submittal chiller cop 6.02

3
Water Cooled Centrifugal Chiller   Page 1 of 3  Job Information Technical Data Sheet Job Name CEmpresal La Molina Date 8/1/2014 Submitted By Fernando Mejia Software Version 09.61 Unit Tag CH1CH2.30.414 Starter FPA# AUTO_FPA_EXPORT  Unit Overview Model Number Capacity ton NPLV kW/ton Voltage Drive Type ASHRAE 90.1 WSC087M 500.0 0.367 380 V / 60 Hz VFD/UM (060YMW) '10  Unit Model Number: WSC087MBC49U/E3012BE2**/C2612BLYY2*****/R134BAABMU Approval: AHRI and ETL / cETL Vessel Code: ASME Compressor Quantity Capacity Control Refrigerant Type Refrigerant Weight Oil Cooler Type 1 Inlet Guide Vanes R134a 1114 lb Water Cooled Evaporator Entering Fluid Temperature Leaving Fluid Temperature Fluid Type Actual Fluid Flow Minimum Fluid Flow 53.99 °F 44.00 °F Water 1200.00 gpm 267.2 gpm Length Diameter Number of Passes Tube Fouling Factor Material Wall Thickness 12 ft 30 in 2 Copper 0.025 in 0.00010 °F.ft².h/Btu Condenser Entering Fluid Temperature Leaving Fluid Temperature Fluid Type Fluid Flow 85.00 °F 93.60 °F Water 1600.00 gpm Length Diameter Number of Passes Tube Fouling Factor Material Wall Thickness 12 ft 26 in 2 Copper 0.025 in 0.00025 °F.ft².h/Btu  Unit Performance Design Capacity ton Input kW Efficiency kW/ton RLA A  NPLV kW/ton Part Load Efficiency Evaporator Fluid Condenser Fluid 75% kW/ton 50% kW/ton 25% kW/ton Pressure Drop ft HO Entering Temperature °F Pressure Drop ft HO Leaving Temperature °F 500.0 291.9 0.584 490 0.367 0.427 0.314 0.413 25.4 53.99 23.2 93.60 

Upload: juan-yenque

Post on 06-Dec-2015

11 views

Category:

Documents


2 download

DESCRIPTION

CHiller COP 6.02

TRANSCRIPT

Page 1: Submittal Chiller COP 6.02

Water Cooled Centrifugal Chiller 

  Page 1 of 3

 

Job Information  Technical Data Sheet 

Job Name  C‐Empresal La Molina 

Date  8/1/2014

Submitted By  Fernando Mejia 

Software Version  09.61 

Unit Tag  CH‐1‐CH‐2.30.4‐14 

Starter FPA#  AUTO_FPA_EXPORT  

Unit Overview 

Model Number  Capacity ton 

NPLV kW/ton 

Voltage Drive Type  ASHRAE 90.1

WSC087M  500.0  0.367  380 V / 60 Hz VFD/UM (060YMW) 

'10 

 

Unit 

Model Number:  WSC087MBC49U/E3012‐BE‐2**/C2612‐BLYY‐2*****/R134‐BAABM‐U 

Approval:  AHRI and ETL / cETL Vessel Code:  ASME 

Compressor Quantity  Capacity Control  Refrigerant Type Refrigerant Weight  Oil Cooler Type

1  Inlet Guide Vanes R134a 1114 lb  Water Cooled

Evaporator 

Entering Fluid Temperature  Leaving Fluid Temperature Fluid Type Actual Fluid Flow  Minimum Fluid Flow

53.99 °F  44.00 °F  Water  1200.00 gpm  267.2 gpm 

Length  Diameter  Number ofPasses 

Tube Fouling Factor

Material Wall Thickness 

12 ft  30 in  2 Copper 0.025 in  0.00010 °F.ft².h/Btu

Condenser

Entering Fluid Temperature  Leaving Fluid Temperature Fluid Type Fluid Flow

85.00 °F  93.60 °F  Water  1600.00 gpm 

Length  Diameter  Number ofPasses 

Tube Fouling Factor

Material Wall Thickness 

12 ft  26 in  2 Copper  0.025 in  0.00025 °F.ft².h/Btu 

 

Unit Performance 

Design

Capacity ton 

Input kW 

Efficiency kW/ton 

RLA A  

NPLVkW/ton 

Part Load Efficiency Evaporator Fluid  Condenser Fluid

75%kW/ton 

50%kW/ton 

25%kW/ton 

Pressure Drop ft H₂O 

Entering Temperature

°F 

Pressure Drop ft H₂O 

LeavingTemperature

°F 

500.0  291.9  0.584  490  0.367  0.427  0.314  0.413  25.4  53.99  23.2  93.60 

Page 2: Submittal Chiller COP 6.02

Water Cooled Centrifugal Chiller 

  Page 2 of 3

 

Unit Performance 

Performance Points Rated at AHRI Condenser Relief

Point #  % of Design Load 

Capacity ton 

Input kW 

Efficiency kW/ton 

RLAA  

Evaporator Fluid Condenser Fluid

Flowgpm 

Temperature Pressure Drop ft H₂O 

Flow gpm 

Temperature Pressure Drop ft H₂O 

Entering°F 

Leaving°F 

Entering°F 

Leaving°F 

1  100.0  500.0  291.9  0.584  490  1,200.00  53.99  44.00  25.4  1,600.00  85.00  93.60  23.2 

2  90.0  450.0  233.0  0.518  404  1,200.00  52.99  44.00  25.4  1,600.00  81.00  88.61  23.5 

3  80.0  400.0  182.6  0.456  334  1,200.00  51.99  44.00  25.5  1,600.00  77.00  83.65  23.9 

4  70.0  350.0  139.5  0.399  277  1,200.00  50.99  44.00  25.5  1,600.00  73.00  78.72  24.3 

5  60.0  300.0  104.4  0.348  232  1,200.00  49.99  44.00  25.6  1,600.00  69.00  73.83  24.7 

6  50.0  250.0  78.5  0.314  201  1,200.00  49.00  44.00  25.6  1,600.00  65.00  68.99  25.1 

7  40.0  200.0  67.7  0.338  188  1,200.00  48.00  44.00  25.7  1,600.00  65.00  68.19  25.1 

8  30.0  150.0  57.2  0.381  175  1,200.00  47.00  44.00  25.7  1,600.00  65.00  67.40  25.2 

9  20.0  100.0  46.1  0.461  162  1,200.00  46.00  44.00  25.7  1,600.00  65.00  66.61  25.2 

10  10.0  50.0  32.0  0.640  145  1,200.00  45.00  44.00  25.8  1,600.00  65.00  65.80  25.3 

 

Service Data 

Service Points Rated at AHRI Condenser Relief

Point #  Superheat Δ °F 

Subcooling Δ °F 

Evaporator Fluid Condenser Fluid

Temperature°F 

Pressurepsig 

Velocityft/s 

Temperature °F 

Pressurepsig 

Velocityft/s 

1  1.0  7.7  42.8  37.8  8.1  95.2  114.4  8.2 

2  1.0  7.0  42.9  38.0  8.1  90.1  104.5  8.2 

3  1.0  6.3  43.1  38.1  8.1  85.0  95.2  8.2 

4  1.0  5.6  43.2  38.2  8.1  79.9  86.6  8.2 

5  1.0  4.9  43.3  38.3  8.1  74.9  78.5  8.2 

6  1.0  4.1  43.4  38.4  8.1  69.9  70.9  8.2 

7  1.0  3.4  43.5  38.6  8.1  68.9  69.5  8.2 

8  1.0  2.7  43.6  38.7  8.1  67.9  68.1  8.2 

9  1.0  1.8  43.8  38.8  8.1  67.0  66.8  8.2 

10  1.0  0.9  43.9  38.9  8.1  66.0  65.4  8.2 

 

Physical 

Evaporator 

Inlet Location  Header Type  Header Material Tube Sheet Material  Design Pressure (Waterside)

Right  Dished, Grooved  Carbon Steel Carbon Steel  150 psig  

Condenser 

Inlet Location  Header Type  Header Material Tube Sheet Material  Design Pressure (Waterside)

Right  Dished, Grooved  Carbon Steel Carbon Steel  150 psig  

 

Electrical 

Voltage  RLA  LRA Power Connection 

Power Factor MCA  MOCP Inrush Value

Correction Corrected

380 V / 60 Hz / 3 Phase  490 A  4320 A Single Point 

Inherent  0.96  619 A  864 A  588 A 

 

Drive  

Type  Model  Location Harmonic Distortion Enclosure Type  Motor Protection

VFD  060YMW  Unit Mounted  Standard  NEMA 1  Standard

 

Page 3: Submittal Chiller COP 6.02

Water Cooled Centrifugal Chiller 

  Page 3 of 3

 

Sound  (without insulation) 

Sound Pressure

63 Hz  125 Hz  250 Hz  500 Hz  1 kHz 2 kHz 4 kHz 8 kHz Overall  75% Load 50% Load 25% Load

69.0  67.0  69.0  73.0  77.0 80.0 80.0 75.0 85.5  83.0  83.0 84.0

Sound Pressure (dB) measured in accordance with ANSI/AHRI Standard 575‐2008 (‘A’ weighted)

 

Options 

Basic Unit 

Packaging:  Wood Skid only 

Insulation 

Thermal:  0.75" on evap shell, suction piping, compressor inlet & motor barrel 

Control 

Communication Protocol:  BACnet MS/TP  

Warranty 

Unit Startup:  None Required 

Standard Warranty:  First Year Entire Unit Parts only (no Labor)Delayed Warranty Start:  None (Startup 12‐18 months after ship date)

 

AHRI Certification 

 

Certified in accordance with the AHRI Water‐Cooled Water Chilling Packages Using Vapor Compression Cycle Certification Program, which is based on AHRI Standard 550/590 (I‐P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org 

Notes 

1. Above RLA, MCA and MOCP  values are per Compressor.2. Performance kW values are total kW, unless noted otherwise. 3. Minimum  flow  is based upon standard condenser water relief and not  increased  lift due to constant condenser water 

temperature. 4. WSC/WDC 063,079,087,100,113,126 models utilize water‐cooled oil cooler as standard equipment. 5. Use only copper supply wires with ampacity based on 75°C conductor rating. (Exception: for equipment rated over 2000 

volts, 90°C or 105°C  rated  conductors  shall be used).   Connections  to  terminals must be made with  copper  lugs and copper wire. 

 

Accessories 

Optional

Part Number  Description 

017503301  Flow Switch, Paddle, 3‐8" Dia, 150PSI, Qty 1 (Not WDC)