Page 1: Surge Protection Short Form Catalogue - LC Automation · 2015-06-10 · C C.16 1366910000 – 2013 Lightning and surge protection for low voltage facilities Type I and II lightning

Surge ProtectionShort Form Catalogue

Electronics

Page 2: Surge Protection Short Form Catalogue - LC Automation · 2015-06-10 · C C.16 1366910000 – 2013 Lightning and surge protection for low voltage facilities Type I and II lightning

Does your structure have external lightning protection? According to the new 17th edition wiring regulations and BS62305-4 you must now install Class I and Class II Surge Protection Devices.

In July 2011, the Institution of Engineering and Technology and the British Standards Institution (BSI) jointly published important changes to The IET Wiring Regulations, 17th Edition, BS 7671:2008 incorporating Amendment No.1, 2011. This set out the national standard to which all new electrical installations must comply and they came into effect on 1st January 2012.

This means new considerations for those of you involved in protecting businesses against the potential effects of transient overvoltages, along with the maintenance, installation and/or design of electrical installations or wiring in buildings.

Any switching operation, fault initiation or interruption is followed by a transient phenomenon in which an overvoltage can occur. Common causes can include power grid quality issues, downed lines or faulty wiring. Surges can also occur through natural causes such as lightning strikes.

NEW Section 534: Devices for protection against overvoltages: this section is a collation of information contained in

• BSEN7671:2008Section443• BSEN60664-1InsulationCo-ordination• BSEN62305-4ProtectionofElectronic Systems within Structures• BSEN61643Parts12&22:Power,Data, TelecomsandSignalSurgeProtection The standard has been designed to ensure that all competent parties adhere to, and implement, lightning and surge protection strategies, within electrical systems. It also lays out selection and erection guidelines for installations.

Classes of Surge Protection Devices

Class I – Use on buildings in applications where there is an external lightning protection system installed, usually installed attheserviceentranceorMainDistributionBoardClass II – Installed after the Class I device if installed or suitable for all other applications at the sub distribution board, or machine control panelsClass III – Installed after class II devices whereaspecificpieceofelectronicequipmentormission-criticalapplicationrequires the highest levels of protection.

Over 60 years of proven industry design and production experience means our customers trust us to deliver innovative, reliable, and safe electrical connectivity solutions.

OurDINENISO/IECaccreditations enable our lab tocarryoutcertifiedtestsforterminal blocks, connectors, and electronic equipment, so you can be safe in the knowledge that our products can be used worldwide.

With a heritage based on outstanding quality standards and service levels, backed up by a team of local technical, engineering and design support we offer you complete peace of mind.

Inadditiontoourstate-of–the-art manufacturing facilities, salesofficesanddistributornetwork, we operate in more than 80 countries, making Weidmüller your true global partner.

SurgeProtectionshould beinstalled

BS 7671:2008 Section 534

Devices for Protection against Overvoltages

BS EN 61643 Pt 12 & 22

Power, Data & Signal Surge Protection

BS EN 62305-4Protection of Equipment

within Structures

BS 7671:2008 Section 443

Overvoltages of Atmospheric or

Switching Origin

Page 3: Surge Protection Short Form Catalogue - LC Automation · 2015-06-10 · C C.16 1366910000 – 2013 Lightning and surge protection for low voltage facilities Type I and II lightning

C

C.16 1366910000 – 2013

Light

ning a

nd su

rge p

rote

ction

for l

ow vo

ltage

facil

ities Type I and II lightning arrester

• No-leakage-current version suitable for use upstream of the electrical meter

• Pluggable arrester• Suitable with 25 kA (10/350 µs) for lightning protection

level I, II, III and IV (LPL I/II/III/IV)• Tested according to IEC 61643-11 for Type I and II surge

protection• Can also be used as Type II surge protection

Technical data

Rated voltage (AC)Highest continuous current (AC)Temporary surge voltage (over-voltage) - TOVRequirements category acc. to IEC 61643-11Lightning test current Iimp (10/350 µs)Discharge current In (8/20µs) wire-wireDischarge current Imax (8/20µs) wire-PEShort-circuit resistance ISCCR

Total discharge current Itotal

Rated load current ILPE conductor current IPE

Short-circuit strength with max. back-up fuseSparkover time / Drop-out timeFusingProtection level UP (typical)Optical function displayDesignColourAmbient temperature (operational)Connection according to IEC 947-7-1SolidStrandedStripping lengthTightening torqueApprovalsApprovalsStandards

Dimensions / Signalling contact infoClamping range (nominal / min. / max.) mm²Height x width x depth mmSignalling contactNote

Ordering data

no remote sig. contactwith remote signalling (R)

Note

AccessoriesNote

VPU I 3/R LCF 280 V / 25 kATN-C

L2OK OKCHANGE

L2 L3

U

CHANGE

L3L1

U

OK CHANGE

L1

11 1412

U

PE (N)PE (N)

230 V280 V440 VType I, Type II 25 kA 25 kA 100 kA 25 kA75 kA125 A0 µA25 kAeff

≤ 100 ns250 A gL≤ 1.6 kVgreen = OK; red = arrester is defective - replaceInstallation housing; 6 TE, Insta IP 20Black, Arrester red-40 °C...+70 °C

2.5...16 mm²2.5...50 mm²15 mm2...3 Nm

IEC61643-11, EN61643-11

no remote sig. contact with remote signalling (R)16 / 2.5 / 50 16 / 2.5 / 5094 / 108 / 69 106 / 108 / 69No 250 V 1A 1CO

Type Qty. Order No.VPU I 3 LCF 280V/25KA 1 1351690000VPU I 3 R LCF 280V/25KA 1 1351670000

Pluggable spare arrester VPU I 0 LCF 280 V/25 kA-1351540000

VPU I 4/R LCF 280 V / 25 kATN-S

L2OK OKCHANGE

L2 L3

U

CHANGE

L3L1

U

OK CHANGE

L1

PE11 1412

U

OK

NCHANGE

N

PE

U

230 V280 V335 VType I, Type II 25 kA 25 kA 100 kA 25 kA100 kA125 A0 µA25 kAeff

≤ 100 ns250 A gL≤ 1.6 kVgreen = OK; red = arrester is defective - replaceInstallation housing; 8 TE, Insta IP 20Black, Arrester red-40 °C...+70 °C

4...16 mm²2.5...50 mm²15 mm2...3 Nm

IEC61643-11, EN61643-11

no remote sig. contact with remote signalling (R)16 / 4 / 50 16 / 2.5 / 5090 / 144 / 69 106 / 144 / 69No 250 V 1A 1CO

Type Qty. Order No.VPU I 4 LCF 280V/25KA 1 1351730000VPU I 4 R LCF 280V/25KA 1 1351720000

Pluggable spare arrester VPU I 0 LCF 280 V/25 kA-1351540000

Type I and II lightning arrester for use upstream of the electrical meter

C

C.16 1366910000 – 2013

Light

ning a

nd su

rge p

rote

ction

for l

ow vo

ltage

facil

ities Type I and II lightning arrester

• No-leakage-current version suitable for use upstream of the electrical meter

• Pluggable arrester• Suitable with 25 kA (10/350 µs) for lightning protection

level I, II, III and IV (LPL I/II/III/IV)• Tested according to IEC 61643-11 for Type I and II surge

protection• Can also be used as Type II surge protection

Technical data

Rated voltage (AC)Highest continuous current (AC)Temporary surge voltage (over-voltage) - TOVRequirements category acc. to IEC 61643-11Lightning test current Iimp (10/350 µs)Discharge current In (8/20µs) wire-wireDischarge current Imax (8/20µs) wire-PEShort-circuit resistance ISCCR

Total discharge current Itotal

Rated load current ILPE conductor current IPE

Short-circuit strength with max. back-up fuseSparkover time / Drop-out timeFusingProtection level UP (typical)Optical function displayDesignColourAmbient temperature (operational)Connection according to IEC 947-7-1SolidStrandedStripping lengthTightening torqueApprovalsApprovalsStandards

Dimensions / Signalling contact infoClamping range (nominal / min. / max.) mm²Height x width x depth mmSignalling contactNote

Ordering data

no remote sig. contactwith remote signalling (R)

Note

AccessoriesNote

VPU I 3/R LCF 280 V / 25 kATN-C

L2OK OKCHANGE

L2 L3

U

CHANGE

L3L1

U

OK CHANGE

L1

11 1412

U

PE (N)PE (N)

230 V280 V440 VType I, Type II 25 kA 25 kA 100 kA 25 kA75 kA125 A0 µA25 kAeff

≤ 100 ns250 A gL≤ 1.6 kVgreen = OK; red = arrester is defective - replaceInstallation housing; 6 TE, Insta IP 20Black, Arrester red-40 °C...+70 °C

2.5...16 mm²2.5...50 mm²15 mm2...3 Nm

IEC61643-11, EN61643-11

no remote sig. contact with remote signalling (R)16 / 2.5 / 50 16 / 2.5 / 5094 / 108 / 69 106 / 108 / 69No 250 V 1A 1CO

Type Qty. Order No.VPU I 3 LCF 280V/25KA 1 1351690000VPU I 3 R LCF 280V/25KA 1 1351670000

Pluggable spare arrester VPU I 0 LCF 280 V/25 kA-1351540000

VPU I 4/R LCF 280 V / 25 kATN-S

L2OK OKCHANGE

L2 L3

U

CHANGE

L3L1

U

OK CHANGE

L1

PE11 1412

U

OK

NCHANGE

N

PE

U

230 V280 V335 VType I, Type II 25 kA 25 kA 100 kA 25 kA100 kA125 A0 µA25 kAeff

≤ 100 ns250 A gL≤ 1.6 kVgreen = OK; red = arrester is defective - replaceInstallation housing; 8 TE, Insta IP 20Black, Arrester red-40 °C...+70 °C

4...16 mm²2.5...50 mm²15 mm2...3 Nm

IEC61643-11, EN61643-11

no remote sig. contact with remote signalling (R)16 / 4 / 50 16 / 2.5 / 5090 / 144 / 69 106 / 144 / 69No 250 V 1A 1CO

Type Qty. Order No.VPU I 4 LCF 280V/25KA 1 1351730000VPU I 4 R LCF 280V/25KA 1 1351720000

Pluggable spare arrester VPU I 0 LCF 280 V/25 kA-1351540000

Type I and II lightning arrester for use upstream of the electrical meter

C

C.18 1366910000 – 2013

Light

ning a

nd su

rge p

rote

ction

for l

ow vo

ltage

facil

ities Type I and II lightning arrester

• No-leakage-current version suitable for use upstream of the electrical meter

• Pluggable arrester• Suitable with 25 kA (10/350 µs) for lightning protection

level I, II, III and IV (LPL I/II/III/IV)• Tested according to IEC 61643-11 for Type I and II surge

protection• Can also be used as Type II surge protection

Technical data

Rated voltage (AC)Highest continuous current (AC)Temporary surge voltage (over-voltage) - TOVRequirements category acc. to IEC 61643-11Lightning test current Iimp (10/350 µs)Discharge current In (8/20µs) wire-wireDischarge current Imax (8/20µs) wire-PEShort-circuit resistance ISCCR

Total discharge current Itotal

Rated load current ILPE conductor current IPE

Short-circuit strength with max. back-up fuseSparkover time / Drop-out timeFusingProtection level UP (typical)Optical function displayDesignColourAmbient temperature (operational)Connection according to IEC 947-7-1SolidStrandedStripping lengthTightening torqueApprovalsApprovalsStandards

Dimensions / Signalling contact infoClamping range (nominal / min. / max.) mm²Height x width x depth mmSignalling contactNote

Ordering data

no remote sig. contactwith remote signalling (R)

Note

AccessoriesNote

VPU I 2/R LCF 280 V / 25 kA1-phase

230 V280 V440 VType I, Type II 25 kA 25 kA 100 kA 25 kA50 kA125 A0 µA25 kAeff

≤ 100 ns250 A gL≤ 1.6 kVgreen = OK; red = arrester is defective - replaceInstallation housing; 4TE, Insta IP 20Black, Arrester red-40 °C...+70 °C

2.5...16 mm²2.5...50 mm²15 mm2...3 Nm

IEC61643-11, EN61643-11

no remote sig. contact with remote signalling (R)16 / 2.5 / 50 16 / 2.5 / 5094 / 72 / 69 106 / 72 / 69No 250 V 1A 1CO

Type Qty. Order No.VPU I 2 LCF 280V/25KA 1 1351640000VPU I 2 R LCF 280V/25KA 1 1351620000

Pluggable spare arrester VPU I 0 LCF 280 V/25 kA-1351540000

VPU I 1/R LCF 280 V / 25 kA1-phase

230 V280 V440 VType I, Type II 25 kA 25 kA 100 kA 25 kA25 kA125 A0 µA25 kAeff

≤ 100 ns250 A gL≤ 1.6 kVgreen = OK; red = arrester is defective - replaceInstallation housing; 2TE, Insta IP 20Black, Arrester red-40 °C...+70 °C

2.5...16 mm²2.5...50 mm²15 mm2...3 Nm

IEC61643-11, EN61643-11

no remote sig. contact with remote signalling (R)16 / 2.5 / 50 16 / 2.5 / 5094 / 35.6 / 69 106 / 35.6 / 69No 250 V 1A 1CO

Type Qty. Order No.VPU I 1 LCF 280V/25KA 1 1351590000VPU I 1 R LCF 280V/25KA 1 1351570000

Pluggable spare arrester VPU I 0 LCF 280 V/25 kA-1351540000

Type I and II lightning arrester for use upstream of the electrical meter

Page 4: Surge Protection Short Form Catalogue - LC Automation · 2015-06-10 · C C.16 1366910000 – 2013 Lightning and surge protection for low voltage facilities Type I and II lightning

C

C.30 1366910000 – 2013

Light

ning a

nd su

rge p

rote

ction

for l

ow vo

ltage

facil

ities

Type I and II lightning arrester for use downstream of electrical meter• Suitable for lightning protection level III and IV (LPL III/

IV)• Pluggable arresters• Tested according to IEC 61643-11 for Type I and II

lightning and surge protection

Technical data

Rated voltage (AC)Highest continuous current (AC)Temporary surge voltage (over-voltage) - TOVRequirements category acc. to IEC 61643-11Lightning test current Iimp (10/350 µs)Short-circuit strength with max. back-up fuseDischarge current In (8/20µs) wire-wireDischarge current Imax (8/20µs) wire-PEShort-circuit resistance ISCCR

Total discharge current Itotal

PE conductor current IPE

Sparkover time / Drop-out timeFusingProtection level UP (typical)Optical function displayDesignColourAmbient temperature (operational)Connection according to IEC 947-7-1SolidStrandedStripping lengthTightening torqueApprovalsApprovalsStandards

Dimensions / Signalling contact infoClamping range (nominal / min. / max.) mm²Height x width x depth mmSignalling contactNote

Ordering data

no remote sig. contactwith remote signalling (R)

Note

AccessoriesNote

VPU I 4/R 280 V / 12.5 kATN-S

L1 L2

U U

PE

OK CHANGE OK CHANGE

L3

U

OK CHANGE

N

U

OK CHANGE

11 1412 PE

230 V280 V335 VType I, Type II 12.5 kA 25 kAeff

25 kA 50 kA 25 kA50 kA30 µA≤ 25 ns250 A gL≤ 1.4 kVgreen = OK; red = arrester is defective - replaceInstallation housing; 4TE, Insta IP 20Black, Arrester red-40 °C...+70 °C

4...16 mm²2.5...50 mm²15 mm2...3 Nm

IEC61643-11, EN61643-11

no remote sig. contact with remote signalling (R)16 / 4 / 50 16 / 4 / 5094 / 71.2 / 69 106 / 71.2 / 69No 250 V 1A 1CO

Type Qty. Order No.VPU I 4 280V/12,5KA 1 1352180000VPU I 4 R 280V/12,5KA 1 1352190000

Pluggable spare arrester VPU I 0 400 V/12.5 kA-1352280000

VPU I 3/R 280 V / 12.5 kATN-C

PE (N)

L1

U

OK CHANGE

L2

U

OK CHANGE

L3

U

OK CHANGE

11 1412 PE (N)

230 V280 V335 VType I, Type II 12.5 kA 25 kAeff

25 kA 50 kA 25 kA37.5 kA30 µA≤ 25 ns250 A gL≤ 1.4 kVgreen = OK; red = arrester is defective - replaceInstallation housing; 3TE, Insta IP 20Black, Arrester red-40 °C...+70 °C

4...16 mm²2.5...50 mm²15 mm2...3 Nm

IEC61643-11, EN61643-11

no remote sig. contact with remote signalling (R)16 / 4 / 50 16 / 4 / 5094 / 53.4 / 69 106 / 53.4 / 69No 250 V 1A 1CO

Type Qty. Order No.VPU I 3 280V/12,5KA 1 1352200000VPU I 3 R 280V/12,5KA 1 1352220000

Pluggable spare arrester VPU I 0 280 V/12.5 kA-1352120000

Type I and II lightning arrester for use downstream of the electrical meter

C

C.311366910000 – 2013

Light

ning a

nd su

rge p

rote

ction

for l

ow vo

ltage

facil

ities

Type I and II lightning arrester for use downstream of electrical meter• Suitable for lightning protection level III and IV (LPL III/

IV)• Pluggable arresters• Tested according to IEC 61643-11 for Type I and II

lightning and surge protection

Technical data

Rated voltage (AC)Highest continuous current (AC)Temporary surge voltage (over-voltage) - TOVRequirements category acc. to IEC 61643-11Lightning test current Iimp (10/350 µs)Short-circuit strength with max. back-up fuseDischarge current In (8/20µs) wire-wireDischarge current Imax (8/20µs) wire-PEShort-circuit resistance ISCCR

Total discharge current Itotal

PE conductor current IPE

Sparkover time / Drop-out timeFusingProtection level UP (typical)Optical function displayDesignColourAmbient temperature (operational)Connection according to IEC 947-7-1SolidStrandedStripping lengthTightening torqueApprovalsApprovalsStandards

Dimensions / Signalling contact infoClamping range (nominal / min. / max.) mm²Height x width x depth mmSignalling contactNote

Ordering data

no remote sig. contactwith remote signalling (R)

Note

AccessoriesNote

VPU I 2/R 280 V / 12.5 kA1-phase

230 V280 V335 VType I, Type II 12.5 kA 25 kAeff

25 kA 50 kA 25 kA25 kA30 µA≤ 25 ns250 A gL≤ 1.4 kVgreen = OK; red = arrester is defective - replaceInstallation housing; 2TE, Insta IP 20Black, Arrester red-40 °C...+70 °C

4...16 mm²2.5...50 mm²15 mm2...3 Nm

IEC61643-11, EN61643-11

no remote sig. contact with remote signalling (R)16 / 4 / 50 16 / 4 / 5094 / 35.6 / 69 106 / 35.6 / 69No 250 V 1A 1CO

Type Qty. Order No.VPU I 2 280V/12,5KA 1 1352150000VPU I 2 R 280V/12,5KA 1 1352170000

Pluggable spare arrester VPU I 0 280 V/12.5 kA-1352120000

VPU I 1/R 280 V / 12.5 kA1-phase

L1

PE (N)

U

OK CHANGE

11 1412

230 V280 V335 VType I, Type II 12.5 kA 25 kAeff

25 kA 50 kA 25 kA12.5 kA30 µA≤ 25 ns250 A gL≤ 1.4 kVgreen = OK; red = arrester is defective - replaceInstallation housing; 1TE, Insta IP 20Black, Arrester red-40 °C...+70 °C

4...16 mm²2.5...50 mm²15 mm2...3 Nm

IEC61643-11, EN61643-11

no remote sig. contact with remote signalling (R)16 / 4 / 50 16 / 4 / 5094 / 17.8 / 69 106 / 17.8 / 69No 250 V 1A 1CO

Type Qty. Order No.VPU I 1 280V/12,5KA 1 1352130000VPU I 1 R 280V/12,5KA 1 1352140000

Pluggable spare arrester VPU I 0 280 V/12.5 kA-1352120000

Type I and II lightning arrester for use downstream of the electrical meter

Page 5: Surge Protection Short Form Catalogue - LC Automation · 2015-06-10 · C C.16 1366910000 – 2013 Lightning and surge protection for low voltage facilities Type I and II lightning

C

C.38 1366910000 – 2013

Light

ning a

nd su

rge p

rote

ction

for l

ow vo

ltage

facil

ities

Type II/III surge protection Uc: 280 V Suitable for 230/400 V mains systems• Pluggable arrester• Coded voltage level• High energy absorption with short time to sparkover• Arrester can be rotated through 180°• No follow-on current• Installation in distribution board• Thermal protection function• Co-ordination with VPU Type I

Technical data

Rated voltageMax. continuous voltage, Uc (AC)Requirements category acc. to IEC 61643-11Rated discharge current (8/20 µs) INLimiting discharge current (8/20 µs) Imax

Discharge current, max. (8/20 µs)Combined pulse Uoc

Short-circuit resistance ISCCR

Total discharge current Itotal

PE conductor current IPE

Sparkover time / Drop-out timeFusingProtection level UP (typical)Temporary surge voltage (over-voltage) - TOVOptical function displayDesignColourAmbient temperature (operational)Storage temperatureConnection according to IEC 947-7-1SolidStrandedStripping lengthTightening torqueApprovalsApprovalsStandards

Dimensions / Signalling contact infoClamping range (nominal / min. / max.) mm²Height x width x depth mmSignalling contactNote

Ordering data

no remote sig. contactwith remote signalling (R)

Note

AccessoriesNote

VPU II 4/R 280 V / 40 kATN-S

L1 L2

PE

U U

OK CHANGE OK CHANGE

L3

U

OK CHANGE

N

U

OK CHANGE

PE11 1412

230 V / 400 V280 V Type II, Type III 20 kA40 kA40 kA10 kV25 kA160 kA30 µA≤ 25 ns125 A gL≤ 1.55 kV 440 Vgreen = OK; red = arrester is defective - replaceInstallation housing; 4TE, Insta IP 20Black, Arrester red-40 °C...+70 °C-40 °C ... +80 °C

2.5...16 mm²2.5...50 mm²15 mm2...3 Nm

IEC61643-11, EN61643-11

no remote sig. contact with remote signalling (R)16 / 2.5 / 50 16 / 2.5 / 5094 / 71.2 / 69 106 / 71.2 / 69No 250 V 1A 1CO

Type Qty. Order No.VPU II 4 280V/40KA 1 1352680000VPU II 4 R 280V/40KA 1 1352690000

Pluggable spare arrester VPU II 0 280 V/40 kA-1352570000

VPU II 3/R 280 V / 40 kATN-C

L1 L2

PE (N)

U U

OK CHANGE OK CHANGE

L3

U

OK CHANGE

PE (N)11 1412

230 V / 400 V280 V Type II, Type III 20 kA40 kA40 kA10 kV25 kA120 kA30 µA≤ 25 ns125 A gL≤ 1.55 kV 440 Vgreen = OK; red = arrester is defective - replaceInstallation housing; 3TEBlack, Arrester red-40 °C...+70 °C-40 °C ... +80 °C

2.5...16 mm²2.5...50 mm²15 mm2...3 Nm

IEC61643-11, EN61643-11

no remote sig. contact with remote signalling (R)16 / 2.5 / 50 16 / 2.5 / 5094 / 53.4 / 69 106 / 53.4 / 69No 250 V 1A 1CO

Type Qty. Order No.VPU II 3 280V/40KA 1 1352700000VPU II 3 R 280V/40KA 1 1352720000

Pluggable spare arrester VPU II 0 280 V/40 kA-1352570000

Type II surge protection

C

C.40 1366910000 – 2013

Light

ning a

nd su

rge p

rote

ction

for l

ow vo

ltage

facil

ities

Type II/III surge protection Uc: 280 V Suitable for 230/400 V mains systems• Pluggable arrester• Coded voltage level• High energy absorption with short time to sparkover• Arrester can be rotated through 180°• No follow-on current• Installation in distribution board• Thermal protection function• Co-ordination with VPU Type I

Technical data

Rated voltageMax. continuous voltage, Uc (AC)Requirements category acc. to IEC 61643-11Rated discharge current (8/20 µs) INLimiting discharge current (8/20 µs) Imax

Discharge current, max. (8/20 µs)Combined pulse Uoc

Short-circuit resistance ISCCR

Total discharge current Itotal

PE conductor current IPE

Sparkover time / Drop-out timeFusingProtection level UP (typical)Temporary surge voltage (over-voltage) - TOVOptical function displayDesignColourAmbient temperature (operational)Storage temperatureConnection according to IEC 947-7-1SolidStrandedStripping lengthTightening torqueApprovalsApprovalsStandards

Dimensions / Signalling contact infoClamping range (nominal / min. / max.) mm²Height x width x depth mmSignalling contactNote

Ordering data

no remote sig. contactwith remote signalling (R)

Note

AccessoriesNote

VPU II 2/R 280 V / 40 kA1-phase

L1 N

U U

PE

OK CHANGE OK CHANGE

PE11 1412

230 V280 V Type II, Type III 20 kA40 kA40 kA10 kV25 kA80 kA30 µA≤ 25 ns125 A gL≤ 1.55 kV 440 Vgreen = OK; red = arrester is defective - replaceInstallation housing; 2TE, Insta IP 20Black, Arrester red-40 °C...+70 °C-40 °C ... +80 °C

2.5...16 mm²2.5...50 mm²15 mm2...3 Nm

IEC61643-11, EN61643-11

no remote sig. contact with remote signalling (R)16 / 2.5 / 50 16 / 2.5 / 5094 / 35.6 / 69 106 / 35.6 / 69No 250 V 1A 1CO

Type Qty. Order No.VPU II 2 280V/40KA 1 1352600000VPU II 2 R 280V/40KA 1 1352620000

Pluggable spare arrester VPU II 0 280 V/40 kA-1352570000

VPU II 1/R 280 V / 40 kA1-phase

L1

PE (N)

U

OK CHANGE

11 1412

230 V280 V Type II, Type III 20 kA40 kA40 kA10 kV25 kA40 kA30 µA≤ 25 ns125 A gL≤ 1.55 kV 440 Vgreen = OK; red = arrester is defective - replaceInstallation housing; 1TEBlack, Arrester red-40 °C...+70 °C-40 °C ... +80 °C

2.5...16 mm²2.5...50 mm²15 mm2...3 Nm

IEC61643-11, EN61643-11

no remote sig. contact with remote signalling (R)16 / 2.5 / 50 16 / 2.5 / 5094 / 17.8 / 69 106 / 17.8 / 69No 250 V 1A 1CO

Type Qty. Order No.VPU II 1 280V/40KA 1 1352580000VPU II 1 R 280V/40KA 1 1352590000

Pluggable spare arrester VPU II 0 280 V/40 kA-1352570000

Type II surge protection

Page 6: Surge Protection Short Form Catalogue - LC Automation · 2015-06-10 · C C.16 1366910000 – 2013 Lightning and surge protection for low voltage facilities Type I and II lightning

C

C.48 1366910000 – 2013

Light

ning a

nd su

rge p

rote

ction

for l

ow vo

ltage

facil

ities

Type II/III surge protection Uc: 150 V Suitable for 120/240 V mains systems• Pluggable arrester• Coded voltage level• High energy absorption with short time to sparkover• Arrester can be rotated through 180°• No follow-on current• Installation in distribution board• Thermal protection function• Co-ordination with VPU Type I

Technical data

Rated voltageMax. continuous voltage, Uc (AC)Requirements category acc. to IEC 61643-11Rated discharge current (8/20 µs) INLimiting discharge current (8/20 µs) Imax

Discharge current, max. (8/20 µs)Combined pulse Uoc

Short-circuit resistance ISCCR

Total discharge current Itotal

PE conductor current IPE

Sparkover time / Drop-out timeFusingProtection level UP (typical)Temporary surge voltage (over-voltage) - TOVOptical function displayDesignColourAmbient temperature (operational)Storage temperatureConnection according to IEC 947-7-1SolidStrandedStripping lengthTightening torqueApprovalsApprovalsStandards

Dimensions / Signalling contact infoClamping range (nominal / min. / max.) mm²Height x width x depth mmSignalling contactNote

Ordering data

no remote sig. contactwith remote signalling (R)

Note

AccessoriesNote

VPU II 4/R 150 V / 40 kATN-S

L1 L2

PE

U U

OK CHANGE OK CHANGE

L3

U

OK CHANGE

N

U

OK CHANGE

11 1412 PE

120 V / 240 V150 V Type II, Type III 20 kA40 kA40 kA10 kV25 kA160 kA30 µA≤ 25 ns125 A gL≤ 0.9 kV 230 Vgreen = OK; red = arrester is defective - replaceInstallation housing; 4TE, Insta IP 20Black, Arrester red-40 °C...+70 °C-40 °C ... +80 °C

2.5...16 mm²2.5...50 mm²15 mm2...3 Nm

IEC61643-11, EN61643-11

no remote sig. contact with remote signalling (R)16 / 2.5 / 50 16 / 2.5 / 5094 / 71.2 / 69 106 / 71.2 / 69No 250 V 1 A 1 NC

Type Qty. Order No.VPU II 4 150V/40KA 1 1352540000VPU II 4 R 150V/40KA 1 1352550000

Pluggable spare arrester VPU II 0 150 V/40 kA-1352450000

VPU II 3/R 150 V / 40 kATN-C

L1 L2

U U

PE (N)

OK CHANGE OK CHANGE

L3

U

OK CHANGE

11 1412 PE (N)

120 V / 240 V150 V Type II, Type III 20 kA40 kA40 kA10 kV25 kA120 kA30 µA≤ 25 ns125 A gL≤ 0.9 kV 230 Vgreen = OK; red = arrester is defective - replaceInstallation housing; 3TEBlack, Arrester red-40 °C...+70 °C-40 °C ... +80 °C

2.5...16 mm²2.5...50 mm²15 mm2...3 Nm

IEC61643-11, EN61643-11

no remote sig. contact with remote signalling (R)16 / 2.5 / 50 16 / 2.5 / 5094 / 53.4 / 69 106 / 53.4 / 69No 250 V 1 A 1 NC

Type Qty. Order No.VPU II 3 150V/40KA 1 1352520000VPU II 3 R 150V/40KA 1 1352530000

Pluggable spare arrester VPU II 0 150 V/40 kA-1352450000

Type II surge protection

C

C.491366910000 – 2013

Light

ning a

nd su

rge p

rote

ction

for l

ow vo

ltage

facil

ities

Type II/III surge protection Uc: 150 V Suitable for 120/240 V mains systems• Pluggable arrester• Coded voltage level• High energy absorption with short time to sparkover• Arrester can be rotated through 180°• No follow-on current• Installation in distribution board• Thermal protection function• Co-ordination with VPU Type I

Technical data

Rated voltageMax. continuous voltage, Uc (AC)Requirements category acc. to IEC 61643-11Rated discharge current (8/20 µs) INLimiting discharge current (8/20 µs) Imax

Discharge current, max. (8/20 µs)Combined pulse Uoc

Short-circuit resistance ISCCR

Total discharge current Itotal

PE conductor current IPE

Sparkover time / Drop-out timeFusingProtection level UP (typical)Temporary surge voltage (over-voltage) - TOVOptical function displayDesignColourAmbient temperature (operational)Storage temperatureConnection according to IEC 947-7-1SolidStrandedStripping lengthTightening torqueApprovalsApprovalsStandards

Dimensions / Signalling contact infoClamping range (nominal / min. / max.) mm²Height x width x depth mmSignalling contactNote

Ordering data

no remote sig. contactwith remote signalling (R)

Note

AccessoriesNote

VPU II 2/R 150 V / 40 kA1-phase

L1 N

U U

PE

OK CHANGE OK CHANGE

11 1412 PE

120 V150 V Type II, Type III 20 kA40 kA40 kA10 kV25 kA80 kA30 µA≤ 25 ns125 A gL≤ 0.9 kV 230 Vgreen = OK; red = arrester is defective - replaceInstallation housing; 2TE, Insta IP 20Black, Arrester red-40 °C...+70 °C-40 °C ... +80 °C

2.5...16 mm²2.5...50 mm²15 mm2...3 Nm

IEC61643-11, EN61643-11

no remote sig. contact with remote signalling (R)16 / 2.5 / 50 16 / 2.5 / 5094 / 35.6 / 69 106 / 35.6 / 69No 250 V 1 A 1 NC

Type Qty. Order No.VPU II 2 150V/40KA 1 1352490000VPU II 2 R 150V/40KA 1 1352500000

Pluggable spare arrester VPU II 0 150 V/40 kA-1352450000

VPU II 1/R 150 V / 40 kA1-phase

L1

PE (N)

U

OK CHANGE

11 1412

120 V150 V Type II, Type III 20 kA40 kA40 kA10 kV25 kA40 kA30 µA≤ 25 ns125 A gL≤ 0.9 kV 230 Vgreen = OK; red = arrester is defective - replaceInstallation housing; 1TE, Insta IP 20Black, Arrester red-40 °C...+70 °C-40 °C ... +80 °C

2.5...16 mm²2.5...50 mm²15 mm2...3 Nm

IEC61643-11, EN61643-11

no remote sig. contact with remote signalling (R)16 / 2.5 / 50 16 / 2.5 / 5094 / 17.8 / 69 106 / 17.8 / 69No 250 V 1 A 1 NC

Type Qty. Order No.VPU II 1 150V/40KA 1 1352470000VPU II 1 R 150V/40KA 1 1352480000

Pluggable spare arrester VPU II 0 150 V/40 kA-1352450000

Type II surge protection

Page 7: Surge Protection Short Form Catalogue - LC Automation · 2015-06-10 · C C.16 1366910000 – 2013 Lightning and surge protection for low voltage facilities Type I and II lightning

C

C.68 1366910000 – 2013

Light

ning a

nd su

rge p

rote

ction

for l

ow vo

ltage

facil

ities Type III with varistors / gas discharge tube

• Type III surge protection• Suitable for protecting terminals• Installed in the vicinity of the equipment to be protected• For mounting on TS35 rail• Arrester with remote signalling contact• Tested in accordance with IEC 61643-11

Technical data

Rated voltage (AC)Rated voltage (DC)Max. continuous voltage, Uc (AC)Max. continuous voltage, Uc (DC)Requirements category acc. to IEC 61643-11Combined pulse Uoc

Rated discharge current (8/20 µs) INShort-circuit resistance ISCCR

Discharge current, max. (8/20 µs)Rated load current ILPE conductor current IPE

Sparkover time / Drop-out timeFusingProtection level UP (typical)Temporary surge voltage (over-voltage) - TOVOptical function displayDesignAmbient temperature (operational)Storage temperatureConnection according to IEC 947-7-1SolidStrandedStripping lengthTightening torqueApprovalsApprovalsStandards

Dimensions / Signalling contact infoClamping range (nominal / min. / max.) mm²Height x width x depth mmSignalling contactNote

Ordering data

Screw connection

Note

AccessoriesNote

VPU III R 230 V / 6 kVFor use as device protector

IN protectedunprotected

U

N´PE´

L

NPE

U

12

11

FAULTOK

230 V

300 V

Type III 3 kV

1.5 kA3 kA16 A0 µA< 100 ns16 A≤ 1.8 kV440 VGreen LED = OK, LED red = arrester faulty, replaceInstallation housing; 1TE, Insta IP 20-40 °C...+70 °C-40°C ... +80°C

0.5...2.5 mm²0.5...2.5 mm²7 mm0.4...0.5 Nm

IEC61643-11, EN61643-11

Screw connection2.5 / 0.5 / 2.5102 / 18 / 71.5250 V 1 A 1 NC

Type Qty. Order No.VPU IIIR 230V/6KV AC 1 1351650000

VPU III R 120 V / 6 kVFor use as device protector

U

N´PE´

L

NPE

U

12

11

FAULTOK

IN protectedunprotected

120 V150 V 212 V 180 V Type III 3 kV

1.5 kA3 kA16 A0 µA< 100 ns16 A≤ 1.75 kV228 VGreen LED = OK, LED red = arrester faulty, replaceInstallation housing; 1TE, Insta IP 20-40 °C...+70 °C-40°C ... +80°C

0.5...2.5 mm²0.5...2.5 mm²7 mm0.4...0.5 Nm

IEC61643-11, EN61643-11

Screw connection2.5 / 0.5 / 2.5102 / 18 / 71.5250 V 1 A 1 NC

Type Qty. Order No.VPU IIIR 120V/6KV AC/DC 1 1351630000

Type III surge protection for terminal devices

C

C.691366910000 – 2013

Light

ning a

nd su

rge p

rote

ction

for l

ow vo

ltage

facil

itiesType III with varistors / gas discharge tube

• Type III surge protection• Suitable for protecting terminals• Installed in the vicinity of the equipment to be protected• For mounting on TS35 rail• Arrester with remote signalling contact• Tested in accordance with IEC 61643-11

Technical data

Rated voltage (AC)Rated voltage (DC)Max. continuous voltage, Uc (AC)Max. continuous voltage, Uc (DC)Requirements category acc. to IEC 61643-11Combined pulse Uoc

Rated discharge current (8/20 µs) INShort-circuit resistance ISCCR

Discharge current, max. (8/20 µs)Rated load current ILPE conductor current IPE

Sparkover time / Drop-out timeFusingProtection level UP (typical)Temporary surge voltage (over-voltage) - TOVOptical function displayDesignAmbient temperature (operational)Storage temperatureConnection according to IEC 947-7-1SolidStrandedStripping lengthTightening torqueApprovalsApprovalsStandards

Dimensions / Signalling contact infoClamping range (nominal / min. / max.) mm²Height x width x depth mmSignalling contactNote

Ordering data

Screw connection

Note

AccessoriesNote

VPU III R 48 V / 4 kVFor use as device protector

U

N´PE´

L

NPE

U

12

11

FAULTOK

IN protectedunprotected

48 V70 V 50 V 72 V Type III 2 kV

1.5 kA2 kA16 A0 µA< 100 ns16 A≤ 950 V91 VGreen LED = OK, LED red = arrester faulty, replaceInstallation housing; 1TE, Insta IP 20-40 °C...+70 °C-40°C ... +80°C

0.5...2.5 mm²0.5...2.5 mm²7 mm0.4...0.5 Nm

IEC61643-11, EN61643-11

Screw connection2.5 / 0.5 / 2.5102 / 18 / 71.5250 V 1 A 1 NC

Type Qty. Order No.VPU III R 48V/4KV AC/DC 1 1351600000

VPU III R 24 V / 4 kVFor use as device protector

U

N´PE´

L

NPE

U

12

11

FAULTOK

IN protectedunprotected

24 V32 V 32 V 53 V Type III 2 kV

1.5 kA2 kA16 A0 µA< 100 ns16 A≤ 890 V45 VGreen LED = OK, LED red = arrester faulty, replaceInstallation housing; 1TE, Insta IP 20-40 °C...+70 °C-40°C ... +80°C

0.5...2.5 mm²0.5...2.5 mm²7 mm0.4...0.5 Nm

IEC61643-11, EN61643-11

Screw connection2.5 / 0.5 / 2.5102 / 18 / 71.5250 V 1 A 1 NC

Type Qty. Order No.VPU III R 24V/4KV AC/DC 1 1351580000

Type III surge protection for terminal devices

Page 8: Surge Protection Short Form Catalogue - LC Automation · 2015-06-10 · C C.16 1366910000 – 2013 Lightning and surge protection for low voltage facilities Type I and II lightning

Weidmüller - Partner in Industrial Connectivity

As experienced experts we support our customers and partners around the world with products, solutions and services in the industrial environment of power, signal and data. We are at home in their industries and markets and know the technological challenges of tomorrow. We are therefore continuously developing innovative, sustainable and useful solutions for their individual needs. Together we set standards in Industrial Connectivity.

Let’s Connect!

www.weidmuller.co.uk

Weidmuller Ltd.

Klippon HouseCenturionCourtOfficeParkMeridian EastMeridianBusinessParkLeicester,LE191TP

Sales: 08450942006Technical: 08450942007

[email protected]

Scan this with your smartphone to visit our website.

Let's Connect.

ArgentinaAustraliaAustriaAzerbaijanBahrainBelarusBelgiumBosnia andHerzegovinaBrazilBulgariaCanadaChileChinaColombiaCosta RicaCroatiaCzech RepublicDenmarkEcuadorEgyptEstoniaFinlandFranceGermanyGreat BritainGreeceHong Kong

HungaryIcelandIndiaIndonesiaIranIrelandIsraelItalyJapanJordanKazakhstanKoreaKuwaitLatviaLebanonLithuaniaLuxembourgMacedoniaMalaysiaMaltaMexicoMoldovaNetherlandsNew ZealandNorwayOmanPakistanPeru

PhilippinesPolandPortugalQatarRomaniaRussiaSaudi ArabiaSerbiaSingaporeSlovakiaSloveniaSouth AfricaSpainSwedenSwitzerlandTaiwanThailandTunisiaTurkeyUkraineUnited ArabEmiratesUnited StatesUruguayUzbekistanVenezuelaVietnam

UKBR0014V1012013