Job Name HOTEL SECRETS AKUMAL
UMA J01Mark for
Date July 15, 2014
Unit Parameters
Unit Size: 15
Insulation: 1" 1.5# Tuf-Skin II Double Wall
Hand: Right
No Export Crate
Controls: No Product Integrated Controls
ANG Angle Filter Section
2in Pleated MERV8 Filters - kit
(9) 16in. x 20in.
LA Horizontal Cooling (LFA) Coil/Fan Section
Fan RPM: 716
Drive
Motor HP: 3
Voltage: 230/460 3 Phase 60Hz
Efficiency: Premium
Enclosure: ODP
RPM: 1800
Manufacturer - Generic
Frame Size - 182T
Motor Shaft Diameter (in.) - 1.125
Full Load Amps - 7.8/3.9
MCA - 9.7/4.9
MOCP - 15/6
Efficiency - 89.5%
Discharge: Top Horiz. Front
CW 14.9 sq.ft. 6 Rows 11 FPI Full Circuit
0.016 in. Tube Wall Thickness
Weights and Dimensions
(LxWxH in ft in) 7' 9" x 5' 5" x 3' 4" **
Dry 1096 LB ** Wet 1180 LB **
6.34
SUBJECT TO CHANGE WITHOUT NOTICE Per Price Pages Dated 01/25/11
-
Job Name HOTEL SECRETS AKUMAL
UMA J01Mark for
Date July 15, 2014
Weights and Dimensions are approximate. Weights include base unit weight, coils (wet & dry), fans and
fan motors, and other components, but does not include filters, drives and skids. Approximate dimensions are
provided primarily for shipping purposes. Shipping skids are not included.
All filter media efficiency ratings are for the filter media only.
6.34
SUBJECT TO CHANGE WITHOUT NOTICE Per Price Pages Dated 01/25/11
-
v6.34 02/11/14 www.carrier.com
Cooling Application's Balance Criteria: Fluid Flow
Coil Model Carrier 28NARow / FPI / Circ 6 / 11 / FL
Face Area Type LargeCoil Face Area 14.90 sqftFace Velocity 436.2 fpmTube Material Al / CuTube Diameter 0.5 inTube spacing: Stf x Str 1.25 x 0.781 inTube Wall Thickness 0.016 in
Actual Airflow 6500 CFMSite Altitude 0 ft
Total Cooling Capacity 293.41 MBHSensible Cooling Capacity 156.81 MBHFluid Flow Rate 41.9 gpmFluid Pressure Drop 3.4 ft wg
Fluid Velocity 2.2 ft/sEntering Fluid Temperature 42.00 FLeaving Fluid Temperature 56.00 FFluid Temperature Rise 14.0 FEntering Air Dry Bulb 77.00 FEntering Air Wet Bulb 68.90 FEntering Air Enthalpy 33.01 BTU/lbLeaving Air Dry Bulb 54.94 FLeaving Air Wet Bulb 54.69 FLeaving Air Enthalpy 23.0 BTU/lb
Air Friction 0.76 in wg
Brine FWBrine Concentration 0 %Fouling Factor 0.0 (hr-sqft-F)/BTU
NOTE: Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory (www.ahridirectory.org).
HOTEL SECRETS AKUMALUMA J01
Project:Tag:
Chilled Water Coil Performance Summary
-
v6.34 02/11/14 www.carrier.com
Fan Model 39L
Unit Size 15
Fan Type LA (For LFA Clg. Coils)
Inlet Guide Vanes No
Actual Airflow, CFM 6500
Site Altitude, ft 0
Upstream Ext. Static, in wg 0.00
Downstream Ext. Static, in wg 0.45
Cooling Coil Static, in wg 0.76
Heating Coil Static, in wg 0.00
Other Losses, in wg 0.00
Total Accessory Static, in wg 0.11
Total Static Pressure, in wg 1.32
Fan RPM 701
Fan BHP 2.4
Acoustic Data:
CasingInletDischarge
807886 63 Hz
746886 125 Hz
656382 250 Hz
636383 500 Hz
585774 1000 Hz
565869 2000 Hz
505063 4000 Hz
453955 8000 Hz
Accessories:
(1) ANG Pleated 2 inch MERV 8 [0.11]
HOTEL SECRETS AKUMALUMA J01
Project:Tag:
Supply Fan Performance Summary
-
Job Name HOTEL SECRETS AKUMAL
UMA J02Mark for
Date July 15, 2014
Unit Parameters
Unit Size: 12
Insulation: 1" 1.5# Tuf-Skin II Double Wall
Hand: Right
No Export Crate
Controls: No Product Integrated Controls
ANG Angle Filter Section
2in Pleated MERV8 Filters - kit
(6) 16in. x 20in.
LA Horizontal Cooling (LFA) Coil/Fan Section
Fan RPM: 1008
Drive
Motor HP: 5
Voltage: 230/460 3 Phase 60Hz
Efficiency: Premium
Enclosure: ODP
RPM: 1800
Manufacturer - Generic
Frame Size - 184T
Motor Shaft Diameter (in.) - 1.125
Full Load Amps - 13/6.5
MCA - 16.2/8.1
MOCP - 25/10
Efficiency - 89.5%
Discharge: Top Horiz. Front
CW 11.2 sq.ft. 6 Rows 14 FPI Full Circuit
0.016 in. Tube Wall Thickness
Weights and Dimensions
(LxWxH in ft in) 6' 4" x 5' 5" x 2' 8" **
Dry 938 LB ** Wet 1002 LB **
6.34
SUBJECT TO CHANGE WITHOUT NOTICE Per Price Pages Dated 01/25/11
-
Job Name HOTEL SECRETS AKUMAL
UMA J02Mark for
Date July 15, 2014
Weights and Dimensions are approximate. Weights include base unit weight, coils (wet & dry), fans and
fan motors, and other components, but does not include filters, drives and skids. Approximate dimensions are
provided primarily for shipping purposes. Shipping skids are not included.
All filter media efficiency ratings are for the filter media only.
6.34
SUBJECT TO CHANGE WITHOUT NOTICE Per Price Pages Dated 01/25/11
-
v6.34 02/11/14 www.carrier.com
Cooling Application's Balance Criteria: Fluid Flow
Coil Model Carrier 28NARow / FPI / Circ 6 / 14 / FL
Face Area Type LargeCoil Face Area 11.20 sqftFace Velocity 491.1 fpmTube Material Al / CuTube Diameter 0.5 inTube spacing: Stf x Str 1.25 x 0.781 inTube Wall Thickness 0.016 in
Actual Airflow 5500 CFMSite Altitude 0 ft
Total Cooling Capacity 260.13 MBHSensible Cooling Capacity 138.08 MBHFluid Flow Rate 37.1 gpmFluid Pressure Drop 4.4 ft wg
Fluid Velocity 2.6 ft/sEntering Fluid Temperature 42.00 FLeaving Fluid Temperature 56.00 FFluid Temperature Rise 14.0 FEntering Air Dry Bulb 77.00 FEntering Air Wet Bulb 68.90 FEntering Air Enthalpy 33.01 BTU/lbLeaving Air Dry Bulb 54.04 FLeaving Air Wet Bulb 53.90 FLeaving Air Enthalpy 22.5 BTU/lb
Air Friction 0.98 in wg
Brine FWBrine Concentration 0 %Fouling Factor 0.0 (hr-sqft-F)/BTU
NOTE: Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory (www.ahridirectory.org).
HOTEL SECRETS AKUMALUMA J02
Project:Tag:
Chilled Water Coil Performance Summary
-
v6.34 02/11/14 www.carrier.com
Fan Model 39L
Unit Size 12
Fan Type LA (For LFA Clg. Coils)
Inlet Guide Vanes No
Actual Airflow, CFM 5500
Site Altitude, ft 0
Upstream Ext. Static, in wg 0.00
Downstream Ext. Static, in wg 0.62
Cooling Coil Static, in wg 0.98
Heating Coil Static, in wg 0.00
Other Losses, in wg 0.00
Total Accessory Static, in wg 0.14
Total Static Pressure, in wg 1.74
Fan RPM 969
Fan BHP 3.0
Acoustic Data:
CasingInletDischarge
848290 63 Hz
787290 125 Hz
696786 250 Hz
646484 500 Hz
666582 1000 Hz
626475 2000 Hz
575770 4000 Hz
534763 8000 Hz
Accessories:
(1) ANG Pleated 2 inch MERV 8 [0.14]
HOTEL SECRETS AKUMALUMA J02
Project:Tag:
Supply Fan Performance Summary