 67.14 8:04 100 145.71 34.21 10:31:20 120 180.44 68.94 8:06:04 100 155.08 43.58 10:32:20 120 181.06 69.56 8:07:10 100 156.48 44.98 10:34:30 120 181.75 70.25 8:08 100 158.04 46.54 10:39 120 8:09:30 100 160.88 49.38 10:40:30 120 183.35 71.85 8:10:30 100 162.98 51.48 10:42:40 120 184.28 72.78 8:12:25 100 165.13 53.63 10:46:35 120 184.78 73.28 8:13:40 100 166.21 54.71 10:54:40 120 188.78 77.28 8:15:20 100 168.17 56.67 10:58:30 120 189.58 78.08 8:18:55 100 167.83 56.33 10:59 120 189.64 78.14 8:20 100 167.27 55.77 10:59:20 120 189.75 78.25 8:21:30 100 167.35 55.85 11:01:20 120 190.05 78.5:=, 8:22:25 100 167.33 55.83· 11:10 120 191.92 80.42 8:23:40 100 167.33 55.83 11:12:50 120 190.88 79.38 8:29 100 167.67 56.17 11:15:20 120 191. 17 79.67 8:34:50 100 167.96 56.46 11:27:40 120 189.25 77.75 8:39:50 100 168.96 57.46 11:31 120 8:44 100 169.69 58.19 11:32:10 120 189.63 78. L;; 8:47:30 100 11:35:30 120 189.96 78.46 8:49:20 100 169.79 58.29 11:41 120 189.67 78.17 8:55:30 100 170.83 59.33 11:46:20 120 189.19 77.69 9:03:50 100 173.10 61.60 11:48:50 120 188.92 77.42 9:11:50 100 173.15 61.65 11:50:20 9:16:20 100 172.65 61.15 11:53 9:17:15 100 172.48 60.98 11:55 9:22 100 172.38 60.88 11:56:40 150 200.19 88.69 9:27:45 100 172.29 60.79 12:03 150 204.71 93.21 9:32:20 100 172.38 60.88 12:03:30 150 204.96 93.46 9:37:35 100 172.42 60.92 12:07:25 150 207.40 95.90 9:44 100 172.31 60.81 12:10 150 208.96 97.46 9:51:30 100 172.40 60.90 12:16:20 150 211. 33 99.83 9:54:30 100 172.38 60.88 12:20:10 150 212.25 100.75 10:00 100 172.83 61. 33 12:29:20 150 215.19 103.69 10:03:30 100 173.04 61. 54 12:30:30 150 215.60 104.10 10:06:30 100 173.15 61.65 12:32:20 150 215.71 104.21 10:09 100 173.11 61.61 12:35 150 216.13 104.63 10:13:10 100 173 61.50 12:40 150 216.71 105.2j

.' ",.,.. """ .. ., .. '-' ...""

Depth to Drawdown Depth to Drawdowr: Time Flow Water (feet) Time Flow Water (feet)

(gpm) (feet) (gpm) (feet)

12:42:40 16:05:40 200 354.73 243.23 12:43:20 150 217 105.50 16:10 200 356.33 244.83 12:48:30 150 217.27 105.77 16:15:10 200 357.92 246.42 12:53 150 217.23 105.73 16:19:50 200 358.92 247.42 12:57:30 150 217.22 105.72 16:26:20 200 359.92 248.42 13:03:30 150 217.33 105.83 16:27:20 13:05:45 16:30:50 200 360.69 249.19 13:12:30 150 216.69 105.19 16:35:10 200 361. 35 249.85 13:15:20 150 216.58 105.08 16:40:10 200 361.92 250.42 13:18:20 150 216.53 105.03 16:45:20 200 363.22 251.72 13:19 16:49:20 200 364.15 252.65 13:24:30 200 230.48 118.98 16:53:20 200 368.71 257.21 13:30 200 236.44 124.94 16:54:20 200 369.42 257.92 13:39 200 248.96 137.46 16:55:10 200 369.88 258.38 13:40 16:56:30 200 370.71 259.21 13:49:10 200 259.88 148.38 16:58:20 200 371.85 260.35 13:55:20 200 265.10 153.60 17:00:10 200 372.88 261.38 14:01 200 269.44 157.94 14:01:30 200 270.10 158.60 Shut down at 17:00:20. 14:01:50 200 270.67 159.17 14:02:10 200 271.13 159.63 14:02:40 200 271.67 160.17 Recovery 14:08 200 276.92 165.42 14:08:30 200 277.27 165.77 Depth to Drawdow! 14:14:40 200 282.88 171. 38 Time Water (feet) 14:15:10 200 283.71 172.21 (feet) 14:15:50 200 284.60 173.10 14:17:40 200 284.58 173.08 17:02:16 320.71 209.21 14:20 200 288.65 177.15 17:02:27 315.71 204.21 14:23:15 200 290.67 179.17 17:02:40 313.71 202.21 14:30 200 293.59 182.09 17:02:56 311.71 200.21 14:35:30 200 299.83 188.33 17:03:03 310.71 199.21 14:38:10 200 302.64 191.14 17:03:09 309.71 198.21 14:40:30 200 304.49 192.99 17:03:20 308.71 197.21 14:44:50 200 307.92 196.42 17:03:28 307.71 196.21 14:49:40 200 308.94 197.44 17:03:36 306.71 195.21 14:56:10 200 313.20 201.70 17:03:45 305.71 194.21 15:00:10 200 317.47 205.97 17:03:51 304.71 193.21 15:03:50 200 320.90 209.40 17:04:00 303.71 192.21 15:07:40 200 323.71 212.21 17:04:07 302.71 191.21 15:12:50 200 325.97 214.47 17:04:15 301.71 190.21 15:16:35 200 327.57 216.07 17:04:21 300.71 189.21 15:25:40 200 335.30 223.80 17:04:29 299.71 188.21 15:29:10 200 337.70 226.20 17:04:39 298.71 187.2l 15:33 200 339.29 227.79 17:04:45 297.71 186.21 15:38:25 200 340.49 228.99 17:04:53 296.71 185.21 15:44:20 200 341.39 229.89 17:05:00 295.71 184.21 15:49:10 200 341.90 230.40 17:05:07 294.71 183.21 15:55 200 349.10 237.60 17:05:17 293.71 182.21 16:00 200 352.52 241. 02 17:05:25 292.71 181.21

.. 1"""'-. ""'" '-' ...., Depth to Drawdown Depth to Drawdowr

Time Water (feet) Time Water (feet) (feet) (feet)

17:05:33 291.71 180.21 17:12:00 241.71 130.21 17:05:40 290.71 179.21 17:12:08 240.71 129.21 17:05:49 289.71 178.21 17:12:15 239.71 128.21 17:05:57 288.71 177.21 17:12:23 238.71 127.21 17:06:04 287.71 176.21 17:12:32 237.71 126.21 17:06:12 286.71 175.21 17:12:42 236.71 125.21 17:06:20 285.71 174.21 17:12:54 235.71 124.21 17:06:27 284.71 173.21 17:13:02 234.71 123.21 17:06:35 283.71 172.21 17:13:13 233.71 122.21 17:06:42 282.71 171. 21 17:13:23 232.71 121.21 17:06:50 281. 71 170.21 17:13:31 231.71 120.21 17:06:57 280.71 169.21 17:13:41 230.71 119.21 17:07:05 279.71 168.21 17:13:53 229.71 118.21 17:07:12 278.71 167.21 17:14:03 228.71 117.21 17:07:20 277.71 166.21 17:14:13 227.71 116.21 17:07:28 276.71 165.21 17:14:21 226.71 115.21 17:07:36 275.71 164.21 17:14:30 225.71 114.21 17:07:44 274.71 163.21 17:14:39 224.71 113.21 17:07:52 273.71 162.21 17:14:47 223.71 112.21 17:07:59 272.71 161.21 17:14:54 222.71 111.21 17:08:07 271.71 160.21 17:15:04 221.71 110.21 17:08:14 270.71 159.21 17:15:11 220.71 109.21 17:08:22 269.71 158.21 17:15:20 219.71 108.21 17:08:29 268.71 157.21 17:15:28 218.71 107.21 17:08:37 267.71 156.21 17:15:36 217.71 106.21 17:08:44 266.71 155.21 17:15:44 216.71 105.21 17:08:53 265.71 154.21 17:15:52 215.71 104.21 17:09:00 264.71 153.21 17:16:00 214.71 103.21 17:09:08 263.71 152.21 17:16:09 213.71 102.21 17:09:14 262.71 151.21 17:16:17 212.71 101.21 17:09:23 261.71 150.21 17:16:25 211.71 100.21 17:09:30 260.71 149.21 17:16:33 210.71 99.21 17:09:38 259.71 148.21 17:16:43 209.71 98.21 17:09:44 258.71 147.21 17:16:50 208.71 97.21 17:09:52 257.71 146.21 17:17:00 207.71 96.21 17;10;00 256.71 145.21 17;17;08 206.71 95.21 17;10:09 255.71 144.21 17;17;17 205.71 94.21 17:10:17 254.71 143.21 17:17:25 204.71 93.21 17:10:25 253.71 142.21 17:17:34 203.71 92.21 17:10:33 252.71 141.21 17:17:42 202.71 91.21 17:10:41 251.71 140.21 17:17:50 201.71 90.21 17:10:48 250.71 139.21 17:17:59 200.71 89.21 17:10:57 249.71 138.21 17:18:08 199.71 88.21 17:11:04 248.71 137.21 17:18:16 198.71 87.21 17:11:12 247.71 136.21 17:18:26 197.71 86.21 17:11:20 246.71 135.21 17:18:34 196.71 85.21 17:11:28 245.71 134.21 17:18:44 195.71 84.21 17:11:35 244.71 133.21 17:18:53 194.71 83.21 17:11:44 243.71 132.21 17:19:02 193.71 82.21 17:11:52 242.71 131. 21 17:19:12 192.71 81.21

• ~ ~. • '-' ...""

Depth to Drawdown Depth to Drawdown Time Water (feet) Time Water (feet)

(feet) (feet)

17:19:21 191.71 80.21 17:31:35 141.71 30.21 17:19:30 190.71 79.21 17:32:02 140.71 29.21 17:19:40 189.71 78.21 17:32:41 139.71 28.21 17:19:48 188.71 77.21 17:33:16 138.71 27.21 17:19:59 187.71 76.21 17:33:58 137.71 26.21 17:20:08 186.71 75.21 17:34:39 136.71 25.21 17:20:18 185.71 74.21 17:35:34 135.71 24.21 17:20:27 184.71 73.21 17:36:28 134.71 23.21 17:20:38 183.71 72.21 17:37:41 133.71 22.21 17:20:47 182.71 71.21 17:38:56 132.71 21.21 17:20:58 181.71 70.21 17:40:43 131. 71 20.21 17:21:08 180.71 69.21 17:42:40 130.71 19.21 17:21:19 179.71 68.21 17:45:35 129.71 18.21 17:21:29 178.71 67.21 17:49:10 128.71 17.21 17:21:40 177.71 66.21 17:55:05 127.71 16.21 17:21:50 176.71 65.21 18:02:10 126.71 15.21 17:22:02 175.71 64.21 18:11:40 125.93 14.43 17:22:12 174.71 63.21 18:15:00 125.60 14.10 17:22:25 173.71 62.21 18:20:00 125.15 13.65 17:22:35 172.71 61.21 18:25:00 124.92 13.42 17:22:46 171.71 60.21 18:30:00 124.69 13.19 17:22:58 170.71 59.21 17:23:10 169.71 58.21 17:23:22 168.71 57.21 17:23:35 167.71 56.21 17:23:46 166.7~ 55.21. 17:24:01 165.71 54.21 17:24:13 164.71 53.21 17:24:27 163.71 52.21 17:24:40 162.71 51.21 17:24:55 161.71 50.21 17:25:07 160.71 49.21 17:25:23 159.71 48.21 17:25:36 158.71 47.21 17:25:53 157.71 46.21 17:26:07 156.71 45.21 17:26:26 155.71 44.21 17:26:42 154.71 43.21

153.71 42.21 17:27:18 152.71 41.21

t ~ > M--4 "

17:27:37 151.71 40.21 17:27:56 150.71 39.21 17:28:16 149.71 38.21 17:28:36 148.71 37.21 17:28:58 147.71 36.21 17:29:21 146.71 35. 2t··

'- 34.21: ,. 17:29:46 145.71 ~, 17:30:09 144.71 33.21 •... ,'

17:30:38 143.71 32.21 ~' . 17:31:03 142.71 31.21 "':" "

~ '", ~"

•• ' 1" .~-.

w o o

N ()l o

o Drawdown and Pumping Rate (feet, gpm)

N o o

-" o o

()l o o

! ;1.1.';')

• - ,~ - r" : ... ', ".,..-

145fJ:24 1~: 10:48

i~:25: 12 1 ~:39:36 15:54:00

1 ():08:24

i E::22:48 16:.37: i 2 :i::51:3f,

o

--.oJ QI QI :t:. c ~ 0 'C ~ III ... 0 'i :J 'C

0 'iii QI

0::

16:48:00 17:02:24 17:16:48

Pukaki Well Step Drawdown Recovery

17:31:12

Time (minutes)

17:45:36 18:00:00

o - ---r--'---1~··-···~--,---.. ---r---··1· -·1---·'" --,-- r--,--- I

............-. • • •

50 - ---------~ -

100 ---- -- .

150

200 -1----

250 ------- ---.

18:14:24 18:28:48 18:43:12

• • • • •

- c Stabilized Drawdown and Pumping Rate Data

Pumping Rate (gpm)

100 120 150

Stabilized Drawdown (feet)

61 78

105

Step Drawdown Results (log - log plot)

o

1000~------------------------~

-.... Q)

~ -c • i 100+-------------.*--~~~--------~

cu ~

C

10~,------------------------~

10 100

Pumping Rate (gpm)

1000

PUKAKI WELL - CONSTANT-RATE TEST Date Started: July 20, 1998 SHUT DOWN - July 30, 1998

Approximate ground elevation: 345' (msl)

Time Flow Depth to (gpm) Water

(feet)

o 116.75

Water level

Elevation (feet)

06:30 09:00 09:00:30

o 116.75 228.25 REMARKS: Started Pumping.

09:01:35 09:02:05 09:02:35 09:03:35 09:04:20 09:04:50 09:05 156.0 09:05:35 09:06:05 09:06:30 09:07:10 09:07:40 09:08 152.4 09:08:10 09:08:30 09:09:10 09:10:40 09:11:10 09:11:35 09:12:05 09:12:35 09:13:10 09:13:40 09:14 150.9 09:14:10 09:15:40 09:16:25 09:18:20 09:19:00 09:19:20 09:19:40 09:20:10 09:20:25 09:20:50 09:21:20 09:21:45 09:22 149.8 09:22:20 09:22:50 09:23:15

meter 214.7T 215·{13 215.44 216.20 216.47

1217.09

217.77 218.29 218.71 219.17 219.82

220.08 220.71 221.13 221. 44 221. 71 222.04 222.57 222.77 223.13 223.52

223.74 224.14 224.68 225.25 225.74 226.04 226.14 226.34 226.68 226.74 227.20 227.34

227.58 227.84 228.01

130.23 129.88 129.56 128.80 128.53 127.91

127.23 126.71 126.29 125.83 125.18

124.92 124.29 123.88 123.56 123.29 122.96 122.43 122.23 121. 88 121.48

121. 26 120.86 120.32 119.75 119.26 118.96 118.86 118.66 118.32 118.26 117.80 117.66

117.42 117.16 116.99

Drawdown Remarks (feet)

3" meter broken, using 6"

98.02 98.38 98.69 99.45 99.72

100.34

101. 02 101.54 101.96 102.42 103.07

103.33 103.96 104.38 104.69 104.96 105.29 105.82 106.02 106.38 106.77

106.99 107.39 107.93 108.50 108.99 109.29 109.39 109.59 109.93 109.99 110.45 110.59

110.83 111.09 111.26

~

"""'" /'~'. ~ .. \.,., \~.

Time Flow Depth to Water Drawdown Remarks (gpm) Water level (feet)

(feet) Elevation (feet)

09:23:40 228.05 116.95 111. 30 09:24:00 228.27 116.73 111. 52 09:24:40 228.60 116.40 111. 85 09:25:10 228.88 116.13 112.13 09:25:25 229 116 112.25 09:25:50 229.38 115.63 112.63 09:26:10 229.64 115.36 112.89 09:26:40 229.93 115.07 113.18 09:27:10 230.08 114.92 113.33 09:27:30 230.33 114.67 113.58 09:28:00 230.66 114.34 113.91 09:28:50 231. 96 113.04 115.21 09:29:20 221.34 123.66 104.59 09:29:50 221. 68 123.32 104.93 09:30 153.0 09:30:20 232.16 112.84 115.41 09:30:50 232.38 112.63 115.63 09:31:20 232.57 112.43 115.82 09:31:50 232.86 112.14 116.11 09:32:20 233.26 111.74 116.51 09:32:50 233.53 111.47 116.78 09:33:20 233.58 111.42 116.83 09:33:50 234.04 110.96 117.29 09:34:20 234.24 110.76 117.49 09:34:50 234.50 110.50 117.75 09:35:20 234.73 110.27 117.98 09:35:50 235.04 109.96 118.29 09:36:20 235.31 109.69 118.56 09:36:50 235.46 109.54 118.71 09:37:20 235.54 109.46 118.79 09:37:50 235.95 109.05 119.20 09:38:20 236.21 108.79 119.46 09:38:50 236.42 108.58 119.67 09:39:20 236.58 108.42 119.83 09:39:50 236.88 108.13 120.13 09:40:20 237.24 107.76 120.49 09:40:50 237.59 107.41 120.84 09:41:20 237.88 107.13 121.13 09:41:50 238.22 106.78 121.47 09:42:20 238.58 106.42 121. 83 09:42:50 238.88 106.13 122.13 09:43:20 239.20 105.80 122.45 09:43:50 239.54 105.46 122.79 09:44:20 239.83 105.17 123.08 09:44:50 240.08 104.92 123.33 09:45 158.6 240 105 123.25 09:45:20 240.36 104.64 123.61 09:45:50 240.59 104.41 123.84 09:46:50 241.30 103.70 124.55 . \

r'

·f - .~ ~

Time Flow Depth to Water Drawdown Remarks (gpm) Water level (feet)

(feet) Elevation (feet)

09:47:20 241. 59 103.41 124.84 09:47:50 241. 56 103.44 124.81 09:48:20 241. 68 103.32 124.93 09:48:50 241. 86 103.14 125.11 09:49:20 241.88 103.13 125.13. 09:49:50 241.86 103.14 125.11 09:50:20 241.84 103.16 125.09 09:50:50 241. 77 103.23 125.02 09:51:20 241.90 103.10 125.15 09:51:50 241.95 103.05 125.20 09:52:20 241.83 103.17 125.08 09:52:50 241. 96 103.04 125.21 09:53:20 242 103 125.25 09:53:50 242 103 125.25 09:54:20 242 103 125.25 09:54:50 242.07 102.93 125.32 09:55:20 242.07 102.93 125.32 09:55:50 242.13 102.88 125.38 09:56:20 242.10 102.90 125.35 09:56:50 242.22 102.78 125.47 09:57:20 242.29 102.71 125.54 09:57:50 242.38 102.63 125.63 09:58:20 242.29 102.71 125.54 09:58:50 242.33 102.67 125.58 09:59:20 242.45 10-2.55 125.70 09:59:50 242.48 102.52 125.73 10:00 144.6 10:00:20 242.54 102.46 125.79 10:00:50 242.54 102.46 125.79 10:01:20 242.61 102.39 125.86 10:01:50 242 103 125.25 10:02:20 242.70 102.30 125.95 10:02:50 242.81 102.19 126.06 10:03:20 242.83 102.17 126.08 10:03:50 242.93 102.07 126.18 10:04:20 243.04 101. 96 126.29 10:04:50 243.06 101.94 126.31 10:05:20 243.13 101.88 126.38 10:05:50 243.16 101.84 126.41 10:06:20 243.24 101.76 126.49 10:06:50 243.24 101.76 126.49 10:07:20 243 102 126.25 10:07:50 243.44 101.56 126.69 10:08:20 243.48 101.52 126.73 10:08:50 243.44 101.56 126.69 10:09:20 243.48 101.52 126.73 10:09:50 243.51 101.49 126.76 10:10:20 243.63 101.38 126.88 10:10:50 243.68 101. 32 126.93

·t 1"'" """ . , -\u.- '..."J

Time Flow Depth to Water Drawdown Remarks (gpm) Water level (feet)

(feet) Elevation (feet)

',.,;" .... ' ... - ,

10:11:20 243.65 101.35 126.90 10:11:50 243.71 101. 29 126.96 10:12:20 243.82 101.18 127.07 10:12:50 243.75 101.25 ·127 10:13:20 243.86 101.14 127.11 10:13:50 243.92 101.08 127.17 10:14:20 243.91 101. 09 127.16 10:15 147.4 10:15:20 243.98 101.02 127.23 10:15:50 243.92 101. 08 127.17 10:16:20 244 101 127.25 10:16:50 244.01 100.99 127.26 10:17:20 244.08 100.92 127.33 10:18:20 244.15 100.85 127.40 10:19:20 244.17 100.83 127.42 10:20:20 244.27 100.73 127.52 10:23 244.39 100.61 127.64 10:30 153.2 244.94 100.06 128.19 10:35 245.35 99.65 128.60 10:40 245.63 99.38 128.88 10:45 148.5 245.90 99.10 129.15 10:50 246.04 98.96 129.29 10:55 246.21 98.79 129.46 11:00 246.23 98.77 129.48 11:05 245.71 99.29 128.96 11:10 245.40 99.60 128.65 11:15 146.3 245.13 99.88 128.38 11:20 245.09 .99.91 128.34 11:25 245.08 99.92 128.33 11:30 245.13 99.88 128.38 11:35 245.29 99.71 128.54 11:40 245.27 99.73 128.52 11:45 245.29 99.71 128.54 11:50 245.29 99.71 128.54 11:55 245.48 99.52 128.73 12:00 245.46 99.54 128.71 12:05 245.44 99.56 128.69 12:10 245.35 99.65 128.60 12:15 245.41 99.59 128.66 12:20 245.42 99.58 128.67 12:25 245.48 99.52 128.73 12:30 245.49 99.51 128.74 12:35 245.40 99.60 128.65 12:40 245.44 99.56 128.69 12:45 150.9 245.46 99.54 128.71 12:50 245.60 99.40 128.85 12:55 245.79 99.21 129.04 13:00 245.83 99.17 129.08 13:05 245.99 99.01 129.24

Time

13:10 13:15 13:20 13:25 13:30 13:35 13:40 13:45 13:50 13:55 14:00 14:05 14:10 14:15 14:20 14:25 14:30 14:35 14:40 14:42 deg.C. 14:45 14:50 15:00 15:30 16:00 17:00

18:00 19:00 20:00

21:00 22:00 23:00

7/21/98 00:00 01:00 02:00 03:00 04:00 05:00 06:00 07:00 08:00 09:00 10:00 11:00

Flow Depth to Water level

Elevation (feet)

Drawdown (feet)

Remarks (gpm) Water

145.2

142.9

149.5 142.5

REMARKS: 147.9 146.2 145.0

REMARKS: 145.4 144.5 145.4

143.2 146.1 144.7 142.7 145.9 143.9 146.7 147.1 144.9 145.1 141.9 144.7

(feet)

246.21 246.50 246.71 247.13 247.50 247.52 247.77 247.67 247.92 248.04

248 248

247.96 247.96 248.50 249.08 249.46 249.88 250.42

• . •• ~ - i

98.79 98.50 98.29 97.88 97.50 97.48 97.23 97.33 97.08 96.96

97 97

97.04 97.04 96.50 95.92 95.54 95.13 94.58

250.83 94.17 251 94

251.10 93.90 251.33 93.67 252.13 92.88 257.71 87.29

Adjusted flow rate 268.73 76.27 271.54 73.46 273.21 71.79

Change shift. 278.92 66.08 275.33 69.67 278.92 66.08

278 278.08 282.42 283.25

283 288.25 290.75 300.04 299.25 299.50 298.60 300.15

67 66.92 62.58 61.75

62 56.75 54.25 44.96 45.75 45.50 46.40 44.85

·''-0''

129.46 129.75 129.96 130.38 130.75, 130.77 131. 02 130.92 131.17 131. 29 131.25 Took water sample. 131. 25 131.21 131.21 131. 75 132.33 132.71 133.13 133.67

134.08 134.25 134.35 134.58 135.38 140.96

Water temp.: 25

back to 150 gpm 151. 98 154.79 156.46

162.17 158.58 Took water sample. 162.17

161.25 161. 33 165.67 166.50 166.25 Took water sample. 171. 50

174 183.29 182.50 182.75 181.85 Adjusted flow rate 183.40

't ,-,., 0 ,'-"'

Time Flow Depth to Water Drawdown Remarks (gpm) Water level (feet)

(feet) Elevation ~. ~. (feet)

12:00 142.4 301.92 43.08 185.17 Adjusted flow rate 13:00 145.4 307.08 37.92 190.33 14:00 146.9 311. 44 33.56 194.69 Adjusted flow rate 14:30 REMARKS: Adjusted flow rate 15:00 147.0 313.38 31. 63 196.63, 16:00 147.5 316.79 28.21 200.04 16:30 REMARKS: Took water sample. 17:00 147.0 317.42 27.58 200.67 18:00 145.2 318.46 26.54 201.71 19:00 145.7 319.75 25.25 203 20:00 147.2 320.88 24.13 204.13 21:00 144.8 321.29 23.71 204.54 22:00 144.9 321.54 23.46 204.79 Change shift 23:00 146.5 322.21 22.79 205.46

7/22/98 00:00 144.5 323.25 21.75 206.50 01:00 145.1 323.29 21.71 206.54 02:00 144.0 322.50 22.50 205.75 03:00 144.5 322.92 22.08 206.17 04:00 143.2 323.83 21.17 207.08 05:00 142.8 323 22 206.25 06:00 141. 0 322.67 22.33 205.92 Change shift 06:13 REMARKS: Opened valve 07:00 146.2 333.38 1'1. 63 216.63 08:00 148.3 337.04 7.96 220.29 09:00 152.0 341.01 3.99 224.26 10:00 146.5 344.10 .90 227.35 11:00 146.2 343.05 1. 95 226.30 12:00 143.6 343.34 1. 66 226.59 12:30 REMARKS: Opened valve 13:00 145.0 345.54 -.54 228.79 14:00 145.3 347.48 -2.48 230.73 15:00 146.0 351.88 -6.88 235.13 16:00 145.8 350.29 -5.29 233.54 16:30 REMARKS: Took water sample. 17:00 145.3 349.58 -4.58 232.83 17:20 REMARKS: Opened valve 18:00 146.6 355.84 -10.84 239.09 19:00 145.3 356.58 -11.58 239.83 20:00 145.6 357 -12 240.25 21:00 145.5 356.92 -11. 92 240.17 22:00 144.9 356.58 -11.58 239.83 23:00 145.7 357.46 -12.46 240.71 23:30 REMARKS: Opened valve

7/23/98 00:00 143.6 359.58 -14.58 242.83 01:00 144.3 358.25 -13.25 241.50

'. r-. ,.on"" 2345X .\..T "'-'

Time Flow Depth to Water Drawdown Remarks (gpm) Water level (feet)

(feet) Elevation (feet)

02:00 143.6 358.75 -13.75 242 02:30 REMARKS: Opened valve 03:00 144.9 360.08 -15.08 243.33 03:40 REMARKS: Opened valvE 04:00 147.9 363 -18 246.25 04:30 REMARKS: Opened valve 05:00 143.6 366.75 -21. 75 250 05:15 REMARKS: Opened valve 06:00 148.1 371.08 -26.08 254.33 07:00 144.4 371. 04 -26.04 254.29 08:00 146.2 371. 24 -26.24 254.49 09:00 144.0 372.02 -27.02 255.27 09:16 REMARKS: Opened valve 09:44 REMARKS: Opened valve 10:00 144.9 375.13 -30.13 258.38

10:30 REMARKS: Adjusting flow rate to 136 gpm (44sec/100gal)

11:00 135.3 366 -21 249.25 12:00 139.4 359.14 -14.14 242.39 13:00 136.7 354.81 -9.81 238.06 14:00 137.9 353 -8 236.25 15:00 137.0 352.42 -7.42 235.67 16:00 137.0 351.64 -6.64 234.89 16:30 REMARKS: Took water sample. 17:00 136.6 353.67 -8.67 236.92 18:00 137.0 352.76 -7.76 236.01 19:00 136.0 353.21 -8.21 236.46 20:00 138.2 353.71 -8.71 236.96 21:00 137.7 354.29 -9.29 237.54 22:00 135.7 353.50 -8.50 236.75 23:00 140.3 351. 33 -6.33 234.58 23:05 REMARKS: Closed valve.

7/24/98 00:00 134.5 352.33 -7.33 235.58 00:05 REMARKS: Opened valve. 01:00 135.4 352.75 -7.75 236 02:00 135.4 350.17 -5.17 233.42 03:00 137.0 351 -6 234.25 04:00 135.6 349.67 -4.67 232.92 05:00 135.8 351. 33 -6.33 234.58 06:00 136.4 350.77 -5.77 234.02 06:30 REMARKS: Opened valve. 07:00 136.3 349.85 -4.85 233.10 08:00 136.7 351. 46 -6.46 234.71 08:30 135.9 351.13 -6.13 234.38 09:00 135.4 350.23 -5.23 233.48 09:30 135.7 351. 06 -6.06 234.31

'. c .:)

Time FloW' Depth to Water Drawdown Remarks (gpm) Water level (feet)

(feet) Elevation (feet)

10:00 135.3 351. 38 -6.38 234.63 11:00 135.2 349.15 -4.15 232.40 11:30 134.7 349.74 -4.74 232.99 12:00 136.0 350.08 -5.08 233.33 12:45 REMARKS: Closed valve 13:00 134.3 351. 83 -6.83 235.08

13:30 REMARKS: Changed flow rate to 130 gpm

14:00 130.7 341 4 224.25 15:00 131.1 337.71 7.29 220.96 16:00 131.1 337 8 220.25 17:00 129.8 337.79 7.21 221.04 18:00 130.2 335.58 9.42 218.83 19:00 129.9 335.63 9.38 218.88 20:00 130.8 336.71 8.29 219.96 21:00 130.4 336.83 8.17 220.08 22:00 130.9 335.17 9.83 218.42 23:00 131. 3 336.21 8.79 219.46

7/25/98 Saturday -00:00 131. 2 335.46 9.54 218.71 00:05 REMARKS: Opened valve. 01:00 135.6 335.46 9.54 218.71 01:05 REMARKS: Closed valve. 02:00 128.5 331. 92 13.08 215.17 03:00 130.3 332.13 12.88 215.38 04:00 129.6 331.63 ;1.3.38 214.88 05:00 129.3 330.92 14.08 214.17

-06: 00 129.5 329.77 15.23 213.02 06:30 REMARKS: Opened valve. 07:00 130.6 330.25 14.75 213.50 08:00 129.8 331.65 13.35 214.90 09:00 129.6 329.76 15.24 213.01 10:00 130.1 328.40 16.60 211.65 11:00 131.7 331.67 13.33 214.92 12:00 129.5 330.03 14.97 213.28 13:00 129.7 329.32 15.68 212.57 14:00 130.5 329.78 15.22 213.03 15:00 130.7 329.08 15.92 212.33 15:45 REMARKS: Opened valve. 16:00 130.4 330.32 14.68 213.57 17:00 131.9 331. 86 13.14 215.11 17:45 REMARKS: Closed valve. 1.8:00 130.5 331.40 13.60 214.65 19:00 130.2 330.10 14.90 213.35 20:00 130.7 329.55 15.45 212.80 21:00 130.1 329.42 15.58 212.67 21:40 REMARKS: Closed valve

, c :)

Time Flow Depth to Water Drawdown Remarks (gpm) Water level (feet)

(feet) Elevation (feet)

22:00 131.2 329.44 15.56 212.69 22:30 REMARKS: Opened valve. 23:00 131. 2 329.44 15.56 212.69

7/26/98 Sunday 00:00 130.8 329.90 15.10 213.15 01:00 130.6 328.48 16.52 211. 73 02:00 130.8 328.31 16.69 211. 56 03:00 130.8 330.50 14.50 213.75 04:00 131.2 330.42 14.58 213.67 05:00 131.0 330 15 213.25 05:30 REMARKS: Closed valve. 06:00 130.5 329.83 15.17 213.08 07:00 130.3 330.08 14.92 213.33 07:30 REMARKS: Opened valve. 08:00 130.4 328.46 16.54 211.71 09:00 131.2 330.16 14.84 213.41 10:00 129.5 327.88 17.13 211.13 11:00 129.5 327.08 17.92 210.33 12:00 130.2 328.13 16.88 211.38 13:00 130.4 327.24 17.76 210.49 14:00 129.3 327.10 17.90 210.35 15:00 130.2 326.23 18.77 209.48 16:00 130.0 324.58 20.42 207.83 17:00 129.9 324.52 20.48 207.77 18:00 130.3 325.15 19.85 208.40 19:00 130.1 325.55 19.45 208.80 20:00 130.5 327.10 17.90 210.35 21:00 130.9 327.97 17.03 211.22 22:00 130.3 326.88 18.13 210.13 23:00 130.0 327.98 17.02 211.23

7/27/98 Monday 00:00 129.6 326.65 18.35 209.90 01:00 129.4 326.75 18.25 210 02:00 129.1 325.69 19.31 208.94 03:00 129.6 325.09 19.91 208.34 04:00 129.3 323.50 21.50 206.75 05:00 129.1 323.38 21. 63 206.63 06:00 129.8 323.69 21.31 206.94 07:00 131. 5 325.67 19.33 208.92 08:00 130.8 326.92 18.08 210.17 09:00 129.6 324.35 20.65 207.60 10:00 128.8 323.33 21. 67 206.58 11:00 129.6 324.11 20.89 207.36 12:00 129.8 324.24 20.76 207.49 13:00 129.5 323.56 21.44 206.81 14:00 129.8 324.24 20.76 207.49 15:00 129.9 324.94 20.06 208.19

· . /"'. ~ ,"-"'

Time Flow Depth to Water Drawdown Remarks (gpm) Water level (feet)

(feet) Elevation (feet)

16:00 129.3 323.34 21. 66 206.59 17:00 129.8 323.97 21. 03 207.22 18:00 129.7 325.75 19.25 209 19:00 130.8 325.59 19.41 208.84 20:00 129.5 325.09 19.91 208.34 21:00 131.2 323.83 21.17 207.08 22:00 129.8 323.67 21. 33 206.92 23:00 130.0 323.51 21.49 206.76

7/28/98 Tuesday 00:00 129.4 322.79 22.21 206.04 01:00 129.5 322.67 22.33 205.92 02:00 130.3 322.46 22.54 205.71 03:00 129.4 322.21 22.79 205.46 04:00 129.5 321.04 23.96 204.29 05:00 130.0 321.13 23.88 204.38 06:00 130.6 321. 34 23.66 204.59 07:00 129.3 321.59 23.41 204.84 08:00 129.7 321.41 23.59 204.66 09:00 129.3 320.81 24.19 204.06 10:00 129.0 320.17 24.83 203.42 11:00 129.7 320.74 24.26 203.99 12:00 130.1 321. 55 23.45 204.80 13:00 129.6 321. 21 23.79 204.46 14:00 129.4 321.59 23.41 204.84 15:00 129.3 322.09 22.91 205.34 16:00 129.6 323.19 21. 81 206.44 17:00 129.3 321.29 23.71 204.54 18:00 130.1 322.47 22.53 205.72 19:00 130.6 322.29 22.71 205.54 20:00 130.1 322.68 22.32 205.93 21:00 129.9 322.99 22.01 206.24 22:00 130.0 323 22 206.25 23:00 130.3 322.96 22.04 206.21

7/29/98 Wednesday 00:00 129.9 323.52 21.48 206.77 01:00 131.7 324.10 20.90 207.35 02:00 129.8 322.13 22.88 205.38 03:00 130.4 321.42 23.58 204.67 04:00 131.5 323.98 21.02 207.23 05:00 129.5 323.17 21. 83 206.42 06:00 130.8 323.14 21. 86 206.39 07:00 130.3 323.56 21.44 206.81 08:00 130.2 324.50 20.50 207.75 09:00 130.3 323.65 21. 35 206.90 10:00 129.5 322.81 22.19 206.06 11:00 129.7 322.44 22.56 205.69 12:00 130.0 322.46 22.54 205.71

c Time Flow Depth to

(gpm) Water (feet)

13:00 130.7 323.32 14:00 130.0 323.63 15:00 130.0 324.46 16:00 130.2 323.33 17:00 130.4 321. 96 18:00 129.9 322.74 19:00 130.2 322.50 20:00 129.6 322.41 21:00 129.6 323 22:00 129.5 322.71 23:00 129.7 322.80

7/30/98 Thursday 00:00 130.5 322.42 01:00 129.8 322.65 02:00 130.2 322.47 03:00 129.6 322.92 04:00 130.5 322.42 05:00 130.2 322.75 06:00 130.7 321. 96 07:00 129.6 321. 56 08:00 129.5 320.92 09:00 129.4 321.17 09:15:00

Water level

Elevation (feet)

21. 68 21.38 20.54 21. 67 _ 23.04 22.26 22.50 22.59

22 22.29 22.20

22.58 22.35 22.53 22.08 22.58 22.25 23.04 23.44 24.08 23.83

PUKAKI WELL - CONSTANT-RATE TEST Date Started: July 20, 1998 SHUT DOWN - July 30, 1998

Time Depth to Drawdown Water Elevation (feet)

(feet) (ft)

7/30/98 Thursday 09:15:00 REMARKS: Shut down. 09:15:52 283 62 166.25 09:15:58 280 65 163.25 09:16:03 278 67 161. 25 09:16:08 274 71 157.25 09:16:11 273 72 156.25 09:16:14 272 73 155.25 09:16:17 271 74 154.25 09:16:19 270 75 153.25 09:16:21 269 76 152.25 09:16:23 268 77 151.25 09:16:27 267 78 150.25 09:16:31 266 79 149.25 09:16:35 265 80 148.25

Drawdown (feet)

206.57 206.88 207.71 206.58 205.21 205.99 205.75 205.66 206.25 205.96 206.05

205.67 205.90 205.72 206.17 205.67

206 205.21 204.81 204.17 204.42

Remarks

Shut down.

Remarks

r" .... '" I'w' j

........ '

Time Depth to Drawdown Remarks Water Elevation (feet)

(feet) (ft)

09:17:01 264 81 147.25 09:17:15 263 82 146.25 09:17:27 262 83 145.25 09:17:39 261 84 144.25 09:17:52 260 85 143.25 09:18:06 259 86 142.25 09:18:19 258 87 141. 25 09:18:32 257 88 140.25 09:18:44 256 89 139.25 09:18:57 255 90 138.25 09:19:09 254 91 137.25 09:19:23 253 92 136.25 09:19:36 252 93 135.25 09:19:48 251 94 134.25 09:20:01 250 95 133.25 09:20:14 249 96 132.25 09:20:26 248 97 131. 25 09:20:39 247 98 130.25 09:20:51 246 99 129.25 09:21:04 245 100 128.25 09:21:17 244 101 127.25 09:21:30 243 102 126.25 09:21:42 242 103 125.25 09:21:56 241 104 124.25 09:22:09 240 105 123.25 09:21:23 239 106 122.25 09:21:36 238 107 121. 25 09:21:50 237 108 120.25 09:23:03 236 109 119.25 09:23:18 235 110 118.25 09:23:31 234 111 117.25 09:23:45 233 112 116.25 09:24:00 232 113 115.25 09:24:13 231 114 114.25 09:24:26 230 115 113.25 09:24:40 229 116 112.25 09:24:54 228 117 111.25 09:25:08 227 118 110.25 09:25:22 226 119 109.25 09:25:38 225 120 108.25 09:25:52 224 121 107.25 09:26:07 223 122 106.25 09:26:22 222 123 105.25 09:26:37 221 124 104.25 09:26:51 220 125 103.25 09:27:07 219 126 102.25 09:27:22 218 127 101.25 09:27:37 217 128 100.25 09:27:53 216 129 99.25 09:28:08 215 130 98.25

r """"" \'-' . ...."

Time Depth· to Drawdown Remarks Water Elevation (feet)

(feet) (ft)

09:28:23 214 131 97.25 09:28:40 213 132 96.25 09:28:56 212 133 95.25 09:29:13 211 134 94.25 09:29:30 210 135 93.25 09:29:47 209 136 92.25 09:30:05 208 137 91. 25 09:30:22 207 138 90.25 09:30:40 206 139 89.25 09:30:59 205 140 88.25 09:31:17 204 141 87.25 09:31:36 203 142 86.25 09:31:55 202 143 85.25 09:32:14 201 144 84.25 09:32:32 200 145 83.25 09:32:52 199 146 82.25 09:33:12 198 147 81.25 09:33:32 197 148 80.25 09:33:52 196 149 79.25 09:34:14 195 150 78.25 09:34:35 194 151 77.25 09:34:56 193 152 76.25 09:35:19 192 153 75.25 09:35:41 191 154 74.25 09:36:04 190 155 73.25 09:36:28 189 156 72.25 09:36:52 188 157 71.25 09:37:17 187 158 70.25 09:37:44 186 159 69.25 09:38:11 185 160 68.25 09:38:42 184 161 67.25 09:39:16 183 162 66.25 09:39:51 182 163 65.25 09:40:28 181 164 64.25 09:41:05 180 165 63.25 09:41:44 179 166 62.25 09:42:24 178 167 61.25 09:43:08 177 168 60.25 09:44:02 176 169 59.25 09:44:57 175 170 58.25 09:45:52 174 171 57.25 09:46:46 173 172 56.25 09:47:42 172 173 55.25 09:48:37 171 174 54.25 09:49:35 170 175 53.25 09:50:35 169 176 52.25 09:51:39 168 177 51.25 09:52:43 167 178 50.25 09:53:48 166 179 49.25 09:54:58 165 180 48.25

, . , ....

l"'" \., ......

Time Depth'to Drawdown Remarks Water Elevation (feet)

(feet) (ft)

09:56:10 164 181 47.25 09:57:28 163 182 46.25 09:58:56 162 183 45.25 10:00:23 161 184 44.25 10:01:53 160 185 43.25 10:03:30 159 186 42.25 10:05:14 158 187 41.25 10:07:14 157 188 40.25 10:09:25 156 189 39.25 10:11:55 155 190 38.25 10:14:34 154 191 37.25 10:17:46 153 192 36.25 10:21:29 152 193 35.25 10:25:54 151 194 34.25 10:31:20 150 195 33.25 10:38:06 149 196 32.25 10:43 148.44 196.56 31. 69 10:48 147.94 197.06 31.19 10:53 147.49 197.51 30.74 10:58 147.10 197.90 30.35 11:03 146.75 198.25 30 11:08 146.44 198.56 29.69 11:13 146.14 198.86 29.39 11:18 145.81 199.19 29.06 11:23 145.49 199.51 28.74 11:28 145.20 199.80 28.45 11:33 144.93 200.07 28.18 11:38 144.67 200.33 27.92 11:43 144.43 200.57 27.68 11:48 144.22 200.78 27.47 11:53 144 201 27.25 11:58 143.77 201.23 27.02 12:03 143.59 201.41 26.84 12:08 143.36 201. 64 26.61 :;1.2:13 143.17 201. 83 26.42 12:18 143.04 201. 96 26.29 12:23 142.84 202.16 26.09 12:40 142.29 202.71 25.54 12:55 141.78 203.22 25.03 13:10 141.33 203.67 24.58 13:25 140.80 204.20 24.05 13:40 140.59 204.41 23.84 13:55 140.20 204.80 23.45 14:10 140.85 204.15 24.10 14:25 139.57 205.43 22.82 14:40 139.23 205.77 22.48 14:55 139 206 22.25

"

Time Depth' to Drawdown Remarks Water Elevation (feet)

(feet) (ft)

7/31/98 08:00 130.27 214.73 13.52 12:00 129.28 215.72 12.53 15:00 128.43 216.57 11. 68

c USGS Monitor Well - Pukaki

Time

(To monitor constant rate well testing of the (DOW) Pukaki Well, which started at 9:00 am, 7/20/98)

(Measurements prior to those listed were made by Steve Gingrich, USGS)

(All measurements are from the lip of the sensor housing to water level. Approximate measuring point elevation: 322' msl.)

USGS Contractor Sensor Sensor

7/20/98 15:00 156.40 16:00 156.81 17:00 157.17 18:00 157.46 19:00 157.80 20:00 158.35 21:00 159.03 22:00 159.85 23:00 159.90

7/21/98 0:00 159.98 01:00 159.75 02:00 159.91 03:00 159.90 04:00 160.05 05:00 160.55 06:00 160.65 07:00 161.90 08:00 162.10 09:00 162.25 10:00 162.40 11:00 162.53 12:00 162.65 13:00 162.81 14:00 162.94 15:00 163.02 16:00 163.20 17:00 163.20 18:00 163.45 19:00 163.62 20:00 164.00 21:00 164.36 22:00 164.39 23:00 164.45

7/22/98 0:00 164.55 01:00 164.80 02:00 164.25

c --'" >...I

Time USGS Contractor Sensor Sensor

03:00 164.35 04:00 164.55 05:00 164.50 06:00 164.51 07:00 164.60 08:00 164.72 09:00 164.81 10:00 164.92 11:00 165.00 12:00 165.02 13:00 165.11 14:00 165.14 15:00 165.22 16:00 165.30 17:00 165.38 18:00 165.40 19:00 165.42 20:00 165.46 21:00 165.44 22:00 165.60 23:00 165.65

7/23/98 0:00 165.61 01:00 165.60 02:00 165.55 03:00 165.57 04:00 165.58 05:00 165.60 06:00 165.48 07:00 165.60 ? 08:00 165.60 ? 09:00 165.60 ? 10:00 165.60 ? 11:00 165.60 ? 12:00 13:00 164.89 ? 14:00 164.05 14:30 162.73 15:00 166.26 16:00 163.20 17:00 163.26 18:00 163.20 19:00 162.42 20:00 163 21:30 163.10 22:00 163.20 23:00 163.15

7/24/98 0:00 163.10

" ,.,g-",,,,",

~~ ....."

Time USGS Contractor Sensor Sensor

01:00 163.15 02:00 163.25 03:00 163.20 04:00 163.45 05:00 163.30 06:00 07:00 162.88 08:00 162.17 09:00 162.24 10:00 162.31 11:00 162.35 12:00 162.31 13:00 162.29 13:21 Adjusted flow rate to 130 gpm 14:00 162.31 15:00 162.32 16:00 162.33 17:00 162.34 18:00 162.38 19:00 162.34 20:00 162.34 21:30 162.38 22:00 162.35 23:00 162.33

7/25/98 Saturday 0:00 162.34 01:00 162.35 02:00 162.35 03:00 162.35 04:00 162.35 05:00 162.35 06:00 162.35 07:00 162.35 08:00 162.35 09:00 162.34 10:00 162.34 11:00 162.33 12:00 162.33 13:00 162.34 14:00 162.35 15:00 162.33 16:00 162.34 17:00 162.33 18:00 162.33 19:00 162.35 20:00 162.35 21:00 162.34 22:00 162.33 23:00 162.34

. . c .-"" -wi

Time USGS Contractor Sensor Sensor

7/26/98 Sunday 0:00 162.36 01:00 162.35 02:00 162.32 03:00 162.34 04:00 162.34 05:00 162.32 06:00 162.33 07:00 162.34 08:00 162.34 09:00 162.33 10:00 162.33 11:00 162.33 12:00 162.32 13:00 162.32 14:00 162.33 15:00 162.31 16:00 162.33 17:00 162.31 18:00 162.32 19:00 162.34 20:00 162.32 21:00 162.34 22:00 162.35 23:00 162.35

7/27/98 Monday 0:00 162.34 01:00 162.35 02:00 162.34 03:00 162.34 04:00 162.35 05:00 162.34 06:00 162.34 07:00 162.33 08:00 162.33 09:00 162.33 10:00 162.34 11:00 162.26 12:00 162.27 13:00 162.32 14:00 162.33 15:00 162.33 16:00 162.32 17:00 162.33 18:00 162.33 19:00 162.32 20:00 162.33 21:00 162.29 22:00 162.32 23:00 162.31

. ".,., "",", . ~ ....,;

Time USGS Contractor Sensor Sensor

7/28/98 Tuesday 0:00 162.30 01:00 162.29 02:00 162.30 03:00 162.31 04:00 162.30 05:00 162.31 06:00 162.29 07:00 162.29 08:00 162.29 09:00 162.33 10:00 162.33 11:00 162.29 12:00 162.29 13:00 162.29 14:00 162.29 15:00 162.29 16:00 162.29 17:00 162.28 18:00 162.29 19:00 162.29 20:00 162.28 21:00 162.28 22:00 162.29 23:00 162.29

7/29/98 Wednesday 0:00 162.28 01:00 162.28 02:00 162.28 03:00 162.28 04:00 162.29 05:00 162.30 06:00 162.29 07:00 162.29 08:00 162.29 09:00 162.27 10:00 162.29 11:00 162.29 12:00 162.28 13:00 162.29 14:00 162.29 15:00 162.30 16:00 162.29 17:00 162.29 18:00 162.29 19:00 162.30 20:00 162.30 21:00 162.29 22:00 162.30 23:00 162.29

· "."...., '''~';''-\~

~ """'" Time USGS Contractor

Sensor Sensor

7/30/98 Thursday 0:00 162.28 01:00 162.29 02:00 162.29 03:00 162.29 04:00 162.30 05:00 162.29 06:00 162.29 07:00 162.29 08:00 162.92 09:00 162.29 09:15 Shut down

USGS Monitor Well - Pukaki RECOVERY - July 30, 1998

NOTE: Shut down was at 9:15, however, contractor's sounder was not working well. Therefore, using the USGS sounder.

Time

09:37:43 09:41: 3 09:42: 3 09:43: 3 09:44: 3 09:45: 3 09:47: 3 09:48: 3 09:49: 3 09:50: 3 09:51: 3 09:52: 3 09:53: 3 09:54: 3 09:55: 3 09:56: 3 09:57: 3 09:58: 3 09:59: 3 10: 0:03 10: 1:03 10: 2:03 10: 3:03 10: 4:03 10: 5:03 10: 6:03

Depth to Water

(feet)

167.05 166.95 166.89 166.85 166.83 166.81 166.79 166.75 166.65 166.57 166.54 166.46 166.43 166.40 166.35 166.34 166.33 166.26 166.22 166.20 166.18 166.14 166.12 166.09 166.07 166.03

5X

Time

10: 7:03 10:10:03 10:11:03 10:12:03 10:13:03 10:14:03 10:15:03 10:16:03 10:17:03 10:18:03 10:19:03 10:20:03 10:21:03 10:22:03 10:23:03 10:24:03 10:25:03 10:26:03 10:27:03 10:28:03 10:29:03 10:30:03 10:31:03 10:32:03 10:33:03 10:34:03 10:35:03 10:36:03 10:37:03 10:39:03 10:40:03 10:41:03 10:42:03 10:43:03 10:44:03 10:45:03 10:46:03 10:47:03 10:48:03 10:49:03 10:50:03 10:51:03 10:52:03 10:53:03 10:54:03 10:56:03 10:58:03 11: 0:03 11: 2:03 11: 4:03

Depth to Water (feet)

165.97 165.82 165.75 165.70 165.67 165.65 165.62 165.58 165.54 165.52 165.52 165.51 165.46 165.41 165.38 165.36 165.32 165.29 165.27 165.25 165.23 165.21 165.18 165.15 165.13 165.10 165.08 165.05 165.03 164.99 164.96 164.94 164.92 164.90 164.88 164.86 164.83 164.81 164.78 164.77 164.74 164.73 164.71 164.69 164.67 164.64 164.60 164.57 164.53 164.50

Contractor's Contractor's Contractor's

Contractor's

sounder reading: 161. 44 sounder reading: 161.41 sounder reading: 161.38

sounder reading: 161. 32

, 345X ."

Time

11: 6:03 11: 8:03 11:10:03 11:12:03 11:18:03 11:23:03 11:28:03 11:33:03 11:38:03 11:43:03 11:48:03 12:12:03 13:13:03 13:35:03 14:22:03 14:44:03 15: 5:03

7/31/98 Friday 8: 0: 00

12: 0:00 15: 0:00

Depth to Water

(feet)

164.45 164.43 164.40 164.36 164.24 164.19 164.11 164.04 163.98 163.90 163.85 163.53 162.92 162.70 162.33 162.16 162.01

157.86 157.30 156.86

Contractor's Contractor's Contractor's

Contractor's Contractor's Contractor's Contractor's

sounder reading: 161.29 sounder reading: 161. 25 sounder reading: 161. 21

sounder reading: 161.08 sounder reading: 161.02 sounder reading: 160.97 sounder reading: 160.89

r' SE~ BY:COUNTY OF KAUAI ; 3- 8-99 ; 9:42AM DEPT, OF WATER'" 808 587 0283;# 1

DEPARTMENT OF WATER COUNTY OF KAUAI

LIHUE. tiAWAlI 96768-:17015

Fsai.mils ua!umittal PB!Jf1

Pl&a&& dalivar the followin~ pa~ss to:

Name: M ~,Lc..'1=O>tCr H-, '"=, .:-~ Company:

From:

Date: r 1 Time:

Me:5:5age: ~,f, ~ L.J~U ~'-"lj!lLt:;. __ , ~ro,,'j.,· 'PI ~t... !be.,.t.4 & ~~"vt ~f""·"'.2 .s;~ ~,I .... Y~ '''''''"'' +k t-o~'" .,ka.G,+' o~ /5 '2. ~"r.tI~f~ (,Ar~c .. ,,," __ "4"..,.~'1t!. ~

L'$~"''1t1V' ;, ~~" is/ ","-",,)

Total number of pages (including transmi tta,l page): ~

I£ yOU do not receive all ol the ~age~ legibly, please ~all b~ck

.' at (808) 245-.?f+'i .

S~nding Fac:!Iimile Numb.er~

Calling Fac:!Iimile Number:

r = •

(808) 246::-5813

(_) ~ 7 - Da,. ~~

/

. ... __ ._ .................. _----- .---~--......... --....... -..... -.......... _ .

.. SE~l BY:COUNTY OF KAUAI ; 3- 8-99 ; 9:42AM DEPT. OF WATER-I 808 587 0283;# 2

Sb.(e of H~Wdii ,; COMMISSION ON WATER RESOURCE MANAGEMENT Department of Land and Natural Resourc~~

,j

o WELL COMPLETION REPORT Cc?~. ~c:P 4f25197 WCR Form

c- ..-A. .'. ." (Chedc Appropr1ate Box), Cl Well Construction [J (Permanent) Pump Installatl9h ~\., ,..0 c: ' ••

InstructIons: Pleue print or type and submit complated report within 30 days aiter welt completion to lha;Cptnmi:osioitf!' Waler Resource Management. P.O. Box 621, Honolulu. Hawaii 98809. An is·bulit dnlwing Of. th& well and chamiClilI anii~S!S'$htl. uld iliso b~ ,sUbmitted For a~&istllnce call the Commlll:lion Re ullllion Branch at 587·0225. or 1·800-4684644 extension 70225. ...:: •. ,.0\ Y.. .

, . 2.

St.te Well No.: 0023:02 Well Name: .... P ..... u .... k .... a~kir--___ ~ __ Location/Address: -IIL~J.u.h::al.uelt....l:B~a"-,,ILLlnu... __________ ~ __ _

0\,·-:,. Isl~"",~,"",i! .... u ..... a ..... i ____ _

Tax Map Key:-,,3~ ..... 8-.... 2 ..... ;2 ___ ~_

I

3. Drilling Company: ni«AOW Offli.lld;; ~;KC' ct<i;;'l~; v .. c 4. Name of driller who performed work: r-::- t..cc /r,u.ltr-H (:'/'!. 5. Type of rig/construction: 'Mz.,.....crP,-;;t Arf 8',<'M k'",<.......,..., H.,;;>~a 6/(('1',tI.~,£"~: 6, Date(s) Well Construction and pump tests (If any) completed: 7/3",1..9.5 7. GROUND ELEVATION (referenced to mean sea level, msl): ft.

Well Bench ~ark (description/location): Elevation(msl): ___ ft. 8. DRILLER.·S LOG: Pleas8 attach geologic log (If BvailabJ8 or if required by permit)

Depths (ft.) Rock Description, Water Level. Dstes, etc. Depths (ft.) Roel< Description. Water Level. Dates, etc.

~ to ~ ~p £) t &7 ...s:...a:.. to ~ ..&.£ew ....... ~<ftprd€R@ Mq/[ ~ to ~ tr"".r<J 7'-"1 t;!.¢-#7vc' 0Ji,I:2 ~ to ~ 6?C-4? M( '" L2

(If mors specs ;s nfifJdad, CO(ltinue on back.)

9. Total dept" of well below ground: 810 ' ft. 10. Hole size: 2.{, inch dia. from .s'-"~,f;B( f ft. to 43 ft. below ground

it 2. inch dla. from 4.3 ft. to ~",-8,-,/.....:l...::? ___ ft. below ground ______ inch dis. from . ft. to ft. below ground

11. Casing Installed: J 2 In. I. O. x 3k In. wall solid section to . q 95ft. below ground _~ __ In. 1.0. x ____ In. wall perforated section to ft. below ground

Casing Material/Slot Size: ______ ~~ ___ _

12. Annulus: Grouted from S ... I E A <,:S ft. below ground to _ ..... l .... · ~ ... >~.~.L.c)' __ ft. below ground

13, 14. 15. 16.

Gravel ,packed from ft. below ground to ft. below ground

Initial water level: 9/,.83 ft. below ground, Date and time of measurement: "7/J /tJ,~ 12.4 0 "" I Initial chloride: ;,'. ;,;,;.". •. ppm Date and time of sampling: _________ _

Initial temperature: "F Date and time of measurement: __ :--__ - __ PUMPING TESTS; Reference Point (RP.) used: G Ro Jer,) f..€\;€ L, which elevation is ft. (1) Step-Drawdown Test Date ?/IJjr?5 (2) Long·term Aquifer Test Date 4%?'~ 11..,;.'

Start water' level (I J. Soft. below R.P. Start water level C(4" 71(" ft. below R,P. End water level 3 7(:. 88 ft. below RP. End wOlter level .3 2.1. 17 ft. below R.P . •

17. Aquifer Pump Test Procedures data & graphs (1.19196 LTAT Form) attached? _ Yes _ No 18. As-built drawings attached attached? _ Yes _ No 19. Other remat1<slcomrnents: (On back of this form)

::~~~;:ng ~ontractor (print) 41~~.~~~~~U,r:;:o. ~~~i!"--~~. :9~~:""/~~~.~\_---- C-57 Lie:a~~ -_/",";/_9l....e

"-/ l .... ;.L.~,J..~:..~--... ------

Surveyor (print) _..!JirylllQl;l.Cau]:lJdL....L.C,fIC?'IfjS'II..I!QQCI""'--_-____ _

Signature

Applicant (print)

Signature

See attached Lie. No. -...IIi41o,;13~3 .. 2---------

Date _ ..... Fer..:o:.:;b~:r:u~a~l;Y"-211iL6:au..., -'1 ..... 99""""9~ __ _

Date

~SEN~ BY:COUNTY OF KAUAI i 3- 8-99 9:43AM DEPT. OF WATER'"

Bench Mark Elevation = 345.88 Northeast Cort?er Box Cut

<::]

4 -~

~ -<1

LI <::]

(i

~ <1

..a 'L1 :.0 -~

<J

New Hell 5' x 51 Conc.rete Slab

~

q

'Ll' : <J

.~ ~G. DorL,?,.() 7..-

808 587 0283i# 3

4

THIS JI'{OR~ HAS PREPARED 8'r' ME OR IJNJ':/£R MY' DlteEGT ~RVI::;IOH NEH PUKAKI HELL

Febrl.lary 26, It:fqCJ

KODANI AND AS50C/A TES, INC . . . _----_._----

l ,"""" ~

DEPARTMENT OF WATER COUNTY OF KAUAI

4398 PUA LOKE STREET P. O. BOX 1706

LIHUE, KAUAI, HAWAII 96766 PHONE: 808-245-5400 FAX: 808-245-5813

DATE: April 8, 1998

TO:

Ms. Lenore Nakama

'tT>,' ~;;~':)'.'

Dept. of Land & Natural Resources - COWRM

,. ~~ ~ .

JOB NO.:

LETTER OF TRANSMITTAL

96-1 & 96-2

RE: Drill & Test Pukaki and Hanamaulu Well #3, Hanamaulu, Kauai

We are sending you X attached: ___ under separate cover via: ___ the following items:

1 Well Construction Permit for Pukaki Well

1 Well Construction Permit for Hanamaulu Well #3

These are transmitted as checked below:

REMARKS:

D for approval

D for approval and signature

D foryouruse

D for review and comment

D approved as submitted

[XJ as requested

D returned for corrections

D other (see remarks below)

If you have any questions, please call Keith Fujimoto at (808) 245-5449.

COPIES TO: Dennis Alkire, Kauai County Housing Agency, w/o enclosures Lee Mueller, Rainbow Drilling Specialists, Inc., w/o enclosures

C:\ .. lJynn\transltr.dot

SIGNEIF £;\:::s~tJ~ Ernest Y. W OLau:anaier & Chief Engineer

If enclosures are not as noted, kindly notify us at once.

\

/

{,

.~ELL CONSTRUCTION PERMIT~ ~ ......

Pukaki Well, Well No. 0023-02 In accordance with Department of land and Natural Resources, Commission on Water Resource Management's Administrative Rules, Section 13-168, entitled 'Water Use, Wells, and Stream Diversion Works", this document permits the construction and testing of Pukaki Well (Well No. 0023-02) at Lihue Basin, Kauai, TMK 3-8-2:2, subject to the Hawaii Well Construction & Pump Installation Standards (1/23/97) which include but are not limited to the following conditions:

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

The Chairperson of the Commission on Water Resource Management (Commission), P.O. Box 621, Honolulu, HI 96809, shall be notified, in writing, at least two (2) weeks before any work authorized by this permit commences.

The well construction permit shall be for construction and testing of the well only. A minimum one-inch diameter monitor tube shall be permanently installed, in a manner acceptable to the Chairperson, to accurately record water levels. The permittee shall coordinate with the Chairperson and conduct a pumping test in accordance with the Standards (a pump testing worksheet is attached). The permittee shall submit to the Chairperson the test results as a basis for supporting an application to install a permanent pump and withdraw water for use. No permanent pump may be installed until a pump installation permit is approved and issued by the Chairperson.

In basal ground water, the depth of the well may not exceed one-fourth (1/4) of the theoretical thickness (41 times initial head) of the basal ground water unless otherwise authorized by the Chairperson.

The permittee shall incorporate mitigation measures to prevent construction debris from entering the aquatic environment, to schedule work to avoid periods of high rainfall, and to revegetate any cleared areas as soon as possible.

In the event that subsurface cultural remains such as artifacts, burials or concentrations of shells or charcoal are encountered during construction, the permittee shall stop work and contact the Department's Historic Preservation Division (587-0045) immediately.

The proposed well construction shall not adversely affect existing or future legal uses of water in the area, including any surface water or established instream flow standards. This permit or the authorization to construct the well shall not constitute a determination of correlative water rights.

The following shall be submitted to the Chairperson within sixty (60) days after completion of work: " a. Well completion report, (attached - Part I, Well Construction Report).

b. Elevation (referenced to mean sea level, msl) survey by a Hawaii-licensed surveyor. c. As-built sectional drawing of the well. d. Plot plan and map showing the exact location of the well. e. Complete pumping test records, including time, pumping rate, drawdown, chloride content, and other data.

The permittee shall comply with all applicable laws, rules, and ordinances, and non-compliance may be grounds for rev0<ctlpn of this permit.

The well construction permit application is incorporated into this permit by reference and is subject to the ~eIDWell Ccfn;truction ~ump Installation Standards (1123/97). ;;'.~ .-' ~ -\'\

" -;.1') The permit may be revoked if work is not started within six (6) months after the date of approval or if work is ~ended o~andone¢lfor six (6) months, unless otherwise specified. The work proposed in the well construction permit application shaJI:!iEr~omplete~ithin two-~2) years from the date of permit approval, unless otherwise specified, The permit may be extended by the Chairperson'JJpon a showing of g60d cause and good-faith performance. A request to extend the permit shall be submitted to the Chairperson no latet-than three (~onths prior to the date the permit expires. If the commencement date is not met, the Commission may revoke the permit aftergivip.g the p~ee notice of the proposed action and an opportunity to be heard. : ,~, ••

If the well is not to be used it must be properly capped. If the well is to be abandoned then the permittee must apPlY1o-ia well a_donment permit in accordance with § 13-168-12(f) prior to any well sealing or plugging work. ie,' \ .' c:::>

12. Special conditions in the attached cover transmittal letter are incorporated herein by reference.

Date of Approval: July 21, 1997 in .l-.1~Chalrperson Expiration Date: July 21, 199~ '\ O· ~ommlsslon on Water Resource Management

I have read the conditions and terms of this permit and understand them. I accept and agree to meet these conditions as a prerequisite and underlying condition of my ability to proceed. I also understand that non-compliance with any permit condition may be grounds for revocation nd fines of up to $1000 per day.

Permittee's Signature::===~~~~~~~~~ _______ _ Date: ____ _

Printed Name: W. Firm or Title:Manager & Chief Engineer

/

Drille(s Signature: 4~ ~ 7 License #: C'iii!: Date: ~ f<9' Printed Name: e U=-c Afve.:ac'€ Firm or Title:/. '6'~ JU/~

, ··VG~/A~/S7~ /.N'C Please sign both copies of this permit, return one to the Chairperson, and remm the other for your records.

Attachment c: USGS

Department of Healthl Safe Drinking Water, Wastewater, and Clean Water Branches Robert Vorfeld, Lihue Plantation Co.

· \

BENJAMIN J. CAYETANO GOVERNOR Of ..... WAII

o o

STATE OF HAWAII DEPARTMENT OF LAND AND NATURAL RESOURCES

COMMISSION ON WATER RESOURCE MANAGEMENT P. D. BOX 1121

Mr. Ernest Y.W. Lau Manager and Chief Engineer Kauai Department of Water P.O. Box 1706 Lihue, ill 96766

Dear Mr. Lau:

HONOLULU. HAWAII 911809

APR 20 IS98

MICHAa D. WILSON CIWlftASON

ROBERT G. GIRALD DAVID A. NOBRIGA LAWRENCE H. MilKE

RICHARD H. COX HERBERT M. RICHARDS. JR.

EDWIN T. SAKODA ACTING OEPIITY DIRECTOR

Thank you for your letter of April 6, 1998, notifying us of the approximate date on which drilling of Well Nos. 0023-02 & 0124-02 will proceed. Please do not forget to return a signed copy of the permits, showing both your signature and your drilling contractor's signature, to validate the permits.

LN:ss

Sincerely,

(ILJ:I;J JJ4 f i,-EDWIN T. SAKODA Acting Deputy Director

~PARTMENT OF WArtR County of Kauai PErr:·,;,'r- ~,

"Water has no Substitute -- Conserve It!"

April 6, 1998

Ms. Lenore Nakama Dept of Land & Natural Resources - COWRM P.O. Box 621 Honolulu, HI 96809

Dear Lenore:

("'. (,,'

\f\..

r"··-r ."

SUBJECT: Job No. 96-1, Drill & Test Pukaki Well (Well No. 0023-02), and Job No. 96-2, Drill & Test Hanamaulu Well #3 (Well No. 0124-02)

As requested, we are notifying you that the County of Kauai has awarded the contracts for these projects to Ra~1:>0w DrillingSpecia1is~, Inc.

We anticipate issuance of a notice to proceed on April 8, 1998. The contractor has indicated that they will start actual drilling within a week of that date.

If you have further questions, please call Keith FujimOto at (808) 245-5449.

Sincerely,

~k~~_, W' EmestY. W. La;U ~ U Manager and Chief Engineer

KF:ls C:\ .. \ls\96-1&2doc

- 4398 Pua Loke Street, Lihue, Kauai, Hawaii or P. O. Box 1706, Lihue, HI 96766·5706-Phone No. (808) 245-5400 - Administration FAX No. (808) 246·8628 - Engineering/Fiscal/Shop FAX No. (808) 245·5813

/

..

,-

MEMORANDUM FOR THE RECORD

SUBJECT: Start Dates for Hanamaulu, Pukaki, and Kilauea Wells, Kauai DWS

FROM: Lenore Nakama

Keith Fujimoto of Kauai DWS called 4/3/98. They will be starting contruction of Hanamaulu No. 3 (0124-02) and Pukaki Wells (0023-02) in about a week. They will be submitting request to extend start date for Kilauea Well (1125-03). Also reminded him to return signed copies of the pennits ASAP. Bill Eddy said that, re: Hanamaulu No.2 (5923-09), they decided not to deepen and will leave as is. They will be submitting WCR1 shortly.

/

BENJAMIN J. CAYETANO GOVERNOR Of HAWAII

MICHAEl D. WIlSON CHAIRPERSON

ROBERT G. GIRAlD DAVID A. NOBRIGA LAWRENCE H. MilKE

STATE OF HAWAII RICHARD H. COX

HERBERT M. RICHARDS, JR.

DEPARTMENT OF LAND AND NATURAL RESOURCES COMMISSION ON WATER RESOURCE MANAGEMENT

P. O. BOX 621

RAE M. LOUI, P.E.

Mr. Ernest Y.W. Lau Manager and Chief Engineer Kauai Department of Water P.O. Box 1706 Lihue, ill 96766

Dear Mr. Lau:

HONOLULU, HAWAII 96809

OCT 28 1997

This is in response to your letter of October 14, 1997, requesting a three-month extension of the start of construction date for the following well projects:

Job No. 96-1 - Pukaki Well (Well No. 0023-02) ( Job No. 96-2 - Hanamaulu Well #3 (Well No. 0124-02) I

Job No. 91-8 - Kilauea Well #3 (Well No. 1125-03) "

By this letter, your request is approved. However, please do not overlook the July 21, 1999 expiration date of your well construction permits. Pursuant to Condition 10, a request to extend the expiration dates must be made at least three (3) months in advance and must be supported by evidence of good cause and good faith performance.

We sincerely appreciate your attention to the conditions of the well construction permits. If you have any questions, please contact Lenore Nakama at 587-0218 or toll-free at 274-3141 (Kauai), extension 70218.

LN:ss

Sincerely,

RAE M. LOrn Deputy Director

DEPUTY

&PARTMENT OF WAitR County of Kauai

"Water has no Substitute -- Conserve It!"

October 14, 1997

Commission on Water Resource Management

P.O. Box 621 Honolulu, HI 96809

Gentlemen:

97 OCT 17

Subject: Job No. 96-1 - Drill and Test Pukaki Well (Well No. 0023-02)

Job No. 96-2 - Drill and Test Hanamaulu Well (Well No. 0124-02)

Job No. 91-8 - Drill and Test Kilauea Well #3 (Well No. 1125-03)

#3

The well construction permits for these projects specifies the start of construction to begin within six months of the issuance of the permits, which were approved on July 21, 1997, making the start of construction date January 21, 1998.

We are finalizing the bid specs; however, we may not be able to meet these deadlines. Therefore, in compliance with your requirements, we would like to extend the start of construction due date for an additional three months.

If there are any questions, please call Keith Fujimoto at 245-5449.

Sincerely,

Ernest Y.W. Lau Manager and Chief Engineer

KF:et Lihue3/COWRM,emi

-- 4398 Pua Loke Street, Lihue, Kauai, Hawaii or P. O. Box 1706, Lihue, HI 96766·5706---Phone No. (808) 245-5400 - Administration FAX No. (808) 246-8628 -- Engineering/Fiscal/Shop FAX No. (808) 245-5813

BENJAMIN J. CAYETA. ... O GOVERNOR OF HAw ....

MICHAEL D MLSON CHAJRPER3CN

ROBERT G5IRALD DAVID A. NOeRIGA

LAWRENCE ... MilKE

STATE OF HAWAII RICHARD -. COX

HERBERT M. RICHARDS. JR.

REF:CWRM-SS DEPARTMENT OF LAND AND NATURAL RESOURCES

COMMISSION ON WATER RESOURCE MANAGEMENT P. O. BOX 621

RAE M. L().;I, P.E.

Mr. Ernest Lau Kauai Department of Water P.O. Box 1706 Lihue, Hawaii 96766-5706

Dear Mr. Lau:

HONOLULU, HAWAII 96809

JUL 23 1997

Well Construction Permit Pukaki (Well No. 0023-02)

Enclosed are two (2) copies of your approved Well Construction Permit for the captioned well(s) which authorizes well construction activities but excludes installation work for your permanent pump. As part of the Chairperson's approval, the following special conditions were added and are part of your permit under Permit Condition 12:

Special Conditions

1. The well shall be cased with new steel casing confonning to one of the manufacturing standards listed in Hawaii Well Construction and Pump Installation Standards (January, 1997) and in the standards of AWWA publication ANSUAWWA A100-90, as may be amended. The physical properties of the steel shall confonn to ASTM A-242, ASTM A53, Type E or S, Grade B, or approved equal. The well casing shall be manufactured in accordance with applicable sections of ASTM A139, as may be amended.

This permit does not authorize work for your permanent pump installation. Approval and issuance of your pump installation permit is contingent upon completed application and information provided to and accepted by Commission staff as required in the Well Construction & Pump Installation Standards (1123/97) and any special conditions performed under this permit. Please note that special conditions may simply highlight application deviations from the Standards.

The well owner is responsible for all conditions of the permit. This includes ensuring that the well construction contractor, or other party who constructs the well(s), submits a completed Part I of the Well Completion Report fonn (enclosed) within sixty (60) days after the well construction work is completed. Be advised that you may be subject to fmes of up to $1000 per day for any violations of your permit conditions.

To validate your permit, please sign and have the contractor sign both permit originals and return one for our files. Also, copies of the aquifer pump test worksheet and the well completion report form are enclosed for your use. Please provide all the infonnation in this packet to your well drilling contractor.

Also attached for your information is a copy of the Department of Health's review comments.

OEP\.,-'

If you have any questions, please call the Commission staff at 587-0218 or toll-free at 274-3141, extension 70218.

Enclosures

Aloha,

-1-rv ICHAEL D. WILSON o r - Chairperson

o WELL CONSTRUCTION PERMIO

Pukaki Well. Well No. 0023-02 In accordance with Department of Land and Natural Resources, Commission on Water Resource Management's Administrative Rules, Section 13-168, entitled 'Water Use, Wells, and Stream Diversion Works", this document pennits the construction and testing of Pukaki Well (Well No. 0023~2) at Lihue Basin, Kaual, TMK 3-8-2:2, subject to the Hawaii Well Construction & Pump Installation Standards (1123197) which include but are not limited to the following conditions:

1. The Chairperson of the Convnission on Water Resource Management (Commission), P.O. Box 621, Honolulu, HI 96809, shall be notified, in writing, at least two (2) weeks before any work authorized by this pennit commences.

2. The well construction permi shan be for construction and testing of the well only. A minimum one-inch diameter monitor tube shall be pennanently installed, in a manner acceptable to the Chairperson, to accurately record water levels. The pennittee shall coordinate with the Chairperson and conduct a pumping test in accordance with the Standards (a pump testing worksheet is attached). The pennittee shall submit to the Chairperson the test results as a basis for supporting an application to install a pennanent pump and withdraw water for use. No pennanent pump may be installed until a pump instaDation pennit is approved and issued by the Chairperson.

3. In basal ground water, the depth of the well may not exceed one-fourth (114) ofthe theoretical thickness (41 times initial head) ofthe basal ground water unless otherwise authorized by the Chairperson.

4. The pennittee shall incorporate mitigation measures to prevent construction debris from entering the aquatic environment, to schedule work to avoid periods of high rainfall, and to revegetate any cleared areas as soon as possible.

5. In the event that subsurface cultural remains such as artifacts, burials or concentrations of shells or charcoal are encountered during construction, the pennittee shall stop work and contact the Department's Historic Preservation Division (587-0045) immediately.

6. The proposed well construction shall not adversely affect existing or future legal uses of water in the area, inck/ding any surface water or established instream flow standards. This pennit or the authorization to construct the well shall not constitute a detennination of correlative water rights.

7. The following shall be submitted to the Chairperson within sixty (60) days after completion of work: a. Well completion report, (attached - Part I, Well Construction Report). b. Elevation (referenced to mean sea level, msl) survey by a Hawaii-licensed surveyor. c. As-built sectional drawing of the well. d. Plot plan and map showing the exact location of the well. e. Complete pumping test records, including time, pumping rate, drawdown, chloride content, and other data.

8. The permittee shall comply with all applicable laws, rules, and ordinances, and non-compliance may be grounds for revocation of this permit.

9. The well construction permi application is incorporated into this pennit by reference and is subject to the Hawai Well Construction & Pump Installation Standards (1123197).

10. The permit may be revoked if work is not started within six (6) months after the date of approval or if work is suspended or abandoned for six (6) months, unless otherwise specified. The work proposed in the well construction pennit application shaD be completed within two (2) years from the date of permi approval, unless otherwise specified. The pennit may be extended by the Chairperson upon a showing of good cause and good-faith performance. A request to extend the permit shan be submitted to the Chairperson no later than three (3) months prior to the date the pennit expires. If the commencement date is not met, the Commission may revoke the pennit after giving the permittee notice of the proposed action and an opportunity to be heard.

11. If the well is not to be used i must be properly capped. If the well is to be abandoned then the pennittee must apply for a well abandonment permit in accordance with §13-168-12(f) prior to any well seating or plugging work.

12. Special conditions in the attached cover transmittal letter are incorporated herein by reference.

Oat. of Approval: July 21, 1997 ~ ~. Chairperson Expiration Date: July 21, 1997 a' - ommission on Water Resource Management

I have read the conditions and terms of this permit and understand them. I accept and agree to meet these conditions as a prerequisite and undertying condition of my ability to proceed. I also understand that non~mpliance with any permit condition may be grounds for revocation and fines of up to $1000 per day.

Permittee's Signature: ________________ _ Date: ____ _

Printed Name: Firm or Title: ___________ _

Driller's Signature: License #: ------ Date: ____ _

Printed Name: Firm or Title: ___________ _

Please sign both copies of this permit, return one to the Chairperson, and retain the other for your records.

Attachment c: USGS

Department of Health! Safe Drinking Water, Wastewater, and Clean Water Branches Robert Vorfeld, Lihue Plantation Co.

--~--~5~3~O~OOO~FE~E~T~~-L--~~~~~~~~~~~~~--~-~'--~~-"-~~-~-~~~"~~----'1

'::: :ed and 24hed by the Geological Survey ~, _ S~S and USC&GS

: -. :! :~o'ogrammetric methods from aerial -~-; :3''=~ 1960-61. Field checked 1963

- ":-:~'a:hlc data compiled from USC&GS Chart 4100 (1959) --,-:- :; ">ot intended for navigational purposes

:-: ~:- ':~_ Old HawaIIan datum _:- ~- : :ased on Hawaii coordinate system, zone 4

_ - -'0',031 Transverse Mercator grid ticks, ~~.- - :.' .... e

"-".- -'!s Indicate selected fence lines

-10

23

APPROXIMATE MfAN DECLINATION, i963

22 lOt\)

f-3

tJEP1H

FOR SALE BY l A FOLDI

Well No.

Well Name

Applicant

0023-02

Pukaki

Kauai DWS

SECTION 1: WELL LOCATION INFORMATION

Island

Aquifer System

Aquifer Sector

KAUAI

LIHUE

HANAMAULU

data

Date of Review

Reviewer

7/18/97 -----------L-N ------------

Proposed Use

Proposed Withdrawal

System Sustainable Yield

Municipal

1000000 ---~---- --------

40

SECTION 2: WELL SECTION DATA (enter data in grey cells only)

Elevation at top of casing

Ground Elevation

Cement Grout

Rock Packing

Hole Diameter

Total Depth

Estimated Head

Calculated Aquifer Thickness

County Water Supply (YIN ?)

ft., m.s.1.

6027 ft.

Solid Casing

Material

Designation

Length

Diameter

Wall Thickness

Casing

Material

Designation

Length

Diameter

Wall Thickness

Openings

Open Hole

Length

Diameter

SECTION 3: CHECKLIST (values to check are shaded)

Well Depth

Theoretical Thickness of Aquifer

1/4 Aquifer Thickness

Depth of Well below Sea Level

Well Casing

Minimum Wall Thickness

Material County or Non-County

Minimum Thickness per standards

Wall Thickness Provided

Minimum Length of Solid Casing

90% of ground to top of aquifer

Length of solid casing Provided

Casing Material

Annular Space

Depth of Grouting

Calculated Depth of Grouting

Depth of Grouting provided

Thickness of Annular Space

Steel

county

6027 ft. 1507 ft. 458 ft. okay (refer to HWCPIS Section 2.2)

0.365 in_

0.375 in. okay (refer to HWCPIS Section 2.4 c)

175.5 ft. 390 ft. okay (refer to HWCPIS Section 2.4 d)

##### ##### (refer to HWCPIS Section 2.4 e)

If the cell above reads #N/A, reference HWCPIS)

136.5 ft. 162 ft. okay (refer to HWCPIS Section 2.6 c)

4 in. okay (refer to HWCPIS Section 2.6 d)

Page 1

o o ~!y~

~ MICHAEl D. WILSON BENJAMIN J. CAYETANO GOVERNOR OF HAWAII CHAIRPERSON

ROBERT G. GIRAI.O DAVID A. NOBRIGA

LAWRENCE H. MilKE

STATE OF HAWAII RICHARD H. COX

HERBERT M. RICHARDS. JR.

DEPARTMENT OF LAND AND NATURAL RESOURCES

COMMISSION ON WATER RESOURCE MANAGEMENT P. O. BOX 621

RAE M. lOUI, P.E. DEPUTY

HONOLULU, HAWAII 96809

JUt~ 23 \997

::0("51 ~

TO: Honorable Lawrence Miike, Director [;;0' -J 0::-

~ Department of Health ~; ::~ Attention: Dennis Tulang, Wastewater Branch .... '~:J. (.....-9

William Wong, Safe Drinking Water Branch ~~~;2 ,.""'"'"1 en

Danis Lau, Clean Wab~r Branch -:c'-,~ ~:~ '~ .... ~

~Chael D. Wilson, Chairperson 1.:'~ :-",:!,. "0

FROM: (.,).~ NI Commission on Water Resour Management ~ -,£; ..

rn;rl SUBJECT: Well Construction/Pump Installation Permit Application for Pukaki (\I\le1I::No. 0022:92)

Transmitted for your review and comment is a copy of the captioned well application.

We would appreciate your comments on the captioned application for any conflicts or inconsistencies with the programs, plans, and objectives specific to your department. Please respond by returning this cover memo form by July 15, 1997.

Please find a map, attached, to locate the proposed well. If you have any questions about this permit application, request additional information, or request additional review time, please contact Lenore Nakama of the Commission staff at 587-0218.

LN:ss Attachment(s)

RESPONSE:

[ I

[ I

[ I

[ I

[ I

This well qualifIeS as a source which will serve as a source of potable water to a public water system (serving 25 or more people at least 60 days per year or has 15 or more service connections) and must receive Director of Health approval plio; to its use to comply with Hawaii Administrative Rules (HAR) , Title 11, Chopter 20, Rules Relating to Potable Water Systems, §11-20-__ Q.

This well does not qualify as a source serving a public water system (serves less than 25 people or more people at least 60 days per year or 15 service connections) and if the well water is used for drinking, the private owner should test for bacteriological and chemical presence before initiating such use and routinely monitor the water quality thereafter. However, if Mure planned use from this source increases to meet the public water system definition then Director of Health approval is required prior to implementation.

If the well is used to supply both potable and non-potable purposes in a single system, the user shall eliminate cross-connections and backflow connections by physically separating potable and non-potable systems by an air gap or an approved backflow preventer, and by clearly labeling all non-potable spigots with warning signs to prevent inadvertent consumption of non-potable water. Backflow prevention devices should be routinely inspected and tested.

It does not appear that this well will be used for consumptive purposes and is not subject to Safe Drinking Water Regulations.

For the applicant's information, a source of possible wastewater contamination [Jis [J Is not located near the proposed well site (information attached).

Other relevant DOH rules/regulations, information, or recommendations are attached.

No comments/objections

Contact Person: kc vi N. f.&i vva~ Phone: __ C) __ B __ h __ L{ __ JU1~~ ____ ____

Signed: G<i0 b. ~) Date: _{fJ+-( 0_0 ...... 1 ........ 1-..&.1 __

;:0 m ("

.if

.< :"1l 0

c o 8FU\NCH

BENJAMIN J. CAYETANO GOVERNOR OF HAWAII

MICHAEL D. WILSON CHAIRPERSON

ROBERT G. GIRALD DAVID A. NOBRIGA

LAWRENCE H. MilKE

STATE OF HAWAII RICHARD H. COX

HERBERT M. RICHARDS. JR.

DEPARTMENT OF LAND AND NATURAL RESOURCES COMMISSION ON WATER RESOURCE MANAGEMENT

P. O. BOX 621

RAE M. LOUI. P.E. DEPUTY

HONOLULU. HAWAII 96809

JUN 23 \997

TO: Honorable Lawrence Miike, Director Department of Health .<

FROM:

Attention: Dennis Tulang, Wastewater Branch William Wong, Safe Drinking Water Branch Denis Lau, Clean Water Branch

~chael D. Wilson, Chairperson o ~~mmission on Water Resour

..

SUBJECT: Well Construction/Pump Installation Permit Application for Pukaki (Well No. 0023-02)

Transmitted for your review and comment is a copy of the captioned well application.

We would appreciate your comments on the captioned application for any conflicts or inconsistencies with the programs, plans, and objectives specific 'to your department. Please respond by returning this cover memo form by July 15. 1997.

Please find a map, attached, to locate the proposed well. If you have any questions about this permit application, request additional information, or request additional review time, please contact Lenore Nakama of the Commission staff at 587-0218.

LN:ss Attachment( s)

RESPONSE:

)L This well qualiflE!s as a source which will serve as a source of potable water to a public water system (serving 25 or more people at least 60 days per year or has 15 or more service connections) and must receive Director of Health approval ~~or to its use to comply with Hawaii Aaminisiralive Ruies Wu'\R). ,,'lIe 11, Chapter 20, Rules Relating to Potable water Systems. §11- 29.

[ I This well does not qualify as a source serving a public water system (serves less than 25 people or more people at least 60 days per year or 15 service connections) and if the well water is used for dMking. the private owner should test for bacteriological and chemical presence before initiating such use and routinely monitor the water quality thereafter. However. if Mure planned use from this source increases to meet the public water system definition then Director c:A Health approval is required prior to implementation.

[ I If the well is used to supply both potable and non-potable purposes ., a single system. the user shall eliminate cross-connections and backflow connections by physically separating potable and non-potable systems by an air gap Dr an approved backflow preventer. and by clearly labeling all non-potable spigots with warning signs to prevent inadvertent consumption of non-potable water. Backflow prevention devices should be routinely inspected and tested.

[ I It does not appear that this well will be used for consumptive purposes and is not subject to Safe Drinking water Regulations.

[ I For the applicanfs information. a source of possible wastewater contamination []is [ ] is not located near the proposed well site (information attached).

[ I Other relevant DOH rules/regulations. information. or recommendations are attached.

[ I No comments/objections

Contact Person: _..,~~..I,.ofl~IJ:::..;:(j~:....;;.......;;,~.,t:-/ _______ _ 7

Signed:--=lz-L...J.' i.,.;...:...'1~¢--.,;~--,--+-Cj ____ _ I

Phone: _S ...... K'u......;;;.6_q~2...:::..5_ft_

(£; 6 $7 Date:

..

BENJAMIN J. CA YET ANa GOVERHOA ~ HAWAI

c o

STATE OF HAWAII DEPARTMENT OF LAND AND NATURAL RESOURCt:S

COMMISSION ON WATER RESOURCE MANAGEMENT P. o. BOX 821

HONOLULU, HAWAII 96809

JJN 23 1997

MICHAEL O. WILSON OWAP£IISON

ROBERT G. GlRAI.D DAViD .... NOBRIGA

LAWRENCE H. MilKE RICHARD H. COX

HERBERT M. RICHARDS, JR.

RAE M. lOUI, P.E. DEPIITY

Mr, Ernest W. Lau Manager and Chief Engineer Kauai Department of Water P.O. Box 1706 Lihue, HI 96766

Dear Mr. Lau:

Well Construction I Pump Installation Permit Application for Hanamaulu 3 (Well No. 0124-02) Well Construction I Pump Installation Permit Application for Pukaki (Well No. 0023-02)

Well Construction Permit Application for Kilauea Well #3 (Well No. 1125-03) After-the-Fact Pump Installation Permit Application for Koloa E (Well No. 5427-03)

This is in response to your letters of April 25, 1997, May 2, 1997, and May 20, 1997. We have received the subject permit applications. However, your applications are incomplete. Matters which must be addressed before we accept your applications as complete are as follows:

1. Wailua Homesteads Well No.3 (Well No. 0424-01) The Well Construction Permit expired on May 5, 1997 (attached). Please submit the items required under Condition 4 within thirty (30) days of the date of this letter.

2. Anahola Well C (Well No. 0818-03) The Pump Installation Permit expired on February IS, 1997 (attached). Please submit the as-built drawing of the installed pump required under Condition 7 within thirty (30) days of the date of this letter.

3. Haena Well (Well No. 1333-01) The Pump Installation Permit expired on April 6, 1995 (attached). Please submit the Well Completion Report Part n and as-built drawing of the installed pump required under Condition 5 within thirty (30) days of the date of this letter.

4. Puhi Monitor (Well No. 5824-08) Puhi Well No.5 (Well No. 5824-09) The Well Construction Permits expired on January 25, 1997 (attached). Our letter of October 18, 1996 requested the Well Completion Report Part I for Well No. 5824-08 (for the work completed to date) and also reminded you of the expiration date and need to request extension or make new application if both wells cannot be completed by the January 25, 1997 completion deadline (attached). Your letter of April 25, 1997 indicates that construction work on both wells is ongoing. However, because the permits have expired, new applications must be made to complete the wells. Any ongoing construction work is being done in violation of your permit and the State Water Code. You must cease & desist all construction work immediately until new well construction permits are approved. We have enclosed the appropriate application forms. Please submit the items required under Condition 4 for the work that has been completed to date for both Well Nos. 5824-08 & 09 within thirty (30) days of the date of this letter.

Mr. Ernest W. Lau Page 2

J.JN 23 1997

c o

5. Thank you for updating us on the status of the Well Completion Reports for Puhi 5 (Well No. 5824-05) and Puhi 4 (5824-06). We will look forward to receiving the reports.

In anticipation of your submittal of the above items, we have routed the application to the Department of Health for their review and comment. Upon receipt of the items requested above, we will continue to process the subject applications, provided that no subsequent permit violations have occurred. Be advised that failure to comply with the terms and conditions of your permits may result in fines of up to S1000 per day.

We note that you have not yet identified the well drilling contractor or pump installation contractor who will be performing the work. To expedite the process, we will accept your completed application for processing without the contractor's signature; however, we will require your licensed contractor to sign the permit document prior to beginning any well construction or pump installation work.

If you have any questions, please contact Lenore Nakama of the Conunission staff at 587-0218 or toll-free at 274-3141, extension 70218.

LN:ss

Sincerely,

RAEM. LOUI Deputy Director

Attachments (Copy of Well Construction Permit for Well No. 0424-01) (Copy of Pump Installation Permit for Well No. 0818-03) (Copy of Pump Installation Permit for Well No. 1333-01) (Copy of Well Construction Permit for Well No. 5824-08) (Copy of Well Construction Permit for Well No. 5824-09) (Copy of CWRM Letter of October 18, 1997) (Application for Permit, 3 Jan 97 WCPIA Form)

BENJAMIN J. CAYETANO GOVERNOR OF HAWAII

MICHAEL D. WILSON CHAIRPERSON

ROBERT G. GIRALD DAVID A. NOBRIGA

LAWRENCE H. MilKE

STATE OF HAWAII RICHARD H. COX

HERBERT M. RICHARDS. JR.

DEPARTMENT OF LAND AND NATURAL RESOURCES

COMMISSION ON WATER RESOURCE MANAGEMENT P. o. BOX 621

RAE M. LOUI, P.E.

TO:

HONOLULU, HAWAII 96809

JUN 23 1997

Honorable Lawrence Miike, Director Department of Health Attention: Dennis Tulang, Wastewater Branch

William Wong, Safe Drinking Water Branch

FROM: ~ Denis Lau, Clean Water Branch

ichael D. Wilson, Chairperson Commission on Water Resourc

SUBJECT: Well Construction/Pump Installation Permit Application for Pukaki (Well No. 0023-02)

Transmitted for your review and comment is a copy of the captioned well application.

We would appreciate your comments on· the captioned application for any conflicts or inconsistencies with the programs, plans, and objectives specific to your department. Please respond by returning this cover memo form by July 15. 1997.

Please find a map, attached, to locate the proposed well. If you have any questions about this permit application, request additional information, or request additional review time, please contact Lenore Nakama of the Commission staff at 587-0218.

LN:ss Attachment(s)

RESPONSE:

( I This well qualifies as a source which will serve as a source of potable water to a public water system (serving 25 or more people at least 60 days per year or has 15 or more service connections) and must receive Director of Health approval ~S?:f to its use to comply with Hawaii Administrative Rules (HAR) , Tille 11, Chapter 20, Rules Relating to Potable water Systems, §11- 9.

[ I This well does not qualify as a source serving a public water system (serves less than 25 people or more people at least 60 days per year or 15 service connections) and if the well water is used for drinking, the prlVate owner should test for bacteriological and chemical presence before initiating such use and routinely monitor the water quality thereafter. However, if Mure planned use from this source increases to meet the public water system definition then Director of Health approval is required prior to implementation.

( I If the well is used to supply both potable and non-potable purposes in a single system, the user shall eliminate cross-connections and backflow connections by physically separating potable and non-potable systems by an air gap or an approved backnow preventer, and by clearly labeling all non-potable spigots with waming signs to prevent inadvertent consumption of non-potable water. Backnow prevention devices should be routinely inspected and tested.

( I It does not appear that this well will be used for consumptive purposes and is not subject to Safe Drinking Water Regulations.

[ I For the applicanfs information, a source of possible wastewater contamination [lis [ I Is not located near the proposed well site (information attached).

[ I Other relevant DOH rules/regulations, information, or recommendations are attached.

[ I No comments/objections

DEPUTY

Contact Person: ________________ _ Phone: ________ _

Signed: ___________________ _ Date:

WATER RESOORCE ASSOCIATES Hydrology • Geology • Engineering

Ms. Rae Loui, Deputy Director Commission on Water Resource Management Dept. of Land & Natural Resources P.O. Box 621 Honolulu, Hawaii 96809

~ Dear~:

May~19, 1997

Application for Well Construction and Pump Installation Permits, Hanamaulu 3 and Pukaki Wells, Lihue Basin, Kauai

Submitted herewith on behalf of the Kauai Department of Water are applications (original and two copies) for well construction and pump installation permits for two exploratory wells (Hanamaulu 3 and Pukaki) in the Lihue basin, Kauai (TMK 3-8-2:2). The final Environmental Assessment for the two well projects was published in the May 8, 1997 OEQC Bulletin (see attached copy, pg 11).

If you or your staff have any questions or need more information to process the application, please call me. Your earliest consideration will be most appreciated.

Sincerely,

DANLUM

Ene. c: Ernest Lau w/enc.

Stan Young w/enc.

1708 1188 Bishop Street, Suite 669'· Honolulu, Hawaii 96813-3302 • (808) 528-0074 • Fax 528-0808

Final Environmental AssessmentslFindings of No Significant Impacts (FONSI)

e (1) Hanamaulu and Lihue Water Development Projects, Phase I

DiStrict: TMK: Applicant:

Accepting Authority:

Consultant:

Lihue 3-8-02:2 County of Kauai, Department of Water P.O. Box 1706 Lihue, Hawaii 96766 Contact: Keith Fujimoto (245-5449)

County ofKauai, Department of Water P.O. Box 1706 Lihue, Hawaii 96766 Contact: Keith Fujimoto (245-5449) Fukunaga and Associates, Inc. 1388 Kapiolani Boulevard, 2nd Floor Honolulu, Hawaii 96814 Contact: Lynn Katahara (944-1821)

Public Challenge Deadline: June 9,1997 Status: FEAlFONSI issued, project may proceed.

The COUDty ofKauai Department of Water proposes to drill, case, and pump test two exploratory potable water wells, Pukaki Well and Hanamaulu Well No.3, located approxi­mately 3 miles northwest of Lihue. Growth and expansion of the Lihue service area has generated potable water demands that surpassed the capacities of the existing sources. Addi­tionally, existing pumpage has been reduced by more than 20 percent because of the large demands and dropping well water levels. The proposed well sites are situated on Lihue Plantation Company lands that are currently used for sugar cane cultivation. The wells will be approximately 800 feet deep, and will be partially cased with 12-inch diameter steel casing. Each source may yield up to 1 million gallons per day. The estimated cost of each proposed well project is $600,000, and construction of each project is expected to last about 6 months.

1

~ (2) Kauai Set Aside State Land for Passive Park Use Landscaping and Expansion of Nawiliwili Park

District: TMK: Applicant:

Accepting

Lihue 3-2-04:9 and 10 Department of Land and Natural Resources P. O. Box 621 Honolulu, Hawaii 96809 Contact: Gary Martin (587-0414)

Authority: Department of Land and Natural Resources P. O. Box 621 Honolulu, Hawaii 96809 Contact: Gary Martin (587-0414)

Public Challenge Deadline: June 9,1997 Status: FEAJFONSI issued, project may proceed.

The realignment of Waapa and Nawiliwili Roads, where they intersect, by the Department of Transportation, Highways Division resulted in a safer intersection and also several remnant parcels of State land. This action proposes to set aside six remnant parcels to the County of Kauai for passive recreational and landscaping purposes and expansion of the Nawiliwili Park. Other than picnic tables, no structural improvements are anticipated.

\ ... • ~ofHawaii 0

COMMISSION ON WATER RESOURCE MANAGEMENT Deparbnent of Land and Natural Resources

APPLICATION FOR PERMIT n 7 FEB 2 ~ p 5: I 3 gg Well Construction or £J Pump Installation

Instructions: Please print in ink or type, attach required maps, and send the completed application & two (~I copies to the Commission on Water Resource Management, P.O. Box 621, Honolulu, Hawaii 96809. This application must be accompanied 1ij(~.D!l!Hefund~~!e.~IJQg fee of $25.00 payable to the Department of Land and Natural Resources. The Commission may not accept incomplete applications. For assistance in completing this application, please call the Commission's Regulation Branch at 587-0225.

1. APPLICANT: (circle primary contact a, b, or c)

@WELLOWNER FirmlName Kauai Dept of Water

Contact Person Ernest Lau Ph' 245-5400 Address _-.;p...:; • .;.O-=.-=Bo=;;x:........:..1..:..7~06-=-=-=::-::---==~::--__

Lihue, Kauai 96766-5706

(c) CONTRACTOR

Primary Fax: 1-808-245-5813

(b) LANDOWNER

FirmlName Lj bIle pJ antatj on Co Contact Person Robert Vorfe 1 (L Ph' 245- J ~_~!t Address 2970 Kel e st., RCX1JD 203

Lihue, Kauai 96766

FirmlName __ ....::n~o~t=--.:a=-~!!a=l~· l::ab=l::e==--___ --C:P1Lh·~ ____ _ Contractor's License No. Contact Person _________________ _ (Please circle type: C-57, Gen.'C', or C-57a, Gen.'A') Address ____________________ _

2. WELL LOCATION/NAME: Puka1<.i Island Kallaj Address __ ~L=i~h=u=e_Ba==s..:..l..:..·n _____________________________ __ Tax Map Key 3-8-2:2

Attach the relevant portion of (a) a 7.5-Minute Series USGS topographic map (scale 1 "=24,000'), and (b) a property tax map, showing

well location referenced to established property boundaries.

3. (a) PROPOSED WORK: IE Drill New Well D Deepen Kllnstall New Pump

D Modify Pump

4.

D Modify Existing Well D Redrill

D Abandon/Seal' o Replace Pump

• Be sure to complete and submit well abandonment report upon completion of work.

(b) WELL lYPE: DOug 0 Bored D Driven UDrilied D Radial

Is this well a part of a battery of wells? DYes KI No

(Briefly describe and fill in the diagram on the back of this form.)

PROPOSED PUMP INFORMATION: Rated Pump Capacity: --7AO.u.OL--- gallons per minute

Pump Type:

Ii! Deep Well Turbine D Rotary D Propeller

o Submersible D Rotary-Displacement D Reciprocating

Motor:

o Diesel

DGas

o Centrifugal 0 Rotary-Gear 0 Impulse '" Electric, rated horsepower: _____ _

If Pump Replacement, Existing Pump Capacity: __ ~ __ _ gallons per minute

5. PROPOSED USE: IiCJ Municipal (including hotels, stores, etc.) o Industrial

o Domestic (individual, noncommercial water sys.) # Dwelling Units __ _

o Irrigation (crop) # Acres ____ __

o Military DOther: ________ _

6. (a) PROPOSED AMOUNT OF WITHDRAWAL: one million gallons per day

(b) METHOD OF FLOW MEASUREMENT: 6a Flow-meter D Open-pipe D Orifice Plate DWeir

7. PENDING ACTIONS: 0 CDUA o SMA DEIS DEA 13 NONE D Other(explain)

Completion Date:

8. REMARKS, EXPLANATIONS: _______________________ _

(if more space IS needed, continue on baCk)

I understand that approval of this application attaches the following standard conditions: 1) the proposed work is to be completed within two (2) ~1!!2rs "f 'h~ approval date; 2) the c.ontractor shall submit to the Commission a well completion/abandonment report within 30 days after the completion date of the permitted work; 3) monthly water use data shall be submitted to the Commission; 4) such approval shall not constitute a determination of correlative water rights and shall not guarantee the pump capacitY or future use up to the permitted pump capacitY ..

Well Owner Kauai Dept of Water Contractor ________________ _

Signa'Ul~:~i@~ Date .n~-6"

Signature -i='="~--4-:....:..,t.~----:.----Date __ ~_~:L~~~ _____ ___

Signature ________________ _ Date _______________ _

--------------------------------------------------------------------------------. For Official Use Only: Date Received ____________ _ Date Accepted _______ __ Field Checked By ________ _ Date _________ _

Longitude _________ _ Latitude _______ _

Aquifer System Name M~k!AcJ 4 \h..JE State Well No. 002.:2,'0'1..

3 Jan 97 WCPIA Fonn

8. Remarks, Explanations (cont'd): _____________________________ _

9. PROPOSED WELL SECTION

Elevation at top of casing ~ft.,msl.

Cement Grout: 162 ft.

Rock Packing none ft.

Hole Diameter: 20 in.

800 ft Total Depth ____ .

Ground Elevation: 342 ft., msl*

Solid Casing: Material ___ -:S~t~ee~l"----------Length ___ ..... 3L.9~O,:__------- ft. Diameter 1 2 in. Wall thickness 3 /S in.

Casing: 0 Perforated 0 Screen Material none Length _____________ ft.

Diameter in. Wall thickness in. Openings _____ sq. in.Il.F.

Open Hole: Length ___ ~4.,:1_O0~------- ft. Diameter 2 a in.

*Approximate elevation at time of filing application. Ground elevation above mean sea level ems I) by a surveyor licensed by the State must be submitted at start of construction. Final elevations of well components shall be submitted in the well completioniwell abandonment reports .

.. •• I

. .

o

~ o o 00

Water Resource Associates

096PUKP (2/17197)

PUKAKIWELL Lihue Basin, Kauai

:proposed Section

1 ft.

Elev.: + 180 ft.

Elev.: -48 ft.

Elev.: -458 ft.

0 0 0

0 0

0 0

0

0 0

0 0

.0 0 12" 0 0

• 0 0

0 0

0 0

0 0

0 0

0 0

Grd. Elev.: 342 ft. (approx.)

0 0

0

0

Cement-Sand Grout

20" dia. Drill Hole

14-'l'--+--- Solid Steel Casing

.0 0

.0 • 0

0

0 0 0

0 0

,; 0

0 0 0 •• 0 f--- Static W.L., approx. 185' depth

Grout Seal (see detail)

Cement Basket

~- Casing Guide

1--'+-- Casing Shoe

GROUT SEAL DETAIL

Cement-Sand Grout

Not to Scale <i Sand

I

#8 Coarse Aggregate

#67 Coarse Aggregat

97 fEB 2 ~ p 5: I 3

L

ei _, '." ' :_"".