stationary diesel generator / catalytic converter emission control

12
1 Stationary Diesel Generator / Catalytic Converter Emission Control Evaluation Power Systems Division Naval Surface Warfare Center, Crane, IN. Cinergy Ventures, Cincinnati, OH Presenter: Brian Fillingim, NSWC Crane

Upload: vuliem

Post on 01-Jan-2017

229 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Stationary Diesel Generator / Catalytic Converter Emission Control

1

Stationary Diesel Generator / Catalytic Converter Emission

Control Evaluation Power Systems Division

Naval Surface Warfare Center, Crane, IN.

Cinergy Ventures, Cincinnati, OH

Presenter: Brian Fillingim, NSWC Crane

Page 2: Stationary Diesel Generator / Catalytic Converter Emission Control

2

Emission Limitation

• Federal Standards for NonRoad Emission Requirements – Tier I Phase - 1996 to 2000– Tier 2 / Tier 3 Phase - 2000 to 2008– Limited Annual Hours to Remain With In

Air Polution Standards for Total Emissions

Page 3: Stationary Diesel Generator / Catalytic Converter Emission Control

3

Page 4: Stationary Diesel Generator / Catalytic Converter Emission Control

4

Method of Reduction

• Selective Catalytic Reduction (SCR) Process

• Exhaust Catalyst with Anhydrous Ammonia (NH3) Injection “Proof of Concept”

Page 5: Stationary Diesel Generator / Catalytic Converter Emission Control

5

SCR Process

SCR Reaction Chemistry4NO + 4NH3 + O2 = 4N2 + 6H2O 6NO2 + 8NH3 + O2 = 7N2 + 12H2O

High Temp and Excess NH34NH3 + 5O2 = 4NO + 6H2O4NH3 + 3O2 = 2N2 + 6H2O

Page 6: Stationary Diesel Generator / Catalytic Converter Emission Control

6

Test Setup

• Caterpillar Model 3306 Diesel Generator Set - 250 Kilowatt (kW)

•  Catalytic Converter in place of Stock Muffler– Catalyst Design and Formulation by Catalytic

Solutions Inc., Oxnard, CA– Catalyst Housing and Integration by

ArvinMeritor Inc, Columbus, IN• Manual Setting for NH3 Injection Flow

Rate into Engine Exhaust

Page 7: Stationary Diesel Generator / Catalytic Converter Emission Control

7

Caterpillar Model 3306

Page 8: Stationary Diesel Generator / Catalytic Converter Emission Control

8

Muffler vs Catalytic Converter

Page 9: Stationary Diesel Generator / Catalytic Converter Emission Control

9

Test Procedure

• Daily Six to Nine Hour Runs•  Four to Six Samples per Test Run of:

O2, CO, NO, NO2, SO2• Temperature (Pre Converter, Post

Converter, Catalyst and Ambient)• Third Party Verification of Emission

Measurements by GE Energy Serivces Inc

Page 10: Stationary Diesel Generator / Catalytic Converter Emission Control

10

Results • 556 Engine Hours • 476 Hours with NH3 Injection•  Final 350 Hours at 90 percent Load (225

kW) with NH3 Injection•  Maximum NOx Reduction with 13 to 16

standard liters per minute (slpm) NH3 injection (0.8 NH3/NOx) at 90 percent Load

• GE Energy Services Inc. measured Comparable Data and No Indications of Secondary Emissions

Page 11: Stationary Diesel Generator / Catalytic Converter Emission Control

11

Conclusions

• NH3 Injection and Catalyst Combination Reduced NOx by Approximately 90 percent

•  Further Evaluation in Colder Ambient Temperatures Indicated

•  Further Development and Evaluation of NH3 Controllers is Indicated