supply air temperature and pressure setpoint reset … air temperature and pressure setpoint reset...

33
Supply Air Temperature and Pressure Setpoint Reset in VAV Systems Based on Zone Demand Steven T. Taylor, PE Reinhard Seidl, PE Taylor Engineering Alameda, CA

Upload: ngothuy

Post on 13-Mar-2018

226 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Supply Air Temperature and Pressure Setpoint Reset in VAV Systems Based on Zone Demand

Steven T. Taylor, PEReinhard Seidl, PE Taylor Engineering Alameda, CA

Page 2: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Outline

Supply Air Temperature and Static Pressure Setpoint Reset in VAV Systems •Control Strategies•Energy impacts•Control SequencesCommissioning•Tuning• “Rogue” Zones

Page 3: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Static Pressure Setpoint Reset

Page 4: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Fan Energy at Varying SP Setpoints

0%

20%

40%

60%

80%

100%

120%

0 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%

Percent Fan CFM

Perc

ent F

an k

W SP setpoint = TSPSP setpoint = TSP*.75SP setpoint = TSP/2SP setpoint = TSP/3SP setpoint = 0

Surge Region

Page 5: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Real Fan Systems Many Hours At Low Loads

0

0.5

1

1.5

2

2.5

3

3.5

4

0 20,000 40,000 60,000 80,000 100,000 120,000 140,000Total CFM (SF-1 + SF-2)

Pres

sure

Dro

p A

cros

s Fa

n ("

H2O

)

Actual DataPerfect System Curve (i.e. SP reset)Design Point (145,000 CFM at 4.0")Likely Actual System Curve (No SP Reset)

Page 6: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Static Pressure Setpoint Reset Control Logic Options

Option 1: Reset static pressure setpoint based on PID Loop on VAV damper positionOption 2: Reset static pressure setpoint using “Trim & Respond”based VAV damper position or airflow demand

Page 7: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Best Choice: Trim and Respond

Advantages•Easier to tune•Can “respond” more quickly than

“trim”•Does not require knowledge of

damper position•Easier to ignore “rogue” zones

Page 8: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Trim & Respond SP Setpoint Reset Logic

Static pressure setpoint shall be reset using trim and respond logic within the range 0.15 inches to 1.5 inches. When fan is off, freeze setpoint at the minimum value (0.15 inches). While fan is proven on, every 2 minutes, decrease the setpoint by 0.04 inches if there two (adjustable) or fewer pressure requests. If there are more than two (adjustable) pressure requests, increase the setpoint by 0.04. Where VAV zone damper position is known, a pressure request is generated when any VAV or underfloor damper served by the system is wide open. Where VAV zone damper position is unknown, a pressure request is made when the ratio of the zone’s actual supply airflow to supply airflow setpoint is less than 90%. Adjustable to limit

dominance of rogue zonesSet by TAB Contractor

Page 9: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Trim & Respond SP Setpoint Reset Logic

Example of heating fan on dual duct system, without calls for heating.

System runs close to minimum: 75°F for temperature SP and 0.24”wg for pressure SP.

Note that actual temperature is much higher than SP, this is because of the mechanics of the burner staging, not because of the reset logic.

Page 10: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Trim & Respond SP Setpoint Reset Logic

Example of heating fan on dual duct system, with calls for heating. Note that calls for heat (3) and calls for pressure (3) coincide here, but don’t necessarily do this.

System runs at maximum: 95°F for temperature SP and 1.5”wg for pressure SP.

Note that, again, actual temperature is much higher than SP, this is because of the mechanics of the burner staging, not because of the reset logic.

Page 11: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Variations on this Sequence

A damper position (valve position, loop output, etc.) of 80% counts as one request, while a position of 95% counts as two requests.The response rate is a function of the number of requests, e.g. response = 0.04” times the number of requests.

Page 12: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Tuning – Unstable Control

y = 0.6709x + 0.2656R2 = 0.5971

0

0.2

0.4

0.6

0.8

1

1.2

1.4

0 0.2 0.4 0.6 0.8 1 1.2 1.4

Actual Static Pressure

Stat

ic P

ress

ure

Setp

oint

Page 13: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Tuning – Stable Control

Page 14: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Supply Air Temperature Reset

Page 15: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Supply Air Temperature Control Optimization

Analyzed for:• Mild California climates• Chilled water plant at building (not central)• Variable speed fans

Probably applicable to more extreme climates as well• Humid climates should use low end of

outdoor air temperature reset ranges

Page 16: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Impact of SAT on Energy Usage Sacramento Office Building

0

5

10

15

20

25

3/4

6:00 3/4

7:00 3/4

8:00 3/4

9:00

3/4

10:0

0

3/4

11:0

0

3/4

12:0

0

3/4

13:0

0

3/4

14:0

0

3/4

15:0

0

3/4

16:0

0

3/4

17:0

0

3/4

18:0

0

3/4

19:0

0

Sou

rce

Ene

rgy,

B

tu/s

f

0

20

40

60

80

100

Out

door

Air

Tem

pera

ture

, F

50 55 60 OAT

0

5

10

15

20

25

8/18

6:00

8/18

7:00

8/18

8:00

8/18

9:00

8/18

10:0

0

8/18

11:0

0

8/18

12:0

0

8/18

13:0

0

8/18

14:0

0

8/18

15:0

0

8/18

16:0

0

8/18

17:0

0

8/18

18:0

0

8/18

19:0

0

Sou

rce

Ene

rgy,

B

tu/s

f

0

20

40

60

80

100

Out

door

Air

Tem

pera

ture

, F

In very hot weather, increased fan energy more than eliminates savings in compressor energy (green line above blue line)

In cool weather, supply temperature reset saves significant energy (longer use of economizer and no excessive fan energy as result of low SAT)

Page 17: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Recommended SAT Reset Logic

Reheat Economizer SAT Logic

None None Constant SAT at design (~55ºF)

Low(e.g. DFDD,

FPU)Yes

Constant SAT at design. Allow to float up by locking out cooling until zone request indicates need for CHW

Medium to High

(e.g. VAVRH)

Yes

Reset by zone cooling demand during cool weather (<55ºF to 60ºF), then ramp down to design SAT in warm weather (>60ºF to 70ºF)

Page 18: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Reheat System SAT Reset Logic

55 65

55

70

60

75

65

Outdoor Air Temperature

Supp

ly Ai

r Tem

pera

ture

Set

poin

t

Tmin = 53F

SAT reset by demandwithin this range

Page 19: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

VAV Reheat System SAT Reset Logic

During occupied mode, the setpoint is reset from T-min (53°F) when the outdoor air temperature is 70°F and above, proportionally up to T-max when the outdoor air temperature is 60°F and below. T-max shall be reset using trim and respond logic within the range 55°F to 65°F. When fan is off, freeze T-max at the maximum value (65ºF). While fan is proven on, every 2 minutes, increase the setpoint by 0.2ºF if there are two (adjustable) or fewer zone cooling requests. If there are more than two (adjustable) cooling requests, decrease the setpoint by 0.3ºF. A cooling request is generated when the cooling loop of any zone served by the system is >99%. Lower if reheat reduced

using “dual maximum” logic and central plant

Adjustable to limit dominance of rogue zones

Page 20: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Performance – Oversized Zones

52

54

56

58

60

62

64

52 54 56 58 60 62 64

Outdoor Air Temperature (oF)

Sup

ply

Air

Tem

pera

ture

Set

poin

t (oF

)

50

55

60

65

70

75

80

85

90

95

7/280:00

7/2812:00

7/290:00

7/2912:00

7/300:00

7/3012:00

7/310:00

7/3112:00

8/1 0:00 8/112:00

Tem

pera

ture

(oF)

0

1

2

3

4

5

6

7

8

9

Num

ber

of C

oolin

g R

eque

sts

SAT SetpointOutdoor Air TemperatureCooling Requests

52

54

56

58

60

62

64

52 54 56 58 60 62 64

Outdoor Air Temperature (oF)

Sup

ply

Air

Tem

pera

ture

Set

poin

t (oF

)

Page 21: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Performance – Rogue Zones

52

54

56

58

60

62

64

52 54 56 58 60 62 64 66 68

Outdoor Air Temperature (oF)

Supp

ly A

ir T

empe

ratu

re S

etpo

int (

oF)

Page 22: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Rogue Zone

0

20

40

60

80

100

6/27/06 3:00 6/27/06 6:00 6/27/06 9:00 6/27/06 12:00 6/27/06 15:00 6/27/06 18:00 6/27/06 21:00

Cool

ing

Loop

Out

put (

%)

VAV2-20 VAV2-21 VAV2-11 VAV2-22 VAV2-23 VAV2-24 VAV2-25VAV2-27 VAV2-30 VAV2-31 VAV2-6 VAV2-7 VAV2-28 VAV2-9

Page 23: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Rogue Zones

Causes• Undersized zone/unexpected loads• Thermostat setting too low• Duct design problem – high pressure drop

fitting or duct section

Page 24: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Handling Rogue Zones

Exclude them from reset sequence• May result in temperature problems in

these zones• Not advised for boss’ office

Limit thermostat setpoint adjustmentsFix duct restrictions/sizing issuesAdd auxiliary cooling to augment VAV

Page 25: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Supply Air SP vs Duct Static SPHighest temp. reset occurs at warmest point of the day. Note that pressure remains high almost all day, possibly rogue zone

Pressure setpoint (blue)

Temp. setpoint (red)

Outside Air Temp. (green)

Page 26: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Supply Air SP vs Duct Static SP

Same building, next day – completely different pictureboth resets now working – might look like they are running in “counter-phase”, but incidental

Pressure setpoint (blue)

Temp. setpoint (red)

Outside Air Temp. (green)

Page 27: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Supply Air SP vs Duct Static SP

Same building, next day – now both resets almost run “in phase”

Pressure setpoint (blue)

Temp. setpoint (red)

Outside Air Temp. (green)

Page 28: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Poor Supply Air Temp controlActual temperature does not adhere to setpoint

Actual temperature (green)

Temperature setpoint (orange)

Page 29: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Poor Supply Air Temp controlTemp. setpoint does not appear to follow prescribed logic, and actual temperature does not adhere to setpoint)

Actual temperature (green)

Temperature setpoint (orange)

Temperature setpoint per sequence of operations (red)

Page 30: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Poor Supply Air Temp controlPressure setpoint (blue)

Temp. setpoint (red)

Actual Temp. (orange)

Outside Air Temp. (green)

Page 31: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Pressure control

Number of pressure requests – when these drop below 5 requests, dP setpoint is lowered

Pressure setpoint (signal stays high even when requests drop, because more than 5 requests)

Page 32: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Pressure control

VFD speed drops to maintain pressure after initial system start, then builds again as VAV’s open after 9AM, then drops as pressure setpoint is reduced.

Pressure setpoint signal stays high (>5 requests)

After initial morning start, VFD speed and pressure setpoint go hand in hand

Page 33: Supply Air Temperature and Pressure Setpoint Reset … Air Temperature and Pressure Setpoint Reset in VAV ... respond logic within the range 0.15 inches to 1.5 inches. ... • May

Summary

Static pressure setpoint reset• Use Trim & Respond SP setpoint reset logic based on

damper position or airflow demandSupply air temperature setpoint reset• Not effective for all systems and climates• Use combination of Trim and Respond SAT reset and

outdoor air temperature reset to minimize fan/cooling/reheat energy use

Commissioning• Tuning is essential for stable operation• Review trend data of normal operation to identify (and fix)

rogue zones