surge arresters - gv kinsman electrical products · application: protection of mv networks and...

13

Upload: tranhuong

Post on 03-May-2019

228 views

Category:

Documents


0 download

TRANSCRIPT

OCP is the latest gapless, zinc oxide arresterfamily from Bowthorpe.

The OCP development was based on 25 yearsof internal experience in arrester design andmanufacture within the TYCO Energy division.

BOWTHORPE OCP BENEFITS:

Tested in accordance with IEC60099-4 atindependent accredited laboratories.

Superior protection margins.

Direct molded housing to prevent moistureingress.

Low residual voltages.

High-energy handling.

Superior TOV performance.

Safe non-shattering short circuit behavior tohigher current levels.

Maintenance free.

Hydrophobic silicone housing, tracking anderosion resistant.

Excellent cantilever and tensile performance.

Excellent vibration and impact withstandcapability.

Quality design and manufacturing, ISO 9001and 14001 compliant.

Electronics

Surge Arresters

Distribution Class - Open Cage Polymeric ‘OCP’

www.dulmison.com.au15-2

Sur

ge

Arr

este

rs

Refer Brochure: Bowthorpe MV arresters OCP EPP-1098 for details

Application:Protection of MV networks and equipment from lightning and switching surge related over-voltages in areas with relatively high iso-keraunic levels. Suitable for both outdoor and indoor useto protect transformers and cable end terminations.

Generic technical data:OCP1 seriesRated discharge current (8/20µs):Line discharge class 1 according toOperating duty impulse withstand current (4/10µs):Long duration current impulse (2000µs):High current short circuit: (pre-failing method)(Safe non-shattering failure mode)Energy 2 Long duration impulses:Cantilever strength

3-24kV Uc10kAIEC 60099-4100kA350A25kA

4.1kJ/kVUc350 Nm

Electronics

Surge Arresters

Distribution Class - Polymeric ‘OCP1’

www.dulmison.com.au 15-3

Sur

ge

Arr

este

rs

TOV of OCP1 with 100kA single shot high current prior energy

1.60

1.55

1.50

1.45

1.40

1.35

1.301 10 100 1000 10000

TOV Curve

Time (s)

Uw

/Uc

Temperature of samples(pre-heated): 60 degrees C according to IEC 60099-4, Ed 2.0 2004.TOV Curve applies to an arrester which has a pre-stress applied prior to TOV verification.This pre-stress is equivalent to one high current impulse of 100kA, 4/10 as per the switchingsurge operating duty test.

Uw = TOV withstand voltage; Uc = continuous operating voltage.

Electronics

Surge Arresters

Distribution Class - Polymeric ‘OCP1’

www.dulmison.com.au15-4

Sur

ge

Arr

este

rs

456891012151820212224

456891012151820212224

56.27.510

11.212.515

18.722.525

26.227.530

13.0316.2919.5526.0629.3232.5839.1048.8758.6465.1668.4271.6878.19

13.8317.2920.7527.6631.1234.5841.5051.8762.2469.1672.6276.0882.99

15.3119.1422.9730.6234.4538.2845.9457.4268.9076.5680.3984.2291.87

15.0418.8022.5630.0833.8437.6045.1256.4067.6875.2078.9682.7290.24

10.4213.0215.6220.8323.4426.0431.2539.0646.8752.0854.6857.2962.50

10.7713.4616.1521.5424.2326.9232.3040.3848.4653.8456.5359.2264.61

Uc

kV (rms)

Ur

kV (rms)

Residual Voltage in kV when tested to the following impulse waveformsLightning Switching

8/20µS 1/20µS 1/20µS5kA 10kA 20kA 10kA 125A 500AOCP1-

456891012151820212224

106106106106106106106128154154180180180

47474747474747576868808080

176176176176176176176214254254293293293

379379379379379379379503629629755755755

183183183183183183183220260260299299299

ImpulseSWkV

PF WetWSkV

OCP-xxS; Standard housing parameters

FO Distmm

Creepagemm

Height LmmOCP1-

456891012151820212224

128128128128128128128154180180205205205

57575757575757688080919191

214214214214214214214254293293334334334

503503503503503503503629755755882882882

214214214214214214214254293293334334334

ImpulseSWkV

PF WetWSkV

OCP-xxL; Extended housing parameters

FO Distmm

Creepagemm

Height LmmOCP1-

97mm

119mm

L

Electronics

Surge Arresters

OCP Series naming and order query descriptionExample: OCP = ‘Open Cage Polymeric’

www.dulmison.com.au 15-1

Sur

ge

Arr

este

rs

OCP0 - 12S - ABC System Voltage Um

122436

185315445

165295425

ph/ph (a) ph/ground (b)

Line discharge class:0 = 5kA, 65kA high current1 = 10kA, 100kA high current, class 12 = 10kA, 100kA high current, class 2

Housing creepage:S = standard creepageL = extended creepage

Accessory selection:M = Mounting bracketE = Earth connectionL = Line connection

Line lead accessories

Arrester Type = Continuous Operating Voltage Uc in kV

Mounting accessories

Ground lead accessories

Additional accessory options available on request.Please contact: [email protected] with your specific requirements.

Uc

03081522

04091824

051020

061221

OCP -

55m

m

55m

m

55m

m55

mm

55m

m

F M N Q V

A

D F M N V

B C N T

OCP - 12 -

b a a

Electronics

Surge Arresters

Station Class - Porcelain

www.dulmison.com.au15-6

Sur

ge

Arr

este

rs

MAAMBAMCAMDA

3 - 2203 - 1563 - 3603 - 360

10101020

2234

40254040

DutykA

LineDischarge

Class

PressureRelief Class

kA

VoltageRating

kVCat No.

• Conventional design• High voltage porcelain• Glazed externally and internally• Varistors in single column, spring loaded with air cavity• Up to 400kV• Pressure relief performance 40kA• Grey or Brown

Refer brochure: Transmission Surge Arresters BOW-EPP-0001 for details.

Electronics

Surge Arresters

Station Class - Polymeric

www.dulmison.com.au 15-7

Sur

ge

Arr

este

rs

HSR2HSR3HSR

6 - 4848 - 8496 - 132

101010

222

DutykA

LineDischarge

Class

VoltageRating

kVCat No.

• Patented design• Void free construction• High cantilever strength which maintains electrical continuity• Non shattering• 25 kA Short Circuit performance• Up to 3 units high• Extended Creepage available

Refer brochure: Transmission Surge Arresters BOW-EPP-0001 for details.

Electronics

Surge Arresters

Station Class - Polymeric

www.dulmison.com.au12-8

Sur

ge

Arr

este

rs

2P3P, 4P, 5P

30 - 16896 - 525

1010/20

33, 4 & 5

DutykA

LineDischarge

Class

VoltageRating

kVCat No.

• Patented Series Parallel design provides the best solution forhigher voltage systems

• Line Discharge Class 2,3,4 & 5 high energy levels• 3KV to 800KV rated systems• Series Parallel design is the number one seismic arrester

which meets the requirements of BPA in USA• NGC Approval at 132, 275 & 400kV• Easy Installation in Remote Locations

Refer brochure: Transmission Surge Arresters BOW-EPP-0001 for details.

• SC12• SC13 (With Leakage Current Display)• & AC (With Auxiliary Contacts)

• Arrester base must be insulated• Insulated bases are available for all Tyco arresters• Same robust design for over twenty years• Leading supplier to OEMs

Electronics

Surge Arresters

Surge Counters

www.dulmison.com.au 15-9

Sur

ge

Arr

este

rs

• Protection of single bond and cross bonded HV cables.• Protects against short circuit induced over voltage

Electronics

Surge Arresters

Sheath Voltage Limiter

www.dulmison.com.au15-10

Sur

ge

Arr

este

rs

CPACSPA2CSPA3

1, 3, 6 & 91, 3, 6 & 91, 3, 6 & 9

123

LineDischarge

Class

VoltageRating

kVCat No.

Electronics

Surge Arresters

DC Traction

www.dulmison.com.au 15-11

Sur

ge

Arr

este

rs

Electrical PerformanceClassification (8/20 µs nominal discharge current) – 10,000 AmpsVoltage Rating – 1kV to 4.9kV DCHigh Current Operation Duty – 100kA 4/10µsHigh Current Single Impulse Energy – 2.3kJ/kV at Ur

Operating Duty Cycle – 2 shots hi-current followed by the voltage profile Ur(300s) then Uc- (1800s) as per EN50123-5 2003 clause 4.7.5.4 and figure 4.1to prove thermal stability.

Refer brochure: DC Traction BOW-EPP-0005 for details

Main FeaturesThe arrester has a 10kA nominal discharge current and100kA duty cycle performance to EN 50123-5-2003.

The patented void free construction of this arresterdesign results in a unit with strength which isimpervious to the ingress of moisture.

The arrester has the following features:• No internal airspace so no moisture ingress• Vandal proof• High cantilever and torsional strength• Non-explosive failure mode• Low weight and small size• Resistant to transport damage and careless handling• Easy to install

Technical DataArrester Type 2DCAFL4 is housed in a die-cast aluminium box finished in grey paint and complieswith IP65. The box is fitted with four aluminium cable glands to BS6121 to accommodate supplycables with diameter 11.00mm to 13.5mm. The box has a stainless steel M12 earth terminal studwith two lock nuts and clamp washers.

The box lid is removed for connections and the internal screw-type terminals will accommodatewires up to 6mm diameter. (Hexagon Key provided.)

Box size: 260mm x 160mm x 90mm

The Arrester Type 2DCAFL4 has the following electrical performance -

Nominal a.c. rating 4.0kv rmsMaximum continuous operating d.c. voltage 5.2kvArrester Classifcation 5000AHigh Current 65kAEnergy handling capability equivalent 1 (IEC 60099-4 Clause 7.4.2 table 4 & 7.5.5.5)Withstand based on 2000ms rectangular wave 250AOperating temperature -40°C to +40°CStandard IEC 60099-4 2001

Electronics

Surge Arresters

Airfield Lighting

www.dulmison.com.au15-12

Sur

ge

Arr

este

rs

Key Features• HV arrester suspended from a transmission line giving

enhanced transmission line performance.• Increasing system line voltage on standard insulated

transmission lines.

Benefits of TLA Applications• Minimising circuit breaker operation with possible

system outage resulting from back flashover on thetransmission line.

• Switching overvoltages are absorbed over the length ofthe line reducing the severity of surge at the substation.

• Transmission systems can be operated even wheresub-soil gives poor tower footing resistance.

• Eliminating interrupted power supply for sensitiveindustrial processes.

• Installing Transmission Line Arresters on a standard 3phase voltage system along the line, at calculatedintervals, allows for optimum performance of the TLA,to give an increased system line voltage.

• Therefore eliminating the need to increase the standardinsulation level required on conventional systemupgrade.

Electronics

Surge Arresters

Transmission Line Arrester

www.dulmison.com.au 15-13

Sur

ge

Arr

este

rsTLA1TLA2TLA3TLA4

16 - 4548 - 96

108 - 144150 - 192

10101010

2222

DutykA

LineDischarge

Class

VoltageRating

kVCat No.