115669
STYLE 9300 AKRON FLOW/PRESSURE SYSTEMS LPM/kPaINSTALLATION CALIBRATION OPERATING INSTRUCTIONS
TABLE OF CONTENTS
Section DeScription page
i installation instructions 1
ii calibration instructions 3
iii operation instructions 5
iV troubleshooting guide 6
V replacement parts 7
List of Figures / Tables
Figure 1 Flow Sensor
Figure 2 a,B,c, typical Valve installations
Figure 3 Saddle clamps
Figure 4 pressure transducer
Figure 5 Meter installation guide
Figure 6 Meter Functions
table 1 Flow chart
Figure 6a
2
Figure 6
3
SECTION IINSTALLATION INSTRUCTIONS
A. SYSTEM COMPONENTS
• DisplayMeter(Figure6) • FlowSensor(Figure1) • PressureTransducer(Figure4) • InterconnectCables5,10or20' • SensorHolder 1. ValveInletAdapters(Figure2A,B&C) 2. Saddles(Figure3)
B. FLOW SENSOR LOCATION
primary 1. Akron'sspeciallydesignedinletadaptersforSwing-outValves.Size2"-4". 2. SaddleClamps.Size2"-5"(Schedule40pipe) Note:Horizontallineinstallationsmustpositionthesensorportwithin180˚ontopside(9:00-3:00).
Avoid
• Installationswherethesensorwouldbelocatedinalinewhereasmallerlineprecedesit. • Installationswheresensorwouldbepositionedfollowingavalveorelbow.Neverinstallflowportvalveadapteron dischargesideofvalve.
• Installationswheresensorwoulddirectlyprecedebypasseductor. Note:Intightinstallationswherewaterflowisturbulent,customcalibrationisrequiredformaximumaccuracy.
c. FLOW SENSOR INSTALLATION
1. Akron Valve Adapter
a. Simply remove retainer nut or plug. b. GreaseO-RingsonsensorwithO-Ringlubeorsiliconegrease.(Removeplasticpaddlewheelprotector.) c. insert sensor into port and push in. d. Alignpin"A"(Figure1)withlocatorholeandpushin. e. replace the retainer nut or plug and tighten with a wrench.
Sensor installation complete
2. Saddle Clamp
a. Determine the location on the pipe. b. Drilla1-1/4"holeinthepipewithaholesaw.Horizontalpipingontopsidefrom9:00-3:00. c. Deburrtheedgeoftheholeandcleantheareawherethegasketseals. d. Centersaddlewithholeinpipe(Sensorlocatorhole"A"(Figure3)maybeoneithersideofpipehole.)
4
e. insert strap into saddle and tighten nuts hand tight. f. Usingatorquewrenchtightennutsalternatelyto80footpounds. g. Followstepsa-einC.1toaddsensor. Sensor installation complete
D. PRESSURE TRANSDUCER INSTALLATION
ThePressureTransducer(Figure4)hasa1/4"NPTmalethread.
1. apply pipe sealant to the thread and insert into provided tapped hole in valve discharge adapter on discharge sideofvalve.
2. Tightenwithwrenchtotorqueusedforsmallpipefittings.
pressure transducer installation is now complete
E. METER INSTALLATION
CAUTION:Alwaysdisconnectallwiringandcablesfromthemeterbeforeelectricarcweldingatanypointon apparatus. Failure to do so will result in damage to meter.
1. Selectmountinglocation(s)formeter(s).Themeteristobemountedfromtheoutsideofthepanelandwill needclearancebehindof3-15/16"widthby2-1/2"depth.
SeeFigure5forcutoutandscrewmountingdimensions.
WARNING:Themeterisasealedunitandthebezelshouldnotbedisassembledfromthecase.
2. Afterthecutoutandmountingholesarefinished,mountthemeterusingtheprovidedfasteners.
3. it is now time to connect the red power wire and, the Black ground wire, to the truck system.
CAUTION:Exercisecautionwhenworkingwiththeelectricalsystem.Disconnectcablefrombatterypositive terminalbeforeconnectingpowertometer.Seetruckmanualforadditionalinformationon electrical system.
CAUTION:Donotconnectmetertoflowsensorortransducercablesuntilpowerhookupisverifiedcorrect anddisplayisworking.Themeterhasreversepolarityprotection,butthetransducerandflow sensordonot,sincetheyrequireshielding.Theywillbegroundedtothepiping.Anymis-wiring could damage all components.
note: Itisessentialthattheconnectorsusedbewater-tighttopreventwaterfromwickingupwiresandinto the meter. always use sealed connectors or splices and the adhesive lined shrink tube provided, or other suitable connectors.
4. Using16or18AWGwire,connecttheRedpositivewiretothe12or24VDCpowersupply.ConnecttheBlack negative wire to a suitable ground.
SPECIFICATIONS:
Sensor Types
FlowMeter-Paddlewheel PressureTransducer-RatioMetric,0.5-4.5VDC,1/4"NPT,Male,0-42bar/0-4200kPa
Meter
operating Voltage 12 or 24 VDc MinimumOperationsVoltage-9.5VDC MaximumOperationsVoltage-32.0VDC OperatingCurrent-150mA DisplayType-LED Enclosure-NEMA4X OperatingTemperature-40˚F-140˚F
F. kPa/LPM POWER-UP OPTION
AkronFlow/PressureMeters,equippedwiththekPaorLPMselectionfeature,allowstheusertoselectthedisplayfunctiontoappearonpower-up.Tomakethisselection,usethefollowingprocedure.
Step 1- PressandholdBOTHbuttonssimultaneouslyforapproximately15seconds,untilthedisplayflashes“CAL” (calibration).Releasebuttons.Afterafewseconds“SIZE”willappearonthedisplayandallmodelightswill be lluminated.
5
SADDLE CLAMP ASSEMBLY
PRESSURE TRANSDUCER & CONNECTOR
Figure 3
Figure 4
6
Figure 2c
inle
ta
ttac
h Va
lve
this
Side
to p
ower
Su
pply
neg
ativ
e(Black)
(Red)
posit
ive
12-24VDC
3”HD21SF
5 3 / 4
7
Step 2- Scrolltheleftbuttonuntil“diSP”appears.
Step 3- Pressandreleaserightbutton.“PPPP”or“rrrr”willappear.“PPPP”signifieskPaand“rrrr”signifiesLPM.
Step 4-Pressandreleaseleftbuttontoselectwhatindicationisdesiredatpower-up.(kPaorLPM)
Step 5-Whenselectionismade,pressandreleaserightbuttontoenterandlock.
Systemwillthenalwaysreturntoyourselectionatpower-up.Tochangemodes,repeatSteps1-5.
SECTION IICALIBRATION INSTRUCTIONS
GENERAL-WhenunitisinCalibrationmode,allmodelightsonleftsideofdisplaywillbeilluminated.Aflashingmodelight indicateswhatfunctionisbeingcalibrated.
A. PRESSURE CALIBRATION
1. prior to calibration, the pressure transducer (Figure 4) must be installed into provided 1/4"NPTpressureport. typically in a valve discharge adapter or piping.
2. open the valve and drain to eliminate any pressure in line. 3. power up the meter. (Figure 5) 4. Afterthedisplayhasgonethroughasequenceofmessages,0 will appear on the display, or an error message mayappearifinthepressuremode.Also,amodelightwillappearontheleftsideofthedisplay.
The unit is now ready for Pressure Calibration
Step 1- PressandholdBOTHbuttonssimultaneouslyforapproximately15seconds,untilthedisplayflashesCAL (calibration).Releasebuttons.AfterafewsecondsSIZEwillappearondisplayandallmodelightswill be illuminated.
Step 2- PressandreleasetheLEFT button. PRES(pressure)willappearonthedisplay.
Step 3- PressandreleaseRIGHT button. the word “ZERO”shouldappearandPSImodelightwillflash.Note:If “ZERO” does not appear, the messages dEAd, EPrL, or EPrH may appear on the display. they indicate possibletransmissionerrorsbetweenthepressuretransducerandthemeter.(Seetroubleshooting guide-SectionIVtoresolve)
Step 4-With“ZERO”appearingondisplay,pressandreleaseright(pressure)button.ZEROwillstartflashing. Afteramoment,0 will appear on display.
note: on digital display, the word “ZERO”isdisplayedas“2Ero”.
Unitisnowreadytoprovidepressurereadingsforoperations.Thisprocedureneednotberepeatedunlessthetransducerormeter is replaced.
B. FLOW CALIBRATION - PIPE SIZE
Typicallyaneworrefurbishedapparatuswillbepre-calibratedusingpipesizemode.Thiscanalsobedonewithanyfieldconversion installing the akron Flow/pressure Systems.
Note:AkronFlow/Pressureunitscanbeinstalledintoexistingflowmeterinstallationsifasaddleclampinstallationexists.(TheAkronsaddleclampwilladapttoholesupto1-3/4"diameter.)Thepanelmeterwillalsofitinplaceofmostflowmeterorpressuregagecutouts.Moststandardpressuregagecutoutscanalsobeusedoreasilymodified.
Step 1- Powerupunit.Noflowisrequiredthroughsystem.
Step 2- Pressandholdbothbuttonssimultaneouslyfor15secondsuntilthedisplayflashesCAL(calibration) releasebuttons.AfterafewsecondsSIZE will appear on the display.
Step 3- Pressandreleaserightbutton,ifunithadpreviouslybeenprogrammedwithapipesize,thatsizewill appear.(SeeNote)
Step 4-Pressandreleaseleftbuttonuntildesiredpipesizeappears.
Step 5-Withcorrectpipesizedisplayed,pressandreleaserightbutton,thepipesizewillflash,then0 will appear ondisplay.Unitisnowcalibratedforpipesize.
note:Ifunitwasnotcalibratedwithpipesize,CUS (custom)willappear.Pressandreleaseleftbutton. FRE(frequency)willappear.Proceedwithsteps4&5.
8
PipeSize Display 2” 0020
2-1/2” 0025 3” 0030 4” 0040 5” 0050
Step 6-Theaccuracyoftheinstallationshouldbechecked,duetopossiblevariationsassociatedwithindividual installations.UseofanAkronStyle9015orFK-25orequiliventWaterFlowTestDeviceisrecommended asthebasisforcomparison.Ifrecalibrationisnecessaryusethecustomflowsettingcoveredinthe nextsection.
C. FLOW CALIBRATION - CUSTOM FLOW SETTINGS (HIGH/LOW)
Formaximumaccuracyofeachflowline,(especiallywithelbowsinline)itmaybedesirabletoseteachdischargelinetoagivenhighflow/lowflowrangeratherthanusingpipesizemode,thiscanbedoneutilizingawaterflowtestkit.(AULclassifiedWaterFlowTestDeviceisrecommended.)Useincludedflowchartprovided.(TABLEI)
Suggested Flow ranges
LineSize LPMLowFlow LPMHighFlow 2” 115 950 2-1/2” 230 2280 3” 600 4880 4” 950 7600 5” 950 7600
Toexplainthisprocedure,a2-1/2”linewitha230LPMlowflowand2280LPMhighflowwillbeused.Seenote followingthisprocedureforotherlinesizesandflows.
Step 1-Powerupunit.
Step 2-Pressandholdbothbuttonssimultaneouslyforapproximately15seconds,untilthedisplayflashesCAL (calibration).Releasebuttons.AfterafewsecondsSIZE will appear on the display.
Step 3- PressandreleaseleftbuttonuntilFLO(flow)appearsonthedisplay.
Step 4-Pressandreleaserightbutton.HIFL(highflow)willappearonthedisplay.
Step 5- Startuppumpandcommencedischargethroughselecteddischargelinewithwaterflowtestkit connectedaccordingtoinstructionsprovidedforitsuse.
Step 6-Bringflowupto2280LPMandmaintainasteadyflow.UsethePressure/FlowConversionSheetprovided withthewaterflowtestkit,orthesheetprovidedinthisprocedure.(TableI)
Step 7- Pressandreleaserightbutton.Themeterwillbegintocountpulsesupto1000.Itwillthenstopand HEND(highend)willappearondisplay.Ifsteadyflowisnotmaintainedduringpulsecounting,press andreleaseleftbutton.HIFL will appear on the display. press and release right button to recollect1000pulses.)
Step 8-Afterensuringthatasteadyreadinghasbeenmaintainedthroughthecountsequence,pressandrelease right button to accept pulse data. 0000 willappearonthedisplay,withfarleft0flashing.
Step 9-Sincethedisplaywillshowfourcharactersandthehighflowis2280,presstheleftbuttonuntil2appears.
Step 10-Pressandreleaserightbutton.Thesecond0fromleftwillbeginflashing.
Step 11-Pressandreleasetheleftbuttonuntil2appears.
Step 12-Pressandreleaserightbutton.Thethird0fromleftwillbeginflashing.Displayshouldread2200. press theleftbuttonuntil8appears.
Step 13-Pressandreleaserightbutton.Theright0willbeginflashing.Thedisplayshouldread2880.
Step 14-Pressandreleaserightbutton.2880willflash.
Ifotherthan2880isdesired,usetheleftbuttontochangenumbersandrightbuttontochangefields,as steps9-13explain.
9
Figure 2b
Att
ach
Valv
e Th
is
Side
Inle
t
4” P
20SF
To P
ower
Su
pply
Neg
ativ
e(B
lack
)
(Red
)Po
siti
ve
12-2
4 V
DC
3 15
/ 16
TYPI
CAL
VALV
E IN
STA
LLAT
ION
10
Figure 2a
ATTACH
VALVE
THIS
SiD
eINLET
2”P20SF
to p
ower
Su
pply
neg
ativ
e(Black)
(Red)
posit
ive
12-24VDC
3 5/ 3
2
TYPI
CAL
VALV
E IN
STA
LLAT
ION
11
Step 15-Ifvalueiscorrect,pressandreleaserightbutton. LOFL(lowflow)willnowappearonthedisplay.Using thePressure/FlowConversionSheetprovidedwiththewaterflowtestkit,holdflowat230LPM and maintain steadyflow.
Step 16-Pressandreleaserightbutton.Themeterwillbegintocountpulsesto1000.Note:TheLowflowpulse collectionwilltakelongerthanhighflowduetolowervelocity.
Step 17-When1000pulseshavebeenreached,thecountingwillstop.LEND(lowend)willappearondisplay.
Step 18-Pressandreleaserightbutton.0000willappearonthedisplay.Proceedasyoudidinsteps9-13,display should show 0230afterstep12using0230insteadof2280.
Step 19-Pressandreleaserightbutton.0230 willflash.
Step 20-Pressandreleaserightbutton.CAL(calibration)willflashmomentarily,indicatingthatthemeteris calibrated. Display will then show 0 with a mode indicator light.
Step 21 -VerifyFlowMetercalibrationbycomparingflowstoaWaterFlowTestDevice.
Unitisnowreadyforuse
NOTE: Thehighflowsettingsshouldbe7-10timesthelowflowsettings.
SECTION IIIOPERATION INSTRUCTIONS
A. GENERAL
Theseinstructionsdescribefeaturesandoperationalstepsforgeneralserviceafterthesystemissetupandcalibrated.(SeeinstallationandcalibrationsectionsI&IIifthishasnotbeendone.)
Themeterconsistsofthedisplayscreenandtwooperationbuttonslocateddirectlybeneaththedisplay.(SeeFigure6)
Whenunitispowered,therearethreeredLEDmodelightsontheleftsideofdisplay.Eachoftheselightsalignwithparticularfunctionmarkedonthebezelface.(SeeFigure6)Theywillonlybeilluminatedindividually,exceptduringpowerupsequenceand calibration.
Theunithasfouroperationfunctions:
1. Flow LPM-ActualLitersperminuteflowing.(Willreadinsingleliterincrementsto1200.Above1200,10liter incrementswillappear.)
2. Flow TOTAL-Totallitersflowedsinceunitwaspoweredup.(FiguredisplayedmustbemultipliedX100togettotal)
3. pressure bar or kPa.
4.LEDINTENSITY-Brightnessofdisplay.
B. OPERATION (SeeFigure6)
Atthetimeofpowerup,allthreemodelightswillappearwithfourZEROS.Insequenceanumbervaluewillappear,followedbyLI, bar or kPa, CUS or PIPE andfinally0.Thiswillbecompleteinafewseconds.
Theunitisnowreadyforoperation
TO READ:
LPM-Pressandreleaseleft(flow)buttontoplacemodelightonLPM. actual LPM will appear on display.
TOTAL FLOW-Pressandreleaseleft(flow)buttontoplacemodelightonTOTAL.Thefiguresdisplayedmustbe multipliedby100togivelitersflowed.
bar or kPa-Pressandreleaseright(pressure)buttontoplacemodelightonbarorkPa.Actualpressurewillappear on display.
LED INTENSITY-TobrightenordimLED,pressandholdleftbuttonuntildesiredbrightnessisdisplayed.
RefertoSectionIV,Troubleshootingguideifproblemsoccur.
12
SECTION IVTROUBLESHOOTING GUIDE
PROBLEM
Display does not illuminate
LPMshows0-waterisflowing
dEAD,EprL,EprHappears on display
LEDDim
LENSFoggy
CHECK
1. power connection2. power Source
1. cable connections2.Shutdownpump-removesensor- spin paddlewheel3.Removesensorfromcableconnect direct to meter spin paddlewheel
1. check pressure transducer connections2. Shutdown pump remove transducer and connect directly to meter
ShoulddissipateshortlyafterusewithLED’slighted.
ACTION
Ifproblemsexistwithpowercheck,correctthem.ReplaceMeterifpowercheck is ok.
Ifdisplayshowsreading,replacecable.Ifnot, replace sensor.
Ifdisplayclears,replacecable.Ifitdoesnot, replace transducer.
Holdleftbuttondownfor5seconds.Should brighten.
Willcausenoharm.Thiswillhappenifmeter is not assembled in a humidity freearea.
dEAd- Hardwareproblem.Probablymeter.EprL- 1.Shorttoground.Checkcable.
2.NotZEROEDat0barorkPa. 3.CheckforvacuuminlineEprH- 1.Transducernotinstalled.
2. Short to power. check cable. 3.NotZEROEDto0barorkPa.
NOTE:Eddycurrentsindischargemanifoldsystemsmaycauseflowsensorpaddlewheelstomoveandsendasignaltothemeterdisplay.Thiscouldregisteraflowreadingwhenthevalveisactuallyclosed.Toeliminatethisfalsereading,wehaveinitiatedaprogramforourflowmetersthatwillnotdisplayareadinguntilaminimumflowisattained.Basedondischargelinesize,theminimumshavebeenestablishedbasedonlogicalflowsforeachsizeline.
LINE SIZE DISPLAY WILL READ ABOVE 2” 75LPM 2 1/2” 95LPM 3” 113LPM 4” 300LPM 5” 340LPM
13
WARRANTY AND DISCLAIMER: We warrant Akron Brass products for a period of five (5) years after purchase against defects in materials or workmanship. Akron Brass will repair or replace product which fails to satisfy this warranty. Repair or replacement shall be at the discretion of Akron Brass. Products must be promptly returned to Akron Brass for warranty service.
We will not be responsible for: wear and tear; any improper installation, use, maintenance or storage; negligence of the owner or user; repair or modification after delivery; damage; failure to follow our instructions or recommendations; or anything else beyond our control. WE MAKE NO WARRANTIES, EXPRESS OR IMPLIED, OTHER THAN THOSE INCLUDED IN THIS WARRANTY STATEMENT, AND WE DISCLAIM ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE. Further, we will not be responsible for any consequential, incidental or indirect damages (including, but not limited to, any loss of profits) from any cause whatsoever. No person has authority to change this warranty.
REvISED: 7/11
ISO 9001 REGISTERED COMPANY
PHONE:330.264.5678or800.228.1161IFAX:330.264.2944or800.531.7335Iakronbrass.com
©AkronBrassCompany.2011Allrightsreserved.NoportionofthiscanbereproducedwithouttheexpresswrittenconsentofAkronBrassCompany.
SECTION VREPLACEMENT PARTS
FLOW SENSOR
5”
2-11/16”REF.
Item Part Number
5’Cable 93000013
10’Cable 93000002
20’Cable 93000014
50’Cable 93000015
transducer 93000030
Meter(kPa) 93000005
Meter(bar) 93000010
Sensor(Flow) 93000004
2”Saddle 93000006
21/2”Saddle 93000007
3”Saddle 93000008
4”Saddle 93000011
5”Saddle 93000016