streamline...538a washing machine 6.0 bels high-wall fan coil 4.7 bels 6.8 bels 7.5 bels one of the...

10
Due to Bryant’s commitment to continuous improvement, specifications are subject to change without notice. © 2002 Bryant Heating & Cooling Systems, Syracuse, NY StreamLine DUCT-FREE SYSTEMS Versatile, efficient cooling and heating – for virtually any room Printed in U.S.A. 8538-003 Heating & Cooling Systems Since 1904 www.bryant.com ®

Upload: others

Post on 24-Jun-2020

14 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: StreamLine...538A Washing machine 6.0 Bels High-Wall Fan Coil 4.7 Bels 6.8 Bels 7.5 Bels One of the primary benefits of Bryant’s duct-free systems, is that they can be installed

Due to Bryant’s commitment to continuous improvement, specifications are subject to change without notice. © 2002 Bryant Heating & Cooling Systems, Syracuse, NY

StreamLineDUCT- FREE SYSTEMS

Versatile,

efficient cooling

and heating –

for virtually

any room

Printed in U.S.A.8538-003

Heating & Cooling SystemsSince 1904

www.bryant.com

®

Page 2: StreamLine...538A Washing machine 6.0 Bels High-Wall Fan Coil 4.7 Bels 6.8 Bels 7.5 Bels One of the primary benefits of Bryant’s duct-free systems, is that they can be installed

The Bryant advantage.

• Over 90 years of HVAC experience

• A nationwide service network

• Skill and engineering craftsmanship behindall units assure quality and performance

• Offering a full line of quality residential andcommercial heating and cooling products

Bryant duct-free systems are the ideal complement to

your ducted system, when it isimpractical or prohibitively expensive to use ductwork.

A creative,economical solution.

Bryant duct-free systems offer a matchedcombination of an outdoor condensing unit andone of four compact, decorative indoor fan coilunits, connected only by refrigerant tubing andwires. One of the four styles will fit anyapplication you might encounter.

Fan coils can be mounted high on the wall or atfloor level, under the ceiling or in a suspendedceiling, permitting inexpensive, creativesolutions to numerous design problemsincluding:

• Add-ons to current space (office or familyroom addition)

• Special space requirements (such as acomputer room and kitchens)

• When adding air conditioning to spaces that are heated by electric heat and have no ductwork

• Historical renovations or whenever it isessential to preserve the appearance of theoriginal structure

• Any room where individual comfort controlis desired (such as a home office)

Why choose duct-free? 3

Featured benefits 4

Fan coil units

Expressions 5

High-wall 6

In-ceiling cassette 7

Under ceiling 8

Condensing units

538J series 9

538 A&B series 10

538 C&D series 11

538S Multi-Split 12

Control units 13

Accessories

Indoor 14

Outdoor 15

Unit Specifications

Indoor 16

Outdoor 17

System Specifications

Cooling Only 18

Heat Pump 19

why choose duct-free systems?table of contents

Page 3: StreamLine...538A Washing machine 6.0 Bels High-Wall Fan Coil 4.7 Bels 6.8 Bels 7.5 Bels One of the primary benefits of Bryant’s duct-free systems, is that they can be installed

Console duct-free systems offerflexibility, energyefficiency andcomplete personalcomfort control. Theslim, attractive fan coilsmount unobtrusively on the ceiling orwall, delivering whisper-quiet cooling andheating in either one or two rooms at a time.Operation is simple with the state-of-the-art,digital, infrared remote controller. Outdoorcondensing units are available in single ormulti-zone configurations.

Other advantages include:

Quiet operation – There are no compressors in, or directly above, the conditioned space; and there is none of the noise usually generatedby air being forced through ductwork. Indoorunits are whisper-quiet, and outdoor unitssatisfy sound level ordinances by operating at levels as low as 6.8 bels.

High efficiency and economy – Because noenergy is lost forcing air through ductworkwhich can result in losses up to 15-20%, duct-free systems are more efficient than comparableducted systems.

Built-in reliability – Our units are designed to provide years of trouble-free operation. Allsystems include protection against freeze-upsand high discharge temperatures. Our simpleself-diagnostic technology helps simplifytroubleshooting on most models.

Individual room comfort – Each space can haveindividual set points and controls for maximumcomfort. The airswing feature onselected modelsallows optimal airmixing to eliminatehot and cold spots.

Simple operation – Wall mount units are micro-processor controlled and include an infraredwireless remote control. In-ceiling and under-ceiling units operate with new solid-state,multi-feature electronic thermostats. All unitsautomatically restart and retain memory afterpower failure, and 24v controlled systems areeasily integrated into most building control systems.

Highest indoor air quality – Our optionaladvanced filtering system* enhancesindoor air quality byremoving dust andparticles from the air and combatingunpleasant odors.

Attractive appearance – Compact size,lightweight and neutral colors allow our unitsto go anywhere and blend with any decor.

* High wall systems only

State-of-the-artInfrared remotecontrol included withconsole system(see page 13)

• Efficiently designed tosave money and energy

• Optional two-way operationallows simultaneousconditioning of secondroom

• Easy to operate withdigital, LCD remote control

• Elegant styling tocomplement anydecor

• Quiet operation, even inturbo mode

• Smooth, consistent air distribution

• Automatic, microprocessor-controlled operation

• Backup electric heater*

• Built-in safety, durabilityand self-diagnosticfeatures

• Simple installation and maintenance

*Heat pump models only

Peopletalking

538A Washingmachine

6.0 Bels

High-Wall Fan Coil

4.7 Bels

6.8 Bels

7.5 Bels

One of the primarybenefits of Bryant’sduct-free systems,is that they can beinstalled in places

where conventionalducted cooling

simply cannot go. Lets you heat or cool two rooms at once.

Installs on the wall near floor level

Installs on the ceiling to save space

WEIGHT (lbs)INDOOR SECTIONNOMINAL

COOLING CAPACITY(Btu/h)

NOMINALHEATING CAPACITY

(Btu/h)WEIGHT (lbs)

WEIGHT

DIMENSIONS (in)

WIDTH DEPTH HEIGHT

40CG018301RM 18,000 -- 39.4 24.0 8.9 66.040CG024301RM 24,000 -- 47.3 24.0 8.9 77.040CG030301RM 30,000 -- 47.3 24.0 8.9 77.040CS018301RM 18,000 18,000 39.4 24.0 8.9 66.040CS024301RM 24,000 24,000 47.3 24.0 8.9 77.040CS030301RM 31,000 31,000 47.3 24.0 8.9 77.0

OUTDOOR SECTION

SYSTEMTYPE

NOMINALCOOLING CAPACITY

(Btu/h)

NOMINALHEATING CAPACITY

(Btu/h)

DIMENSIONS (in)

WIDTH DEPTH HEIGHT

SINGLE ZONE 38CG018301RM 18,000 -- 35.4 25.2 9.88 143.0SINGLE ZONE 38CG024301RM 24,000 -- 35.4 25.2 9.88 143.0SINGLE ZONE 38CG030301RM 30,000 -- 43.3 25.2 12.6 165.0SINGLE ZONE 38CS018301RM 18,000 18,000 35.4 25.2 9.88 143.0SINGLE ZONE 38CS024301RM 24,000 24,000 35.4 25.2 9.88 143.0SINGLE ZONE 38CS030301RM 30,000 31,000 43.3 25.2 12.6 165.0MULTI-ZONE 38SC030301RM 30,000 -- 43.3 48.8 12.6 330.0MULTI-ZONE 38SB030301RM 30,000 31,000 43.3 48.8 12.6 330.0

* Contact your local dealer for availability.

WEIGHT (lbs)

console systemtwo-way cooling and heatingfeatured benefits

Page 4: StreamLine...538A Washing machine 6.0 Bels High-Wall Fan Coil 4.7 Bels 6.8 Bels 7.5 Bels One of the primary benefits of Bryant’s duct-free systems, is that they can be installed

For quietcomfort andattractive design,Bryant’s high-wallduct-free system iswithout equal. Mountedon a small amount of wallspace near the ceiling, it fits seamlesslyinto nearly any decor. Comfort levels can beeasily and precisely controlled using theinfrared remote control.

These highly efficient, economical heat/coolsystems pay for themselves in energy savings.Perfect for add-ons and retrofits in smalloffices, home offices, shops, healthcare waitingrooms, bank rooms with ATMs, computerrooms and other small areas.

619EAX0090W0 9000 — 33.46 6.29 11.02 18.7619ENX0120H0 12000 .75 33.61 7.28 11.81 24.2619ENX0180H0 18000 1.8 45.28 8.66 14.17 38.5619ENX0240H0 24000 1.8 45.28 8.66 14.17 42.9

WEIGHT (lbs)MODELELECTRIC

HEAT(kW)

DIMENSIONS (in)

WIDTH DEPTH HEIGHT

Cooling Only

Heat Pump

WEIGHT (lbs)MODELNOMINALCAPACITY

(Btu/h)

NOMINALCAPACITY

(Btu/h)

ELECTRICHEAT(kW)

DIMENSIONS (in)

WIDTH DEPTH HEIGHT

Indoor unit includes metering device, power and control wiring (35 ft.) and mounting bracket.*Selected models

Infrared remotecontroller includedwith indoor unit(see page 13)

• Lightweight; easyinstallation andmaintenance

• Supplementalelectric heat on heatpumps*

• Air distribution maybe adjusted throughchoice of fan speedsand louver settings

• Easy operationthrough auto modes

• Dehumidificationmode allows perfecthumidity control

• Easy-to-change,cleanable air filters

• Standard safetyfeatures includefreeze-up protection,high temperatureprotection, self-diagnostics

• Intelligentmicroprocessorcontrol 619EAX0090E0 9000 — 33.46 6.29 11.02 18.7

12000 — 33.61 7.28 11.81 24.2619ENX0180E0 18000 — 45.28 8.66 14.17 38.5619ENX0240E0 24000 — 45.28 8.66 14.17 42.9

Outdoor section

WEIGHT (lbs)

high-wallfan coils

619EAX, ENX, 0120E0

Cassette units are ideal for retrofits andmodernizations with suspended ceilings. The indoor unit installs like fluorescent lightsin standard ceiling grids and requires lessthan 12" of vertical plenum space.

Cassettes are operated by a single outdoorcondensing unit, and offer whisper-quiet andeconomical comfort control. The In-ceilingcassette has four adjustable diffusers that

distribute air evenly, without drafts andcan be adjusted for two-way, three-

way or four-way air distribution.In addition to traditional heat

pump operation, cassettescan be matched to coolingonly condensers toprovide a straightelectric heat option.

With its built-incondensate pump, the

In-Ceiling Cassette fancoil can be installed quickly

and can be moved later to suitchanging space requirements.

• Efficient airdistributioneliminates hot and cold spots

• 2' x 2' and 2' x 4'configurations drop into existingceilings grids

• 24 volt controlvoltage allowinterface withstandard controlsand energymanagementsystems

• Freeze protection

• Fresh air intakeallows for up to 15% of outside air*

• Branch duct cansupply adjacentrooms

• Supplementalelectric heat on heat pump

in-ceilingcassette fan coils

619FNX0240W0 18000 1.8 28.00 28.00 11.75 66.1619FNX0360W0 25000-29000 2.7 49.62 28.00 11.75 109.6619FNX0480W0 33000-34400 2.7 49.62 28.00 11.75 118.8

Cooling Only

Heat Pump

WEIGHT (lbs)MODEL CAPACITY(Btu/h)

ELECTRICHEAT(kW)

DIMENSIONS (in)

WIDTH DEPTH HEIGHT

619FNX0240E0 18300 — 28.00 28.00 11.75 61.6619FNX0360E0 24000-33000 — 49.62 28.00 11.75 105.8

WEIGHT (lbs)

WEIGHT (lbs)

MODEL CAPACITY(Btu/h)

ELECTRICHEAT(kW)

DIMENSIONS (in)

WIDTH DEPTH HEIGHT

Indoor unit includes AccuRator ®, condensate pump and support bracket. Grille and thermostat sold separately.System specification-see page 15

* When used with optional power vent fan motor

Outdoor section

Page 5: StreamLine...538A Washing machine 6.0 Bels High-Wall Fan Coil 4.7 Bels 6.8 Bels 7.5 Bels One of the primary benefits of Bryant’s duct-free systems, is that they can be installed

Choice of three solid-state24v electronic wall-mountedthermostats, sold separately(see page 13)

Underceiling systems are idealin applicationswhere there is noavailable space above theceiling, or ceiling height isrestricted. The systems take upless than 10" and provide quiet,effective cooling and heating from18,000 Btu/h to 60,000 Btu/h. Thesesystems provide efficiencies as high as 12SEER, and offer many flexible options suchas fresh air intake, condensate pumps andlow ambient operation down to –20° F. Inaddition to traditional heat pump operation,underceiling units can be matched to coolingonly condensing units to provide a straightelectric heat option.

619CNX0240E0AC 24000 — 50.94 23.12 9.94 108.0619CNX0360E0AC 36000 — 58.81 23.12 9.94 117.0619CNX0480E0AC 48000 — 71.56 23.12 9.94 149.0619CNX0600E0AA 60000 — 92.00 23.12 9.94 179.0

• Variable fresh airintake allows up to 30% outside air*

• Auto “pulse”louvers provideeven coveragethroughout space

• Freeze protection

• Supplementalelectric heat on heat pump

• 24 volt controlvoltage allowsinterface withstandard controls and energymanagementsystems

under ceilingfan coils

WEIGHT (lbs)MODELNOMINALCAPACITY

(Btu/h)

ELECTRICHEAT(kW)

DIMENSIONS (in)

WIDTH DEPTH HEIGHT

Cooling Only

WEIGHT (lbs)MODELNOMINALCAPACITY

(Btu/h)

ELECTRICHEAT(kW)

DIMENSIONS (in)

WIDTH DEPTH HEIGHT

Heat Pump

Indoor unit includes AccuRator® and mounting brackets.

* When used with optional power vent fan motor

619CNX0240W0AC 24000 2.0 50.94 23.12 9.94 110.0619CNX0360W0AC 36000 3.0 58.81 23.12 9.94 119.0619CNX0480W0AC 48000 4.0 71.56 23.12 9.94 151.0619CNX0600W0AA 60000 5.0 92.00 23.12 9.94 181.0

Outdoor section

WEIGHT (lbs)

For residential and lightcommercial applications, theBryant 538J Cooling OnlyCondensing Unit offers all thefeatures and benefits you could want, at aremarkably low cost. Operation is extremely quiet, thanks toour unique cowl induction fan design and scroll compressor.

This small-footprint unit (with the same chassis size as the538A) may be used with selected Bryant fan coil units. It alsoincludes horizontal discharge air flow, and offers a widevariety of optional add-on accessories.

538J light commercialcondensing units

WEIGHT (lbs)MODEL

NOMINALCOOLINGCAPACITY

(Btu/h)SOUND DATA (BELS)

DIMENSIONS (in)

WIDTH DEPTH HEIGHT

Cooling Only

538JNX018000 18000 6.5 36.94 14.5 25.13 130.0538JNX024000 24000 6.8 36.94 14.5 25.13 136.0538JNX030000 30000 6.4 36.94 14.5 25.13 161.0538JNX036000 36400 7.1 36.94 14.5 25.13 185.0538JNX048000 48000 7.2 44.56 17.0 37.19 222.0538JNX060000 60000 7.1 44.56 17.0 37.19 249.0

• Very low soundlevels

• Quick and easyinstallation andmaintenance

• Low pressure safetyswitch

• Compact design

• 100-foot line length,equivalent 75-footvertical separation

• Galvanized steelcasing with zincphosphate coating

WEIGHT (lbs)

Page 6: StreamLine...538A Washing machine 6.0 Bels High-Wall Fan Coil 4.7 Bels 6.8 Bels 7.5 Bels One of the primary benefits of Bryant’s duct-free systems, is that they can be installed

This series of condensingunits combines small size,reduced weight andenhanced performancewith state-of-the-artstyling. Designed foruse with Bryant HighWall fan coil units,these are cooling andheat pump condensingunits operating at 9,000 and 12,000 btu/h.

• Advancedhorizontal air flow design

• Can be installed 12 in. away fromoutside wall

• Lightweight

• Whisper quietoperation

• Quick and easyinstallation and maintenance

• Galvanized steelcasing with zincphosphate coating

538 C&D seriescondensing units

WEIGHT (lbs)MODEL

NOMINALCOOLINGCAPACITY

(Btu/h)SOUND DATA (BELS)

DIMENSIONS (in)

WIDTH DEPTH HEIGHT

Cooling Only

Heat Pump

538CAX009000 9000 6.4 26.1 8.9 23.25 55.012000 6.5 26.1 8.9 23.25 62.0

WEIGHT (lbs)MODEL

NOMINALCOOLINGCAPACITY

(Btu/h)SOUND DATA (BELS)

DIMENSIONS (in)

WIDTH DEPTH HEIGHT

538DAX009000 9000 6.5 26.1 8.9 23.25 60.7538DNX012000 12000 6.5 26.1 8.9 23.25 66.5

In areas of limited space, or when low-noise isessential, specify the 538 A & B Series CondensingUnit. Designed for use with selected Bryant fan coil units, this compact, quiet unit features an advanced horizontal airflow design, low-velocity air discharge, energy-efficient

operation, and low cost.

This is the only dedicated commercialunit with all safety features

standard. Featuring a smallfootprint, it may

be placed as close as sixinches from walls or buildings.

• Multiple voltage and phases available

• Oversizedaccumulator

• Lock-out compressorprotection andhigh/low pressureswitches

• Galvanized steelcasing with zincphosphate coating

• Premium solid brassservice valves

• Quick and easyinstallation andmaintenance

• Scroll compressorfor reliability andquietness (mostmodels)

• 200-foot equivalentline lengths, 150-footvertical separation †

538 A&B seriescondensing unit

WEIGHT (lbs)MODEL

NOMINALCOOLINGCAPACITY

(Btu/h)

SOUND DATA(BELS)

DIMENSIONS (in)

WIDTH DEPTH HEIGHT

WEIGHT (lbs)MODEL

NOMINALCOOLINGCAPACITY

(Btu/h)

SOUND DATA (BELS)

DIMENSIONS (in)

WIDTH DEPTH HEIGHT

Cooling Only

Heat Pump

† A field supplied liquid selnoid valve is required for applications over 100 ft

538BNX018000 18000 7.0 36.94 14.56 25.13 154.0538BNX024000 24000 6.8 36.94 14.56 25.13 167.0538BNX030000 30000 6.8 36.94 14.56 25.13 180.0538BNX036000 36000 6.8 36.94 14.56 25.13 184.0538 BPX, BEX, 036000 36000 6.8 44.56 17.06 37.19 249.0538 BNX, BPX, BEX, 048000 48000 7.6 44.56 17.06 37.19 252.0538 BNX, BPX, BEX, 060000 60000 7.2 44.56 17.06 37.19 272.0

538ANX018000 18000 7.0 36.94 14.56 25.13 150.0538ANX024000 24000 6.8 36.94 14.56 25.13 154.0538ANX030000 30000 6.8 36.94 14.56 25.13 169.0538 ANX, APX, AEX, 036000 36000 6.8 36.94 14.56 25.13 179.0538 ANX, APX, AEX, 048000 48000 7.2 44.56 17.06 37.19 270.0538 ANX, APX, AEX, 060000 60000 7.2 44.56 17.06 37.19 290.0

WEIGHT (lbs)

WEIGHT (lbs)

WEIGHT (lbs)

WEIGHT (lbs)

Cooling Only units can be usedin stackable configurations foreconomy of space

538 CAX, CNX 012000

Visit the Energy Star website at www.energystar.govfor qualifying systems

Money Isn't All You're Saving

Page 7: StreamLine...538A Washing machine 6.0 Bels High-Wall Fan Coil 4.7 Bels 6.8 Bels 7.5 Bels One of the primary benefits of Bryant’s duct-free systems, is that they can be installed

New electronic digital low-profile thermostatfor all Bryant duct-free in-ceiling and underceiling units, sold separately

• Simple push-button control sets heating/coolingtemperature set points. Auto changeovermode controls both heat and cool

• Three models: – Flat Stat – Slim Line – 5-1-1 Programmable

• Independent fan only operation

• Backlit LCD display

• Time and day indicator

• Locking keypad

• Clock backup

• Optionalremote roomsensor

• LimitedTemperatureOverride – setable for one hour

• Choice ofdegrees

(C or F) may be displayed with a

simple toggle

• 24v control voltage – increases flexibilityallowing interface with standard controls and energy management systems

The 538S Multi-Split serves two zones,allowing many indoor fan coil combinations.

Cooling capacity is 24,000 btu. Thesesystems operate in a variety of

combinations for 619C, 619Eand 619F fan coils.

The 538S also permitsstandard ducted fancoil operation inconjunction withduct-free splitsystems. For more

information, contactyour local Bryant

dealer.

• 12 SEER withmatched systems

• Scroll Compressors

• TXV’s in outdoorunit

• High & Lowpressure switches

• Standard lowambient

• 6.8 Bels

• Compact cabinetdesign

• Galvanized steelcasing with zincphosphate coating

538S multi-splitcondensing unit

619FNX0240E0 2 IN-CEILING CASSETTE 10.5 2.20 1050 23000619CNX0240E0AC* 2 CEILING SUSPENDED 10.8 2.22 1000 24000619ENX0180E0 2 HIGH WALL 11.3 2.03 960 23000619FNX0240E0 1 IN-CEILING CASSETTE

10.3 2.24 1025 23000538SNX024000 619CNX0240E0AC* 1 CEILING SUSPENDED 2 TONS 12.0

619FNX0240E0 1 IN-CEILING CASSETTE10.7 2.14 1005 23000

619ENX0180E0 1 HIGH WALL619CNX0240E0AC* 1 CEILING SUSPENDED

10.7 2.15 980 23000619ENX0180E0 1 HIGH WALL

FAN COIL TYPE(S)NOMINALSYSTEM

CAPACITYSEER EER TOTAL

kW

TOTALSTANDARD

CFM (ATHIGH SPEED

SYSTEM NET

COOLING(Btuh)

OUTDOORSOUNDRATING(Bels)

INDOOR SECTIONS

MODELOUTDOORSECTION QUANTITY

* Unit must be reconfigured for 1-1/2 ton (18,000 Btu/h) operation. Refer to installation instructions included with the fan coil unit for more details.

6.8

With Bryant’s high-tech

control units,operation couldn’t

be easier.

• Advanced, 24-hour on/off timer.

Built-in clock displays current time

• Sleep mode

• Dehumidification mode

• Auto changeover/cooling to heating

• Auto air swing louver

• Countdown start/stop timer

• Ergonomically designed hand set

• Auto fan speeds

Wireless infrared remote controller included standardwith all Bryantduct-freehigh-wall and console systems

control units

High-wall remote

Console remote

Page 8: StreamLine...538A Washing machine 6.0 Bels High-Wall Fan Coil 4.7 Bels 6.8 Bels 7.5 Bels One of the primary benefits of Bryant’s duct-free systems, is that they can be installed

Many options are also available for the Duct-free Systems’outdoor condensing units.

Choices include the following.

Low ambient kits – Controls fan motor cyclesin response to outdoor temperatures below 40° F.

Wind baffle – Sheet metal wrapper; improvesunit operation in high winds. Recommendedwhenever low-ambient kit is used.

Stacking kit – Rails designed for stacking allsize 018 and larger units.

Wall mount kit – Brackets can be used to raiseunit above ground level or mount on wall. Forsize 018 and larger.

Crankcase heater – For units with scrollcompressors. Recommended for low-ambientapplications.

Winter start kit – An SPST relay. Requiredwhen unit is intended to operate in coolingambiants below 40˚F.

outdooraccessories

Charcoal filter kit – For high-wall units.Improves indoor air quality; removes odors,micro-particles and Volatile Organic Compounds.

Fresh air intake – Comprised of fresh air intakemounting kit and power vent fan motor. Bothcomponents must be used together. The filter is mounted at the fan coil unit and providesfiltering of outdoor air before it enters the unit.

Condensate pump – Mounts inside with quickplug-in connections. Standard on 619FNX.

Remote locking mount – Keeps remotecontroller securely in place. Includes screw-out lock.

Remote room sensor kit – Designed to sense the air temperature at a remote location and send this information by digital communicationto the thermostat.

Indoor guard kit – Guard for discharge grilleused to prevent objects from entering the airsweep mechanism.

indooraccessories

Optional Outdoor Accessories

Recommended accessories for COOLING ONLY units using low ambient controller:

DESCRIPTION ORDERING NUMBER FOR MODELS

Hard Start Kit KSAHS1401AAA 538ANX024-060, ALL 538S, 538BNX030 & 036Insulated 25’ Tubing Kit 389062-701 538C & 538D (009 & 012)Low Ambient Controller 53DS-900---060 All outdoor units (Standard option on 538SNX Units)Stacking Kit 53DS-900---075 538A(N,P,E)018-036, 538SNX024

53DS-900---076 538A(N,P,E)048-060Wall Mount Kit 53DS-900---077 538A(N,P,E)018-036, 538SNX024, 538BNX018-036, 538DNX018-024

53DS-900---078 538A(N,P,E)048-060, 538B(P,E)X036, 538B(N,P,E)048-060Wind Baffle 53DS-900---065 538C & 538D (009 & 012)

53DS-900---070 538A(N,P,E)018-036, 538SNX024, 538BNX018-036, 538DNX018-02453DS-900---071 538A(N,P,E)048-060, 538B(P,E)X036, 538B(N,P,E)048-060

Recommended accessories for HEAT PUMP units using low ambient controller:

Crankcase Heater KAACH1201AAA 538BNX030-036 (Standard option on all other H/Ps)Isolation Relay KHAIR0101AAA Required for all heat pump unitsWinter Start Kit (Cooling - for OA below 40˚ F) KAAWS0101AAA ALL 538B(N,P,E)X (Not required for 538D009, 012)

Crankcase Heater 53DS-900---068 538CAX00900053DS-900---069 538CNX012000KAACH1201AAA 538A(N,P,E)X024-060, ALL 538SNXKAACH1301AAA 538AEX036-060

Winter Start Kit (for OA below 40˚ F) KAAWS0101AAA ALL 538A(N,P,E)X, 538SNX (Not required for 538C009, 012)

Bryant Duct-freeSystems may be

enhanced by a widevariety of accessories.

Choose from all the quality options

shown here.

Optional Indoor Accessories

DESCRIPTION ORDERING NUMBER FOR MODELS

Carbon Filter Kit 53DS-900---047 619EAX009 (C/O & H/P)53DS-900---048 619ENX012 (C/O & H/P)53DS-900---049 619ENX018, 024 (C/O & H/P)

Carbon Filter Replacement (qty 4) 53DS-900---050 619EAX009 (C/O & H/P)53DS-900---051 619ENX012 (C/O & H/P)53DS-900---052 619ENX018, 024 (C/O & H/P)

Condensate Pump 53DS-900---079 All 619C (Standard option on 619F)Condensate Pump (115 V) 53DS-900---062 619EAX009 (C/O & H/P)Condensate Pump (230 V) 53DS-900---064 619ENX012, 018, 024 (C/O & H/P)Fresh Air Intake Mounting Kit 53DS-900---006 All 619C (2 required for 048 & 060 size models)

53DS-900---067 All 619FPower Vent Fan Motor (for fresh air) 53DS-900---066 All 619C, 619F (required with each Fresh Air Intake Mounting Kit)Indoor Guard Kit 389067-701 619CNX024 (C/O & H/P)

389067-702 619CNX036 (C/O & H/P)389067-703 619CNX048 (C/O & H/P)

Remote Controller Locking Mount Kit 53DS-900---059 All 619ERear Outlet Grille 53DS-900---080 All 619G, 619HRemote Room Sensor Kit 33CSSEN-WB All 619C, 619F (in conjunction with all 53DFS thermostats)

Required Components

DESCRIPTION ORDERING NUMBER FOR MODELS

Cassette Grille 40QKB900---213 619FNX024 (C/O & H/P)Cassette Grille 40QKB900---214 619FNX036, 048 (C/O & H/P)Flat Stat 53DFS-250-FSBRY COOLING ONLYSlim Line 53DFS-250-SLBRY COOLING ONLY & HEAT PUMP5-1-1 Programmable 53DFS-T2-HPBRY COOLING ONLY

Page 9: StreamLine...538A Washing machine 6.0 Bels High-Wall Fan Coil 4.7 Bels 6.8 Bels 7.5 Bels One of the primary benefits of Bryant’s duct-free systems, is that they can be installed

heat pump system specifications

CFM – Cubic Feet Per MinuteSEER – Seasonal Energy Efficiency Rating

cooling only system specifications

NOMINALINDOOR OUTDOOR

ARIARICAPACITY

UNIT UNITCAPACITY

CFMSEER EER INDOOR INDOOR OUTDOOR OUTDOOR

TONS Btuh POWER PRESSURE POWER PRESSURE

0.75 619EAX0090E0 538CAX009000 8,500 215 10.5 9.7 50.4 42.1 62.3 54.0

1.0619EAX0120E0 538CAX012000 11,000 300 10.5 9.3

54.0 45.763.1 54.8

619ENX0120E0 538CNX012000 11,600 302 11.0 10.1 63.1 54.8

1.5 619ENX0180E0538ANX018000 17,300 480 11.3 10.4

57.6 49.366.1 57.8

538JNX018000 16,200 480 11.0 9.7 59.5 51.2538JNX018000 17,600 550 11.7 10.4 59.2 51.2

2.0 619ENX0240E0 538ANX024000 22,600 550 12.0 10.8 62.5 54.2 65.5 57.2538JNX024000 22,600 550 11.3 11.3 63.2 54.9

1.5 619CNX0240E0AC538ANX018000 18,000 500 12.0 11.0

57.2 48.966.1 57.8

538JNX018000 18,000 500 11.6 10.5 59.5 51.2

2.0 619CNX0240E0AC538ANX024000 22,800 600 12.0 11.0

58.4 50.165.5 57.2

538JNX024000 23,000 600 11.0 11.2 63.2 54.9

2.5 619CNX0360E0AC538ANX030000 30,000 840 12.0 11.0

68.4 60.163.0 54.7

538JNX030000 29,000 840 10.3 9.7 59.5 51.2

3.0 619CNX0360E0AC538ANX,APX,AEX,036000 34,000 840 12.0 10.5

68.4 60.164.5 56.2

538JNX036000 34,000 840 10.1 9.6 64.7 56.4

4.0 619CNX0480E0AC538ANX,APX,AEX,048000 47,000 1,200 12.0 10.8

67.3 59.070.1 61.8

538JNX048000 45,500 1,200 10.8 9.9 65.4 57.1

5.0 619CNX0600E0AC538ANX,APX,AEX,060000 58,000 1,600 12.0 11.2

70.1 61.869.4 61.1

538JNX060000 58,500 1,600 10.8 9.5 65.8 57.5

1.5 619FNX0240E0538ANX018000 18,300 525 11.0 10.4

56.3 48.066.1 57.8

538JNX018000 17,800 525 11.4 10.6 59.5 51.2538ANX024000 24,000 915 11.0 10.9 65.5 57.2

2.0538JNX024000 24,000 915 11.8 11.3 63.2 54.9

2.5 619FNX0360E0538ANX030000 30,000 915 10.8 9.6

54.8 46.563.0 54.7

3.0538JNX030000 29,000 915 11.1 10.1 59.5 51.2

538ANX, APX, AEX, 036000 33,000 915 10.8 10.5 64.5 56.2538JNX036000 34,400 915 10.5 9.7 64.7 56.4

1.5 40CG018301RM 38CG018301 18,000 650 10.0 -- 55.0 38.0 79.0 49.02.0 40CG024301RM 38CG024301 23,400 800 10.0 -- 56.0 40.0 74.0 49.02.5 40CG030301RM 38CG030301 30,000 800 10.0 -- 55.0 40.0 78.0 49.0

2.5 40CG030301RM 38SC030301 30,000 800 10.0 -- 55.0 40.0 80.0 49.0

SOUND RATING (dBa)

CFM – Cubic Feet Per MinuteHSPF – Heating Seasonal Performance FactorSEER – Seasonal Energy Efficiency RatingC/O – Cooling OnlyH/P – Heat Pump

NOMINALINDOOR OUTDOOR ARICAPACITY

UNIT UNITC/O H/P

CFMSEER EER HSPF INDOOR INDOOR OUTDOOR OUTDOOR

TONS Btuh Btuh POWER PRESSURE POWER PRESSURE

0.8 619EAX0090W0 538DAX009000 8,700 9,000 252 10.0 9.2 6.8 50.6 42.3 63.4 55.11.0 619ENX0120H0 538DNX012000 11,100 11,700 300 10.0 9.5 6.8 54.0 45.7 62.8 54.51.5 619ENX0180H0 538DNX018000 17,300 16,400 485 11.0 10.1 6.8 58.6 50.3 67.2 58.92.0 619ENX0240H0 538DNX024000 23,200 21,000 520 11.0 10.4 6.8 61.7 53.4 63.3 55.0

2.0 619CNX0240W0AC538BNX018000 19,000 17,000 500 11.0 10.0 7.2

57.2 48.967.2 58.9

538BNX024000 24,000 22,600 525 11.0 10.0 7.3 66.3 58.0538BNX030000 30,000 28,000 870 11.0 10.2 7.4 65.9 57.6

3.0 619CNX0360W0AC 538BNX036000 34,600 33,000 870 11.5 10.2 7.2 68.4 60.1 66.2 57.9538BPX, BEX, 036000 36,000 34,400 870 11.0 9.8 6.8 71.5 63.2

4.0 619CNX0480W0AC 538BNX, BPX, BEX, 048000 48,000 45,500 1,100 10.2 9.6 7.3 67.3 59.0 73.0 64.75.0 619CNX0600W0AA 538BNX, BPX, BEX, 060000 58,000 57,500 1,600 11.0 11.0 7.4 70.1 61.8 73.6 65.3

1.8 619FNX0240W0 538BNX018000 18,000 17,600 525 10.0 9.0 6.8 56.3 48.0 67.2 58.9

2.0 619FNX0360W0538BNX024000 25,000 23,800 980 10.7 10.2 7.6

54.8 46.566.3 58.0

538BNX030000 29,000 27,000 980 11.5 11.1 7.6 65.9 57.6

3.0 619FNX0480W0538BNX036000 33,000 33,000 1,100 10.5 9.5 6.8

59.1 50.866.2 57.9

538BPX,BEX, 036000 34,400 34,000 1,100 10.0 9.2 6.8 71.5 63.2

1.5 40CS018301RM 38CS018301 18,000 18,000 650 10.0 -- -- 55.0 38.0 79.0 49.02.0 40CS024301RM 38CS024301 23,400 24,000 800 10.0 -- -- 56.0 40.0 74.0 49.02.5 40CS030301RM 38CS030301 30,000 31,000 800 10.0 -- -- 55.0 40.0 78.0 49.0

2.5 40CS030301RM 38SB030301 30,000 31,000 800 10.0 -- 55.0 40.0 80.0 49.0

SOUND RATING (dBa)ARI CAPACITIES

Cooling Only High Wall

Cooling Only Cassette

Cooling Only Console

Cooling Only Console Multi Split

Cooling Only Under Ceiling

Heat Pump High Wall

Heat Pump Under Ceiling

Heat Pump Cassette

Heat Pump Console

Heat Pump Console Multi Split

Page 10: StreamLine...538A Washing machine 6.0 Bels High-Wall Fan Coil 4.7 Bels 6.8 Bels 7.5 Bels One of the primary benefits of Bryant’s duct-free systems, is that they can be installed

Notes: 1) Vert Lift is Fan Coil above Condenser. Vert drop is Fan Coil below Condenser.2) MCA and MOCP are for both indoor and outdoor units (system) and are listed in the outdoor unit.3) Two MCA and MOCP ratings are shown for units with separate unit and heater circuits.

The first value applies to unit circuit, the second applies to the heater circuit.

Legend: *Valve connection size is 3/4". Recommended line size is 7/8". MCA – Minimum Circuit Amps**Valve connection size is 7/8". Recommended line size is 1-1/8". MOCP – Maximum Overcurrent Protection Amps

VERT VERT MAX TUBE CONNECTIONS DIMENSIONSMODEL VOLTAGE MCA MOCP LIFT DROP TUBE LIQUID VAPOR WIDTH HEIGHT DEPTH WEIGHT

Note #1 Note #1 LENGTH

619EAX0090E0 115-1-60 Note #2 Note #2 -- -- -- -- -- 33.5 11.0 6.3 18.7619EAX0120E0 115-1-60 Note #2 Note #2 -- -- -- -- -- 33.6 11.8 7.3 24.2619ENX0120E0 208/230-1-60 Note #2 Note #2 -- -- -- -- -- 33.6 11.8 7.3 24.2619ENX0180E0 208/230-1-60 0.66 15 -- -- -- -- -- 45.3 14.2 8.7 38.5619ENX0240E0 208/230-1-60 0.66 15 -- -- -- -- -- 45.3 14.2 8.7 42.9619EAX0090W0 115-1-60 Note #2 Note #2 -- -- -- -- -- 33.5 11.0 6.3 18.7619ENX0120H0 208/230-1-60 Note #2 Note #2 -- -- -- -- -- 33.5 11.8 7.3 24.2619ENX0180H0 208/230-1-60 10.9 15 -- -- -- -- -- 45.3 14.2 8.7 38.5619ENX0240H0 208/230-1-60 10.9 15 -- -- -- -- -- 45.3 14.2 8.7 42.9619CNX0240E0AC 208/230-1-60 0.63 15 -- -- -- -- -- 50.9 10.3 23.1 108.0619CNX0360E0AC 208/230-1-60 1.60 15 -- -- -- -- -- 58.8 10.3 23.1 117.0619CNX0480E0AC 208/230-1-60 2.00 15 -- -- -- -- -- 71.6 10.3 23.1 149.0619CNX0600E0AA 208/230-1-60 3.30 15 -- -- -- -- -- 92.0 10.3 23.1 179.0619CNX0240W0AC 208/230-1-60 9.29 15 -- -- -- -- -- 50.9 10.3 23.1 110.0619CNX0360W0AC 208/230-1-60 17.70 20 -- -- -- -- -- 58.8 10.3 23.1 119.0619CNX0480W0AC 208/230-1-60 23.80 25 -- -- -- -- -- 71.6 10.3 23.1 151.0619CNX0600W0AA 208/230-1-60 28.70 30 -- -- -- -- -- 92.0 10.3 23.1 181.0619FNX0240E0 208/230-1-60 0.55 15 -- -- -- -- -- 28.0 11.8 28.0 61.6619FNX0360E0 208/230-1-60 1.10 15 -- -- -- -- -- 49.6 11.8 28.0 105.8619FNX0240W0 208/230-1-60 .6/ 7.5 15/15 -- -- -- -- -- 28.0 11.8 28.0 66.1619FNX0360W0 208/230-1-60 1.0/15.0 15/15 -- -- -- -- -- 49.6 11.8 28.0 105.8619FNX0480W0 208/230-1-60 1.0/15.0 15/15 -- -- -- -- -- 49.6 11.8 28.0 118.040CG018301RM 208/230-1-60 Note #2 Note #2 -- -- -- -- -- 39.4 24.0 8.9 66.040CG024301RM 208/230-1-60 Note #2 Note #2 -- -- -- -- -- 47.3 24.0 8.9 77.040CG030301RM 208/230-1-60 Note #2 Note #2 -- -- -- -- -- 47.3 24.0 8.9 77.040CS018301RM 208/230-1-60 Note #2 Note #2 -- -- -- -- -- 39.4 24.0 8.9 66.040CS024301RM 208/230-1-60 Note #2 Note #2 -- -- -- -- -- 47.3 24.0 8.9 77.040CS030301RM 208/230-1-60 Note #2 Note #2 -- -- -- -- -- 47.3 24.0 8.9 77.0

indoor unit specifications

outdoor unit specifications

19

Notes: 1) Vert Lift is Fan Coil above Condenser. Vert drop is Fan Coil below Condenser.2) MCA and MOCP are for both indoor and outdoor units (system) and are listed in the outdoor unit.3) Two MCA and MOCP ratings are shown for units with separate unit and heater circuits.

The first value applies to unit circuit, the second applies to the heater circuit.

Legend: *Valve connection size is 3/4". Recommended line size is 7/8". MCA – Minimum Circuit Amps**Valve connection size is 7/8". Recommended line size is 1-1/8". MOCP – Maximum Overcurrent Protection Amps

VERT VERT MAX TUBE CONNECTIONS DIMENSIONSMODEL VOLTAGE MCA MOCP LIFT DROP TUBE LIQUID VAPOR WIDTH HEIGHT DEPTH WEIGHT

Note #1 Note #1 LENGTH

538CAX009000 115-1-60 12.10 15 30' 30' 50’' 1/4" od 1/2" od 26.1 23.2 8.9 55.0538CAX012000 115-1-60 17.00 15 30' 30' 50’ 1/4" od 1/2" od 26.1 23.3 8.9 62.0538CNX012000 208/230-1-60 8.50 15 30' 30' 50’ 1/4" od 1/2" od 26.1 23.3 8.9 62.0538DAX009000 115-1-60 11.20 15 30' 30' 50’ 1/4" od 1/2" od 26.1 23.3 8.9 60.7538DNX012000 208/230-1-60 12.00 15 30' 30' 50’ 1/4" od 1/2" od 26.1 23.3 8.9 66.5538DNX018000 208/230-1-60 13.00 20 65' 150' 200' 3/8" od 5/8" od 36.9 25.1 14.6 154.0538DNX024000 208/230-1-60 15.30 25 65' 150' 200' 3/8" od 5/8" od 36.9 25.1 14.6 167.0538ANX018000 208/230-1-60 10.70 15 65' 150' 200' 3/8" od 5/8" od 36.9 25.1 14.6 150.0538ANX024000 208/230-1-60 16.80 25 65' 150' 200' 3/8" od 5/8" od 36.9 25.1 14.6 154.0538ANX030000 208/230-1-60 19.50 30 65' 150' 200' 3/8" od 3/4" od 36.9 25.1 14.6 169.0538ANX036000 208/230-1-60 23.20 40 65' 150' 200' 3/8" od 7/8" od * 36.9 25.1 14.6 179.0538APX036000 208/230-3-60 15.00 25 65' 150' 200' 3/8" od 7/8" od * 36.9 25.1 14.6 179.0538AEX036000 460-3-60 7.50 15 65' 150' 200' 3/8" od 7/8" od * 36.9 25.1 14.6 179.0538ANX048000 208/230-1-60 34.50 60 65' 150' 200' 3/8" od 7/8" od 44.6 37.2 17.1 270.0538APX048000 208/230-3-60 20.20 35 65' 150' 200' 3/8" od 7/8" od 44.6 37.2 17.1 270.0538AEX048000 460-3-60 11.10 15 65' 150' 200' 3/8" od 7/8" od 44.6 37.2 17.1 270.0538ANX060000 208/230-1-60 36.60 60 65' 150' 200' 3/8" od 1-1/8" od** 44.6 37.2 17.1 290.0538APX060000 208/230-3-60 21.50 35 65' 150' 200' 3/8" od 1-1/8" od** 44.6 37.2 17.1 290.0538AEX060000 460-3-60 10.80 15 65' 150' 200' 3/8" od 1-1/8" od** 44.6 37.2 17.1 290.0538JNX018000 208/230-1-60 14.10 25 65' 75' 100' 3/8" od 5/8" od 36.9 25.1 14.5 130.0538JNX024000 208/230-1-60 17.20 30 65' 75' 100' 3/8" od 5/8" od 36.9 25.1 14.5 136.0538JNX030000 208/230-1-60 20.30 35 65' 75' 100' 3/8" od 3/4" od 36.9 25.1 14.5 161.0538JNX036000 208/230-1-60 21.20 30 65' 75' 100' 3/8" od 3/4" od 36.9 25.1 14.5 185.0538JNX048000 208/230-1-60 31.80 50 65' 75' 100' 3/8" od 3/4" od 44.6 37.2 17.1 222.0538JNX060000 208/230-1-60 37.20 65 65' 75' 100' 3/8" od 3/4" od 44.6 37.2 17.1 249.0538SNX024000 208/230-1-60 16.80 25 30' 30' 50' 3/8" od (2) 5/8" od (2) 36.9 25.1 14.5 159.0538BNX018000 208/230-1-60 13.00 20 65' 150' 200' 3/8" od 5/8" od 36.9 25.1 14.6 154.0538BNX024000 208/230-1-60 15.30 25 65' 150' 200' 3/8" od 5/8" od 36.9 25.1 14.6 167.0538BNX030000 208/230-1-60 17.60 30 65' 150' 200' 3/8" od 3/4" od 36.9 25.1 14.6 180.0538BNX036000 208/230-1-60 23.10 40 65' 150' 200' 3/8" od 7/8" od* 36.9 25.1 14.6 184.0538BPX036000 208/230-3-60 15.50 25 65' 150' 200' 3/8" od 3/4" od 44.6 37.2 17.1 249.0538BEX036000 460-3-60 7.30 15 65' 150' 200' 3/8" od 3/4" od 44.6 37.2 17.1 249.0538BNX048000 208/230-1-60 30.50 50 65' 150' 200' 3/8" od 7/8" od 44.6 37.2 17.1 252.0538BPX048000 208/230-3-60 20.60 35 65' 150' 200' 3/8" od 7/8" od 44.6 37.2 17.1 252.0538BEX048000 460-3-60 9.90 15 65' 150' 200' 3/8" od 7/8" od 44.6 37.2 17.1 252.0538BNX060000 208/230-1-60 42.00 60 65' 150' 200' 3/8" od 1-1/8" od ** 44.6 37.2 17.1 272.0538BPX060000 208/230-3-60 27.00 45 65' 150' 200' 3/8" od 1-1/8" od ** 44.6 37.2 17.1 272.0538BEX060000 460-3-60 15.00 25 65' 150' 200' 3/8" od 1-1/8" od ** 44.6 37.2 17.1 272.038CG018301 208/230-1-60 0.80 15 49' 49' 98' 1/4" od 1/2" od 35.4 25.2 9.88 143.038CG024301 208/230-1-60 0.80 15 66' 66' 131' 3/8" od 5/8" od 35.4 25.2 9.88 143.038CG030301 208/230-1-60 0.80 15 33' 33' 98' 3/8" od 5/8" od 43.3 25.2 12.6 165.038CS018301 208/230-1-60 11.50 25 49' 49' 98' 1/4" od 1/2" od 35.4 25.2 9.88 143.038CS024301 208/230-1-60 17.00 35 66' 66' 131' 3/8" od 5/8" od 35.4 25.2 9.88 143.038CS030301 208/230-1-60 17.00 40 33' 33' 98' 3/8" od 5/8" od 43.3 25.2 12.6 165.038SC030301 208/230-1-60 0.8 X 2 15 X 2 33' 33' 98' 3/8" od 5/8" od 43.3 48.8 12.6 330.038SB030301 208/230-1-60 17.0 X 2 40 X 2 33' 33' 98' 3/8" od 5/8" od 43.3 48.8 12.6 330.0